2Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
September 2021Quick Start Guide
1About this guide
This guide provides basic installation and configuration instructions for the
Rosemount 8800D Vortex Flow Meter with Modbus protocol.
For more information on installation and configuration instructions,
diagnostics, maintenance, service, and troubleshooting, please refer to the
reference manual 00809-0400-4004.
For hazardous location installation, including Explosion-proof, Flameproof,
or Intrinsic Safety (I.S.), please consult 00825-VA00-0001 Approval
Document.
1.1Hazard messages
This document uses the following criteria for hazard messages based on
ANSI standards Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not
avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can
occur if a situation is not avoided. There is no credible risk of physical injury.
Quick Start Guide 3
Quick Start Guide September 2021
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or
misconfiguration of end users' equipment. Protect against all intentional or
unintentional unauthorized use.
Physical security is an important part of any security program and
fundamental to protecting your system. Restrict physical access to protect
users' assets. This is true for all systems used within the facility.
1.2Safety messages
WARNING
Explosion hazards. Failure to follow these instructions could cause an
explosion, resulting in death or serious injury.
• Verify the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
• Installation of this transmitter in an explosive environment must be in
accordance with the appropriate local, national, and international
standards, codes, and practices. Review the approvals documents for
any restrictions associated with a safe installation.
• Do not remove transmitter covers or thermocouple (if equipped) in
explosive atmospheres when the circuit is live. Both transmitter covers
must be fully engaged to meet explosion-proof requirements.
• Before connecting a hand-held communicator in an explosive
atmosphere, make sure the instruments in the loop are installed in
accordance with intrinsically safe or non-incendive field wiring practices.
WARNING
Electrical shock hazard. Failure to follow this instruction could result in death
or serious injury. Avoid contact with the leads and terminals. High voltage
that may be present on leads can cause electrical shock.
4Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
September 2021Quick Start Guide
WARNING
General hazard. Failure to follow these instructions could result in death or
serious injury.
• This product is intended to be used as a flowmeter for liquid, gas, or
steam applications. Do not use for any other purpose.
• Make sure only qualified personnel perform the installation.
Quick Start Guide 5
Quick Start Guide September 2021
2Return policy
Emerson procedures must be followed when returning equipment. These
procedures ensure legal compliance with government transportation
agencies and help provide a safe working environment for Emerson
employees. Failure to follow Emerson procedures will result in your
equipment being refused delivery.
6Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
September 2021Quick Start Guide
3Emerson Flow customer service
Email:
• Worldwide: flow.support@emerson.com
• Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South AmericaEurope and Middle EastAsia Pacific
United States 800 522 6277 U.K.0870 240
Canada+1 303 527
5200
Mexico+41 (0) 41
7686 111
Argentina+54 11 4837
7000
Brazil+55 15 3413
8000
Venezuela+58 26 1731
3446
The
Netherlands
France0800 917 901 India800 440 1468
Germany0800 182
Italy8008 77334China+86 21 2892
Central &
Eastern
Europe
Russia/CIS+7 495 995
Egypt0800 000
Oman800 70101Thailand001 800 441
Qatar431 0044Malaysia800 814 008
Kuwait663 299 01
South Africa800 991 390
Saudi Arabia800 844 9564
UAE800 0444
1978
+31 (0) 704
136 666
5347
+41 (0) 41
7686 111
9559
0015
0684
Australia800 158 727
New Zealand099 128 804
Pakistan888 550 2682
9000
Japan+81 3 5769
6803
South Korea+82 2 3438
4600
Singapore+65 6 777
8211
6426
Quick Start Guide 7
Quick Start Guide September 2021
4Pre-installation
4.1Planning
4.1.1Sizing
To determine the correct meter size for optimal flow meter performance:
• Determine the limits of measuring flow.
• Determine the process conditions so that they are within the stated
requirements for Reynolds number and velocity.
Sizing calculations are required to select the proper flow meter size. These
calculations provide pressure loss, accuracy, and minimum and maximum
flow rate data to guide in proper selection. Vortex sizing software can be
found using the Selection and Sizing tool. The Selection and Sizing tool can
be accessed online or downloaded for offline use using this link:
www.Emerson.com/FlowSizing.
4.1.2Wetted material selection
Ensure that the process fluid is compatible with the meter body wetted
materials when specifying the Rosemount 8800D. Corrosion will shorten the
life of the meter body. Consult recognized sources of corrosion data or
contact Emerson Flow Sales Representative for more information.
Note
If Positive Material Identification (PMI) is required, perform test on a
machined surface.
4.1.3Orientation
The best orientation for the meter depends on the process fluid,
environmental factors, and any other nearby equipment.
Vertical installation
Vertical, upward, installation allows upward process liquid flow and is
generally preferred. Upward flow ensures that the meter body always
remains full and that any solids in the fluid are evenly distributed.
The meter can be mounted in the vertical down position when measuring
gas or steam flows. This type of application is strongly discouraged for liquid
flows, although it can be done with proper piping design.
8Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
September 2021Quick Start Guide
Figure 4-1: Vertical installation
AB
A. Liquid or gas flow
B. Gas flow
Note
To ensure the meter body remains full, avoid downward vertical liquid flows
where back pressure is inadequate.
Horizontal installation
For horizontal installation, the preferred orientation is to have the
electronics installed to the side of the pipe. In liquid applications, this helps
prevent any entrained air or solids from striking the shedder bar and
disrupting the shedding frequency. In gas or steam applications, this helps
prevent any entrained liquid (such as condensate) or solids from striking the
shedder bar and disrupting the shedding frequency.
Figure 4-2: Horizontal installation
B
A
A. Preferred installation—meter body installed with electronics to side of
pipe
B. Acceptable installation—meter body installed with electronics above pipe
Quick Start Guide 9
Quick Start Guide September 2021
High-temperature installations
The maximum process temperature for integral electronics is dependent on
the ambient temperature where the meter is installed. The electronics must
not exceed 185 °F (85 °C).
Figure 4-3 shows combinations of ambient and process temperatures
needed to maintain a housing temperature of less than 185 °F (85 °C).
Figure 4-3: Ambient/Process temperature limits
200 (93)
180(82)
160 (71)
600 (316)
700 (371)
C
800 (427)
900 (482)
1000 (538)
A
140 (60)
120 (49)
100 (38)
80 (27)
60 (16)
0
100 (38)
200 (93)
300 (149)
400 (204)
500 (260)
B
A. Ambient temperature °F (°C)
B. Process temperature °F (°C)
C. 185 °F (85 °C) Housing temperature limit.
Note
The indicated limits are for horizontal pipe and vertical meter position, with
meter and pipe insulated with 3 in. (77 mm) of ceramic fiber insulation.
Install the meter body so the electronics are positioned to the side of the
pipe or below the pipe as shown in Figure 4-4. Insulation may also be
required around the pipe to maintain an electronics temperature below
185 °F (85 °C). See Figure 5-2 for special insulation considerations.
10Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
September 2021Quick Start Guide
Figure 4-4: Examples of high-temperature installations
B
A
A. Preferred installation—The meter body installed with the electronics to
the side of the pipe.
B. Acceptable installation—The meter body installed with the electronics
below the pipe.
4.1.4Location
Hazardous area
The transmitter has an explosion-proof housing and circuitry suitable for
intrinsically safe and non-incendive operation. Individual transmitters are
clearly marked with a tag indicating the certifications they carry. For
hazardous location installation, including Explosion-proof, Flameproof,or
Intrinsic Safety (I.S.), please consult the Emerson 8800 Approval Document
00825-VA00-0001.
Environmental considerations
Avoid excessive heat and vibration to ensure maximum flow meter life.
Typical problem areas include high-vibration lines with integrally mounted
electronics, warm-climate installations in direct sunlight, and outdoor
installations in cold climates.
Although the signal conditioning functions reduce susceptibility to
extraneous noise, some environments are more suitable than others. Avoid
placing the flow meter or its wiring close to devices that produce high
intensity electromagnetic and electrostatic fields. Such devices include
electric welding equipment, large electric motors and transformers, and
communication transmitters.
Upstream and downstream piping
The meter may be installed with a minimum of ten diameters (D) of straight
pipe length upstream and five diameters (D) of straight pipe length
downstream.
Quick Start Guide 11
Quick Start Guide September 2021
To achieve reference accuracy, straight pipe lengths of 35D upstream and
5D downstream are required. The value of the K-factor may shift up to 0.5%
when the upstream straight pipe length is between 10D and 35D. For
optional K-factor corrections, see Rosemount™ 8800 Vortex Installation Effects
Technical Data Sheet.
Steam piping
For steam applications, avoid installations such as the one shown in the
following figure. Such installations may cause a water-hammer condition at
start-up due to trapped condensation. The high force from the water
hammer can stress the sensing mechanism and cause permanent damage to
the sensor.
Figure 4-5: Wrong steam pipe installation
Pressure and temperature transmitter location
When using pressure and temperature transmitters in conjunction with the
vortex flow meter for compensated mass flows, install the transmitter(s)
downstream of the vortex flow meter.
12Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
September 2021Quick Start Guide
Figure 4-6: Pressure and temperature transmitter location
C
A
B
D
A. Pressure transmitter
B. Four straight pipe diameters downstream
C. Temperature transmitter
D. Six straight pipe diameters downstream
4.1.5Power supply
The transmitter requires 10 to 30 VDC. The maximum power consumption is
0.4 W.
4.2Commissioning
For proper configuration and operation, commission the meter before
putting it into operation. Bench commissioning also enables you to check
hardware settings, test the flowmeter electronics, verify flowmeter
configuration data, and check output variables. Any problems can be
corrected—or configuration settings changed—before going out into the
installation environment. To commission on the bench, connect a
configuration device to the signal loop in accordance the device
instructions.
4.2.1Alarm and security jumper configuration
Two jumpers on the transmitter specify the alarm and security modes. Set
these jumpers during the commissioning stage to avoid exposing the
electronics to the plant environment. The two jumpers can be found on the
electronics board stack or on the LCD display.
Alarm
Security
Quick Start Guide 13
The jumper setting for Alarm has no effect when the HART
address is set to 1, which is the required setting for the
transmitter when configured for use on a Modbus network.
You can protect the configuration data with the security lockout
jumper. With the security lockout jumper ON, any configuration
Quick Start Guide September 2021
changes attempted on the electronics are disallowed. You can
still access and review any of the operating parameters and scroll
through the available parameters, but no changes can be made.
The factory sets the jumper according to the Configuration Data
Sheet, if applicable, or OFF by default.
Note
If you will be changing configuration variables frequently, it may
be useful to leave the security lockout jumper in the OFF position
to avoid exposing the flow meter electronics to the plant
environment.
To access the jumpers, remove the transmitter electronics housing or the
LCD cover (if equipped) opposite of the terminal block, See Figure 4-7 and
Figure 4-8.
Figure 4-7: Alarm and security jumpers (no LCD option)
VORTEX
4-20mA
HART
14Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
TP1
TEST FREQ
IN
September 2021Quick Start Guide
Figure 4-8: Alarm and security jumpers (with LCD option)
HILO
HILO
ALARM
ALARM
FLOW
SECURITY
SECURITY
ONOFF
ONOFF
4.2.2Calibration
The flow meter is wet-calibrated at the factory and needs no further
calibration during installation. The calibration factor (K-factor) is indicated
on each meter body and is entered into the electronics. Verification can be
accomplished with a configuration device.
Quick Start Guide 15
Quick Start Guide September 2021
5Basic installation
5.1Handling
Handle all parts carefully to prevent damage. Whenever possible, transport
the system to the installation site in the original shipping containers. Keep
the shipping plugs in the conduit connections until you are ready to connect
and seal them.
NOTICE
To avoid damage to the meter, do not lift the flow meter by the transmitter.
Lift the meter by the meter body. Lifting supports can be tied around the
meter body as shown.
Figure 5-1: Lifting supports
5.2Flow direction
The meter can only measure flow in the direction indicated on the meter
body. Be sure to mount the meter body so the FORWARD end of the flow
arrow points in the direction of the flow in the pipe.
5.3
16Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
Gaskets
The flow meter requires gaskets supplied by the user. Be sure to select
gasket material that is compatible with the process fluid and pressure
ratings of the specific installation.
September 2021Quick Start Guide
Note
Ensure the inside diameter of the gasket is larger than the inside diameter of
the flow meter and adjacent piping. If gasket material extends into the flow
stream, it will disturb the flow and cause inaccurate measurements.
5.4Insulation
Insulation should extend to the end of the bolt on the bottom of the meter
body and should leave at least 1-in. (25 mm) of clearance around the
electronics bracket. The electronics bracket and electronics housing should
not be insulated. See Figure 5-2.
Figure 5-2: Insulation best practice to prevent electronics overheating
A. Support tube
CAUTION
In high temperature installations, to avoid damage to the electronics on
integral units or to the remote cable on remote units, only insulate the
meter body as shown. Do not insulate the support tube. See also
Orientation.
5.5
Quick Start Guide 17
Flanged-style flow meter mounting
Most vortex flow meters use a flanged-style process connection. Physical
mounting of a flanged-style flow meter is similar to installing a typical
section of pipe. Conventional tools, equipment, and accessories (such as
Quick Start Guide September 2021
bolts and gaskets) are required. Tighten the nuts following the sequence
shown in Figure 5-4.
Note
The required bolt load for sealing the gasket joint is affected by several
factors, including operating pressure and gasket material, width, and
condition. A number of factors also affect the actual bolt load resulting from
a measured torque, including condition of bolt threads, friction between the
nut head and the flange, and parallelism of the flanges. Due to these
application-dependent factors, the required torque for each application may
be different. Follow the guidelines outlined in ASME PCC-1 for proper bolt
tightening. Make sure the flow meter is centered between flanges of the
same nominal size and rating as the flow meter.
Figure 5-3: Flanged-style flow meter installation
A. Installation studs and nuts (supplied by customer)
B. Gaskets (supplied by customer)
C. Flow
18Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
September 2021Quick Start Guide
Figure 5-4: Flange bolt torquing sequence
5.6Wafer-style flow meter alignment and mounting
Center the wafer-style meter body inside diameter with respect to the inside
diameter of the adjoining upstream and downstream piping. This will ensure
the flow meter achieves its specified accuracy. Alignment rings are provided
with each wafer-style meter body for centering purposes. Follow these steps
to align the meter body for installation. Refer to Figure 5-5.
1. Place the alignment rings over each end of the meter body.
2. Insert the studs for the bottom side of the meter body between the
pipe flanges.
3. Place the meter body (with alignment rings) between the flanges.
• Make sure the alignment rings are properly placed onto the
studs.
• Align the studs with the markings on the ring that correspond to
the flange you are using.
Note
Be sure to align the flow meter so the electronics are accessible, the
conduits drain, and the flow meter is not subject to direct heat.
4. Place the remaining studs between the pipe flanges.
5. Tighten the nuts in the sequence shown in Figure 5-4.
Quick Start Guide 19
Quick Start Guide September 2021
6. Check for leaks at the flanges after tightening the flange bolts.
Note
The required bolt load for sealing the gasket joint is affected by
several factors, including operating pressure and gasket material,
width, and condition. A number of factors also affect the actual bolt
load resulting from a measured torque, including condition of bolt
threads, friction between the nut head and the flange, and
parallelism of the flanges. Due to these application-dependent
factors, the required torque for each application may be different.
Follow the guidelines outlined in ASME PCC-1 for proper bolt
tightening. Make sure the flow meter is centered between flanges of
the same nominal size and rating as the flow meter.
Figure 5-5: Wafer-style flow meter installation with alignment
rings
B
B
A
C
D
A. Installation studs and nuts (supplied by customer)
B. Alignment rings
C. Spacer (for Rosemount 8800D to maintain Rosemount 8800A
dimensions)
D. Flow
Note
See for instructions on retrofitting 8800D to 8800A installations.
5.6.1Stud bolts for wafer-style flow meters
The following tables list the recommended minimum stud bolt lengths for
wafer-style meter body size and different flange ratings.
20Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
September 2021Quick Start Guide
Table 5-1: Stud bolt length for wafer-style flow meters with ASME B16.5
flanges
Line sizeMinimum recommended stud bolt lengths (in inches) for
½-inch6.006.256.25
1-inch6.257.007.50
1½-inch7.258.509.00
2-inch8.508.759.50
3-inch9.0010.0010.50
4-inch9.5010.7512.25
6-inch10.7511.5014.00
8-inch12.7514.5016.75
each flange rating
Class 150Class 300Class 600
Table 5-2: Stud bolt length for wafer-style flow meters with EN 1092
flanges
Line sizeMinimum recommended stud bolt lengths (in mm) for each
DN 15160160170170
DN 25160160200200
DN 40200200230230
DN 50220220250270
DN 80230230260280
DN 100240260290310
DN 150270300330350
DN 200320360400420
flange rating
PN 16PN 40PN 63PN 100
Line sizeMinimum recommended stud bolt lengths (in mm) for
15mm150155185
25mm175175190
40mm195195225
Quick Start Guide 21
each flange rating
JIS 10kJIS 16k and 20kJIS 40k
Quick Start Guide September 2021
Line sizeMinimum recommended stud bolt lengths (in mm) for
50mm210215230
80mm220245265
100mm235260295
150mm270290355
200mm310335410
each flange rating
JIS 10kJIS 16k and 20kJIS 40k
5.7Cable glands
If you are using cable glands instead of conduit, follow the cable gland
manufacturer’s instructions for preparation and make the connections in a
conventional manner in accordance with local or plant electrical codes. Be
sure to properly seal unused ports to prevent moisture or other
contamination from entering the terminal block compartment of the
electronics housing.
5.8Flow meter grounding
Grounding is not required in typical vortex applications; however, a proper
ground will eliminate possible noise pickup by the electronics. Grounding
straps may be used to ensure that the meter is grounded to the process
piping. If you are using the transient protection option (T1), grounding
straps are required to provide a proper low impedance ground.
Note
Properly ground flow meter body and transmitter per the local code.
To use grounding straps, secure one end of the grounding strap to the bolt
extending from the side of the meter body and attach the other end of each
grounding strap to a suitable ground. See Figure 5-6.
22Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
September 2021Quick Start Guide
Figure 5-6: Grounding connections
A. Internal ground connection
B. External ground assembly
5.9Grounding the transmitter case
The transmitter case should always be grounded in accordance with national
and local electrical codes. The most effective transmitter case grounding
method is direct connection to earth ground with minimal impedance.
Methods for grounding the transmitter case include:
Internal
Ground
Connection
External
Ground
Assembly
Note
Grounding the transmitter case using the threaded conduit connection may
not provide a sufficient ground. The transient protection terminal block
(Option Code T1) does not provide transient protection unless the
Quick Start Guide 23
The Internal Ground Connection screw is inside the FIELD
TERMINALS side of the electronics housing. This screw is
identified by a ground symbol ( ), and is standard on all
Rosemount 8800D transmitters.
This assembly is located on the outside of the electronics
housing and is included with the optional transient
protection terminal block (Option Code T1). The External
Ground Assembly can also be ordered with the
transmitter (Option Code V5) and is automatically
included with certain hazardous area approvals. See
Figure 5-6 for the location of the external ground
assembly.
Quick Start Guide September 2021
transmitter case is properly grounded. For transient terminal block
grounding, see the Reference Manual. Use the above guidelines to ground
the transmitter case. Do not run the transient protection ground wire with
signal wiring as the ground wire may carry excessive electric current if a
lightning strike occurs.
5.10Conduit installation
Prevent condensation in any conduit from flowing into the housing by
mounting the flowmeter at a high point in the conduit run. If the flowmeter
is mounted at a low point in the conduit run, the terminal compartment
could fill with fluid.
If the conduit originates above the flowmeter, route conduit below the
flowmeter to form a drip loop before entry. In some cases a drain seal may
need to be installed.
Figure 5-7: Proper conduit installation
AA
A. Conduit line
5.11
24Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
Wiring
1. Supply 10–30 VDC to the positive (+) and negative (–) terminals. The
power terminals are polarity insensitive: the polarity of the DC power
leads does not matter when connecting to the power terminals.
September 2021Quick Start Guide
Figure 5-8: Modbus and power supply wiring
5.12
C
B
A
A. RS-485 (A)
B. RS-485 (B)
C. 10–30 VDC power supply
2. Connect Modbus RTU communication wires to the Modbus A and B
terminals.
Note
Twisted pair wiring is required for RS-485 bus wiring. Wiring runs
under 1000 ft (305 m) should be AWG 22 or larger. Wiring runs from
1000 to 4000 ft. (305 to 1219 m) should be AWG 20 or larger. Wiring
should not exceed AWG 16.
Remote installation
If a remote electronics option (Rxx or Axx) was ordered, the flow meter
assembly will be shipped in two parts:
• The meter body with an adapter installed in the support tube and an
interconnecting coaxial cable attached to it.
• The electronics housing installed on a mounting bracket.
If an armored remote electronics option (Axx) was ordered, follow the same
instructions as for the standard remote cable connection with the exception
that the cable may not need to be run through conduit. Both standard and
armored cable include cable glands. Information on remote installation can
be found in Cable connections.
Quick Start Guide 25
Quick Start Guide September 2021
5.12.1 Mounting
Mount the meter body in the process flow line as described earlier in this
section. Mount the bracket and electronics housing in the desired location.
The housing can be repositioned on the bracket to facilitate field wiring and
conduit routing.
26Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
September 2021Quick Start Guide
5.12.2 Cable connections
Complete these steps for connecting the loose end of the coaxial cable to
the electronics housing. If connecting/disconnecting the meter adapter to
the meter body,.
Figure 5-9: Remote installation
A
B
C
D
E
F
P
G
O
H
N
J
K
I
M
L
A. ½ NPT conduit adapter or cable gland (supplied by customer for Rxx
options)
B. Coaxial cable
C. Meter adapter
D. Union
E. Washer
F. Nut
G. Sensor cable nut
H. Support tube
I. Meter body
J. Electronics housing
K. Coaxial cable SMA nut
L. ½ NPT conduit adapter or cable gland (supplied by customer for Rxx
options)
M. Housing adapter screws
N. Housing adapter
O. Housing base screw (one of four)
P. Ground connection
Quick Start Guide 27
Quick Start Guide September 2021
CAUTION
To prevent moisture from entering the coaxial cable connections, install the
interconnecting coaxial cable in a single dedicated conduit run or use sealed
cable glands at both ends of the cable.
In remote mount configurations when ordered with a hazardous area option
code, the remote sensor cable and the interconnecting thermocouple cable
are protected by separate intrinsic safety circuits, and must be segregated
from each other, other intrinsically safe circuits, and non-intrinsically safe
circuits per local and national wiring code.
CAUTION
The coaxial remote cable cannot be field terminated or cut to length. Coil
any extra coaxial cable with no less than a 2-in. (51 mm) radius.
1. If you plan to run the coaxial cable in conduit, carefully cut the
conduit to the desired length to provide for proper assembly at the
housing. A junction box may be placed in the conduit run to provide a
space for extra coaxial cable length.
2. Slide the conduit adapter or cable gland over the loose end of the
coaxial cable and fasten it to the adapter on the meter body support
tube. If coaxial remote cable originates or any part of the cable is
above the flow meter, route cable below the flow meter to form a
drip loop before the meter body support tube.
3. If using conduit, route the coaxial cable through the conduit.
4. Place a conduit adapter or cable gland over the end of the coaxial
cable.
5. Remove the housing adapter from the electronics housing.
28Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
September 2021Quick Start Guide
6. Slide the housing adapter over the coaxial cable.
7. Remove one of the four housing base screws.
8. Attach the coaxial cable ground wire to the housing via the housing
base ground screw.
9. Attach and hand tighten the coaxial cable SMA nut to the electronics
housing to 7 in-lbs (0.8 N-m).
Figure 5-10: Attaching and tightening SMA nut
A
B
A. SMA nut
B. Hand tighten
Note
Do not over-tighten the coaxial cable nut to the electronics housing.
10. Align the housing adapter with the housing and attach with two
screws.
11. Tighten the conduit adapter or cable gland to the housing adapter.
5.12.3 Housing rotation
The entire electronics housing may be rotated in 90° increments for easy
viewing. Use the following steps to change the housing orientation,
1. Loosen the housing rotation set screws at the base of the electronics
housing with a 5/32” hex wrench by turning the screws clockwise
(inward) until they clear the support tube.
2. Slowly pull the electronics housing out of the support tube.
Quick Start Guide 29
Quick Start Guide September 2021
CAUTION
Do not pull the housing more than 1.5 in. (40 mm) from the top of
the support tube until the sensor cable is disconnected. Damage to
the sensor may occur if this sensor cable is stressed.
3. Unscrew the sensor cable from the housing with a 5/16” open end
wrench.
4. Rotate the housing to the desired orientation.
5. Hold it in this orientation while you screw the sensor cable onto the
base of the housing.
CAUTION
Do not rotate the housing while the sensor cable is attached to the
base of the housing. This will stress the cable and may damage the
sensor.
6. Place the electronics housing into the top of the support tube.
7. Use a hex wrench to turn the housing rotation screws counterclockwise (outward) to engage the support tube.
5.12.4 Specifications and requirements for remote sensor cable
If using a Rosemount remote sensor cable, observe these specifications and
requirements.
• The remote sensor cable is a proprietary design tri-axial cable
• It is considered a low voltage signal cable
• It is rated for and/or part of intrinsically safe installations
• Non armored version is designed to be run through metal conduit
• Cable is water resistant, but not submersible. As a best practice,
exposure to moisture should be avoided if possible
• Rated operating temperature is –58°F to +392°F (–50°C to +200°C)
• Flame Resistant in accordance with IEC 60332-3
• Non-armored and armored version minimum bend diameter is 8 inches
(203 mm)
• Nominal O.D. of the non-armored version is 0.160 inches (4 mm)
• Nominal O.D. of the armored version is 0.282 inches (7.1 mm)
30Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
September 2021Quick Start Guide
Figure 5-11: Non-armored cable
A. Transmitter end
B. Sensor end
C. Minimum bend diameter
D. Nominal O.D.
Figure 5-12: Armored cable
A. Transmitter end
B. Sensor end
C. Minimum bend diameter
5.13
Quick Start Guide 31
Quad transmitter numbering and orientation
When quad vortex flow meters are ordered, for configuration purposes, the
transmitters are identified as Transmitter 1, Transmitter 2, Transmitter 3,
and Transmitter 4. The transmitter and meter body nameplate of a Quad
Vortex flow meter can be used to identify and verify the transmitter number.
See Figure 5-13 for Quad transmitter orientation and nameplate locations.
Quick Start Guide September 2021
See Figure 4-14 and 4-15 for Quad transmitter and meter body nameplate
number location.
Figure 5-13: Quad transmitter numbering
A. Transmitter nameplate (Transmitter 1)
B. Meter body nameplate (Transmitter 1)
32Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
September 2021Quick Start Guide
Figure 5-14: Quad transmitter nameplate
Figure 5-15: Quad meter body nameplate
Quick Start Guide 33
Quick Start Guide September 2021
6Basic configuration
6.1About basic configuration
The transmitter will be configured at the factory before shipment. If further
configuration changes are required, note the following:
• A HART communication tool must be used. Examples are ProLink III
Software or AMS Software with a HART modem, or Emerson AMS Trex
Device Communicator or 475 Field Communicator.
• The transmitter leaves the factory at HART address 1. Verify that the
HART communication tool is configured to poll beyond address 0.
Important
Do not change the transmitter HART address; it should always be set to
1.
• The COMM terminals must be used for configuration. A built-in load
resistor is provided for HART communication; an external load resistor is
not required.
Note
After measurement configuration and Modbus communication settings are
configured with a HART communicatoin tool, the flow meter can be used to
output measurement data to a Modbus host.
6.2Connect configuration tool
If configuration changes are needed, connect the configuration tool to the
transmitter as shown in Figure 6-1.
34Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
C
B
A
September 2021Quick Start Guide
Figure 6-1: HART configuration tool connection to COMM port
A. Example AMS Trex Device Communicator
B. Example ProLink III software on PC
C. 10–30 VDC power supply
Tip
If you do not have an external power supply during configuration, you can
temporarily power the transmitter directly through the COMM terminals
using the AMS Trex Device Communicator.
6.3
Process variables
Process variables define the flow meter output. When commissioning a flow
meter, review each process variable, its function and output, and take
corrective action if necessary before using the flow meter in a process
application.
6.3.1Primary variable mapping
Allows the user to select which variables the transmitter will output.
ProLink III
Flow variables are available as Corrected Volume Flow, Mass Flow, Velocity
Flow, Volume Flow or Process Temperature (MTA option only).
Quick Start Guide 35
When bench commissioning, the flow values for each variable should be
zero and the temperature value should be the ambient temperature.
If the units for the flow or temperature variables are not correct, refer to
Process variable units. Use the Process Variable Units function to select the
units for your application.
6.3.2Process variable units
ProLink IIIDevice Tools→Configuration→Process
Measurement→(select type)
Allows for the viewing and configuration of Process Variable Units such as
Volume, Velocity, Mass Flow, Electronics Temperature, Process Density, and
Corrected Volume units, including corrected volume Special Units
configuration.
Volume flow units
Allows the user to select the volumetric flow units from the available list.
Table 6-1: Volume flow units
gallons per secondgallons per minutegallons per hour
gallons per daycubic feet per secondcubic feet per minute
cubic feet per hourcubic feet per daybarrels per second
barrels per minutebarrels per hourbarrels per day
imperial gallons per
second
imperial gallons per dayliters per secondliters per minute
liters per hourliters per daycubic meters per second
cubic meters per minutecubic meters per hourcubic meters per day
mega cubic meters per
day
imperial gallons per
minute
special units
imperial gallons per hour
Corrected volumetric flow units
Allows the user to select the corrected volumetric flow units from the
available list.
Table 6-2: Corrected volume flow units
gallons per secondgallons per minutegallons per hour
gallons per daycubic feet per secondstandard cubic feet per
standard cubic feet per
hour
barrels per minutebarrels per hourbarrels per day
36Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
cubic feet per daybarrels per second
minute
September 2021Quick Start Guide
Table 6-2: Corrected volume flow units (continued)
imperial gallons per
second
imperial gallons per dayliters per secondliters per minute
liters per hourliters per daynormal cubic meters per
normal cubic meters per
hour
cubic meters per minutecubic meters per hourcubic meters per day
special units
imperial gallons per
minute
normal cubic meters per
day
imperial gallons per hour
minute
cubic meters per second
Note
When measuring corrected volumetric flow, a base density and process
density must be provided. The base density and process density are used to
calculate the density ratio which is a value used to convert actual volume
flow to corrected volume flow.
Mass flow units
Allows the user to select the mass flow units from the available list. (1 STon =
2000 lb; 1 MetTon = 1000 kg)
Table 6-3: Mass flow units
grams per hourgrams per minutegrams per second
kilograms per daykilograms per hourkilograms per minute
kilograms per secondpounds per minutepounds per hour
pounds per dayspecial unitsshort tons per day
short tons per hourshort tons per minutepounds per second
tons (metric) per daytons (metric) per hourtons (metric) per minute
Note
If you select a Mass Flow Units option, you must enter process density in
your configuration.
Velocity flow units
Allows the user to select the Velocity Flow Units from the available list.
• feet per second
• meters per second
Quick Start Guide 37
Quick Start Guide September 2021
Velocity measurement base
Determines if the velocity measurement is based on the mating pipe ID or
the meter body ID. This is important for Reducer™ Vortex Applications.
The flow meter can be used for liquid or gas/steam applications, but it must
be configured specifically for the application. If the flow meter is not
configured for the proper process, readings will be inaccurate. Select the
appropriate process configuration parameters for your application:
Transmitter mode
For units with an integral temperature sensor, the temperature sensor can
be activated here.
• Without Temperature Sensor
• With Temperature Sensor
Set process fluid
Select the fluid type—either Liquid, Gas/Steam, Tcomp Sat Steam, or Tcomp
Liquids. Tcomp Sat Steam and Tcomp Liquids require the MTA Option and
provide dynamic density compensation based on the process temperature
reading.
Fixed process temperature
Needed for the electronics to compensate for thermal expansion of the flow
meter as the process temperature differs from the reference temperature.
Process temperature is the temperature of the liquid or gas in the line during
flow meter operation.
May also be used as a back-up temperature value in the event of a
temperature sensor failure if the MTA option is installed.
Fixed process density
A Fixed Process Density must be accurately configured if mass flow or
corrected volume flow measurements are used. In mass flow it is used to
convert volume flow to mass flow. In corrected volume flow it is used with
the base process density to derive a density ratio which in turn is used to
convert volume flow to corrected volume flow. In temperature
compensated fluids the fixed process density is still required as it is used to
convert volume flow sensor limits to sensor limits for temperature
compensated fluids.
38Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
September 2021Quick Start Guide
Note
If mass or corrected volume units are chosen, you must enter the density of
your process fluid into the software. Be careful to enter the correct density.
The mass flow rate and density ratio are calculated using this user-entered
density, and unless the transmitter is in TComp Sat Steam or TComp Liquids
mode where changes in density are automatically being compensated for,
any error in this number will cause error in the measurement.
Base process density
The density of the fluid at base conditions. This density is used in corrected
volume flow measurement. It is not required for volume flow, mass flow, or
velocity flow. The Base Process Density is used with the Process Density to
calculate the Density Ratio. In temperature compensated fluids, the Process
Density is calculated by the transmitter. In non-temperature compensated
fluids the Fixed Process Density is used to calculate a fixed Density Ratio.
Density Ratio is used to convert actual volumetric flow to standard
volumetric flow rates based on the following equation:
Density ratio = density at actual (flowing) conditions/density at standard
(base) conditions
A factory calibration number relating the flow through the meter to the
shedding frequency measured by the electronics. Every vortex meter
manufactured by Emerson is run through a water calibration to determine
this value.
Enables the user to specify the type of flange on the flow meter for later
reference. This variable is preset at the factory but can be changed if
necessary.
The pipe I.D. (inside diameter) of the pipe adjacent to the flow meter can
cause entrance effects that may alter flow meter readings. Configuring the
actual mating pipe inside diameter will correct for theses effects. Enter the
appropriate value for this variable.
Pipe I.D. values for schedule 10, 40, and 80 piping are given in the following
table. If the mating pipe I.D. is not listed in the table, confirm it with the
manufacturer or measure it yourself.
Table 6-5: Pipe IDs for Schedule 10, 40, and 80 piping
40Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol
Schedule 10
inches (mm)
Schedule 40
inches (mm)
Schedule 80
inches (mm)
September 2021Quick Start Guide
6.8Optimize Digital Signal Processing (DSP)
ProLink IIIDevice Tools→Configuration→Process
Measurement→Signal Processing
A function that can be used to optimize the range of the flow meter based
on the density of the fluid. The electronics uses process density to calculate
the minimum measurable flow rate, while retaining at least a 4:1 signal to
the trigger level ratio. This function will also reset all of the filters to optimize
the flow meter performance over the new range. If the configuration of the
device has changed, this method should be executed to ensure the signal
processing parameters are set to their optimum settings. For dynamic
process densities, select a density value that is lower than the lowest
expected flowing density.
6.9Modbus communication settings
Table 6-6: Modbus default and configurable communication settings
ParameterRosemount
Baud rate96001200, 2400, 4800, 9600,
Start bits
Data Bits
ParityEvenNoneNone, Odd, Even
Stop BitsOneOneOne, two
Address range12461–247
(1) If the transmitter was ordered without communication settings, these will be
To implement the Modbus communication settings using a HART
communication device, you must enter the parameters in the form of a text
string into the HART Message field.
Quick Start Guide 41
Quick Start Guide September 2021
Note
The HART address must be set to 1 to ensure that the HART message field is
implemented by the transmitter.
The string is in the following example format: HMC A44 B4800 PO S2
HMC
These three characters are required at the beginning of the
configuration string.
A44
A indicates that the following number is the new Address (address
44). Leading zeros are not needed.
B4800
B indicates that the following number is the new Baud rate (1200,
2400, 4800, 9600, 19200, 38400).
PO
P identifies the following letter as Parity type (O = odd, E = even,
and N = none).
S2
S indicates that the following figure is the number of Stop bits (1 =
one, 2 = two).
Only values that differ from the current values need to be included. For
example, if only the address is changed, the following text string is written
into the HART Message: HMC A127.
Note
If the string is entered as only "HMC" the Modbus settings will be reset to
their HMC default values shown in Table 6-6. This will not affect other
transmitter configuration settings.
Note
Cycle power after sending the message and wait 60 seconds after the power
is restored for changes to take effect.
Alarm handling
The output from the Modbus transmitter in case of an error (such as a field
device malfunction) can be configured. The values for Modbus registers
corresponding to PV, SV, TV, and QV will be changed accordingly (applicable
registers in area 1300, 2000, 2100, and 2200).
Write HART Message field for HART address 1 device per Table 6-7.
Note
Cycle power after sending the message and wait 60 seconds after the power
is restored for changes to take effect.
Table 6-7: Modbus alarm configuration settings
StringAlarm output
HMC ENNot a number (NaN), default
42Rosemount™ 8800D Vortex Flow Meter with Modbus Protocol