The pressure transmitter measures and monitors pressure in a facility.
1.1Pressure specifications
To ensure product performance and safety, adhere to the following specifications.
1.1.1Measuring range
This table shows the range at which the pressure transmitter is able to measure pressure.
Pressure rangeMeasuring range limits
inH2Ombar
1A-2.0 to 40-5 to 99.5
2A-5.0 to 100-12.4 to 248.8
1.1.2
psibar
3A-14.5 to 14.5-1 to 1
2B-0.73 to 14.5-0.05 to 1
4A-1.45 to 20-0.1 to 1.38
5A-1.8 to 36-0.124 to 2.48
6A-14.5 to 55-1 to 3.79
7A-14.5 to 85-1 to 5.86
8A-14.5 to 145-1 to 10
9A-14.5 to 230-1 to 15.9
1B-14.5 to 360-1 to 24.8
Note
The pressure transmitter is vacuum resistant. There are restrictions for nominal pressure
ranges at or below 4.35 psi (300 mbar). Adhere to the specifications in the data sheet.
Overpressure limits
The table in this topic shows maximum allowable pressure for the pressure transmitter.
CAUTION
Take appropriate measures to avoid exceeding the specified overpressure limits.
Quick Start Guide5
Page 6
IntroductionQuick Start Guide
January 201900825-0100-4327
Pressure rangeOverpressure limits
inH2Obar
1A16064
2A24006
psibar
3A14510
2B14510
4A21515
5A29020
6A43530
7A43530
8A72550
9A108575
1B1450100
1.1.3Burst pressure limits
The burst pressure limit is the pressure at which the pressure transmitter will no longer
function or be damaged.
CAUTION
Do not exceed the burst pressure limit. Exceeding the burst pressure limit can damage the
pressure transmitter. Continuing to use the pressure transmitter after exceeding the burst
pressure limit can cause damage and physical injury.
Pressure range
1A1204430
2A1204430
3A43530
2B43530
4A58040
5A72550
6A1450100
Burst pressure limits
inH2Obar
psibar
7A1450100
8A2175150
9A3625250
6Quick Start Guide
Page 7
Quick Start GuideIntroduction
00825-0100-4327January 2019
Pressure rangeBurst pressure limits
1B5075350
1.2Operating modes
The wiring configuration sets the operating mode. After wiring the pressure transmitter, it
automatically recognizes the connections and changes to the respective operating mode.
For more information, see Electrical connection.
1.2.1Two-wire operation
OUT2 (pin 2)
The analog signal proportional to pressure (4-20 mA or 20-4 mA).
1.2.2Three-wire operation
OUT1 (pin 4)
OUT2 (pin 2)
Switching signal for system pressure limit value
• Switching signal used for system pressure limit value
• Analog signal proportional to pressure (4-20 mA or 20-4 mA)
1.3Functions
The Rosemount 326P Pressure transmitter performs the functions described in this
section.
1.3.1
Switching function
The switching function is available only for three-wire operations. OUT1 or OUT2 changes
its switching status if the pressure is above or below the set switching limits (SPx, rPx).
These switching functions are available:
Set the width of the window using the difference between SPx and rPx. SPx is the upper
value and rPx is the lower value.
Quick Start Guide7
Page 8
IntroductionQuick Start Guide
January 201900825-0100-4327
Figure 1-1: Hysteresis functionFigure 1-2: Window function
• SP: Set point
• rP: Reset point
• P: Pressure
• Hy: Hysteresis
• Hno: Hysteresis function/normally open
• Hnc: Hysteresis function/normally closed
1.3.2Analog signal
The transmitter communicates measured pressure using an analog signal.
OU2 defines whether the set measuring range is provided as 4-20 mA (OU2 = I) or as 20-4
mA (OU2 = InEG).
Rerange the transmitter (set new values for ASP and AEP) by either manually entering
range points or with an applied pressure source.
• Applying a pressure source for the analog start point (tASP) or manually setting the
parameter (ASP) defines the measured value when the analog signal is 4 mA (20 mA at
InEG).
• Applying a pressure source for the analog end point (tASP) or manually setting the
parameter (ASP) defines the measured value when the output signal is 20 mA (4 mA at
InEG).
• FE: Window
• Fno: Window function/normally open
• Fnc: Window function/normally closed
Minimum distance between ASP and AEP is 25 percent of the upper range limit (maximum
rangedown 4:1). For pressure range 3A, the minimum distance is 25 percent of the
measuring span.
MAW: initial value of the measuring range (Lower range limit [LRL])
MEW: final value of the measuring range (Upper range limit [URL])
1: OU2 = I
2: OU2 = InEG
In the set measuring range the output signal is between 4 and 20 mA (OU2 = I) or between
20 and 4 mA (OU2 = InEG). When pressure is outside the set measuring range, the output
signal is as follows:
• System pressure above the measuring range:
— Output signal > 20 mA if OU2 = I.
— Output signal 4 to 3.8 mA if OU2 = InEG.
• System pressure below the measuring range:
— Output signal 4 to 3.8 mA if OU2 = I.
— Output signal > 20 mA if OU2 = InEG.
Customer-specific calibration (sensor trim)
A customer specific calibration (sensor trim) corrects the pressure offset and pressure
range to match a pressure standard. This provides a slope correction to the transmitter's
current characterization curve. An accurate pressure standard is required for a full
calibration. For more information on performing a Sensor Trim, see Perform a sensor trim.
• Sensor Trim is a two-point sensor calibration that applies two end-point pressures
(CP1, CP2) then linearizes the output between them. CP1 and CP2 must be within the
scaled measuring range. For more information, see Analog signal.
• Zero trim is a single-point offset adjustment. It compensates for mounting position
effects and is most effective when performed with the transmitter installed in its final
Quick Start Guide9
Page 10
IntroductionQuick Start Guide
January 201900825-0100-4327
mounting position. Since zero trim maintains the slope of the characterization curve,
do not use it in place of a Sensor Trim over the full sensor range. For more information,
see Perform manual zero trim.
Reset the calibration by resetting all parameters to the factory default settings. For more
information, see Resetting all parameters to factory default settings.
• P: measured pressure
P‘: modified measured value
• CP1: calibration point 1
CP1‘: modified measured value for CP1
• CP2: calibration point 2
• 1: curve of measured values at factory
setting
• 2: curve of measured values after calibration
• P: measured pressure
P‘: modified measured value
• CP1: calibration point 1
CP2: calibration point 2
CP2‘: modified measured value for CP2
• 1: curve of measured values at factory
setting
• 2: curve of measured values after calibration
• P: measured pressure
P‘: modified measured value
• CP1: calibration point 1
CP1‘: modified measured value for CP1
• CP2: calibration point 2
CP2‘: modified measured value for CP2
• 1: curve of measured values at factory
setting
• 2: curve of measured values after calibration
10Quick Start Guide
Page 11
Quick Start Guide
00825-0100-4327January 2019
Installation
2Installation
This section contains instructions for installing and wiring the Rosemount 326P Pressure
Transmitter.
Note
Before installing or removing the unit, ensure no pressure is applied to the system. Note
that when the pressure transmitter displays 0%, pressure might still be applied to the
system.
2.1Installation orientation (3-A® standards)
For optimized cleaning of the measuring element in hygienic areas according to the 3-A
standards, follow these guidelines when installing the pressure transmitter.
To ensure the medium can run off the measuring element, do not install the unit at the
lowest point of a pipe or container.
Note
This product is not suitable for use where the criteria for paragraph E1.2 / 63-03 of the
3-A® standard 63-03 must be met.
2.2Hygienic process connection adapter
installation
Hygienic process connection adapters allow the transmitter to be installed according to
application requirements. All connection adapters include an EPDM O-ring. More sealing
rings are available to be ordered as accessories. See the Rosemount 326P Product DataSheet for all available connectors and accessories. Hygienic process connection adapters
include installation instructions with the packaging.
2.3Electrical connection
This section provides instructions for wiring the pressure transmitter. A qualified
electrician must wire the pressure transmitter. The electrical installation must adhere to
national and international regulations.
Voltage supply according to EN 50178, SELV, PELV.
2.3.1
Wiring for two-wire operation
Follow these steps to wire the pressure transmitter for two-wire operation.
Procedure
1. Disconnect the power.
2. Wire the pressure transmitter according to Figure 2-1.
Quick Start Guide11
Page 12
InstallationQuick Start Guide
January 201900825-0100-4327
Figure 2-1: Connection for two-wire operation
BNBrown
WHWhite
OUTAnalog output (4-20 mA)
Colors to DIN EN 60947-5-2
2.3.2
Wiring for three-wire operation
Follow these steps to wire the pressure transmitter for three-wire operation.
Procedure
1. Disconnect the power.
2. Wire the pressure transmitter according to Figure 2-2.
Figure 2-2: Connection for three-wire operation
BK
BNBrown
BUBlue
WHWhite
OUT1Switching output
OUT2Switching output or analog output (4-20
Black
mA)
Colors to DIN EN 60947-5-2
12Quick Start Guide
Page 13
Quick Start GuideInstallation
00825-0100-4327January 2019
Wiring examples
2 x positive switching2 x negative switching
1 x positive switching / 1 x analog1 x negative switching / 1 x analog
Note
If the analog signal current (I) is selected in the menu under OU2 and the output is not
connected (resistor = infinite), the pressure transmitter displays the error message W532
in intervals. This does not affect the measuring result. As an alternative, configure OU2 to
a switching output.
Quick Start Guide13
Page 14
InstallationQuick Start Guide
January 201900825-0100-4327
14Quick Start Guide
Page 15
Quick Start GuideOperation
00825-0100-4327January 2019
3Operation
This section provides instructions for configuring parameter settings.
3.1Display and function buttons
The pressure transmitter displays information using the display and can be controlled
using the function buttons.
1 to 8: Indicator LEDs
LED 1 to LED 5System pressure in the set unit of measurement.
LED 6If OU2 is configured as an analog output, it indicates the system pressure
in percent of the scaling of the analog output (range ASP to AEP).
If OU2 is configured as a switching output, it indicates the system
pressure in percent of the upper range limit (URL).
LED 7Switching status of OUT2 (illuminates when output 2 is switched).
LED 8Switching status of OUT1 (illuminates if output 1 is switched).
9: Alphanumeric display, 4 digits
• Current system pressure
• Parameters and parameter values
10: Set button
Selects a parameter from the menu and modifies the value by holding pressed for five seconds.
11: Mode/Enter button
Scrolls through the menu and acknowledges parameter values.
Quick Start Guide15
Page 16
OperationQuick Start Guide
January 201900825-0100-4327
3.1.1Read the set parameters
Follow these steps to view the set parameter values.
Procedure
1. Press Mode/Enter until the pressure transmitter displays the desired parameter.
2. Press Set.
The pressure transmitter displays the value currently set for the selected parameter
for 15 seconds then returns to run mode.
3.1.2Change the display in run mode
Follow these steps to view the pressure measurement in different indicator types. During
normal operation, the pressure transmitter displays the pressure measurement in the
selected unit of measurement.
Procedure
• Press Set.
The pressure transmitter displays the following information for 15 seconds:
— System pressure in percent of the set scaling of the analog output if OU2 is
configured as analog output.
— System pressure in percent of the upper range limit if OU2 is configured as
switching output.
16Quick Start Guide
Page 17
Quick Start GuideOperation
00825-0100-4327January 2019
3.2Menu
This section explains the pressure transmitter menu options and structure.
3.2.1Main menu structure
The main menu includes options for accessing other menus, setting output functions, and
changing the display mode.
Figure 3-1: Main menu
• 1: Change to the extended functions menu (level 2)
• Menu items highlighted gray are not available for two-wire operation.
Option
SP1/rP1
OU1
OU2Output function for OUT2:
tCOFPerform Zero Trim.
Quick Start Guide17
(1)
(1)
Description
Upper and lower limit values for system pressure at which OUT1 switches.
Output function for OUT1:
Switching signal for the pressure limit values: hysteresis function (H ..) or
window function (F ..), either normally open (. no) or normally closed (. nc).
• Switching signal for the pressure limit values: hysteresis function (H ..) or
window function (F ..), either normally open (. no) or normally closed (. nc);
(only available for three-wire operation).
• analog signal for the current system pressure: 4-20 mA (I), 20-4 mA (InEG).
Page 18
Operation
January 201900825-0100-4327
OptionDescription
tASPSet analog start point (4 mA if OU2 = I, 20 mA if OU2 = InEG) using an applied
pressure source.
tAEPSet analog end point (20 mA if OU2 = I, 4 mA if OU2 = InEG) using an applied
pressure source.
SP2/rP2
EFExtended functions and opening the extended functions menu (level 2).
(1) Not active in a two-wire operation.
(1)
Upper and lower limit values for system pressure at which OUT2 switches.
Quick Start Guide
3.2.2Extended functions menu
The extended functions menu provides options for configuring pressure transmitter
parameters.
Figure 3-2: Extended functions menu (level 2)
• 1: Change to the main menu
• 2: Change to the simulation menu
Menu items highlighted gray are not available for two-wire operation.
18Quick Start Guide
Page 19
Quick Start GuideOperation
00825-0100-4327January 2019
Table 3-1: Extended functions menu options
OptionDescription
UniStandard unit of measurement for system pressure
SELdDisplay mode:
1. Pressure in the unit set in Uni
2. Pressure in percent of the set scaling of the analog output
ASPAnalog start point for system pressure: measured value at which 4 mA is
provided (20 mA if OU2 = InEG)
AEPAnalog end point for system pressure: measured value at which 20 mA is
provided (4 mA if OU2 = InEG)
HIHighest measured system pressure
LOLowest measured system pressure
COFZero trim
(1)
dS1
(1)
dr1
dS2
(1)
dr2
FOU1
(1)
(1)
Switch-on delay for OUT1
Switch-off delay for OUT1
Switch-on delay for OUT2; only active if OU2 = Hnc, Hno, Fnc or Fno
Switch-off delay for OUT2; only active if OU2 = Hnc, Hno, Fnc or Fno
Status of output 1 in case of an internal fault
FOU2Status of output 2 in case of an internal fault
(1)
P-n
Switching logic for the outputs: pnp or npn
dAPDamping for switching outputs and display
dAADamping for analog output (OUT2)
diSUpdate rate and orientation of the display
CALCalibration function (setting the curve of measured values)
CP1Calibration point 1
CP2Calibration point 2
SIMSwitch to the simulation menu (level 3)
rESRestore factory default settings
(1) Not active in a two-wire operation.
Quick Start Guide19
Page 20
OperationQuick Start Guide
January 201900825-0100-4327
3.2.3Simulation menu
The simulation menu provides options for configuring and executing transmitter
simulations.
Figure 3-3: Simulation menu (SEL=OU)
The options shown appear when SEL is set to OU.
Table 3-2: Simulation menu (SEL=OU)
OptionDescription
SELStatus to be simulated. Output functions OU.
(1)
S.OU1
S.OU2Simulation values for OUT2; only active if SEL = OU.
S.TIMTime for the simulation process in minutes.
S.ONStarts the simulation process.
(1) Not active in two-wire operation
Simulation values for OUT1; only active for three-wire operation and if SEL =
OU.
• OPEN: Output inactive
• CLOS: Output active
• For three-wire operation and if OUT2 has been configured as switching
output: output inactive (OPEN) or active (CLOS).
• If OUT2 is set as an analog output: analog signal between 3.6 and 21.1 mA
During the simulation process the display alternately shows SIM and the
current operation indication.
If the simulation process is aborted, the pressure transmitter displays S.OFF for
two seconds, then SEL is active again.
20Quick Start Guide
Page 21
Quick Start GuideOperation
00825-0100-4327January 2019
Figure 3-4: Simulation menu (SEL = Proc)
The options shown appear when SEL is set to OU.
Table 3-3: Simulation menu (SEL = Proc)
OptionDescription
SELStatus to be simulated: Process value Proc.
S.PrSimulation of a process value; active only if SEL = Proc. Any value between
lower and upper range limits (LRL and URL).
S.TIMTime for the simulation process in minutes.
S.ONStarts the simulation process.
During the simulation process the display alternately shows SIM and the
current operation indication.
If the simulation process is aborted, the pressure transmitter displays S.OFF for
two seconds, then SEL is active again.
3.3Parameter settings
This section provides instructions for modifying parameter values. While modifying
parameter values, the pressure transmitter remains in operating mode. It continues to
monitor pressure levels using the existing parameter values until the new parameter
Quick Start Guide21
Page 22
Operation
January 201900825-0100-4327
values are set. The pressure transmitter changes the parameter values immediately for
COF, CP1, and CP2.
Quick Start Guide
3.3.1Modify parameter settings
Follow these steps to modify parameter values.
Procedure
1. Press Mode/Enter to select a parameter.
2. Press and hold Set.
The pressure transmitter flashes the current value for five seconds.
3. Modify the parameter value.
• Press Set to change the value incrementally.
• Press and hold Set to change the value continuously.
• To reduce the value, continue to press Set until the pressure transmitter reaches
the value limit and restarts at the value minimum.
4. Press Mode/Enter.
The pressure transmitter displays the parameter and saves the new parameter
value.
Switching menu levels
Follow these steps to change from the main menu to the extended functions menu.
Procedure
1. Press Mode/Enter until the pressure transmitter displays EF.
2. Press Set.
The pressure transmitter displays Uni.
3. If the extended menu is locked with an access code, enter the access code.
a) Press Set until the pressure transmitter displays the valid access code.
b) Press Mode/Enter.
By default the extended functions menu is unlocked.
Locking and unlocking the pressure transmitter
Follow these steps to lock or unlock the pressure transmitter. While locked, the pressure
transmitter does not allow parameter values to change and displays Loc if attempted.
Procedure
1. To lock: press and hold Mode/Enter and Set for 10 seconds.
The pressure transmitter locks and displays Loc.
2. To unlock: press and hold Mode/Enter and Set for 10 seconds while the pressure
transmitter is locked.
The pressure transmitter unlocks and displays uLoc.
22Quick Start Guide
Page 23
Quick Start Guide
00825-0100-4327January 2019
Operation
3.3.2Configuring the display
This section provides instructions for changing how the pressure transmitter displays
pressure data.
Change the unit of measurement
Follow these steps to change the unit of measurement in which the pressure transmitter
displays process pressure.
Procedure
1. Select Uni from the extended functions menu.
2. Press and hold Set to modify the parameter value.
3. Select a unit of measurement.
• For bar or mbar, select bAr or mbAr
• For mPa or kPa, select MPA or kPA
• For psi, select PSI (only available with pressure ranges 3A, 5A, 6A, 8A, 1B, 2B)
• For InH2O, select IH2O (only available with pressure ranges 1A, 2A, 3A, 5A, 2B)
• For mWS, select mWS (only available with pressure ranges 3A, 5A, 2B)
• For mmWS, select mmWS (only available with pressure ranges 1A, 2A)
4. Press Mode/Enter.
Change the indication type
Follow these steps to change how the pressure transmitter displays pressure level.
Procedure
1. Select SELd from the extended functions menu.
2. Press and hold Set to modify the parameter value.
3. Select a type of indication.
• P: system pressure in the unit set in Uni.
• P%: system pressure in percent of the set scaling of the analog output; the
following applies: 0% = ASP value ; 100% = AEP value. If OU2 is configured as
switching output, ASP and AEP are not active. In this case the following applies:
0% = lower range limit (LRL) / 100% = upper range limit (URL).
4. Press Mode/Enter.
Note
Pressure may still be applied to the system if the pressure transmitter shows 0%
pressure.
Quick Start Guide23
Page 24
Operation
January 201900825-0100-4327
Quick Start Guide
Change the update rate and display orientation
The update rate sets how often the pressure transmitter displays new data. The diS
parameter also sets the orientation of the display. Follow these steps to change the update
rate and orientation of the display.
Procedure
1. Select diS from the extended functions menu.
2. Press and hold Set to modify the parameter value.
3. Select an update rate or an update rate with a rotated display.
• d1: Updates the measured values every 50 ms.
• d2: Updates the measured values every 200 ms.
• d3: Updates the measured values every 600 ms.
• rd1, rd2, rd3: Rotates the display by 180° and selects the corresponding update
rate.
• OFF: Deactivates the display while in run mode. When a button is pressed, the
pressure transmitter displays the system pressure for 15 seconds. Pressing
Mode/Enter again activates the display. The LED indicators remain active when
the display is deactivated. Also, the pressure transmitter displays error messages
when the display is deactivated.
3.3.3
Set output signals
This section provides instructions for setting output functions and limits.
Setting output functions
Follow these steps to set the function of output 1 and output 2.
Procedure
1. Select OU1 from the menu.
2. Press and hold Set to modify the parameter value.
3. Set the switching function.
• Hno: hysteresis function/NO
• Hnc: hysteresis function/NC
• Fno: window function/NO
• Fnc: window function/NC
4. Press Mode/Enter.
5. Select OU2 from the menu.
6. Press and hold Set to modify the parameter value.
7. Set the function.
• Hno: hysteresis function/NO
24Quick Start Guide
Page 25
Quick Start Guide
00825-0100-4327January 2019
• Hnc: hysteresis function/NC
• Fno: window function/NO
• Fnc: window function/NC
• I: current signal proportional to pressure 4-20 mA
• InEG: current signal proportional to pressure 20-4 mA
8. Press Mode/Enter.
Operation
Set switching limits
Follow these steps to set the limits that cause the outputs to switch.
Procedure
1. Select SP1 or SP2 from the menu.
2. Press and hold Set to modify the parameter value.
3. Set the limit at which the output switches.
4. Press Mode/Enter.
5. Select rP1 or rP2 from the menu.
6. Press and hold Set to modify the parameter value.
7. Set the limit at which the output resets.
The rPx value is always lower than SPx. The pressure transmitter accepts only values
lower than the value for SPx.
8. Press Mode/Enter.
Automatically scale the analog output
Follow these steps to set the start and end value of the analog output to the current
system pressure reading. If the automatic setting is invalid, the pressure transmitter
displays UL or OL. After acknowledging an incorrect value, the pressure senor displays Err
and does not accept the incorrect value.
Procedure
1. Set the minimum pressure requested in the system.
a) Select tASP from the menu.
b) Press and hold Set.
The display flashes the current set value.
c) Release Set when the value stops flashing.
The pressure transmitter displays the new value.
d) Press Mode/Enter.
The current system pressure is defined as the start value for the analog
signal.
2. Set the maximum pressure requested in the system.
a) Select tAEP from the menu.
Quick Start Guide25
Page 26
Operation
January 201900825-0100-4327
b) Press and hold Set.
The current value flashes on the display.
c) Release Set when the value stops flashing.
The pressure transmitter displays the new value.
d) Press Mode/Enter.
The pressure transmitter sets the current system pressure as the end value
for the analog signal.
Quick Start Guide
Manually scale the analog output
Follow these steps to manually set the start value (ASP) and end value (AEP) for the analog
output. The values for ASP and AEP must be within defined limits.
Procedure
1. Select ASP from the extended functions menu.
2. Press and hold Set to modify the parameter value.
3. Set the measured value at which the pressure transmitter provides 4 mA (20 mA if
OU2 = InEG).
4. Select AEP from the extended functions menu.
5. Press and hold Set to modify the parameter value.
6. Set the measured value at which the pressure transmitter provides 20 mA (4 mA if
OU2 = InEG).
3.3.4
Note
The minimum distance between ASP and AEP must be 25 percent of the upper
range limit (maximum rangedown is 4:1).
Optional settings
This section provides instructions for modifying optional settings. Modification of these
settings is not required for normal operation of the pressure transmitter.
Perform manual zero trim
Follow these steps to manually scale the pressure offset by +/-5 percent. Use this after
installation to trim out any measurement offsets because of mounting effects.
Procedure
1. Select COF from the extended functions menu.
2. Press and hold Set to modify the parameter value.
3. Set the value between -5% and 5%.
The pressure transmitter modifies the measured pressure by this value.
26Quick Start Guide
Page 27
Quick Start GuideOperation
00825-0100-4327January 2019
Perform an automatic zero trim
Follow these steps to automatically scale the pressure offset by +/-5 percent. Use this after
installation to trim out any measurement offsets because of mounting effects.
Prerequisites
Ensure no pressure is applied to the pressure transmitter.
Procedure
1. Select tCOF from the menu.
2. Press and hold Set.
The current offset value appears then the current system pressure appears.
3. Release Set.
4. Press Mode/Enter to confirm the new offset value.
Setting output reaction to fault conditions
Follow these steps to modify how the outputs react to fault conditions.
Procedure
1. Select FOU1 from the extended functions menu.
2. Press and hold Set to modify the parameter value.
3. Set the value for output 1.
• On: output 1 switches on in case of a fault.
• OFF: output 1 switches off in case of a fault.
• OU: output 1 switches irrespective of a fault as defined by parameters SP1, rP1
und OU1.
4. Select FOU2 from the extended functions menu.
5. Press and hold Set to modify the parameter value.
6. Set the value for output 2.
• On: output 2 switches on in case of a fault, the analog signal goes to the upper
final value.
• OFF: output 2 switches off in case of a fault, the analog signal goes to the lower
final value.
• OU: output 2 switches irrespective of the fault as defined by parameters SP2,
rP2, OU2. The analog signal corresponds to the measured value.
Postrequisites
For more information on error messages, see Error messages.
Quick Start Guide27
Page 28
Operation
January 201900825-0100-4327
Quick Start Guide
Setting a delay for the switching outputs
Follow these steps to modify the time before an output switches after a fault. The
maximum delay time is 50 seconds.
Procedure
1. Select the switch-on delay parameter for the output from the extended functions
menu.
• Select dS1 to modify the switch-on delay for OUT1.
• Select dS2 to modify the switch-on delay for OUT2.
2. Press and hold Set to modify the parameter value.
3. Set the value between 0.1 and 50 seconds.
4. Select the switch-off delay parameter for the output from the extended functions
menu.
• Select dr1 to modify the switch-off delay for OUT1.
• Select dr2 to modify the switch-off delay for OUT2.
5. Press and hold Set to modify the parameter value.
6. Set the value between 0.1 and 50 seconds.
Setting the value to 0.0 deactivates the delay.
Setting the output logic for the switching outputs
Follow these steps to change the output logic for the switching outputs.
Procedure
1. Select P-n from the extended functions menu.
2. Press and hold Set to modify the parameter value.
3. Set the parameter to PnP or nPn.
4. Press Mode/Enter.
Setting damping for the switching signal
Damping the switching signal prevents the outputs from erroneously switching because of
erratic pressure readings. The damping value is the response time in seconds between
pressure change and change to the switching status. The damping value also influences
the value displayed on the pressure transmitter and the switching frequency (fmax = 1 ÷
2dAP).
Procedure
1. Select dAP from the extended functions menu.
2. Press and hold Set to modify the parameter value.
3. Set the value between 0.0 and 30 seconds.
A value of 0.0 seconds deactivates damping.
4. Press Mode/Enter.
28Quick Start Guide
Page 29
Quick Start Guide
00825-0100-4327January 2019
Operation
Setting a damping for the analog signal
Damping the analog signal prevents the 4-20 mA output from erroneously changing
because of erratic pressure readings. The analog damping value is the response time in
seconds between pressure change and the change of the analog signal.
Procedure
1. Select dAA from the extended functions menu.
2. Press and hold Set to modify the parameter value.
3. Set a value between 0.01 and 99.99 seconds.
A value of 0.0 seconds deactivates damping.
4. Press Mode/Enter.
Perform a sensor trim
Follow these steps to perform a sensor trim and calibrate the pressure transmitter
measurement.
Procedure
1. Apply a defined reference pressure to the transmitter between ASP and AEP.
2. Select CAL from the menu.
3. Press Set.
The pressure transmitter displays CP1.
4. Press and hold Set for five seconds.
The pressure transmitter displays the current pressure measurement.
5. Press Set until the pressure transmitter displays the reference pressure.
The pressure output can change by up to two percent of the upper range limit.
6. Press Mode/Enter.
The pressure transmitter displays CP1.
7. Press Mode/Enter again.
The pressure transmitter displays CP2.
8. To apply a second point on the curve or measured values, apply a second defined
reference pressure to the transmitter.
The minimum distance between the calibration points CP1 and CP2 is five percent
of the upper range limit.
9. Press and hold Set for five seconds.
The pressure transmitter displays the current pressure measurement.
10. Press Set until the pressure transmitter displays the reference pressure or the
corresponding analog signal is provided on OUT2.
The pressure output can change by up to two percent of the upper range limit.
11. Press Mode/Enter.
The pressure transmitter displays CP2.
12. Press Mode/Enter again.
The pressure transmitter displays CAL.
Quick Start Guide29
Page 30
Operation
January 201900825-0100-4327
Quick Start Guide
3.3.5Service fuctions
This section provides instructions for viewing and managing parameters.
View the highest and lowest measured pressure
The pressure transmitter saves the highest and lowest measured preasure values. Follow
these steps to view the highest and lowest pressure values previously measured by the
pressure transmitter.
Procedure
1. To view the maximum pressure value, select HI from the extended functions menu.
2. To view the minimum pressure value, select LO from the extended functions menu.
Deleting high and low pressure memory
Follow these steps to clear the highest and lowest pressure readings on the pressure
transmitter.
Procedure
3.3.6
1. Select HI or LO from the extended functions menu.
2. Press and hold Set until the pressure transmitter displays ---.
3. Press Mode/Enter.
Resetting all parameters to factory default settings
Follow these steps to reset all of the parameters to the factory default settings.
Prerequisites
Before resetting the parameters, record the current parameters using Factory settings.
Procedure
1. Select rES from the extended functions menu.
2. Press and hold Set until the pressure transmitter displays ---.
3. Press Mode/Enter.
Simulation function
During a simulation, the pressure transmitter replicates error conditions for testing
purposes. This section includes instructions for using the simulation function.
Open the simulation menu
Open the simulation menu to view simulation options and parameters.
Procedure
1. Select EF from the menu.
2. Press Set.
30Quick Start Guide
Page 31
Quick Start Guide
00825-0100-4327January 2019
The extended functions menu opens.
3. Select SIM from the menu.
4. Press Set.
The simulation menu opens. The first option is SEL.
Operation
Set the simulation output state
Follow these steps to set the output state for a simulation.
Procedure
1. Select SEL from the simulation menu.
2. Press and hold Set to change the simulation menu to OU.
3. For three-wire operation, select S.OU1 from the simulation menu.
For two-wire operation, skip to step Step 6.
4. Press and hold Set to set the value.
• OPEN: output 1 not active/open
• CLOS: output 1 active/closed
5. Press Mode/Enter.
6. Select S.OU2 from the simulation menu.
7. Press and hold Set to set the value.
• If OU2 = Hnc, Hno, Fnc or Fno (not in two-wire operation):
— OPEN: output 2 not active/open.
— CLOS: output 2 active/closed.
• If OU2 = I or InEG:
— 3.60-21.10 mA in steps of 0.01 mA.
8. Press Mode/Enter.
Set the simulation pressure value
The pressure transmitter will display the simulation pressure value during the simulation.
Follow these steps to set the pressure value for the simulation.
Procedure
1. Select SEL from the simulation menu.
2. Press and hold Set to change the simulation menu to Proc.
3. Press Mode/Enter.
The pressure transmitter displays S.Pr.
4. Select S.Pr from the simulation menu.
5. Press and hold Set to modify the pressure value.
6. Press Mode/Enter.
Quick Start Guide31
Page 32
OperationQuick Start Guide
January 201900825-0100-4327
Set simulation duration
Follow these steps to set the duration of the simulation. Simulations can run between 1-60
minutes.
Procedure
1. Select S.TIM from the simulation menu.
2. Press and hold Set to modify the parameter value.
3. Set the duration value between 1-60 minutes.
4. Press Mode/Enter.
Start a simulation
Follow these steps to start a simulation.
Prerequisites
Set the simulation parameters.
Procedure
1. Select S.ON from the simulation menu.
2. Press and hold Set until the pressure transmitter displays SIM and the current
operating indicator.
Current operation indications include:
• Current system pressure if SEL = OU.
• Simulated measured value set in S.Pr if SEL = Proc.
The simulation runs until the set duration time elapses. Then, the pressure transmitter
displays S.OFF then SEL.
Abort a simulation
Follow these steps to stop a simulation before the duration time elapses.
Procedure
Press Mode/Enter or Set.
The pressure transmitter displays S.OFF for two seconds then displays SEL.
32Quick Start Guide
Page 33
Quick Start GuideSetting ranges
00825-0100-4327January 2019
4Setting ranges
This section contains the minimum and maximum settings for the specified parameters by
pressure range.
Table 4-1: SP1 and SP2
UnitMinimumMaximumStep increment
Pressure range 1A
inH2O-1.9240.000.04
mbar-4.899.50.1
kPa-0.489.950.01
mmWS-4910161
Pressure range 2A
inH2O-4.8100.00.1
mbar-12.0248.80.2
kPa-1.2024.880.02
mmWS-12225402
Pressure range 3A
psi-14.4514.500.05
inH20-4004011
mbar-99810001
kPa-99.8100.00.1
mWS-10.1810.200.01
Pressure range 2B
psi-0.7014.500.01
inH2O-19.2401.60.4
mbar-4810001
kPa-4.8100.00.1
mWS-0.4910.200.01
Pressure range 4A
psi-1.420.000.02
inH2O-39637.00.5
mbar-9615862
kPa-9.6158.60.2
mWS-0.9816.10.02
Quick Start Guide33
Page 34
Setting rangesQuick Start Guide
January 201900825-0100-4327
Table 4-1: SP1 and SP2 (continued)
UnitMinimumMaximumStep increment
Pressure range 5A
psi-1.7436.000.03
inH2O-489971
bar-0.1202.4820.002
kPa-12.0248.20.2
mWS-1.2225.310.01
Pressure range 6A
psi-14.3555.000.05
bar-0.9903.790.005
kPa-99.0379.00.5
Pressure range 7A
psi-14.485.00.1
bar-0.995.8600.005
kPa-99.0586.00.5
Pressure range 8A
psi-14.2145.00.1
bar-0.9810.000.01
MPa-0.0981.0000.001
Pressure range 9A
psi-14.2230.00.2
bar-0.9815.860.02
MPa-0.0981.5860.002
Pressure range 1B
psi-13.8360.00.3
bar-0.9624.820.02
MPa-0.0962.4820.002
Table 4-2: rP1 and rP2
UnitMinimumMaximumStep increment
Pressure range 1A
inH2O-2.0039.920.04
mbar-5.099.30.1
kPa-0.509.930.01
mmWS-5110141
34Quick Start Guide
Page 35
Quick Start GuideSetting ranges
00825-0100-4327January 2019
Table 4-2: rP1 and rP2 (continued)
UnitMinimumMaximumStep increment
Pressure range 2A
inH2O-5.099.80.1
mbar-12.4248.40.2
kPa-1.2424.840.02
mmWS-12625362
Pressure range 3A
psi-14.5014.450.05
inH2O-4014001
mbar-10009981
kPa-100.099.80.1
mWS-10.2010.180.01
Pressure range 2B
psi-0.7314.470.01
inH2O-20.0400.80.4
mbar-509981
kPa-5.099.80.1
mWS-0.5110.180.01
Pressure range 4A
psi-1.4419.960.02
inH2O-406360.5
mbar-10015822
kPa-10.0158.20.2
mWS-1.0216.060.02
Pressure range 5A
psi-1.8035.940.03
inH2O-509951
bar-0.1242.4780.002
kPa-12.4247.80.2
mWS-1.2625.290.01
Pressure range 6A
psi-14.5054.90.05
bar-1.0003.780.005
kPa-100.03780.5
Quick Start Guide35
Page 36
Setting rangesQuick Start Guide
January 201900825-0100-4327
Table 4-2: rP1 and rP2 (continued)
UnitMinimumMaximumStep increment
Pressure range 7A
psi-14.584.80.1
bar-1.05.850.005
kPa-100.0585.00.5
Pressure range 8A
psi-14.5144.70.1
bar-1.009.980.01
MPa-0.1000.9980.001
9A
psi-14.6229.60.2
bar-1.015.820.02
MPa-0.11.5820.002
Pressure range 1B
psi-14.4359.40.3
bar-1.0024.780.02
MPa-0.1002.4780.002
Table 4-3: ASP
UnitMinimumMaximumStep increment
Pressure range 1A
inH2O-2.0030.000.04
mbar-5.074.60.1
kPa-0.507.460.01
mmWS-517621
Pressure range 2A
inH2O-5.075.00.1
mbar-12.4186.60.2
kPa-1.2418.660.02
mmWS-12619042
Pressure range 3A
psi-14.507.250.05
inH2O-4012011
mbar-10005001
kPa-100.050.00.1
36Quick Start Guide
Page 37
Quick Start GuideSetting ranges
00825-0100-4327January 2019
Table 4-3: ASP (continued)
UnitMinimumMaximumStep increment
mWS-10.205.100.01
Pressure range 2B
psi-0.7310.880.01
inH2O-20.0301.20.4
mbar-507501
kPa-5.075.00.1
mWS-0.517.650.01
Pressure range 4A
psi-1.4615.000.02
inH2O-40477.50.5
mbar-10011882
kPa-10.0118.80.2
mWS-1.0212.060.02
Pressure range 5A
psi-1.8027.000.03
inH2O-507471
bar-0.1241.8600.002
kPa-12.4186.00.2
mWS-1.2618.980.01
Pressure range 6A
psi-14.5041.250.05
bar-1.0002.8400.005
kPa-100.0284.00.5
Pressure range 7A
psi-14.563.70.1
bar-1.04.3950.005
kPa-100.0439.50.5
Pressure range 8A
psi-14.5108.70.1
bar-1.007.500.01
MPa-0.1000.7500.001
Pressure range 9A
psi-14.6172.40.2
Quick Start Guide37
Page 38
Setting rangesQuick Start Guide
January 201900825-0100-4327
Table 4-3: ASP (continued)
UnitMinimumMaximumStep increment
bar-1.011.880.02
MPa-0.11.190.002
Pressure range 1B
psi-14.4270.00.3
bar-1.0018.580.02
MPa-0.1001.8620.002
Table 4-4: AEP
UnitMinimumMaximumStep increment
Pressure range 1A
inH2O8.00400.04
mbar19.995.50.1
kPa1.999.950.01
mmWS20310161
Pressure range 2A
inH2O20.01000.1
mbar49.8248.80.2
kPa4.9824.880.02
mmWS51025402
Pressure range 3A
psi-7.2514.500.05
inH2O-2014011
mbar-50010001
kPa-50.0100.00.1
mWS-5.1010.200.01
Pressure range 2B
psi2.9014.500.01
inH2O80.4401.60.4
mbar20010001
kPa20.0100.00.1
mWS2.0410.200.01
Pressure range 4A
psi3.54200.02
inH2O199.56370.5
38Quick Start Guide
Page 39
Quick Start GuideSetting ranges
00825-0100-4327January 2019
Table 4-4: AEP (continued)
UnitMinimumMaximumStep increment
mbar29815862
kPa29.8158.60.2
mWS3.0216.10.02
Pressure range 5A
psi7.20360.03
inH2O2009971
bar0.4982.4820.002
kPa49.8248.20.2
mWS5.0725.310.01
Pressure range 6A
psi-0.75550.05
bar-.0503.790.005
kPa-5.03790.5
Pressure range 7A
psi6.8850.1
bar0.4655.860.005
kPa46.55860.5
Pressure range 8A
psi21.8145.00.1
bar1.5010.000.01
MPa0.1501.0000.001
Pressure range 9A
psi43.02300.2
bar2.9815.860.02
MPa0.2981.5860.002
Pressure range 1B
psi75.6360.00.3
bar5.2024.820.02
MPa0.5222.4820.002
Quick Start Guide39
Page 40
Setting rangesQuick Start Guide
January 201900825-0100-4327
40Quick Start Guide
Page 41
Quick Start GuideTroubleshooting
00825-0100-4327January 2019
5Troubleshooting
The pressure transmitter monitors itself for issues then reports the issues using the
display. If the pressure transmitter detects a fault, it will react according to FOU1 and
FOU2. Use the information in this section to identify and resolve common issues with the
pressure transmitter.
5.1Error messages
Use the information in the table below to resolve errors with the pressure transmitter.
DisplayDescriptionCorrective actions
OffThe supply voltage is too low (fault
number W403).
PARAThe parameter setting is outside the
permitted range.
E100The pressure transmitter detected an
internal error.
5.2Warning messages
Use the information in the table below to resolve issues indicated by warning messages
with the pressure transmitter.
Display
SC1OUT1 FlashesExcessive current switching
SC2OUT2 FlashesExcessive current switching
LED StatusDescriptionCorrective actions
output 1.
output 2.
• Check and/or correct the supply
voltage.
• In a two-wire operation, check
and/or correct the connected
load.
Reset the parameter.
Replace the pressure transmitter.
Check switching output 1 for a
short circuit or excessive
current then remove the fault.
Check switching output 2 for a
short circuit or excessive
current then remove the fault.
SCOUT1 and
OUT2 are
flashing
OLThe measured value is more
ULThe measured value is more
Quick Start Guide41
Excessive current switching
output 1 and switching output
2.
than five percent above the
upper range limit (URL).
than five percent below the
lower range limit (LRL).
Check switching output 1 and 2
for a short circuit or excessive
current then remove the fault.
Check the system pressure and
correct it if necessary.
Check the system pressure and
correct it if necessary.
Page 42
TroubleshootingQuick Start Guide
January 201900825-0100-4327
DisplayLED StatusDescriptionCorrective actions
W531The analog output is at the
upper limit (20.5 mA).
LocThe pressure transmitter does
not allow parameter settings to
change because the buttons
are locked.
W530The analog output is at the
lower limit (3.8 mA).
W532The load at the analog output is
too high
(1)
W203The pressure transmitter
encountered an error during
the temperature compensation
of the pressure measurement
which can result in reduced
accuracy.
W703The medium temperature is
above 302 °F (150 °C)
W704The medium temperature is
below -22°F (-30°C).
Increase the AEP value if
possible (for OU2 = InEG,
increase ASP value) or reduce
the system pressure.
Unlock the buttons.(Locking
and unlocking the pressure
transmitter)
Reduce the ASP value (for OU2
= InEG increase AEP value) or
increase the system pressure.
Reduce the load at output 2 or
increase the supply voltage.
Replace the pressure
transmitter.
Reduce the medium
temperature.
Increase the medium
temperature.
W161The pressure transmitter
temperature is above 194°F
Remove any insulation around
the pressure transmitter.
(90°C).
W162The pressure transmitter
temperature is below -22°F
Insulate the pressure
transmitter.
(-30°C).
(1) The pressure transmitter displays this message only for a three-wire operation. For two-wire
operation, it detects and displays under voltage. If the pressure transmitter does not use OU2 for
the application, avoid the message by defining a switching function for OU2
42Quick Start Guide
Page 43
Quick Start GuideProduct certifications
00825-0100-4327January 2019
6Product certifications
6.1European directive information
The most recent revision of the EC Declaration of Conformity can be found at
Emerson.com/Rosemount.
6.2Ordinary location information
As standard, this product has been examined and tested to determine that the design
meets the basic electrical, mechanical, and fire protection requirements by a nationally
recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and
Health Administration (OSHA).
6.33-A® certification
This product is authorized to display the 3-A symbol. Ensure gaskets and process
connection accessories selected for installation meet both the application and 3-A
requirements. A certificate of compliance is available at Emerson.com/Rosemount.
6.4Other industry certifications
All Rosemount 326P transmitter surfaces and materials which come into contact with
process medium comply with the following regulations:
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a
trademark and service mark of Emerson Electric Co. Rosemount is mark of one of the
Emerson family of companies. All other marks are the property of their respective owners.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.