By integrating Rosemount pressure transmitters with
the 405 Compact Orifice Series primary element,
Rosemount provides the highest performing DP
Flowmeters. This fully integrated flowmeter
eliminates the need for fittings, tubing, valves,
adapters, manifolds, and mounting brackets, thereby
reducing welding and installation time.
Less Expensive than an Orifice Plate Installation
Direct mounting minimizes total installed cost by
reducing engineering, procurement, labor, and
material expenditures while offering unsurpassed
utility.
Direct Mount
A 3-valve isolation manifold and 1-in (25 mm) thick
wafer-style body allows direct mounting while
eliminating field connections between the process
and the differential pressure-measuring device. The
integral configuration results in a robust, inexpensive,
and easy-to-install assembly.
Accurate and Repeatable
The 405C Conditioning Orifice is ideal for limited pipe
run measurements in gas, liquid, or steam
applications (8-in. (200 mm) nominal diameter and
smaller lines). The 405C Conditioning Orifice delivers
consistent and accurate measurements one would
expect from traditional orifice plate technology.
Centering Mechanism
Improper centering of any orifice type device can
cause an error of up to ±5% in small line sizes. A
centering mechanism independent of flange rating is
standard with the 405 Compact Orifice Series.
Annubar® Flowmeter Series: Rosemount
3051SFA ProBar
and 285
The state-of-the-art, fifth generation Rosemount 485 Annubar
combined with the 3051S or 3095 MultiVariable transmitter creates
an accurate, repeatable and dependable insertion-type flowmeter.
The Rosemount 285 provides a commercial product offering for
your general purpose applications.
Compact Orifice Flowmeter Series: Rosemount
3051SFC, 3095MFC, and 405
Compact Orifice Flowmeters can be installed between existing
flanges, up to a Class 600 (PN100) rating. In tight fit applications,
a conditioning orifice plate version is available, requiring only two
diameters of straight run upstream.
®
, 3095MFA Mass ProBar®, 485,
Based on ASME/ISO Corner Tap Design
The incorporation of design features from proven
standards results in a product that performs in a
predictable manner and operates on well-known
principles.
Advanced PlantWeb
Rosemount orifice flowmeters power
PlantWeb through a scalable
architecture, advanced diagnostics, and
MultiVariable capabilities. This reduces
operational and maintenance
expenditures while improving throughput
and utilities management.
Rosemount DP-Flow Solutions
Integral Orifice Flowmeter Series: Rosemount 3051SFP
ProPlate®, 3095MFP Mass ProPlate, and 1195
These integral orifice flowmeters eliminate the inaccuracies that
become more pronounced in small orifice line installations. The
completely assembled, ready to install flowmeters reduce cost and
simplify installation.
Orifice Plate Primary Element Systems: Rosemount
1495 and 1595 Orifice Plates, 1496 Flange Unions and
1497 Meter Sections
A comprehensive offering of orifice plates, flange unions and
meter sections that is easy to specify and order. The 1595
Conditioning Orifice provides superior performance in tight fit
applications.
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
®
Functionality
2
Product Data Sheet
Rosemount 3051SFC Compact Orifice Flowmeter
See ordering information on page 16.
•Combines the Rosemount 3051S scalable pressure
transmitter with the 405 Compact Orifice Primary
•Accuracy up to ±0.80% of volumetric rate
•Remote display and interface assembly enables direct mounting
with “at-grade” operator interface
•F
OUNDATION
®
fieldbus protocol available
•Ideal fluid type: liquid
Rosemount 3095MFC Compact Orifice Mass Flowmeter
See ordering information on page 29.
•Combines the Rosemount 3095MV MultiVariable
mass flow transmitter with the 405 Compact Orifice Primary
•Accuracy up to ±0.70% of mass flow rate
•Measures differential pressure, static pressure,
and process temperature (remotely) all in one flowmeter assembly
•Dynamically calculates compensated mass flow
•Ideal fluid types: gas and steam
Rosemount 405 Compact Orifice Primary
See ordering information on page 38.
•Integral manifold head allows direct
mounting of DP transmitters
•Ideal fluid types: liquid, gas, and steam
•Accuracy up to ±0.5% of discharge coefficient uncertainty
(4) For 0.65 beta and ReD< 10,000 add an additional ± 0.5% to the
(1)
(2)
(3)
Discharge Coefficient Uncertainty.
0.4
0.65
0.4
0.65
0.4
0.65
0.4
0.65
turndown)
±1.05%
±1.35%
±2.45%±2.35%±2.30%
(4)
±2.00%±1.90%±1.85%
(4)
±1.55%±1.45%±1.40%
(4)
Ultra
(8:1 flow
turndown)
±0.85%
±1.20%
Repeatability
±0.1%
Ultra for
(14:1 flow
turndown)
±0.80%
±1.15%
Functional
Service
• Liquid
•Gas
•Steam
Flow
4–20 mA/HART
Zero and Span Adjustment
Zero and span values can be set anywhere within the range.
Span must be greater than or equal to the minimum span.
Output
Two-wire 4–20 mA is user-selectable for linear or square root
output. Digital process variable superimposed on 4–20 mA
signal, available to any host that conforms to the HART
protocol.
Power Supply
External power supply required.
Standard transmitter (4–20 mA): 10.5 to 42.4 V dc with no load
3051S HART Diagnostics transmitter: 12 to 42 Vdc with no load
Line Sizes
•1/2-in. (15 mm) – not available for the 3051SFCC
• 1-in. (25 mm) – not available or the 3051SFCC
1
/2-in. (40 mm) – not available for the 3051SFCC
•1
• 2-in. (50 mm)
• 3-in. (80 mm)
• 4-in. (100 mm)
• 5-in (125 mm)
• 6-in. (150 mm)
• 8-in. (200 mm)
• 10-in. (250 mm)
• 12-in (300 mm)
Performance Statement Assumptions
• Measured pipe I.D
Sizing
Contact an Emerson Process Management representative for
assistance. A Configuration Data Sheet is required prior to order
for application verification.
4
Product Data Sheet
Voltage (V dc)
Load (Ohms)
Operating
Region
1387
1000
500
0
10.5 2030
42.4
Voltage (V dc)
Load (Ohms)
Operating
Region
1322
1000
500
0
12.0 2030
42.4
00813-0100-4810, Rev HA
March 2008
Rosemount Compact Orifice
Flowmeter Series
Load Limitations
Maximum loop resistance is determined by the voltage level of
the external power supply, as described by:
Standard Transmitter
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 10.5)
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 12.0)
The HART communicator requires a minimum
loop resistance of 250Ω for communication.
ASP™ Diagnostics Suite for HART (Option Code DA1)
The 3051S provides Abnormal Situation Prevention indication
for a breakthrough in diagnostic capability. The New 3051S
ASP™ Diagnostics Suite for HART includes Statistical
Process Monitoring (SPM), variable logging with time stamp
and advanced process alerts. The enhanced EDDL graphic
display provides an intuitive and user-friendly interface to
better visualize these diagnostics.
The integral SPM technology calculates the mean and
standard deviation of the process variable 22 times per
second and makes them available to the user. The 3051S
uses these values and highly flexible configuration options for
customization to detect many user-defined or application
specific abnormal situations (e.g. detecting plugged impulse
lines and fluid composition change). Variable logging with time
stamp and advanced process alerts capture valuable process
and sensor data to enable quick troubleshooting of application
and installation issues.
FOUNDATION fieldbus
Power Supply
External power supply required; transmitters operate on 9.0 to
32.0 V dc transmitter terminal voltage.
Current Draw
17.5 mA for all configurations (including LCD display option)
• Contains hardware, electronics, and diagnostic information.
Transducer Block
• Contains actual sensor measurement data including the
sensor diagnostics and the ability to trim the pressure
sensor or recall factory defaults.
LCD Block
• Configures the local display.
2 Analog Input Blocks
• Processes the measurements for input into other function
blocks. The output value is in engineering or custom units
and contains a status indicating measurement quality.
PID Block with Auto-tune
• Contains all logic to perform PID control in the field including
cascade and feedforward. Auto-tune capability allows for
superior tuning for optimized control performance.
Backup Link Active Scheduler (LAS)
The transmitter can function as a Link Active Scheduler if the
current link master device fails or is removed from the
segment.
Software Upgrade in the Field
Software for the 3051S with F
upgrade in the field using the F
Device Software Download procedure.
PlantWeb Alerts
Enable the full power of the PlantWeb digital architecture by
diagnosing instrumentation issues, communicating advisory,
maintenance, and failure details, and recommending a
solution.
Advanced Control Function Block Suite
(Option Code A01)
Input Selector Block
• Selects between inputs and generates an output using
specific selection strategies such as minimum, maximum,
midpoint, average, or first “good.”
Arithmetic Block
• Provides pre-defined application-based equations including
flow with partial density compensation, electronic remote
seals, hydrostatic tank gauging, ratio control and others.
Signal Characterizer Block
• Characterizes or approximates any function that defines an
input/output relationship by configuring up to twenty X, Y
coordinates. The block interpolates an output value for a
given input value using the curve defined by the configured
coordinates.
Integrator Bock
• Compares the integrated or accumulated value from one or
two variables to pre-trip and trip limits and generates
discrete output signals when the limits are reached. This
block is useful for calculating total flow, total mass, or
volume over time.
OUNDATION fieldbus is easy to
OUNDATION fieldbus Common
5
Rosemount Compact Orifice
Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Output Splitter Block
• Splits the output of one PID or other control block so that the
PID will control two valves or other actuators.
Control Selector Block
• Selects one of up to three inputs (highest, middle, or lowest)
that are normally connected to the outputs of PID or other
control function blocks.
BlockExecution Time
ResourceTransducerLCD BlockAnalog Input 1, 220 milliseconds
PID with Auto-tune35 milliseconds
Input Selector20 milliseconds
Arithmetic20 milliseconds
Signal Characterizer20 milliseconds
Integrator20 milliseconds
Output Splitter20 milliseconds
Control Selector20 milliseconds
Fully Compensated Mass Flow Block (Option Code H01)
Calculates fully compensated mass flow based on differential
pressure with external process pressure and temperature
measurements over the fieldbus segment. Configuration for the
mass flow calculation is easily accomplished using the
Rosemount 3095 Engineering Assistant.
ASP™ Diagnostics Suite for F
Code D01)
The 3051S ASP™ Diagnostics Suite for F
provides Abnormal Situation Prevention indication and enhanced
EDDL graphic displays for easy visual analysis.
The integral Statistical Process Monitoring (SPM) technology
calculates the mean and standard deviation of the process
variable 22 times per second and makes them available to the
user. The 3051S uses these values and highly flexible
configuration options for customization to detect many
user-defined or application specific abnormal situations (e.g.
detecting plugged impulse lines and fluid composition change).
OUNDATION fieldbus (Option
OUNDATION fieldbus
Process Temperature Limits
Direct Mount Transmitter
• 450 °F (232 °C)
Remote Mount Transmitter
• 850 °F (454 °C) – Stainless Steel
Transmitter Temperature Limits
Ambient
• –40 to 185 °F (–40 to 85 °C)
• With Integral Display
Storage
• –50 to 230 °F (–46 to 110 °C)
• With Integral Display: –40 to 185 °F (–40 to 85 °C)
• With Wireless Output (Code X): –40 to 185 °F (–40 to 85 °C)
(1)
: –40 to 175 °F (–40 to 80 °C)
Differential Pressure Limits
Maximum differential pressure (DP) up to 800 inH2O.
Pressure Limits
Direct Mount Transmitter
• Pressure retention per ANSI B16.5 600# or DIN PN
(2)
Static Pressure Limits
• Range 1A: Operates within specification between static line
pressures of 0.5 psia to 2000 psig (0.03 to 138 bar)
• Ranges 2A– 3A: Operates within specifications between
static line pressures of 0.5 psia and 3626 psig (0.03 bar-A to
250 bar-G)
Vibration Limits
Qualified per IEC61298-3 (1998) for field with high vibration level or
pipeline with high vibration level (10-60Hz 0.21mm displacement
peak amplitude / 60 - 500Hz 3g).
The weight and length of the transmitter assembly shall not exceed
5.8 lbs and 7.75-in.
Burst Pressure Limits
Coplanar or traditional process flange
• 10000 psig (689,5 bar)
Wireless Self-Organizing Networks
Output
Wireless enabled HART.
Transmit Rate
User selectable, 15 sec. to 60 min.
Power Module
Replaceable, Intrinsically Safe Lithium-thionyl chloride Power
Module with polybutadine terephthalate (PBT) enclosure.
Five-year life at one minute transmit rate: ten-year life at ten
minute transmit rate.
(1) Reference conditions are 70 °F (21 °C), and routing data for three
additional network devices.
NOTE
Continuous exposure to ambient temperature limits, -40 °F (-40
°C) or 185 °F (85 °C), may reduce specified life by less than 20
percent.
6
(1)
(1) LCD display may not be readable and LCD updates will be
slower at temperatures below -4 °F (-20 °C).
(2) Static pressure selection may effect pressure limitations.
Product Data Sheet
T
c
T
d
Td = Dead Time
T
c
= Time Constant
Pressure Released
Response Time = Td+T
c
63.2% of Total
Step Change
Time
0%
100%
36.8%
Transmitter Output vs. Time
00813-0100-4810, Rev HA
March 2008
Rosemount Compact Orifice
Flowmeter Series
Overpressure Limits
Transmitters withstand the following limits without damage:
• Range 1A: 2000 psig (138 bar)
• Ranges 2A–3A: 3626 psig (250 bar)
TABLE 2. Overpressure Limits
StandardTyp e
(1)
Carbon Steel
Rating
Stainless
Steel Rating
ANSI/ASME Class 150285 (20)275 (19)
ANSI/ASME Class 300740 (51)720 (50)
ANSI/ASME Class 6001480 (102)1440 (99)
At 100 °F (38 °C), the rating decreases with increasing temperature.
At 248 °F (120 °C), the rating decreases with increasing temperature.
(1) Carbon Steel and Stainless Steel Ratings are measured in
psig (bar).
Humidity Limits
• 0–100% relative humidity
Turn-On Time
Performance within specifications less than 2 seconds (typical)
after power is applied to the transmitter
Damping
Analog output response to a step input change is user-selectable
from 0 to 60 seconds for one time constant. This software damping
is in addition to sensor module response time
Dynamic Performance
(1)
Failure Mode Alarm
HART 4-20mA (output option codes A and B)
If self-diagnostics detect a gross transmitter failure, the analog
signal will be driven offscale to alert the user. Rosemount
standard (default), NAMUR, and custom alarm levels are
available (see Table 3).
High or low alarm signal is software-selectable or
hardware-selectable via the optional switch (option D1).
TABLE 3. Alarm Configuration
High AlarmLow Alarm
Default≥ 21.75 mA≤ 3.75 mA
NAMUR compliant
Custom levels
(1) Analog output levels are compliant with NAMUR
recommendation NE 43, see option codes C4 or C5.
(2) Low alarm must be 0.1 mA less than low saturation and high
alarm must be 0.1 mA greater than high saturation.
connections fixed to terminal block for output code A
Material of Construction
Body/Plate
•316 SST
• 50 micro-inch Ra surface finish
Manifold Head/Valves
•316 SST
Flange Studs and Nuts
• Customer supplied
• Available as a spare part
Transmitter Connection Studs and Nuts
• Studs– A193 Grade B8M.
• Nuts– A194 Grade 8M.
Gasket and O-rings
• Gaskets are customer supplied.
• Durlon 8500 fiber gaskets are recommended. Consult an
Emerson Process Management representative for use with
other gaskets.
• Available as a spare part
NOTE
Gaskets and O-rings must be replaced when the 405 is
disassembled.
1
/2-in. NPT nipple and union (078
1
/2-in., 1-in.,
Process-Wetted Parts
Integral Manifolds
•316 SST
• Hastelloy C-276
Remote Manifolds
•316 SST
• Hastelloy C-276
Transmitter Vent Valves and Process Flanges
•316 SST
• Hastelloy C-276
• Glass-filled PTFE O-rings
Process Isolating Diaphragms
• 316L SST
• Hastelloy C-276
Integral Manifold O-Rings
• PTFE/Graphite
Non-Wetted Parts
Sensor Module Fill Fluid
• Silicone oil
• Inert Fill optional
Cover O-rings
•Buna-N
Remote Mounting Brackets
• SST
Electronic Housing
• Low copper aluminum, NEMA 4x, IP65
• SST (optional)
Paint
• Polyurethane
Bolts
•CS
Transmitter Connections
Remote Mount
• Available with
connections
Orifice Type
• Square edged, Wafer style
Orifice Pressure Taps
• Corner
1
/4-in. (standard) or 1/2-in. (option code E)
Process Connections
Mounts between the following flange configurations:
ASME B16.5
(ANSI)
Class 150
Class 300
Class 600
ANSI alignment ring is included as standard when ordering.
8
DINJIS
PN16 (option code G)
PN40 (option code H)
PN100 (option code H)
10k (option code B)
20k (option code R)
40k (option code S)
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Rosemount Compact Orifice
Flowmeter Series
Typical Orifice Hole Sizes (For 3051SFCC)
Beta is calculated by: (β) = dC / Pipe ID, where the calculated bore
is equal to 2 x typical orifice hole size (d
shows the diameter of each of the four typical orifice holes.
Improper centering of any orifice type device can cause an error of
up to ±5% in small line sizes. A centering mechanism (centering
ring) independent of flange rating comes standard with the 405
Compact Orifice Series.
10
Liquid (Vertical)
360°
FLOW
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
PRODUCT CERTIFICATIONS
Approved Manufacturing Locations
Rosemount Inc. — Chanhassen, Minnesota USA
Emerson Process Management GmbH & Co. — Wessling,
Germany
Emerson Process Management Asia Pacific Private Limited —
Singapore
Beijing Rosemount Far East Instrument Co., LTD — Beijing, China
European Directive Information
The EC declaration of conformity for all applicable European
directives for this product can be found at www.rosemount.com. A
hard copy may be obtained by contacting an Emerson Process
Management representative.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the
ATEX Directive.
European Pressure Equipment Directive (PED) (97/23/EC)
Models 3051S_CA4; 3051S_CD2, 3, 4, 5; (also with P9 option)
Pressure Transmitters — QS Certificate of Assessment EC No. PED-H-20, Module H Conformity Assessment
All other Model 3051S Pressure Transmitters
— Sound Engineering Practice
Transmitter Attachments: Diaphragm Seal - Process Flange Manifold
Primary Elements, Flowmeter
— See appropriate Primary Element QIG
— Sound Engineering Practice
Electro Magnetic Compatibility (EMC) (89/336/EEC)
All Models: EN 50081-1: 1992; EN 50082-2:1995;
EN 61326-1:1997 – Industrial
Ordinary Location Certification for FM
As standard, the transmitter has been examined and tested to
determine that the design meets basic electrical, mechanical, and
fire protection requirements by FM, a nationally recognized testing
laboratory (NRTL) as accredited by the Federal Occupational
Safety and Health Administration (OSHA).
Hazardous Locations Certifications
North American Certifications
FM Approvals
E5Explosion-proof for Class I, Division 1, Groups B, C, and D;
dust-ignition proof for Class II and Class III, Division 1,
Groups E, F, and G; hazardous locations; enclosure Type
4X, conduit seal not required when installed according to
Rosemount drawing 03151-1003.
Rosemount Compact Orifice
Flowmeter Series
I5/IE Intrinsically Safe for use in Class I, Division 1, Groups A, B,
C, and D; Class II, Division 1, Groups E, F, and G; Class III,
Division 1; Class I, Zone 0 AEx ia IIC when connected in
accordance with Rosemount drawing 03151-1006;
Non-incendive for Class I, Division 2, Groups A, B, C, and D
Enclosure Type 4X
For entity parameters see control drawing 03151-1006.
Canadian Standards Association (CSA)
E6Explosion-proof for Class I, Division 1, Groups B, C, and D;
Dust-Ignition-Proof for Class II and Class III, Division 1,
Groups E, F, and G; suitable for Class I, Division 2, Groups
A, B, C, and D, when installed per Rosemount drawing
03151-1013, CSA Enclosure Type 4X; conduit seal not
required.
I6/IF Intrinsically Safe for Class I, Division 1, Groups A, B, C, and
D when connected in accordance with Rosemount drawings
03151-1016;
For entity parameters see control drawing 03151-1016.
European Certifications
I1/IA ATEX Intrinsic Safety
Certificate No.: BAS01ATEX1303X II 1G
EEx ia IIC T4 (T
Display/Quick Connect/HART Diagnostics
EEx ia IIC T4 (T
EEx ia IIC T4 (T
IP66
118 0
TABLE 8. Input Parameters
Loop / Power Groups
U
= 30 VHART / FOUNDATION fieldbus/ Remote
i
Ui = 17.5 VFISCO
I
= 300 mAHART / FOUNDATION fieldbus/ Remote
i
Ii = 380 mAFISCO
P
= 1.0 WHART / Remote Display / Quick Connect /
i
Pi = 1.3 WFOUNDATION fieldbus
P
= 5.32 WFISCO
i
Ci = 30 nFSuperModule Platform / Quick Connect
C
= 11.4 nFHART / HART Diagnostics
i
Ci = 0FOUNDATION fieldbus / Remote Display /
L
= 0HART / FOUNDATION fieldbus/ FISCO /
i
Li = 60 µHRemote Display
Special conditions for safe use (x)
1. The apparatus, excluding the Types 3051 S-T and 3051
S-C (In-line and Coplanar SuperModules respectively), is
not capable of withstanding the 500V test as defined in
Clause 6.4.12 of EN 50020. This must be considered
during installation.
2. The terminal pins of the Types 3051 S-T and 3051 S-C
must be protected to IP20 minimum.
= -60 °C to 70 °C) -HART/Remote
a
= -60 °C to 70 °C) -FOUNDATION fieldbus
a
= -60 °C to 40 °C) -FISCO
a
Display / Quick Connect / HART
Diagnostics
Display / Quick Connect / HART
Diagnostics
HART Diagnostics
FISCO
Quick Connect / HART Diagnostics
11
Rosemount Compact Orifice
Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
N1ATEX Typ e n
Certificate No.: BAS01ATEX3304X II 3 G
EEx nL IIC T4 (T
Ui = 45 Vdc max
IP66
Special conditions for safe use (x)
The apparatus is not capable of withstanding the 500V
insulation test required by Clause 9.1 of EN 50021: 1999.
This must be taken into account when installing the
apparatus.
ND ATEX Dust
Certificate No.: BAS01ATEX1374X II 1 D
T105°C (-20 °C ≤ T
= 42.4 volts max
V
max
A = 22 mA
IP66
118 0
Special conditions for safe use (x)
1. The user must ensure that the maximum rated voltage
and current (42.4 volts, 22 milliampere, DC) are not
exceeded. All connections to other apparatus or
associated apparatus shall have control over this voltage
and current equivalent to a category “ib” circuit according
to EN 50020.
2. Cable entries must be used which maintain the ingress
protection of the enclosure to at least IP66.
3. Unused cable entries must be filled with suitable blanking
plugs which maintain the ingress protection of the
enclosure to at least IP66.
4. Cable entries and blanking plugs must be suitable for the
ambient range of the apparatus and capable of
withstanding a 7J impact test.
5. The 3051S must be securely screwed in place to maintain
the ingress protection of the enclosure.
E1ATEX Flameproof
Certificate No.: KEMA00ATEX2143X II 1/2 G
EEx d IIC T6 (-50 °C ≤ T
EEx d IIC T5 (-50 °C ≤ T
= 42.4V
V
max
118 0
Special conditions for safe use (x)
This device contains a thin wall diaphragm. Installation,
maintenance and use shall take into account the
environmental conditions to which the diaphragm will be
subjected. The manufacturer’s instructions for installation
and maintenance shall be followed in detail to assure safety
during its expected lifetime. The Model 3051S pressure
transmitter must include a Series 300S housing integrally
mounted to a Series Model 3051S Sensor module as per
Rosemount drawing 03151-1023.
= -40 °C TO 70 °C)
a
≤ 85 °C)
amb
≤ 65 °C)
amb
≤ 80 °C)
amb
Japanese Certifications
E4TIIS Flameproof
Ex d IIC T6
Certificate Description
TC15682 Coplanar with Junction Box Housing
TC15683Coplanar with PlantWeb Housing
TC15684Coplanar with PlantWeb Housing
TC15685In-Line SST with Junction Box Housing
TC15686In-Line Hastelloy with Junction Box Housing
TC15687In-Line SST with PlantWeb Housing
TC15688In-Line Hastelloy with Plantweb Housing
TC15689In-Line SST with Plantweb Housing
TC15690In-Line Hastelloy with PlantWeb Housing
and LCD Display
and LCD Display
and LCD Display
Australian Certifications
E7SAA Flameproof and Dust Ignition-proof
Certification No.: AUS Ex 3798X
Ex d IIC T6 (T
DIP A21 TA T6 (T
Special conditions for safe use (x)
1. It is a condition of safe use that each housing shall be
connected to external circuits via suitable conduit or
Standards Australia certified cable glands. Where only one
entry is used for connection to external circuits, the unused
entry shall be closed by means of the blanking plug
supplied by the equipment manufacturer or by a suitable
Standards Australia certified blanking plug.
2. It is a condition of safe use that a dielectric strength test
shall be applied whenever the terminal block is changed or
replaced in either the dual compartment or single
compartment housings. The breakdown current shall be
less than 5 mA, when 500 V, 47 to 62 Hz, is applied for one
minute. Note: if tested with an optional T1 transient
protector terminal block fitted, the protection will operate
and hence there will be no current indicated.
3. It is a condition of safe use that each transmitter module
shall be used with a Model 300S housing, in order to
comply with flameproof requirements.
4. It is a condition of safe use that each model 300S housing
fitted with a transmitter module shall be marked with the
same certification marking code information. Should the
housing be replaced after initial supply to another model
300S housing, the replacement housing shall have the
same certification marking code information as the
housing it replaces.
= 60°C) IP66
a
= 60°C) IP66
a
12
Product Data Sheet
µ
00813-0100-4810, Rev HA
March 2008
Rosemount Compact Orifice
Flowmeter Series
IECEx Certifications
I7/IG IECEx Intrinsic Safety
Certificate No.: IECExBAS04.0017X
Ex ia IIC T4 (T
Display/Quick Connect/HART Diagnostics
Ex ia IIC T4 (T
Ex ia IIC T4 (T
IP66
TABLE 9. Input Parameters
Loop / PowerGroups
U
= 30 VHART / FOUNDATION fieldbus/
i
Ui = 17.5 VFISCO
I
= 300 mAHART / FOUNDATION fieldbus/
i
Ii = 380 mAFISCO
P
= 1.0 WHART / Remote Display / Quick
i
Pi = 1.3 WFOUNDATION fieldbus
P
= 5.32 WFISCO
i
Ci = 30 nFSuperModule Platform / Quick
C
= 11.4 nFHART / HART Diagnostics
i
Ci = 0FOUNDATION fieldbus / Remote
= 0HART / FOUNDATION fieldbus /
L
i
Li = 60 HRemote Display
Special conditions for safe use (x)
1. The Models 3051S HART 4-20mA, 3051S fieldbus,
3051S Profibus and 3051S FISCO are not capable of
withstanding the 500V test as defined in clause 6.4.12 of
IEC 60079-11. This must be taken into account during
installation.
2. The terminal pins of the Types 3051S-T and 3051S-C
must be protected to IP20 minimum.
Certificate No.: IECExBAS04.0018X
Ex nC IIC T4 (Ta = -40 °C to 70 °C)
Ui = 45 Vdc MAX
IP66
Special conditions for safe use (x)
The apparatus is not capable of withstanding the 500 V
insulation test required by Clause 8 of IEC 79-15: 1987.
Combinations of Certifications
Stainless steel certification tag is provided when optional approval
is specified. Once a device labeled with multiple approval types is
installed, it should not be reinstalled using any other approval
types. Permanently mark the approval label to distinguish it from
unused approval types.
K1Combination of E1, I1, N1, and ND
K5Combination of E5 and I5
K6Combination of E6 and I6
K7Combination of E7, I7, and N7
KA Combination of E1, I1, E6, and I6
KB Combination of E5, I5, I6 and E6
KC Combination of E5, E1, I5 and I1
KD Combination of E5, I5, E6, I6, E1, and I1
13
Rosemount Compact Orifice
Radio Power Label
Figure 1.
Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
WIRELESS CERTIFICATIONS
Telecommunication Compliance
All wireless devices require certification to ensure that they adhere to
regulations regarding the use of the RF spectrum. Nearly every
country requires this type of product certification. Emerson is working
with governmental agencies around the world to supply fully
compliant products and remove the risk of violating country directives
or laws governing wireless device usage.
FCC and IC Approvals
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following conditions: This device may not cause
harmful interference this device must accept any interference
received, including interference that may cause undesired operation.
This device must be installed to ensure a minimum antenna
separation distance of 20cm from all persons.
Ordinary Location Certification for FM
As standard, the transmitter has been examined and tested to
determine that the design meets basic electrical, mechanical, and fire
protection requirements by FM, a nationally recognized testing
laboratory (NRTL) as accredited by the Federal Occupational Safety
and Health Administration (OSHA).
European Directive Information
The EC declaration of conformity for all applicable European
directives for this product can be found at www.rosemount.com. A
hard copy may be obtained by contacting an Emerson Process
Management representative.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX Directive.
European Pressure Equipment Directive (PED) (97/23/EC)
Models 3051S_CA4; 3051S_CD2, 3, 4, 5; (also with P9 option)
Pressure Transmitters — QS Certificate of Assessment EC No. PED-H-100, Module H Conformity Assessment
All other Model 3051S Pressure Transmitters
— Sound Engineering Practice
Transmitter Attachments: Diaphragm Seal - Process Flange Manifold
Primary Elements, Flowmeter
— See appropriate Primary Element QIG
Electro Magnetic Compatibility (EMC) (2004/108/EC)
All Models: EN 50081-1: 1992; EN 50082-2:1995;
EN 61326-1:1997 + A1, A2, and A3 – Industrial
Radio and Telecommunications Terminal Equipment Directive
(R&TTE)(1999/5/EC)
Emerson Process Management complies with the R&TTE
Directive.
— Sound Engineering Practice
Hazardous Locations Certifications
North American Certifications
Factory Mutual (FM) Approvals
I5 FM Intrinsically Safe, Non-Incendive, and Dust Ignition-proof.
Intrinsically Safe for Class I/II/III, Division 1,
Groups A, B, C, D, E, F, and G.
Zone Marking: Class I, Zone 0, AEx ia llC
Temperature Codes T4 (T
Non-Incendive for Class I, Division 2, Groups A, B, C, and D.
Dust Ignition-proof for Class II/III, Division 1,
Groups E, F, and G.
Ambient temperature limits: -50 to 85° C
For use with Rosemount SmartPower options
00753-9220-XXXX only.
Enclosure Type 4X / IP66
CSA - Canadian Standards Association
I6 CSA Intrinsically Safe
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D.
Temp Code T3C
Enclosure Type 4X / IP66
For use with Rosemount SmartPower options
00753-9220-XXXX only.
European Certifications
I1 ATEX Intrinsic Safety
Certificate No.: BAS01ATEX1303X II 1G
Ex ia IIC T4 (T
IP66
For use with Rosemount SmartPower options
00753-9220-XXXX only.
1180
CountryRestriction
BulgariaGeneral authorization required for outdoor use
FranceOutdoor use limited to 10mW e.i.r.p.
Italy If used outside of own premises, general
NorwayMay be restricted in the geographical area within
RomaniaUse on a secondary basis. Individual license
Radio Power Label (See
Figure 1) indicates output
power configuration of the radio.
Devices with this label are
configured for output power less
than 10 mW e.i.r.p. At time of
purchase the customer must
specify ultimate country of
installation and operation.
= -60 °C to 70 °C)
a
and public service
authorization is required.
a radius of 20 km from the center of Ny-Alesund.
required.
= -50 to 70° C)
amb
14
IECEx Certifications
I7 IECEx Intrinsic Safety
Certificate No.: IECEx BAS 04.0017X
Ex ia IIC T4 (Ta = -60 °C to 70 °C)
For use with Rosemount SmartPower options
00753-9220-XXXX only.
IP66
Product Data Sheet
1.13 (28.7)
1.00 (25.4
C
A
B
1.13 (28.7)
1.00 (25.4
C
00813-0100-4810, Rev HA
March 2008
DIMENSIONAL DRAWINGS
Rosemount 3051SFC Compact Orifice Flowmeter
Orifice Plate Front ViewOrifice Plate Side ViewOrifice Plate Top View
B
A
Compact Orifice Plate
(Primary Element Type code P)
Rosemount Compact Orifice
Flowmeter Series
D
D
(Primary Element Type code C)
Conditioning Orifice Plate
TABLE 10. Dimensional Drawings
Plate TypeABTransmitter HeightCD
Type P and C5.50 (140)Transmitter Height + A7.75 (197)7.75 (197) - closed
(1) Measurement in inches (millimeters).
(1)
8.25 (210) - open
6.00 (152) - closed
6.25 (159) - open
15
Rosemount Compact Orifice
Flowmeter Series
ORDERING INFORMATION
Rosemount 3051SFC Compact Orifice Flowmeter Ordering Information
Safety Certified to IEC 61508 with certificate of FMEDA data
Material Cert per ISO 10474 3.1.B and EN 10204 3.1.B
1
/2-14 NPT
1
/2
1
/2-14 NPT
1
/2-14 NPT
1
/2
1
/2-14 NPT
1
/2-14 NPT
1
/2-14 NPT
17
Rosemount Compact Orifice
Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series
Rosemount 3051SFC Compact Orifice Flowmeter Ordering Information
Code Conformance
J2ANSI B31.1
J3ANSI B31.3
J4ANSI B31.8
Material Conformance
(11)
J5
Country Certification
J1Canadian Registration
Product Certifications
E1ATEX Flameproof
I1ATEX Intrinsic Safety
IEFM FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
IFCSA FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
(1)
IA
N1ATEX Type n
NDATEX Dust
K1ATEX Flameproof, Intrinsic Safety, Type n, Dust (combination of E1, I1, N1, and ND)
E4TIIS Flameproof
E5FM Explosion-proof, Dust Ignition-proof
I5FM Intrinsically Safe, Division 2
K5FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5 and I5)
E6CSA Explosion-proof, Dust Ignition-proof, Division 2
I6CSA Intrinsically Safe
K6CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E6 and I6)
(1)
E7
I7IECEx Intrinsic Safety
IGIECEx FISCO Intrinsic Safety; for FOUNDATION fieldbus protocol only
N7IECEx Type n
K7SAA Flameproof, Dust Ignition-proof, IECEx Intrinsic Safety, Type n (combination of E7, I7, and N7)
KAATEX and CSA Flameproof, Intrinsically Safe, Division 2 (combination of E1, I1, E6, and I6)
KBFM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5, E6, I5, and I6)
KCFM and ATEX Explosion-proof, Intrinsically Safe, Division 2 (combination of E5, E1, I5, and I1)
KDFM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of E5, I5, E6, I6, E1, and I1)
Alternative Transmitter Material of Construction
L1Inert Sensor Fill Fluid
L2Graphite-filled PTFE o-ring
LAInert sensor fill fluid and graphite-filled PTFE o-ring
Display
M5PlantWeb LCD display
(7)(13)
M7
(7)(13)
M8
(7)(13)
M9
Terminal Blocks
(14)
T1
(15)
T2
(15)
T3
Manifold for Remote Mount Option
F23-Valve Manifold, SST
F65-Valve Manifold, SST
PlantWeb Control Functionality
(16)
A01
PlantWeb Diagnostic Functionality
(16)
D01
(17)
DA1
NACE MR-0175 / ISO 15156
ATEX FISCO Intrinsic Safety; for FOUNDATION fieldbus protocol only
SAA Flameproof, Dust Ignition-proof
Note: Only available on Housing Style codes 00, 1A, 1J, 2A, 2J, 2E, or 2M.
Note: Only available on Housing Style codes 00, 1A, 1J, 2A, 2J, 2E, or 2M.
Note: Only available on Housing Style codes 00, 1A, 1J, 2A, 2J, 2E, or 2M.
Note: Only available on Housing Style codes 00, 1A, 1J, 2A, 2J, 2E, or 2M.
(12)
Remote mount LCD display and interface, no cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output
Remote mount LCD display and interface, 50 ft. (15 m) cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output
Remote mount LCD display and interface, 100 ft. (31 m) cable; PlantWeb housing, SST bracket, requires 4-20 mA / Hart output
Transient terminal block
Terminal block with WAGO spring clamp terminals
Transient terminal block with WAGO spring clamp terminals
FOUNDATION fieldbus Advanced Control Function Block Suite
FOUNDATION fieldbus Diagnostics Suite
HART Diagnostic Suite
March 2008
18
Product Data Sheet
Rosemount Compact Orifice
00813-0100-4810, Rev HA
March 2008
Flowmeter Series
Rosemount 3051SFC Compact Orifice Flowmeter Ordering Information
PlantWeb Enhanced Measurement Functionality
(16)(18)
H01
CodeWireless Options - Select code from each wireless category (example: WA2WK1)
Wireless Transmit Rate
WAUser Configurable Transmit Rate
Operating Frequency and Protocol
12.4 GHz DSSS, HART
2900 MHz FHSS, HART
Antenna
WKOmnidirectional, Integral Antenna
SmartPower
1Long-life Power Module Adapter, Intrinsically Safe
CodeOptions
Special Configuration (Software)
(7)(19)
C4
(7)(19)
C5
(7)(19)
C6
(7)(19)
C7
(7)(19)
C8
Special Configuration (Hardware)
(7)(19)
D1
D4External ground screw
(7)(19)
DA
Conduit Electrical Connector
(20)
ZE
(20)
ZM
(1) Consult factory for availability.
(2) Not available for Primary Element Type code C.
(3) For 2-in. (50.8 mm) line sizes the Beta Ratio is 0.6 for Primary Element Type code C.
(4) Requires PlantWeb housing.
(5) Available approvals are FM Intrinsically Safe, Division 2 (option code I5), CSA Intrinsically Safe (option code I6), ATEX Intrinsic Safety
(option code I1; only available with 2.4 GHz), and IECEx Intrinsic Safety (option code I7; only available with 2.4 GHz).
(6) Available with output code A only. Available approvals are FM Intrinsically Safe, Division 2 (option code I5) or ATEX Intrinsic Safety (option code I1). Contact
an Emerson Process Management representative for additional information.
(7) Not available with Output Protocol code X.
(8) Not available with Primary Element Type code P.
(9) Not available with output code F or X. Not available with housing code 01 or 7J.
(10) Instrument valves not included in Traceability Certification.
(11) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits
apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
(12) Not available with Housing code 01 or 7J.
(13) Not available with output code F, Housing code 01, option code DA1, or option code QT.
(14) Not available with Housing code 00, 01, 5A, or 7J.
(15) Available with Output Protocol code A and Plantweb housing only.
(16) Requires PlantWeb housing and output code F.
(17) Requires PlantWeb housing and output code A. Includes Hardware Adjustments as standard. Not available with option code QT.
(18) Requires Rosemount Engineering Assistant to configure.
(19) Not available for Output Protocol code F or Housing code 01.
(20) Not available with Housing code 00, 01, 5A, or 7J. Available with Intrinsically Safe approvals only. For FM Intrinsically Safe, Division 2
(option code I5) or FM FISCO Intrinsically Safe (option code IE), install in accordance with Rosemount drawing 03151-1009 to maintain outdoor rating (NEMA
4X and IP66).
Fully Compensated Mass Flow Block
™
NOTE: Long-life Power Module must be shipped separately, order Part No. 00753-9220-0001.
NAMUR alarm and saturation signal levels, high alarm
NAMUR alarm and saturation signal levels, low alarm
Custom alarm and saturation signal levels, high alarm
Note: A Configuration Data Sheet must be completed, see document number 00806-0100-4810.
Custom alarm and saturation signal levels, low alarm
Note: A Configuration Data Sheet must be completed, see document number 00806-0100-4810.
Low alarm (standard Rosemount alarm and saturation signal levels)
Hardware adjustment (zero, span, alarm, security) and external ground screw
M12, 4-pin, Male Connector (eurofast®)
A size Mini, 4-pin, Male Connector (minifast®)
19
Rosemount Compact Orifice
Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series
March 2008
Rosemount 3095MFC Compact Orifice Mass Flowmeter
SPECIFICATIONS
Performance
System Reference Accuracy
Percent (%) of mass flow rate
TABLE 11. 3095MFC Compact Orifice Mass Flowmeter
Mass flow
TYPEBETA
3095MFCC0.4±0.90%±0.70%
3095MFCP
3095MFCP
3095MFCP
(1) Line sizes 1/2-in. (15mm)
(2) Line sizes 1-in. to 1 1/2-in. (25 mm to 40 mm)
(3) Line sizes 2-in. to 12-in. (50 mm to 300 mm)
(4) For 0.65 beta and ReD< 10,000 add an additional ±0.5% to the
(1)
(2)
(3)
Discharge Coefficient Uncertainty.
0.65±1.30%±1.15%
0.4
(4)
0.65
0.4
(4)
0.65
0.4
(4)
0.65
(8:1 flow
turndown)
±2.50%±2.45%
±2.10%±2.00%
±1.50%±1.40%
Repeatability
±0.1%
Line Sizes
•1/2-in. (15 mm) – not available for the 3095MFCC
• 1-in. (25 mm) – not available for the 3095MFCC
1
/2-in. (40 mm) – not available for the 3095MFCC
•1
• 2-in. (50 mm)
• 3-in. (80 mm)
• 4-in. (100 mm)
• 5-in (125 mm)
• 6-in. (150 mm)
• 8-in. (200 mm)
• 10-in. (250 mm)
• 12-in (300 mm)
Output
Two-wire 4–20 mA, user-selectable for DP, AP, GP, PT, mass flow,
or totalized flow. Digital HART protocol superimposed on 4–20 mA
signal, available to any host that conforms to the HART protocol.
Performance Statement Assumptions
• Measured pipe I.D
• Electronics are trimmed for optimum flow accuracy
Ultra for Flow
(10:1 flow
turndown)
Functional
Service
• Liquid
•Gas
•Steam
Power Supply
4–20 mA option
• External power supply required. Standard transmitter
(4–20 mA) operates on 11 to 55 v dc with no load
Process Temperature Limits
Direct Mount Transmitter
• 450 °F (232 °C)
Remote Mount Transmitter
• 850 °F (454 °C) – Stainless Steel
Transmitter Temperature Limits
Ambient
• -40 to 185 °F (-40 to 85 °C)
• with integral display: -4 to 175 °F (-20 to 80 °C)
Storage
• -50 to 230 °F (-46 to 110 °C)
• with integral display: -40 to 185 °F (-40 to 85 °C)
Differential Pressure Limits
Maximum differential pressure (DP) up to 800 inH2O.
Pressure Limits
Direct Mount Transmitter
• Pressure retention per ANSI B16.5 600# or DIN PN 100
Overpressure Limits
0 to 2 times the absolute pressure range with a maximum of 3626
psia (250 bar).
Static Pressure Limits
Operates within specification between static pressures of 0.5 psia
(0.03 bar-A) and the URL of the static pressure sensor.
Vibration Limits
Qualified per IEC61298-3 (1998) for field with high vibration level
or pipeline with high vibration level (10-60Hz 0.21mm
displacement peak amplitude / 60 - 500Hz 3g).
The weight and length of the transmitter assembly shall not
exceed 5.8 lbs and 7.75-in.
(1)
Sizing
Contact an Emerson Process Management representative for
assistance. A Configuration Data Sheet is required prior to order
for application verification.
20
(1) Static pressure selection may effect pressure limitations.
Product Data Sheet
Load (Ohms)
0
11.042.4
(1)
55
Operating
Region
(1) For CSA approval, power supply must not exceed 42.4 V dc.
(2) HART protocol communication requires a loop resistance value
between 250-1100 ohms, inclusive.
Power Supply
250
16.5
(2)
Maximum Loop Resistance = Power Supply - 11.0
0.022
2000
00813-0100-4810, Rev HA
March 2008
Rosemount Compact Orifice
Flowmeter Series
Load Limitations
Maximum loop resistance is determined by the voltage level of
the external power supply, as described by:
FOUNDATION fieldbus (output option code V)
Power Supply
External power supply required; transmitters operate on 9.0 to
32.0 V dc transmitter terminal voltage.
Current Draw
17.5 mA for all configurations (including LCD display option)
Humidity Limits
• 0–100% relative humidity
Turn-On Time
Digital and analog measured variables will be within specification
7 – 10 seconds after power is applied to the transmitter.
Digital and analog flow output will be within specifications 10 – 14
seconds after power is applied to the transmitter.
Damping
Analog output response to a step input change is user-selectable
from 0 to 29 seconds for one time constant. This software damping
is in addition to sensor module response time
Failure Mode Alarm
Output Code A
If self-diagnostics detect a non-recoverable transmitter failure,
the analog signal will be driven either below 3.75 mA or above
21.75 mA to alert the user. High or low alarm signal is
user-selectable by internal jumper pins.
Output Code V
If self-diagnostics detect a gross transmitter failure, that
information gets passed as a status along with the process
variable(s).
Configuration
HART Hand-held Communicator (Model 275 or 375)
• Performs traditional transmitter maintenance functions
• Enables mass flow configuration, maintenance, and diagnostic
functions via HART modem (output option code A)
Enables mass flow configuration via PCMCIA Interface for
F
OUNDATION fieldbus (output option code V)
Physical Properties Database
• Maintained in Engineering Assistant Software Configurator
• Physical properties for over 110 fluids
• Natural gas per AGA
• Steam and water per ASME
• Other database fluids per American Institute of Chemical
Engineers (AIChE)
• Optional custom entry
FOUNDATION fieldbus Function Blocks
Standard Function Blocks
Resource Block
• Contains hardware, electronics, and diagnostic information.
Transducer Block
• Contains actual sensor measurement data including the
sensor diagnostics and the ability to trim the pressure
sensor or recall factory defaults.
LCD Block
• Configures the local display.
5 Analog Input Blocks
• Processes the measurements for input into other function
blocks. The output value is in engineering or custom units
and contains a status indicating measurement quality.
PID Block with Auto-tune
• Contains all logic to perform PID control in the field including
cascade and feedforward. Auto-tune capability allows for
superior tuning for optimized control performance.
Advanced Control Function Block Suite
(Option Code A01)
Input Selector Block
• Selects between inputs and generates an output using
specific selection strategies such as minimum, maximum,
midpoint, average, or first “good.”
Arithmetic Block
• Provides pre-defined application-based equations including
flow with partial density compensation, electronic remote
seals, hydrostatic tank gauging, ratio control and others.
Signal Characterizer Block
• Characterizes or approximates any function that defines an
input/output relationship by configuring up to twenty X, Y
coordinates. The block interpolates an output value for a
given input value using the curve defined by the configured
coordinates.
Integrator Bock
• Compares the integrated or accumulated value from one or
two variables to pre-trip and trip limits and generates
discrete output signals when the limits are reached. This
block is useful for calculating total flow, total mass, or
volume over time.
Output Splitter Block
• Splits the output of one PID or other control block so that the
PID will control two valves or other actuators.
Control Selector Block
• Selects one of up to three inputs (highest, middle, or lowest)
that are normally connected to the outputs of PID or other
control function blocks.
21
Rosemount Compact Orifice
Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Physical
Temperature Measurement
Remote RTD
• 100 Ohm platinum with
series with Rosemount 644 housing)
Model 0078D21N00A025T32Ex
Connection Head: 00644-4410-0011
• Standard RTD cable is shielded armored cable, length is 12
feet (3.66 m)
• Remote RTD material is SST
Thermowell
1
/2-in. x 1/2-in. NPT, 316 SST
•
NOTE
Remote temperature measurement is not available for
and 11/2-in. sizes.
Electronic Connections for Remote Mount
•1/2–14 NPT, G1/2, and M20 × 1.5 (CM20) conduit. HART
interface connections fixed to terminal block for output code A
Process-Wetted Parts
Integral Manifolds
•316 SST
• Hastelloy C-276
Remote Manifolds
•316 SST
• Hastelloy C-276
Transmitter Vent Valves and Process Flanges
•316 SST
• Hastelloy C-276
• Glass-filled PTFE O-rings
Process Isolating Diaphragms
•316L SST
• Hastelloy C-276
Integral Manifold O-Rings
• PTFE/Graphite
Non-Wetted Parts
Sensor Module Fill Fluid
• Silicone oil
• Inert Fill optional
Cover O-rings
• Buna-N
Remote Mounting Brackets
•SST
Electronic Housing
• Low copper aluminum, NEMA 4x, IP65
• SST (optional)
Paint
• Polyurethane
Bolts
•CS
(1)
1
/2-in. NPT nipple and union (078
1
/2-in., 1-in.,
Material of Construction
Body/Plate
•316 SST
• 50 micro-inch Ra surface finish
Manifold Head/Valves
•316 SST
Flange Studs and Nuts
• Customer supplied
• Available as a spare part
Transmitter Connection Studs and Nuts
• Studs– A193 Grade B8M.
• Nuts– A194 Grade 8M.
Gasket and O-rings
• Gaskets are customer supplied.
• Durlon 8500 fiber gaskets are recommended. Consult an
Emerson Process Management representative for use with
other gaskets.
• Available as a spare part
NOTE
Gaskets and O-rings should be replaced when the 405 is
disassembled.
Transmitter Connections
Remote Mount
• Available with
connections
Orifice Type
• Square edged, Wafer style
Orifice Pressure Taps
• Corner
1
/4-in. (standard) or 1/2-in. (option code E)
Process Connections
Mounts between the following flange configurations
ASME B16.5
(ANSI)
Class 150
Class 300
Class 600
ANSI alignment ring is included as standard when ordering
DINJIS
PN16 (option code G)
PN40 (option code H)
PN100 (option code H)
10k (option code B)
20k (option code R)
40k (option code S)
22
(1)
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Rosemount Compact Orifice
Flowmeter Series
Typical Orifice Hole Sizes (For 3095MFCC)
Beta is calculated by: (β) = dC / Pipe ID, where the calculated bore
is equal to 2 x typical orifice hole size (d
shows the diameter of each of the four typical orifice holes.
Improper centering of any orifice type device can cause an error of
up to ±5% in small line sizes. A centering mechanism (centering
ring) independent of flange rating comes standard with the 405
Compact Orifice Series.
Pipe Orientation
Pipe orientation for both 3095MFCC Compact Conditioning Mass
Orifice and standard 3095MFCP Compact Mass Orifice.
Flowmeter orientation for both 3095MFC Conditioning Compact
Orifice and standard Compact Orifice.
Gas (Horizontal)
Liquid and Steam (Horizontal)
Rosemount Compact Orifice
Flowmeter Series
50°
50°
80°
Gas (Vertical)
Liquid (Vertical)
25
Rosemount Compact Orifice
Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
PRODUCT CERTIFICATIONS
Rosemount 3095 with HART
European Directive Information
The EC declaration of conformity for all applicable European
directives for this product can be found on the Rosemount website
at www.rosemount.com. A hard copy may be obtained by
contacting our local sales office.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX Directive.
European Pressure Equipment Directive (PED)
(97/23/EC)
3095M_2/3,4/D Flow Transmitters — QS Certificate of
Assessment - EC No. PED-H-20
Module H Conformity Assessment
All other 3095_ Transmitters/Level Controller —
Sound Engineering Practice
Transmitter Attachments: Process Flange - Manifold —
Sound Engineering Practice
Electro Magnetic Compatibility (EMC)
(89/336/EEC)
3095MV Flow Transmitters
— EN 50081-1: 1992; EN 50082-2:1995;
EN 61326-1:1997 – Industrial
Ordinary Location Certification for Factory
Mutual
As standard, the transmitter has been examined and tested to
determine that the design meets basic electrical, mechanical, and
fire protection requirements by FM, a nationally recognized testing
laboratory (NRTL) as accredited by the Federal Occupational
Safety and Health Administration (OSHA).
Hazardous Locations Certifications
North American Certifications
FM Approvals
E5Explosion Proof for Class I, Division 1, Groups B, C, and D.
Dust-Ignition Proof for Class II/Class III, Division 1, Groups
E, F, and G. Enclosure type NEMA 4X. Factory Sealed.
Provides nonincendive RTD connections for Class I, Division
2, Groups A, B, C, and D.
I5Intrinsically Safe for use in Class I, II and III, Division 1,
Groups A, B, C, D, E, F, and G hazardous outdoor locations.
Non-incendive for Class I, Division 2, Gro ups A, B, C, and D.
Temperature Code T4. Factory Sealed.
For input parameters and installation see control drawing
03095-1020.
Canadian Standards Association (CSA)
E6Explosion Proof for Class I, Division 1, Groups B, C, and D.
Dust-Ignition Proof for Class II/Class III, Division 1, Groups
E, F, and G. CSA enclosure Type 4X suitable for indoor and
outdoor hazardous locations. Provides nonincendive RTD
connection for Class I, Division 2, Groups A, B, C, and
D.Factory Sealed. Install in accordance with Rosemount
Drawing 03095-1024. Approved for Class I, Division 2,
Groups A, B, C, and D.
I6Intrinsically Safe for Class I, Division 1, Groups A, B, C, and
D. when installed in accordance with Rosemount drawing
03095-1021. Temperature Code T3C.
For input parameters and installation see control drawing
03095-1021.
European Certifications
I1ATEX Intrinsic Safety
Certificate Number: BAS98ATEX1359X II 1 G
EEx ia IIC T5 (T
EEx ia IIC T4 (T
118 0
TABLE 16. Connection Parameters (Power/Signal
Te rm i na l s)
= 30V
U
i
Ii = 200 mA
= 1.0 W
P
i
Ci = 0.012 µF
= 0
L
i
TABLE 17. Temperature Sensor Connection Parameters
The 3095, when fitted with the transient terminal block
(order code B), are not capable of withstanding the 500 volts
insulation test required by EN50 020, Clause 6.4.12 (1994).
This condition must be accounted for during installation.
N1ATEX Type N
Certificate Number: BAS98ATEX3360X II 3 G
EEx nL IIC T5 (T
EEx nL IIC T4 (T
= 55V
U
i
= –45 °C to 40 °C)
amb
= –45 °C to 70 °C)
amb
= –45 °C to 40 °C)
amb
= –45 °C to 70 °C)
amb
26
The apparatus is designed for connection to a remote
temperature sensor such as a resistance temperature
detection (RTD)
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Rosemount Compact Orifice
Flowmeter Series
Special Conditions for Safe Use
The 3095, when fitted with the transient terminal block
(order code B), are not capable of withstanding the 500 volts
insulation test required by EN50 021, Clause 9.1 (1995).
This condition must be accounted for during installation.
E1ATEX Flameproof
Certificate Number: KEMA02ATEX2320X II 1/2 G
EEx d IIC T5 (-50°C ≤ T
T6 (-50°C ≤ T
118 0
Special Conditions for Safe Use (x):
The device contains a thin wall diaphragm. Installation,
maintenance, and use shall take into account the
environmental conditions to which the diaphragm will be
subjected. The manufacturer’s instructions for installation
and maintenance shall be followed in detail to assure safety
during its expected lifetime.
ND ATEX Dust
Certificate Number: KEMA02ATEX2321 II 1 D
V = 55 Vdc MAX
I = 23 mA MAX
IP66
118 0
amb
amb
≤ 80°C)
≤ 65°C)
Combinations of Certifications
Stainless steel certification tag is provided when optional approval
is specified. Once a device labeled with multiple approval types is
installed, it should not be reinstalled using any other approval
types. Permanently mark the approval label to distinguish it from
unused approval types.
K5E5 and I5 combination
K6E6 and I6 combination
K1I1, N1, E1, and ND combination
Electro Magnetic Compatibility (EMC) (89/336/EEC)
3095 Flow Transmitters
— EN 50081-1: 1992; EN 50082-2:1995; EN 61326-1:1997 –
Industrial
Ordinary Location Certification for Factory Mutual
As standard, the transmitter has been examined and tested to
determine that the design meets basic electrical, mechanical, and
fire protection requirements by FM, a nationally recognized testing
laboratory (NRTL) as accredited by the Federal Occupational
Safety and Health Administration (OSHA).
E5Explosion Proof for Class I, Division 1, Groups B, C, and D.
Dust-Ignition Proof for Class II/Class III, Division 1, Groups
E, F, and G. Enclosure type NEMA 4X. Factory Sealed.
Provides nonincendive RTD connections for Class I,
Division 2, Groups A, B, C, and D.
I5Intrinsically Safe for use in Class I, II and III, Division 1,
Groups A, B, C, D, E, F, and G hazardous outdoor locations.
Non-incendive for Class I, Division 2, Groups A, B, C, and D.
Temperature Code T4. Factory Sealed.
For input parameters and installation see control drawing
03095-1020.
IEFISCO for use in Class I, II and III, Division 1, Groups A, B,
C, D, E, F, and G hazardous outdoor locations. Temperature
Code T4. Factory Sealed.
Rosemount 3095 with Fieldbus
European Directive Information
The EC declaration of conformity for all applicable European
directives for this product can be found on the Rosemount website
at www.rosemount.com. A hard copy may be obtained by
contacting our local sales office.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX Directive.
European Pressure Equipment Directive (PED)
(97/23/EC)
3095F_2/3,4/D and 3095M_2/3,4/D Flow Transmitters
— QS Certificate of Assessment - EC No. PED-H-20
Module H Conformity Assessment
All other 3095_ Transmitters/Level Controller
— Sound Engineering Practice
Transmitter Attachments: Process Flange - Manifold
— Sound Engineering Practice
Primary Elements, Flowmeter
— See appropriate Primary Element QIG
For input parameters and installation see control drawing
03095-1020.
Combinations of Certifications
Stainless steel certification tag is provided when optional approval
is specified. Once a device labeled with multiple approval types is
installed, it should not be reinstalled using any other approval
types. Permanently mark the approval label to distinguish it from
unused approval types.
K5 E5 and I5 combination
Canadian Standards Association (CSA)
IFCSA FISCO Intrinsically Safe; for FOUNDATION fieldbus
protocol only
European Certifications
IAATEX FISCO Intrinsically Safe; for FOUNDATION fieldbus
protocol only
Australian Certifications
IGIECEx FISCO Intrinsic Safety
27
Rosemount Compact Orifice
A
B
D
1.13 (28.7)
1.00 (25.4
A
B
D
1.13 (28.7)
1.00 (25.4
Flowmeter Series
DIMENSIONAL DRAWINGS
Rosemount 3095MFC Compact Orifice Mass Flowmeter
Orifice Plate Front ViewOrifice Plate Side ViewOrifice Plate Top View
Compact Orifice Plate
(Primary Element Type code P)
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
C
(Primary Element Type code C)
Conditioning Orifice Plate
TABLE 19. Dimensional Drawings
Plate TypeABTransmitter HeightCD
Type P & C5.50 (140)Transmitter Height + A6.25 (159)7.75 (197) - closed
(1) Measurement is in inches (millimeters).
(1)
8.25 (210) - open
C
6.0 (152) - closed
6.25 (159) - open
28
Product Data Sheet
Rosemount Compact Orifice
00813-0100-4810, Rev HA
March 2008
ORDERING INFORMATION
Rosemount 3095MFC Compact Orifice Mass Flowmeter Ordering Information
Material certification per ISO 10474 3.1.B and EN 10204 3.1.B
NACE MR-0175 / ISO 15156
FM FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
CSA FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
ATEX FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
IECEx FISCO Intrinsic Safety
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
30
Product Data Sheet
Rosemount Compact Orifice
00813-0100-4810, Rev HA
March 2008
Flowmeter Series
Rosemount 3095MFC Compact Orifice Mass Flowmeter Ordering Information
I3China Intrinsic Safety
E3China Flameproof
Alternative Transmitter Material of Construction
(9)
L1
Display
M5Integral mount LCD display
Terminal Blocks
T1Transient Protection
Manifold for Remote Mount Option
F23-Valve Manifold, SST
F65-Valve Manifold, SST
Typical Model Number: 3051MFC C S 040 N 040 0 3 B A 1A
(1) Consult factory for availability.
(2) Not available for Primary Element Type code C.
(3) For 2-in. (50.8 mm) line sizes the Beta Ratio is 0.6 for Primary Element Type code C.
(4) Ultra for Flow applicable for HART protocol, DP ranges 2 and 3 with SST isolator material and silicone fill fluid options only.
(5) Function Blocks include: Arithmetic, Integrator, Analog Output, Signal Characterizer, Control Selector, and Output Selector.
(6) Not available with Primary Element Type code P.
(7) Instrument valves not included in Traceability Certification.
(8) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO 15156 for sour oil field production environments. Environmental
(9) Not available with DP range 1.
Inert Sensor Fill Fluid
limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
31
Rosemount Compact Orifice
Flowmeter Series
Rosemount 405 Compact Orifice Primary Element
SPECIFICATIONS
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Performance
Discharge Coefficient Uncertainty
TABLE 20. 405 Compact Orifice Primary Element
Discharge Coefficient
Typ eBeta
405C
(Conditioning Compact)
(1)(2)
405P
(Standard Compact)
405P
(Standard Compact)
(1) Line sizes 1/2 to 11/2-in. (12.7 to 38.1 mm).
(2) Discharge Coefficient Uncertainty for
(3) Line sizes 2 to 12-in. (50 mm to 300 mm)
(3)
is ±2.25%.
0.4±0.50%
0.65±1.00%
0.4±1.75%
0.65±1.75%
0.4±1.25%
0.65±1.25%
1
Uncertainty
/2-in. units with Beta = 0.65
Line Sizes
•1/2-in. (15 mm) – not available for the 405C
• 1-in. (25 mm) – not available for the 405C
1
/2-in. (40 mm) – not available for the 405C
•1
• 2-in. (50 mm)
• 3-in. (80 mm)
• 4-in. (100 mm)
• 5-in (125 mm)
• 6-in. (150 mm)
• 8-in. (200 mm)
• 10-in. (250 mm)
• 12-in (300 mm)
Sizing
Contact an Emerson Process Management sales representative
assistance. A “Configuration Data Sheet” is required prior to order
for application verification.
Functional
Vibration Limits
Qualified per IEC61298-3 (1998) for field with high vibration level
or pipeline with high vibration level (10-60Hz 0.21mm
displacement peak amplitude / 60 - 500Hz 3g).
The weight and length of the transmitter assembly shall not
exceed 5.8 lbs and 7.75-in.
Assembly to a transmitter
Select option code C11 for the Rosemount 3051S transmitter (or
option code S3 for the Rosemount 3051C or 3095MV transmitters)
to factory assemble the Rosemount 405 to a Rosemount pressure
transmitter. If the 405 and transmitter are not factory assembled,
they may be shipped separately. For a consolidated shipment,
inform the Emerson Process Management representative when
placing the order.
Physical
Material of Construction
Body/Plate
•316 SST
• 50 micro-inch Ra surface finish
Manifold Head/Valves
•316 SST
Flange Studs and Nuts
• Customer supplied
• Available as a spare part
Transmitter Connection Studs and Nuts
• Studs– A193 Grade B8M.
• Nuts– A194 Grade 8M.
Gasket and O-rings
• Gaskets are customer supplied.
• Durlon 8500 fiber gaskets are recommended. Consult an
Emerson Process Management representative for use with
other gaskets.
• Available as a spare part
Service
•Liquid
•Gas
• Vapor
Operating Process Temperature Limits
Standard (direct/remote mount):
• –40 to 450 °F (–40 to 232 °C)
Extended (remote mount only with option code T):
• –148 to 850 °F (–100 to 454 °C)
Differential Pressure Limits
Maximum differential pressure (DP) up to 800 inH2O.
Maximum Working Pressure
• Pressure retention per ANSI B16.5 600# or DIN PN100
32
NOTE
Gaskets and O-rings should be replaced when the 405 is
disassembled.
Transmitter Connections
Direct Mount
• Integrally mount to 3051 and 3095 transmitters,
range 1, 2, and 3.
Remote Mount
• Available with
connections
Orifice Type
• Square edged, Wafer style
Orifice Pressure Taps
• Corner
1
/4-in. (standard) or 1/2-in. (option code E)
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Rosemount Compact Orifice
Flowmeter Series
Process Connections
Mounts between the following flange configurations:
ASME B16.5
(ANSI)
Class 150
Class 300
Class 600
DINJIS
PN16 (option code G)
PN40 (option code H)
PN100 (option code H)
10k (option code B)
20k (option code R)
40k (option code S)
ANSI alignment ring is included as standard when ordering.
Typical Orifice Hole Sizes (For 405C)
Beta is calculated by: (β) = dC / Pipe ID, where the calculated bore
is equal to 2 x typical orifice hole size (d
shows the diameter of each of the four typical orifice holes.
Use the appropriate lengths of straight pipe upstream and
downstream of the 405 to minimize the effects of moderate flow
disturbances in the pipe. Table 23 and Table 24 lists
recommended lengths of straight pipe per ISO 5167.
TABLE 23. 405C Straight Pipe Requirements
Beta0.400.65
Reducer (1 line size)2 2
Single 90° bend or tee2 2
Two or more 90 ° bends in the same
plane
Two or more 90° bends in different
plane
side of primary
Up to 10° of swirl2 2
Upstream (inlet)
Butterfly valve (75% to 100% open)2 N/A
Downstream (outlet) side of primary
TABLE 24. 405P Straight Pipe Requirements
Beta0.400.65
(2)(3)
Downstream (outlet) side of primary
(1) Consult an Emerson Process Management representative if
(2) Recommended lengths represented in pipe diameters per ISO
(3) Refer to ISO 5167 for recommended lengths when using flow
Reducer512
Single 90° bend or tee1644
Two or more 90 ° bends
in the same plane
Two or more 90° bends in different
Improper centering of any orifice type device can cause an error of
up to ±5% in small line sizes. A centering mechanism (centering
ring) independent of flange rating comes standard with the 405
Compact Orifice Series.
34
Product Data Sheet
30°
120°
30°
360°
FLOW
360°
FLOW
00813-0100-4810, Rev HA
March 2008
Flowmeter Orientation
Flowmeter orientation for the Conditioning Compact Orifice and
standard Compact Orifice.
Gas (Horizontal)
Liquid and Steam (Horizontal)
Rosemount Compact Orifice
Flowmeter Series
50°
50°
80°
Gas (Vertical)
Liquid (Vertical)
35
Rosemount Compact Orifice
VALVE
EQUALIZER
1/4"-in NPT
INSTRUMENT
INSTRUMENT
HIGH
VALVE
VALVE
LOW
ADAPTER
PLATE
.85 (21.6)
(54.1)
2.13
1.13 (28.7)
1.00 (25.4)
Flowmeter Series
DIMENSIONAL DRAWINGS
Rosemount 405 Compact Orifice Plate
(Remote Mount Transmitter)
Adapter Plate (R3)Flange Adapter (R3 with option E)
1/2"-in NPT
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
2.13
(54.1)
Compact Orifice Plate
(Primary Element Type code P)
1/4"-in NPT
HIGH
INSTRUMENT
VALVE
ADAPTER
PLATE
EQUALIZER
VALVE
2.13
(54.1)
.85 (21.6)
LOW
INSTRUMENT
VALVE
HIGH
INSTRUMENT
VALVE
ADAPTER
PLATE
EQUALIZER
VALVE
HIGH
INSTRUMENT
VALVE
ADAPTER
PLATE
EQUALIZER
1/2"-in NPT
VALVE
2.13
(54.1)
FLANGE
ADAPTER
.85 (21.6)
1.13 (28.7)
1.00 (25.4)
LOW
INSTRUMENT
VALVE
FLANGE
ADAPTER
LOW
INSTRUMENT
VALVE
.85 (21.6)
Conditioning Orifice Plate
36
(Primary Element Type code C)
1.13 (28.7)
1.00 (25.4)
1.13 (28.7)
1.00 (25.4)
Product Data Sheet
HIGH
EQUALIZER
VALVE
VALVE
INSTRUMENT
LOW
INSTRUMENT
VALVE
1.30
1.13 (28.7)
1.00 (25.4)
(33)
2.13
(54.1)
1.13 (28.7)
1.00 (25.4)
00813-0100-4810, Rev HA
March 2008
Front View (transmitter connection A3)Front View (transmitter connection D3)
HIGH
INSTRUMENT
VALVE
ADAPTER
PLATE
EQUALIZER
VALVE
Rosemount Compact Orifice
Flowmeter Series
Rosemount 405 Compact Orifice Plate
(Direct Mount)
2.13
(54.1)
LOW
INSTRUMENT
VALVE
.70
(18)
Compact Orifice Plate
(Primary Element Type code P)
(Primary Element Type code C)
Conditioning Orifice Plate
1.13 (28.7)
1.00 (25.4)
HIGH
INSTRUMENT
VALVE
EQUALIZER
VALVE
1.30
(33)
2.13
(54.1)
LOW
INSTRUMENT
VALVE
1.13 (28.7)
1.00 (25.4)
NOTE
Transmitter connection code A3 is to be used with a traditional style transmitter (such as a Rosemount 1151). This
is a stainless steel adapter plate for allowing the direct mount of traditional style transmitters.
37
Rosemount Compact Orifice
Flowmeter Series
ORDERING INFORMATION
Rosemount 405 Compact Orifice Primary Element Ordering Information
D3Coplanar, Direct mount, 3-valve integral manifold, SST
R3Remote-mount, 1/4-in. NPT connections
A3Traditional, Direct mount, 3-valve integral manifold with adapter plate, SST
CodeOptions
Installation Accessories
GDIN Alignment Ring (PN 16)
HDIN Alignment Ring (PN 40, PN 100)
BJIS Alignment Ring 10K
RJIS Alignment Ring 20K
SJIS Alignment Ring 40K
Adapters
EFlange adapters 316 SST (
High Temperature Applications
TGraphite valve packing (Tmax = 850 °F)
Flow Calibration
(4)
WC
(4)
WD
Pressure Testing
P1Hydrostatic testing with certificate
Special Cleaning
P2Cleaning for special processes
PACleaning per ASTM G93 Level D (section 11.4)
Rosemount 405 Compact Orifice Primary Element Ordering Information
Special Inspection
QC1Visual and Dimensional Inspection with certification
QC7Inspection and performance certification
Material Traceability Certification
(5)
Q8
Code Conformance
J2ANSI B31.1
J3ANSI B31.3
J4ANSI B31.8
Material Conformance
(6)
J5
Country Certification
J1Canadian Registration
Typical Model Number: 405 C S 040 N 040 D3
(1) Consult factory for availability.
(2) Not available for Primary Element Type code C.
(3) For 2-in. (50.8 mm) line sizes the Beta Ratio is 0.6 for Primary Element Type code C.
(4) Not available with Primary Element Type code P.
(5) Instrument valves not included in Traceability Certification.
(6) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits
Material certification per ISO 10474 3.1.B and EN 10204 3.1.B
NACE MR-0175 / 15156
apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
39
Rosemount Compact Orifice
Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series
March 2008
HART Configuration Data Sheet (CDS)
DP FLOW CDS
Complete this form to define a custom flow configuration for DP Flowmeters. Unless specified, the flowmeter will
be shipped with the default values identified by the H symbol.
For technical assistance in filling out this CDS, call a Rosemount representative.
NOTE
Any missing information will be processed with the indicated default values.
* = Required Item
★ = Default
Customer Information
Customer:Contact Name:
Customer Phone:Customer Fax:
Customer Approval Sign-Off:Customer PO:
Calculation Approval
❑ Check this box if a calculation for approval prior to manufacturing is required
Application and Configuration Data Sheet (Required with Order)
❑ 485 Annubar/ 3095MFA Mass ProBar, 3051SFA ProBar
❑ 285 Annubar
❑ Annubar Diamond II + / Mass Probar
❑ Long Radius Wall Taps, ASME
❑ Long Radius Wall Taps, ISO
❑ ISA 1932, ISO
Venturi
❑ Nozzle, ISO
❑ Rough Cast/Fabricated Inlet, ASME
❑ Round Cast Inlet, ISO
❑ Machined Inlet, ASME
❑ Machined Inlet, ISO
❑ Welded Inlet, ISO
Other (All options require a discharge coefficient value)
❑ Calibrated Orifice: Flange, Corner, or D & D/2 Taps.
Discharge coefficient: __________________
❑ Calibrated Orifice: 2
Discharge coefficient: __________________
1
/2 D & 8D Taps
❑ Calibrating Nozzle
Discharge coefficient: __________________
❑ Calibrating Venturi
Discharge coefficient: __________________
❑ Area Averaging Meter
Discharge coefficient: __________________
❑ V-Cone
Discharge coefficient: __________________
Special Annubar dimension (required if customer supplies mounting hardware).
®
Diameter (d) ________________
Orifice
❑ 3051SFP, 3095MFP, 1195
❑ 405C, 405P, 3051SFC, 3095MFC
❑ 1595 Conditioning Orifice
❑ 2
❑ Corner Taps, ASME
❑ Corner Taps, ISO
❑ D & D/2 Taps, ASME
❑ D & D/2 Taps, ISO
❑ D & D/2 Taps, ISO 99 Amendment 1
❑ Flange Taps, AGA
❑ Flange Taps, ASME
❑ Flange Taps, ISO
❑ Flange Taps, ISO 99 Amendment 1
❑ Small Bore, Flange Taps, ASME
❑ inch★
❑ millimeters
Rosemount Compact Orifice
Flowmeter Series
1
/2D & 8D Taps, ASME
at __________
❑ ODF _____❑ ODT _____
❑ °F
❑ 68 °F★
❑ °C
Pipe Information
* Orientation / Flow Direction:
* Line Size / Schedule: ___________________________________Body I.D. (D): ___________________________________
Materials of Construction
* Pipe Material
* Primary Element Material
Operating Conditions
4 mA value MinimumNormalMaximumFull Scale:20 mA flow rate
❑ 316 SST❑ Hastelloy❑ Other ___________________ (Please verify material availability)
(1)
(1)
(1)
**
**
**
(1)
(1)
(design to P and T)
(2)
*
*
Design
❑ Normal Mode ★ (Requires a RTD to be connected. If the RTD is disconnected or fails, the 3095MV output goes to alarm value)
❑ Fixed Temperature Mode: Specify the fixed temperature value _____________________ ❑ °F❑ °C
❑ Backup Mode (Uses the connected RTD for temperature measurement. If the RTD is disconnected or fails, the transmitter uses a fixed
temperature value as a backup. This will not cause the mA output to go to alarm value and can potentially cause inaccurate flow
measurement.) Fixed temperature value to be used as backup_________________
FOUNDATION fieldbus™ Configuration Data Sheet (CDS)
DP FLOW CDS
Complete this form to define a custom flow configuration for DP Flowmeters. Unless specified, the flowmeter will
be shipped with the default values identified by the H symbol.
For technical assistance in filling out this CDS, call a Rosemount representative.
NOTE
Any missing information will be processed with the indicated default values.
* = Required Item
★ = Default
Customer Information
Customer:Contact Name:
Customer Phone:Customer Fax:
Customer Approval Sign-Off:Customer PO:
Calculation Approval
❑ Check this box if a calculation for approval prior to manufacturing is required
Application and Configuration Data Sheet (Required with Order)
❑ 485 Annubar/ 3095MFA Mass ProBar, 3051SFA ProBar
❑ 285 Annubar
❑ Annubar Diamond II + / Mass Probar
❑ Long Radius Wall Taps, ASME
❑ Long Radius Wall Taps, ISO
❑ ISA 1932, ISO
Venturi
❑ Nozzle, ISO
❑ Rough Cast/Fabricated Inlet, ASME
❑ Round Cast Inlet, ISO
❑ Machined Inlet, ASME
❑ Machined Inlet, ISO
❑ Welded Inlet, ISO
Other (All options require a discharge coefficient value)
❑ Calibrated Orifice: Flange, Corner, or D & D/2 Taps.
Discharge coefficient: __________________
❑ Calibrated Orifice: 2
Discharge coefficient: __________________
1
/2 D & 8D Taps
❑ Calibrating Nozzle
Discharge coefficient: __________________
❑ Calibrating Venturi
Discharge coefficient: __________________
❑ Area Averaging Meter
Discharge coefficient: __________________
❑ V-Cone
Discharge coefficient: __________________
Special Annubar dimension (required if customer supplies mounting hardware).
®
Diameter (d) ________________
Orifice
❑ 3051SFP, 3095MFP, 1195
❑ 405C, 405P, 3051SFC, 3095MFC
❑ 1595 Conditioning Orifice
❑ 2
❑ Corner Taps, ASME
❑ Corner Taps, ISO
❑ D & D/2 Taps, ASME
❑ D & D/2 Taps, ISO
❑ D & D/2 Taps, ISO 99 Amendment 1
❑ Flange Taps, AGA
❑ Flange Taps, ASME
❑ Flange Taps, ISO
❑ Flange Taps, ISO 99 Amendment 1
❑ Small Bore, Flange Taps, ASME
❑ inch★
❑ millimeters
1
/2D & 8D Taps, ASME
at __________
❑ ODF _____❑ ODT _____
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
❑ °F
❑ 68 °F★
❑ °C
Pipe Information
* Orientation / Flow Direction:
* Line Size / Schedule: ___________________________________Body I.D. (D): ___________________________________
Materials of Construction
* Pipe Material
* Primary Element Material
Operating Conditions
4 mA value MinimumNormalMaximumFull Scale:20 mA flow rate
❑ 316 SST❑ Hastelloy❑ Other ___________________ (Please verify material availability)
(1)
(1)
(1)
**
**
**
(1)
(1)
(design to P and T)
(2)
*
*
Design
❑ Normal Mode ★ (Requires a RTD to be connected. If the RTD is disconnected or fails, the 3095MV output goes to alarm value)
❑ Fixed Temperature Mode: Specify the fixed temperature value _____________________ ❑ °F❑ °C
❑ Backup Mode (Uses the connected RTD for temperature measurement. If the RTD is disconnected or fails, the transmitter uses a fixed
temperature value as a backup. This will not cause the mA output to go to alarm value and can potentially cause inaccurate flow
measurement.) Fixed temperature value to be used as backup_________________
AI Block Name (Flow):____________________________ (AI 1400 ★)
AI Block Name (DP):____________________________ (AI 1500 ★)
AI Block Name (SP):____________________________ (AI 1600 ★)
AI Block Name (PT):____________________________ (AI 1700 ★)
INTEG Block Name (Flow Total): ____________________________ (INTEG 2100 ★)
Drawing/Notes
45
Rosemount Compact Orifice
Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Fluid Data Sheet (FDS)
For custom fluid not in the Rosemount Fluid Database
For technical assistance in filling out this CDS, call an Emerson Process Management representative. Complete
this form to define a custom fluid. The H symbol identifies the default value.
NOTE
This form is not required if using the Rosemount Fluid Database.
* = Required Item
★ = Default
Customer Information
Customer:Contact Name:
Customer Phone:Customer Fax:
Customer PO:
Fluid Properties
❑ Custom Liquid– Complete Table❑ Liquid
❑ Custom Gas– Complete Table❑ Gas
❑ Custom Natural Gas– Complete Table❑ Natural Gas
For Rosemount Use Only
S.O.:LI
CHAMP:DATE:
ADMIN:
46
Product Data Sheet
Rosemount Compact Orifice
00813-0100-4810, Rev HA
March 2008
Flowmeter Series
TABLE 27. Custom Liquid Worksheet
* = Required Item
★ = Default
Mass Liquid Density and Viscosity Information
1. Fill in the following operating temperatures
a) _________________________ min
1
b) _________________________ [
c) _________________________ [
d) _________________________ max
2. Transfer the values from the above section to the numbered lines below.
3. Check one Density box, then enter the values for each temperature and the standard density.
4. Check one Viscosity box, then enter values for each temperature. (At least one viscosity value is required).
Density
❑ Density in lbs/CuFt
❑ Density in kg/CuM
/3 (max - min))] + min
2
/3 (max - min))] + min
Viscosity
❑ Viscosity in centipoise
❑ Viscosity in lbs/ft sec
❑ Viscosity in pascal sec
TemperatureTemperature
a) _____________ mina) _____________ min.
Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale
The Emerson logo is a trade mark and service mark of Emerson Electric Co.
Rosemount, the Rosemount logotype, ProPlate, Mass ProPlate, and Annubar are registered trademarks of Rosemount Inc.
All other marks are the property of their respective owners.
Emerson Process Management
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN USA 55317
T (US) (800) 999-9307
T (Intnl) (952) 906-8888
F (952) 949-7001
www.rosemount.com
Emerson Process Management
Heath Place
Bognor Regis
West Sussex PO22 9SH
England
T 44 (0) 1243 863121
F 44 (0) 1243 867554