Rosemount 3095MFC Data sheet

Product Data Sheet
00813-0100-4810, Rev HA March 2008
Rosemount Compact Orifice
Rosemount Compact Orifice Flowmeter Series
INTEGRATED DESIGN FOR LIMITED STRAIGHT PIPE RUN, CLOSED LOOP CONTROL, AND GENERAL PURPOSE MONITORING APPLICATIONS
• Reduced installation cost compared to a traditional orifice plate
• Accurate and repeatable
• Easy-to-install direct mount assembly
• Self-centering
• Based on ASME/ISO corner tap design
• Patented technology
Flowmeter Series
Content
The Rosemount 405 Compact Orifice Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Rosemount DP-Flow Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Rosemount 3051SFC Compact Orifice Flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Product Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 15
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 16
Rosemount 3095MFC Compact Orifice Mass Flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . page 20
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 20
Product Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 28
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 29
Rosemount 405 Compact Orifice Primary Element. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 32
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 32
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 36
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 38
HART Configuration Data Sheet (CDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 40
F
OUNDATION fieldbus
Configuration Data Sheet (CDS) . . . . . . . . . . . . . . . . . . . . . . . . . . page 43
Fluid Data Sheet (FDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 46
www.rosemount.com
Rosemount Compact Orifice
Rosemount pressure transmitters
combined with the Rosemount 405 Compact
Orifice create Best-in-Class Flowmeters
3051SFC Compact
Orifice Flowmeter
3095MFC Compact
Orifice Mass Flowmeter
405C
405P
Flowmeter Series
The Rosemount 405 Compact Orifice Series
Best-in-Class Integrated DP Flowmeters
By integrating Rosemount pressure transmitters with the 405 Compact Orifice Series primary element, Rosemount provides the highest performing DP Flowmeters. This fully integrated flowmeter eliminates the need for fittings, tubing, valves, adapters, manifolds, and mounting brackets, thereby reducing welding and installation time.
Less Expensive than an Orifice Plate Installation
Direct mounting minimizes total installed cost by reducing engineering, procurement, labor, and material expenditures while offering unsurpassed utility.
Direct Mount
A 3-valve isolation manifold and 1-in (25 mm) thick wafer-style body allows direct mounting while eliminating field connections between the process and the differential pressure-measuring device. The integral configuration results in a robust, inexpensive, and easy-to-install assembly.
Accurate and Repeatable
The 405C Conditioning Orifice is ideal for limited pipe run measurements in gas, liquid, or steam applications (8-in. (200 mm) nominal diameter and smaller lines). The 405C Conditioning Orifice delivers consistent and accurate measurements one would expect from traditional orifice plate technology.
Centering Mechanism
Improper centering of any orifice type device can cause an error of up to ±5% in small line sizes. A centering mechanism independent of flange rating is standard with the 405 Compact Orifice Series.
Annubar® Flowmeter Series: Rosemount
3051SFA ProBar and 285
The state-of-the-art, fifth generation Rosemount 485 Annubar combined with the 3051S or 3095 MultiVariable transmitter creates an accurate, repeatable and dependable insertion-type flowmeter. The Rosemount 285 provides a commercial product offering for your general purpose applications.
Compact Orifice Flowmeter Series: Rosemount 3051SFC, 3095MFC, and 405
Compact Orifice Flowmeters can be installed between existing flanges, up to a Class 600 (PN100) rating. In tight fit applications, a conditioning orifice plate version is available, requiring only two diameters of straight run upstream.
®
, 3095MFA Mass ProBar®, 485,
Based on ASME/ISO Corner Tap Design
The incorporation of design features from proven standards results in a product that performs in a predictable manner and operates on well-known principles.
Advanced PlantWeb
Rosemount orifice flowmeters power PlantWeb through a scalable architecture, advanced diagnostics, and MultiVariable capabilities. This reduces operational and maintenance expenditures while improving throughput
and utilities management.
Rosemount DP-Flow Solutions
Integral Orifice Flowmeter Series: Rosemount 3051SFP
ProPlate®, 3095MFP Mass ProPlate, and 1195
These integral orifice flowmeters eliminate the inaccuracies that become more pronounced in small orifice line installations. The completely assembled, ready to install flowmeters reduce cost and simplify installation.
Orifice Plate Primary Element Systems: Rosemount 1495 and 1595 Orifice Plates, 1496 Flange Unions and 1497 Meter Sections
A comprehensive offering of orifice plates, flange unions and meter sections that is easy to specify and order. The 1595 Conditioning Orifice provides superior performance in tight fit applications.
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
®
Functionality
2
Product Data Sheet
Rosemount 3051SFC Compact Orifice Flowmeter
See ordering information on page 16.
Combines the Rosemount 3051S scalable pressure transmitter with the 405 Compact Orifice Primary
Accuracy up to ±0.80% of volumetric rate
Remote display and interface assembly enables direct mounting with “at-grade” operator interface
F
OUNDATION
®
fieldbus protocol available
Ideal fluid type: liquid
Rosemount 3095MFC Compact Orifice Mass Flowmeter
See ordering information on page 29.
Combines the Rosemount 3095MV MultiVariable mass flow transmitter with the 405 Compact Orifice Primary
Accuracy up to ±0.70% of mass flow rate
Measures differential pressure, static pressure, and process temperature (remotely) all in one flowmeter assembly
Dynamically calculates compensated mass flow
Ideal fluid types: gas and steam
Rosemount 405 Compact Orifice Primary
See ordering information on page 38.
Integral manifold head allows direct mounting of DP transmitters
Ideal fluid types: liquid, gas, and steam
Accuracy up to ±0.5% of discharge coefficient uncertainty
Direct mounting capability to ANSI 600# rating
Self-centering alignment ring
3095MFC Compact Orifice
Mass Flowmeter
405C Conditioning
Orifice
3051SFC Compact
Orifice Flowmeter
405P Compact
Orifice
00813-0100-4810, Rev HA March 2008
405 Compact Orifice Series Selection Guide
Rosemount Compact Orifice
Flowmeter Series
3
Rosemount Compact Orifice Flowmeter Series
Rosemount 3051SFC Compact Orifice Flowmeter
SPECIFICATIONS
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Performance
System Reference Accuracy
Percent (%) of volumetric flow rate TABLE 1. 3051SFC Compact Orifice Flowmeter
Classic
(8:1 flow
Typ e Beta
3051SFCC
3051SFCP
3051SFCP
3051SFCP
(1) Line sizes 1/2-in. (15mm).
(2) Line sizes 1-in. to 1 1/2-in. (25mm to 40mm).
(3) Line sizes 2-in. to 12-in. (50mm to 300mm).
(4) For 0.65 beta and ReD< 10,000 add an additional ± 0.5% to the
(1)
(2)
(3)
Discharge Coefficient Uncertainty.
0.4
0.65
0.4
0.65
0.4
0.65
0.4
0.65
turndown)
±1.05% ±1.35%
±2.45% ±2.35% ±2.30%
(4)
±2.00% ±1.90% ±1.85%
(4)
±1.55% ±1.45% ±1.40%
(4)
Ultra
(8:1 flow
turndown)
±0.85% ±1.20%
Repeatability
±0.1%
Ultra for
(14:1 flow
turndown)
±0.80% ±1.15%
Functional
Service
• Liquid
•Gas
•Steam
Flow
4–20 mA/HART
Zero and Span Adjustment
Zero and span values can be set anywhere within the range. Span must be greater than or equal to the minimum span.
Output
Two-wire 4–20 mA is user-selectable for linear or square root output. Digital process variable superimposed on 4–20 mA signal, available to any host that conforms to the HART protocol.
Power Supply
External power supply required.
Standard transmitter (4–20 mA): 10.5 to 42.4 V dc with no load
3051S HART Diagnostics transmitter: 12 to 42 Vdc with no load
Line Sizes
•1/2-in. (15 mm) – not available for the 3051SFCC
• 1-in. (25 mm) – not available or the 3051SFCC
1
/2-in. (40 mm) – not available for the 3051SFCC
•1
• 2-in. (50 mm)
• 3-in. (80 mm)
• 4-in. (100 mm)
• 5-in (125 mm)
• 6-in. (150 mm)
• 8-in. (200 mm)
• 10-in. (250 mm)
• 12-in (300 mm)
Performance Statement Assumptions
• Measured pipe I.D
Sizing
Contact an Emerson Process Management representative for assistance. A Configuration Data Sheet is required prior to order for application verification.
4
Product Data Sheet
Voltage (V dc)
Load (Ohms)
Operating
Region
1387
1000
500
0
10.5 20 30
42.4
Voltage (V dc)
Load (Ohms)
Operating
Region
1322
1000
500
0
12.0 20 30
42.4
00813-0100-4810, Rev HA March 2008
Rosemount Compact Orifice
Flowmeter Series
Load Limitations
Maximum loop resistance is determined by the voltage level of the external power supply, as described by:
Standard Transmitter
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 10.5)
The HART communicator requires a minimum
loop resistance of 250Ω for communication.
3051S HART Diagnostics Transmitter (option code DA1)
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 12.0)
The HART communicator requires a minimum
loop resistance of 250Ω for communication.
ASP™ Diagnostics Suite for HART (Option Code DA1)
The 3051S provides Abnormal Situation Prevention indication for a breakthrough in diagnostic capability. The New 3051S ASP™ Diagnostics Suite for HART includes Statistical Process Monitoring (SPM), variable logging with time stamp and advanced process alerts. The enhanced EDDL graphic display provides an intuitive and user-friendly interface to better visualize these diagnostics.
The integral SPM technology calculates the mean and standard deviation of the process variable 22 times per second and makes them available to the user. The 3051S uses these values and highly flexible configuration options for customization to detect many user-defined or application specific abnormal situations (e.g. detecting plugged impulse lines and fluid composition change). Variable logging with time stamp and advanced process alerts capture valuable process and sensor data to enable quick troubleshooting of application and installation issues.
FOUNDATION fieldbus
Power Supply
External power supply required; transmitters operate on 9.0 to
32.0 V dc transmitter terminal voltage.
Current Draw
17.5 mA for all configurations (including LCD display option)
OUNDATION fieldbus Parameters
F
Schedule Entries 14 (max.) Links 30 (max.) Virtual Communications Relationships (VCR) 20 (max.)
Standard Function Blocks
Resource Block
• Contains hardware, electronics, and diagnostic information.
Transducer Block
• Contains actual sensor measurement data including the sensor diagnostics and the ability to trim the pressure sensor or recall factory defaults.
LCD Block
• Configures the local display.
2 Analog Input Blocks
• Processes the measurements for input into other function blocks. The output value is in engineering or custom units and contains a status indicating measurement quality.
PID Block with Auto-tune
• Contains all logic to perform PID control in the field including cascade and feedforward. Auto-tune capability allows for superior tuning for optimized control performance.
Backup Link Active Scheduler (LAS)
The transmitter can function as a Link Active Scheduler if the current link master device fails or is removed from the segment.
Software Upgrade in the Field
Software for the 3051S with F upgrade in the field using the F Device Software Download procedure.
PlantWeb Alerts
Enable the full power of the PlantWeb digital architecture by diagnosing instrumentation issues, communicating advisory, maintenance, and failure details, and recommending a solution.
Advanced Control Function Block Suite (Option Code A01)
Input Selector Block
• Selects between inputs and generates an output using specific selection strategies such as minimum, maximum, midpoint, average, or first “good.”
Arithmetic Block
• Provides pre-defined application-based equations including flow with partial density compensation, electronic remote seals, hydrostatic tank gauging, ratio control and others.
Signal Characterizer Block
• Characterizes or approximates any function that defines an
input/output relationship by configuring up to twenty X, Y coordinates. The block interpolates an output value for a given input value using the curve defined by the configured coordinates.
Integrator Bock
• Compares the integrated or accumulated value from one or
two variables to pre-trip and trip limits and generates discrete output signals when the limits are reached. This block is useful for calculating total flow, total mass, or volume over time.
OUNDATION fieldbus is easy to
OUNDATION fieldbus Common
5
Rosemount Compact Orifice Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Output Splitter Block
• Splits the output of one PID or other control block so that the PID will control two valves or other actuators.
Control Selector Block
• Selects one of up to three inputs (highest, middle, or lowest) that are normally connected to the outputs of PID or other control function blocks.
Block Execution Time
Resource ­Transducer ­LCD Block ­Analog Input 1, 2 20 milliseconds PID with Auto-tune 35 milliseconds Input Selector 20 milliseconds Arithmetic 20 milliseconds Signal Characterizer 20 milliseconds Integrator 20 milliseconds Output Splitter 20 milliseconds Control Selector 20 milliseconds
Fully Compensated Mass Flow Block (Option Code H01)
Calculates fully compensated mass flow based on differential pressure with external process pressure and temperature measurements over the fieldbus segment. Configuration for the mass flow calculation is easily accomplished using the Rosemount 3095 Engineering Assistant.
ASP™ Diagnostics Suite for F Code D01)
The 3051S ASP™ Diagnostics Suite for F provides Abnormal Situation Prevention indication and enhanced EDDL graphic displays for easy visual analysis.
The integral Statistical Process Monitoring (SPM) technology calculates the mean and standard deviation of the process variable 22 times per second and makes them available to the user. The 3051S uses these values and highly flexible configuration options for customization to detect many user-defined or application specific abnormal situations (e.g. detecting plugged impulse lines and fluid composition change).
OUNDATION fieldbus (Option
OUNDATION fieldbus
Process Temperature Limits
Direct Mount Transmitter
• 450 °F (232 °C)
Remote Mount Transmitter
• 850 °F (454 °C) – Stainless Steel
Transmitter Temperature Limits
Ambient
• –40 to 185 °F (–40 to 85 °C)
• With Integral Display
Storage
• –50 to 230 °F (–46 to 110 °C)
• With Integral Display: –40 to 185 °F (–40 to 85 °C)
• With Wireless Output (Code X): –40 to 185 °F (–40 to 85 °C)
(1)
: –40 to 175 °F (–40 to 80 °C)
Differential Pressure Limits
Maximum differential pressure (DP) up to 800 inH2O.
Pressure Limits
Direct Mount Transmitter
• Pressure retention per ANSI B16.5 600# or DIN PN
(2)
Static Pressure Limits
• Range 1A: Operates within specification between static line pressures of 0.5 psia to 2000 psig (0.03 to 138 bar)
• Ranges 2A– 3A: Operates within specifications between static line pressures of 0.5 psia and 3626 psig (0.03 bar-A to 250 bar-G)
Vibration Limits
Qualified per IEC61298-3 (1998) for field with high vibration level or pipeline with high vibration level (10-60Hz 0.21mm displacement peak amplitude / 60 - 500Hz 3g).
The weight and length of the transmitter assembly shall not exceed
5.8 lbs and 7.75-in.
Burst Pressure Limits
Coplanar or traditional process flange
• 10000 psig (689,5 bar)
Wireless Self-Organizing Networks
Output
Wireless enabled HART.
Transmit Rate
User selectable, 15 sec. to 60 min.
Power Module
Replaceable, Intrinsically Safe Lithium-thionyl chloride Power Module with polybutadine terephthalate (PBT) enclosure. Five-year life at one minute transmit rate: ten-year life at ten minute transmit rate.
(1) Reference conditions are 70 °F (21 °C), and routing data for three
additional network devices. NOTE Continuous exposure to ambient temperature limits, -40 °F (-40 °C) or 185 °F (85 °C), may reduce specified life by less than 20 percent.
6
(1)
(1) LCD display may not be readable and LCD updates will be
slower at temperatures below -4 °F (-20 °C).
(2) Static pressure selection may effect pressure limitations.
Product Data Sheet
T
c
T
d
Td = Dead Time T
c
= Time Constant
Pressure Released
Response Time = Td+T
c
63.2% of Total Step Change
Time
0%
100%
36.8%
Transmitter Output vs. Time
00813-0100-4810, Rev HA March 2008
Rosemount Compact Orifice
Flowmeter Series
Overpressure Limits
Transmitters withstand the following limits without damage:
• Range 1A: 2000 psig (138 bar)
• Ranges 2A–3A: 3626 psig (250 bar)
TABLE 2. Overpressure Limits
Standard Typ e
(1)
Carbon Steel Rating
Stainless Steel Rating
ANSI/ASME Class 150 285 (20) 275 (19) ANSI/ASME Class 300 740 (51) 720 (50) ANSI/ASME Class 600 1480 (102) 1440 (99)
At 100 °F (38 °C), the rating decreases with increasing temperature.
DIN PN 10/40 580 (40) 580 (40) DIN PN 10/16 232 (16) 232 (16) DIN PN 25/40 580 (40) 580 (40)
At 248 °F (120 °C), the rating decreases with increasing temperature.
(1) Carbon Steel and Stainless Steel Ratings are measured in
psig (bar).
Humidity Limits
• 0–100% relative humidity
Turn-On Time
Performance within specifications less than 2 seconds (typical) after power is applied to the transmitter
Damping
Analog output response to a step input change is user-selectable from 0 to 60 seconds for one time constant. This software damping is in addition to sensor module response time
Dynamic Performance
(1)
Failure Mode Alarm
HART 4-20mA (output option codes A and B)
If self-diagnostics detect a gross transmitter failure, the analog signal will be driven offscale to alert the user. Rosemount standard (default), NAMUR, and custom alarm levels are available (see Table 3).
High or low alarm signal is software-selectable or hardware-selectable via the optional switch (option D1).
TABLE 3. Alarm Configuration
High Alarm Low Alarm
Default 21.75 mA 3.75 mA NAMUR compliant Custom levels
(1) Analog output levels are compliant with NAMUR
recommendation NE 43, see option codes C4 or C5.
(2) Low alarm must be 0.1 mA less than low saturation and high
alarm must be 0.1 mA greater than high saturation.
3051S Safety-Certified Transmitter Failure Values
Safety accuracy: 2.0% Safety response time: 1.5 seconds
(1) A 2% variation of the transmitter mA output is allowed before
a safety trip. Trip values in the DCS or safety logic solver should be derated by 2%.
(1)
(2)
22.5 mA 3.6 mA
20.2 - 23.0 mA 3.6 - 3.8 mA
(1)
Total Response Time (Td + Tc)
Dead Time (Td) Update Rate 3051S 22 times per second 22 times per second
(1)
3051S_C, Ranges 2A - 3A:
Range 1A:
(5)
(1) Does not apply to wireless output code X. See “Wireless Self-Organizing Networks” on page 6 for wireless transmit rate.
(2) Dead time and update rate apply to all models and ranges; analog output only
(3) Transmitter fieldbus output only, segment macro-cycle not included.
(4) Nominal total response time at 75 °F (24 °C) reference conditions. For option code DA1, add 45 milliseconds (nominal) to 4-20 mA (HART®) total
response time values.
(5) For option code DA1, dead time (Td) is 90 milliseconds (nominal).
4 - 20 mA (HART®)
(4)
:
100 milliseconds 255 milliseconds
45 milliseconds (nominal) 97 milliseconds
(2)
Fieldbus protocol
152 milliseconds 307 milliseconds
(3)
Typical Transmitter Response Time
7
Rosemount Compact Orifice Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Physical
Temperature Measurement
Remote RTD
• 100 Ohm platinum with series with Rosemount 644 housing) Model 0078D21N00A025T32Ex Connection Head: 00644-4410-0011
• Standard RTD cable is shielded armored cable, length is 12 feet (3.66 m)
Thermowell with Remote RTD
1
/2-in. x 1/2-in. NPT, 316 SST
NOTE
Remote temperature measurement is not available for and 11/2-in. sizes.
Electronic Connections for Remote Mount
1
/2–14 NPT, G1/2, and M20 × 1.5 (CM20) conduit. HART interface
connections fixed to terminal block for output code A
Material of Construction
Body/Plate
•316 SST
• 50 micro-inch Ra surface finish
Manifold Head/Valves
•316 SST
Flange Studs and Nuts
• Customer supplied
• Available as a spare part
Transmitter Connection Studs and Nuts
• Studs– A193 Grade B8M.
• Nuts– A194 Grade 8M.
Gasket and O-rings
• Gaskets are customer supplied.
• Durlon 8500 fiber gaskets are recommended. Consult an Emerson Process Management representative for use with other gaskets.
• Available as a spare part
NOTE
Gaskets and O-rings must be replaced when the 405 is disassembled.
1
/2-in. NPT nipple and union (078
1
/2-in., 1-in.,
Process-Wetted Parts
Integral Manifolds
•316 SST
• Hastelloy C-276
Remote Manifolds
•316 SST
• Hastelloy C-276
Transmitter Vent Valves and Process Flanges
•316 SST
• Hastelloy C-276
• Glass-filled PTFE O-rings
Process Isolating Diaphragms
• 316L SST
• Hastelloy C-276
Integral Manifold O-Rings
• PTFE/Graphite
Non-Wetted Parts
Sensor Module Fill Fluid
• Silicone oil
• Inert Fill optional
Cover O-rings
•Buna-N
Remote Mounting Brackets
• SST
Electronic Housing
• Low copper aluminum, NEMA 4x, IP65
• SST (optional)
Paint
• Polyurethane
Bolts
•CS
Transmitter Connections
Remote Mount
• Available with connections
Orifice Type
• Square edged, Wafer style
Orifice Pressure Taps
• Corner
1
/4-in. (standard) or 1/2-in. (option code E)
Process Connections
Mounts between the following flange configurations:
ASME B16.5 (ANSI)
Class 150
Class 300
Class 600
ANSI alignment ring is included as standard when ordering.
8
DIN JIS
PN16 (option code G)
PN40 (option code H)
PN100 (option code H)
10k (option code B)
20k (option code R)
40k (option code S)
Product Data Sheet
00813-0100-4810, Rev HA March 2008
Rosemount Compact Orifice
Flowmeter Series
Typical Orifice Hole Sizes (For 3051SFCC)
Beta is calculated by: (β) = dC / Pipe ID, where the calculated bore is equal to 2 x typical orifice hole size (d shows the diameter of each of the four typical orifice holes.
TABLE 4. β = 0.4
(1)(2)
Line Size 3051SFCC 3051SFCP
1
/2-in. (15 mm) Not Available 0.249 (6.325)
1-in. (25 mm) Not Available 0.420 (10.668)
1
/2-in. (40 mm) Not Available 0.644 (16.358)
1 2-in. (50 mm) 0.413 (10.490) 0.827 (21.006) 3-in. (80 mm) 0.614 (15.596) 1.227 (31.166) 4-in. (100 mm) 0.805 (20.447) 1.610 (40.894) 5-in. (125 mm) 1.009 (25.629) 2.019 (51.283) 6-in. (150 mm) 1.213 (30.810) 2.426 (61.620) 8-in. (200 mm) 1.596 (40.538) 3.192 (81.077) 10-in. (250 mm) 2.004 (50.902) 4.008 (101.80) 12-in. (300 mm) 2.400 (60.960) 4.800 (121.92)
TABLE 5. β = 0.65
(1)(2)
Line Size 3051SFCC 3051SFCP
1
/2-in. (15 mm) Not Available 0.404 (10.262)
1-in. (25 mm) Not Available 0.682 (17.323)
1
/2-in. (40 mm) Not Available 1.047 (26.594)
1 2-in. (50 mm) 0.620 (15.748) 3-in. (80 mm) 0.997 (25.324) 1.994 (50.648) 4-in. (100 mm) 1.308 (33.223) 2.617 (66.472) 5-in. (125 mm) 1.640 (40.640) 3.281 (83.34) 6-in. (150 mm) 1.971 (50.063) 3.942 (100.127) 8-in. (200 mm) 2.594 (65.888) 5.188 (131.775) 10-in. (250 mm) 3.257 (82.728) 6.513 (165.43) 12-in. (300 mm) 3.900 (99.060) 7.800 (198.120)
(1) Measurement is in inches (millimeters)
(2) Tolerance = ±0.002-in.
(3) Beta (β) = 0.60-in. (15.24 mm) for 2-in. line size only.
= 2d). The table below
C
(3)
1.344 (34.138)
3051SFC Weight
Line Size Direct Mount (D3)
1
/2-in. (15 mm) 10.7 (4.58) 7.5 (3.70)
1-in. (25 mm) 11.45 (5. 1 9) 8.25 (4.07)
1
/2-in. (40 mm) 11.95 (5.42) 8.75 (4.32)
1 2-in. (50 mm) 12.20 (5.53) 9.00 (4.44) 3-in. (80 mm) 14.20 (6.44) 11.00 (5.43) 4-in. (100 mm) 16.70 (7.57) 13.50 (6.67) 5-in. (125 mm) 18.45 (8.37) 15.25 (7.53) 6-in. (150 mm) 20.20 (9.16) 17.00 (8.40) 8-in. (200 mm) 25.45 (11.54) 22.25 (10.99) 10-in (250 mm) 30.70 (13.92) 27.50 (13.58) 12-in (300 mm) 36.70 (16.64) 33.50 (16.54)
(1) Measurement in lb (kg).
(2) Includes 3051S Coplanar PlantWeb housing transmitter.
(1)(2)
Remote Mount (R3)
3095MFC Weight
Line Size Direct Mount (D3)
1
/2-in. (15 mm) 9.50 (4.69) 6.3 (3.11)
1-in. (25 mm) 10.25 (5.06) 7.05 (3.48)
1
/2-in. (40 mm) 10.75 (5.31) 7.55 (3.73)
1 2-in. (50 mm) 11.00 (5.43) 7.80 (3.85) 3-in. (80 mm) 13.00 (6.42) 9.80 (4.84) 4-in. (100 mm) 15.50 (7.65) 12.30 (6.07) 5-in. (125 mm) 17.25 (8.52) 14.05 (6.94) 6-in. (150 mm) 19.00 (9.38) 15.80 (7.80) 8-in. (200 mm) 24.25 (11.98) 21.05 (10.40) 10-in (250 mm) 29.50 (14.57) 26.30 (12.9) 12-in (300 mm) 35.50 (17.53) 32.30 (15.95)
(1) Measurement in lb (kg).
(2) Includes 3095 MultiVariable transmitter.
(1)(2)
Remote Mount (R3)
405 Weight
Line Size Direct Mount (D3)
1
/2-in. (15 mm) 3.50 (1.73) 7.5 (3.70)
1-in. (25 mm) 4.25 (2.10) 8.25 (4.07)
1
/2-in. (40 mm) 4.75 (2.34) 8.75 (4.32)
1 2-in. (50 mm) 5.00 (2.47) 9.00 (4.44) 3-in. (80 mm) 7.00 (3.45) 11.00 (5.43) 4-in. (100 mm) 9.50 (4.69) 13.50 (6.67) 5-in. (125 mm) 11.25 (5.55) 15.25 (7.53) 6-in. (150 mm) 13.00 (6.41) 17.00 (8.40) 8-in. (200 mm) 18.25 (9.00) 22.25 (10.99) 10-in (250 mm) 23.50 (11.59) 27.50 (13.58) 12-in (300 mm) 29.50 (14.55) 33.50 (16.54)
(1) Measurement in lb (kg).
(2) Includes 405 Direct Mount option D3.
(1)(2)
Remote Mount (R3)
(1)
(1)
(1)
9
Rosemount Compact Orifice
Upstream (inlet)
side of primary
3051SFCDP Compact Orifice
3051SFCDC
Conditioning
Orifice
30°
120°
30°
360°
FLOW
Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Installation Considerations
Straight Run Requirements
TABLE 6. 3051SFCC Straight Pipe Requirements
Beta 0.40 0.65
Reducer (1 line size) 2 2 Single 90° bend or tee 2 2 Two or more 90 ° bends in the same
plane Two or more 90° bends in different
plane
side of primary
Up to 10° of swirl 2 2
Upstream (inlet)
Butterfly valve (75% to 100% open) 2 N/A
Downstream (outlet) side of primary
TABLE 7. 3051SFCP Straight Pipe Requirements
Beta 0.40 0.65
(2)(3)
Downstream (outlet) side of primary
(1) Consult an Emerson Process Management representative if
(2) Recommended lengths represented in pipe diameters per
(3) Refer to ISO 5167 for recommended lengths when using flow
Reducer (1 line size) 5 12 Single 90° bend or tee 16 44 Two or more 90 ° bends
in the same plane Two or more 90° bends
in different plane Expander 12 28 Ball / Gate valve fully open 12 18
disturbance is not listed.
ISO 5167.
straighteners.
(1)
2 2
2 2
22
(1)(2)(3)
10 44
50 60
6 7
Flowmeter Orientation
Flowmeter orientation for both 3051SFC Conditioning Compact Orifice and standard Compact Orifice.
Gas (Horizontal)
Liquid and Steam (Horizontal)
50°
50°
80°
Gas (Vertical)
Pipe Orientation
Pipe orientation for both 3051SFCC Compact Conditioning and standard 3051SFCP Compact Orifice.
Process
Orientation/ Flow Direction
Horizontal D/R D/R D/R Vertical Up R D/R R Vertical Down D/R NR NR
(1) D = Direct mount acceptable (recommended)
R = Remote mount acceptable NR = Not recommended
Gas Liquid Steam
(1)
Pipe Centering
Improper centering of any orifice type device can cause an error of up to ±5% in small line sizes. A centering mechanism (centering ring) independent of flange rating comes standard with the 405 Compact Orifice Series.
10
Liquid (Vertical)
360°
FLOW
Product Data Sheet
00813-0100-4810, Rev HA March 2008
PRODUCT CERTIFICATIONS
Approved Manufacturing Locations
Rosemount Inc. — Chanhassen, Minnesota USA
Emerson Process Management GmbH & Co. — Wessling, Germany
Emerson Process Management Asia Pacific Private Limited — Singapore
Beijing Rosemount Far East Instrument Co., LTD — Beijing, China
European Directive Information
The EC declaration of conformity for all applicable European directives for this product can be found at www.rosemount.com. A hard copy may be obtained by contacting an Emerson Process Management representative.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX Directive.
European Pressure Equipment Directive (PED) (97/23/EC)
Models 3051S_CA4; 3051S_CD2, 3, 4, 5; (also with P9 option) Pressure Transmitters — QS Certificate of Assessment ­EC No. PED-H-20, Module H Conformity Assessment
All other Model 3051S Pressure Transmitters — Sound Engineering Practice
Transmitter Attachments: Diaphragm Seal - Process Flange ­Manifold
Primary Elements, Flowmeter — See appropriate Primary Element QIG
— Sound Engineering Practice
Electro Magnetic Compatibility (EMC) (89/336/EEC)
All Models: EN 50081-1: 1992; EN 50082-2:1995; EN 61326-1:1997 – Industrial
Ordinary Location Certification for FM
As standard, the transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
Hazardous Locations Certifications
North American Certifications
FM Approvals
E5 Explosion-proof for Class I, Division 1, Groups B, C, and D;
dust-ignition proof for Class II and Class III, Division 1, Groups E, F, and G; hazardous locations; enclosure Type 4X, conduit seal not required when installed according to Rosemount drawing 03151-1003.
Rosemount Compact Orifice
Flowmeter Series
I5/IE Intrinsically Safe for use in Class I, Division 1, Groups A, B,
C, and D; Class II, Division 1, Groups E, F, and G; Class III, Division 1; Class I, Zone 0 AEx ia IIC when connected in accordance with Rosemount drawing 03151-1006; Non-incendive for Class I, Division 2, Groups A, B, C, and D Enclosure Type 4X For entity parameters see control drawing 03151-1006.
Canadian Standards Association (CSA)
E6 Explosion-proof for Class I, Division 1, Groups B, C, and D;
Dust-Ignition-Proof for Class II and Class III, Division 1, Groups E, F, and G; suitable for Class I, Division 2, Groups A, B, C, and D, when installed per Rosemount drawing 03151-1013, CSA Enclosure Type 4X; conduit seal not required.
I6/IF Intrinsically Safe for Class I, Division 1, Groups A, B, C, and
D when connected in accordance with Rosemount drawings 03151-1016; For entity parameters see control drawing 03151-1016.
European Certifications
I1/IA ATEX Intrinsic Safety
Certificate No.: BAS01ATEX1303X II 1G EEx ia IIC T4 (T Display/Quick Connect/HART Diagnostics EEx ia IIC T4 (T EEx ia IIC T4 (T IP66
118 0
TABLE 8. Input Parameters
Loop / Power Groups
U
= 30 V HART / FOUNDATION fieldbus/ Remote
i
Ui = 17.5 V FISCO I
= 300 mA HART / FOUNDATION fieldbus/ Remote
i
Ii = 380 mA FISCO P
= 1.0 W HART / Remote Display / Quick Connect /
i
Pi = 1.3 W FOUNDATION fieldbus P
= 5.32 W FISCO
i
Ci = 30 nF SuperModule Platform / Quick Connect C
= 11.4 nF HART / HART Diagnostics
i
Ci = 0 FOUNDATION fieldbus / Remote Display /
L
= 0 HART / FOUNDATION fieldbus/ FISCO /
i
Li = 60 µH Remote Display
Special conditions for safe use (x)
1. The apparatus, excluding the Types 3051 S-T and 3051 S-C (In-line and Coplanar SuperModules respectively), is not capable of withstanding the 500V test as defined in Clause 6.4.12 of EN 50020. This must be considered during installation.
2. The terminal pins of the Types 3051 S-T and 3051 S-C must be protected to IP20 minimum.
= -60 °C to 70 °C) -HART/Remote
a
= -60 °C to 70 °C) -FOUNDATION fieldbus
a
= -60 °C to 40 °C) -FISCO
a
Display / Quick Connect / HART Diagnostics
Display / Quick Connect / HART Diagnostics
HART Diagnostics
FISCO
Quick Connect / HART Diagnostics
11
Rosemount Compact Orifice Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
N1 ATEX Typ e n
Certificate No.: BAS01ATEX3304X II 3 G EEx nL IIC T4 (T Ui = 45 Vdc max IP66
Special conditions for safe use (x)
The apparatus is not capable of withstanding the 500V insulation test required by Clause 9.1 of EN 50021: 1999. This must be taken into account when installing the apparatus.
ND ATEX Dust
Certificate No.: BAS01ATEX1374X II 1 D T105°C (-20 °C ≤ T
= 42.4 volts max
V
max
A = 22 mA IP66
118 0
Special conditions for safe use (x)
1. The user must ensure that the maximum rated voltage and current (42.4 volts, 22 milliampere, DC) are not exceeded. All connections to other apparatus or associated apparatus shall have control over this voltage and current equivalent to a category “ib” circuit according to EN 50020.
2. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
3. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
4. Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7J impact test.
5. The 3051S must be securely screwed in place to maintain the ingress protection of the enclosure.
E1 ATEX Flameproof
Certificate No.: KEMA00ATEX2143X II 1/2 G EEx d IIC T6 (-50 °C ≤ T EEx d IIC T5 (-50 °C ≤ T
= 42.4V
V
max
118 0
Special conditions for safe use (x)
This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime. The Model 3051S pressure transmitter must include a Series 300S housing integrally mounted to a Series Model 3051S Sensor module as per Rosemount drawing 03151-1023.
= -40 °C TO 70 °C)
a
85 °C)
amb
65 °C)
amb
80 °C)
amb
Japanese Certifications
E4 TIIS Flameproof
Ex d IIC T6
Certificate Description
TC15682 Coplanar with Junction Box Housing TC15683 Coplanar with PlantWeb Housing TC15684 Coplanar with PlantWeb Housing
TC15685 In-Line SST with Junction Box Housing TC15686 In-Line Hastelloy with Junction Box Housing TC15687 In-Line SST with PlantWeb Housing TC15688 In-Line Hastelloy with Plantweb Housing TC15689 In-Line SST with Plantweb Housing
TC15690 In-Line Hastelloy with PlantWeb Housing
and LCD Display
and LCD Display
and LCD Display
Australian Certifications
E7 SAA Flameproof and Dust Ignition-proof
Certification No.: AUS Ex 3798X Ex d IIC T6 (T DIP A21 TA T6 (T
Special conditions for safe use (x)
1. It is a condition of safe use that each housing shall be connected to external circuits via suitable conduit or Standards Australia certified cable glands. Where only one entry is used for connection to external circuits, the unused entry shall be closed by means of the blanking plug supplied by the equipment manufacturer or by a suitable Standards Australia certified blanking plug.
2. It is a condition of safe use that a dielectric strength test shall be applied whenever the terminal block is changed or replaced in either the dual compartment or single compartment housings. The breakdown current shall be less than 5 mA, when 500 V, 47 to 62 Hz, is applied for one minute. Note: if tested with an optional T1 transient protector terminal block fitted, the protection will operate and hence there will be no current indicated.
3. It is a condition of safe use that each transmitter module shall be used with a Model 300S housing, in order to comply with flameproof requirements.
4. It is a condition of safe use that each model 300S housing fitted with a transmitter module shall be marked with the same certification marking code information. Should the housing be replaced after initial supply to another model 300S housing, the replacement housing shall have the same certification marking code information as the housing it replaces.
= 60°C) IP66
a
= 60°C) IP66
a
12
Product Data Sheet
µ
00813-0100-4810, Rev HA March 2008
Rosemount Compact Orifice
Flowmeter Series
IECEx Certifications
I7/IG IECEx Intrinsic Safety
Certificate No.: IECExBAS04.0017X Ex ia IIC T4 (T Display/Quick Connect/HART Diagnostics Ex ia IIC T4 (T Ex ia IIC T4 (T IP66
TABLE 9. Input Parameters
Loop / Power Groups
U
= 30 V HART / FOUNDATION fieldbus/
i
Ui = 17.5 V FISCO I
= 300 mA HART / FOUNDATION fieldbus/
i
Ii = 380 mA FISCO P
= 1.0 W HART / Remote Display / Quick
i
Pi = 1.3 W FOUNDATION fieldbus P
= 5.32 W FISCO
i
Ci = 30 nF SuperModule Platform / Quick
C
= 11.4 nF HART / HART Diagnostics
i
Ci = 0 FOUNDATION fieldbus / Remote
= 0 HART / FOUNDATION fieldbus /
L
i
Li = 60 H Remote Display
Special conditions for safe use (x)
1. The Models 3051S HART 4-20mA, 3051S fieldbus, 3051S Profibus and 3051S FISCO are not capable of withstanding the 500V test as defined in clause 6.4.12 of IEC 60079-11. This must be taken into account during installation.
2. The terminal pins of the Types 3051S-T and 3051S-C must be protected to IP20 minimum.
= -60 °C to 70 °C) -HART/Remote
a
= -60 °C to 70 °C) -FOUNDATION fieldbus
a
= -60 °C to 40 °C) -FISCO
a
Remote Display / Quick Connect / HART Diagnostics
Remote Display / Quick Connect / HART Diagnostics
Connect / HART Diagnostics
Connect
Display / FISCO / Quick Connect / HART Diagnostics
FISCO / Quick Connect / HART Diagnostics
N7 IECEx Type n
Certificate No.: IECExBAS04.0018X Ex nC IIC T4 (Ta = -40 °C to 70 °C) Ui = 45 Vdc MAX IP66
Special conditions for safe use (x)
The apparatus is not capable of withstanding the 500 V insulation test required by Clause 8 of IEC 79-15: 1987.
Combinations of Certifications
Stainless steel certification tag is provided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinstalled using any other approval types. Permanently mark the approval label to distinguish it from unused approval types.
K1 Combination of E1, I1, N1, and ND
K5 Combination of E5 and I5
K6 Combination of E6 and I6
K7 Combination of E7, I7, and N7
KA Combination of E1, I1, E6, and I6
KB Combination of E5, I5, I6 and E6
KC Combination of E5, E1, I5 and I1
KD Combination of E5, I5, E6, I6, E1, and I1
13
Rosemount Compact Orifice
Radio Power Label
Figure 1.
Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
WIRELESS CERTIFICATIONS
Telecommunication Compliance
All wireless devices require certification to ensure that they adhere to regulations regarding the use of the RF spectrum. Nearly every country requires this type of product certification. Emerson is working with governmental agencies around the world to supply fully compliant products and remove the risk of violating country directives or laws governing wireless device usage.
FCC and IC Approvals
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause harmful interference this device must accept any interference received, including interference that may cause undesired operation.
This device must be installed to ensure a minimum antenna separation distance of 20cm from all persons.
Ordinary Location Certification for FM
As standard, the transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
European Directive Information
The EC declaration of conformity for all applicable European directives for this product can be found at www.rosemount.com. A hard copy may be obtained by contacting an Emerson Process Management representative.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX Directive.
European Pressure Equipment Directive (PED) (97/23/EC)
Models 3051S_CA4; 3051S_CD2, 3, 4, 5; (also with P9 option) Pressure Transmitters — QS Certificate of Assessment ­EC No. PED-H-100, Module H Conformity Assessment
All other Model 3051S Pressure Transmitters — Sound Engineering Practice
Transmitter Attachments: Diaphragm Seal - Process Flange ­Manifold
Primary Elements, Flowmeter — See appropriate Primary Element QIG
Electro Magnetic Compatibility (EMC) (2004/108/EC)
All Models: EN 50081-1: 1992; EN 50082-2:1995; EN 61326-1:1997 + A1, A2, and A3 – Industrial
Radio and Telecommunications Terminal Equipment Directive (R&TTE)(1999/5/EC)
Emerson Process Management complies with the R&TTE Directive.
— Sound Engineering Practice
Hazardous Locations Certifications
North American Certifications
Factory Mutual (FM) Approvals
I5 FM Intrinsically Safe, Non-Incendive, and Dust Ignition-proof.
Intrinsically Safe for Class I/II/III, Division 1, Groups A, B, C, D, E, F, and G. Zone Marking: Class I, Zone 0, AEx ia llC Temperature Codes T4 (T Non-Incendive for Class I, Division 2, Groups A, B, C, and D. Dust Ignition-proof for Class II/III, Division 1, Groups E, F, and G. Ambient temperature limits: -50 to 85° C For use with Rosemount SmartPower options 00753-9220-XXXX only. Enclosure Type 4X / IP66
CSA - Canadian Standards Association
I6 CSA Intrinsically Safe
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D. Temp Code T3C Enclosure Type 4X / IP66 For use with Rosemount SmartPower options 00753-9220-XXXX only.
European Certifications
I1 ATEX Intrinsic Safety
Certificate No.: BAS01ATEX1303X II 1G Ex ia IIC T4 (T IP66 For use with Rosemount SmartPower options 00753-9220-XXXX only.
1180
Country Restriction
Bulgaria General authorization required for outdoor use
France Outdoor use limited to 10mW e.i.r.p. Italy If used outside of own premises, general
Norway May be restricted in the geographical area within
Romania Use on a secondary basis. Individual license
Radio Power Label (See Figure 1) indicates output power configuration of the radio. Devices with this label are configured for output power less than 10 mW e.i.r.p. At time of purchase the customer must specify ultimate country of installation and operation.
= -60 °C to 70 °C)
a
and public service
authorization is required.
a radius of 20 km from the center of Ny-Alesund.
required.
= -50 to 70° C)
amb
14
IECEx Certifications
I7 IECEx Intrinsic Safety
Certificate No.: IECEx BAS 04.0017X Ex ia IIC T4 (Ta = -60 °C to 70 °C) For use with Rosemount SmartPower options 00753-9220-XXXX only. IP66
Product Data Sheet
1.13 (28.7)
1.00 (25.4
C
A
B
1.13 (28.7)
1.00 (25.4
C
00813-0100-4810, Rev HA March 2008
DIMENSIONAL DRAWINGS
Rosemount 3051SFC Compact Orifice Flowmeter
Orifice Plate Front View Orifice Plate Side View Orifice Plate Top View
B
A
Compact Orifice Plate
(Primary Element Type code P)
Rosemount Compact Orifice
Flowmeter Series
D
D
(Primary Element Type code C)
Conditioning Orifice Plate
TABLE 10. Dimensional Drawings
Plate Type A B Transmitter Height C D
Type P and C 5.50 (140) Transmitter Height + A 7.75 (197) 7.75 (197) - closed
(1) Measurement in inches (millimeters).
(1)
8.25 (210) - open
6.00 (152) - closed
6.25 (159) - open
15
Rosemount Compact Orifice Flowmeter Series
ORDERING INFORMATION
Rosemount 3051SFC Compact Orifice Flowmeter Ordering Information
Model Product Description
3051SFC Compact Orifice Flowmeter
Code Measurement Type
D Differential Pressure
Code Primary Element Type
C Conditioning Orifice Plate P Orifice Plate
Code Material Type
S 316 Stainless Steel (SST)
(1)
H
Code Line Size
(2) 1
005
(2)
010
(2)
015 020 2-in. (50 mm) 030 3-in. (80 mm) 040 4-in. (100 mm)
(1)
050 060 6-in. (150 mm) 080 8-in. (200 mm)
(1)
100
(1)
120
Code Primary Element Style
N Square Edged
Code Beta Ratio
040 0.40 Beta Ratio (β)
(3)
065
Code Temperature Measurement
R Remote Thermowell and RTD
(1)
T 0 No Temperature Sensor
Code Transmitter Connection Platform
3 Direct-mount, 3-valve integral manifold, SST 7 Remote-mount, 1/4-in. NPT connections
Code Differential Pressure Range
1 0 to 25 in H2O (0 to 62.2 mbar) 2 0 to 250 in H2O (0 to 623 mbar) 3 0 to 1000 in H2O (0 to 2.5 bar)
Code Static Pressure Range
A None
Code Output Protocol
A 4–20 mA with digital signal based on HART protocol
(4)
F
(5)
X
Hastelloy
/2-in. (15 mm) 1-in. (25 mm) 11/2-in. (40 mm)
5-in. (125 mm)
10-in (250 mm) 12-in. (300 mm)
0.65 Beta Ratio (β)
Integral RTD and Thermowell
FOUNDATION fieldbus protocol Wireless (Requires wireless options and wireless housing 5A)
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
16
Product Data Sheet
Rosemount Compact Orifice
00813-0100-4810, Rev HA March 2008
Flowmeter Series
Rosemount 3051SFC Compact Orifice Flowmeter Ordering Information
Code Transmitter Housing Style Material Conduit Entry Size
00 None (Customer-supplied electrical connection) 01 Assemble to Rosemount 753R Web-based Monitoring Indicator 1A PlantWeb Housing Aluminum 1B PlantWeb Housing Aluminum M20 x 1.5 (CM20) 1C PlantWeb Housing Aluminum G 1J PlantWeb Housing 316L SST 1K PlantWeb Housing 316L SST M20 x 1.5 (CM20) 1L PlantWeb Housing 316L SST G1/2 2A Junction Box Housing Aluminum 2B Junction Box Housing Aluminum M20 x 1.5 (CM20) 2C Junction Box Housing Aluminum G 2E Junction Box housing with output for remote display and interface Aluminum 2F Junction Box housing with output for remote display and interface Aluminum M20 x 1.5 (CM20) 2G Junction Box housing with output for remote display and interface Aluminum G1/2 2J Junction Box Housing 316L SST 2M Junction Box housing with output for remote display and interface 316L SST 5A Wireless PlantWeb housing Aluminum M20 x 1.5 (CM20)
(6)
7J
Code Transmitter Performance Class for Flow
(7)
1 2 Classic: up to ± 1.05% flow rate accuracy, 8:1 flow turndown, 5-year stability
(7)
3
Code Options
Installation Accessories
G DIN Alignment Ring (PN 16) H DIN Alignment Ring (PN 40, PN 100) B JIS Alignment Ring 10K R JIS Alignment Ring 20K S JIS Alignment Ring 40K
Remote Adapters
E Flange adapters 316 SST (1/2-in. NPT)
High Temperature Applications
T Graphite valve packing (Tmax = 850 °F)
Flow Calibration
(8)
WC
(8)
WD
Pressure Testing
P1 Hydrostatic testing with certificate
Special Cleaning
P2 Cleaning for special processes PA Cleaning per ASTM G93 Level D (section 11.4)
Special Inspection
QC1 Visual and dimensional inspection with certificate QC7 Inspection and performance certificate
Transmitter Calibration Certification
Q4 Calibration Data Certificate for Transmitter QP Calibration Data Certificate and Tamper Evident Seal
Safety Certification
QS Certificate of FMEDA data
(9)
QT
Material Traceability Certifications
(10)
Q8
Quick Connect (A size Mini, 4-pin male termination)
Ultra: up to ± 0.85% flow rate accuracy, 8:1 flow turndown, 10-year stability, limited 12-year warranty
Ultra for Flow: up to ± 0.75% flow rate accuracy, 14:1 flow turndown, 10-year stability. limited 12-year warranty
Discharge coefficient verification (3 point) Discharge coefficient verification (10 point)
Safety Certified to IEC 61508 with certificate of FMEDA data
Material Cert per ISO 10474 3.1.B and EN 10204 3.1.B
1
/2-14 NPT
1
/2
1
/2-14 NPT
1
/2-14 NPT
1
/2
1
/2-14 NPT
1
/2-14 NPT
1
/2-14 NPT
17
Rosemount Compact Orifice
Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series
Rosemount 3051SFC Compact Orifice Flowmeter Ordering Information
Code Conformance
J2 ANSI B31.1 J3 ANSI B31.3 J4 ANSI B31.8
Material Conformance
(11)
J5
Country Certification
J1 Canadian Registration
Product Certifications
E1 ATEX Flameproof I1 ATEX Intrinsic Safety IE FM FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only IF CSA FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
(1)
IA N1 ATEX Type n ND ATEX Dust K1 ATEX Flameproof, Intrinsic Safety, Type n, Dust (combination of E1, I1, N1, and ND) E4 TIIS Flameproof E5 FM Explosion-proof, Dust Ignition-proof I5 FM Intrinsically Safe, Division 2 K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5 and I5) E6 CSA Explosion-proof, Dust Ignition-proof, Division 2 I6 CSA Intrinsically Safe K6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E6 and I6)
(1)
E7 I7 IECEx Intrinsic Safety IG IECEx FISCO Intrinsic Safety; for FOUNDATION fieldbus protocol only N7 IECEx Type n K7 SAA Flameproof, Dust Ignition-proof, IECEx Intrinsic Safety, Type n (combination of E7, I7, and N7) KA ATEX and CSA Flameproof, Intrinsically Safe, Division 2 (combination of E1, I1, E6, and I6)
KB FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5, E6, I5, and I6)
KC FM and ATEX Explosion-proof, Intrinsically Safe, Division 2 (combination of E5, E1, I5, and I1)
KD FM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of E5, I5, E6, I6, E1, and I1)
Alternative Transmitter Material of Construction
L1 Inert Sensor Fill Fluid L2 Graphite-filled PTFE o-ring LA Inert sensor fill fluid and graphite-filled PTFE o-ring
Display
M5 PlantWeb LCD display
(7)(13)
M7
(7)(13)
M8
(7)(13)
M9
Terminal Blocks
(14)
T1
(15)
T2
(15)
T3
Manifold for Remote Mount Option
F2 3-Valve Manifold, SST F6 5-Valve Manifold, SST
PlantWeb Control Functionality
(16)
A01
PlantWeb Diagnostic Functionality
(16)
D01
(17)
DA1
NACE MR-0175 / ISO 15156
ATEX FISCO Intrinsic Safety; for FOUNDATION fieldbus protocol only
SAA Flameproof, Dust Ignition-proof
Note: Only available on Housing Style codes 00, 1A, 1J, 2A, 2J, 2E, or 2M.
Note: Only available on Housing Style codes 00, 1A, 1J, 2A, 2J, 2E, or 2M.
Note: Only available on Housing Style codes 00, 1A, 1J, 2A, 2J, 2E, or 2M.
Note: Only available on Housing Style codes 00, 1A, 1J, 2A, 2J, 2E, or 2M.
(12)
Remote mount LCD display and interface, no cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output Remote mount LCD display and interface, 50 ft. (15 m) cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output Remote mount LCD display and interface, 100 ft. (31 m) cable; PlantWeb housing, SST bracket, requires 4-20 mA / Hart output
Transient terminal block Terminal block with WAGO spring clamp terminals Transient terminal block with WAGO spring clamp terminals
FOUNDATION fieldbus Advanced Control Function Block Suite
FOUNDATION fieldbus Diagnostics Suite HART Diagnostic Suite
March 2008
18
Product Data Sheet
Rosemount Compact Orifice
00813-0100-4810, Rev HA March 2008
Flowmeter Series
Rosemount 3051SFC Compact Orifice Flowmeter Ordering Information
PlantWeb Enhanced Measurement Functionality
(16)(18)
H01
Code Wireless Options - Select code from each wireless category (example: WA2WK1)
Wireless Transmit Rate
WA User Configurable Transmit Rate
Operating Frequency and Protocol
1 2.4 GHz DSSS, HART 2 900 MHz FHSS, HART
Antenna
WK Omnidirectional, Integral Antenna
SmartPower
1 Long-life Power Module Adapter, Intrinsically Safe
Code Options
Special Configuration (Software)
(7)(19)
C4
(7)(19)
C5
(7)(19)
C6
(7)(19)
C7
(7)(19)
C8
Special Configuration (Hardware)
(7)(19)
D1 D4 External ground screw
(7)(19)
DA
Conduit Electrical Connector
(20)
ZE
(20)
ZM
(1) Consult factory for availability.
(2) Not available for Primary Element Type code C.
(3) For 2-in. (50.8 mm) line sizes the Beta Ratio is 0.6 for Primary Element Type code C.
(4) Requires PlantWeb housing.
(5) Available approvals are FM Intrinsically Safe, Division 2 (option code I5), CSA Intrinsically Safe (option code I6), ATEX Intrinsic Safety
(option code I1; only available with 2.4 GHz), and IECEx Intrinsic Safety (option code I7; only available with 2.4 GHz).
(6) Available with output code A only. Available approvals are FM Intrinsically Safe, Division 2 (option code I5) or ATEX Intrinsic Safety (option code I1). Contact
an Emerson Process Management representative for additional information.
(7) Not available with Output Protocol code X.
(8) Not available with Primary Element Type code P.
(9) Not available with output code F or X. Not available with housing code 01 or 7J.
(10) Instrument valves not included in Traceability Certification.
(11) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits
apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
(12) Not available with Housing code 01 or 7J.
(13) Not available with output code F, Housing code 01, option code DA1, or option code QT.
(14) Not available with Housing code 00, 01, 5A, or 7J.
(15) Available with Output Protocol code A and Plantweb housing only.
(16) Requires PlantWeb housing and output code F.
(17) Requires PlantWeb housing and output code A. Includes Hardware Adjustments as standard. Not available with option code QT.
(18) Requires Rosemount Engineering Assistant to configure.
(19) Not available for Output Protocol code F or Housing code 01.
(20) Not available with Housing code 00, 01, 5A, or 7J. Available with Intrinsically Safe approvals only. For FM Intrinsically Safe, Division 2
(option code I5) or FM FISCO Intrinsically Safe (option code IE), install in accordance with Rosemount drawing 03151-1009 to maintain outdoor rating (NEMA 4X and IP66).
Fully Compensated Mass Flow Block
NOTE: Long-life Power Module must be shipped separately, order Part No. 00753-9220-0001.
NAMUR alarm and saturation signal levels, high alarm NAMUR alarm and saturation signal levels, low alarm Custom alarm and saturation signal levels, high alarm
Note: A Configuration Data Sheet must be completed, see document number 00806-0100-4810.
Custom alarm and saturation signal levels, low alarm
Note: A Configuration Data Sheet must be completed, see document number 00806-0100-4810.
Low alarm (standard Rosemount alarm and saturation signal levels)
Hardware Adjustment (zero, span, alarm, security).
Hardware adjustment (zero, span, alarm, security) and external ground screw
M12, 4-pin, Male Connector (eurofast®) A size Mini, 4-pin, Male Connector (minifast®)
19
Rosemount Compact Orifice
Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series
March 2008
Rosemount 3095MFC Compact Orifice Mass Flowmeter
SPECIFICATIONS
Performance
System Reference Accuracy
Percent (%) of mass flow rate
TABLE 11. 3095MFC Compact Orifice Mass Flowmeter
Mass flow
TYPE BETA
3095MFCC 0.4 ±0.90% ±0.70%
3095MFCP
3095MFCP
3095MFCP
(1) Line sizes 1/2-in. (15mm)
(2) Line sizes 1-in. to 1 1/2-in. (25 mm to 40 mm)
(3) Line sizes 2-in. to 12-in. (50 mm to 300 mm)
(4) For 0.65 beta and ReD< 10,000 add an additional ±0.5% to the
(1)
(2)
(3)
Discharge Coefficient Uncertainty.
0.65 ±1.30% ±1.15%
0.4
(4)
0.65
0.4
(4)
0.65
0.4
(4)
0.65
(8:1 flow
turndown)
±2.50% ±2.45%
±2.10% ±2.00%
±1.50% ±1.40%
Repeatability
±0.1%
Line Sizes
•1/2-in. (15 mm) – not available for the 3095MFCC
• 1-in. (25 mm) – not available for the 3095MFCC
1
/2-in. (40 mm) – not available for the 3095MFCC
•1
• 2-in. (50 mm)
• 3-in. (80 mm)
• 4-in. (100 mm)
• 5-in (125 mm)
• 6-in. (150 mm)
• 8-in. (200 mm)
• 10-in. (250 mm)
• 12-in (300 mm)
Output
Two-wire 4–20 mA, user-selectable for DP, AP, GP, PT, mass flow, or totalized flow. Digital HART protocol superimposed on 4–20 mA signal, available to any host that conforms to the HART protocol.
Performance Statement Assumptions
• Measured pipe I.D
• Electronics are trimmed for optimum flow accuracy
Ultra for Flow
(10:1 flow turndown)
Functional
Service
• Liquid
•Gas
•Steam
Power Supply
4–20 mA option
• External power supply required. Standard transmitter (4–20 mA) operates on 11 to 55 v dc with no load
Process Temperature Limits
Direct Mount Transmitter
• 450 °F (232 °C)
Remote Mount Transmitter
• 850 °F (454 °C) – Stainless Steel
Transmitter Temperature Limits
Ambient
• -40 to 185 °F (-40 to 85 °C)
• with integral display: -4 to 175 °F (-20 to 80 °C)
Storage
• -50 to 230 °F (-46 to 110 °C)
• with integral display: -40 to 185 °F (-40 to 85 °C)
Differential Pressure Limits
Maximum differential pressure (DP) up to 800 inH2O.
Pressure Limits
Direct Mount Transmitter
• Pressure retention per ANSI B16.5 600# or DIN PN 100
Overpressure Limits
0 to 2 times the absolute pressure range with a maximum of 3626 psia (250 bar).
Static Pressure Limits
Operates within specification between static pressures of 0.5 psia (0.03 bar-A) and the URL of the static pressure sensor.
Vibration Limits
Qualified per IEC61298-3 (1998) for field with high vibration level or pipeline with high vibration level (10-60Hz 0.21mm displacement peak amplitude / 60 - 500Hz 3g).
The weight and length of the transmitter assembly shall not exceed 5.8 lbs and 7.75-in.
(1)
Sizing
Contact an Emerson Process Management representative for assistance. A Configuration Data Sheet is required prior to order for application verification.
20
(1) Static pressure selection may effect pressure limitations.
Product Data Sheet
Load (Ohms)
0
11.0 42.4
(1)
55
Operating
Region
(1) For CSA approval, power supply must not exceed 42.4 V dc.
(2) HART protocol communication requires a loop resistance value
between 250-1100 ohms, inclusive.
Power Supply
250
16.5
(2)
Maximum Loop Resistance = Power Supply - 11.0
0.022
2000
00813-0100-4810, Rev HA March 2008
Rosemount Compact Orifice
Flowmeter Series
Load Limitations
Maximum loop resistance is determined by the voltage level of the external power supply, as described by:
FOUNDATION fieldbus (output option code V)
Power Supply
External power supply required; transmitters operate on 9.0 to
32.0 V dc transmitter terminal voltage.
Current Draw
17.5 mA for all configurations (including LCD display option)
Humidity Limits
• 0–100% relative humidity
Turn-On Time
Digital and analog measured variables will be within specification 7 – 10 seconds after power is applied to the transmitter.
Digital and analog flow output will be within specifications 10 – 14 seconds after power is applied to the transmitter.
Damping
Analog output response to a step input change is user-selectable from 0 to 29 seconds for one time constant. This software damping is in addition to sensor module response time
Failure Mode Alarm
Output Code A
If self-diagnostics detect a non-recoverable transmitter failure, the analog signal will be driven either below 3.75 mA or above
21.75 mA to alert the user. High or low alarm signal is user-selectable by internal jumper pins.
Output Code V
If self-diagnostics detect a gross transmitter failure, that information gets passed as a status along with the process variable(s).
Configuration
HART Hand-held Communicator (Model 275 or 375)
• Performs traditional transmitter maintenance functions
3095 Multivariable Engineering Assistant (EA) software package
• Contains built-in physical property database
• Enables mass flow configuration, maintenance, and diagnostic functions via HART modem (output option code A)
Enables mass flow configuration via PCMCIA Interface for F
OUNDATION fieldbus (output option code V)
Physical Properties Database
• Maintained in Engineering Assistant Software Configurator
• Physical properties for over 110 fluids
• Natural gas per AGA
• Steam and water per ASME
• Other database fluids per American Institute of Chemical Engineers (AIChE)
• Optional custom entry
FOUNDATION fieldbus Function Blocks
Standard Function Blocks
Resource Block
• Contains hardware, electronics, and diagnostic information.
Transducer Block
• Contains actual sensor measurement data including the sensor diagnostics and the ability to trim the pressure sensor or recall factory defaults.
LCD Block
• Configures the local display.
5 Analog Input Blocks
• Processes the measurements for input into other function
blocks. The output value is in engineering or custom units and contains a status indicating measurement quality.
PID Block with Auto-tune
• Contains all logic to perform PID control in the field including
cascade and feedforward. Auto-tune capability allows for superior tuning for optimized control performance.
Advanced Control Function Block Suite (Option Code A01)
Input Selector Block
• Selects between inputs and generates an output using specific selection strategies such as minimum, maximum, midpoint, average, or first “good.”
Arithmetic Block
• Provides pre-defined application-based equations including flow with partial density compensation, electronic remote seals, hydrostatic tank gauging, ratio control and others.
Signal Characterizer Block
• Characterizes or approximates any function that defines an input/output relationship by configuring up to twenty X, Y coordinates. The block interpolates an output value for a given input value using the curve defined by the configured coordinates.
Integrator Bock
• Compares the integrated or accumulated value from one or two variables to pre-trip and trip limits and generates discrete output signals when the limits are reached. This block is useful for calculating total flow, total mass, or volume over time.
Output Splitter Block
• Splits the output of one PID or other control block so that the PID will control two valves or other actuators.
Control Selector Block
• Selects one of up to three inputs (highest, middle, or lowest) that are normally connected to the outputs of PID or other control function blocks.
21
Rosemount Compact Orifice Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Physical
Temperature Measurement
Remote RTD
• 100 Ohm platinum with series with Rosemount 644 housing) Model 0078D21N00A025T32Ex Connection Head: 00644-4410-0011
• Standard RTD cable is shielded armored cable, length is 12 feet (3.66 m)
• Remote RTD material is SST
Thermowell
1
/2-in. x 1/2-in. NPT, 316 SST
NOTE
Remote temperature measurement is not available for and 11/2-in. sizes.
Electronic Connections for Remote Mount
•1/2–14 NPT, G1/2, and M20 × 1.5 (CM20) conduit. HART interface connections fixed to terminal block for output code A
Process-Wetted Parts
Integral Manifolds
•316 SST
• Hastelloy C-276
Remote Manifolds
•316 SST
• Hastelloy C-276
Transmitter Vent Valves and Process Flanges
•316 SST
• Hastelloy C-276
• Glass-filled PTFE O-rings
Process Isolating Diaphragms
•316L SST
• Hastelloy C-276
Integral Manifold O-Rings
• PTFE/Graphite
Non-Wetted Parts
Sensor Module Fill Fluid
• Silicone oil
• Inert Fill optional
Cover O-rings
• Buna-N
Remote Mounting Brackets
•SST
Electronic Housing
• Low copper aluminum, NEMA 4x, IP65
• SST (optional)
Paint
• Polyurethane
Bolts
•CS
(1)
1
/2-in. NPT nipple and union (078
1
/2-in., 1-in.,
Material of Construction
Body/Plate
•316 SST
• 50 micro-inch Ra surface finish
Manifold Head/Valves
•316 SST
Flange Studs and Nuts
• Customer supplied
• Available as a spare part
Transmitter Connection Studs and Nuts
• Studs– A193 Grade B8M.
• Nuts– A194 Grade 8M.
Gasket and O-rings
• Gaskets are customer supplied.
• Durlon 8500 fiber gaskets are recommended. Consult an Emerson Process Management representative for use with other gaskets.
• Available as a spare part
NOTE
Gaskets and O-rings should be replaced when the 405 is disassembled.
Transmitter Connections
Remote Mount
• Available with connections
Orifice Type
• Square edged, Wafer style
Orifice Pressure Taps
• Corner
1
/4-in. (standard) or 1/2-in. (option code E)
Process Connections
Mounts between the following flange configurations
ASME B16.5 (ANSI)
Class 150
Class 300
Class 600
ANSI alignment ring is included as standard when ordering
DIN JIS
PN16 (option code G)
PN40 (option code H)
PN100 (option code H)
10k (option code B)
20k (option code R)
40k (option code S)
22
(1)
Product Data Sheet
00813-0100-4810, Rev HA March 2008
Rosemount Compact Orifice
Flowmeter Series
Typical Orifice Hole Sizes (For 3095MFCC)
Beta is calculated by: (β) = dC / Pipe ID, where the calculated bore is equal to 2 x typical orifice hole size (d shows the diameter of each of the four typical orifice holes.
TABLE 12. β = 0.4
(1)(2)
Line Size 3051SFCC 3051SFCP
1
/2-in. (15 mm) Not Available 0.249 (6.325)
1-in. (25 mm) Not Available 0.420 (10.668)
1
/2-in. (40 mm) Not Available 0.644 (16.358)
1 2-in. (50 mm) 0.413 (10.490) 0.827 (21.006) 3-in. (80 mm) 0.614 (15.596) 1.227 (31.166) 4-in. (100 mm) 0.805 (20.447) 1.610 (40.894) 5-in. (125 mm) 1.009 (25.629) 2.019 (51.283) 6-in. (150 mm) 1.213 (30.810) 2.426 (61.620) 8-in. (200 mm) 1.596 (40.538) 3.192 (81.077) 10-in. (250 mm) 2.004 (50.902) 4.008 (101.80) 12-in. (300 mm) 2.400 (60.960) 4.800 (121.92)
TABLE 13. β = 0.65
(1)(2)
Line Size 3051SFCC 3051SFCP
1
/2-in. (15 mm) Not Available 0.404 (10.262)
1-in. (25 mm) Not Available 0.682 (17.323)
1
/2-in. (40 mm) Not Available 1.047 (26.594)
1 2-in. (50 mm) 0.620 (15.748) 3-in. (80 mm) 0.997 (25.324) 1.994 (50.648) 4-in. (100 mm) 1.308 (33.223) 2.617 (66.472) 5-in. (125 mm) 1.640 (40.640) 3.281 (83.34) 6-in. (150 mm) 1.971 (50.063) 3.942 (100.127) 8-in. (200 mm) 2.594 (65.888) 5.188 (131.775) 10-in. (250 mm) 3.257 (82.728) 6.513 (165.43) 12-in. (300 mm) 3.900 (99.060) 7.800 (198.120)
(1) Measurement is in inches (millimeters)
(2) Tolerance = ±0.002-in.
(3) Beta (β) = 0.60-in. (15.24 mm) for 2-in. line size only.
= 2d). The table below
C
(3)
1.344 (34.138)
3051SFC Weight
Line Size Direct Mount (D3)
1
/2-in. (15 mm) 10.7 (4.58) 7.5 (3.70)
1-in. (25 mm) 11.45 (5. 19) 8.25 (4.07)
1
/2-in. (40 mm) 11.95 (5.42) 8.75 (4.32)
1 2-in. (50 mm) 12.20 (5.53) 9.00 (4.44) 3-in. (80 mm) 14.20 (6.44) 11.00 (5.43) 4-in. (100 mm) 16.70 (7.57) 13.50 (6.67) 5-in. (125 mm) 18.45 (8.37) 15.25 (7.53) 6-in. (150 mm) 20.20 (9.16) 17.00 (8.40) 8-in. (200 mm) 25.45 (11.54) 22.25 (10.99) 10-in (250 mm) 30.70 (13.92) 27.50 (13.58) 12-in (300 mm) 36.70 (16.64) 33.50 (16.54)
(1) Measurement in lb (kg).
(2) Includes 3051S Coplanar PlantWeb housing transmitter.
(1)(2)
Remote Mount (R3)
3095MFC Weight
Line Size Direct Mount (D3)
1
/2-in. (15 mm) 9.50 (4.69) 6.3 (3.11)
1-in. (25 mm) 10.25 (5.06) 7.05 (3.48)
1
/2-in. (40 mm) 10.75 (5.31) 7.55 (3.73)
1 2-in. (50 mm) 11.00 (5.43) 7.80 (3.85) 3-in. (80 mm) 13.00 (6.42) 9.80 (4.84) 4-in. (100 mm) 15.50 (7.65) 12.30 (6.07) 5-in. (125 mm) 17.25 (8.52) 14.05 (6.94) 6-in. (150 mm) 19.00 (9.38) 15.80 (7.80) 8-in. (200 mm) 24.25 (11.98) 21.05 (10.40) 10-in (250 mm) 29.50 (14.57) 26.30 (12.9) 12-in (300 mm) 35.50 (17.53) 32.30 (15.95)
(1) Measurement in lb (kg).
(2) Includes 3095 MultiVariable transmitter.
(1)(2)
Remote Mount (R3)
405 Weight
Line Size Direct Mount (D3)
1
/2-in. (15 mm) 3.50 (1.73) 7.5 (3.70)
1-in. (25 mm) 4.25 (2.10) 8.25 (4.07)
1
/2-in. (40 mm) 4.75 (2.34) 8.75 (4.32)
1 2-in. (50 mm) 5.00 (2.47) 9.00 (4.44) 3-in. (80 mm) 7.00 (3.45) 11.00 (5.43) 4-in. (100 mm) 9.50 (4.69) 13.50 (6.67) 5-in. (125 mm) 11.25 (5.55) 15.25 (7.53) 6-in. (150 mm) 13.00 (6.41) 17.00 (8.40) 8-in. (200 mm) 18.25 (9.00) 22.25 (10.99) 10-in (250 mm) 23.50 (11.59) 27.50 (13.58) 12-in (300 mm) 29.50 (14.55) 33.50 (16.54)
(1) Measurement in lb (kg).
(2) Includes 405 Direct Mount option D3.
(1)(2)
Remote Mount (R3)
(1)
(1)
(1)
23
Rosemount Compact Orifice
Upstream (inlet)
side of primary
3095MFCDP
Compact Orifice
3095MFCDC
Conditioning Orifice
Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Installation Considerations
Straight Run Requirements
TABLE 14. 3095MFCC Straight Pipe Requirements
Beta 0.40 0.65
Reducer (1 line size) 2 2 Single 90° bend or tee 2 2 Two or more 90 ° bends in the same
plane Two or more 90° bends in different
plane
side of primary
Up to 10° of swirl 2 2
Upstream (inlet)
Butterfly valve (75% to 100% open) 2 N/A
Downstream (outlet) side of primary
TABLE 15. 3095MFCP Straight Pipe Requirements
Beta 0.40 0.65
(2)(3)
Downstream (outlet) side of primary
(1) Consult an Emerson Process Management representative if
(2) Recommended lengths represented in pipe diameters per ISO
(3) Refer to ISO 5167 for recommended lengths when using flow
Reducer 5 12 Single 90° bend or tee 16 44 Two or more 90 ° bends
in the same plane Two or more 90° bends in different
plane Expander 12 28 Ball / Gate valve fully open 12 18
disturbance is not listed.
5167.
straighteners.
(1)
2 2
2 2
22
(1)(2)(3)
10 44
50 60
6 7
Pipe Centering
Improper centering of any orifice type device can cause an error of up to ±5% in small line sizes. A centering mechanism (centering ring) independent of flange rating comes standard with the 405 Compact Orifice Series.
Pipe Orientation
Pipe orientation for both 3095MFCC Compact Conditioning Mass Orifice and standard 3095MFCP Compact Mass Orifice.
Horizontal D/R D/R D/R Vertical Up R D/R R Vertical Down D/R NR NR
24
Orientation/ Flow Direction
(1) D = Direct mount acceptable (recommended)
R = Remote mount acceptable NR = Not recommended
Gas Liquid Steam
Process
(1)
Product Data Sheet
30°
120°
30°
360°
FLOW
360°
FLOW
00813-0100-4810, Rev HA March 2008
Flowmeter Orientation
Flowmeter orientation for both 3095MFC Conditioning Compact Orifice and standard Compact Orifice.
Gas (Horizontal)
Liquid and Steam (Horizontal)
Rosemount Compact Orifice
Flowmeter Series
50°
50°
80°
Gas (Vertical)
Liquid (Vertical)
25
Rosemount Compact Orifice Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
PRODUCT CERTIFICATIONS
Rosemount 3095 with HART
European Directive Information
The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting our local sales office.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX Directive.
European Pressure Equipment Directive (PED) (97/23/EC)
3095M_2/3,4/D Flow Transmitters — QS Certificate of Assessment - EC No. PED-H-20 Module H Conformity Assessment
All other 3095_ Transmitters/Level Controller — Sound Engineering Practice
Transmitter Attachments: Process Flange - Manifold — Sound Engineering Practice
Electro Magnetic Compatibility (EMC) (89/336/EEC)
3095MV Flow Transmitters
— EN 50081-1: 1992; EN 50082-2:1995;
EN 61326-1:1997 – Industrial
Ordinary Location Certification for Factory Mutual
As standard, the transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
Hazardous Locations Certifications
North American Certifications
FM Approvals
E5 Explosion Proof for Class I, Division 1, Groups B, C, and D.
Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F, and G. Enclosure type NEMA 4X. Factory Sealed. Provides nonincendive RTD connections for Class I, Division 2, Groups A, B, C, and D.
I5 Intrinsically Safe for use in Class I, II and III, Division 1,
Groups A, B, C, D, E, F, and G hazardous outdoor locations. Non-incendive for Class I, Division 2, Gro ups A, B, C, and D. Temperature Code T4. Factory Sealed.
For input parameters and installation see control drawing 03095-1020.
Canadian Standards Association (CSA)
E6 Explosion Proof for Class I, Division 1, Groups B, C, and D.
Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F, and G. CSA enclosure Type 4X suitable for indoor and outdoor hazardous locations. Provides nonincendive RTD connection for Class I, Division 2, Groups A, B, C, and D.Factory Sealed. Install in accordance with Rosemount Drawing 03095-1024. Approved for Class I, Division 2, Groups A, B, C, and D.
I6 Intrinsically Safe for Class I, Division 1, Groups A, B, C, and
D. when installed in accordance with Rosemount drawing 03095-1021. Temperature Code T3C.
For input parameters and installation see control drawing 03095-1021.
European Certifications
I1 ATEX Intrinsic Safety
Certificate Number: BAS98ATEX1359X II 1 G
EEx ia IIC T5 (T EEx ia IIC T4 (T
118 0
TABLE 16. Connection Parameters (Power/Signal Te rm i na l s)
= 30V
U
i
Ii = 200 mA
= 1.0 W
P
i
Ci = 0.012 µF
= 0
L
i
TABLE 17. Temperature Sensor Connection Parameters
= 30V
U
o
Io = 19 mA
= 140 mW
P
o
Ci = 0.002 µF
= 0
L
i
TABLE 18. Temp Sensor Terminals Connection Parameters
C
= 0.066 F Gas Group IIC
o
Co = 0.560 ␮F Gas Group IIB
= 1.82 F Gas Group IIA
C
o
Lo = 96 mH Gas Group IIC
= 365 mH Gas Group IIB
L
o
Lo = 696 mH Gas Group IIA
= 247 H/ohm Gas Group IIC
L
o/Ro
Lo/Ro = 633 ␮H/ohm Gas Group IIB
= 633 H/ohm Gas Group IIA
L
o/Ro
Special Conditions for Safe Use
The 3095, when fitted with the transient terminal block (order code B), are not capable of withstanding the 500 volts insulation test required by EN50 020, Clause 6.4.12 (1994). This condition must be accounted for during installation.
N1 ATEX Type N
Certificate Number: BAS98ATEX3360X II 3 G
EEx nL IIC T5 (T EEx nL IIC T4 (T
= 55V
U
i
= –45 °C to 40 °C)
amb
= –45 °C to 70 °C)
amb
= –45 °C to 40 °C)
amb
= –45 °C to 70 °C)
amb
26
The apparatus is designed for connection to a remote temperature sensor such as a resistance temperature detection (RTD)
Product Data Sheet
00813-0100-4810, Rev HA March 2008
Rosemount Compact Orifice
Flowmeter Series
Special Conditions for Safe Use
The 3095, when fitted with the transient terminal block (order code B), are not capable of withstanding the 500 volts insulation test required by EN50 021, Clause 9.1 (1995). This condition must be accounted for during installation.
E1 ATEX Flameproof
Certificate Number: KEMA02ATEX2320X II 1/2 G EEx d IIC T5 (-50°C ≤ T
T6 (-50°C ≤ T
118 0
Special Conditions for Safe Use (x):
The device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
ND ATEX Dust
Certificate Number: KEMA02ATEX2321 II 1 D V = 55 Vdc MAX I = 23 mA MAX IP66
118 0
amb
amb
80°C) 65°C)
Combinations of Certifications
Stainless steel certification tag is provided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinstalled using any other approval types. Permanently mark the approval label to distinguish it from unused approval types.
K5 E5 and I5 combination
K6 E6 and I6 combination
K1 I1, N1, E1, and ND combination
Electro Magnetic Compatibility (EMC) (89/336/EEC)
3095 Flow Transmitters
— EN 50081-1: 1992; EN 50082-2:1995; EN 61326-1:1997 – Industrial
Ordinary Location Certification for Factory Mutual
As standard, the transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
Rosemount 3095 Fieldbus Hazardous Locations Certifications
North American Certifications
FM Approvals
E5 Explosion Proof for Class I, Division 1, Groups B, C, and D.
Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F, and G. Enclosure type NEMA 4X. Factory Sealed. Provides nonincendive RTD connections for Class I, Division 2, Groups A, B, C, and D.
I5 Intrinsically Safe for use in Class I, II and III, Division 1,
Groups A, B, C, D, E, F, and G hazardous outdoor locations. Non-incendive for Class I, Division 2, Groups A, B, C, and D. Temperature Code T4. Factory Sealed.
For input parameters and installation see control drawing 03095-1020.
IE FISCO for use in Class I, II and III, Division 1, Groups A, B,
C, D, E, F, and G hazardous outdoor locations. Temperature Code T4. Factory Sealed.
Rosemount 3095 with Fieldbus
European Directive Information
The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting our local sales office.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX Directive.
European Pressure Equipment Directive (PED) (97/23/EC)
3095F_2/3,4/D and 3095M_2/3,4/D Flow Transmitters
— QS Certificate of Assessment - EC No. PED-H-20 Module H Conformity Assessment
All other 3095_ Transmitters/Level Controller
— Sound Engineering Practice
Transmitter Attachments: Process Flange - Manifold
— Sound Engineering Practice
Primary Elements, Flowmeter
— See appropriate Primary Element QIG
For input parameters and installation see control drawing 03095-1020.
Combinations of Certifications
Stainless steel certification tag is provided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinstalled using any other approval types. Permanently mark the approval label to distinguish it from unused approval types.
K5 E5 and I5 combination
Canadian Standards Association (CSA)
IF CSA FISCO Intrinsically Safe; for FOUNDATION fieldbus
protocol only
European Certifications
IA ATEX FISCO Intrinsically Safe; for FOUNDATION fieldbus
protocol only
Australian Certifications
IG IECEx FISCO Intrinsic Safety
27
Rosemount Compact Orifice
A
B
D
1.13 (28.7)
1.00 (25.4
A
B
D
1.13 (28.7)
1.00 (25.4
Flowmeter Series
DIMENSIONAL DRAWINGS
Rosemount 3095MFC Compact Orifice Mass Flowmeter
Orifice Plate Front View Orifice Plate Side View Orifice Plate Top View
Compact Orifice Plate
(Primary Element Type code P)
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
C
(Primary Element Type code C)
Conditioning Orifice Plate
TABLE 19. Dimensional Drawings
Plate Type A B Transmitter Height C D
Type P & C 5.50 (140) Transmitter Height + A 6.25 (159) 7.75 (197) - closed
(1) Measurement is in inches (millimeters).
(1)
8.25 (210) - open
C
6.0 (152) - closed
6.25 (159) - open
28
Product Data Sheet
Rosemount Compact Orifice
00813-0100-4810, Rev HA March 2008
ORDERING INFORMATION
Rosemount 3095MFC Compact Orifice Mass Flowmeter Ordering Information
Model Product Description
3095MFC Compact Orifice Mass Flowmeter
Code Primary Element Type
C Conditioning Orifice Plate P Orifice Plate
Code Material Type
S 316 Stainless Steel (SST)
(1)
H
Code Line Size
(2) 1
005
(2)
010
(2)
015 020 2-in. (50 mm) 030 3-in. (80 mm) 040 4-in. (100 mm)
(1)
050 060 6-in. (150 mm) 080 8-in. (200 mm)
(1)
100
(1)
120
Code Primary Element Style
N Square Edged
Code Beta Ratio
040 0.40 Beta Ratio (β)
(3)
065
Code Temperature Measurement
R Remote Thermowell and RTD
(1)
T 0 No Temperature Sensor
Code Transmitter Connection Platform
3 Direct-mount, 3-valve integral manifold, SST 7 Remote-mount, 1/4-in. NPT connections
Code Differential Pressure Range
1 0 to 25 in H2O (0 to 62.2 mbar) 2 0 to 250 in H2O (0 to 623 mbar) 3 0 to 1000 in H2O (0 to 2.5 bar)
Code Static Pressure Range
B 0 – 8 to 0 – 800 psia (0 –55.16 to 0 – 5515.8 kPa) C 0 – 8 to 0 – 800 psig (0 –55.16 to 0 – 5515.8 kPa) D 0 – 36.2 to 0 – 3626 psia (0 –250 to 0 – 25000 kPa) E 0 – 36.2 to 0 – 3626 psig (0 –250 to 0 – 25000 kPa)
Code Output Protocol
A 4–20 mA with digital signal based on HART protocol V FOUNDATION fieldbus protocol
Code Transmitter Housing Style Conduit Entry Size
1A Polyurethane-covered aluminum 1B Polyurethane-covered aluminum M20 x 1.5 (CM20) 1C Polyurethane-covered aluminum PG 13.5 1J SST 1K SST M20 x 1.5 (CM20) 1L SST PG 13.5
Hastelloy
/2-in. (15 mm) 1-in. (25 mm) 11/2-in. (40 mm)
5-in. (125 mm)
10-in (250 mm) 12-in. (300 mm)
0.65 Beta Ratio (β)
Integral RTD and Thermowell
1
/2-14 NPT
1
/2-14 NPT
Flowmeter Series
29
Rosemount Compact Orifice Flowmeter Series
Rosemount 3095MFC Compact Orifice Mass Flowmeter Ordering Information
Code Options
Performance Class
(4)
U3
PlantWeb Control Functionality
(5)
A01
Installation Accessories
G DIN Alignment Ring (PN 16) H DIN Alignment Ring (PN 40, PN 100) B JIS Alignment Ring 10K R JIS Alignment Ring 20K S JIS Alignment Ring 40K
Remote Adapters
E Flange adapters 316 SST (
High Temperature Applications
T Graphite valve packing (Tmax = 850 °F)
Flow Calibration
(6)
WC
(6)
WD
Pressure Testing
P1 Hydrostatic Testing with certificate
Special Cleaning
P2 Cleaning for special processes PA Cleaning per ASTM G93 Level D (section 11.4)
Special Inspection
QC1 Visual and dimensional inspection with certificate QC7 Inspection and performance certificate
Transmitter Calibration Certification
Q4 Calibration data certificate for transmitter
Material Traceability Certification
(7)
Q8
Code Conformance
J2 ANSI B31.1 J3 ANSI B31.3 J4 ANSI B31.8
Material Conformance
(8)(9)
J5
Country Certification
J1 Canadian Registration
Product Certifications
E1 ATEX Flameproof I1 ATEX Intrinsic Safety N1 ATEX Type n K1 ATEX Flameproof, Intrinsic Safety, Type n, Dust (combination of E1, I1, N1, and ND) ND ATEX Dust E5 FM Explosion-proof, Dust Ignition-proof I5 FM Intrinsically Safe, Division 2 K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5 and I5) E6 CSA Explosion-proof, Dust Ignition-proof, Division 2 I6 CSA Intrinsically Safe, Division 2 K6 CSA Explosion-proof, Intrinsically Safe, Division 2 (combination of E6 and I6)
(1)
IE
(1)
IF
(1)
IA
(1)
IG I7 IECEx Intrinsic Safety E4 TIIS Flameproof ID TIIS FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only
Ultra for Flow: up to ±0.70% mass flow rate accuracy, up to 10:1 turndown, 10-year stability, limited 12-year warranty
Advanced Control Function Block Suite
1
/2-in. NPT)
Discharge coefficient verification (3 point) Discharge coefficient verification (10 point)
Material certification per ISO 10474 3.1.B and EN 10204 3.1.B
NACE MR-0175 / ISO 15156
FM FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only CSA FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only ATEX FISCO Intrinsically Safe; for FOUNDATION fieldbus protocol only IECEx FISCO Intrinsic Safety
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
30
Product Data Sheet
Rosemount Compact Orifice
00813-0100-4810, Rev HA March 2008
Flowmeter Series
Rosemount 3095MFC Compact Orifice Mass Flowmeter Ordering Information
I3 China Intrinsic Safety E3 China Flameproof
Alternative Transmitter Material of Construction
(9)
L1
Display
M5 Integral mount LCD display
Terminal Blocks
T1 Transient Protection
Manifold for Remote Mount Option
F2 3-Valve Manifold, SST F6 5-Valve Manifold, SST
Typical Model Number: 3051MFC C S 040 N 040 0 3 B A 1A
(1) Consult factory for availability.
(2) Not available for Primary Element Type code C.
(3) For 2-in. (50.8 mm) line sizes the Beta Ratio is 0.6 for Primary Element Type code C.
(4) Ultra for Flow applicable for HART protocol, DP ranges 2 and 3 with SST isolator material and silicone fill fluid options only.
(5) Function Blocks include: Arithmetic, Integrator, Analog Output, Signal Characterizer, Control Selector, and Output Selector.
(6) Not available with Primary Element Type code P.
(7) Instrument valves not included in Traceability Certification.
(8) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO 15156 for sour oil field production environments. Environmental
(9) Not available with DP range 1.
Inert Sensor Fill Fluid
limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
31
Rosemount Compact Orifice Flowmeter Series
Rosemount 405 Compact Orifice Primary Element
SPECIFICATIONS
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Performance
Discharge Coefficient Uncertainty
TABLE 20. 405 Compact Orifice Primary Element
Discharge Coefficient
Typ e Beta
405C (Conditioning Compact)
(1)(2)
405P (Standard Compact)
405P (Standard Compact)
(1) Line sizes 1/2 to 11/2-in. (12.7 to 38.1 mm).
(2) Discharge Coefficient Uncertainty for
(3) Line sizes 2 to 12-in. (50 mm to 300 mm)
(3)
is ±2.25%.
0.4 ±0.50%
0.65 ±1.00%
0.4 ±1.75%
0.65 ±1.75%
0.4 ±1.25%
0.65 ±1.25%
1
Uncertainty
/2-in. units with Beta = 0.65
Line Sizes
•1/2-in. (15 mm) – not available for the 405C
• 1-in. (25 mm) – not available for the 405C
1
/2-in. (40 mm) – not available for the 405C
•1
• 2-in. (50 mm)
• 3-in. (80 mm)
• 4-in. (100 mm)
• 5-in (125 mm)
• 6-in. (150 mm)
• 8-in. (200 mm)
• 10-in. (250 mm)
• 12-in (300 mm)
Sizing
Contact an Emerson Process Management sales representative assistance. A “Configuration Data Sheet” is required prior to order for application verification.
Functional
Vibration Limits
Qualified per IEC61298-3 (1998) for field with high vibration level or pipeline with high vibration level (10-60Hz 0.21mm displacement peak amplitude / 60 - 500Hz 3g).
The weight and length of the transmitter assembly shall not exceed 5.8 lbs and 7.75-in.
Assembly to a transmitter
Select option code C11 for the Rosemount 3051S transmitter (or option code S3 for the Rosemount 3051C or 3095MV transmitters) to factory assemble the Rosemount 405 to a Rosemount pressure transmitter. If the 405 and transmitter are not factory assembled, they may be shipped separately. For a consolidated shipment, inform the Emerson Process Management representative when placing the order.
Physical
Material of Construction
Body/Plate
•316 SST
• 50 micro-inch Ra surface finish
Manifold Head/Valves
•316 SST
Flange Studs and Nuts
• Customer supplied
• Available as a spare part
Transmitter Connection Studs and Nuts
• Studs– A193 Grade B8M.
• Nuts– A194 Grade 8M.
Gasket and O-rings
• Gaskets are customer supplied.
• Durlon 8500 fiber gaskets are recommended. Consult an Emerson Process Management representative for use with other gaskets.
• Available as a spare part
Service
•Liquid
•Gas
• Vapor
Operating Process Temperature Limits
Standard (direct/remote mount):
• –40 to 450 °F (–40 to 232 °C)
Extended (remote mount only with option code T):
• –148 to 850 °F (–100 to 454 °C)
Differential Pressure Limits
Maximum differential pressure (DP) up to 800 inH2O.
Maximum Working Pressure
• Pressure retention per ANSI B16.5 600# or DIN PN100
32
NOTE
Gaskets and O-rings should be replaced when the 405 is disassembled.
Transmitter Connections
Direct Mount
• Integrally mount to 3051 and 3095 transmitters, range 1, 2, and 3.
Remote Mount
• Available with connections
Orifice Type
• Square edged, Wafer style
Orifice Pressure Taps
• Corner
1
/4-in. (standard) or 1/2-in. (option code E)
Product Data Sheet
00813-0100-4810, Rev HA March 2008
Rosemount Compact Orifice
Flowmeter Series
Process Connections
Mounts between the following flange configurations:
ASME B16.5 (ANSI)
Class 150
Class 300
Class 600
DIN JIS
PN16 (option code G)
PN40 (option code H)
PN100 (option code H)
10k (option code B)
20k (option code R)
40k (option code S)
ANSI alignment ring is included as standard when ordering.
Typical Orifice Hole Sizes (For 405C)
Beta is calculated by: (β) = dC / Pipe ID, where the calculated bore is equal to 2 x typical orifice hole size (d shows the diameter of each of the four typical orifice holes.
TABLE 21. β = 0.4
(1)(2)
Line Size 3051SFCC 3051SFCP
1
/2-in. (15 mm) Not Available 0.249 (6.325)
1-in. (25 mm) Not Available 0.420 (10.668)
1
/2-in. (40 mm) Not Available 0.644 (16.358)
1 2-in. (50 mm) 0.413 (10.490) 0.827 (21.006) 3-in. (80 mm) 0.614 (15.596) 1.227 (31.166) 4-in. (100 mm) 0.805 (20.447) 1.610 (40.894) 5-in. (125 mm) 1.009 (25.629) 2.019 (51.283) 6-in. (150 mm) 1.213 (30.810) 2.426 (61.620) 8-in. (200 mm) 1.596 (40.538) 3.192 (81.077) 10-in. (250 mm) 2.004 (50.902) 4.008 (101.80) 12-in. (300 mm) 2.400 (60.960) 4.800 (121.92)
TABLE 22. β = 0.65
(1)(2)
Line Size 3051SFCC 3051SFCP
1
/2-in. (15 mm) Not Available 0.404 (10.262)
1-in. (25 mm) Not Available 0.682 (17.323)
1
/2-in. (40 mm) Not Available 1.047 (26.594)
1 2-in. (50 mm) 0.620 (15.748) 3-in. (80 mm) 0.997 (25.324) 1.994 (50.648) 4-in. (100 mm) 1.308 (33.223) 2.617 (66.472) 5-in. (125 mm) 1.640 (40.640) 3.281 (83.34) 6-in. (150 mm) 1.971 (50.063) 3.942 (100.127) 8-in. (200 mm) 2.594 (65.888) 5.188 (131.775) 10-in. (250 mm) 3.257 (82.728) 6.513 (165.43) 12-in. (300 mm) 3.900 (99.060) 7.800 (198.120)
(1) Measurement is in inches (millimeters)
(2) Tolerance = ±0.002-in.
(3) Beta (β) = 0.60-in. (15.24 mm) for 2-in. line size only.
= 2d). The table below
C
(3)
1.344 (34.138)
3051SFC Weight
Line Size Direct Mount (D3)
1
/2-in. (15 mm) 10.7 (4.58) 7.5 (3.70)
1-in. (25 mm) 11.45 (5. 19) 8.25 (4.07)
1
/2-in. (40 mm) 11.95 (5.42) 8.75 (4.32)
1 2-in. (50 mm) 12.20 (5.53) 9.00 (4.44) 3-in. (80 mm) 14.20 (6.44) 11.00 (5.43) 4-in. (100 mm) 16.70 (7.57) 13.50 (6.67) 5-in. (125 mm) 18.45 (8.37) 15.25 (7.53) 6-in. (150 mm) 20.20 (9.16) 17.00 (8.40) 8-in. (200 mm) 25.45 (11.54) 22.25 (10.99) 10-in (250 mm) 30.70 (13.92) 27.50 (13.58) 12-in (300 mm) 36.70 (16.64) 33.50 (16.54)
(1) Measurement in lb (kg).
(2) Includes 3051S Coplanar PlantWeb housing transmitter.
(1)(2)
Remote Mount (R3)
3095MFC Weight
Line Size Direct Mount (D3)
1
/2-in. (15 mm) 9.50 (4.69) 6.3 (3.11)
1-in. (25 mm) 10.25 (5.06) 7.05 (3.48)
1
/2-in. (40 mm) 10.75 (5.31) 7.55 (3.73)
1 2-in. (50 mm) 11.00 (5.43) 7.80 (3.85) 3-in. (80 mm) 13.00 (6.42) 9.80 (4.84) 4-in. (100 mm) 15.50 (7.65) 12.30 (6.07) 5-in. (125 mm) 17.25 (8.52) 14.05 (6.94) 6-in. (150 mm) 19.00 (9.38) 15.80 (7.80) 8-in. (200 mm) 24.25 (11.98) 21.05 (10.40) 10-in (250 mm) 29.50 (14.57) 26.30 (12.9) 12-in (300 mm) 35.50 (17.53) 32.30 (15.95)
(1) Measurement in lb (kg).
(2) Includes 3095 MultiVariable transmitter.
(1)(2)
Remote Mount (R3)
405 Weight
Line Size Direct Mount (D3)
1
/2-in. (15 mm) 3.50 (1.73) 7.5 (3.70)
1-in. (25 mm) 4.25 (2.10) 8.25 (4.07)
1
/2-in. (40 mm) 4.75 (2.34) 8.75 (4.32)
1 2-in. (50 mm) 5.00 (2.47) 9.00 (4.44) 3-in. (80 mm) 7.00 (3.45) 11.00 (5.43) 4-in. (100 mm) 9.50 (4.69) 13.50 (6.67) 5-in. (125 mm) 11.25 (5.55) 15.25 (7.53) 6-in. (150 mm) 13.00 (6.41) 17.00 (8.40) 8-in. (200 mm) 18.25 (9.00) 22.25 (10.99) 10-in (250 mm) 23.50 (11.59) 27.50 (13.58) 12-in (300 mm) 29.50 (14.55) 33.50 (16.54)
(1) Measurement in lb (kg).
(2) Includes 405 Direct Mount option D3.
(1)(2)
Remote Mount (R3)
(1)
(1)
(1)
33
Rosemount Compact Orifice
Upstream (inlet)
side of primary
405C Conditioning
Orifice
405P Compact
Orifice
Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Installation Consideration
Straight Pipe Requirement
Use the appropriate lengths of straight pipe upstream and downstream of the 405 to minimize the effects of moderate flow disturbances in the pipe. Table 23 and Table 24 lists recommended lengths of straight pipe per ISO 5167.
TABLE 23. 405C Straight Pipe Requirements
Beta 0.40 0.65
Reducer (1 line size) 2 2 Single 90° bend or tee 2 2 Two or more 90 ° bends in the same
plane Two or more 90° bends in different
plane
side of primary
Up to 10° of swirl 2 2
Upstream (inlet)
Butterfly valve (75% to 100% open) 2 N/A
Downstream (outlet) side of primary
TABLE 24. 405P Straight Pipe Requirements
Beta 0.40 0.65
(2)(3)
Downstream (outlet) side of primary
(1) Consult an Emerson Process Management representative if
(2) Recommended lengths represented in pipe diameters per ISO
(3) Refer to ISO 5167 for recommended lengths when using flow
Reducer 5 12 Single 90° bend or tee 16 44 Two or more 90 ° bends
in the same plane Two or more 90° bends in different
plane Expander 12 28 Ball / Gate valve fully open 12 18
disturbance is not listed.
5167.
straighteners.
(1)
2 2
2 2
2 2
(1)(2)(3)
10 44
50 60
6 7
Pipe Orientation
Process
Orientation/ Flow Direction
Horizontal D/R D/R D/R Vertical Up R D/R R Vertical Down D/R NR NR
(1) D = Direct mount acceptable (recommended)
R = Remote mount acceptable NR = Not recommended
Gas Liquid Steam
(1)
Pipe Centering
Improper centering of any orifice type device can cause an error of up to ±5% in small line sizes. A centering mechanism (centering ring) independent of flange rating comes standard with the 405 Compact Orifice Series.
34
Product Data Sheet
30°
120°
30°
360°
FLOW
360°
FLOW
00813-0100-4810, Rev HA March 2008
Flowmeter Orientation
Flowmeter orientation for the Conditioning Compact Orifice and standard Compact Orifice.
Gas (Horizontal)
Liquid and Steam (Horizontal)
Rosemount Compact Orifice
Flowmeter Series
50°
50°
80°
Gas (Vertical)
Liquid (Vertical)
35
Rosemount Compact Orifice
VALVE
EQUALIZER
1/4"-in NPT
INSTRUMENT
INSTRUMENT
HIGH
VALVE
VALVE
LOW
ADAPTER
PLATE
.85 (21.6)
(54.1)
2.13
1.13 (28.7)
1.00 (25.4)
Flowmeter Series
DIMENSIONAL DRAWINGS
Rosemount 405 Compact Orifice Plate
(Remote Mount Transmitter)
Adapter Plate (R3) Flange Adapter (R3 with option E)
1/2"-in NPT
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
2.13
(54.1)
Compact Orifice Plate
(Primary Element Type code P)
1/4"-in NPT
HIGH
INSTRUMENT
VALVE
ADAPTER
PLATE
EQUALIZER
VALVE
2.13
(54.1)
.85 (21.6)
LOW INSTRUMENT VALVE
HIGH
INSTRUMENT
VALVE
ADAPTER
PLATE
EQUALIZER
VALVE
HIGH
INSTRUMENT
VALVE
ADAPTER
PLATE
EQUALIZER
1/2"-in NPT
VALVE
2.13
(54.1)
FLANGE ADAPTER
.85 (21.6)
1.13 (28.7)
1.00 (25.4)
LOW INSTRUMENT VALVE
FLANGE ADAPTER
LOW INSTRUMENT VALVE
.85 (21.6)
Conditioning Orifice Plate
36
(Primary Element Type code C)
1.13 (28.7)
1.00 (25.4)
1.13 (28.7)
1.00 (25.4)
Product Data Sheet
HIGH
EQUALIZER
VALVE
VALVE
INSTRUMENT
LOW INSTRUMENT VALVE
1.30
1.13 (28.7)
1.00 (25.4)
(33)
2.13
(54.1)
1.13 (28.7)
1.00 (25.4)
00813-0100-4810, Rev HA March 2008
Front View (transmitter connection A3) Front View (transmitter connection D3)
HIGH
INSTRUMENT
VALVE
ADAPTER
PLATE
EQUALIZER
VALVE
Rosemount Compact Orifice
Flowmeter Series
Rosemount 405 Compact Orifice Plate
(Direct Mount)
2.13
(54.1)
LOW INSTRUMENT VALVE
.70 (18)
Compact Orifice Plate
(Primary Element Type code P)
(Primary Element Type code C)
Conditioning Orifice Plate
1.13 (28.7)
1.00 (25.4)
HIGH
INSTRUMENT
VALVE
EQUALIZER
VALVE
1.30 (33)
2.13
(54.1)
LOW INSTRUMENT VALVE
1.13 (28.7)
1.00 (25.4)
NOTE
Transmitter connection code A3 is to be used with a traditional style transmitter (such as a Rosemount 1151). This is a stainless steel adapter plate for allowing the direct mount of traditional style transmitters.
37
Rosemount Compact Orifice Flowmeter Series
ORDERING INFORMATION
Rosemount 405 Compact Orifice Primary Element Ordering Information
Model Product Description
405 Compact Primary Element
Code Primary Element Type
C Conditioning Orifice Plate P Orifice Plate
Code Material Type
S 316 Stainless Steel (SST)
(1)
H
Code Line Size
(2) 1
005
(2)
010
(2)
015 020 2-in. (50 mm) 030 3-in. (80 mm) 040 4-in. (100 mm)
(1)
050 060 6-in. (150 mm) 080 8-in. (200 mm)
(1)
100
(1)
120
Code Temperature Measurement
R Remote Thermowell and RTD
(1)
T 0 No Temperature Sensor
Code Beta Ratio
040 0.40 Beta Ratio (β)
(3)
065
Code Transmitter Connection
D3 Coplanar, Direct mount, 3-valve integral manifold, SST R3 Remote-mount, 1/4-in. NPT connections A3 Traditional, Direct mount, 3-valve integral manifold with adapter plate, SST
Code Options
Installation Accessories
G DIN Alignment Ring (PN 16) H DIN Alignment Ring (PN 40, PN 100) B JIS Alignment Ring 10K R JIS Alignment Ring 20K S JIS Alignment Ring 40K
Adapters
E Flange adapters 316 SST (
High Temperature Applications
T Graphite valve packing (Tmax = 850 °F)
Flow Calibration
(4)
WC
(4)
WD
Pressure Testing
P1 Hydrostatic testing with certificate
Special Cleaning
P2 Cleaning for special processes PA Cleaning per ASTM G93 Level D (section 11.4)
Continued on Next Page
Hastelloy
/2-in. (15 mm) 1-in. (25 mm) 11/2-in. (40 mm)
5-in. (125 mm)
10-in. (250 mm) 12-in. (300 mm)
Integral RTD and Thermowell
0.65 Beta Ratio (β)
1
/2-in. NPT)
Discharge coefficient verification (3 point) Discharge coefficient verification (10 point)
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
38
Product Data Sheet
Rosemount Compact Orifice
00813-0100-4810, Rev HA March 2008
Flowmeter Series
Rosemount 405 Compact Orifice Primary Element Ordering Information
Special Inspection
QC1 Visual and Dimensional Inspection with certification QC7 Inspection and performance certification
Material Traceability Certification
(5)
Q8
Code Conformance
J2 ANSI B31.1 J3 ANSI B31.3 J4 ANSI B31.8
Material Conformance
(6)
J5
Country Certification
J1 Canadian Registration
Typical Model Number: 405 C S 040 N 040 D3
(1) Consult factory for availability.
(2) Not available for Primary Element Type code C.
(3) For 2-in. (50.8 mm) line sizes the Beta Ratio is 0.6 for Primary Element Type code C.
(4) Not available with Primary Element Type code P.
(5) Instrument valves not included in Traceability Certification.
(6) Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits
Material certification per ISO 10474 3.1.B and EN 10204 3.1.B
NACE MR-0175 / 15156
apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
39
Rosemount Compact Orifice
Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series
March 2008
HART Configuration Data Sheet (CDS)
DP FLOW CDS
Complete this form to define a custom flow configuration for DP Flowmeters. Unless specified, the flowmeter will be shipped with the default values identified by the H symbol.
For technical assistance in filling out this CDS, call a Rosemount representative.
NOTE
Any missing information will be processed with the indicated default values.
* = Required Item = Default
Customer Information
Customer: Contact Name:
Customer Phone: Customer Fax:
Customer Approval Sign-Off: Customer PO:
Calculation Approval
Check this box if a calculation for approval prior to manufacturing is required
Application and Configuration Data Sheet (Required with Order)
Ta g:
Model No
* Select fluid type Liquid Gas Steam
* Fluid name
Flowmeter Information (optional)
* Failure Mode Alarm Direction (select one)
Software Tag: ___ ___ ___ ___ ___ ___ ___ ___ (8 characters)
Descriptor: ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ (16 characters)
Message: ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___
Date: Day __ __ (numeric) Month __ __ (numeric) Year __ __ (numeric)
(1) A complete model number is required before Rosemount Inc. can process the order.
(2) If the Fluid is not located in Table 25 on page 42, the “Ordering Information” on page 38 must be completed.
(1)
(2)
Alarm High★❑ Alarm Low
___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ (32 characters)
For Rosemount Use Only
S.O.: LI
CHAMP: DATE:
ADMIN:
40
Product Data Sheet
00813-0100-4810, Rev HA March 2008
* = Required Item = Default
Primary Element Information
* Select Differential Producer (Select One)
Annubar
485 Annubar/ 3095MFA Mass ProBar, 3051SFA ProBar 285 AnnubarAnnubar Diamond II + / Mass Probar Long Radius Wall Taps, ASME Long Radius Wall Taps, ISO ISA 1932, ISO
Venturi
Nozzle, ISO Rough Cast/Fabricated Inlet, ASME Round Cast Inlet, ISO Machined Inlet, ASME Machined Inlet, ISO Welded Inlet, ISO
Other (All options require a discharge coefficient value)
Calibrated Orifice: Flange, Corner, or D & D/2 Taps.
Discharge coefficient: __________________
Calibrated Orifice: 2
Discharge coefficient: __________________
1
/2 D & 8D Taps
Calibrating Nozzle
Discharge coefficient: __________________
Calibrating Venturi
Discharge coefficient: __________________
Area Averaging Meter
Discharge coefficient: __________________
V-Cone
Discharge coefficient: __________________
Special Annubar dimension (required if customer supplies mounting hardware).
®
Diameter (d) ________________
Orifice
3051SFP, 3095MFP, 1195 405C, 405P, 3051SFC, 3095MFC 1595 Conditioning Orifice 2 Corner Taps, ASME Corner Taps, ISO D & D/2 Taps, ASME D & D/2 Taps, ISO D & D/2 Taps, ISO 99 Amendment 1 Flange Taps, AGA Flange Taps, ASME Flange Taps, ISO Flange Taps, ISO 99 Amendment 1 Small Bore, Flange Taps, ASME
inch★ ❑ millimeters
Rosemount Compact Orifice
Flowmeter Series
1
/2D & 8D Taps, ASME
at __________
ODF _____ ODT _____
°F 68 °F
°C
Pipe Information
* Orientation / Flow Direction:
* Line Size / Schedule: ___________________________________ Body I.D. (D): ___________________________________
Materials of Construction
* Pipe Material
* Primary Element Material
Operating Conditions
4 mA value Minimum Normal Maximum Full Scale:20 mA flow rate
Flow Rate 0 *
Pressure (P) *
Temperature (T) *
RTD Mode
Vertical Up Vertical Down Horizontal
Carbon Steel 304 SST 316 SST Hastelloy Other ________________
316 SST Hastelloy Other ___________________ (Please verify material availability)
(1)
(1)
(1)
**
* *
* *
(1)
(1)
(design to P and T)
(2)
*
*
Design
Normal Mode (Requires a RTD to be connected. If the RTD is disconnected or fails, the 3095MV output goes to alarm value)
Fixed Temperature Mode: Specify the fixed temperature value _____________________ ❑ °F ❑ °C
Backup Mode (Uses the connected RTD for temperature measurement. If the RTD is disconnected or fails, the transmitter uses a fixed
temperature value as a backup. This will not cause the mA output to go to alarm value and can potentially cause inaccurate flow measurement.) Fixed temperature value to be used as backup_________________
°F °C
41
Rosemount Compact Orifice
Product Data Sheet
00813-0100-4810, Rev HA
Flowmeter Series
March 2008
* = Required Item = Default
Base Conditions
Standard Base (P=14.696 psia / 101.325 kPa abs, T= 60 °F (15.56 °C))
Normal Base (P=14.696 psia / 101.325 kPa abs, T= 32 °F (0 °C))
Standard Base for Natural Gas (AGA) (P=14.73 psia, T= 60°F (15.56 °C))
User Defined: P= ________ Units: ________ T= ________ Units = ________
Compressibility at Base: ________________________ OR Density at Base: ________________________
(1) Operating ranges for pressure and temperature are needed for transmitter configuration.
(2) Required to verify that the product selection meets design criteria.
TABLE 25. Rosemount Fluids Database
Acetic Acid Acetone Acetonitrile Acetylene Acrylonitrile Air Allyl Alcohol Ammonia Argon Benzene Benzaldehyde Benzyl Alcohol Biphenyl Carbon Dioxide Carbon Monoxide Carbon Tetrachloride Chlorine Chlorotrifluoroethylene Chloroprene Cycloheptane Cyclohexane Cyclopentane Cyclopentene Cyclopropane
(1) This list is subject to change without notice. Steam per ASME Steam tables. All other fluids per AlChE.
Divinyl Ether Ethane Ethanol Ethylamine Ethylbenzene Ethylene Ethylene Glycol Ethylene Oxide Fluorene Furan Helium-4 Hydrazine Hydrogen Hydrogen Chloride Hydrogen Cyanide Hydrogen Peroxide Hydrogen Sulfide Isobutane Isobutene Isobutyl benzene Isopentane Isoprene Isopropanol
(1)
Methane Methanol Methyl Acrylate Methyl Ethyl Ketone Methyl Vinyl Ether m-Chloronitrobenzene Neon Neopentane Nitric Acid Nitric Oxide Nitrobenzene m-Dichlorobenzene Nitroethane Nitrogen Nitromethane Nitrous Oxide n-Butane n-Butanol n-Butyraldehyde n-Butyronitrile n-Decane n-Dodecane n-Heptadecane n-Heptane
n-Hexane n-Octane n-Pentane Oxygen Pentafluorothane Phenol Propadiene Pyrene Propylene Styrene Sulfer Dioxide Propane Toluene Trichloroethylene Vinyl Acetate Vinyl Chloride Vinyl Cyclohexane Water 1-Butene 1-Decene 1-Decanal 1-Decanol 1-Dodecene 1-Dodecanol
1-Heptanol 1-Heptene 1-Hexene 1-Hexadecanol 1-0ctanol 1-Octene 1-Nonanol 1-Pentadecanol 1-Pentanol 1-Pentene 1-Undecanol 1-Nonanal 1,2,4- Trichlorobenzene 1,1,2- Trichloroethane 1,1,2,2- Tetrafluoroethane 1,2-Butadiene 1,3-Butadiene 1,3,5- Trichlorobenzene 1,4-Dioxane 1,4-Hexadiene 2-Methyl-1-Pentene 2,2-Dimethylbutane
Drawing/Notes
42
Product Data Sheet
Rosemount Compact Orifice
00813-0100-4810, Rev HA March 2008
Flowmeter Series
FOUNDATION fieldbus™ Configuration Data Sheet (CDS)
DP FLOW CDS
Complete this form to define a custom flow configuration for DP Flowmeters. Unless specified, the flowmeter will be shipped with the default values identified by the H symbol.
For technical assistance in filling out this CDS, call a Rosemount representative.
NOTE
Any missing information will be processed with the indicated default values.
* = Required Item = Default
Customer Information
Customer: Contact Name:
Customer Phone: Customer Fax:
Customer Approval Sign-Off: Customer PO:
Calculation Approval
Check this box if a calculation for approval prior to manufacturing is required
Application and Configuration Data Sheet (Required with Order)
Ta g:
Model No
* Select fluid type Liquid Gas Steam
* Fluid name
Flowmeter Information (optional)
* Failure Mode Alarm Direction (select one)
Software Tag: ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ (16 characters)
Descriptor: ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___
Message: ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___
Date: Day __ __ (numeric) Month __ __ (numeric) Year __ __ (numeric)
(1) A complete model number is required before Rosemount Inc. can process the order.
(2) If the Fluid is not located in Table 26 on page 45, the “Ordering Information” on page 38 must be completed.
(1)
(2)
Alarm High★❑ Alarm Low
___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ (32 characters)
___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ (32 characters)
For Rosemount Use Only
S.O.: LI
CHAMP: DATE:
ADMIN:
43
Rosemount Compact Orifice Flowmeter Series
* = Required Item = Default
Primary Element Information
* Select Differential Producer (Select One)
Annubar
485 Annubar/ 3095MFA Mass ProBar, 3051SFA ProBar 285 AnnubarAnnubar Diamond II + / Mass Probar Long Radius Wall Taps, ASME Long Radius Wall Taps, ISO ISA 1932, ISO
Venturi
Nozzle, ISO Rough Cast/Fabricated Inlet, ASME Round Cast Inlet, ISO Machined Inlet, ASME Machined Inlet, ISO Welded Inlet, ISO
Other (All options require a discharge coefficient value)
Calibrated Orifice: Flange, Corner, or D & D/2 Taps.
Discharge coefficient: __________________
Calibrated Orifice: 2
Discharge coefficient: __________________
1
/2 D & 8D Taps
Calibrating Nozzle
Discharge coefficient: __________________
Calibrating Venturi
Discharge coefficient: __________________
Area Averaging Meter
Discharge coefficient: __________________
V-Cone
Discharge coefficient: __________________
Special Annubar dimension (required if customer supplies mounting hardware).
®
Diameter (d) ________________
Orifice
3051SFP, 3095MFP, 1195 405C, 405P, 3051SFC, 3095MFC 1595 Conditioning Orifice 2 Corner Taps, ASME Corner Taps, ISO D & D/2 Taps, ASME D & D/2 Taps, ISO D & D/2 Taps, ISO 99 Amendment 1 Flange Taps, AGA Flange Taps, ASME Flange Taps, ISO Flange Taps, ISO 99 Amendment 1 Small Bore, Flange Taps, ASME
inch★ ❑ millimeters
1
/2D & 8D Taps, ASME
at __________
ODF _____ ODT _____
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
°F 68 °F
°C
Pipe Information
* Orientation / Flow Direction:
* Line Size / Schedule: ___________________________________ Body I.D. (D): ___________________________________
Materials of Construction
* Pipe Material
* Primary Element Material
Operating Conditions
4 mA value Minimum Normal Maximum Full Scale:20 mA flow rate
Flow Rate 0 *
Pressure (P) *
Temperature (T) *
RTD Mode
Vertical Up Vertical Down Horizontal
Carbon Steel 304 SST 316 SST Hastelloy Other ________________
316 SST Hastelloy Other ___________________ (Please verify material availability)
(1)
(1)
(1)
**
* *
* *
(1)
(1)
(design to P and T)
(2)
*
*
Design
Normal Mode (Requires a RTD to be connected. If the RTD is disconnected or fails, the 3095MV output goes to alarm value)
Fixed Temperature Mode: Specify the fixed temperature value _____________________ ❑ °F ❑ °C
Backup Mode (Uses the connected RTD for temperature measurement. If the RTD is disconnected or fails, the transmitter uses a fixed
temperature value as a backup. This will not cause the mA output to go to alarm value and can potentially cause inaccurate flow measurement.) Fixed temperature value to be used as backup_________________
°F °C
44
Product Data Sheet
Rosemount Compact Orifice
00813-0100-4810, Rev HA March 2008
Flowmeter Series
* = Required Item = Default
Base Conditions
Standard Base (P=14.696 psia / 101.325 kPa abs, T= 60 °F (15.56 °C))
Normal Base (P=14.696 psia / 101.325 kPa abs, T= 32 °F (0 °C))
Standard Base for Natural Gas (AGA) (P=14.73 psia, T= 60°F (15.56 °C))
User Defined: P= ________ Units: ________ T= ________ Units = ________
Compressibility at Base: ________________________ OR Density at Base: ________________________
(1) Operating ranges for pressure and temperature are needed for transmitter configuration.
(2) Required to verify that the product selection meets design criteria.
TABLE 26. Rosemount Fluids Database
Acetic Acid Acetone Acetonitrile Acetylene Acrylonitrile Air Allyl Alcohol Ammonia Argon Benzene Benzaldehyde Benzyl Alcohol Biphenyl Carbon Dioxide Carbon Monoxide Carbon Tetrachloride Chlorine Chlorotrifluoroethylene Chloroprene Cycloheptane Cyclohexane Cyclopentane Cyclopentene Cyclopropane
(1) This list is subject to change without notice. Steam per ASME Steam tables. All other fluids per AlChE.
Divinyl Ether Ethane Ethanol Ethylamine Ethylbenzene Ethylene Ethylene Glycol Ethylene Oxide Fluorene Furan Helium-4 Hydrazine Hydrogen Hydrogen Chloride Hydrogen Cyanide Hydrogen Peroxide Hydrogen Sulfide Isobutane Isobutene Isobutyl benzene Isopentane Isoprene Isopropanol
(1)
Methane Methanol Methyl Acrylate Methyl Ethyl Ketone Methyl Vinyl Ether m-Chloronitrobenzene Neon Neopentane Nitric Acid Nitric Oxide Nitrobenzene m-Dichlorobenzene Nitroethane Nitrogen Nitromethane Nitrous Oxide n-Butane n-Butanol n-Butyraldehyde n-Butyronitrile n-Decane n-Dodecane n-Heptadecane n-Heptane
n-Hexane n-Octane n-Pentane Oxygen Pentafluorothane Phenol Propadiene Pyrene Propylene Styrene Sulfer Dioxide Propane Toluene Trichloroethylene Vinyl Acetate Vinyl Chloride Vinyl Cyclohexane Water 1-Butene 1-Decene 1-Decanal 1-Decanol 1-Dodecene 1-Dodecanol
1-Heptanol 1-Heptene 1-Hexene 1-Hexadecanol 1-0ctanol 1-Octene 1-Nonanol 1-Pentadecanol 1-Pentanol 1-Pentene 1-Undecanol 1-Nonanal 1,2,4- Trichlorobenzene 1,1,2- Trichloroethane 1,1,2,2- Tetrafluoroethane 1,2-Butadiene 1,3-Butadiene 1,3,5- Trichlorobenzene 1,4-Dioxane 1,4-Hexadiene 2-Methyl-1-Pentene 2,2-Dimethylbutane
Block Tag Names
AI Block Name (Flow): ____________________________ (AI 1400 ★) AI Block Name (DP): ____________________________ (AI 1500 ★) AI Block Name (SP): ____________________________ (AI 1600 ★) AI Block Name (PT): ____________________________ (AI 1700 ★) INTEG Block Name (Flow Total): ____________________________ (INTEG 2100 ★)
Drawing/Notes
45
Rosemount Compact Orifice Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Fluid Data Sheet (FDS)
For custom fluid not in the Rosemount Fluid Database
For technical assistance in filling out this CDS, call an Emerson Process Management representative. Complete this form to define a custom fluid. The H symbol identifies the default value.
NOTE
This form is not required if using the Rosemount Fluid Database.
* = Required Item = Default
Customer Information
Customer: Contact Name:
Customer Phone: Customer Fax:
Customer PO:
Fluid Properties
Custom Liquid– Complete Table ❑ Liquid
Custom Gas– Complete Table ❑ Gas
Custom Natural Gas– Complete Table ❑ Natural Gas
For Rosemount Use Only
S.O.: LI
CHAMP: DATE:
ADMIN:
46
Product Data Sheet
Rosemount Compact Orifice
00813-0100-4810, Rev HA March 2008
Flowmeter Series
TABLE 27. Custom Liquid Worksheet
* = Required Item = Default
Mass Liquid Density and Viscosity Information
1. Fill in the following operating temperatures
a) _________________________ min
1
b) _________________________ [
c) _________________________ [
d) _________________________ max
2. Transfer the values from the above section to the numbered lines below.
3. Check one Density box, then enter the values for each temperature and the standard density.
4. Check one Viscosity box, then enter values for each temperature. (At least one viscosity value is required). Density
Density in lbs/CuFt Density in kg/CuM
/3 (max - min))] + min
2
/3 (max - min))] + min
Viscosity
Viscosity in centipoise Viscosity in lbs/ft sec Viscosity in pascal sec
Temperature Temperature a) _____________ min a) _____________ min.
1
b) _____________ [
c) _____________ [
/3 (max - min))] + min b) _____________ [1/3 (max - min))] + min
2
/3 (max - min))] + min c) _____________ [2/3 (max - min))] + min
d) _____________ max d) _____________ max
Base density: __________________________________________________________ (at base reference conditions specified)
Volumetric Liquid Density and Viscosity Information
* Density at Flow: _________________________________________________ Units: lb/ft3❑ Kg/m3❑ Other:
OR
Specific Gravity at Flow: ____________________________________________
* Viscosity at Flow: ________________________________________________ Units: Centipoise Other:
47
Rosemount Compact Orifice Flowmeter Series
TABLE 28. Custom Gas Worksheet
* = Required Item = Default
Mass Gas Compressibility and Viscosity Information
1. Fill in the following operating pressures and operating temperatures
Operating Pressures Operating Temperatures
1) _____________ min 5) _____________ min
1
2) _____________ [
3) _____________ [
4) _____________ max 8) _____________ [
2. Transfer the values from the above section to the numbered lines below
3. Check one Density/Compressibility box, then enter the 12 values for each pressure/temperature range.
4. Check one Viscosity box, then enter values for each temperature. (At least one viscosity value is required).
5. Enter values for molecular weight, isentropic exponent, and standard density (or standard compressibility). Density
Density in lbs/CuFt Density in kg/CuM Compressibility
Pressure Temperature Temperature
/3 (max - min))] + min 6) _____________ [1/2 (max - min))] + min
2
/3 (max - min))] + min 7) _____________ max
1
/3 (max - min))] + min
2
9) _____________ [
Viscosity
/3 (max - min))] + min
Viscosity in centipoise Viscosity in lbs/ft sec Viscosity in pascal sec
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
1) ____________ 5) _____________________________ 5) ________________________________________
2) ____________ 5) _____________________________ 8) ________________________________________
3) ____________ 5) _____________________________ 9) ________________________________________
4) ____________ 5) _____________________________ 7) ________________________________________
1) ____________ 6) _____________________________
2) ____________ 6) _____________________________ Molecular Weight: _________________________
3) ____________ 6) _____________________________ Isentropic Exponent: _______________________ 1.4
4) ____________ 6) _____________________________
1) ____________ 7) _____________________________
2) ____________ 7) _____________________________
3) ____________ 7) _____________________________
4) ____________ 7) _____________________________
Standard density/compressibility: __________________________________________________________
Volumetric Gas Compressibility and Viscosity Information
* Density at Flow: ______________________________ Units: lb/ft3❑ Kg/m3❑ Other:
OR
M.W. / Specific Gravity at Flow: _________________________________________________
Compressibility at Flow: _____________________________________________________
Compressibility at Base: ____________________________________________________
* Viscosity at Flow: _____________________________ Units: Centipoise Other: Isentropic Exponent (K):______ 1.4
48
Product Data Sheet
00813-0100-4810, Rev HA March 2008
Rosemount Compact Orifice
Flowmeter Series
49
Rosemount Compact Orifice Flowmeter Series
Product Data Sheet
00813-0100-4810, Rev HA
March 2008
Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale The Emerson logo is a trade mark and service mark of Emerson Electric Co. Rosemount, the Rosemount logotype, ProPlate, Mass ProPlate, and Annubar are registered trademarks of Rosemount Inc. All other marks are the property of their respective owners.
Emerson Process Management Rosemount Inc.
8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906-8888 F (952) 949-7001
www.rosemount.com
Emerson Process Management
Heath Place Bognor Regis West Sussex PO22 9SH England T 44 (0) 1243 863121 F 44 (0) 1243 867554
Emerson Process Management Asia Pacific Private Limited
1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947 Enquiries@AP.EmersonProcess.com
¢00813-0100-4810;¤
© 2008 Rosemount Inc. All rights reserved.