The Rosemount Wireless Pressure Gauge from Emerson™ utilizes industry-proven Rosemount pressure sensor
technology to deliver accurate, reliable pressure information. It features up to 150x overpressure protection
and two layers of process isolation providing a safer field environment. Rosemount sensor technology
eliminates many gauge challenges by replacing mechanical parts that inhibit traditional gauges from
reporting or displaying the correct pressure. The Rosemount Wireless Pressure Gauge features a large 4.5-in.
(114 mm) face for easy field visibility. It has up to a 10-year installed life, reducing costs and time involved with
maintenance.
Rosemount Wireless Pressure Gauge
Product Benefits
Reduce maintenance challenges
Get up to 10 years of reliable readings through industry-proven Rosemount pressure sensor technology
Reduce common mechanical gauge failures caused by vibration, overpressure and other environmental factors
Have confidence in pressure gauge health with local indicator light
Improve personnel safety
Keep people out of hazardous areas by minimizing operator rounds
Gain peace of mind with overpressure ratings from 1.5x to 150x and two layers of process isolation
Access pressure data continuously
Get accurate readings as frequently as once per minute with WirelessHART technology
View pressure reading locally with large 4.5-in. (114 mm) dial
Table 1. Rosemount Wireless Pressure Gauge Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
ModelDevice type
WPGWireless Pressure Gauge
Dial size
454.5-in. (114.3 mm)
Gauge output
XWireless with user-configurable update rate, 2.4 GHz DSSS, WirelessHART
Product certifications
I1ATEX Intrinsic Safety
I2INMETRO Intrinsic Safety
I4TIIS Intrinsic Safety
I5US Intrinsically Safe
I6Canada Intrinsically Safe
I7IECEx Intrinsic Safety
IMTechnical Regulations Customs Union (EAC) Intrinsic Safety
NANo approval
Measurement type
GGage
★
★
★
★
★
★
★
★
★
★
★
★
AAbsolute
CCompound
VVa cuum
Process connection style
(1)
Connection styleIsolating diaphragm material
11
12
1
/2-14 NPT male316L SST
1
/2-14 NPT maleAlloy C-276
21G1/2 male (EN 837)316L SST
22G1/2 male (EN 837)Alloy C-276
01Alternate process connection316 SST
02 Alternate process connectionAlloy C-276
Primary engineering unit
Apsi
BkiloPascals (kPa)
Emerson.com/Rosemount
★
★
★
★
★
★
★
★
★
★
★
★
3
Rosemount Wireless Pressure Gauge
January 2018
Table 1. Rosemount Wireless Pressure Gauge Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Dbar
EmBar
FMegaPascals (MPa)
GinH2O
Hkg/cm
2
IftH2O
JmmH2O
KinHg
LcmH2O
McmHg
NmmHg
(2)(3)
P
Percent of range (% of range)
Scale ranges
Reference tables in Pressure scale ranges section for scale ranges by engineering unit.
Options (include with selected model number)
★
★
★
★
★
★
★
★
★
★
★
Secondary engineering unit (dual scale)
(4)
DA
(4)
DB
(4)
DD
(4)
DH
(2)(3)(5)(6)
DC
Manifolds assemblies
psi
kiloPascals (kPa)
bar
2
kg/cm
Custom units
(7)(8)(9)
S5Assemble to Rosemount 306 Integral Manifold
Diaphragm seal assembly
(8)(9)(10)
S1Assemble to one Rosemount 1199 Diaphragm Seal
Extended product warranty
WR33-year limited warranty
WR55-year limited warranty
Mounting bracket
B4Bracket for 2-in. pipe or panel mounting, all SST
★
★
★
★
★
★
★
4
Emerson.com/Rosemount
January 2018
Rosemount Wireless Pressure Gauge
Table 1. Rosemount Wireless Pressure Gauge Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Custom configuration
C1Custom configuration
Calibration certification
Q4Calibration certificate
Material traceability certification
Q8Material traceability certification per EN 10204 3.1
NACE certificate
Q15Certificate of compliance to NACE® MR0175/ISO 15156 for wetted materials
Q25Certificate of compliance to NACE MR0103 for wetted materials
Pressure testing
P1Hydrostatic testing with certificate
Surface finish
(11)
Q16Surface finish certificate for Sanitary Remote Seals
Normal range indication
LKGreen, yellow and red sticker kit
Alternate process connection
(12)
★
★
★
★
★
★
★
★
P01Level flange (SST), 1-in. ANSI Class 150
P02Level flange (SST), 1-in. ANSI Class 300
P11Level flange (SST), 2-in. ANSI Class 150
P12Level flange (SST), 2-in. ANSI Class 300
P21Level flange (SST), 3-in. ANS I Class 150
P22Level flange (SST), 3-in. ANSI Class 300
P31 Level flange (SST), DIN-DN 50 PN 40
P41Level flange (SST), DIN-DN 80 PN 40
W01Level flange (SST), 1-in. ANSI Class 150, All welded construction
W02Level flange (SST), 1-in. ANSI Class 300, All welded construction
W11Level flange (SST), 2-in. ANSI Class 150, All welded construction
W12Level flange (SST), 2-in. ANSI Class 300, All welded construction
W21Level flange (SST), 3-in. ANSI Class 150, All welded construction
W22Level flange (SST), 3-in. ANSI Class 300, All welded construction
W31Level flange (SST), DIN-DN 50 PN 40, All welded construction
W41Level flange (SST), DIN-DN 80 PN 40, All welded construction
Emerson.com/Rosemount
5
Rosemount Wireless Pressure Gauge
1.Materials of Construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to
certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
2.Not available with Measurement Type Compound.
3.Not available with Measurement Type Vacuum.
4.Not available with Primary Engineering Unit “P” (Percent of Range).
5.Requires Primary Engineering Unit of “A” (psi) or “D” (bar).
6.Requires Custom Configuration model code “C1”.
7.Requires Process Connection Style “11” or “12”.
8.Integrated manifold and diaphragm seal assemblies cannot be combined.
9.“Assemble-to” items are specified separately and require a completed model number.
10.Requires Process Connection 11.
11.Requires diaphragm seal assembly “S1”
12.Requires process connection style “01” or “02”
January 2018
Figure 1. Model Number Ordering Example
Model
Dial
size
WPG45XI1A11A6-digit numeric valueDA, S1...
Factory definedEnd-user defined
Gauge
output
Product
certification
Measurement
type
Process
connection style
Primary
engineering unit
Scale rangeOptions
6
Emerson.com/Rosemount
January 2018
Pressure scale ranges
Additional scale ranges available. Contact Emerson for additional information.
Rosemount Wireless Pressure Gauge
Psi
Code
000000-15/0
Gage/absolute
0 to psi
00000555
0000101010
0000151515
0000202020
0000303030
0000505050
0000606060
0000757575
000100100100
000150150150
000160160160
000200200200
000300300300
000400400N/A
000500500N/A
000600600N/A
000800800N/A
0010001000N/A
0015001500N/A
0020002000N/A
0030003000N/A
0040004000N/A
Vacuum
-psi to 0
Compound
-30 inHg to 0 to psi
(1)
Bar-kg/cm2
2
Vacuum
Compound
-1 bar to 0 to bar or
-1 kg/cm2 to 0 to
kg/cm
Code
000000-1/0
Gage/absolute
000000D400.40.4
000000D600.60.6
00000111
000001D501.51.5
000001D601.61.6
00000222
000002D502.52.5
00000333
00000444
00000555
00000666
00000999
0000101010
0000151515
0000161616
0000202020
00002424N/A
00002525N/A
00004040N/A
00005050N/A
00006060N/A
-bar to 0 or -kg/cm2 to 0
0 to bar or
0 to kg/cm
2
1.Vacuum scale will be in inHg and positive pressure in psi. Only applies to psi.
Emerson.com/Rosemount
00007070N/A
000100100N/A
000160160N/A
000250250N/A
7
Rosemount Wireless Pressure Gauge
January 2018
kiloPascals (kPa)
Code
000000-100/0
Gage/absolute
0 to kPa
0000404040
0000606060
000100
000150150150
000160160160
000200200200
000250250250
000300300300
000400400400
000500500500
000600600600
000900900900
00100010001000
00150015001500
00160016001600
00200020002000
0024002400N/A
0025002500N/A
0040004000N/A
0050005000N/A
0060006000N/A
01000010000N/A
02500025000N/A
100
Vacuum
-kPa to 0
Compound
-100 kPa to 0 to kPa
100
mbar
Code
000000-1000/0
Gage/absolute
0 to mbar
000400400400
000600600600
00100010001000
00150015001500
00200020002000
00300030003000
00400040004000
00500050005000
00600060006000
00900090009000
Vacu um
-mbar to 0
Compound
-1000 mbar to 0 to mbar
MegaPascals (MPa)
Code
000000-0.1/0
Gage/absolute
0 to MPa
000000D200.20.2
000000D500.50.5
00000111
000001D501.51.5
00000222
000002D502.5N/A
Vacu um
-MPa to 0
Compound
-0.1 MPa to 0 to MPa
inH2O
Code
000000-400/0
Vacu um
-inH
2
O to 0
Gage/absolute
0 to inH
000200200200
000300300300
000800800800
8
O
2
Emerson.com/Rosemount
-400 inH
Compound
O to 0 to inH2O
2
January 2018
Rosemount Wireless Pressure Gauge
ftH2O
Code
000000-30/0
Gage/absolute
0 to ftH2O
0000353535
0000606060
0000707070
000100100100
000140140140
000240240240
000400400400
000500500500
000700700700
000900900N/A
Vacuum
-ftH2O to 0
Compound
-30 ftH2O to 0 to ftH2O
mmH2O
Code
000000-10000/0
Gage/absolute
0 to mmH2O
00750075007500
0400004000040000
200000200000200000
Vacuum
-mmH
O to 0
2
Compound
-10000 mmH2O to 0 to
mmH
2
inHg
Code
000000-30/0
Gage/absolute
0 to inHg
Vacuum
-inHg to 0
Compound
-30 inHg to 0 to inHg
cmH2O
Code
000000-1000/0
Gage/absolute
0 to cmH
000500500500
000900900900
-cmH2O to 0
O
2
Vacu um
Compound
-1000 cmH2O to 0 to
cmH2O
cmHg
Code
000000-75/0
Gage/absolute
0 to cmHg
000150150150
000750750750
0040004000N/A
02000020000N/A
Vacu um
-cmHg to 0
Compound
-75 cmHg to 0 to cmHg
mmHg
Code
O
000000-750/0
Gage/absolute
0 to mmHg
00150015001500
00750075007500
04000040000N/A
200000200000N/A
Percent of range
CodeGage/absolute
00003030
(1)
Vacu um
-mmHg to 0
Compound
-750 mmHg to 0 to mmHg
0000121212
0000151515
0000161616
0000202020
0000303030
0000606060
000300300300
Emerson.com/Rosemount
000150150
000800800
0040004000
1.Scale will read 0-100 percent. Code selected is representative of the desired
working pressure range in psi.
9
Rosemount Wireless Pressure Gauge
Specifications
January 2018
Physical specifications
Material selection
Emerson provides a variety of Rosemount products with various
product options and configurations including materials of
construction that can be expected to perform well in a wide
range of applications. The Rosemount product information
presented is intended as a guide for the purchaser to make an
appropriate selection for the application. It is the purchaser’s
sole responsibility to make a careful analysis of all process
parameters (such as all chemical components, temperature,
pressure, flow rate, abrasives, contaminants, etc.), when
specifying product materials, options, and components for the
particular application. Emerson is not in a position to evaluate or
guarantee the compatibility of the process fluid or other process
parameters with the product options, configuration, or
materials of construction selected.
Dial size
4.5-in. (114.3 millimeter)
Scale ranges
From vacuum up to 4,000 psi (275 bar)
Single scale considerations
The number of major graduations is a direct result of the
specified combination of primary engineering unit and scale
range.
Dual scale considerations
The number of major graduations on the inner scale is the direct
result of the combination of primary engineering unit and
secondary engineering unit.
Process connections
1
/2-14 NPT male, G1/2 male (EN 837) and alternate process
connections
Field Communicator connections
Communication terminals are accessible by removing cover.
Material of construction
Housing
Engineered Polymer, NEMA
®
4X and IP66/67
Shipping weight
1.8 lb (0.82 kg)
Options
Mounting bracket (Code B4)
1.0 lb (0.5 kg)
Normal Range Indication (Code LK)
0.02 lb (11 g)
Rosemount 1199 Seal Systems
Reference the Rosemount DP Level Product Data Sheet
shipping weights.
Rosemount 306 Integrated Manifolds
Reference the Rosemount Manifolds Product Data Sheet for
shipping weights.
for
Operating specifications
Conformance to specification (±3σ [Sigma])
Technology leadership, advanced manufacturing techniques,
and statistical process control ensure specification conformance
to at least ±3σ.
2.220 °F (1 04 °C) limit in vacuum service; 130 °F (54 °C) for pressures below
0.5 psia.
Emerson.com/Rosemount
January 2018
Rosemount Wireless Pressure Gauge
Electrical connections/battery
Replaceable, non-rechargeable, 3.6 V primary cell,
lithium-thionyl chloride battery
10 year battery life at reference conditions
(1)
Overpressure limit
Scale range
5 – 30 psi
(0.35 – 2 bar)
31 – 150 psi
(2.1 – 10.3 bar)
151 – 800 psi
(10.4 – 55.1 bar)
801 – 4,000 psi
(55.2 – 275 bar)
Maximum
working pressure
30 psi (2 bar)750 psi (51.7 bar)
150 psi (10.3 bar)1,500 psi (103.4 bar)
800 psi (55.1 bar)1,600 psi (110.3 bar)
4,000 psi (275 bar)6,000 psi (413.7 bar)
Maximum
overpressure limit
Burst pressure limit
11,000 psi (758 bar)
Minimum span limits for percent of range
engineering unit
The maximum rangedown is 10:1. The device maintains
reference accuracy specification up to 6:1 rangedown. After 6:1
rangedown the reference accuracy decreases to 1% of span.
Scale rangeSpan (6:1 ratio)
5 – 30 psi
(0.35 – 2 bar)
31 – 150 psi
(2.1 – 10.3 bar)
151 – 800 psi
(10.4 – 55.1 bar)
801 – 4,000 psi
(55.2 – 275 bar)
5 psi (0.34 bar)3 psi (0.21 bar)
25 psi (1.72 bar)15 psi (1.03 bar)
134 psi (9.24 bar)80 psi (5.51 bar)
667 psi (45.99 bar)
Minimum span
(10:1 ratio)
400 psi
(27.5 bar)
Digital zero trim
An offset adjustment to compensate for mounting position
effects, up to 5 percent of Span
Humidity limits
0-95% relative humidity
Electromagnetic compatibility (EMC)
Meets all industrial environment requirements of EN61326.
Maximum deviation < 1 percent span during EMC disturbance.
Status indication
Device status is indicated by local LED. Reference the Rosemount
Wireless Pressure Gauge Quick Start Guide for further detail.
Wireless update rate is user-selectable from one minute to
60 minutes and is separate from local display. When wireless is
activated, the update rate defaults to once a minute.
Vibration effect
No significant effect when tested per IEC60770-1 or ASME B40.1
requirements
IEC60770-1 high vibration level - field or pipeline: 10–60 Hz
0.21 mm displacement peak amplitude/60–2000 Hz 3 g
Ambient temperature effect per 18 °F (10 °C)
Scale rangeAmbient temperature effect
Wireless pressure gauge
Up to 4,000 psi (275 bar)±0.3 of span
Wireless pressure gauge with remote seal
Up to 4,000 psi (275 bar)
1.Reference conditions are 70 °F (21 °C), Stable operating pressure with periodic changes, transmit rate of once per minute, and routing data for three
additional network devices.
A copy of the EU Declaration of Conformity can be found at the
end of the Quick Start Guide. The most recent revision of the EU
Declaration of Conformity can be found at
Emerson.com/Rosemount
.
Telecommunication compliance
All wireless devices require certification to ensure that they
adhere to regulations regarding the use of the RF spectrum.
Nearly every country requires this type of product certification.
Emerson is working with governmental agencies around the
world to supply fully compliant products and remove the risk of
violating country directives or laws governing wireless device
usage.
FCC and IC (WPG Only)
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following conditions: This devices may not cause
harmful interference, this devices must accept any interference
received, including interference that may cause undesired
operation. This device must be installed to ensure a minimum
antenna separation distance of 20 cm from all persons. This
device complies with Industry Canada license-exempt RSS-247.
Operation is subject to the following two conditions: (1) this
device may not cause interference, and (2) this device must
accept any interference, including interference that may cause
undesired operation of the device.
Ordinary location certification from
CSA
The product has been examined and tested to determine that
the design meets the basic electrical, mechanical, and fire
protection requirements by CSA, a nationally recognized test
laboratory (NRTL) as accredited by the Federal Occupational
Safety and Health Administration (OSHA).
Installing in North America
The US National Electrical Code (NEC) and the Canadian
Electrical Code (CEC) permit the use of Division marked
equipment in Zones and Zone marked equipment in Divisions.
The markings must be suitable for the area classification, gas,
and temperature class. This information is clearly defined in the
respective codes.
USA
I5U.S.A. Intrinsically Safe (IS)
Certificate: [CSA] 70047656
Standards: FM 3600 – 2011, FM 3610 – 2010, UL Standard
Markings: IS CL I, DIV 1, GP A, B, C, D T4; Class 1, Zone 0,
≤ T
AEx ia IIC T4 Ga; T4 (-40 °C
when installed per Rosemount drawing
00G45-1020; Type 4X; IP66/67
≤ +70 °C)
a
Changes or modification to the equipment not expressly
approved by Emerson could void the user's authority to operate
the equipment.
Cet appareil est conforme à la Partie 15 de la réglementation
FCC. Son fonctionnement est soumis aux conditions suivantes:
Cet appareil ne doit pas causer d'interférences nuisibles. Cet
appareil doit accepter toute interférence reçue, incluant toute
interférence pouvant causer un fonctionnement indésirable. Cet
appareil doit être installé pour assurer une distance minimum de
l'antenne de séparation de 20 cm de toute personne. Cet
appareil est conforme à la norme RSS-247 Industrie Canada
exempt de licence. Son fonctionnement est soumis aux deux
conditions suivantes: (1) cet appareil ne doit pas provoquer
d'interférences et (2) cet appareil doit accepter toute
interférence, y compris les interférences pouvant causer un
mauvais fonctionnement du dispositif. Les changements ou les
modifications apportés à l'équipement qui n'est pas
expressément approuvé par Rousemount Incpourraient annuler
l'autorité de l'utilisateur à utiliser cet équipement.
Emerson.com/Rosemount
Special Conditions for Safe Use (X):
1. Do not replace battery when explosive atmosphere is
present.
2. Use only 00G45-9000-0001 batteries.
3. The surface resistivity of the housing is greater than 1G .
To avoid electrostatic charge build-up, it must not be
rubbed or cleaned with solvents or a dry cloth.
4. Substitution of components may impair intrinsic safety.
Markings: Intrinsically Safe for Class I, Division 1, Groups A,
≤ T
B, C, D T4; Ex ia IIC T4 Ga T4 (-40 °C
°C) when installed per Rosemount drawing
00G45-1020; Type 4X; IP66/67
≤ +70
a
13
Rosemount Wireless Pressure Gauge
Ω
January 2018
Special Conditions for Safe Use (X):
1. Do not replace battery when explosive atmosphere is
present.
Ne pas remplacer les accumulateurs si une atmosphère
explosive peut être présente.
2. Use only 00G45-9000-0001 batteries.
Utiliser uniquement des accumulateurs
00G45-9000-0001.
3. The surface resistivity of the housing is greater than 1G .
To avoid electrostatic charge build-up, it must not be
rubbed or cleaned with solvents or a dry cloth.
La résistivité de surface du boÎtier est supérieure à un
gigaohm. Pour éviter l’accumulation de charge
électrostatique, ne pas frotter ou nettoyer avec des
produits solvants ou un chiffon sec.
4. Substitution of components may impair intrinsic safety.
La substitution de composants peut compromettre la
sécurité intrinsèque.
Europe
I1ATEX Intrinsic Safety
Certificate: Baseefa16ATEX0005X
Standards: EN 60079-0: 2012 + A11: 2013, EN 60079-11:
1. The plastic may constitute a potential electrostatic ignition
risk and must not be rubbed or cleaned with a dry cloth.
2. The measured capacitance between the equipment
enclosure and metallic inline sensor module is 4.7pF. This
must be considered only when the WPG is integrated into
a system where the process connection is not grounded.
3. Do not change the battery when an explosive atmosphere
is present.
4. Only replace battery with Rosemount Part No.
00G45-9000-0001.
≤ +70 °C)
a
Brazil
I2INMETRO Intrinsic Safety (Only available with the WPG)
1. The plastic enclosure may constitute a potential
electrostatic ignition risk and must not be rubbed or
cleaned with a dry cloth.
2. The measured capacitance between the equipment
enclosure and metallic inline sensor module is 4.7pF. This
must be considered only when the WPG is integrated into
a system where the process connection is not grounded.
3. Do not change the battery when an explosive atmosphere
is present.
4. Only replace battery with Rosemount Part No.
00G45-9000-0001.
Special Conditions for Safe Use (X):
1. See certificate for special conditions.
Japan
I4TIIS Intrinsic Safety (Only available with the WPG)
Certificate: TC22068X
Markings: Ex ia IIC T4 Ga, T4 (-40 °C ≤ Ta ≤ +70 °C)
Special Conditions for Safe Use (X):
1. See certificate for special conditions.
EAC - Belarus, Kazakhstan, Russia
IM Technical Regulation Customs Union (EAC) Intrinsic Safety
(Only available with the WPG)
Certificate: TC RU C-US.AA87.B.00372
Markings: 0Ex ia IIC T4 Ga X, T4 (-40 °C ≤ Ta ≤ +70 °C)
IP66/67
Emerson Terms and Conditions of Sale are available upon request.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
Instrument Toolkit, Rosemount and Rosemount logotype are trademarks of
Emerson.
All other marks are the property of their respective owners.