Rosemount 8800D Series Vortex Flow Meter with FOUNDATION Fieldbus Manuals & Guides

Rosemount™ 8800D Series Vortex Flowmeter

with FOUNDATION™ Fieldbus
Reference Manual
00809-0100-4772, Rev FB
May 2019
Reference Manual
00809-0100-4772, Rev FB
Contents
1Section 1: Introduction
2Section 2: Configuration and Operation
Table of Contents
May 2019
1.1 Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
OUNDATION Fieldbus technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.2 F
1.3 System description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.3 User interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.4 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.5 General block information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.5.1 Modes of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.5.2 Block instantiation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.6 Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.6.1 FEATURES and FEATURES_SEL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.6.2 MAX_NOTIFY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.6.3 PlantWeb
2.7 Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
2.7.1 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
2.7.2 XMTR_MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.7.3 PROCESS_FLUID. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
2.7.4 Reference K_FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
2.7.5 FIXED_PROC_TEMPERATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.7.6 FIXED_PROC_DENSITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
2.7.7 FLANGE_TYPE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.7.8 PIPE_INSIDE_DIAMETER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
2.7.9 DAMPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.7.10 FILTER_AUTO_ADJUST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.7.11 PRIMARY_VALUE_RANGE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.7.12 SENSOR_RANGE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.7.13 SECONDARY_VALUE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
2.7.14 INSTALLATION_EFFECTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.7.15 PROCESS_DENSITY_RATIO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
2.7.16 METER_DISPLAY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.7.17 PROC_TEMP_DAMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table of Contents
1
Table of Contents
May 2019
Reference Manual
00809-0100-4772, Rev FB
2.7.18 VEL_MEAS_BASE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.7.19 TC_FAILURE_MODE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
2.7.20 LFC_RESPONSE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
2.7.21 CALC_PROC_DENSITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.7.22 PROC_TEMP_RANGE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
2.7.23 ELEC_TEMP_RANGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.8 Analog Input (AI) Function Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
2.8.1 Filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.8.2 Low cutoff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
2.8.3 Process alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.8.4 Alarm priority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.8.5 Status options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
2.8.6 Advanced features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.9 Flow simulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
2.9.1 Using transducer block parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.9.2 Configuration software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.10 Device capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
2.10.1 Link active scheduler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
2.10.2 Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3Section 3: Installation
3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
3.2 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
3.3 Environmental considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
3.4 Meter body installation tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
3.4.1 Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
3.4.2 Flow direction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
3.4.3 Upstream/downstream piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.4.4 Flowmeter orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.4.5 High-temperature installations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.4.6 Steam installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
3.4.7 Conduit connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
3.4.8 High-point installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.5 Hazardous locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
3.5.1 Cable gland . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
3.5.2 Gaskets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
3.5.3 Meter body grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
3.5.4 Flange bolts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2
Table of Contents
Reference Manual
00809-0100-4772, Rev FB
Table of Contents
May 2019
3.5.5 Wafer-style flowmeter alignment and mounting . . . . . . . . . . . . . . . . . . 31
3.5.6 Flanged-style flowmeter mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
3.5.7 Remote electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.5.8 Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.6 Electronics considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
3.6.1 Grounding the transmitter case . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
3.6.2 Commissioning tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
3.6.3 Foundation
Fieldbus transmitter power requirement . . . . . . . . . . . . . 39
3.6.4 Power conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
3.6.5 Field wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
3.6.6 Hardware configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
3.6.7 Simulate enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.6.8 Transmitter security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3.6.9 LCD display option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
3.7 Transmitter configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
4Section 4: Transducer Block
4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
4.1.1 Quick transducer block configuration guide . . . . . . . . . . . . . . . . . . . . . . 43
4.2 Parameters and descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
4.2.1 Block/transducer errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
4.2.2 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
4.2.3 Alarm detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
4.2.4 Status handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
4.2.5 Error conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
4.3 Flow units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
4.3.1 Standard/normal flow units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
4.4 Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
4.4.1 Process Variables (PV). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
4.4.2 Basic setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
4.4.3 Flow units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
4.4.4 Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
4.4.5 Filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
4.4.6 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
4.4.7 Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Table of Contents
5Section 5: Resource Block
5.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
3
Table of Contents
May 2019
Reference Manual
00809-0100-4772, Rev FB
5.1.1 Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
5.2 Parameters and descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
5.2.1 Block errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.2.2 Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.2.3 Alarm detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
5.2.4 Status handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
5.2.5 VCR. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
5.2.6 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
6Section 6: Analog Input Function Block
6.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
6.2 Analog Input (AI) Function Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
6.2.1 Configure the AI Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
7Section 7: Troubleshooting
7.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
7.2 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
7.3 Troubleshooting tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82
7.4 Advanced troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88
7.4.1 TP1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
7.5 Hardware maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
7.5.1 Replacing the F
7.5.2 Replacing the F
OUNDATION Fieldbus terminal block in the housing. . . . 90
OUNDATION Fieldbus electronics boards . . . . . . . . . . . . . 92
7.5.3 Replacing the FOUNDATION Fieldbus electronics housing . . . . . . . . . . . .93
7.5.4 Replacing the sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
7.5.5 Replacing the sensor: removable and integral support tubes. . . . . . . . 96
7.5.6 Remote electronics procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
7.5.7 Coaxial cable at the electronics housing . . . . . . . . . . . . . . . . . . . . . . . . .103
7.5.8 Changing the F
OUNDATION Fieldbus housing orientation . . . . . . . . . . .104
7.5.9 Temperature sensor replacement (MTA option only). . . . . . . . . . . . . .105
7.5.10 Troubleshooting a remote mount cable . . . . . . . . . . . . . . . . . . . . . . . . .106
7.6 Return of material. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
AAppendix A: Specifications and Reference Data
A.1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
A.2 Functional specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
A.3 Performance specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
A.4 Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
4
Table of Contents
Reference Manual
00809-0100-4772, Rev FB
BAppendix B: Product Certifications
Table of Contents
May 2019
A.5 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
B.1 Product certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
B.1.1 Approved manufacturing locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133
B.1.2 Flameproof enclosure Ex d protection type in accordance with IEC
60079-1, EN 60079-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133
B.1.3 Type n protection type in accordance with IEC 60079-15,
EN60079-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133
B.2 European directive information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
B.3 ATEX Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
B.4 European Pressure Equipment Directive (PED). . . . . . . . . . . . . . . . . . . . . . . . . 133
B.4.1 Rosemount 8800D Vortex Flowmeter Line Size 40 mm to
300 mm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133
B.4.2 Rosemount 8800D Vortex Flowmeter Line Size 15 mm and
25 mm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133
B.4.3 Sound Engineering Practice (SEP). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133
B.5 Hazardous location certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
B.5.1 North American certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134
B.5.2 European certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134
B.5.3 International IECEx certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135
B.5.4 Chinese certifications (NEPSI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137
B.5.5 Brazilian certifications (INMETRO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .138
B.5.6 EAC—Compliance with the requirements of technical regulations
of the Customs Union . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139
Table of Contents
CAppendix C: Electronics Verification
C.1 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
C.2 Electronics verification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
C.2.1 Electronics verification using internal flow simulation . . . . . . . . . . . . .151
C.2.2 Internal flow simulation—fixed flow rate . . . . . . . . . . . . . . . . . . . . . . . . .151
C.2.3 Internal flow simulation—varying flow rate. . . . . . . . . . . . . . . . . . . . . . .151
C.2.4 Exiting flow simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .152
C.2.5 Electronics verification using an external frequency generator . . . . .152
C.2.6 Calculating output variables with known input frequency . . . . . . . . .155
C.3 Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
C.3.1 English units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .157
C.3.2 SI units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .159
5
Table of Contents
May 2019
Reference Manual
00809-0100-4772, Rev FB
DAppendix D: Alerts
D.1 Alerts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
D.2 PlantWeb alerts overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
D.3 Alert configuration NE107 and PlantWeb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
D.4 Alert simulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
6
Table of Contents
Reference Manual
00809-0100-4772, Rev FB
Rosemount™ 8800D Vortex Flowmeter
NOTICE
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
Within the United States, Emerson Process Management has two toll-free assistance numbers:
Customer Central Technical support, quoting, and order-related questions.
1-800-522-6277 (7:00 am to 7:00 pm CST) North American Response Center
Equipment service needs. 1-800-654-7768 (24 hours—includes Canada) Outside of the United States, contact your local Emerson Process Management
representative.
Title Page
May 2019
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson Process Management Sales Representative.
Title Page
1
Title Page
May 2019
Reference Manual
00809-0100-4772, Rev FB
2
Title Page
Reference Manual
00809-0100-4772, Rev FB

Section 1 Introduction

1.1 Using this manual

The sections in this manual provide information on installing, configuring, troubleshooting, and performing other procedures for the Rosemount
OUNDATION
F The sections are organized as follows:
Section 2: Configuration and Operation describes operation, software functionality, and
configuration procedures.
Section 3: Installation provides assistance in hardware installation and wiring.
Section 4: Transducer Block provides descriptions of transducer block parameters, errors,
and diagnostics.
Section 5: Resource Block provides descriptions of resource block parameters, errors, and
diagnostics.
Fieldbus. Specifications and other important information are also included.
Introduction
8800D Vortex Flowmeter with
May 2019
Section 6: Analog Input Function Block provides descriptions of analog input function block
parameters, errors, and diagnostics.
Section 7: Troubleshooting provides troubleshooting information for the most common
problems that occur during operation. It describes the advanced troubleshooting features provided by the flowmeter and provides the maintenance procedures required to disassemble and re-assemble the hardware components.
Appendix A: Specifications and Reference Data provides reference and specification data
for the flowmeter and its applications.
Appendix B: Product Certifications provides the available product certfications and
hazardous area approvals.
Appendix C: Electronics Verification provides a procedure for verification of electronic
output to assist in meeting the quality standards for ISO 9001-certified manufacturing processes.

1.2 FOUNDATION Fieldbus technology

FOUNDATION Fieldbus is an all digital, serial, two-way communication system that interconnects field equipment such as sensors, actuators, and controllers. Fieldbus is a Local Area Network (LAN) with built-in capability to distribute control applications across the network for instruments that are used in both process and manufacturing automation
Introduction
1
Introduction
May 2019
environments. The fieldbus environment is the base level group of digital networks in the hierarchy of plant networks.
The fieldbus retains the desirable features of the 4–20 mA analog system, including a standardized physical interface to the wire, bus-powered devices on a single pair of wires, and intrinsic safety options. In addition, it enables the following capabilities:
Increased capabilities due to full digital communications
Reduced wiring and wire terminations due to multiple devices on one pair of wires
Increased selection of suppliers due to interoperability
Reduced loading on control room equipment with the distribution of some control
and input/output functions to field devices
Speed options for process control and manufacturing applications.

1.3 System description

The Rosemount 8800D Vortex Flowmeter with FOUNDATION fieldbus consists of a meter body and transmitter. It measures volumetric flow rate by detecting the vortices created by a fluid passing by the shedder bar.
Reference Manual
00809-0100-4772, Rev FB
The meter body is installed in-line with process piping. A sensor is located at the end of the shedder bar and creates an alternating sine wave signal due to the passing vortices. The transmitter measures the frequency of the signal and converts it into a flowrate.
This manual is designed to assist in the installation and operation of the flowmeter.
This product is intended to be used as a flowmeter for liquid, gas, or steam applications. Any use other than for which it was intended may result in serious injury or death.
2
Introduction
Reference Manual
00809-0100-4772, Rev FB
Configuration and Operation
May 2019

Section 2 Configuration and Operation

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
User interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
General block information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8
Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 12
Analog Input (AI) Function Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 16
Flow simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 18
Device capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19

2.1 Overview

This section covers operation, software functionality, and configuration procedures for the Rosemount
organized by block information. For detailed information about the function blocks used in the flowmeter, refer to the Rosemount F
8800D Vortex Flowmeter with FOUNDATION™ Fieldbus. This section is

2.2 Safety messages

Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that raises potential safety
issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
Explosions can result in death or serious injury.
Do not remove the transmitter covers in explosive environments when the circuit
is live.
Transmitter covers must be fully engaged to meet explosion proof requirements. Before connecting a configuration tool in an explosive atmosphere, make sure
the instruments in the loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.
OUNDATION Fieldbus Block Reference Manual.
Configuration and Operation
3
Configuration and Operation
May 2019
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may
be present on leads can cause electrical shock.

2.3 User interfaces

The flowmeter has both DD and DTM™-based user interfaces. All device configuration and maintenance tasks can be performed using either communication technology.
Device Descriptors (DDs) and DTM files for Rosemount products are available on the
Emerson Install Kits website
The DD capabilities supported will vary based on host supplier and host revision. Check with the host supplier to determine and obtain the appropriate DD for your situation. The type of DD your host supports may influence navigation between different functions.
Reference Manual
00809-0100-4772, Rev FB
.

2.4 Commissioning

Commissioning the flowmeter consists of verifying the transmitter configuration and operation. Typically this should be done before the flowmeter is installed in the application environment. In most cases, the user-supplied variables are pre-configured in the transmitter at the factory, so the meter is ready to use upon arrival at the end user installation.
Configuration may be required if:
Any configuration variables have changed.
A replacement transmitter is being installed.
To commission, connect power to the device and connect a Field Communicator or Foundation Fieldbus host system to the signal loop.
1. Verify the device powers up and communicates with the Field Communicator or host system.
2. Verify transmitter configuration parameters. Following are typical parameters to check:
Tag
Transmitter Mode
Process Fluid
Reference K-factor
Flange Type
Mating Pipe ID
PV Units (configured in the AI block)
4
Configuration and Operation
Reference Manual
00809-0100-4772, Rev FB
Configuration and Operation
May 2019
Fixed Process Temperature
Fixed Process Density and Density Units
Density Ratio (for Standard or Normal flow units only)
Flow Damping
3. If transmitter functional verification is required, refer to Appendix C: Electronics
Verification.
The flowchart in Figure 2-1 is a general guide for commissioning and meter installation. It can serve as a checklist to be referenced before and during installation of the flowmeter.
Configuration and Operation
5
Configuration and Operation
May 2019
Figure 2-1. General Guide for Commissioning and Meter Installation
Reference Manual
00809-0100-4772, Rev FB
START HERE
LCD Display?
No
Installed?
No
Using
Meter
Bench
Commissioning
?
Yes
Review
Configuration
Is
Configuration
OK?
No
A
Go to
Configure
Yes
Local
Display
Yes
DONE
No
Yes
A
CONFIGURE
Tag
Transmitter
Mode
Process Fluid
Reference
K-Factor
Flange Type
Mating Pipe ID
PV Units
(configured in
the AI block)
Flow Damping
B
FIELD
INSTALL
Mount
Flowmeter
Mount
Conduit
Wire
Flowmeter
Power
Flowmeter
Did you
Configure on
Bench?
No
Review
Configuration
Yes
DONE
B
Go to
Process
Temperature
Damping
Configure if
Necessary
Go to
A
Fixed Process Temperature
Auto Adjust Filter
Density Ratio
(for Standard or
Normal flow
units only)
Process Density
and Density
Units (for mass
flow units only)
6
Configuration and Operation
Reference Manual
00809-0100-4772, Rev FB

2.5 General block information

Reference information on the process control function blocks can be found in the Function Block manual document number 00809-0100-4783.

2.5.1 Modes of operation

The Resource, Transducer, and all other function blocks in the device have modes of operation. These modes govern the operation of the block. Every block supports both automatic (AUTO) and out of service (OOS) modes. Other modes may also be supported.
For the procedures described in this manual, it will be helpful to understand the following modes:
AUTO
The functions performed by the block will execute. If the block has any outputs, these will continue to update. This is typically the normal operating mode.
Out of Service (OOS)
Configuration and Operation
May 2019
The functions performed by the block will not execute. If the block has any outputs, these will typically not update and the status of any values passed to downstream blocks will be “BAD”. To make changes to the configuration of the block, change the mode of the block to OOS. When the changes are complete, change the mode back to AUTO.
MAN
In this mode, variables that are passed out of the block can be manually set for testing or override purposes.
Other types of modes
Other types of modes are Cas, RCas, ROut, IMan and LO. Some of these may be supported by different function blocks in the flowmeter. For more information, see the Function Block manual, document 00809-0100-4783.
Note
When an upstream block is set to OOS, the output status of all downstream blocks will be affected. The figure below depicts the hierarchy of blocks.
Resource Block
Transducer
Block
Analog Input
(AI Block)
Other
function
blocks
Changing modes
Configuration and Operation
To change the operating mode, set the MODE_BLK.TARGET to the desired mode. After a short delay, the parameter MODE_BLOCK.ACTUAL should reflect the mode change if the block is operating properly.
7
Configuration and Operation
May 2019
Permitted modes
It is possible to prevent unauthorized changes to the operating mode of a block. To do this, configure MODE_BLOCK.PERMITTED to allow only the desired operating modes. It is recommended to always select OOS as one of the permitted modes.

2.5.2 Block instantiation

The Rosemount 8800D Device Revision 10 supports block instantiation. Previous device revisions do not support block instantiation. When a device supports block instantiation, the number of blocks and block types can be defined to match specific application needs. The number of blocks that can be instantiated is only limited by the amount of memory within the device and the block types that are supported by the device. Instantiation does not apply to standard device blocks like the Resource, Sensor Transducer, Analog Input, and PID Blocks.
By reading the parameter “FREE_SPACE” in the Resource Block you can determine how many blocks you can instantiate. Each block that you instantiate takes up 4.5573% of the “FREE_SPACE”.
Block instantiation is done by the host control system or configuration tool, but not all hosts are required to implement this functionality. Refer to your specific host or configuration tool manual for more information.
Reference Manual
00809-0100-4772, Rev FB

2.6 Resource Block

The Resource Block contains diagnostic, hardware and electronics information. There are no linkable inputs or outputs to the Resource Block.

2.6.1 FEATURES and FEATURES_SEL

The FEATURES parameter is read only and defines which features are supported by the flowmeter. Below is a list of the FEATURES the flowmeter supports.
FEATURES_SEL is used to turn on any of the supported features that are found in the FEATURES parameter. The default setting of the flowmeter does not select any of these features. Choose one or more of the supported features if any.
UNICODE
All configurable string variables in the flow meter, except tag names, are octet strings. Either ASCII or Unicode may be used. If the configuration device is generating Unicode octet strings, you must set the Unicode option bit.
REPORTS
The flow meter supports alert reports. The Reports option bit must be set in the features bit string to use this feature. If it is not set, the host must poll for alerts. If this bit is set, the transmitter will actively report alerts.
SOFT W LOCK and HARD W LOCK
Inputs to the security and write lock functions include the hardware security switch, the hardware and software write lock bits of the FEATURE_SEL parameter, the WRITE_LOCK parameter, and the DEFINE_WRITE_LOCK parameter.
8
Configuration and Operation
Reference Manual
00809-0100-4772, Rev FB
The WRITE_LOCK parameter prevents modification of parameters within the device except to clear the WRITE_LOCK parameter. During this time, the block will function normally updating inputs and outputs and executing algorithms. When the WRITE_LOCK condition is cleared, a WRITE_ALM alert is generated with a priority that corresponds to the WRITE_PRI parameter.
The FEATURE_SEL parameter enables the user to select a hardware or software write lock or no write lock capability. To enable the hardware security function, enable the HW_SEL bit in the FEATURE_SEL parameter. When this bit has been enabled the WRITE_LOCK parameter becomes read only and will reflect the state of the hardware switch. In order to enable the software write lock, the SW_SEL bit must be set in the FEATURE_SEL parameter. Once this bit is set, the WRITE_LOCK parameter may be set to “Locked” or “Not Locked.” Once the WRITE_LOCK parameter is set to “Locked” by either the software or the hardware lock, all user requested writes as determined by the DEFINE_WRITE_LOCK parameter shall be rejected.
The DEFINE_WRITE_LOCK parameter allows the user to configure whether the write lock functions (both software and hardware) will control writing to all blocks, or only to the resource and transducer blocks. Internally updated data such as process variables and diagnostics will not be restricted by the security switch.
Configuration and Operation
May 2019
Table 2-1displays all possible configurations of the WRITE_LOCK parameter.
Table 2-1. Configurations of the WRITE_LOCK Parameter
Write
FEATURE_SEL
HW_SEL bit
0 (off) 0 (off) NA 1 (unlocked) Read only NA All 0 (off) 1 (on) NA 1 (unlocked) Read/Write NA All 0 (off) 1 (on) NA 2 (locked) Read/Write Physical Function
0 (off) 1 (on) NA 2 (locked) Read/Write Everything None 1 (on) 0 (off)
1 (on) 0 (off) 1 (locked) 2 (locked) Read only Physical Function
1 (on) 0 (off) 1 (locked) 2 (locked) Read only Everything None
1. The hardware and software write lock select bits are mutually exclusive and the hardware select has the highest priority. When the HW_SEL bit if set to 1 (on), the SW_SEL bit is automatically set to 0 (off) and is read only.
FEATURE_SEL
SW_SEL bit
(1)
SECURITY
SWITCH
0
(unlocked)
WRITE_LOCK
WRITE_LOCK
1 (unlocked) Read only NA All
Read/Write
DEFINE_WRITE_LOCK
access to
blocks
Blocks
Blocks

2.6.2 MAX_NOTIFY

The MAX_NOTIFY parameter value is the maximum number of alert reports that the resource can have sent without getting a confirmation, corresponding to the amount of buffer space available for alert messages. The number can be set lower, to control alert flooding, by adjusting the LIM_NOTIFY parameter value. If LIM_NOTIFY is set to zero, then no alerts are reported.
only
only

2.6.3 PlantWeb™ alarms

The alarms and recommended actions should be used in conjunction with Table 7-2.
Configuration and Operation
9
Configuration and Operation
May 2019
The Resource Block will act as a coordinator for PlantWeb alarms. There will be three alarm parameters (FAILED_ALARM, MAINT_ALARM, and ADVISE_ALARM) which will contain information regarding some of the device errors which are detected by the transmitter software. There will be a RECOMMENDED_ACTION parameter which will be used to display the recommended action text for the highest priority alarm. FAILED_ALARM will have the highest priority followed by MAINT_ALARM and ADVISE_ALARM will be the lowest priority.
FAILED_ALARMS
A failure alarm indicates a failure within a device that will make the device or some part of the device non-operational. This implies that the device is in need of repair and must be fixed immediately. There are four parameters associated with FAILED_ALARMS specifically, they are described below.
FAILED_ENABLED
This parameter contains a list of failures in the device which makes the device non-operational that will cause an alarm to be sent. Below is a list of the failures with the highest priority first.
1. NV memory failure
Reference Manual
00809-0100-4772, Rev FB
2. Sensor board electronics failure
3. Output board electronics failure
4. Thermocouple failure (MTA only)
FAILED_MASK
This parameter will mask any of the failed conditions listed in FAILED_ENABLED. A bit on means that the condition is masked out from alarming and will not be reported.
FAILED_PRI
Designates the alarming priority of the FAILED_ALM, see “Alarm priority” on page 17. The default is 0 and the recommended value are between 8 and 15.
FAILED_ACTIVE
This parameter displays which of the alarms is active. Only the alarm with the highest priority will be displayed. This priority is not the same as the FAILED_PRI parameter described above. This priority is hard coded within the device and is not user configurable.
FAILED_ALM
Alarm indicating a failure within a device which makes the device non-operational.
MAINT_ALARMS
A maintenance alarm indicates the device or some part of the device needs maintenance soon. If the condition is ignored, the device will eventually fail. There are five parameters associated with MAINT_ALARMS, they are described below.
MAINT_ENABLED
The MAINT_ENABLED parameter contains a list of conditions indicating the device or some part of the device needs maintenance soon. If the condition is ignored, the device will eventually fail.
10
Configuration and Operation
Reference Manual
00809-0100-4772, Rev FB
Below is a list of the conditions with the highest priority first.
1. Low pass filter over range
2. Low-flow cutoff over range
3. Density calc using fixed temp (MTA only)
4. Trigger over range
5. Electronics temp beyond limit (MTA only)
MAINT_MASK
The MAINT_MASK parameter will mask any of the failed conditions listed in MAINT_ENABLED. A bit on means that the condition is masked out from alarming and will not be reported.
MAINT_PRI
MAINT_PRI designates the alarming priority of the MAINT_ALM, “Process alarms” on
page 16. The default is 0 and the recommended values is 3 to 7.
Configuration and Operation
May 2019
MAINT_ACTIVE
The MAINT_ACTIVE parameter displays which of the alarms is active. Only the condition with the highest priority will be displayed. This priority is not the same as the MAINT_PRI parameter described above. This priority is hard coded within the device and is not user configurable.
MAINT_ALM
An alarm indicating the device needs maintenance soon. If the condition is ignored, the device will eventually fail.
Advisory alarms
An advisory alarm indicates informative conditions that do not have a direct impact on the device's primary functions There are five parameters associated with ADVISE_ALARMS.
ADVISE_ENABLED
The ADVISE_ENABLED parameter contains a list of informative conditions that do not have a direct impact on the device's primary functions. Below is a list of the advisories with the highest priority first.
Configuration and Operation
11
Configuration and Operation
May 2019
1. Flow simulation mode
2. PWA simulation active
3. Low flow cutoff active
4. Flow signal injection
5. PV range exceeded
6. Sensor range exceeded
7. Process temp above USL (427 °C) (MTA only)
8. Process temp below LSL ( –50 °C) (MTA only)
9. Process temp above sat steam limit (MTA only)
10. Process temp below sat steam limit (MTA only)
ADVISE_MASK
Reference Manual
00809-0100-4772, Rev FB
The ADVISE_MASK parameter will mask any of the failed conditions listed in ADVISE_ENABLED. A bit on means the condition is masked out from alarming and will not be reported.
ADVISE_PRI
ADVISE_PRI designates the alarming priority of the ADVISE_ALM, see “Process alarms” on
page 16. The default is 0 and the recommended values are 1 or 2.
ADVISE_ACTIVE
The ADVISE_ACTIVE parameter displays which of the advisories is active. Only the advisory with the highest priority will be displayed. This priority is not the same as the ADVISE_PRI parameter described above. This priority is hard coded within the device and is not user configurable.
ADVISE_ALM
ADVISE_ALM is an alarm indicating advisory alarms. These conditions do not have a direct impact on the process or device integrity.
Recommended actions for PlantWeb alarms
The RECOMMENDED_ACTION parameter displays a text string that will give a recommended course of action to take based on which type and which specific event of the PlantWeb alarms is active Table 5-1. Reference Index Number 78.

2.7 Transducer Block

The Transducer Block contains sensor and process fluid information used by the transmitter for accurate measurements.
12
Configuration and Operation
Reference Manual
00809-0100-4772, Rev FB

2.7.1 Parameters

To make parameter changes, the Block Mode must be in the Out of Service (OOS) mode of operation.
The Transducer Block parameters must be correct for an accurate measurement. These parameters are factory configured specifically for the measurement when the transmitter
is sized using Rosemount Instrument Toolkit

2.7.2 XMTR_MODE

Transmitter Mode
Without Temperature Sensor—No process temperature sensor available (Non MTA electronics)
With Temperature Sensor—Process temperature sensor installed (MTA electronics only)

2.7.3 PROCESS_FLUID

Liquid—Process fluid is liquid
program.
Configuration and Operation
May 2019
Gas/Steam—Process fluid is a gas
T Comp Sat Steam—Temperature Compensated Saturated Steam (MTA electronics only)

2.7.4 Reference K_FACTOR

The factory calibrated K-Factor stamped on the meter body

2.7.5 FIXED_PROC_TEMPERATURE

Fixed Process Temperature. The operating temperature of the process

2.7.6 FIXED_PROC_DENSITY

Fixed Process Density. The density of the process fluid at flowing pressure and temperature

2.7.7 FLANGE_TYPE

The flange rating and type to match the vortex meter body

2.7.8 PIPE_INSIDE_DIAMETER

The inside diameter (I.D.) of the mating pipe where the meter body is installed.

2.7.9 DAMPING

The flow damping value. Default is 2 seconds. Valid range is 0.2 to 255 seconds.

2.7.10 FILTER_AUTO_ADJUST

Optimize Signal Processing based on the density of the process fluid. Select the incremental value equal to or less than the process fluid density.
Configuration and Operation
13
Configuration and Operation
May 2019

2.7.11 PRIMARY_VALUE_RANGE

Range of the flow measurement. The units match the XD_SCALE units from the AI Block assigned to Flow

2.7.12 SENSOR_RANGE

Range the meter is capable of measuring. The maximum measurable flow rate the vortex meter will measure
The units match the XD_SCALE units from the AI Block assigned to Flow

2.7.13 SECONDARY_VALUE

The shedding frequency measured by the vortex sensor in units of Hz

2.7.14 INSTALLATION_EFFECTS

Installation Effect correction factor. Use when the meter is installed in less than ideal piping configuration. See Installation Effects document 00816-0100-3250 for details.
Reference Manual
00809-0100-4772, Rev FB
Valid range -1.5 to 1.5

2.7.15 PROCESS_DENSITY_RATIO

Density Ratio = Density at flowing P and T/Density at Standard P and T
The transmitter only uses density ratio when the flow output is in Standard or Normal units.
Examples of Standard unit: Standard Cubic Feet per Minute, SCFM
Example of Normal unit: Normal Cubic Meters per hour, NCMH

2.7.16 METER_DISPLAY

Data displayed locally on LCD display.
The following measurements can be displayed on the flowmeter LCD display:
Flow
Transducer Percent Range—Percent range of maximum accurate flow
Process Temperature—MTA electronics only
Process Density—MTA electronics only
Shedding Frequency
Electronics Temperature—MTA electronics only
Integrator Block Out—Totalized flow from Vortex meter Integrator Block

2.7.17 PROC_TEMP_DAMP

Process Temperature Damping. Only vortex meters with the MTA option measure process temperature.
The units are seconds, default is 2 seconds. Valid range is 0.4 to 32 seconds.
14
Configuration and Operation
Reference Manual
00809-0100-4772, Rev FB

2.7.18 VEL_MEAS_BASE

Velocity Measurement Base. The velocity calculation can be based on the Mating Pipe inside diameter or the Meter body inside diameter. Default is the Mating pipe ID.

2.7.19 TC_FAILURE_MODE

Thermocouple Failure Mode. The MTA optioned meters measure process temperature with a thermocouple. If the thermocouple fails, the transmitter will indicate the failed sensor input. There are two options available for the transmitter operation after the sensor fails.
Sensor Failure; Status is BAD—Mass Flow measurement status is BAD.
Use Fixed Temp; Status is UNCERTAIN—Mass Flow calculation uses fixed temperature values when calculating density and status of measurement is UNCERTAIN .

2.7.20 LFC_RESPONSE

Low Flow Cutoff Response. The flow measurement will be 0 when the measured flow is less than the Low Flow Cutoff.
Configuration and Operation
May 2019
The transition from the flow measurement down to 0 flow can be Damped or Stepped.
Damped will transition to 0 flow based on the Damping setting.
Stepped will transition to 0 flow as soon as the Low Flow Cutoff activates.

2.7.21 CALC_PROC_DENSITY

Calculated Process Density. The MTA optioned transmitters calculate the density of Saturated Steam based on the process temperature measurement.
The Calculated Process Density is used to determine the Mass Flow rate of saturated steam.

2.7.22 PROC_TEMP_RANGE

MTA option only. Process Temperature Range.
The process temperature range is the minimum and maximum temperature of the vortex sensor.
The Units will match the XD_SCALE units of the AI Block assigned to Process Temperature

2.7.23 ELEC_TEMP_RANGE

MTA option only. Electronics Temperature Range.
Configuration and Operation
The electronics temperature range is the minimum and maximum temperature rating for the electronic components.
The Units will match the XD_SCALE units of the AI Block assigned to Electronics Temperature.
15
Configuration and Operation
May 2019

2.8 Analog Input (AI) Function Block

For information on the Analog Input (AI) Function Block, refer to Section 6.

2.8.1 Filtering

The filtering feature changes the response time of the device to smooth variations in output readings caused by rapid changes in input. Adjust the filter time constant (in seconds) using the PV_FTIME parameter. Set the filter time constant to zero to disable the filter feature.
Figure 2-2. Analog Input PV_FTIME Filtering
OUT (mode in man)
OUT (mode in auto)
Reference Manual
00809-0100-4772, Rev FB
PV
FIELD_VAL
PV_FTIME

2.8.2 Low cutoff

When the converted input value is below the limit specified by the LOW_CUT parameter, and the Low Cutoff I/O option (IO_OPTS) is enabled (True), a value of zero is used for the converted value (PV). This option is useful to eliminate false readings when the flow measurement is close to zero.
Note
Low Cutoff is the only I/O option supported by the AI block. Set the I/O option in Manual or Out of Service mode only.

2.8.3 Process alarms

Process Alarm detection is based on the OUT value. Configure the alarm limits of the following standard alarms:
63% of Change
Time (seconds)
High (HI_LIM)
High high (HI_HI_LIM)
Low (LO_LIM)
Low low (LO_LO_LIM)
16
Configuration and Operation
Reference Manual
00809-0100-4772, Rev FB
In order to avoid alarm chattering when the variable is oscillating around the alarm limit, an alarm hysteresis in percent of the PV span can be set using the ALARM_HYS parameter. The priority of each alarm is set in the following parameters:
HI_PRI
HI_HI_PRI
LO_PRI
LO_LO_PRI

2.8.4 Alarm priority

Alarms are grouped into five levels of priority:
Priority
number Priority description
0 The alarm condition is not used. 1 An alarm condition with a priority of 1 is recognized by the system, but is
not reported to the operator.
2 An alarm condition with a priority of 2 is reported to the operator.
3-7 Alarm conditions of priority 3 to 7 are advisory alarms of increasing
priority.
8-15 Alarm conditions of priority 8 to 15 are critical alarms of increasing
priority.
Configuration and Operation
May 2019

2.8.5 Status options

Status options (STATUS_OPTS) supported by the AI block are shown below:
Propagate fault forward
If the status from the sensor is Bad, Device failure or Bad, Sensor failure, propagate it to OUT without generating an alarm. The use of these sub-status in OUT is determined by this option. Through this option, the user may determine whether alarming (sending of an alert) will be done by the block or propagated downstream for alarming.
Uncertain if limited
Set the output status of the Analog Input block to uncertain if the measured or calculated value is limited.
BAD if limited
Set the output status to Bad if the sensor is violating a high or low limit.
Uncertain if man mode
Set the output status of the Analog Input block to uncertain if the actual mode of the block is Man.
Note
The instrument must be in Out of Service mode to set the status option.

2.8.6 Advanced features

The AI Function Block provides added capability through the addition of the following parameters:
Configuration and Operation
17
Configuration and Operation
May 2019
ALARM_TYPE
ALARM_TYPE allows one or more of the process alarm conditions detected by the AI function block to be used in setting its OUT_D parameter.
OUT_D
OUT_D is the discrete output of the AI function block based on the detection of process alarm condition(s). This parameter may be linked to other function blocks that require a discrete input based on the detected alarm condition.

2.9 Flow simulation

The electronics is capable of internally generating a flow signal that may be used to simulate a sensor signal. The simulated signal amplitude is based on the transmitter required minimum process density. The simulated signal can be a constant frequency or the simulated signal can be a varying frequency to represent a ramping flow rate.
Simulating the flow signal requires the simulate ENABLE jumper on the transmitter electronics board to be in the ‘ON’ position. The transmitters are shipped with the jumper in the ‘OFF’ position.
Reference Manual
00809-0100-4772, Rev FB

2.9.1 Using transducer block parameters

SIMULATION_CONTROL
Sim Disabled—Normal operation, no simulated flow signal.
Sim—Internal Generator—The internal frequency generator will produce the frequency signal.
Sim—External Generator—An External Frequency generator can be connected to Freq In and Ground connections on the electronics board.
SIMULATION_UNITS
PV Engineering Units—Simulated flow will be in engineering units.
PV Percent of Range—Simulated flow will be in percentage of Primary Value flow range.
SIMULATION_HIGH_POINT
High simulation value in engineering units or percentage.
SIMULATION _LOW_POINT
Low simulation value in engineering units or percentage.
SIMULATION_RAMP_PERIOD
The time, in seconds, between low and high simulation points.

2.9.2 Configuration software

Configuration Software, such as AMS™ Wireless Configurator, simplifies the simulation process.
18
Configuration and Operation
Reference Manual
00809-0100-4772, Rev FB
AMS Revision 12 with Rosemount 8800D Device Revision 9
Set Target Mode to Out of Service by unchecking Auto and checking Out of Service boxes.
Set the simulation values as desired and return the mode to Auto.
The flow value will be simulated until the simulation is disabled. Simulation is also disabled with a power cycle.
Device Revision 10
The Device Rev 10 interface steps through the simulation configuration after clicking the ‘Simulate Flow’ button. Follow the steps for the desired flow simulation.

2.10 Device capabilities

2.10.1 Link active scheduler

The flowmeter can be designated to act as the Backup Link Active Scheduler (BLAS) in the event that the LAS is disconnected from the segment. As the backup LAS, the flowmeter will take over the management of communications until the host is restored.
Configuration and Operation
May 2019
The host system may provide a configuration tool specifically designed to designate a particular device as a backup LAS. Otherwise, this can be configured manually as follows:
1. Access the Management Information Bose (MIB) for the flowmeter.
2. To activate the LAS capability, write 0x02 to the BOOT_OPERAT_FUNCTIONAL_CLASS object (Index 605). To deactivate, write 0x01.
3. Restart the processor.

2.10.2 Capabilities

Virtual Communication Relationship (VCRs)
There are a total of 20 VCRs. One is permanent and 19 are fully configurable by the host system. Twenty-five link objects are available.
Configuration and Operation
19
Configuration and Operation
May 2019
Table 2-2. Network Parameters and Values
Network parameter Value
Slot Time 6
Maximum Response Delay 4
Maximum Inactivity to Claim LAS Delay 47
Minimum Inter DLPDU Delay 7
Time Sync class 4 (1ms)
Maximum Scheduling Overhead 21
Per CLPDU PhL Overhead 4
Maximum Inter-channel Signal Skew 0
Required Number of Post-transmission-gab-ext Units 0
Required Number of Preamble-extension Units 1
Host timer recommendations
T1 = 96000 T2 = 1920000 T3 = 480000
Reference Manual
00809-0100-4772, Rev FB
Block execution times
Analog Input = 15 ms PID = 20 ms Arithmetic = 20 ms Integrator = 25 ms
20
Configuration and Operation
Loading...
+ 148 hidden pages