The pressure transmitter measures and monitors pressure in a facility.
1.1Pressure specifications
To ensure product performance and safety, adhere to the following specifications.
1.1.1Measuring range
This table shows the range at which the pressure transmitter is able to measure pressure.
Pressure rangeMeasuring range limits
inH2Ombar
1A-2.0 to 40-5 to 99.5
2A-5.0 to 100-12.4 to 248.8
1.1.2
psibar
3A-14.5 to 14.5-1 to 1
2B-0.73 to 14.5-0.05 to 1
4A-1.45 to 20-0.1 to 1.38
5A-1.8 to 36-0.124 to 2.48
6A-14.5 to 55-1 to 3.79
7A-14.5 to 85-1 to 5.86
8A-14.5 to 145-1 to 10
9A-14.5 to 230-1 to 15.9
1B-14.5 to 360-1 to 24.8
Note
The pressure transmitter is vacuum resistant. There are restrictions for nominal pressure
ranges at or below 4.35 psi (300 mbar). Adhere to the specifications in the data sheet.
Overpressure limits
The table in this topic shows maximum allowable pressure for the pressure transmitter.
CAUTION
Take appropriate measures to avoid exceeding the specified overpressure limits.
Quick Start Guide5
IntroductionQuick Start Guide
January 201900825-0100-4327
Pressure rangeOverpressure limits
inH2Obar
1A16064
2A24006
psibar
3A14510
2B14510
4A21515
5A29020
6A43530
7A43530
8A72550
9A108575
1B1450100
1.1.3Burst pressure limits
The burst pressure limit is the pressure at which the pressure transmitter will no longer
function or be damaged.
CAUTION
Do not exceed the burst pressure limit. Exceeding the burst pressure limit can damage the
pressure transmitter. Continuing to use the pressure transmitter after exceeding the burst
pressure limit can cause damage and physical injury.
Pressure range
1A1204430
2A1204430
3A43530
2B43530
4A58040
5A72550
6A1450100
Burst pressure limits
inH2Obar
psibar
7A1450100
8A2175150
9A3625250
6Quick Start Guide
Quick Start GuideIntroduction
00825-0100-4327January 2019
Pressure rangeBurst pressure limits
1B5075350
1.2Operating modes
The wiring configuration sets the operating mode. After wiring the pressure transmitter, it
automatically recognizes the connections and changes to the respective operating mode.
For more information, see Electrical connection.
1.2.1Two-wire operation
OUT2 (pin 2)
The analog signal proportional to pressure (4-20 mA or 20-4 mA).
1.2.2Three-wire operation
OUT1 (pin 4)
OUT2 (pin 2)
Switching signal for system pressure limit value
• Switching signal used for system pressure limit value
• Analog signal proportional to pressure (4-20 mA or 20-4 mA)
1.3Functions
The Rosemount 326P Pressure transmitter performs the functions described in this
section.
1.3.1
Switching function
The switching function is available only for three-wire operations. OUT1 or OUT2 changes
its switching status if the pressure is above or below the set switching limits (SPx, rPx).
These switching functions are available:
Set the width of the window using the difference between SPx and rPx. SPx is the upper
value and rPx is the lower value.
Quick Start Guide7
IntroductionQuick Start Guide
January 201900825-0100-4327
Figure 1-1: Hysteresis functionFigure 1-2: Window function
• SP: Set point
• rP: Reset point
• P: Pressure
• Hy: Hysteresis
• Hno: Hysteresis function/normally open
• Hnc: Hysteresis function/normally closed
1.3.2Analog signal
The transmitter communicates measured pressure using an analog signal.
OU2 defines whether the set measuring range is provided as 4-20 mA (OU2 = I) or as 20-4
mA (OU2 = InEG).
Rerange the transmitter (set new values for ASP and AEP) by either manually entering
range points or with an applied pressure source.
• Applying a pressure source for the analog start point (tASP) or manually setting the
parameter (ASP) defines the measured value when the analog signal is 4 mA (20 mA at
InEG).
• Applying a pressure source for the analog end point (tASP) or manually setting the
parameter (ASP) defines the measured value when the output signal is 20 mA (4 mA at
InEG).
• FE: Window
• Fno: Window function/normally open
• Fnc: Window function/normally closed
Minimum distance between ASP and AEP is 25 percent of the upper range limit (maximum
rangedown 4:1). For pressure range 3A, the minimum distance is 25 percent of the
measuring span.
MAW: initial value of the measuring range (Lower range limit [LRL])
MEW: final value of the measuring range (Upper range limit [URL])
1: OU2 = I
2: OU2 = InEG
In the set measuring range the output signal is between 4 and 20 mA (OU2 = I) or between
20 and 4 mA (OU2 = InEG). When pressure is outside the set measuring range, the output
signal is as follows:
• System pressure above the measuring range:
— Output signal > 20 mA if OU2 = I.
— Output signal 4 to 3.8 mA if OU2 = InEG.
• System pressure below the measuring range:
— Output signal 4 to 3.8 mA if OU2 = I.
— Output signal > 20 mA if OU2 = InEG.
Customer-specific calibration (sensor trim)
A customer specific calibration (sensor trim) corrects the pressure offset and pressure
range to match a pressure standard. This provides a slope correction to the transmitter's
current characterization curve. An accurate pressure standard is required for a full
calibration. For more information on performing a Sensor Trim, see Perform a sensor trim.
• Sensor Trim is a two-point sensor calibration that applies two end-point pressures
(CP1, CP2) then linearizes the output between them. CP1 and CP2 must be within the
scaled measuring range. For more information, see Analog signal.
• Zero trim is a single-point offset adjustment. It compensates for mounting position
effects and is most effective when performed with the transmitter installed in its final
Quick Start Guide9
IntroductionQuick Start Guide
January 201900825-0100-4327
mounting position. Since zero trim maintains the slope of the characterization curve,
do not use it in place of a Sensor Trim over the full sensor range. For more information,
see Perform manual zero trim.
Reset the calibration by resetting all parameters to the factory default settings. For more
information, see Resetting all parameters to factory default settings.
• P: measured pressure
P‘: modified measured value
• CP1: calibration point 1
CP1‘: modified measured value for CP1
• CP2: calibration point 2
• 1: curve of measured values at factory
setting
• 2: curve of measured values after calibration
• P: measured pressure
P‘: modified measured value
• CP1: calibration point 1
CP2: calibration point 2
CP2‘: modified measured value for CP2
• 1: curve of measured values at factory
setting
• 2: curve of measured values after calibration
• P: measured pressure
P‘: modified measured value
• CP1: calibration point 1
CP1‘: modified measured value for CP1
• CP2: calibration point 2
CP2‘: modified measured value for CP2
• 1: curve of measured values at factory
setting
• 2: curve of measured values after calibration
10Quick Start Guide
Quick Start Guide
00825-0100-4327January 2019
Installation
2Installation
This section contains instructions for installing and wiring the Rosemount 326P Pressure
Transmitter.
Note
Before installing or removing the unit, ensure no pressure is applied to the system. Note
that when the pressure transmitter displays 0%, pressure might still be applied to the
system.
2.1Installation orientation (3-A® standards)
For optimized cleaning of the measuring element in hygienic areas according to the 3-A
standards, follow these guidelines when installing the pressure transmitter.
To ensure the medium can run off the measuring element, do not install the unit at the
lowest point of a pipe or container.
Note
This product is not suitable for use where the criteria for paragraph E1.2 / 63-03 of the
3-A® standard 63-03 must be met.
2.2Hygienic process connection adapter
installation
Hygienic process connection adapters allow the transmitter to be installed according to
application requirements. All connection adapters include an EPDM O-ring. More sealing
rings are available to be ordered as accessories. See the Rosemount 326P Product DataSheet for all available connectors and accessories. Hygienic process connection adapters
include installation instructions with the packaging.
2.3Electrical connection
This section provides instructions for wiring the pressure transmitter. A qualified
electrician must wire the pressure transmitter. The electrical installation must adhere to
national and international regulations.
Voltage supply according to EN 50178, SELV, PELV.
2.3.1
Wiring for two-wire operation
Follow these steps to wire the pressure transmitter for two-wire operation.
Procedure
1. Disconnect the power.
2. Wire the pressure transmitter according to Figure 2-1.
Quick Start Guide11
InstallationQuick Start Guide
January 201900825-0100-4327
Figure 2-1: Connection for two-wire operation
BNBrown
WHWhite
OUTAnalog output (4-20 mA)
Colors to DIN EN 60947-5-2
2.3.2
Wiring for three-wire operation
Follow these steps to wire the pressure transmitter for three-wire operation.
Procedure
1. Disconnect the power.
2. Wire the pressure transmitter according to Figure 2-2.
Figure 2-2: Connection for three-wire operation
BK
BNBrown
BUBlue
WHWhite
OUT1Switching output
OUT2Switching output or analog output (4-20
Black
mA)
Colors to DIN EN 60947-5-2
12Quick Start Guide
Quick Start GuideInstallation
00825-0100-4327January 2019
Wiring examples
2 x positive switching2 x negative switching
1 x positive switching / 1 x analog1 x negative switching / 1 x analog
Note
If the analog signal current (I) is selected in the menu under OU2 and the output is not
connected (resistor = infinite), the pressure transmitter displays the error message W532
in intervals. This does not affect the measuring result. As an alternative, configure OU2 to
a switching output.
Quick Start Guide13
InstallationQuick Start Guide
January 201900825-0100-4327
14Quick Start Guide
Quick Start GuideOperation
00825-0100-4327January 2019
3Operation
This section provides instructions for configuring parameter settings.
3.1Display and function buttons
The pressure transmitter displays information using the display and can be controlled
using the function buttons.
1 to 8: Indicator LEDs
LED 1 to LED 5System pressure in the set unit of measurement.
LED 6If OU2 is configured as an analog output, it indicates the system pressure
in percent of the scaling of the analog output (range ASP to AEP).
If OU2 is configured as a switching output, it indicates the system
pressure in percent of the upper range limit (URL).
LED 7Switching status of OUT2 (illuminates when output 2 is switched).
LED 8Switching status of OUT1 (illuminates if output 1 is switched).
9: Alphanumeric display, 4 digits
• Current system pressure
• Parameters and parameter values
10: Set button
Selects a parameter from the menu and modifies the value by holding pressed for five seconds.
11: Mode/Enter button
Scrolls through the menu and acknowledges parameter values.
Quick Start Guide15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.