The Rosemount 326T Temperature Transmitter detects media temperature and converts
it into an analog output signal (4 - 20 mA).
1.1Functions and features
The temperature transmitter converts the measured signal into a temperatureproportional analog signal. Depending on the parameter setting, the output signal is:
• 4-20 mA with setting OU = I
• 20-4 mA with setting OU = Ineg
The temperature transmitter can scale the analog signal to accommodate the application.
For more technical data, see the Rosemount™ 326T Temperature Transmitter Product
Data Sheet or Emerson.com/Rosemount.
Maximum measuring range when OU = I
• MAW = initial value of the measuring range
• MEW = final value of the measuring range
Note
The minimum difference between ASP and AEP is 9 °F (5 °C).
If the temperature is within the measuring range, the output signal is between 4-20 mA. If
the temperature is outside the measuring range, the output signal is between these
ranges:
Measuring range scaled when OU = I
• ASP = analog start point
• AEP = analog end point
Temperature condition
Temperature > AEP20-20.6 mA4-3.7 mA
Temperature > MEW20.6 mA3.7 mA
Temperature < ASP4-3.7 mA20-20.6 mA
Quick Start Guide5
Output signal when OU = IOutput signal when OU = Ineg
Page 6
IntroductionQuick Start Guide
January 201900825-0100-4328
Temperature conditionOutput signal when OU = IOutput signal when OU = Ineg
Temperature < MAW3.7 mA20.6 mA
Note
In a fault condition, the output signal reacts according to the FOU parameter.
6Quick Start Guide
Page 7
Quick Start GuideInstallation
00825-0100-4328January 2019
2Installation
This section provides instructions for mounting and connecting the temperature
transmitter.
2.1Mounting the transmitter
Follow these instructions to mount the temperature transmitter.
Note
If installing in a 3-A compliant environment, follow 3-A standards for installation.
Procedure
1. Position the transmitter to the desired orientation.
2. Install the clamp following recommended torque values provided by the clamp
manufacturer.
2.2Connect the transmitter
Follow these instructions to connect the temperature transmitter for two-wire or four-wire
operations.
CAUTION
• A certified electrician must wire the temperature transmitter.
• Adhere to national and international regulations when wiring the temperature
transmitter.
Voltage supply to EN 50178, SELV, PELV / "supply class 2" to cULus.
Procedure
1. Disconnect power from the temperature transmitter.
2. Connect the temperature transmitter according to these wiring diagrams.
Quick Start Guide7
Page 8
InstallationQuick Start Guide
January 201900825-0100-4328
Figure 2-1: Two-wire operation
Pin 1L+
Pin 2Analog signal for temperature
Figure 2-2: Four-wire operation
Pin 1L+
Pin 2Analog signal for temperature
Pin 3L-
Pin 4IO-Link
8Quick Start Guide
Page 9
Quick Start Guide
00825-0100-4328January 2019
Operation
3Operation
This section provides information for using the temperature transmitter.
3.1Display elements
The front of the temperature transmitter includes an alphanumeric display and LED
indicators.
A. Current temperature in °C
B. Current temperature in °F
C. Seven-segment LED display (4 digits)
3.2Parameter settings
Use an IO-Link capable tool to read current process values and modify parameter values.
3.2.1
3.2.2
General information
The temperature transmitter uses an IO-Link communication interface that requires an IOLink master for operation.
IO-Link enables direct access to process and diagnostic data and allows the setting of
parameter values.
IO-Link information
The IODDs necessary for configuring the IO-Link device, detailed information about
process data structure, diagnostic information, parameter addresses and the necessary
Quick Start Guide9
Page 10
OperationQuick Start Guide
January 201900825-0100-4328
information about the required IO-Link hardware and software are available at
Emerson.com/Rosemount
3.3Adjustable parameters
Use IO-Link software to configure these parameters.
ParameterDescription
OU2Output function: analog signal is 4-20 mA (I) or 20-4 mA (Ineg)
ASP2Analog start point for the measured temperature value.
AEP2Analog end point for the measured temperature value. The minimum
difference between ASP2 and AEP2 is 9 °F (5 °C).
COFZero point calibration. Offsets the zero point ± 18 °F in steps of .18 °F (±
10 °C in steps of 0.1 °C).
FOU2Behavior of the output after a fault.
• ON: the analog signal is driven to 21.1 mA.
• OFF: the analog signal is driven to 3.5 mA.
UniSets the temperature unit in °F or °C.
Update rate of displayThe rate at which the transmitter updates the displayed temperature
measurement.
• d1: 50 ms
• d2: 200 ms
• d3: 600 ms
Orientation of displayrd: rotates the display by 180°.
3.4Operating modes
The temperature transmitter uses different operating modes depending on the measured
temperature.
After turning on the temperature transmitter the temperature transmitter displays the
current measured temperature and the analog output provides a signal proportional to
the measured temperature.
If the temperature is outside of the measuring range the temperature transmitter displays
OL or UL.
10Quick Start Guide
Page 11
Quick Start GuideTemperature resistance
00825-0100-4328January 2019
4Temperature resistance
This graph shows the reduction of maximum operation time based on process
temperature.
Quick Start Guide11
Page 12
Temperature resistanceQuick Start Guide
January 201900825-0100-4328
12Quick Start Guide
Page 13
Quick Start GuideProduct certifications
00825-0100-4328January 2019
5Product certifications
5.1European directive information
The most recent revision of the EC Declaration of Conformity can be found at
Emerson.com/Rosemount.
5.2Ordinary location information
As standard, this product has been examined and tested to determine that the design
meets the basic electrical, mechanical, and fire protection requirements by a nationally
recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and
Health Administration (OSHA).
Voltage supply to EN 50178, SELV, PELV / "supply class 2" to cULus.
5.33-A® certification
This product is authorized to display the 3-A symbol. Ensure gaskets and process
connection accessories selected for installation meet both the application and 3-A
requirements. A certificate of compliance is available at Emerson.com/Rosemount.
5.4Other industry certifications
All Rosemount 326T transmitter surfaces and materials which come into contact with
process medium comply with the following regulations:
Quick Start Guide13
Page 14
Product certificationsQuick Start Guide
January 201900825-0100-4328
14Quick Start Guide
Page 15
Quick Start GuideFactory settings
00825-0100-4328January 2019
6Factory settings
Use this worksheet to reference factory default settings and record user-modified settings.
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a
trademark and service mark of Emerson Electric Co. Rosemount is mark of one of the
Emerson family of companies. All other marks are the property of their respective owners.