Rosemount 3051T Data sheet

Product Data Sheet
00813-0100-4001, Rev TC
Rosemount™ 3051 Pressure Transmitter
March 2018
With the Rosemount 3051 Pressure Transmitter, you’ll gain more control over your plant. You’ll be able to reduce product variation and complexity, as well as your total cost of ownership by leveraging one device across a number of pressure, level, and flow applications. You’ll have access to information you can use to diagnose, correct, and even prevent issues. And with unparalleled reliability and experience, the Rosemount 3051 is the industry standard that will help increase efficiency and safety so your operations can remain globally competitive.
Rosemount 3051

Setting the standard for pressure measurement

Proven best-in-class performance, reliability and safety

More than seven million installed
Reference accuracy 0.04 percent of span
Installed total performance of 0.14 percent of span
10-year stability of 0.2 percent of URL
SIL2/3 certified (IEC 61508)

Maximize installation and application flexibility with the coplanar platform

Improve reliability and performance with integrated DP
Flowmeters, DP Level solutions and integral manifolds
Easy installation with all solutions fully assembled, leak-tested
and calibrated
Meet your application needs with an unsurpassed offering
March 2018

Advanced functionality

Power advisory diagnostics
Detect on-scale failures caused by electrical loop issues before they impact your process
operation
This capability is safety certified for your most critical applications
Local operator interface (LOI)
Straightforward menus and built-in configuration buttons allow you commission the device in
less than a minute
Configure in hazardous-area locations without removing the transmitter cover using external
buttons
Contents
Rosemount 3051C Coplanar Pressure Transmitter . . . 4
Rosemount 3051T In-Line Pressure Transmitter . . . . .11
Rosemount 3051L Level Transmitter . . . . . . . . . . . . . . 37
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Rosemount 3051CF Flowmeter selection guide . . . . .17
Rosemount 3051CFA Annubar Flowmeter . . . . . . . . .18
Rosemount 3051CFC Compact Flowmeter . . . . . . . . .26
Rosemount 3051CFP Integral Orifice Flowmeter . . . .31
2
Product certifications
Pipe I.D. range codes
. . . . . . . . . . . . . . . . . . . . . . . . . . 56
. . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Emerson.com/Rosemount
March 2018
Rosemount 3051
Industry leading capabilities extended to IEC 62591
®
(WirelessHART
Cost effectively implement wireless on the industry's most proven platform
Optimize safety with the industry's only intrinsically safe power module
Eliminate wiring design and construction complexities to lower costs by 40 to 60 percent
Quickly deploy new pressure, level, and flow measurements in 70 percent less time
)

Innovative, integrated DP Flowmeters

Fully assembled, configured, and leak tested for out-of-the-box installation
Reduce straight pipe requirements, lower permanent pressure loss, and achieve accurate
measurement in small line sizes
Up to 1.65 percent volumetric flow accuracy at 8:1 turndown

Proven, reliable, and innovative DP Level Technologies

Connect to virtually any process with a comprehensive offering of process connections, fill
fluids, direct mount, or capillary connections and materials
Quantify and optimize total system performance with QZ option
Operate at higher temperature and in vacuum applications
Optimize level measurement with cost efficient Rosemount Tuned-System
Assemblies

Instrument manifolds – quality, convenient, and easy

Designed and engineered for optimal performance with Rosemount transmitters
Save installation time and money with factory assembly
Offers a variety of styles, materials, and configurations
Emerson.com/Rosemount
3
Rosemount 3051
March 2018

Rosemount 3051C Coplanar Pressure Transmitter

Rosemount 3051C Coplanar™ Pressure Transmitters are the industry standard for differential, gage, and absolute pressure measurement. The coplanar platform enables seamless integration with manifolds, flow and level solutions. Capabilities include:
Power advisory can proactively detect degraded electrical loop integrity issues
(option code DA0)
LOI with straightforward menus and built-in configuration buttons (option code M4)
Safety Certification (option code QT)
Additional information:
Specifications: page 44 Certifications: page 56 Dimensional drawings: page 67
See Specifications and options for more details on each configuration. Specification and selection of product materials, options, or components must be made by the purchaser of the equipment. See page 53 for more information on material selection.
Table 1. Rosemount 3051C Coplanar Pressure Transmitters Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
(1)
Model
3051C Coplanar pressure transmitter
Transmitter t ype
Measurement type
D Differential
G Gage
(2)
A
Absolute
Pressure range
Differential (Rosemount 3051CD)
1
2
3
4
5
(3)
0
–25 to 25 inH2O (–62,16 to 62,16 mbar)
–250 to 250 inH2O (–621,60 to 621,60 mbar)
–1000 to 1000 inH2O (–2,48 to 2,48 bar)
–300 to 300 psi (–20,68 to 20,68 bar)
–2000 to 2000 psi (–137,89 to 137,89 bar)
–3 to 3 inH2O (-7,46 to 7,46 mbar)
Gage (Rosemount 3051CG)
–25 to 25 inH2O (–62,16 to 62,16 mbar)
–250 to 250 inH2O (–621,60 to 621,60 mbar)
–393 to 1000 inH2O (–0,97 to 2,48 bar)
–14.2 to 300 psi (–0,97 to 20,68 bar)
–14.2 to 2000 psi (–0,97 to 137,89 bar)
N/A N/A
Absolute (Rosemount 3051CA)
0 to 30 psia (0 to 2,06 bar)
0 to 150 psia (0 to 10,34 bar)
0 to 800 psia (0 to 55,15 bar)
0 to 4000 psia (0 to 275,79 bar)
N/A
Transmitter output
(4)
A
F FOUNDATION™ Fieldbus Protocol
(5)
W
(6)
X
(7)
M
4–20 mA with digital signal based on HART® Protocol
PROFIBUS® PA Protocol
Wireless (requires wireless options and engineered polymer housing)
Low-power, 1–5 Vdc with digital signal based on HART Protocol
4
Emerson.com/Rosemount
March 2018
Rosemount 3051
Table 1. Rosemount 3051C Coplanar Pressure Transmitters Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Materials of construction
Process flange type Flange material Drain/vent
2 Coplanar Stainless steel (SST) SST
(8)
3
Coplanar Cast C-276 Alloy C-276
4 Coplanar Alloy 400 Alloy 400/K-500
5 Coplanar Plated carbon steel (CS) SST
(8)
7
(8)
8
Coplanar SST Alloy C-276
Coplanar Plated CS Alloy C-276
0 Alternate process connection
Isolating diaphragm
(8)
2
(8)
3
(9)
4
(9)
5
(9)
6
(9)
7
316L SST
Alloy C-276
Alloy 400
Tantalum (available on Rosemount 3051CD and CG, ranges 2–5 only; not available on Rosemount 3051CA)
Gold-plated alloy 400 (use in combination with O-ring option code B)
Gold-plated 316 SST
O-ring
A Glass-filled PTFE
B Graphite-filled PTFE
Sensor fill fluid
1 Silicone
(9)
2
Inert (differential and gage only)
Housing material Conduit entry size
A Aluminum
B Aluminum M20 x 1.5
E Aluminum, ultra low copper
F Aluminum, ultra low copper M20 x 1.5
J SST
K SST M20 x 1.5
(10)
P
(11)
D
(11)
M
Engineered polymer No conduit entries
Aluminum G1/2
SST G1/2
1
/2–14 NPT
1
/2–14 NPT
1
/2–14 NPT
Wireless options (requires wireless output code X and engineered polymer housing code P)
Wireless transmit rate, operating frequency, and protocol
WA3 User Configurable Transmit Rate, 2.4GHz WirelessHART Protocol
Antenna and SmartPower
WP5 Internal antenna, compatible with Green Power Module (I.S. Power Module sold separately)
Emerson.com/Rosemount
5
Rosemount 3051
March 2018
Table 1. Rosemount 3051C Coplanar Pressure Transmitters Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Options (include with selected model number)
Extended product warranty
WR3 3-year limited warranty
WR5 5-year limited warranty
Plantweb™ control functionality
A01 FOUNDATION Fieldbus control function block suite
Plantweb diagnostic functionality
(13)
DA0
(12)
D01
Alternate flange
Power Advisory HART Diagnostic
FOUNDATION Fieldbus Diagnostics Suite
(14)
H2 Traditional flange, 316 SST, SST drain/vent
(8)
H3
Traditional flange, alloy C, alloy C-276 drain/vent
H4 Traditional flange, cast alloy 400, alloy 400/K-500 drain/vent
(8)
H7
Traditional flange, 316 SST, alloy C-276 drain/vent
HJ DIN-compliant traditional flange,SST,7/16-in. adapter/manifold bolting
FA Level flange, SST, 2-in., ANSI class 150, vertical mount 316 SST drain/vent
FB Level flange, SST, 2-in., ANSI Class 300, vertical mount 316 SST drain/vent
FC Level flange, SST, 3-in., ANSI Class 150, vertical mount 316 SST drain/vent
FD Level flange, SST, 3-in., ANSI Class 300, vertical mount 316 SST drain/vent
FP DIN level flange, SST, DN 50, PN 40, vertical mount 316 SST drain/vent
FQ DIN level flange, SST, DN 80, PN 40, vertical mount 316 SST drain/vent
(15)
HK
DIN compliant traditional flange, SST, 10 mm adapter/manifold bolting 316 SST
HL DIN compliant traditional flange, SST, 12 mm adapter/manifold bolting 316 SST
Manifold assembly
(16)
S5 Assemble to Rosemount 305 Integral Manifold
S6 Assemble to Rosemount 304 Manifold or Connection System
Integral mount primary element
S3 Assemble to Rosemount 405 Compact Orifice Plate
(17)
S4
Seal assemblies
(18)
S1
(19)
S2
Mounting bracket
B4 Coplanar flange bracket, all SST, 2-in. pipe and panel
B1 Traditional flange bracket, CS, 2-in. pipe
B2 Traditional flange bracket, CS, panel
B3 Traditional flange flat bracket, CS, 2-in. pipe
B7 Traditional flange bracket, B1 with SST bolts
B8 Traditional flange bracket, B2 with SST bolts
B9 Traditional flange bracket, B3 with SST bolts
Assemble to Rosemount Annubar™ or Rosemount 1195 Integral Orifice
(16)
Assemble to one Rosemount 1199 seal
Assemble to two Rosemount 1199 seals
(20)
(12)
(15)(16)
6
Emerson.com/Rosemount
March 2018
Rosemount 3051
Table 1. Rosemount 3051C Coplanar Pressure Transmitters Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
BA Traditional flange bracket, B1, all SST
BC Traditional flange bracket, B3, all SST
Product certifications
E8 ATEX Flameproof and Dust Certification
(21)
I1
IA ATEX FISCO Intrinsic Safety; for FOUNDATION Fieldbus or PROFIBUS PA Protocol only
N1 ATEX Type n Certification and Dust
K8 ATEX Flameproof, Intrinsic Safety, Type n, Dust (combination of E8, I1, and N1)
(22)
E4
E5 FM Explosion-proof, Dust Ignition-Proof
(23)
I5
IE FM FISCO Intrinsically Safe; for FOUNDATION Fieldbus or PROFIBUS PA Protocol only
K5 FM Explosion-proof, Dust Ignition-Proof, Intrinsically Safe, and Division 2
C6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2
(10)
I6
K6 CSA and ATEX Explosion-proof, Intrinsically Safe, and Division 2 (combination of C6, E8, and I1)
E7 IECEx Flameproof, Dust Ignition-proof
I7 IECEx Intrinsic Safety
N7 IECEx Type n Certification
K7 IECEx Flame-proof, Dust Ignition-proof, Intrinsic Safety, and Type n (combination of I7, N7, and E7)
E2 INMETRO Flameproof
I2 INMETRO Intrinsic Safety
IB INMETRO FISCO intrinsically safe; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only
K2 INMETRO Flameproof, Intrinsic Safety
E3 China Flameproof
I3 China Intrinsic Safety
N3 China Type n
EM Technical Regulations Customs Union (EAC) Flameproof
IM Technical Regulations Customs Union (EAC) Intrinsic Safety
KM Technical Regulations Customs Union (EAC) Flameproof and Intrinsic Safety
KB FM and CSA Explosion-proof, Dust Ignition Proof, Intrinsically Safe, and Division 2 (combination of K5 and C6)
KD FM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of K5, C6, I1, and E8)
Drinking water approval
DW NSF drinking water approval
Shipboard approvals
SBS American Bureau of Shipping
(25)
SBV
SDN Det Norske Veritas
(25)
SLL
Custody transfer
C5
ATEX Intrinsic Safety and Dust
TIIS Flame-proof
FM Intrinsically Safe, Nonincendive
CSA Intrinsic Safety
(24)
(9)
Bureau Veritas (BV)
Lloyds Register (LR)
(13)
Measurement Canada Accuracy Approval (limited availability depending on transmitter type and range;
contact an Emerson
representative)
Emerson.com/Rosemount
7
Rosemount 3051
March 2018
Table 1. Rosemount 3051C Coplanar Pressure Transmitters Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Bolting material
L4 Austenitic 316 SST bolts
L5 ASTM A 193, grade B7M bolts
L6 Alloy K-500 bolts
Display and interface options
(26)
M4
LCD display with LOI
M5 LCD display
Calibration certificate
Q4 Calibration Certificate
(27)
QG
Calibration Certificate and GOST Verification Certificate
QP Calibration certification and tamper evident seal
Material traceability certification
Q8 Material Traceability Certification per EN 10204 3.1
Quality certification for safety
QS Prior-use certificate of FMEDA data
QT Safety certified to IEC 61508 with certificate of FMEDA
(13)
Configuration buttons
(13)
D4
(28)
DZ
Transient protection
Analog zero and span
Digital zero trim
(9)(29)
T1 Transient protection terminal block
Software configuration
(28)
Custom Software Configuration
C1
(For wired, see the Rosemount 3051 Configuration Data Sheet For wireless, see the Rosemount 3051 Wireless Configuration Data Sheet.
.
)
Low power output
C2 0.8–3.2 Vdc output with digital signal based on HART Protocol (available with output code M only)
Gage pressure calibration
C3 Gage calibration (Rosemount 3051ca4 only)
Alarm levels
C4 Analog output levels compliant with NAMUR recommendation NE 43, alarm high
CN Analog output levels compliant with NAMUR recommendation NE 43, alarm low
CR
CS
CT Rosemount standard low alarm
(13)
Custom alarm and saturation signal levels, high alarm (requires C1 and Rosemount 3051 Configuration Data Sheet
Custom alarm and saturation signal levels, low alarm (requires C1 and Rosemount 3051 Configuration Data Sheet
)
)
Pressure testing
P1 Hydrostatic testing with certificate
8
Emerson.com/Rosemount
March 2018
Rosemount 3051
Table 1. Rosemount 3051C Coplanar Pressure Transmitters Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Cleaning process area
P2 Cleaning for special service
P3 Cleaning for <1 PPM chlorine/fluorine
Flange adapters
DF
(30)
1
/2–14 NPT flange adapter(s)
Vent/drain valves
D7 Coplanar flange without drain/vent ports
Conduit plug
(9)(31)
DO 316 SST conduit plug
RC1/4 RC1/2 process connection
(32)
D9 RC 1/4 flange with RC 1/2 flange adapter - SST
Max static line pressure
P9 4500 psig (310,26 bar) static pressure limit (Rosemount 3051CD ranges 2–5 only)
Ground screw
V5 External ground screw assembly
(9)(33)
Surface finish
Q16 Surface finish certification for sanitary remote seals
Toolkit total system performance reports
QZ Remote seal system performance calculation report
Conduit electrical connector
(9)
GE M12, 4-pin, male connector (eurofast®)
GM A size Mini, 4-pin, male connector (minifast®)
NACE® certificate
(34)
Q15 Certificate of Compliance to NACE MR0175/ISO 15156 for wetted materials
Q25 Certificate of Compliance to NACE MR0103 for wetted materials
Cold temperature
(35)
BR5 –58 °F (–50 °C) cold temperature
BR6 –76 °F (–60 °C) cold temperature
HART Revision configuration (requires HART output code A)
(4)
HR5 Configured for HART Revision 5
HR7 Configured for HART Revision 7
Typical model number: 3051CD 2 A 2 2 A 1 A B4
1. Select configuration buttons (option code D4 or DZ) or LOI (option code M4) if local configuration buttons are required.
2. If ordered with Wireless output code X, only range 1–4, 316L SST diaphragm material (code 2), silicone fill fluid (code 1) and wireless housing (code P) are available.
3. Rosemount 3051CD0 is only available with output code A and X. For output code A, only process flange code 0 (alternate flange H2, H7, HJ, or HK), isolating diaphragm code 2, O ring code A and bolting option L4 are available. For output code X, only process flange code 0 (alternate flange H2), isolating diaphragm code 2, O ring code A and bolting option L4 are available.
Emerson.com/Rosemount
9
Rosemount 3051
4. O pti on HR 5 co nfig ure s the HAR T out put to HA RT Re vis ion 5 . Op tion HR7 conf igu res t he H ART outp ut to HAR T Rev isio n 7. The devi ce can be field configured to H ART Revision 5 or 7 if desired. HART Revision 5 is the default HART output.
5. For local addressing and configuration, M4 LOI is required.
6. Available approvals are FM Intrinsically Safe, (option code I5), CSA Intrinsically Safe (option code I6), ATEX Intrinsic Safety (option code I1), IECEx Intrinsic Safety (option code I7) and EAC Intrinsic Safety (option code IM).
7. Only available with C6, E2, E5, I5, K5, KB, and E8 product certifications. Not available with GE, GM, SBS, DA0, M4, D4, DZ, QT, HR5, HR7, CR, CS, and CT.
8. Materials of Construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
9. Not available with wireless output (code X).
10. Only available with wireless output (code X).
11. Not available with Product certifications options E8, K8, E5, K5, C6, K6, E7, K7, E2, K2, E3, KB, and KD.
12. Only valid with F
13. Only available with HART 4–20 mA output (code A).
14. Requires 0 code in materials of construction for alternate process connection.
15. Not valid with option code P9 for 4500 psi static pressure.
16. “Assemble-to” items are specified separately and require a completed model number.
17. Process flange limited to coplanar (option codes 2, 3, 5, 7, 8) or traditional (option codes H2, H3, H7).
18. Not valid with option code D9 for RC
19. Not valid for option codes DF and D9 for adapters.
20. Panel mounting bolts are not supplied.
21. Dust approval not applicable to output code X. See “Certificate: AG-0226; AG-0454; AG-0477” on page 62 for wireless approvals.
22. Only available with output codes A - 4–20mA HART, F - F
23. Nonincendive certification not provided with Wireless output (code X).
24. Not available with Alloy C-276 isolator (code 3), tantalum isolator (code 5), all cast C-276 flanges, all plated carbon steel (CS) flanges, all DIN flanges, all Level flanges, assemble-to manifolds (codes S5 and S6), assemble-to seals (codes S1 and S2), assemble-to primary elements (codes S3 and S4), surface finish certification (code Q16), and remote seal system report (code QZ).
25. Only available with product certifications E7, E8, I1, I7, IA, K7, K8, KD, N1, and N7
26. Not available with F
27. Contact an Emerson representative for availability.
28. Only available with HART 4–20 mA output (code A) and wireless output (code X)
29. The T1 option is not needed with FISCO Product Certifications; transient protection is included in the FISCO product certification codes IA, IB, and IE.
30. Not valid with alternate process connection options S3, S4, S5, and S6.
31. Transmitter is shipped with a 316 SST conduit plug (uninstalled) in place of standard CS conduit plug.
32. Not available with alternate process connection; DIN flanges and level flanges.
33. The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.
34. NACE compliant wetted materials are identified by Footnote 8.
35. Only available on pressure ranges 1–5, with silicone sensor fill fluid and SST or C-276 isolating diaphragms.
OUNDATION Fieldbus output (code F).
1
/2 adapters.
OUNDATION Fieldbus, and W - PROFIBUS PA. Also only available with G
OUNDATION Fieldbus (code F), wireless (code X), or low power (code M).
1
/2 housing thread types.
March 2018
10
Emerson.com/Rosemount
March 2018
Rosemount 3051

Rosemount 3051T In-Line Pressure Transmitter

Rosemount 3051T In-Line Pressure Transmitters are the industry standard for gage and absolute pressure measurement. The in-line, compact design allows the transmitter to be connected directly to a process for quick, easy and cost effective installation. Capabilities include:
Power advisory can proactively detect degraded electrical loop integrity issues
(option code DA0)
LOI with straightforward menus and built-in configuration buttons (option code M4)
Safety Certification (option code QT)
Additional information:
Specifications: page 44 Certifications: page 56 Dimensional drawings: page 67
See “Specifications” on page 44 and options for more details on each configuration. Specification and selection of product materials, options, or components must be made by the purchaser of the equipment. See page 53 for more information on material selection.
Table 2. Rosemount 3051T In-Line Pressure Transmitter Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
(1)
Model
Transmitter type
3051T In-line pressure transmitter
Pressure type
G Gage
(2)
A
Absolute
Pressure range
Gage (Rosemount 3051TG)
1 –14.7 to 30 psi (–1,01 to 2,06 bar) 0 to 30 psia (0 to 2,06 bar)
2 –14.7 to 150 psi (–1,01 to 10,34 bar) 0 to 150 psia (0 to 10,34 bar)
3 –14.7 to 800 psi (–1,01 to 55,15 bar) 0 to 800 psia (0 to 55,15 bar)
4 –14.7 to 4000 psi (–1,01 to 275,79 bar) 0 to 4000 psia (0 to 275,79 bar)
5 –14.7 to 10000 psi (–1,01 to 689,47 bar) 0 to 10000 psia (0 to 689,47 bar)
(4)
6
–14.7 to 20000 psi (–1,01 to 1378,95 bar) 0 to 20000 psia (0 to 1378,95 bar)
(3)
Absolute (Rosemount 3051TA)
Transmitter outpu t
(5)
A
F FOUNDATION Fieldbus Protocol
(6)
W
(7)
X
(8)
M
4–20 mA with digital signal based on HART Protocol
PROFIBUS PA Protocol
Wireless (requires wireless options and engineered polymer housing)
Low-power 1–5 Vdc with digital signal based on HART Protocol
Emerson.com/Rosemount
11
Rosemount 3051
March 2018
Table 2. Rosemount 3051T In-Line Pressure Transmitter Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Process connection style
2B
(9)
2C
(10)
2F
(11)
61
Isolating diaphragm
2 316L SST 316L SST
3 Alloy C-276 Alloy C-276
7 Gold-plated 316 SST 316L SST
1
/2–14 NPT female (range 1–5 only)
G1/2 A DIN 16288 male (range 1–4 only)
Coned and threaded, compatible with autoclave type F-250-C (range 5–6 only)
Non-threaded Instrument flange (range 1–4 only)
(12)
Process connection wetted parts material
Sensor fill fluid
1 Silicone
(11)
2
Inert
Housing material Conduit entry size
A Aluminum
B Aluminum M20 x 1.5
E Aluminum, ultra low copper
F Aluminum, ultra low copper M20 x 1.5
J SST
K SST M20 x 1.5
(13)
P
(14)
D
(14)
M
Engineered polymer No conduit entries
Aluminum G1/2
SST G1/2
1
/2–14 NPT
1
/2–14 NPT
1
/2–14 NPT
Wireless options (requires wireless output code X and engineered polymer housing code P)
Wireless transmit rate, operating frequency, and protocol
WA3 User configurable transmit rate, 2.4GHz WirelessHART Protocol
Antenna and SmartPower
WP5 Internal antenna, compatible with Green Power Module (I.S. Power Module sold separately)
Options (include with selected model number)
Extended product warranty
WR3 3-year limited warranty
WR5 5-year limited warranty
12
Emerson.com/Rosemount
March 2018
Rosemount 3051
Table 2. Rosemount 3051T In-Line Pressure Transmitter Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Plantweb control functionality
(15)
A01 FOUNDATION Fieldbus control function block suite
Plantweb diagnostic functionality
(24)
DA0
(15)
D01
Integral assembly
S5 Assemble to Rosemount 306 Integral Manifold
Diaphragm seal assemblies
S1 Assemble to one Rosemount 1199 seal
Mounting bracket
B4 Bracket for 2-in. pipe or panel mounting, all SST
Power Advisory HART diagnostic
FOUNDATION Fieldbus diagnostics suite
(16)
(16)
(17)
Product certifications
E8 ATEX Flameproof and Dust Certification
(18)
I1
IA ATEX Intrinsic Safety for FISCO; for F
N1 ATEX Type n Certification and Dust
K8 ATEX Flame-proof, Intrinsic Safety, Type n, Dust (combination of E8, I1, and N1)
(19)
E4
E5 FM Explosion-proof, Dust Ignition-proof
(20)
I5
IE FM FISCO Intrinsically Safe; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only
K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2
C6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2
(13)
I6
K6 CSA and ATEX Explosion-proof, Intrinsically Safe, and Division 2 (combination of C6, E8, and I1)
E7 IECEx Flameproof, Dust Ignition-proof
I7 IECEx Intrinsic Safety
N7 IECEx Type n Certification
ATEX Intrinsic Safety and Dust
OUNDATION Fieldbus or PROFIBUS PA Protocols only
TIIS Flameproof
FM Intrinsically Safe, Nonincendive
CSA Intrinsic Safety
K7 IECEx Flameproof, Dust Ignition-proof, Intrinsic Safety, and Type n (combination of I7, N7, and E7)
E2 INMETRO Flameproof
I2 INMETRO Intrinsic Safety
IB INMETRO FISCO intrinsically safe; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only
K2 INMETRO Flameproof, Intrinsic Safety
E3 China Flameproof
Emerson.com/Rosemount
13
Rosemount 3051
March 2018
Table 2. Rosemount 3051T In-Line Pressure Transmitter Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
I3 China Intrinsic Safety
N3 China Type n
EM Technical Regulations Customs Union (EAC) Flameproof
IM Technical Regulations Customs Union (EAC) Intrinsic Safety
KM Technical Regulations Customs Union (EAC) Flameproof and Intrinsic Safety
KB FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2 (combination of K5 and C6)
KD FM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of K5, C6, I1, and E8)
Drinking water approval
(21)
DW NSF drinking water approval
Shipboard approvals
(11)
SBS American Bureau of Shipping
(22)
SBV
Bureau Veritas (BV)
SDN Det Norske Veritas
(22)
SLL
Lloyds Register (LR)
Custody transfer
C5
Measurement Canada Accuracy Approval (Limited availability depending on transmitter type and range. Contact an Emerson representative.)
Calibration certification
Q4 Calibration Certificate
(23)
QG
Calibration Certificate and GOST Verification Certificate
QP Calibration Certification and tamper evident seal
Material traceability certification
Q8 Material Traceability Certification per EN 10204 3.1
Quality certification for safety
(24)
QS Prior-use certificate of FMEDA Data
QT Safety certified to IEC 61508 with certificate of FMEDA
Configuration buttons
(24)
D4
DZ
(25)
Analog zero and span
Digital zero trim
Display and interface options
(26)
M4
LCD display with LOI
M5 LCD display
Wireless SST sensor module
(13)
WSM Wireless SST sensor module
14
Emerson.com/Rosemount
March 2018
Rosemount 3051
Table 2. Rosemount 3051T In-Line Pressure Transmitter Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Conduit plug
(11)(27)
DO 316 SST conduit plug
Transient terminal block
(11)(28)
T1 Transient protection terminal block
Software configuration
(25)
Custom Software Configuration
C1
(For wired, see the Rosemount 3051 Configuration Data Sheet. For wireless, see the Rosemount 3051 Wireless Configuration Data Sheet.
)
Low power output
C2 0.8–3.2 Vdc output with digital signal based on HART Protocol (available with output code M only)
Alarm levels
C4 Analog output levels compliant with NAMUR recommendation NE 43, alarm high
CN Analog output levels compliant with NAMUR recommendation NE 43, low alarm
CR
CS
(24)
Custom alarm and saturation signal levels, high alarm (requires C1 and Rosemount 3051 Configuration Data Sheet
Custom alarm and saturation signal levels, low alarm (requires C1 and Rosemount 3051 Configuration Data Sheet)
)
CT Rosemount standard low alarm
Pressure testing
P1 Hydrostatic testing with certificate
Cleaning process area
(29)
P2 Cleaning for special service
P3 Cleaning for <1 PPM chlorine/fluorine
Ground screw
(11)(30)
V5 External ground screw assembly
Surface finish
Q16 Surface finish certification for sanitary remote seals
Toolkit total system performance reports
QZ Remote seal system performance calculation report
Conduit electrical connector
GE M12, 4-pin, male connector (eurofast)
GM A size mini, 4-pin, male connector (minifast)
NACE certificate
(31)
(11)
Q15 Certificate of Compliance to NACE MR0175/ISO15156 for wetted materials
Q25 Certificate of Compliance to NACE MR0103 for wetted materials
Emerson.com/Rosemount
15
Rosemount 3051
March 2018
Table 2. Rosemount 3051T In-Line Pressure Transmitter Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Cold temperature
BR5 –50 °F (–58 °C) cold temperature
BR6 –76 °F (–60 °C) cold temperature
HART Revision configuration (requires HART output code A)
(5)
HR5 Configured for HART Revision 5
HR7 Configured for HART Revision 7
Typical model number: 3051T G 5 F 2A 2 1 A B4
1. Select configuration buttons (option code D4 or DZ) or LOI (option code M4) if local configuration buttons are required.
2. Wireless output (code X) only available in absolute measurement type (code A) in range 1–5 with (code P). Wireless output and range 6 is only available with coned and threaded process connection (code 2F) and polymer housing.
3. Rosemount 3051TG lower range limit varies with atmospheric pressure.
4. Not available with PROFIBUS PA or low power 1–5 Vdc transmitter output (option code W or M), inert sensor fill fluid (option code 2), NSW drinking water approval (option code DW), or assemble to manifolds (option code S5).
5. O pti on HR 5 co nfig ure s the HAR T out put to H ART Re vis ion 5. O ptio n HR 7 con figu res the HART out put t o HA RT Re visi on 7 . Th e dev ice can be field configured to HART Revision 5 or 7 if desired. HART Revision 5 is the default HART output.
6. For local addressing and configuration, M4 LOI is required.
7. Requires wireless options and engineered polymer housing. Available approvals are FM Intrinsically Safe, (option code I5), CSA Intrinsically Safe (option code I6), ATEX Intrinsic Safety (option code I1), IECEx Intrinsic Safety (option code I7), and EAC Intrinsic Safety (option code IM).
8. Only available with C6, E2, E5, I5, K5, KB, and E8 product certifications. Not available with GE, GM, SBS, DA0, M4, D4, DZ, QT, HR5, HR7, CR, CS, and CT.
9. Wireless output (code X) only available in G fluid (code 1) and housing (code P).
10. Not available with wireless output for range 5.
11. Not available with wireless (output code X).
12. Materials of construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
13. Only available with wireless (output code X).
14. Not available with Product certifications options E8, K8, E5, K5, C6, K6, E7, K7, E2, K2, E3, KB, and KD.
15. Only valid with F
16. “Assemble-to” items are specified separately and require a completed model number.
17. Panel mounting bolts are not supplied.
18. Dust approval not applicable to output code X. See “Certificate: AG-0226; AG-0454; AG-0477” on page 62 for wireless approvals.
19. Only available with output codes A - 4–20mA HART, F - F
20. Nonincendive certification not provided with wireless output (code X).
21. Not available with Alloy C-276 isolator (option code 3), assemble-to manifolds (option code S5), assemble-to seals (option code S1), surface finish certification (option code Q16), and remote seal system report (option code QZ).
22. Only available with product certifications E7, E8, I1, I7, IA, K7, K8, KD, N1, and N7.
23. Contact an Emerson representative for availability.
24. Only available with HART 4–20 mA output (code A).
25. Only available with HART 4–20 mA output (code A) and wireless output (code X).
26. Not available with F
27. Transmitter is shipped with 316 SST conduit plug (uninstalled) in place of standard CS conduit plug.
28. The T1 option is not needed with FISCO Product Certifications; transient protection is included in the FISCO product certification codes IA, IB, and IE.
29. Not valid with alternate process connection S5.
30. The V5 option is not needed with T1 option; external ground screw assembly is included with the T1 option.
31. NACE compliant wetted materials are identified by Footnote 11.
OUNDATION Fieldbus output code F.
OUNDATION Fieldbus (code F) and wireless output (code X) or low power (code M).
1
/2 A DIN 16288 male process connection (code 2C) with range 1–4, 316 SST isolating diaphragm (code 2), silicone fill
OUNDATION Fieldbus, and W - PROFIBUS PA. Also only available with G
1
/2–14 NPT process connection (code 2B), and polymer housing
1
/2 housing thread types.
16
Emerson.com/Rosemount
March 2018
Rosemount 3051

Rosemount 3051CF Flowmeter selection guide

Rosemount 3051CF Flowmeters combine the proven Rosemount 3051 Pressure Transmitter and the latest primary element technologies. All flowmeters are fully assembled, calibrated, configured, and leak tested for out-of-the-box installation and are available with wired or wireless capabilities to meet all of your application needs.
Rosemount 3051CFA Annubar Flowmeter
Rosemount Annubar technology minimizes permanent pressure loss while delivering best in class accuracy.
Lowest material costs for large line sizes
Flo-tap enables installation without process shutdown
Realize up to 96 percent less permanent pressure loss compared to
traditional orifice plate installations
Rosemount 3051CFC Compact Conditioning Flowmeter
Rosemount Compact Conditioning technologies provide unprecedented performance with minimal straight-run requirements. Solutions include conditioning orifice plate or Rosemount Annubar primary elements.
Conditioning Orifice requires only two pipe diameters upstream and
downstream
Eliminate swirl and regular profiles resulting in more stable and
accurate flow measurement
Savings up to 55 percent when compared to a traditional orifice plate
installation can be realized
Emerson.com/Rosemount
Rosemount 3051CFP Integral Orifice Flowmeter
Rosemount Integral Orifice Flowmeters deliver highly accurate small-bore flow measurement capability with minimal installation and maintenance requirements.
Best performance for small line sizes
(15 to 40 mm)
Precision honed pipe section and tight machining tolerances deliver
higher installed performance
Reduces uncertainty by up to five percent compared to traditional
orifice plate installation
1
/2- to 11/2-in.
17
Rosemount 3051
March 2018

Rosemount 3051CFA Annubar Flowmeter

The Rosemount 3051CFA Annubar Flowmeter utilizes the T-shaped sensor design that delivers best in class accuracy and performance while meeting the needs of diverse process applications, whether it is high accuracy for precision control or high strength for severe flow applications. Main capabilities include:
Up to 1.8 percent of flow rate accuracy
Available in 2-to 96-in. (50 to 2400 mm) line
Fully assembled and leak tested for out-of-the-box installation
Power advisory can proactively detect degraded electrical loop integrity issues
(option code DA0)
LOI with straightforward menus and built-in configuration buttons
(option code M4)
Additional information:
Specifications: page 44 Certifications: page 56 Dimensional drawings: page 67
See “Specifications” on page 44 and options for more details on each configuration. Specification and selection of product materials, options, or components must be made by the purchaser of the equipment. See page 53 for more information on material selection.
Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
(1)
Model
3051CFA Rosemount Annubar Flowmeter
Product description
Measurement type
D Differential Pressure
Fluid type
L Liquid
G Gas
S Steam
Line size
020 2-in. (50 mm)
025 21/2-in. (63.5 mm)
030 3-in. (80 mm)
035 31/2-in. (89 mm)
040 4-in. (100 mm)
050 5-in. (125 mm)
060 6-in. (150 mm)
070 7-in. (175 mm)
080 8-in. (200 mm)
100 10-in. (250 mm)
120 12-in. (300 mm)
140 14-in. (350 mm)
160 16-in. (400 mm)
180 18-in. (450 mm)
200 20-in. (500 mm)
18
Emerson.com/Rosemount
March 2018
Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
240 24-in. (600 mm)
300 30-in. (750 mm)
360 36-in. (900 mm)
420 42-in. (1066 mm)
480 48-in. (1210 mm)
600 60-in. (1520 mm)
720 72-in. (1820 mm)
780 78-in (1950 mm)
840 84-in. (2100 mm)
900 90-in. (2250 mm)
960 96-in (2400 mm)
Rosemount 3051
Pipe I.D. range
C Range C from the Pipe I.D. range codes table
D Range D from the Pipe I.D. range codes table
A Range A from the Pipe I.D. range codes table
B Range B from the Pipe I.D. range codes table
E Range E from the Pipe I.D. range codes table
Z Non-standard Pipe I.D. range codes or line sizes greater than 12-in.
Pipe material/mounting assembly material
C CS (A105)
S 316 SST
0 No mounting (customer supplied)
G Chrome-moly grade F-11
N Chrome-moly grade F-22
J Chrome-moly grade F-91
Piping orientation
H Horizontal piping
D Vertical piping with downwards flow
U Vertical piping with upwards flow
Annubar type
P Pak-lok
F Flanged with opposite side support
L Flange-lok
G Gear-drive flo-tap
M Manual flo-tap
Sensor material
S 316 SST
H Alloy C-276
Sensor size
1 Sensor size 1 — line sizes 2- to 8-in. (50 to 200 mm)
2 Sensor size 2 — line sizes 6- to 96-in. (150 to 2400 mm)
3 Sensor size 3 — line sizes greater than 12-in. (300 mm)
Emerson.com/Rosemount
19
Rosemount 3051
March 2018
Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Mounting type
T1 Compression or threaded connection
A1 Class 150 RF ANSI
A3 Class 300 RF ANSI
A6 Class 600RF ANSI
D1 DN PN16 flange
D3 DN PN40 flange
D6 DN PN100 flange
(2)
A9
(2)
AF
(2)
AT
R1 Class 150 RTJ flange
R3 Class 300 RTJ flange
R6 Class 600RTJ flange
(2)
R9
(2)
RF
(2)
RT
Class 900 RF ANSI
Class 1500 RF ANSI
Class 2500 RF ANSI
Class 900 RTJ flange
Class 1500 RTJ flange
Class 2500 RTJ flange
Opposite side support or packing gland
0 No opposite side support or packing gland (required for pak-lok and flange-lok models)
Opposite side support – required for flanged models
C NPT threaded opposite support assembly – extended tip
D Welded opposite support assembly – extended tip
Packing gland – required for flo-tap models
Packing gland material Rod material Packing material
(3)
J
(3)
K
(3)
L
(3)
N
SST packing gland/cage nipple CS PTFE
SST packing gland/cage nipple SST PTFE
SST packing gland/cage nipple CS Graphite
SST packing gland/cage nipple SST Graphite
R Alloy C-276 packing gland/cage nipple SST Graphite
Isolation valve for flo-tap models
0 Not applicable or customer supplied
1 Gate valve, CS
2 Gate valve, SST
5 Ball valve, CS
6 Ball valve, SST
Temperature measurement
T Integral RTD – not available with flanged model greater than Class 600
0 No temperature sensor
R Remote Thermowell and RTD
20
Emerson.com/Rosemount
March 2018
Rosemount 3051
Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Transmitter connection platform
3 Direct-mount, Integral 3-valve manifold– not available with flanged model greater than Class 600
5 Direct -mount, 5-valve manifold – not available with flanged model greater than Class 600
7 Remote-mount NPT connections (1/2-in. NPT)
6 Direct-mount, high temperature 5-valve Manifold – not available with flanged model greater than Class 600
8 Remote-mount SW connections (1/2-in.)
Differential pressure range
1 0 to 25 in H2O (0 to 62,16 mbar)
2 0 to 250 in H2O (0 to 621,60 mbar)
3 0 to 1000 in H2O (0 to 2,48 bar)
Transmitter outpu t
(4)
A
F FOUNDATION Fieldbus Protocol
(5)
W
(6)
X
(7)
M
4–20 mA with digital signal based on HART Protocol
PROFIBUS PA Protocol
Wireless (requires wireless options and engineered polymer housing)
Low-power 1–5 Vdc with digital signal based on HART Protocol
Transmitter housing material Conduit entry size
A Aluminum
B Aluminum M20 x 1.5
J SST
E Aluminum, ultra copper low
F Aluminum, ultra copper low M20 x 1.5
K SST M20 x 1.5
(8)
P
(9)
D
(9)
M
Engineered polymer No conduit entries
Aluminum G1/2
SST G1/2
1
/2–14 NPT
1
/2–14 NPT
1
/2–14 NPT
Transmitter performance class
1 1.8 percent flow rate accuracy, 8:1 flow turndown, 5-yr. stability
Wireless options (requires wireless output code X and Engineered Polymer Housing Code P)
Wireless transmit rate, operating frequency, and protocol
WA3 User configurable transmit rate, 2.4GHz WirelessHART Protocol
Antenna and SmartPower
WP5 Internal antenna, compatible with Green Power Module (I.S. Power Module sold separately)
Options (include with selected model number)
Extended product warranty
WR3 3-year limited warranty
WR5 5-year limited warranty
Emerson.com/Rosemount
21
Rosemount 3051
Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Pressure testing
P1 Hydrostatic testing with certificate
PX Extended hydrostatic testing
(10)
March 2018
Special cleaning
P2 Cleaning for special services
PA Cleaning per ASTM G93 Level D (section 11.4)
Material testing
V1 Dye penetrant exam
Material examination
V2 Radiographic Examination
Flow calibration
W1 Flow calibration (Average K)
Special inspection
QC1 Visual and dimensional inspection with certificate
QC7 Inspection & performance certificate
Surface finish
RL Surface finish for low pipe Reynolds number in gas and steam
RH Surface finish for high pipe Reynolds number in liquid
Material traceability certification
Q8 Material Traceability Certification per EN 10474:2004 3.1
Code conformance
J2 ANSI/ASME B31.1
J3 ANSI/ASME B31.3
Materials conformance
J5 NACE MR-0175 / ISO 15156
(12)
(13)
(11)
Country certification
J6 European Pressure Directive (PED)
J1 Canadian Registration
Installed in flanged pipe spool section
H3 Class 150 flanged connection with Rosemount standard length and schedule
H4 Class 300 flanged connection with Rosemount standard length and schedule
H5 Class 600 flanged connection with Rosemount standard length and schedule
Instrument connections for remote mount options
G2 Needle valves, SST
G6 OS&Y gate valve, SST
G1 Needle valves, CS
G3 Needle valves, alloy C-276
G5 OS&Y gate valve, CS
G7 OS&Y gate valve, alloy C-276
22
Emerson.com/Rosemount
March 2018
Rosemount 3051
Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Special shipment
Y1 Mounting hardware shipped separately
Special dimensions
VM Variable mounting
VT Variable tip
VS Variable length spool section
Plantweb control functionality
(14)
A01 FOUNDATION Fieldbus control function block suite
Plantweb diagnostic functionality
(15)
DA0
D01
(14)
Power Advisory HART diagnostic
FOUNDATION Fieldbus diagnostics suite
Product certifications
E8 ATEX Flameproof, Dust
(16)
I1
IA ATEX FISCO Intrinsic Safety; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only
N1 ATEX Type n and Dust
K8 ATEX Flameproof, Intrinsic Safety, Type n, Dust (combination of E8, I1 and N1)
E5 FM Explosion-proof, Dust Ignition-proof
(17)
I5
IE FM FISCO Intrinsically Safe; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only
K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2 (combination of E5 and I5)
C6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2
(8)
I6
K6 CSA and ATEX Explosion-proof, Intrinsically Safe, and Division 2 (combination of C6, E8, and I1)
E7 IECEx Flameproof, Dust Ignition-proof
I7 IECEx Intrinsic Safety
N7 IECEx Type n
K7 IECEx Flameproof, Dust Ignition-proof, Intrinsic Safety, and Type n (combination of I7, N7, and E7)
E2 INMETRO Flameproof
I2 INMETRO Intrinsic Safety
IB INMETRO FISCO intrinsically safe; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only
K2 INMETRO Flameproof, Intrinsic Safety
E3 China Flameproof
I3 China Intrinsic Safety
KB FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2 (combination of K5 and C6)
KD CSA, FM, and ATEX Explosion-proof, Intrinsically Safe (combination of K5, C6, I1, and E8)
ATEX Intrinsic Safety and Dust
FM Intrinsically Safe, Nonincendive
CSA Intrinsically Safe
Sensor fill fluid and O-ring options
(18)
L1
Inert sensor fill fluid (silicone fill fluid is standard)
L2 Graphite-filled (PTFE) O-ring
(18)
LA
Inert sensor fill fluid and graphite-filled (PTFE) O-ring
Emerson.com/Rosemount
23
Rosemount 3051
March 2018
Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The starred offerings () represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Shipboard approvals
(18)
SBS American Bureau of Shipping
(19)
SLL
Lloyds Register (LR)
Display and interface options
(20)
M4
LCD display with LOI
M5 LCD display
Transmitter calibration certification
Q4 Calibration certificate for transmitter
Quality certification for safety
(15)
QS Prior-use certificate of FMEDA data
QT Safety certified to IEC 61508 with certificate of FMEDA
Transient protection
(18)(21)
T1 Transient terminal block
Manifold for remote mount option
F2 3-valve manifold, SST
F6 5-valve manifold, SST
F1 3-valve manifold, CS
F3 3-valve manifold, alloy C-276
F5 5-valve manifold, CS
F7 5-valve manifold, alloy C-276
Lower power output
C2 0.8–3.2 Vdc output with digital signal based on HART Protocol (available with output code M only)
Alarm levels
(15)
C4 NAMUR alarm and saturation levels, high alarm
CN NAMUR alarm and saturation levels, low alarm
CR Custom alarm and saturation signal levels, high alarm
CS Custom alarm and saturation signal levels, low alarm
CT Rosemount standard low alarm
Configuration buttons
(15)
D4
(22)
DZ
Ground screw
Analog zero and span
Digital zero trim
(18)(23)
V5 External ground screw assembly
HART Revision configuration (requires HART Protocol output code A)
(4)
HR5 Configured for HART Revision 5
HR7 Configured for HART Revision 7
Typical model number: 3051CFA D L 060 D C H P S 2 T1 0 0 0 3 2 A A 1
1. Select configuration buttons (option code D4 or DZ) or LOI (option code M4) if local configuration buttons are required.
24
Emerson.com/Rosemount
March 2018
2. Available in remote mount applications only.
3. The cage nipple is constructed of Rosemount 304 SST.
4. O pti on HR 5 co nfig ure s the HAR T out put to HA RT Re vis ion 5. Op tio n HR7 con figu res the H ART outp ut t o HA RT Rev isi on 7 . The dev ice can be field configured to HART Revision 5 or 7 if desired. HART Revision 5 is the default HART output.
5. For local addressing and configuration, M4 LOI is required.
6. Requires wireless options and engineered polymer housing. Available approvals are FM Intrinsically Safe, (option code I5), CSA Intrinsically Safe (option code I6), ATEX Intrinsic Safety (option code I1), and IECEx Intrinsic Safety (option code I7).
7. Only available with C6, E2, E5, I5, K5, KB, and E8 approval. Not available with GE, GM, SBS, DA0, M4, D4, DZ, QT, HR5, HR7, CR, CS, and CT.
8. Only available with wireless (code X).
9. Not available with Product certifications options E8, K8, E5, K5, C6, K6, E7, K7, E2, K2, E3, KB, and KD.
10. Applies to assembled flowmeter only, mounting not tested.
11. Instrument connections for remote mount options and isolation valves for flo-tap models are not included in the Material Traceability Certification.
12. Not available with transmitter connection platform 6.
13. Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
14. Only valid with F
15. Only available with 4–20 mA HART (code A).
16. Dust approval not applicable to output code X. See “Certificate: AG-0226; AG-0454; AG-0477” on page 62 for wireless approvals.
17. Nonincendive certification not provided with wireless output (code X).
18. Not available with wireless output (code X).
19. Only available with Product cer tifications E7, E8, I1, I7, IA, K7, K8, KD, N1, and N7
20. Not available with F
21. The T1 option is not needed with FISCO Product Certifications, transient protection is included with the FISCO Product Certification codes IA, IB, and IE.
22. Only available with 4–20 mA HART (output code A) and wireless (output code X).
23. The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.
OUNDATION Fieldbus (code F).
OUNDATION Fieldbus (output code F) or wireless (output code X) or low power (output code M).
Rosemount 3051
Emerson.com/Rosemount
25