Rosemount 644 Temperature Transmitter
with Profibus PA
www.rosemount.com
Reference Manual
NOTICE
00809-0300-4728, Rev AA
January 2011
Rosemount 644
Rosemount 644 Temperature
Transmitter with Profibus PA
Rosemount 644 Hardware Revision 9
Read this manual before working with the product. For personal and system safety, and for
optimum product performance, make sure to thoroughly understand the contents before
installing, using, or maintaining this product.
The United States has two toll-free assistance numbers and one international number.
Customer Central
1-800-999-9307 (7:00 a.m. to 7:00 p.m. CST)
National Response Center
1-800-654-7768 (24 hours a day)
Equipment service needs
International
1-(952) 906-8888
The products described in this document are NOT designed for nuclear-qualified
applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware
or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact an Emerson Process
Management Sales Representative.
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or
serious injury.
• Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
• Do not remove the connection head cover in explosive atmospheres when the
circuit is live.
• Before connecting Profibus devices in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or
non-intrinsic field wiring practices.
• Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
• All connection head covers must be fully engaged to meet
explosion-proof requirements.
Process leaks could result in death or serious injury.
• Do not remove the thermowell while in operation.
• Install and tighten thermowells and sensors before applying pressure
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
www.rosemount.com
Reference Manual
00809-0300-4728, Rev AA
Rosemount 644
January 2011
USING THIS MANUALThe sections in this manual provide information on installing, operating, and
maintaining the Rosemount 644 with Profibus PA protocol. The sections are
organized as follows:
Section 2: Configuration provides instruction on commissioning and operating
the Rosemount 644 PA transmitter. Information on software functions,
configuration parameters, and online variables is also included.
Section 3: Hardware Installation contains mechanical mounting and
installation instructions, and field upgrade options.
Section 4: Electrical Installation contains electrical installation instructions,
with wiring and power considerations.
Section 5: Calibration contains techniques for calibration and troubleshooting
Appendix A: Specifications and Reference Data supplies reference and
specification data, as well as ordering information.
Appendix B: Product Certifications contains intrinsic safety approval
information, European ATEX directive information, and approval drawings.
Appendix C: Profibus Block Information contains Profibus block and
parameter information.
TRANSMITTER
OVERVIEW
Features of the Rosemount 644 with Profibus PA include:
•Accepts inputs from a wide variety of sensors (T/C, RTD, Ohm, mV)
•Configuration using Siemens SIMATIC PDM
•Electronics that are completely encapsulated in epoxy making the
transmitter extremely durable and ensuring long-term reliability
•A compact size and a variety of housing options allowing mounting
flexibility for the control room or the field
Refer to the following literature for a full range of compatible connection
heads, sensors, and thermowells provided by Emerson Process
Management.
•Temperature Sensors and Assemblies Product Data Sheet, Volume 1
(document number 00813-0100-2654)
•Temperature Sensors and Assemblies Product Data Sheet, Volume 2
(document number 00813-0200-2654)
•Rosemount 1067 compact sensor and 1097 Thermowell Product Data
Sheet (00813-0100-4951)
•Rosemount 65Q and 65B Resistance Temperature Sensors for
Hygienic and Sanitary Applications Product Data Sheet
(00813-0100-4827)
NOTE
For Rosemount 644 with HART
Product Manual 00809-0100-4728.
®
or FOUNDATION™ fieldbus, see Rosemount
1-2
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
DEVICE REVISION
Table 1-1. Device Revisions
(NE53)
Date
11/ 101.01.0163.02New
Software
Revision
Profibus
Profile
Changes to
Software
Product
Compatible Files
644 GSD: EPM1039.gsd
Profile:3.02 GSD: pa139700.gsd
DD: see Rosemount.com
DTM: see Rosemount.com
Manual
Revision
AA
CONSIDERATIONS
GeneralElectrical temperature sensors such as RTDs and thermocouples produce
low-level signals proportional to their sensed temperature. The 644 converts
the low-level sensor signal to digital Profibus PA signal that is relatively
insensitive to lead length and electrical noise. This signal is then transmitted
to the control room via two wires.
CommissioningThe transmitter can be commissioned before or after installation. It may be
useful to commission it on the bench, before installation, to ensure proper
operation and to become familiar with its functionality. Make sure the
instruments in the loop are installed in accordance with intrinsically safe,
FISCO, or non-incendive field wiring practices.
MechanicalLocation
When choosing an installation location and position, take into account the
need for access to the transmitter.
Special Mounting
Special mounting hardware is available for mounting a 644 head mount
transmitter to a DIN rail, or assembling a new 644 head mount to an existing
threaded sensor connection head (former option code L1).
Electrical Proper electrical installation is necessary to prevent errors due to sensor lead
resistance and electrical noise. For best results, shielded cable should be
used in electrically noisy environments.
Make wiring connections through the cable entry in the side of the connection
head. Be sure to provide adequate clearance for cover removal.
EnvironmentalThe transmitter electronics module is permanently sealed within the housing,
resisting moisture and corrosive damage. Verify that the operating
atmosphere of the transmitter is consistent with the appropriate hazardous
locations certifications.
Temperature Effects
The transmitter will operate within specifications for ambient temperatures
between –40 and 185 °F (–40 and 85 °C). Heat from the process is
transferred from the thermowell to the transmitter housing. If the expected
process temperature is near or beyond specification limits, consider the use of
additional thermowell lagging, and extension nipple, or a remote mounting
configuration to isolate the transmitter from the process.
1-3
Rosemount 644
Housing Temperature Rise, Above
Ambient °C (°F)
3456789
0
60 (108)
50 (90)
40 (72)
30 (54)
20 (36)
10 (18)
3.6
22
Extension Length (in.)
815 °C (1500 °F) Oven Temperature
540 °C (1000 °F)
Oven Temperature
250 °C (482 °F) Oven Temperature
Figure 1-1. 644 head mount
Transmitter Connection Head
Temperature Rise vs. Extension
Length
Reference Manual
00809-0300-4728, Rev AA
January 2011
Figure 1-1 provides an example of the relationship between transmitter
housing temperature rise and extension length.
Example
The transmitter specification limit is 85 °C. If the ambient temperature is 55 °C
and the process temperature to be measured is 800 °C, the maximum
permissible connection head temperature rise is the transmitter specification
limit minus the ambient temperature (moves 85 to 55 °C), or 30 °C.
In this case, an extension of 100 mm meets this requirement, but 125 mm
provides a margin of 8 °C, thereby reducing any temperature effects in the
transmitter.
RETURN OF MATERIALSTo expedite the return process in North America, call the Emerson Process
Management National Response Center toll-free at 800-654-7768. This
center, available 24 hours a day, will assist you with any needed information
or materials.
The center will ask for the following information:
•Product model
•Serial numbers
•The last process material to which the product was exposed
The center will provide
•A Return Material Authorization (RMA) number
•Instructions and procedures that are necessary to return goods that
were exposed to hazardous substances
For other locations, please contact an Emerson Process Management sales
representative.
1-4
NOTE
If a hazardous substance is identified, a Material Safety Data Sheet (MSDS),
required by law to be available to people exposed to specific hazardous
substances, must be included with the returned materials.
Transmitter Setup Using Class 2 Master . . . . . . . . . . . . .page 2-4
Transmitter Online Setup with DD or DTM . . . . . . . . . . . .page 2-6
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or
serious injury.
• Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
• Do not remove the connection head cover in explosive atmospheres when the
circuit is live.
• Before connecting Profibus devices in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
• Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
• All connection head covers must be fully engaged to meet
explosion-proof requirements.
Process leaks could result in death or serious injury.
• Do not remove the thermowell while in operation.
• Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
www.rosemount.com
Rosemount 644
START
HERE
Bench
Calibration?
BASIC SETUP
Set Sensor Type
Set Number of Wires
Set Units
Set Range Values
Set Damping
VERIFY
Simulate Sensor Input
Within
Specifications?
Refer to Section 2: Configuration
FIELD INSTALL
Mount Transmitter
Wire Transmitter
Power Transmitter
FINISHED
Figure 2-1. Configuration
Flowchart
Reference Manual
00809-0300-4728, Rev AA
January 2011
2-2
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
CONFIGURATION
GUIDELINES
Profile 3.02 Identification
Number Adaptation
Mode
To configure on the bench, required equipment includes a power supply, a
class 2 master with DP/PA coupler, proper cable, and terminators. Verify that
the Security hardware jumper is set to the OFF position in order to proceed
with configuration. See Figure 4-2 for jumper location.
Setup for the Rosemount 644 can be done via Siemens SIMATIC
software or any other DD or DTM based Class 2 master.
Rosemount 644 Profibus Profile 3.02 devices are set to Identification Number
Adaptation Mode when shipped from the factory. This mode allows the
transmitter to communicate with any Profibus class 1 master with either the
generic Profile GSD (9700) or Rosemount 644 specific GSD (1039).
®
PDM
Block ModesWhen configuring a device with a class 2 master, it is best practice to set
blocks to OOS when downloading parameters that affect the transmitter
output. However, the 644 will allow configuration changes made in AUTO to
be downloaded to the device. This prevents the class one master from seeing
a jump in output without a status change. Setting the blocks OOS and back
into Auto is done automatically when using the class two master configuration
wizards within the Rosemount 644 DD or DTM. This is done so no additional
action is required when configuring the device.
Configuration ToolsThe Rosemount 644 can be configured through the factory at order entry or
using a class 2 master. The C1 option code must be ordered to obtain
addressing and configuration of the device at the factory.
Class 2 masters require either DD or DTM files for configuration. These files
can be found at www.rosemount.com or by contacting your local Emerson
Process representative.
The remainder of this section will cover the configuration tasks using the
Class 2 master configuration tool.
NOTE
Instructions in this section use the terminology found in the class 2 master.
See Appendix C: Profibus Block Information to cross reference parameters
between the class2 master, and the Profibus specification.
BASIC SETUP TASKS
Device DescriptionBefore configuring the device, ensure the host has the appropriate Device
Description file revision for this device. The device descriptor can be found on
www.rosemount.com. The initial release of the Rosemount 644 with Profibus
PA protocol is device revision 1.
Assign AddressThe Rosemount 644 is shipped with a temporary address of 126. This must
be changed to a unique value between 1 and 125 in order to establish
communication with the class 1 master. Usually, addresses 1-2 are reserved
for masters, therefore transmitter addresses between 3 and 125 are
recommended for the device.
Address can be set using either:
•Factory Configuration (C1 option code)
•Class 2 master – see respective class 2 master manual for setting
instrument addresses
2-3
Reference Manual
00809-0300-4728, Rev AA
Rosemount 644
January 2011
Default ConfigurationUnless otherwise specified, the Rosemount 644 will be shipped with the
following settings:
Table 2-1. Temperature
configuration defaults
TRANSMITTER SETUP
USING CLASS 2
MASTER
Basic Transmitter Setup
Table 2-2. Basic Transmitter
Configuration using Class 2
master
Device Address: 126
Sensor Type: RTD, Pt 100 (= 0.00385, 4 wire)
Damping: 5 sec.
Units of Measurement: °C
Alarm Limits:
• HI-HI: Infinity
• HI: Infinity
• LO: - Infinity
• LO-LO: Infinity
Local Display (when installed): Engineering Units of Temperature
Measurement Range: 0 °C to 100 °C
Desired ActionMenu >> Parameter >> Value
Set Sensor TypePrimary Value>>Sensor>>Sensor Type
Set Connection Type (Number of Wires) Primary Value>>Sensor>>Sensor Connection
Set Units
Set Upper Range ValuePrimary Value>>Process Value Scale>>Upper Value
Set Lower Range ValuePrimary Value>>Process Value Scale>>Lower Value
Set Damping ValuePrimary Value>>Sensor>>Damping Value
* Please see “Basic Transmitter Configuration using DD or DTM” on page 2-6 for considerations
when changing units.
*
Primary Value>>Sensor>>Primary Value Unit
Process AlarmsProcess alarms activate an output alarm status when the configured alarm
point is exceeded. A process alarm will be transmitted continuously if the
output set points are exceeded. The alarms will reset once the value returns
within range.
Process Alarm parameters are defined as follows
•HI-HI Alarm: Changes Output Status to Good – Critical Alarm – Hi Limit
•HI Warning: Changes Output Status to Good – Advisory Alarm – Hi
Limit
•LO Warning: Changes Output Status to Good – Advisory Alarm – Lo
Limit
•LO-LO Alarm: Changes Output Status to Good – Critical Alarm – Lo
Limit
•Alarm Hysteresis: Amount the output value must pass back into range
before alarm is cleared.
Example: Upper Alarm = 100 °C. Alarm Hysteresis = 0.5 °C. After
activation at 100 °C, the alarm will clear once the output goes below
99.5 °C = 100 - 0.5 °C.
Process Alerts can be set using,
2-4
•Class 2 master – see Table 2-3 for configuration
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
Table 2-3. Process Alarm
Configuration using Class 2
master
Desired ActionMenu Path
Enter Process Alarm LevelsOutput>>Output Limits>>LO-LO Alarm
Output>>Output Limits>>LO Warning
Output>>Output Limits>>HI Warning
Output>>Output Limits>>HI- HI Alarm
SimulationSimulation is in the AI block and used to verify the output from the transducer
block. The Rosemount 644 has a simulation jumper located on the transmitter
puck top cover that must be set to the ON position in order to simulate.
NOTE
This jumper position is ignored when the transmitter is initially powered. The
jumper position must be changed while the transmitter is powered to activate
simulation. If power is removed and restored, the simulation mode will be OFF
regardless of jumper position.
With simulation enabled, the actual measurement value has no impact on the
OUT value or the status. The OUT value will equal the simulated value from
the transducer block plus any scaling or linearization effects performed in the
AI block.
Table 2-4. Simulation
configuration using Class 2
master
Once the simulation jumper is set to on, simulation mode can be activated
Using a Class 2 master see Table 2-4.
Desired ActionMenu >> Parameter >> Value
Enable SimulateMain Setup>>Human Interface>>
Simulation Status>>State>>
Select Enabled
Enter Simulation Value
Select Simulation Status>>Press “Download
to device” icon
Disable SimulateMain Setup>>Human Interface>>
Simulation Status>>State>>
Select Disabled
Press “Download to device” icon
2-5
Rosemount 644
TRANSMITTER ONLINE
SETUP WITH DD OR DTM
Basic Transmitter Setup
Reference Manual
00809-0300-4728, Rev AA
January 2011
Table 2-5. Basic Transmitter
Configuration using DD or DTM
Using Guided Setup
Desired ActionMenu >> Category >> Method
Set Sensor TypeConfigure>>Guided Setup>>Configure Sensor Method
Set Connection Type Configure>>Guided Setup>>Configure Sensor Method
Set UnitsConfigure>>Guided Setup>>Configure Sensor Method
Set DampingConfigure>>Guided Setup>>Configure Sensor Method
Using Manual Setup
Desired ActionMenu >> Category >> Tab >> Value
Set Sensor TypeConfigure>>Manual Setup>>Sensor>>Sensor Type
Set Connection Type
(Number of Wires)
Set UnitsConfigure>>Manual Setup>>Classic
Set DampingConfigure>>Manual Setup>>Sensor>>Damping Value
Set Upper Range ValueConfigure>>Manual Setup>>Classic View>>Analog
Set Lower Range ValueConfigure>>Manual Setup>>Classic View>>Analog
NOTE
Changes made to the PRIMARY_VALUE_UNIT parameter through Manual
Setup>>Classic View are only reflected in the Transducer Block parameters.
To change the AI OUT units the PV Scale and OUT Scale need to be updated
to mirror the upper and lower sensor limits in the desired units.
2-6
Example: (All values are arbitrary)
The default configuration of the device is:
4-wire PT100_A_385AI.OUT = 23 °C
PRIMARY_VALUE_UNIT = °CPV_SCALE = 100, 0
PV.VALUE = 23 °COUT_SCALE = 100,0, °C
SV.VALUE = 23 °C
USL = 850 °C
LSL = -200 °C
If the user desires to change the units to °F, only the parameters in Bold will
change with the PRIMARY_VALUE_UNIT. The AI.OUT will stay in °C until the
PV_SCALE and OUT_SCALE are configured to match each other. (This can
be with the measurement range or the sensor limits.
4-wire PT100_A_385AI.OUT = 23 °C
PRIMARY_VALUE_UNIT = °CPV_SCALE = 212, 32
PV.VALUE = 73 °COUT_SCALE = 100,0, °C
SV.VALUE = 73 ° C
USL = 1562 °C
LSL = -328 °C
So the following change is needed:
PV_SCALE = 1562,-328 (make the same as USL and LSL)
OUT_SCALE = 1562,-328, °F (make the same as PV_SCALE)
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
Process AlarmsProcess Alarms can be set using a DD or DTM – see Table 2-6 for
configuration.
Table 2-6. Process Alarm
Configuration using DD or DTM
Desired ActionMenu Path
Enter Process Alert LevelsConfigure>>Alarm Setup>>LO-LO>>[Value]
LCD DisplayThe LCD display connects directly to the top of the transmitter puck and uses
a 10-pin connector to directly connect to the electronics board. A display
cover is provided to accommodate the display.
The display always indicates the transmitter output temperature as well as
abbreviated diagnostic status when applicable. When turned on, the display
will alternate between the selected variables.
For LCD display configuration using a DD or DTM see Table 2-7.
Table 2-7. LCD Display
Configuration using DD or DTM
OVERVIEWThe information in this section covers installation considerations for the
Rosemount 644. A Quick Installation Guide is shipped with every transmitter
to describe pipe-fitting, wiring procedures, and basic configuration for initial
installation.
SAFETY MESSAGESProcedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
raises potential safety issues is indicated by a warning symbol ( ). Refer to
the following safety messages before performing an operation preceded by
this symbol.
Warnings
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Please review
the approvals section of this reference manual for any restrictions associated with a safe
installation.
• In an Explosion-Proof/Flameproof installation, do not remove the transmitter
covers when power is applied to the unit.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
Electrical shock could cause death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present on
leads can cause electrical shock.
Individual transmitters are clearly marked with a tag indicating the approvals
they carry. Transmitters must be installed in accordance with all applicable
codes and standards to maintain these certified ratings. Refer to ““Hazardous
Locations Certificates” on page B-2 for information on these approvals.
www.rosemount.com
Reference Manual
Transmitter
Mounting
Hardware
Rail Clip
Transmitter
Mounting
Hardware
Rail Clip
00809-0300-4728, Rev AA
Rosemount 644
January 2011
MOUNTINGMount the transmitter at a high point in the conduit run to prevent moisture
from draining into the transmitter housing.
The 644 head mount installs
•In a connection head or universal head mounted directly on a sensor
assembly
•Apart from a sensor assembly using a universal head
•To a DIN rail using an optional mounting clip.
The 644 rail mount attaches directly to a wall or to a DIN rail.
Mounting a 644H to a DIN Rail
To attach a head mount transmitter to a DIN rail, assemble the appropriate rail
mounting kit (part number 00644-5301-0010) to the transmitter as shown in
Figure 3-1.
Figure 3-1. Assembling Rail Clip
Hardware to a 644
G-Rail (asymmetric)Top Hat Rail (symmetric)
Note: Kit includes Mounting Hardware and both types of Rail Kits.
Retrofitting a 644H for Use in an Existing Threaded Sensor Connection
Head
To mount a 644 in an existing threaded sensor connection head (former
option code L1), order the 644H retrofit kit (part number 00644-5321-0010).
The retrofit kit includes a new mounting bracket and all associated hardware
necessary to facilitate the installation of the 644H in the existing head. See
Figure 3-2.
3-2
Reference Manual
Kit includes
replacement bracket
and screws.
Existing Threaded Sensor Connection Head
(Former option code L1)
A
D
B
C
E
F
00809-0300-4728, Rev AA
January 2011
Figure 3-2. Assembling 644H for
Use in an Existing L1
Connection Head
INSTALLATION
Rosemount 644
Typical European
Installation
Head Mount Transmitter with DIN Plate Style Sensor
1.Attach the thermowell to the pipe or process container wall. Install
and tighten the thermowell before applying process pressure.
2.Assemble the transmitter to the sensor. Push the transmitter
mounting screws through the sensor mounting plate and insert the
snap rings (optional) into the transmitter mounting screw groove.
3.Wire the sensor to the transmitter (see Figure 4-3 on page 4-3).
4.Insert the transmitter-sensor assembly into the connection head.
Thread the transmitter mounting screw into the connection head
mounting holes. Assemble the extension to the connection head.
Insert the assembly into the thermowell.
5.Attach conduit or a cable gland to the open connection head entry.
6.Insert the shielded cable leads into the connection head through the
conduit or cable entry. Seal the entry properly.
7.Connect the shielded power cable leads to the transmitter power
terminals. Avoid contact with sensor leads and sensor connections.
8.Install and tighten the connection head cover. Enclosure covers must
be fully engaged to meet explosion-proof requirements.
A = 644H TransmitterD = Transmitter Mounting Screws
B = Connection HeadE = Integral Mount Sensor with Flying Leads
C = ThermowellF = Extension
3-3
Rosemount 644
A
B
C
D
E
Reference Manual
00809-0300-4728, Rev AA
January 2011
Typical North American
Installation
Head Mount Transmitter with Threaded Sensor
1.Attach the thermowell to the pipe or process container wall. Install
and tighten thermowells before applying process pressure.
2.Attach necessary extension nipples and adapters to the thermowell.
Seal the nipple and adapter threads with silicone tape.
3.Screw the sensor into the thermowell. Install drain seals if required for
severe environments or to satisfy code requirements.
4.Pull the sensor wiring leads through the universal head and
transmitter. Mount the transmitter in the universal head by threading
the transmitter mounting screws into the universal head mounting
holes.
5.Mount the transmitter-sensor assembly into the thermowell. Seal
adapter threads with silicone tape.
6.Install a cable gland or conduit for field wiring to the conduit entry of
the universal head. Seal threads with silicone tape.
7.Pull the field wiring leads through the conduit into the universal head.
Attach the sensor and power leads to the transmitter. Avoid contact
with other terminals.
8.Install and tighten the universal head cover. Enclosure covers must
be fully engaged to meet explosion-proof requirements.
3-4
A = Threaded ThermowellD = Universal Head
B = Threaded Style SensorE = Conduit Entry
C = Standard Extension
Reference Manual
644H
Captive Mounting Screws and Springs
Meter Spacer
LCD Display
10 pin Connector
00809-0300-4728, Rev AA
January 2011
Rosemount 644
LCD Display InstallationThe LCD display provides local indication of the transmitter output and
abbreviated diagnostic messages governing transmitter operation.
Transmitters ordered with the LCD display are shipped with the meter
installed. After-market installation requires the meter kit (part number
00644-4430-0001), which includes:
•LCD display assembly (includes LCD display, meter spacer,
and 2 screws)
•Meter cover with O-ring in place
Figure 3-3. Installing the LCD
Display
Use the following procedure to install the meter.
1.If the transmitter is installed in a loop, secure the loop and disconnect
the power. If the transmitter is installed in an enclosure, remove the
cover from the enclosure.
2.Decide meter orientation (the meter can be rotated in 90°
increments). To change meter orientation, remove the screws located
above and below the display screen. Lift the meter off the meter
spacer. Remove the 10-pin plug and re-insert it in the location that will
result in the desired viewing orientation.
3.Reattach the meter to the meter spacer using the screws. If the meter
was rotated 90° from its original position it will be necessary to
remove the screws from their original holes and re-insert them in the
adjacent screws holes.
4.Line up the 10-pin connector with the 10-pin socket and push the
meter into the transmitter until it snaps into place.
5.Attach and tighten the universal head cover. Enclosure covers must
be fully engaged to meet explosion-proof requirements.
6.Use a Profibus Class 2 master to configure the meter to the desired
display parameters.
NOTE
Observe the following LCD display temperature limits:
Operating: –4 to 185 °F (–20 to 85 °C)
Storage: –50 to 185 °F (–45 to 85 °C)
OVERVIEWThe information in this section covers installation considerations for the
Rosemount 644. A Quick Installation Guide is shipped with every transmitter
to describe pipe-fitting, wiring procedures, and basic configuration for initial
installation.
SAFETY MESSAGESProcedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or
serious injury.
• Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
• Do not remove the connection head cover in explosive atmospheres when the
circuit is live.
• Before powering Profibus devices segment in an explosive atmosphere, make sure
the instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
• Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
• All connection head covers must be fully engaged to meet
explosion-proof requirements.
Process leaks could result in death or serious injury.
• Do not remove the thermowell while in operation.
• Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
www.rosemount.com
Reference Manual
1 2 3 4
Sensor
Terminals
Communication
Terminals
Power Terminals
00809-0300-4728, Rev AA
Rosemount 644
January 2011
WIRINGAll power to the transmitter is supplied over the signal wiring. Use ordinary
copper wire of sufficient size to ensure that the voltage across the transmitter
power terminals does not drop below 9 Vdc for Profibus PA. If the sensor is
installed in a high-voltage environment and a fault condition or installation
error occurs, the sensor leads and transmitter terminals could carry lethal
voltages. Use extreme caution when making contact with the leads and
terminals.
NOTE
Do not apply high voltage (e.g., ac line voltage) to the transmitter terminals.
Abnormally high voltage can damage the unit. (Sensor and transmitter power
terminals are rated to 42.4 Vdc. A constant 42.4 volts across the sensor
terminals may damage the unit.)
The transmitters will accept inputs from a variety of RTD and thermocouple
types. Refer to Figure 4-1 when making sensor connections. Refer to
Figure 4-2 for Profibus installations.
Use the following steps to wire the power and sensor to the transmitter:
1.Connect the positive power lead to the .+. terminal. Connect the
negative power lead to the .-. terminal.
2.Tighten the terminal screws. When tightening the sensor and power
wires, the max torque is 6-in.-lbs (0.7 N-m).
3.Apply power.
Figure 4-1. Transmitter Power,
Communication and Sensor
Te rm i na l
644H
4-2
Reference Manual
Profibus DP
Profibus PA
MBP-IS at 31.25KBd
Terminator
6234 ft (1900m) max
(Depending on cable characteristics)
DP/PA
Coupler
PROFIBUS
Class 2
Master
(Configurati
on Tool)
RS-485 up to 12 MBD
Profibus Transmitter
Power/
Signal
Wiring
2-wire
RTD and
3-wire RTD
and
4-wire RTD
and
T/C
and mV
*
1234
1234
1234
1234
00809-0300-4728, Rev AA
January 2011
Figure 4-2. Typical connection of
a Profibus configuration host to
a transmitter loop
Rosemount 644
NOTE
1.Each Segment in a Profibus trunk must be terminated at both ends.
2.Some DP/PA couplers contain the power supply, one terminator, and
the power conditioner within the coupling device.
3.The configuration tool is typically located in the control room.
Sensor ConnectionsThe 644 is compatible with a number of RTD and thermocouple sensor types.
Figure 4-3 shows the correct input connections to the sensor terminals on the
transmitter. To ensure a proper sensor connection, anchor the sensor lead
wires into the appropriate compression terminals and tighten the screws.
Figure 4-3. Sensor Wiring
Diagrams
* Emerson Process Management provides 4-wire sensors for all single element RTDs. Use these
RTDs in 3-wire configurations by leaving the unneeded leads disconnected and insulated with electrical
tape.
Thermocouple or Millivolt Inputs
The thermocouple can be connected directly to the transmitter. Use
appropriate thermocouple extension wire if mounting the transmitter remotely
from the sensor. Make millivolt input connections with copper wire. Use
shielding for long runs of wire.
The transmitters will accept a variety of RTD configurations, including 2-wire,
3-wire, and 4-wire. If the transmitter is mounted remotely from a 3-wire or
4-wire RTD, it will operate within specifications, without recalibration, for lead
wire resistances of up to 60 ohms per lead (equivalent to 6,000 feet of
20 AWG wire). In this case, the leads between the RTD and transmitter
should be shielded. If using only two leads, both RTD leads are in series with
the sensor element, so significant errors can occur if the lead lengths exceed
three feet of 20 AWG wire (approximately 0.05 °C/ft). For longer runs, attach a
third or fourth lead as described above.
Sensor Lead Wire Resistance Effect– RTD Input
When using a 4-wire RTD, the effect of lead resistance is eliminated and has
no impact on accuracy. However, a 3-wire sensor will not fully cancel lead
resistance error because it cannot compensate for imbalances in resistance
between the lead wires. Using the same type of wire on all three lead wires
will make a 3-wire RTD installation as accurate as possible. A 2-wire sensor
will produce the largest error because it directly adds the lead wire resistance
to the sensor resistance. For 2- and 3-wire RTDs, an additional lead wire
resistance error is induced with ambient temperature variations. The table and
the examples shown below help quantify these errors.
Table 4-1. Examples of
Approximate Basic Error
Sensor InputApproximate Basic Error
4-wire RTDNone (independent of lead wire resistance)
3-wire RTD± 1.0 in reading per ohm of unbalanced lead wire
resistance (Unbalanced lead wire resistance =
maximum imbalance between any two leads.)
2-wire RTD1.0 in reading per ohm of lead wire resistance
Examples of Approximate Lead Wire Resistance Effect Calculations
Given:
Total cable length:150 m
Imbalance of the lead wires at 20 °C:1.5
Resistance/length (18 AWG Cu):0.025 /m °C
Temperature coefficient of Cu (Cu):0.039 / °C
Temperature coefficient of Pt(Pt):0.00385 / °C
Change in Ambient Temperature (T
):25 °C
amb
RTD Resistance at 0 °C (Ro):100 (for Pt 100 RTD)
•Pt100 4-wire RTD: No lead wire resistance effect.
Lead wire imbalance seen by the transmitter = 0.5
•Pt100 2-wire RTD:
Lead wire resistance seen by the transmitter = 150 m × 2 wires ×
0.025
/m = 7.5
Profibus PA Installation
Powered over Profibus PA with standard Profibus power supplies; the
transmitter operates between 9.0 and 32.0 Vdc, 11 mA maximum. Transmitter
power terminals are rated to 42.4 Vdc. The power terminals on the 644 with
Profibus are polarity insensitive.
Ground the TransmitterThe transmitter will operate with the current signal loop either floating or
grounded. However, the extra noise in floating systems affects many types of
readout devices. If the signal appears noisy or erratic, grounding the current
signal loop at a single point may solve the problem. The best place to ground
the loop is at the negative terminal of the power supply. Do not ground the
current signal loop at more than one point.
The transmitter is electrically isolated to 500 Vdc/ac rms (707 Vdc), so the
input circuit may also be grounded at any single point. When using a
grounded thermocouple, the grounded junction serves as this point.
Neither side of the loop should be grounded on Profibus PA devices. Only the
shield wire should be grounded.
NOTE
Do not ground the signal wire at both ends.
Ungrounded Thermocouple, mV, and RTD/Ohm Inputs
Each process installation has different requirements for grounding. Use the
grounding options recommended by the facility for the specific sensor type, or
begin with grounding Option 1 (the most common).
4-5
Rosemount 644
Sensor Wires
Profibus PA segment
Shield ground point
Connect shields together, electrically isolated from the transmitter.
Transmitter
Sensor Wires
Shield ground point
Transmitter
Profibus PA segment
Sensor Wires
Shield ground point
Transmitter
Profibus PA segment
Reference Manual
00809-0300-4728, Rev AA
January 2011
Option 1:
1.Connect signal wiring shield to the sensor wiring shield.
2.Ensure the two shields are tied together and electrically isolated from
the transmitter housing.
3.Ground shield at the power supply end only.
4.Ensure that the sensor shield is electrically isolated from the
surrounding grounded fixtures.
Option 2:
1.Connect sensor wiring shield to the transmitter housing (only if the
housing is grounded).
2.Ensure the sensor shield is electrically isolated from surrounding
fixtures that may be grounded.
3.Ground signal wiring shield at the power supply end.
Option 3:
1.Ground sensor wiring shield at the sensor, if possible.
2.Ensure that the sensor wiring and signal wiring shields are electrically
isolated from the transmitter housing.
3.Do not connect the signal wiring shield to the sensor wiring shield.
4.Ground signal wiring shield at the power supply end.
4-6
Reference Manual
Sensor Wires
Shield ground point
Transmitter
Profibus PA segment
00809-0300-4728, Rev AA
January 2011
Rosemount 644
Grounded Thermocouple Inputs
1.Ground sensor wiring shield at the sensor.
2.Ensure that the sensor wiring and signal wiring shields are electrically
isolated from the transmitter housing.
3.Do not connect the signal wiring shield to the sensor wiring shield.
4.Ground signal wiring shield at the power supply end.
OVERVIEWThis section contains information on calibrating the Rosemount 644 Profibus
Temperature Transmitter using either the Local Operator Interface (LOI) or a
class two master.
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or
serious injury.
• Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
• Do not remove the connection head cover in explosive atmospheres when the
circuit is live.
• Before connecting Profibus devices in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or
non-intrinsic field wiring practices.
• Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
• All connection head covers must be fully engaged to meet
explosion-proof requirements.
Process leaks could result in death or serious injury.
• Do not remove the thermowell while in operation.
• Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
www.rosemount.com
00809-0300-4728, Rev AA
Rosemount 644
Sensor Transducer BlockSensor Calibration, Lower and Upper Trim Methods
In order to calibrate the transmitter, run the Lower and Upper Trim Methods. If
your system does not support methods, manually configure the Transducer
Block parameters listed below.
1.Set TARGET_MODE to OOS
2.Set SENSOR_CAL_METHOD to User Trim
3.Set CAL_UNIT to supported engineering units in the Transducer
Block
4.Apply temperature that corresponds to the lower calibration point and
allow the temperature to stabilize. The temperature must be between
the range limits defined in PRIMRY_VALUE_RANGE.
5.Set values of CAL_POINT_LO to correspond to the temperature
applied by the sensor.
6.Set SENSOR_CAL_METHOD to User Trim
7.Apply temperature, temperature corresponding to the upper
calibration
8.Allow temperature to stabilize.
9.Set CAL_POINT_HI
Reference Manual
January 2011
NOTE
CAL_POINT_HI must be less than UPPER_SENSOR_LIMIT and greater
than CAL_POINT_LO + CAL_MIN_SPAN
10. Set SENSOR_CAL_DATE to the current date.
11. Set SENSOR_CAL_WHO to the person responsible for the
calibration.
12. Set SENSOR _CAL_LOC to the calibration location.
13. Set TARGET_MODE to AUTO
NOTE
If trim fails the transmitter will automatically revert to factory trim. Excessive
correction or sensor failure could cause device status to read “calibration
error”. To clear this, trim the transmitter.
Recall Factory Trim
To recall a factory trim on the transmitter, run the Recall Factory Trim. If your
system does not support methods, manually configure the Transducer Block
parameters listed below.
1.Set TARGET_MODE to OOS
2.Set SENSOR_CAL_METHOD to Factory Trim.
3.Set SENSOR_CAL_DATE to the current date.
4.Set SENSOR_CAL_WHO to the person responsible for the
calibration.
5.Set SENSOR _CAL_LOC to the calibration location.
6.Set TARGET_MODE to AUTO.
5-2
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
NOTE
When sensor type is changed, the transmitter reverts to the factory trim.
Changing sensor type causes you to loose any trim performed on the
transmitter.
Alert Messages and Fail Safe Type Selection . . . . . . . . .page 6-6
OVERVIEWThis section contains information on how to troubleshoot the Rosemount 644
Profibus Pressure Transmitter.
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or
serious injury.
• Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
• Do not remove the connection head cover in explosive atmospheres when the
circuit is live.
• Before connecting Profibus devices in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or
non-intrinsic field wiring practices.
• Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
• All connection head covers must be fully engaged to meet
explosion-proof requirements.
Process leaks could result in death or serious injury.
• Do not remove the thermowell while in operation.
• Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
www.rosemount.com
Rosemount 644
Reference Manual
00809-0300-4728, Rev AA
January 2011
DIAGNOSTICS
IDENTIFICATION AND
RECOMMENDATION
The Rosemount 644 Profibus device diagnostics can be used to warn a user
about a potential transmitter error. There is a transmitter error if the Output
Status reads anything but Good or Good - Function Check, or the LCD reads ERROR SENSOR or ERROR DEVICE. Use Table 6-1 to identify what
Diagnostic Condition exists based on the combination of errors under the
Physical Block Diagnostic Extension and PV Status columns. Once the
condition is identified, use the Recommended Actions column to remedy the
Integrity Error
NV memory integrity
Error
ROM integrity error
NA
(PV Status unchanged)
More Diagnosis Available,
Not Limited
BAD, Maintenance Alarm,
More Diagnosis Available,
Not Limited
BAD, Maintenance Alarm,
More Diagnosis Available,
Not Limited
BAD, Maintenance Alarm,
More Diagnosis Available,
Not Limited
1. Independently measure the ambient temperature of the
transmitter's environment.
2. If the ambient temperature is above the transmitter's
operating range, modify the installation to correct the
ambient temperature.
3. If the ambient temperature is within the transmitter's
operating range, replace the transmitter.
1. Revert to Factory Calibration.
2. Re-calibrate the device. Make sure the user entered
calibration points are close to the applied calibration
temperature.
1. Restart the processor.
2. If the condition persists, replace the electronics or the
transmitter.
1. If possible, revert to the previous software revision.
2. Contact a Service Center and verify the transmitter
information using the Show Transmitter Information
button.
1. Restart the processor.
2. If the error persists, download the transmitter
configuration.
3. If the error persists, replace the electronics or the
transmitter.
6-2
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
Diagnostics
Sensor FailureSensor Open
Sensor Beyond Operating
Limits
Terminal Temperature
Failure
Terminal Temperature
Beyond Operating Limits
Physical Block
Diagnostic Extension
Sensor Shorted
Sensor Beyond
Operating Limits
Terminal Temperature
Failure
Terminal Temperature
Beyond Operating
Limits
PV StatusRecommended Actions
BAD, Maintenance Alarm,
More Diagnosis Available,
Not Limited
BAD, Maintenance Alarm,
More Diagnosis Available,
Lo / Hi Limited
BAD, Maintenance Alarm,
More Diagnosis Available,
Not Limited
UNCERTAIN, Process
Related, No Maintenance,
Not Limited
1. Verify the sensor configuration.
2. If the error persists, verify the sensor connection and
wiring. Refer to the device and sensor wiring diagrams
to ensure proper wiring.
3. If the error persists, verify the integrity of the sensor
and sensor lead wires. If the sensor is faulty, repair or
replace the sensor.
1. Verify the process temperature is within the specified
sensor type's range.
2. If the error persists, verify the sensor connection and
wiring. Refer to the device and sensor wiring diagrams
to ensure proper wiring.
3. If the error persists, verify the integrity of the sensor
and sensor lead wires. If the sensor is faulty, repair or
replace the sensor.
1. Verify the temperature of the transmitter's ambient
environment is within the transmitter's specified
operating limits. Refer to the product manual for the
transmitter's operating limits.
2. If the ambient temperature is within the specified
operating limits, replace the transmitter.
1. Verify the temperature of the transmitter's ambient
environment is within the transmitter's specified
operating limits. Refer to the product manual for the
transmitter's operating limits.
2. If the ambient temperature is within the specified
operating limits, replace the transmitter.
6-3
Rosemount 644
Standard Diagnosc Response
6 Bytes
Extended Diagnosc Data
Device Related
Header ByteStatus, Slot Number,
Status Specifier
DiagnosisExtended Diagnosis
(Vendor Specific)
0 0 x x x x x x3 Bytes4 Bytes3 Bytes
Extended Diagnosis
76543210
6362616059585756
Byte 1
Byte 2
Unit_Diag_Bit
Bit
76543210
7170696867666564
76543210
7978777675747372
Byte 3
76543210
3130292827262524
Diagnosis
Byte 1 Byte 2
76543210
3938373635343332
76543210
5554535251504948
76543210
4746454443424140
Byte 3Byte 4
Unit_Diag_Bit
Bit
1
1
Reference Manual
00809-0300-4728, Rev AA
January 2011
Extended Diagnostics
Identification with class
one master
Figure 6-1. Extended
Diagnostics Identification
Figure 6-2. Diagnoses and
Extended Diagnoses Bit
Identification
If using a class one master to identify Physical Block Diagnostic Extensions,
see Figure 6-1 and Figure 6-2 for diagnostic bit information. Table 6-1 and
Table 6-2 list the diagnostic description for each bit.
NOTE
A class two master will automatically decode bits and provide diagnostic
names.
6-4
Reference Manual
00809-0300-4728, Rev AA
January 2011
Table 6-1. Diagnosis
Descriptions
Device Related Diagnosis
Byte-BitUnit_Diag_Bit
2-335Restart
2-436Cold Start
2-537Maintenance Required
2-739Ident_Number violation
3-040Failure of the device
3-141Maintenance demanded
3-242Function Check
3-343Process not returning valid values
4-755Extension Available
(1) Unit_Diag_Bit located in GSD file
(1)
Diagnostic Description
Rosemount 644
Table 6-2. Extended Diagnosis
Descriptions
Extension Byte-Bit
6-096Invalid Configuration
6-197ASIC RCV Error
6-298ASIC TX Error
6-399ASIC Interrupt Error
6-4100Reference Error
6-5101ASIC Configuration Error
6-6102Sensor Open
6-7103Sensor Shorted
5-088Terminal Temperature Failure
5-189Sensor out of Operating Range
5-290Sensor Beyond Operating Limits
5-391Terminal Temperature Out of Operating Range
5-492Terminal Temperature Out of Operating Limits
5-593Sensor Degraded
5-694Calibration Error
5-795Manufacturing Block Integrity Error
4-080Hardware/Software Incompatible
4-181Non-Volatile Memory Integrity Error
4-282ROM Integrity Error
(1) Unit_Diag_Bit located in GSD file
(1)
Diagnostic
Byte-BitUnit_Diag_Bit
(1)
Diagnostic Description
6-5
Rosemount 644
Reference Manual
00809-0300-4728, Rev AA
January 2011
PLANTWEB AND NE107
DIAGNOSTICS
Table 6-3. Output Status
ALERT MESSAGES AND
FAIL SAFE TYPE
SELECTION
Table 6-3 describes the recommended status of each diagnostic condition
based on PlantWeb and Namur NE107 recommendations.
NamePlantWeb Alert Category NE107 Category
PV Simulation Enabled AdvisoryCheck
AI in Manual Mode AdvisoryCheck
Sensor Out of Operating Range Maintenance Out of spec
Sensor Degraded Maintenance Out of spec
Terminal Temperature Out of Operating
Table 6-4 defines the output status and LCD messages that will be driven by a
diagnostic condition. This table can be used to determine what type of fail
safe value setting is preferred. Fail safe type can be set with a class two
master under fail safe >> fail safe mode.
Table 6-4. Alert Messages
Diagnostic
FSAFE_TYPE 0
(Failsafe Value)
Configuration Error75 - Uncertain, Substitute
set, Constant
Electronics Failure75 - Uncertain, Substitute
set, Constant
Primary Value Failure Sensor is Open
Primary Value Failure Sensor is Shorted
Primary Value Degraded Sensor Out of Operating
Range
Primary Value Failure Sensor Beyond Operating
Limits
Primary Value Degraded Sensor Degraded
Terminal Temperature Failure 75 - Uncertain, Substitute
Terminal Temperature Out of
Operating Range
75 - Uncertain, Substitute
set, Constant
75 - Uncertain, Substitute
set, Constant
120 - UNCERTAIN,
Process Related, No
Maintenance, Not Limited
75 - Uncertain, Substitute
set, Constant
120 - UNCERTAIN,
Process Related, No
Maintenance, Not Limited
set, Constant
NA
(Status unchanged)
Output Status
(based on Fail Safe Type)
FSAFE_TYPE 1
(Last usable Value)
75 - Uncertain, Substitute
set, Constant
75 - Uncertain, Substitute
set, Constant
75 - Uncertain, Substitute
set, Constant
75 - Uncertain, Substitute
set, Constant
120 - UNCERTAIN,
Process Related, No
Maintenance, Not Limited
75 - Uncertain, Substitute
set, Constant
120 - UNCERTAIN,
Process Related, No
Maintenance, Not Limited
75 - Uncertain, Substitute
set, Constant
NA
(Status unchanged)
FSAFE_TYPE 2
(Wrong calculated Value)
36 - BAD, Maintenance
Alarm, Not Limited
36 - BAD, Maintenance
Alarm, Not Limited
36 - BAD, Maintenance
Alarm, Not Limited
36 - BAD, Maintenance
Alarm, Not Limited
120 - UNCERTAIN, Process
Related, No Maintenance,
Not Limited
37 or 38 - BAD, Maintenance
Alarm, Lo / Hi Limited
120 - UNCERTAIN, Process
Related, No Maintenance,
Not Limited
36 - BAD, Maintenance
Alarm, Not Limited
NA
(Status unchanged)
LCD Output
“ERROR SENSOR”
“ERROR DEVICE”
“ERROR SENSOR”
“ERROR SENSOR”
N/A
“ERROR SENSOR”
“ERROR SENSOR”
“ERROR DEVICE”
N/A
6-6
Reference Manual
00809-0300-4728, Rev AA
January 2011
Diagnostic
Terminal Temperature
Beyond Operating Limits
Calibration Error75 - Uncertain, Substitute
Memory Failure75 - Uncertain, Substitute
Table 6-5. Output Status Bit
Definition
120 - UNCERTAIN,
Process Related, No
Maintenance, Not Limited
set, Constant
set, Constant
Bad - passivated 0x2335
Bad, maintenance alarm, more diagnostics
available
Bad, process related - no maintenance 0x2840
Uncertain, substitute set0x4B75
Uncertain, process related, no maintenance0x78120
Good, ok 0x80128
Good, update event0x84132
Good, advisory alarm, low limit 0x89137
Good, advisory alarm, high limit 0x8A138
Good, critical alarm, low limit 0x8D141
Good, critical alarm, high limit 0x8E142
Good, function check 0xBC188
Rosemount 644
Output Status
(based on Fail Safe Type)
120 - UNCERTAIN,
Process Related, No
Maintenance, Not Limited
75 - Uncertain, Substitute
set, Constant
75 - Uncertain, Substitute
set, Constant
Condensed StatusAI Block OUT Status Parameter
DescriptionHEXDECIMAL
120 - UNCERTAIN, Process
Related, No Maintenance,
Not Limited
User-selectable; sensor terminals rated to 42.4 Vdc. See “Accuracy” on
page A-5 for sensor options.
Output
Single 2-wired device with digital output with Profibus PA (compliant with
profile 3.02).
Isolation
Input/output isolation tested to 620 Vac (880 Vdc) at 50/60 Hz for 2 seconds
minimum.
Local Display
The optional five-digit integral LCD Display includes a floating or fixed decimal
point. It can also display engineering units (°F, °C, °R, K, , and millivolts),
milliampere, and percent of span. The display can be configured to alternate
between selected display options. Display settings are preconfigured at the
factory according to the standard transmitter configuration. They can be
reconfigured in the field using a Profibus Class 2 master.
Humidity Limits
0–99% relative humidity
Update Time
0.5 seconds
www.rosemount.com
Rosemount 644
Physical Electrical Connections
ModelPower and Sensor Terminals
644HCompression screws permanently fixed to terminal block
Materials of Constructions (Stainless Steel Housing for Biotechnology,
Pharmaceutical Industries, and Sanitary Applications)
Housing and Standard Meter Cover
• 316 SST
Cover O-Ring
• Buna-N
®
glass reinforced
Reference Manual
00809-0300-4728, Rev AA
January 2011
Mounting
The 644H installs in a connection head or universal head mounted directly on
a sensor assembly, apart from a sensor assembly using a universal head, or
to a DIN rail using an optional mounting clip.
Weight
CodeOptionsWeight
644HProfibus Head Mount Transmitter92 g (3.25 oz)
M5LCD Display38 g (1.34 oz)
J5, J6Universal Head, Standard Cover577 g (20.35 oz)
J5, J6Universal Head, Meter Cover667 g (23.53 oz)
Weight (Stainless Steel Housing for Biotechnology, Pharmaceutical
Industries, and Sanitary Applications)
Option Code Standard CoverMeter Cover
S1840 g (27 oz)995 g (32 oz)
S2840 g (27 oz)995 g (32 oz)
S3840 g (27 oz)995 g (32 oz)
S4840 g (27 oz)995 g (32 oz)
Enclosure Ratings (644H)
All option codes (S1, S2, S3, S4, J5, J6, J7, and J8) are NEMA 4X, IP66,
and IP68. Option code J6 is CSA Enclosure Type 4X.
Sanitary Housing Surface
Surface finish is polished to 32 RMA. Laser etched product marking on
housing and standard covers.
A-2
Reference Manual
2-wire
RTD and
3-wire RTD
and
4-wire RTD
and
T/C
and mV
*
1234
12 34
1234
1234
00809-0300-4728, Rev AA
January 2011
Performance CE Mark
The 644 meets all requirements listed under IEC 61326: Amendment 1, 1998.
Power Supply Effect
Less than ±0.005% of span per volt
Stability
RTDs and thermocouples have a stability of ±0.15% of output reading or 0.15
°C (whichever is greater) for 24 months
Vibration Effect
The 644 is tested to the following specifications with no effect
on performance:
FrequencyVibration
10 to 60 Hz0.21 mm displacement
60 to 500 Hz3 g peak acceleration
Sensor Connections
Rosemount 644
* Rosemount Inc. provides 4-wire sensors for all single element R TDs. You can use these RTDsin3-wire
configurations by leaving the unneeded leads disconnected and insulated withelectrical tape.
Function BlocksPhysical Block
• The Physical Block contains physical transmitter information including
manufacturer identification, device type, software tag, and unique
identification.
Transducer Block
• The Transducer Block contains the actual temperature measurement data,
including sensor 1 and terminal temperature. It includes information about
sensor type and configuration, engineering units, linearization, re-ranging,
damping, temperature correction, and diagnostics.
Analog Input Block (AI)
• The Analog Input Block processes the measurement and makes it
available on the Profibus segment. Allows filtering, alarming, and
engineering unit changes.
644 Sensor Connections Diagram
Turn on time
Performance within specifications in less than 20 seconds after power is
applied, when damping value is set to 0 seconds.
A-3
Rosemount 644
Reference Manual
00809-0300-4728, Rev AA
January 2011
Power Supply
Powered over Profibus with standard fieldbus power supplies. The transmitter
operates between 9.0 and 32.0 Vdc,12 mA maximum. The power terminals
are rated to 42.4 Vdc (max.)
Alarms
The AI function block allows the user to configure the alarms to HI-HI, HI, LO,
or LO-LO with hysteresis settings.
A-4
Reference Manual
00809-0300-4728, Rev AA
January 2011
Accuracy
Table A-1. Rosemount 644 Input Options and Accuracy.
Sensor
Options
2-, 3-, 4-wire RTDs°C°F°C°F°C°F
Pt 100 ( = 0.00385)IEC 751–200 to 850–328 to 15621018± 0.15± 0.27±0.03% of span
Pt 200 ( = 0.00385)IEC 751–200 to 850–328 to 15621018± 0.15 ± 0.27 ±0.03% of span
Pt 500 ( = 0.00385)IEC 751–200 to 850–328 to 15621018± 0.19± 0.34±0.03% of span
Pt 1000 ( = 0.00385)IEC 751–200 to 300–328 to 5721018± 0.19± 0.34±0.03% of span
Pt 100 ( = 0.003916)JIS 1604–200 to 645–328 to 11931018± 0.15± 0.27±0.03% of span
Pt 200 ( = 0.003916)JIS 1604–200 to 645–328 to 11931018± 0.27± 0.49±0.03% of span
Ni 120Edison Curve No. 7–70 to 300–94 to 5721018± 0.15± 0.27±0.03% of span
Cu 10Edison Copper Winding No. 15–50 to 250–58 to 4821018±1.40± 2.52±0.03% of span
Pt 50 ( = 0.00391)GOST 6651-94–200 to 550–328 to 10221018± 0.30± 0.54±0.03% of span
Pt 100 ( = 0.00391)GOST 6651-94–200 to 550–328 to 10221018± 0.15± 0.27±0.03% of span
Cu 50 ( = 0.00426)GOST 6651-94–50 to 200–58 to 3921018±1.34± 2.41±0.03% of span
Cu 10 ( = 0.00428)GOST 6651-94–185 to 200–301 to 3921018±1.34± 2.41±0.03% of span
Cu 10 ( = 0.00426)GOST 6651-94–50 to 200–58 to 3921018±0.67± 1.20±0.03% of span
Cu 10 ( = 0.00428)GOST 6651-94–185 to 200–301 to 3921018±0.67± 1.20±0.03% of span
Thermocouples
(5)
Type B
(4)
NIST Monograph 175, IEC 584100 to 1820212 to 33082545± 0.77± 1.39±0.03% of span
Type ENIST Monograph 175, IEC 584–50 to 1000–58 to 18322545± 0.20± 0.36±0.03% of span
Type JNIST Monograph 175, IEC 584–180 to 760–292 to 14002545± 0.35± 0.63±0.03% of span
(6)
Type K
NIST Monograph 175, IEC 584–180 to 1372–292 to 25012545± 0.50± 0.90±0.03% of span
Type NNIST Monograph 175, IEC 584–200 to 1300–328 to 23722545± 0.50± 0.90±0.03% of span
Type RNIST Monograph 175, IEC 5840 to 176832 to 32142545± 0.75± 1.35±0.03% of span
(1) No minimum or maximum span restrictions within the input ranges. Recommended minimum span will hold noise within accuracy specification with damping at zero
seconds.
(2) The published digital accuracy applies over the entire sensor input range. Di gital output can be accessed by Prof ibus Communications or Rosemount control system.
(3) Total Analog accuracy is the sum of digital and D/A accuracies. This is not applicable for FOUNDATION fieldbus.
(4) Total digital accuracy for thermocouple measurement: sum of digital accuracy +0.5 °C. (cold juncti on accuracy).
(5) Digital accuracy for NIST Type B T/C is ±3.0 °C (±5.4 °F) from 100 to 300 °C (212 to 572 °F).
(6) Digital accuracy for NIST Type K T/C is ±0.70 °C (±1.26 °F) from –180 to –90 °C (–292 to –130 °F).
Sensor
Reference
Input
Ranges
Recommended
Min. Span
Rosemount 644
(1)
Digital
Accuracy
(2)
Accuracy
D/A
(3)
A-5
Reference Manual
00809-0300-4728, Rev AA
Rosemount 644
Ambient Temperature Effect
Temperature Effects per 1.0 °C
Input Range
Sensor OptionsSensor Reference
2-, 3-, 4-wire RTDs
Pt 100 ( = 0.00385)IEC 751-200 to 8500.003 °C (0.0054 °F)Entire Sensor Input Range
Pt 200 ( = 0.00385)IEC 751-200 to 8500.004 °C (0.0072 °F)Entire Sensor Input Range
Pt 500 ( = 0.00385)IEC 751-200 to 8500.003 °C (0.0054 °F)Entire Sensor Input Range
Pt 1000 ( = 0.00385)IEC 751-200 to 3000.003 °C (0.0054 °F)Entire Sensor Input Range
Pt 100 ( = 0.003916)JIS 1604-200 to 6450.003 °C (0.0054 °F)Entire Sensor Input Range
Pt 200 ( = 0.003916)JIS 1604-200 to 6450.004 °C (0.0072 °F)Entire Sensor Input Range
Ni 120Edison Curve No. 7-70 to 3000.003 °C (0.0054 °F)Entire Sensor Input Range
Cu 10Edison Copper Winding No. 15-50 to 2500.03 °C (0.054 °F)Entire Sensor Input Range
Pt 50 ( = 0.00391)GOST 6651-94-200 to 5500.004 °C (0.0072 °F)Entire Sensor Input Range
Pt 100 ( = 0.00391)GOST 6651-94-200 to 5500.003 °C (0.0054 °F)Entire Sensor Input Range
Cu 50 ( = 0.00426)GOST 6651-94-50 to 2000.008 °C (0.0144 °F)Entire Sensor Input Range
Cu 50 ( = 0.00428)GOST 6651-94-185 to 2000.008 °C (0.0144 °F)Entire Sensor Input Range
Cu 100 ( = 0.00426)GOST 6651-94-50 to 2000.004 °C (0.0072 °F)Entire Sensor Input Range
Cu 100 ( = 0.00428)GOST 6651-94-185 to 2000.004 °C (0.0072 °F)Entire Sensor Input Range
Thermocouples
Type BNIST Monograph 175, IEC 584100 to 1820
Type ENIST Monograph 175, IEC 584-50 to 10000.005 °C + (0.0043% of T)All
Type JNIST Monograph 175, IEC 584-180 to 760
Type KNIST Monograph 175, IEC 584-180 to 1372
Type NNIST Monograph 175, IEC 584-200 to 13000.0068 °C + (0.00036% of T)All
Type RNIST Monograph 175, IEC 5840 to 1768
Type SNIST Monograph 175, IEC 5840 to 1768
Type TNIST Monograph 175, IEC 584-200 to 400
DIN Type LDIN 43710-200 to 900
DIN Type UDIN 43710-200 to 900
Type W5Re/W26ReASTM E 988-960 to 2000
GOST Type LGOST R 8.585-2001-200 to 800
Other Input Types
Millivolt Input-10 to 100 mV 0.0005 mVEntire Sensor Input Range
2-, 3-, 4-wire Ohm0 to 2000 0.0084 Entire Sensor Input Range
(1) Change in ambient is with reference to the calibration temperature of the tr ansmitter 68 °F (20 °C) from factory.
(°C)
Transmitters can be installed in locations where the ambient temperature is between –40 and 85 °C (–40 and 185
°F). In order to maintain excellent accuracy performance, each transmitter is individually characterized over this
ambient temperature range at the factory.
A-6
(1.8 °F) Change in Ambient
Temperature
0.014 °CT 1000 °C
0.032 °C – (0.0025% of (T –
300))
0.054 °C – (0.011% of (T – 100)) 100 °C T < 300 °C
0.0054 °C + (0.00029%of T)T 0 °C
0.0054 °C + (0.0025% of
absolute value T)
0.0061 °C + (0.0054% of T)T 0 °C
0.0061 °C + (0.0025% of
absolute value T)
0.016 °CT 200 °C
0.023 °C – (0.0036% of T)T < 200 °C
0.016 °CT 200 °C
0.023 °C – (0.0036% of T)T < 200 °C
0.0064 °CT 0 °C
0.0064 °C +(0.0043% of
absolute value T)
0.0054 °C + (0.00029% of T)T 0 °C
0.0054 °C + (0.0025% of
absolute value T)
0.0064 °CT 0 °C
0.0064 °C + (0.0043% of
absolute value T)
0.016 °CT 200 °C
0.023 °C – (0.0036% of T)T < 200 °C
0.007 °CT 0 °C
0.007 °C – (0.003% of absolute
value T)
(1)
Range
300 °C T < 1000 °C
T < 0 °C
T < 0 °C
T < 0 °C
T < 0 °C
T < 0 °C
T < 0 °C
January 2011
Reference Manual
Simulation Switch
Standard
Sensor
Terminals
Communication
Terminals
60 (2.4)
33
(1.3)
Power
Terminals
33 (1.30)
24 (1.0)
Meter
Connector
95 (3.74)
96 (3.76)
112 (4.41)
Meter Cover
316 SST “U”
Bolt Mounting,
2-inch Pipe
75
(2.93)
Label
Standard
Cover
LCD
Display
103 (4.03) with LCD
Display
78 (3.07)
128 (5.04)
with LCD
Display
100
(3.93)
104
(4.09)
00809-0300-4728, Rev AA
January 2011
DIMENSIONAL DRAWINGS
Shown with Standard Compression Screw Terminals
Rosemount 644
644H (DIN A Head Mount)
Threaded-Sensor Universal Head
(Option code J5, J6, J7 or J8)
Note: A “U” Bolt is shipped with each universal head unless assembly
option XA is ordered. Since the head is integrally mounted to the sensor, it
may not need to be used.
Dimensions are in millimeters (inches)
Integral DIN Style Sensor
Connection Head (see Sensor PDS for
ordering options)
Note: If ordering the transmitter with a DIN style sensor, it is required that
the enclosure be ordered within the Sensor Model (Product Data Sheet
doc # 00813-0200-2654) rather tha n within the transmitter model, this is in
order to drive necessary parts.
A-7
Rosemount 644
644H
Captive Mounting
Screws and Springs
Meter Spacer
LCD Display
10 pin Connector
G-Rail
Grooves
Top Hat Rail
Grooves
Screw Holes
for Mounting
to a Wall
Transmitter
Mounting
Hardware
Rail Clip
Transmitter
Mounting
Hardware
Rail Clip
Kit includes replacement
bracket and screws.
Existing Threaded Sensor
Connection Head
(former option code L1)
644R Rail & Walls Clips644H Rail Clips
Reference Manual
00809-0300-4728, Rev AA
January 2011
644H with LCD Display
Mounting Kits for 644H
G-Rail (asymmetric)Top Hat Rail (symmetric)
Note: Kit (part number 00644-5321-0010) includes a new mounting bracket and the hardware necessary to facilitate the installation.
A-8
Note: Kit (part number 00644-5301-0010) includes
mounting hardware and both types of rail kits.
644H Retrofit Kit
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
ORDERING INFORMATION
Table A-2. Rosemount 644 Smart Temperature Transmitter Ordering Information
★ The Standard offering represents the most common models and options. These options should be selected for best delivery.
__The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
● = Available
– = Not Available
ModelProduct Description
644Smart Temperature Transmitter
Transmitter Type
StandardStandard
HHead Mount (suitable for mounting in the field with enclosure options below)
RRail Mount★
Output
HeadRail
StandardStandard
A4–20 mA with Digital Signal based on HART protocol
FFOUNDATION fieldbus digital signal (includes 2 AI function blocks and Backup Link Active
●●
●
–★
Scheduler)
WProfibus PA digital signal
●
–★
Product Certifications
Hazardous Locations Certificates (consult factory for availability)
AFWA
StandardStandard
E5
I5
K5
(1)
(2)
FM Explosion–Proof
FM Intrinsic Safety (includes standard I.S. and FISCO for fieldbus units)
(2)
FM Intrinsic Safety and Explosion–Proof combination (includes standard I.S. and
●●●–
●●●●
●●●–
FISCO for fieldbus units)
KCFM/CSA Intrinsic Safety and Non-incendive Approval
(2)
I6
K6
CSA Intrinsic Safety (includes standard I.S. and FISCO for fieldbus units)
(1)(3)
CSA Intrinsic Safety and Explosion–Proof combination (includes standard I.S. and
●●●–
●●●–
●●●–
FISCO for fieldbus units)
I3NEPSI Intrinsic Safety
E3NEPSI Flameproof
(1)
E1
N1
(1)
ATEX Flameproof
ATEX Type n
NCATEX Type n Component
(1)
ND
I1
E7
I7
N7
(2)
(3)(2)
ATEX Dust Ignition–Proof
ATEX Intrinsic Safety (includes standard I.S. and FISCO for fieldbus units)
(1)
IECEx Flameproof and Dust
IECEx Intrinsic Safety (includes standard I.S. and FISCO for fieldbus units)
XASensor specified separately and assembled to transmitter
●●●–
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
A-9
Reference Manual
00809-0300-4728, Rev AA
Rosemount 644
Table A-2. Rosemount 644 Smart Temperature Transmitter Ordering Information
★ The Standard offering represents the most common models and options. These options should be selected for best delivery.
__The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
● = Available
– = Not Available
HeadRail
AFWA
Enclosure
StandardStandard
(4)(5)
J5
Universal Head (junction box), aluminum alloy with 50.8 mm (2-in.) SST pipe bracket
(M20 entries)
(3)
J6
J7
(3)(5)
Universal Head (junction box), aluminum alloy with 50.8 mm (2-in.) SST pipe bracket
1
(
/2–14 NPT entries)
Universal Head (junction box), cast SST with 50.8 mm (2-in.) SST pipe bracket (M20
entries)
(3)
J8
Universal Head (junction box), cast SST with 50.8 mm (2-in.) SST pipe bracket (1/2–14
NPT entries)
Expanded
S1Connection Head, Polished Stainless Steel (1/2–14 NPT entries)
S2Connection Head, Polished Stainless Steel (1/2–14 NPSM entries)
S3Connection Head, Polished Stainless Steel (M20 x 1.5 conduit and entries)
S4Connection Head, Polished Stainless Steel (M20 x 1.5 conduit entries, M24 x 1.5 head
entry)
Local Display (644H only)
StandardStandard
M5LCD Display
Expanded
M6LCD Display with Polycarbonate Meter Face
Configuration
StandardStandard
C1Factory configuration date, descriptor, and message fields (CDS, document number
00806-0100-4728 required).
Analog Output
StandardStandard
A1Analog output levels compliant with NAMUR-recommendations NE 43: June 1997: high
alarm configuration
CNAnalog output levels compliant with NAMUR-recommendations NE 43: June 1997: low
alarm configuration
C8Low Alarm (standard Rosemount alarm and saturation values)
Filter
StandardStandard
F660 Hz line voltage filter
Trim
StandardStandard
C2Transmitter-sensor matching, trim to specific Rosemount RTD calibration schedule
(CVD constants)
Calibration Option
StandardStandard
C45-point calibration. Use option code Q4 to generate a calibration certificate
Q4Calibration certificate. 3-Point calibration with certificate
●●●–
●●●–
●●●–
●●●–
●●●–
●●●–
●●●–
●●●–
●●●–
●●●–
●●●●
●––●
●––●
●––●
●●●●
●●●●
●●●●
●●●●
HeadRail
AFWA
January 2011
★
★
★
★
★
★
★
★
★
★
★
★
★
A-10
Reference Manual
00809-0300-4728, Rev AA
January 2011
Table A-2. Rosemount 644 Smart Temperature Transmitter Ordering Information
★ The Standard offering represents the most common models and options. These options should be selected for best delivery.
__The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
Accessory Options
StandardStandard
G1External ground lug assembly
G2Cable gland
(7)
, EEx d, Brass, 7.5 mm - 11.99 mm
G7Cable gland, M20x1.5, EEx e, Blue, Polyamide, Diam 5-9mm
G3Cover chain. Only available with enclosure option codes J5 or J6. Not available with
LCD Display option code M5.
G5WAGO spring clamp terminals
Interlinkbt Connector
StandardStandard
(8)
GE
GM
Eurofast® Interlinkbt Connector
(8)
Minifast® Interlinkbt Connector
External Label
StandardStandard
ELExternal label for ATEX Intrinsic Safety
Typical Rail Mount Model Number: 644 R A I5
Typical Head Mount Model Number: 644 H F I5 M5 J5 C1
(1) Requires enclosure option J5, J6, J7, or J8.
(2) When IS approval is ordered on a Profibus PA, both standard IS and FISCO IS approvals apply. The device label is marked appropriately.
(3) Consult factory for availability.
(4) Suitable for remote mount configuration.
(5) When ordered with XA,
(6) Only available with Enclosure option code J5 or J6. For A TEX approved unit s the Grou nd Lug Assembly is included. It is not necessary to include code G1
for units with ATEX approvals.
(7) Only available with Enclosure option code J5.
(8) Available with Intrinsically Safe approvals only. For FM Intrinsically Safe or non-incendive approval (option code I5), install in accordance with Rosemount
drawing 03151-1009 to maintain NEMA 4X rating.
1
/2“ NPT enclosure will come equipped with an M20 adapter with the sensor installed as process ready.
(6)
(see “External Ground Screw Assembly” on page A-12)
Rosemount 644
● = Available
– = Not Available
●●
●●
●●
●●
●●
●●
●●
●●
●
●
●
●
●
●
●
●
–
–
–
–
–
–
–
–
★
★
★
★
★
★
★
★
NOTE
For additional options (e.g. “K” codes), please contact your local Emerson Process Management representative.
A-11
Rosemount 644
Reference Manual
00809-0300-4728, Rev AA
January 2011
Tagging
Hardware
• 13 characters total
• Tags are adhesive labels
• Permanently attached to transmitter
• Character height is
1
/16-in (1.6 mm)
Software
• Order with C1 option
• The transmitter can store up to 13 characters for Profibus PA. If no characters are specified,
the first 8 characters of the hardware tag are the default.
Considerations
Special Mounting Considerations
See “Mounting Kits for 644H” on page A-8 for the special hardware that is available to:
• Mount a 644H to a DIN rail. (see Table A-3 on page A-12)
• Retrofit a new 644H to replace an existing 644H transmitter in an existing threaded sensor
connection head.(see Table A-3 on page A-12)
External Ground Screw Assembly
The external ground screw assembly can be ordered by specifying code G1 when an enclosure is
specified. However, some approvals include the ground screw assembly in the transmitter
shipment, hence it is not necessary to order code G1. The table below identifies which approval
options include the external ground screw assembly and which do not.
Aluminum alloy Universal Head, standard cover—M20 entries
Aluminum alloy Universal Head, meter cover—M20 entries
Aluminum alloy Universal Head, standard cover—1/2-14 NPT entries
Aluminum alloy Universal Head, meter cover—1/2-14 NPT entries
LCD Display (includes meter and meter spacer assembly)
LCD Display kit (includes meter and meter spacer assembly, and meter cover)
Ground screw assembly kit
Kit, Hardware for mounting a 644H to a DIN rail (includes clips for symmetrical and asymmetrical rails)
Kit, Hardware for retrofitting a 644H in an existing threaded sensor connection head (former option code L1)
Kit, 316 U-Bolt for Universal Housing
Universal clip for rail or wall mount
24 Inches of symmetric (top hat) rail
24 Inches of asymmetric (G) rail
Ground clamp for symmetric or asymmetric rail
End clamp for symmetric or asymmetric rail
Snap rings kit (used for assembly to a DIN sensor – quantity 12)
SST Universal Head, standard cover—M20 entries
A-12
Part Number
00644-4420-0002
00644-4420-0102
00644-4420-0001
00644-4420-0101
00644-4430-0002
00644-4430-0001
00644-4431-0001
00644-5301-0010
00644-5321-0010
00644-4423-0001
03044-4103-0001
03044-4200-0001
03044-4201-0001
03044-4202-0001
03044-4203-0001
00644-4432-0001
00644-4433-0002
Reference Manual
00809-0300-4728, Rev AA
January 2011
Table A-3. Transmitter Accessories
Part Description
SST Universal Head, meter cover—M20 entries
SST Universal Head, standard cover—1/2-14 NPT entries
SST Universal Head, meter cover—1/2-14 NPT entries
Polished SST Connection Head, standard cover—1/2-14 NPT entries
Polished SST Connection Head, meter cover—1/2-14 NPT entries
Polished SST Connection Head, standard cover—1/2-14 NPSM entries
Polished SST Connection Head, meter cover—1/2-14 NPSM entries
Polished SST Connection Head, standard cover—M20 x 1.5 entries
Polished SST Connection Head, meter cover—M20 x 1.5 entries
Polished SST Connection Head, standard cover—M20 x 1.5 / M24 x 1.5 entries
Polished SST Connection Head, meter cover—M20 x 1.5 / M24 x 1.5 entries
Rosemount 644
Part Number
00644-4433-0102
00644-4433-0001
00644-4433-0101
00079-0312-0011
00079-0312-0111
00079-0312-0022
00079-0312-0122
00079-0312-0033
00079-0312-0133
00079-0312-0034
00079-0312-0134
A-13
Rosemount 644
79.8 (3.14)
70.0 (2.76)
33 (1.3)
76.2 (3.0)
24.4
(0.96)
25.4 (1.0)
44.5 (1.75)
27.9 (1.1)
Standard Cover
Housing
O-Ring
70.0 (2.76)
33 (1.3)
76.2 (3.0)
47 (1.85)
61 (2.4)
25.4 (1.0)
44.5 (1.75)
27.9 (1.1)
74.4 (2.93)
LCD Display Cover
Housing
O-Ring
Dimensional Drawings
Reference Manual
00809-0300-4728, Rev AA
January 2011
Sanitary Housing Covers
Standard Cover
LCD Display Cover
A-14
Dimensions are in millimeters (inches)
Reference Manual
00809-0300-4728, Rev AA
January 2011
ConfigurationTransmitter Configuration
The transmitter is available with standard configuration setting for Profibus PA
(see “Standard Profibus PA Configuration”). The configuration settings and
block configuration may be changed in the field with Emerson’s DeltaV
™
AMS
Suite, Handheld Field Communicator or other host or
configuration tool.
Standard Profibus PA Configuration
Unless specified, the transmitter will be shipped as follows:
Device Address: 126
Sensor Type: RTD, Pt 100 (=0.00385, 4-wire)
Damping: 5 sec.
Units of Measurement: °C
Line Voltage Filter: 50 Hz
Software Tag:
Alarm Limits:
• HI-HI: Infinity
• HI: Infinity
• LO: - Infinity
• LO-LO: Infinity
Local Display (when installed): Engineering Units of
Temperature
Emerson Process Management Rosemount Division. – Chanhassen,
Minnesota, USA
Rosemount Temperature GmbH – Germany
Emerson Process Management Asia Pacific – Singapore
The EC declaration of conformity for all applicable European directives for this
product can be found on the Rosemount website at www.rosemount.com. A
hard copy may be obtained by contacting our local sales representative.
ATEX Directive (94/9/EC)
Rosemount Inc. complies with the ATEX Directive.
CE Electromagnetic Compatibility Compliance Testing
The 644 meets the criteria under IEC 61326:2006
www.rosemount.com
Rosemount 644
HAZARDOUS LOCATIONS CERTIFICATES
Rosemount 644 with
Profibus PA
North American Certifications
Factory Mutual (FM) Approvals
I5FM Intrinsically Safe
Intrinsically Safe (Entity) / FISCO for use in Class I/II/III, Division 1,
Groups A, B, C, D, E, F, and G; when installed per control drawing
00644-2075.
Temperature Code: T4A (T
Nonincendive for use in Class I, Division 2, Groups A, B, C, and D.
Temperature Code: T6 (T
E5 FM Explosion Proof
Explosion Proof for Class I, Division 1, Groups B, C, and D.
Nonincendive for use in Class 1, Division 2, Groups A, B, C, and D.
Temperature Code: T5 (T
When installed per Rosemount control drawing 00644-1049
Dust Ignition Proof for Class II/III, Division 1, Groups E, F, G.
Temperature Code: T5 (T
When installed per Rosemount drawing 00644-1049.
(J5, J6, and J8 options only.)
= – 50 °C to 60 °C).
amb
= – 50 °C to 70 °C);
amb
T5 (T
= – 50 °C to 85 °C)
amb
= – 50 °C to 85 °C)
amb
= – 50 °C to 85 °C)
a
Reference Manual
00809-0300-4728, Rev AA
January 2011
Canadian Standards Association (CSA) Approvals
I6CSA Intrinsically Safe
Intrinsically Safe and FISCO for Class I, Division 1, groups A, B, C, and
D when connected per Rosemount drawing 00644-2076.
Temperature code: T4 (T
Suitable for Class I, Division 2, groups A, B, C, and D (must be installed
in a suitable enclosure)
K6 CSA Intrinsically Safe, Explosion–proof
Includes Intrinsically Safe “I6” and Explosion-Proof for Class I, Division 1,
groups B, C, and D.
Dust-Ignition Proof for Class II, Division 1, Groups E, F, and G.
Dust-Ignition Proof for Class III, Division 1
Seal not required.
CSA Enclosure Type 4X
Temperature Code: T4 (T
T5 (T
NOTE
K6 is only available with 644H option codes J5 and J6.
= – 50 °C to 60 °C);
amb
= – 50 °C to 60 °C);
amb
= – 50 °C to 85 °C)
amb
B-2
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
European Certifications
ATEX Approvals
E1 ATEX Flame Proof
Certificate Number: KEMA99ATEX8715X
ATEX Marking: II 2 G
1180
Ex d IIC T6 (–40 °C T
U
= 32 Vdc
SPECIAL CONDITIONS FOR SAFE USE (X):
For information on the dimensions of the flameproof joints the manufacturer
shall be contacted.
I1ATEX Intrinsic Safety
Certificate Number: Baseefa03ATEX0499X
ATEX Marking: II 1 G
1180
Ex ia IIC T4 (-50 °C T
65 °C)
amb
amb
60 °C)
Table B-1. Entity Parameters
I.S. Loop/Power Terminals
Ui = 30 V
Ii = 300 mA
Pi = 1.3 W
Ci = 2.1 nF
Li = 0
FISCO Loop/Power Terminals
Ui = 17.5 V
Ii = 380 mA
Pi = 5.32 W
Ci = 2.1 nF
Li = 0
Sensor Terminals
Uo = 13.9 V
Io = 23 mA
Po = 79 mW
Ci = 7.7 nF
Li = 0
SPECIAL CONDITIONS FOR SAFE USE (X):
The apparatus must be installed in an enclosure which affords it a degree of
protection of at least IP20. Non-metallic enclosures must have a surface
resistance of less than 1G, light alloy or zirconium enclosures must be
protected from impact and friction when installed.
B-3
Rosemount 644
Reference Manual
00809-0300-4728, Rev AA
January 2011
N1 ATEX Type n
Certificate Number: BAS00ATEX3145
ATEX Marking: II 3 G
Ex nL IIC T5 (-40 °C T
U
= 32 V
i
NC ATEX Type n Component
Certificate Number: BAS99ATEX3084U
ATEX Marking: II 3 G
Ex nL IIC T5 (-40 °C T
U
= 32 V
i
NOTE
The equipment must be installed in an enclosure meeting the requirements of
IP54 and the requirements of the impact tests described in EN50021.
ND ATEX Dust Ignition-Proof
Certificate Number: KEMA99ATEX8715X
ATEX Marking: II 1 D
tD A20 T95°C (-40 °C T
1180
IP66
amb
amb
amb
70 °C)
70 °C)
85 °C)
SPECIAL CONDITIONS FOR SAFE USE (X):
For information on the dimensions of the flameproof joints the manufacturer
shall be contacted.
IECEx Certifications
E7 IECEx Flameproof and Dust
Certificate Number: IECEx KEM 09.0015X
Ex d IIC T6 (Flameproof)
Ex tD A20 IP 66 T 95 °C (Dust)
Vmax = 32 V
SPECIAL CONDITIONS FOR SAFE USE (X):
For information on the dimensions of the flameproof joints the manufacturer
shall be contacted.
Table B-2. Electrical Data
TransmitterSensor
V
= 32 VdcU
max
I
= 12.0 mAI
max
I7IECEx Intrinsic Safety
Certificate Number: IECEx BAS 07.0053X
Ex ia IIC T4/T5/T6
Table B-3. Temperature Classification
P
i (W)
1.3T4-50 °C to 60 °C
5.32 (FISCO Group IIC)T4-60 °C to 80 °C
= 5 Vdc
max
= 2.0 mA
max
Temperature
Class
T
amb
B-4
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
SPECIAL CONDITIONS FOR SAFE USE (X):
1.The apparatus must be installed in an enclosure which affords it a
degree of protection of at least IP20.
2.Non-metallic enclosures must have a surface resistance of less than
1 G; light alloy or zirconium enclosures must be protected from
impact and friction when installed.
Table B-4. Entity Parameters
Transmitter (I.S.)Transmitter (FISCO)Sensor
U
= 30 VdcUi = 17.5 VdcUo = 13.9 Vdc
i
Ii = 300 mAIi = 380 mAIo = 23 mA
Pi = 1.3 WPi = 5.32 WPo = 79 mW
Ci = 2.1 nFCi = 2.1 nFCi = 7.7 nF
Li = 0 mHLi = 0 mHLi = 0 mH
N7 IECEx Type n
Certificate Number: IECEx BAS 07.0055
Ex nA nL IIC T5 (-40 °C T
Table B-5. Electrical Data
TransmitterSensor
RTDThermocouple
Ui = 32 VUi = 5 VUi = 0
70 °C)
amb
NG IECEx Type n Component
Certificate Number: IECEx BAS 07.0054U
Ex nA nL IIC T5 (-40 °C T
Input Parameter: Ui = 32 Vdc
SCHEDULE OF LIMITATIONS:
The component must be housed in a suitably certified enclosure that provides
a degree of protection of at least IP54.
75 °C)
amb
Japanese Certifications
Japanese Industrial Standard (JIS) Approvals
I4JIS Intrinsic Safety
E4 JIS Explosion Proof
Table B-6. Certificate and Description
CertificateDescription
C15744644H with meter and no
sensor
C15745644H without meter and
no sensor
C15749644H without meter and
with RTD
C15750644H without meter and
with thermocouple
Approval
Group
Ex d II CT6
Ex d II CT6
Ex d II BT4
Ex d II BT4
Temp
Code
B-5
Rosemount 644
Table B-6. Certificate and Description
CertificateDescription
C15751644H with meter and
thermocouple
C15752644H with meter and
RTD
C15910644H without meter and
with thermocouple
C15911644H with meter and
thermocouple
C15912644H without meter and
with RTD
C15913644H with meter and
RTD
Combination Approvals
K5 Combination of I5 and E5.
Reference Manual
00809-0300-4728, Rev AA
January 2011
Approval
Group
Ex d II BT4
Ex d II BT4
Ex d II B + H2T4
Ex d II B + H2T4
Ex d II B + H2T4
Ex d II B + H2T4
Temp
Code
Russian GOST Certifications
PPC BA-13006:
0 Ex ia IIC T4/T5/T6
Kazakhstan GOST
Pattern approval Certificate for Measuring Instruments
See Certificate
Ukraine GOST
Pattern Approval for Measuring Instruments
See Certificate
B-6
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
INSTALLATION
DRAWINGS
The installation guidelines presented by the drawings must be followed in
order to maintain certified ratings for installed transmitters.
Rosemount Drawing 00644-1064, 1 Sheet,
Canadian Standards Association Intrinsic Safety Installation Drawing
Rosemount Drawing 00644-1059, 1 Sheet;
Canadian Standards Association Explosion-Proof Installation Drawing
Rosemount Drawing 00644-2076, 3 Sheets;
Canadian Standards Association 644 Fieldbus Intrinsic Safety/FISCO
Installation Drawing
Once a device labeled with multiple approval types is installed, it should not
be reinstalled using any of the other labeled approval types. To ensure this,
the approval label should be permanently marked to distinguish the used from
the unused approval type(s).
B-7
Rosemount 644
Figure B-1. CSA Intrinsic Safety Installation Drawing 00644-1064, Rev. AB
Reference Manual
00809-0300-4728, Rev AA
January 2011
B-8
Reference Manual
00809-0300-4728, Rev AA
January 2011
Figure B-2. CSA Explosion-Proof Installation Drawing 00644-1059, Rev. AF
Rosemount 644
B-9
Reference Manual
00809-0300-4728, Rev AA
Rosemount 644
Figure B-3. CSA 644 Fieldbus Intrinsic Safety, FISCO Installation Drawing 00644-2076, Rev. AB Sheet 1 of 3
January 2011
B-10
Reference Manual
00809-0300-4728, Rev AA
January 2011
Sheet 2 of 3
Rosemount 644
B-11
Rosemount 644
Sheet 3 of 3
Reference Manual
00809-0300-4728, Rev AA
January 2011
B-12
Reference Manual
00809-0300-4728, Rev AA
January 2011
Figure B-4. FM Intrinsic Safety Installation Drawing 00644-0009, Rev. AD Sheet 1 of 2
Rosemount 644
B-13
Rosemount 644
Sheet 2 of 2
Reference Manual
00809-0300-4728, Rev AA
January 2011
B-14
Reference Manual
00809-0300-4728, Rev AA
January 2011
Figure B-5. FM Explosion-Proof Installation Drawing 00644-1049, Rev. AD
Rosemount 644
B-15
Reference Manual
00809-0300-4728, Rev AA
Rosemount 644
Figure B-6. FM 644 Fieldbus Intrinsic Safety and FISCO Installation Drawing 00644-2075, Rev. AB Sheet 1 of 3
OVERVIEWThis Appendix contains Profibus block and parameter information.
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices.
Please review the approval sections of the 644 Profibus reference manual for any restrictions
associated with a safe installation.
• In an Explosion-Proof/Flameproof installation, do not remove the transmitter covers
when power is applied to the unit.
Process leaks could result in death or serious injury.
• Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present on leads
can cause electrical shock.
www.rosemount.com
Reference Manual
00809-0300-4728, Rev AA
Rosemount 644
January 2011
RESOURCE BLOCKTable C-1 through Table C-3 can be used to cross reference parameters from
the Profibus specification, class 2 master, DD, or DTM
Table C-1. Physical Block Parameters
SlotIndexParameter NameDD LabelHelp Text
016BLOCK_OBJECTThis object contains the
characteristics of the blocks.
017ST_REVStatic RevisionParameter that changes by 1 when the
018TAG_DESCTa gA user-supplied description of the block.
019STRATEGYStrategyThe STRATEGY parameter has a
020ALERT_KEYAlert KeyThe ALERT_KEY parameter has a user
022MODE_BLKN/AThe MODE_BLK parameter is a structured
023ALARM_SUMN/AThe parameter ALARM_SUM summarizes
024SOFTWARE_REVISIONSoftware RevisionRevision-number of the software of the field
025HARDWARE_REVHardware RevisionRevision-number of the hardware of the field
026DEVICE_MAN_IDManufacturer IDIdentification code of the manufacturer of the
027DEVICE_IDModelManufacturer specific identification of the
028DEVICE_SER_NUMPermanent TagSerial number of the field device.
029DIAGNOSISDiagnosisDetailed information of the device, bitwise
030DIAGNOSIS_EXTENSIONDiagnosis ExtensionAdditional manufacturer-specific information
031DIAGNOSIS_MASKDiagnosis MaskDefinition of supported DIAGNOSIS
032DIAGNOSIS_MASK_EXTENSIONDiagnosis Mask ExtensionDefinition of supported
034WRITE_LOCKINGWrite LockSoftware write protection.
035FACTORY_RESETFactory ResetThe command for resetting a device to default
036DESCRIPTORDescriptorUser-definable text (a string) to describe the
The BLOCK_OBJECT parameter is the first
parameter of every block. It contains the
characteristics of the block e.g. block type
and profile number.
corresponding block has been modified.
user-specified value. This assigned value can
be used in configuration or diagnostics as a
key in sorting block information.
assigned value which may be used in sorting
alarms or events generated by a block.
which mode is desired for the block. It is
normally set by a control application or by an
operator through a human interface
application.
parameter composed of the actual mode, the
normal mode, and the permitted mode.
the status of up to 16 block alarms.
device.
device.
field device.
device.
coded.
of the device, bitwise coded. More than one
message possible at once.
information-bits. 0: not supported 1:
supported
DIAGNOSIS_EXTENSION information-bits.
0: not supported 1: supported
values. The setting of the bus address is not
affected.
device within the application.
C-2
Reference Manual
00809-0300-4728, Rev AA
January 2011
Table C-1. Physical Block Parameters
SlotIndexParameter NameDD LabelHelp Text
037DEVICE_MESSAGEMessageUser-definable MESSAGE to describe the
device within the application or in the plant.
Date of installation of the device.
038DEVICE_INSTALL_DATEInstallation DateDate of installation of the device.
040IDENT_NUMBER_SELECTORGSD TypeThe Profibus Ident Number.
042FEATUREFeaturesIndicates optional features implemented in
the device and the status of these features
which indicates if the feature is supported or
not supported.
043COND_STATUS_DIAGCurrent Status and Diagnostic Indicates the mode of a device that can be
configured for status and diagnostic
behavior.
049DEVICE_ADDRESSAddressThe address of the device.
050STACK_LIB_VERSIONStack RevisionThe version of the registered stack in the
device.
051OUTPUT_BOARD_SNOutput Board Serial NumberThe serial number given to the electronics
output board.
052FINAL_ASSY_NUMFinal Assembly NumberAn identifying number given to the device at
Final Assembly
053CONFIGURE_LCDConfigure LCDSelection of what parameters to be displayed
on the LCD.
054IDENT_VALUEPROFIBUS Ident NumberEach PROFIBUS device shall have an
Ident Number provided by PI. The Ident
Number specifies the cyclic behavior of a
device which is described in the
corresponding GSD file. A PROFIBUS PA
device shall support at least one profile
specific Ident Number.
Rosemount 644
Table C-2. Transducer Block Parameters
SlotIndexParameter NameDD LabelHelp Text
216BLOCK_OBJECTThis object contains the
characteristics of the blocks.
217ST_REVStatic RevisionParameter that changes by 1 when the
218TAG_DESCTa gA user-supplied description of the block.
219STRATEGYStrategyThe STRATEGY parameter has a
220ALERT_KEYAlert KeyThe ALERT_KEY parameter has a user
Process value
225PRIMARY_VALUE_UNITPrimary Value UnitSelects the unit code of the
PRIMARY_VALUE and other values.
226SECONDARY_VALUE_1Secondary ValueProcess value connected to channel 1 and
228SENSOR_MEAS_TYPESensor Measurement TypeMathematical function to calculate
229INPUT_RANGEElectrical Input Range and
Mode
230LIN_TYPESensor TypeSelects the type of sensor (Code) for
235BIAS_1BiasBias that can be algebraically added to the
237UPPER_SENSOR_LIMITUpper Sensor LimitPhysical upper limit function of the sensor
238LOWER_SENSOR_LIMITLower Sensor LimitPhysical lower limit function of the sensor
240INPUT_FAULT_GENInput MalfunctionInput malfunction: Diagnosis object for errors
241INPUT_FAULT_1SV Input MalfunctionInput malfunction: Diagnosis object for errors
243SENSOR_WIRE_CHECK_1Check Open/Short SensorEnables lead breakage and short circuit
249RJ_TEMPTerminal TemperatureReference junction temperature.
250RJ_TYPEReference JunctionSelects reference junction from internal to
252SENSOR_CONNECTIONSensor ConnectionConnection to the sensor, selected for 2, 3,
253COMP_WIRE12-Wire OffsetValue in Ω to compensate line resistance
279CAL_POINT_HIUpper Cal PointThis parameter contains the highest
280CAL_POINT_LOLower Cal PointThis parameter contains the lowest calibrated
281CAL_MIN_SPANCalibration Minimum SpanThis parameter contains the minimum
282CAL_UNITCalibration UnitThe units used for Calibration.
283SENSOR_CAL_METHODMethodMethod used to calibrate the temperature
284SENSOR_CAL_LOCLocationThe location the calibration was performed.
285SENSOR_CAL_DATEDateThe date the calibration was performed.
286SENSOR_CAL_WHOPerformed ByThe name of the person performing the
287SENSOR_SNSensor Serial NumberThe serial number associated with the sensor
corrected by BIAS_1.
PRIMARY_VALUE (PV).
Electrical input range and mode.
Thermocouples, Rtd, Pyrometers or linear.
process value of channel 1.
(e.g. Pt 100 = 850 °C) and input range.
(e.g. Pt 100 = -200 °C) and input range.
that concerns all values.
that concern SV_1.
detection for Sensor 1.
fixed value.
and 4 wires connection.
when the thermo resistance is connected with
2 wires.
calibrated value. For calibration of the high
limit point give the high measurement value
(pressure) to the sensor and transfer this
point as HIGH to the transmitter.
value. For calibration of the low limit point
give the low measurement value (pressure) to
the sensor and transfer this point as LOW to
the transmitter.
calibration span value allowed. This minimum
span information is necessary to ensure that
when calibration is done, the two calibrated
points (high and low) are not too close
together.
sensor.
calibration.
reading the temperature.
January 2011
C-4
Reference Manual
00809-0300-4728, Rev AA
January 2011
Table C-2. Transducer Block Parameters
SlotIndexParameter NameDD LabelHelp Text
289TERMINAL_TEMP_RANGETerminal Temperature RangeThe temperature range associated with the
terminal temperature of the device.
290ASIC_REJECTIONAC Power FilterShould be configured to the frequency of AC
Power (50Hz/60Hz) currently running in the
facility.
291CALIBRATOR_MODEActive Calibrator ModeSelect ‘Active Calibrator On’ if using a
calibration device. This is critical if the
calibrator requires constant current for
calibration. If using a sensor or a calibration
device that can accept pulsed current, select
‘Active Calibrator Off’.
292OPEN_SNSR_HOLDOFFOpen Sensor HoldoffA software feature that has the transmitter
perform additional verification of the open
sensor status prior to activating the
transmitter alarm. If the additional verification
shows that the open sensor condition is not
valid, the transmitter will not go into alarm.
293INTER_DETECT_THRESHTransient FilterThe Intermittent Sensor Detect feature is
designed to guard against process
temperature readings caused by intermittent
open sensor conditions (and open sensor
condition lasting less than one update).
Default is set to 0.2% of the sensor limits. The
feature can be switched on or off and can be
adjusted from 0 to 100% of the sensor limits.
294CAL_VAN_DUSEN_COEFFCallendar-Van DusenThe calculated coefficients used in the
Callendar Van dusen equation to characterize
the sensor curve with Transmitter-Sensor
matching.
Rosemount 644
Table C-3. Analog Input Block Parameters
SlotIndexParameter NameDD LabelHelp Text
116BLOCK_OBJECTThis object contains the
characteristics of the blocks.
117ST_REVStatic RevisionParameter that changes by 1 when the
118TAG_DESCTag DescriptionA user-supplied description of the block.
119STRATEGYStrategyThe STRATEGY parameter has a
120ALERT_KEYAlert KeyThe ALERT_KEY parameter has a user
122MODE_BLKN/AThe MODE_BLK parameter is a structured
123ALARM_SUMN/AThe parameter ALARM_SUM summarizes
The BLOCK_OBJECT parameter is the first
parameter of every block. It contains the
characteristics of the block e.g. block type
and profile number.
corresponding block has been modified.
user-specified value. This assigned value can
be used in configuration or diagnostics as a
key in sorting block information.
assigned value which may be used in sorting
alarms or events generated by a block.
which mode is desired for the block. It is
normally set by a control application or by an
operator through a human interface
application.
parameter composed of the actual mode, the
normal mode and the permitted mode.
the status of up to 16 block alarms.
C-5
Reference Manual
00809-0300-4728, Rev AA
Rosemount 644
Table C-3. Analog Input Block Parameters
SlotIndexParameter NameDD LabelHelp Text
124BATCHBatchThe Batch parameter is necessary in a
distributed fieldbus system to identify used
and available channels, in addition to identify
the current batch in case of alerts.
126OUTOutThe Function Block parameter OUT contains
127PV_SCALEPV Scale - Upper Value
PV Scale - Lower Value
128OUT_SCALEOut ScaleThe Function Block parameter OUT_SCALE
129LIN_TYPELinearization TypeType of linearization.
130CHANNELChannelReference to the active Transducer Block
132PV_FTIMEDamping ValueFilter time of the Process Variable.
133FSAFE_TYPEFail Safe TypeDefines the reaction of the device, if a fault is
134FSAFE_VALUEFail Safe ValueDefault value for the OUT parameter, if a
135ALARM_HYSAlarm HysteresisHysteresis. The hysteresis is expressed as
137HI_HI_LIMHi HiValue for upper limit of alarms.
139HI_LIMHiValue for upper limit of warnings.
141LO_LIMLoValue for lower limit of warnings.
143LO_LO_LIMLo LoValue for the lower limit of alarms.
150SIMULATESimulateFor commissioning and test purposes the
the current measurement value in a vendor
specific or configuration adjusted engineering
unit and the belonging status in AUTO
MODE.
Conversion of the Process Variable into
percent using the high and low scale values.
contains the values of the lower limit and
upper limit effective range.
which provides the measurement value to the
Function Block.
detected.
sensor or sensor electronic fault is detected.
value below high limit and above low limit in
the engineering unit of expressed as value
below high limit and above low limit in the
engineering unit of xx_LIM.
input value from the Transducer Block in the
Analog Input Function Block AI-FB can be
modified.
January 2011
C-6
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
CONDENSED STATUSThe Rosemount 644 device utilizes condensed status as recommended by
the Profile 3.02 specification and NE 107. Condensed status has some
additional bits and changed bit assignments from classic status. Confirm bit
assignment using Table C-4 and Table C-5.
Table C-4. Diagnostic Descriptions
Device Related Diagnosis
Byte-BitUnit_Diag_Bit
2-335Restart
2-436Cold Start
2-537Maintenance Required
2-739Ident_Number violation
3-040Failure of the device
3-141Maintenance demanded
3-242Function Check
3-343Process not returning valid values
4-755Extension Available
(1) Unit_Diag_Bit located in GSD file
(1)
Diagnostic Description
Table C-5. Output Status Bit Definition
Condensed StatusAI Block OUT Status Parameter
DescriptionHEXDECIMAL
Bad - passivated 0x2335
Bad, maintenance alarm, more diagnostics available 0x2436
Bad, process related - no maintenance 0x2840
Uncertain, substitute set0x4B75
Uncertain, process related, no maintenance0x78120
Good, ok 0x80128
Good, update event0x84132
Good, advisory alarm, low limit 0x89137
Good, advisory alarm, high limit 0x8A138
Good, critical alarm, low limit 0x8D141
Good, critical alarm, high limit 0x8E142
Good, function check 0xBC188
C-7
Rosemount 644
Reference Manual
00809-0300-4728, Rev AA
January 2011
C-8
Reference Manual
00809-0300-4728, Rev AA
January 2011
Standard Terms and Conditions of Sale can be found at www.rosemount.com/terms_of_sale
The Emerson logo is a trademark and service mark of Emerson Electric Co.
Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
PlantWeb is a registered trademark of one of the Emerson Process Management group of companies.
Profibus PA is a registered trademark of Profibus International.
Lexan and Noryl are registered trademark of General Electric.
WAGO is a registered trademark of Kontakttechnik GmbH, Germany.
All other marks are the property of their respective owners.