With the Rosemount 3051 Pressure Transmitter, you’ll gain more control over your plant. You’ll be able to
reduce product variation and complexity, as well as your total cost of ownership by leveraging one device
across a number of pressure, level, and flow applications. You’ll have access to information you can use to
diagnose, correct, and even prevent issues. And with unparalleled reliability and experience, the Rosemount
3051 is the industry standard that will help increase efficiency and safety so your operations can remain
globally competitive.
Rosemount 3051
Setting the standard for pressure measurement
Proven best-in-class performance,
reliability and safety
More than seven million installed
Reference accuracy 0.04 percent of span
Installed total performance of 0.14 percent of span
10-year stability of 0.2 percent of URL
SIL2/3 certified (IEC 61508)
Maximize installation and application
flexibility with the coplanar platform
Improve reliability and performance with integrated DP
Flowmeters, DP Level solutions and integral manifolds
Easy installation with all solutions fully assembled, leak-tested
and calibrated
Meet your application needs with an unsurpassed offering
March 2018
Advanced functionality
Power advisory diagnostics
Detect on-scale failures caused by electrical loop issues before they impact your process
operation
This capability is safety certified for your most critical applications
Local operator interface (LOI)
Straightforward menus and built-in configuration buttons allow you commission the device in
less than a minute
Configure in hazardous-area locations without removing the transmitter cover using external
Industry leading capabilities extended to IEC 62591
®
(WirelessHART
Cost effectively implement wireless on the industry's most proven platform
Optimize safety with the industry's only intrinsically safe power module
Eliminate wiring design and construction complexities to lower costs by 40 to 60 percent
Quickly deploy new pressure, level, and flow measurements in 70 percent less time
)
Innovative, integrated DP Flowmeters
Fully assembled, configured, and leak tested for out-of-the-box installation
Reduce straight pipe requirements, lower permanent pressure loss, and achieve accurate
measurement in small line sizes
Up to 1.65 percent volumetric flow accuracy at 8:1 turndown
Proven, reliable, and innovative DP Level Technologies
Connect to virtually any process with a comprehensive offering of process connections, fill
fluids, direct mount, or capillary connections and materials
Quantify and optimize total system performance with QZ option
Operate at higher temperature and in vacuum applications
Optimize level measurement with cost efficient Rosemount Tuned-System
™
Assemblies
Instrument manifolds – quality, convenient, and easy
Designed and engineered for optimal performance with Rosemount transmitters
Save installation time and money with factory assembly
Offers a variety of styles, materials, and configurations
Emerson.com/Rosemount
3
Rosemount 3051
March 2018
Rosemount 3051C Coplanar Pressure Transmitter
Rosemount 3051C Coplanar™ Pressure Transmitters are the industry standard for differential,
gage, and absolute pressure measurement. The coplanar platform enables seamless integration
with manifolds, flow and level solutions. Capabilities include:
Power advisory can proactively detect degraded electrical loop integrity issues
(option code DA0)
LOI with straightforward menus and built-in configuration buttons (option code M4)
See Specifications and options for more details on each configuration. Specification and selection of product materials, options, or
components must be made by the purchaser of the equipment. See page 53 for more information on material selection.
Table 1. Rosemount 3051C Coplanar Pressure Transmitters Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
(1)
Model
3051CCoplanar pressure transmitter
Transmitter t ype
Measurement type
DDifferential ★
GGage★
(2)
A
Absolute
Pressure range
Differential
(Rosemount 3051CD)
1
2
3
4
5
(3)
0
–25 to 25 inH2O
(–62,16 to 62,16 mbar)
–250 to 250 inH2O
(–621,60 to 621,60 mbar)
–1000 to 1000 inH2O
(–2,48 to 2,48 bar)
–300 to 300 psi
(–20,68 to 20,68 bar)
–2000 to 2000 psi
(–137,89 to 137,89 bar)
–3 to 3 inH2O
(-7,46 to 7,46 mbar)
Gage
(Rosemount 3051CG)
–25 to 25 inH2O
(–62,16 to 62,16 mbar)
–250 to 250 inH2O
(–621,60 to 621,60 mbar)
–393 to 1000 inH2O
(–0,97 to 2,48 bar)
–14.2 to 300 psi
(–0,97 to 20,68 bar)
–14.2 to 2000 psi
(–0,97 to 137,89 bar)
N/AN/A
Absolute
(Rosemount 3051CA)
0 to 30 psia
(0 to 2,06 bar)
0 to 150 psia
(0 to 10,34 bar)
0 to 800 psia
(0 to 55,15 bar)
0 to 4000 psia
(0 to 275,79 bar)
N/A★
Transmitter output
(4)
A
FFOUNDATION™ Fieldbus Protocol★
(5)
W
(6)
X
(7)
M
4–20 mA with digital signal based on HART® Protocol★
PROFIBUS® PA Protocol★
Wireless (requires wireless options and engineered polymer housing)★
Low-power, 1–5 Vdc with digital signal based on HART Protocol
★
★
★
★
4
Emerson.com/Rosemount
March 2018
Rosemount 3051
Table 1. Rosemount 3051C Coplanar Pressure Transmitters Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Materials of construction
Process flange typeFlange materialDrain/vent
2Coplanar Stainless steel (SST)SST★
(8)
3
Coplanar Cast C-276Alloy C-276★
4Coplanar Alloy 400Alloy 400/K-500★
5Coplanar Plated carbon steel (CS)SST★
(8)
7
(8)
8
Coplanar SSTAlloy C-276★
Coplanar Plated CSAlloy C-276★
0Alternate process connection★
Isolating diaphragm
(8)
2
(8)
3
(9)
4
(9)
5
(9)
6
(9)
7
316L SST★
Alloy C-276★
Alloy 400
Tantalum (available on Rosemount 3051CD and CG, ranges 2–5 only; not available on Rosemount 3051CA)
Gold-plated alloy 400 (use in combination with O-ring option code B)
Gold-plated 316 SST
O-ring
AGlass-filled PTFE★
BGraphite-filled PTFE★
Sensor fill fluid
1Silicone★
(9)
2
Inert (differential and gage only)★
Housing materialConduit entry size
AAluminum
BAluminumM20 x 1.5★
EAluminum, ultra low copper
FAluminum, ultra low copperM20 x 1.5★
JSST
KSSTM20 x 1.5★
(10)
P
(11)
D
(11)
M
Engineered polymerNo conduit entries★
AluminumG1/2
SSTG1/2
1
/2–14 NPT★
1
/2–14 NPT★
1
/2–14 NPT★
Wireless options (requires wireless output code X and engineered polymer housing code P)
Wireless transmit rate, operating frequency, and protocol
WP5Internal antenna, compatible with Green Power Module (I.S. Power Module sold separately)★
™
Emerson.com/Rosemount
5
Rosemount 3051
March 2018
Table 1. Rosemount 3051C Coplanar Pressure Transmitters Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Options (include with selected model number)
Extended product warranty
WR33-year limited warranty★
WR55-year limited warranty★
Plantweb™ control functionality
A01FOUNDATION Fieldbus control function block suite★
Plantweb diagnostic functionality
(13)
DA0
(12)
D01
Alternate flange
Power Advisory HART Diagnostic★
FOUNDATION Fieldbus Diagnostics Suite★
(14)
H2Traditional flange, 316 SST, SST drain/vent★
(8)
H3
Traditional flange, alloy C, alloy C-276 drain/vent★
Assemble to Rosemount Annubar™ or Rosemount 1195 Integral Orifice★
(16)
Assemble to one Rosemount 1199 seal★
Assemble to two Rosemount 1199 seals★
(20)
(12)
(15)(16)
6
Emerson.com/Rosemount
March 2018
Rosemount 3051
Table 1. Rosemount 3051C Coplanar Pressure Transmitters Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
BATraditional flange bracket, B1, all SST★
BCTraditional flange bracket, B3, all SST★
Product certifications
E8ATEX Flameproof and Dust Certification★
(21)
I1
IAATEX FISCO Intrinsic Safety; for FOUNDATION Fieldbus or PROFIBUS PA Protocol only★
N1ATEX Type n Certification and Dust ★
K8ATEX Flameproof, Intrinsic Safety, Type n, Dust (combination of E8, I1, and N1)★
(22)
E4
E5FM Explosion-proof, Dust Ignition-Proof★
(23)
I5
IEFM FISCO Intrinsically Safe; for FOUNDATION Fieldbus or PROFIBUS PA Protocol only★
K5FM Explosion-proof, Dust Ignition-Proof, Intrinsically Safe, and Division 2★
C6CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2 ★
(10)
I6
K6CSA and ATEX Explosion-proof, Intrinsically Safe, and Division 2 (combination of C6, E8, and I1)★
E7IECEx Flameproof, Dust Ignition-proof ★
I7IECEx Intrinsic Safety ★
N7IECEx Type n Certification★
K7IECEx Flame-proof, Dust Ignition-proof, Intrinsic Safety, and Type n (combination of I7, N7, and E7)★
E2INMETRO Flameproof★
I2INMETRO Intrinsic Safety★
IBINMETRO FISCO intrinsically safe; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only★
K2INMETRO Flameproof, Intrinsic Safety★
E3China Flameproof★
I3China Intrinsic Safety★
N3China Type n★
EMTechnical Regulations Customs Union (EAC) Flameproof★
IMTechnical Regulations Customs Union (EAC) Intrinsic Safety★
KMTechnical Regulations Customs Union (EAC) Flameproof and Intrinsic Safety★
KBFM and CSA Explosion-proof, Dust Ignition Proof, Intrinsically Safe, and Division 2 (combination of K5 and C6) ★
KDFM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of K5, C6, I1, and E8)★
Drinking water approval
DWNSF drinking water approval★
Shipboard approvals
SBSAmerican Bureau of Shipping★
(25)
SBV
SDNDet Norske Veritas★
(25)
SLL
Custody transfer
C5
ATEX Intrinsic Safety and Dust★
TIIS Flame-proof ★
FM Intrinsically Safe, Nonincendive★
CSA Intrinsic Safety★
(24)
(9)
Bureau Veritas (BV)★
Lloyds Register (LR)★
(13)
Measurement Canada Accuracy Approval (limited availability depending on transmitter type and range;
™
contact an Emerson
representative)
★
Emerson.com/Rosemount
7
Rosemount 3051
March 2018
Table 1. Rosemount 3051C Coplanar Pressure Transmitters Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Bolting material
L4Austenitic 316 SST bolts★
L5ASTM A 193, grade B7M bolts★
L6Alloy K-500 bolts★
Display and interface options
(26)
M4
LCD display with LOI ★
M5LCD display★
Calibration certificate
Q4Calibration Certificate★
(27)
QG
Calibration Certificate and GOST Verification Certificate★
QPCalibration certification and tamper evident seal★
Material traceability certification
Q8Material Traceability Certification per EN 10204 3.1★
Quality certification for safety
QSPrior-use certificate of FMEDA data★
QTSafety certified to IEC 61508 with certificate of FMEDA★
(13)
Configuration buttons
(13)
D4
(28)
DZ
Transient protection
Analog zero and span ★
Digital zero trim★
(9)(29)
T1Transient protection terminal block★
Software configuration
(28)
Custom Software Configuration
C1
(For wired, see the Rosemount 3051 Configuration Data Sheet
For wireless, see the Rosemount 3051 Wireless Configuration Data Sheet.
.
)
Low power output
C20.8–3.2 Vdc output with digital signal based on HART Protocol (available with output code M only)★
Gage pressure calibration
C3Gage calibration (Rosemount 3051ca4 only)★
Alarm levels
C4Analog output levels compliant with NAMUR recommendation NE 43, alarm high★
CNAnalog output levels compliant with NAMUR recommendation NE 43, alarm low★
CR
CS
CTRosemount standard low alarm★
(13)
Custom alarm and saturation signal levels, high alarm
(requires C1 and Rosemount 3051 Configuration Data Sheet
Custom alarm and saturation signal levels, low alarm
(requires C1 and Rosemount 3051 Configuration Data Sheet
)
)
★
★
★
Pressure testing
P1Hydrostatic testing with certificate
8
Emerson.com/Rosemount
March 2018
Rosemount 3051
Table 1. Rosemount 3051C Coplanar Pressure Transmitters Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Q16Surface finish certification for sanitary remote seals★
Toolkit total system performance reports
QZRemote seal system performance calculation report★
Conduit electrical connector
(9)
GEM12, 4-pin, male connector (eurofast®)★
GMA size Mini, 4-pin, male connector (minifast®)★
NACE® certificate
(34)
Q15Certificate of Compliance to NACE MR0175/ISO 15156 for wetted materials★
Q25Certificate of Compliance to NACE MR0103 for wetted materials★
Cold temperature
(35)
BR5–58 °F (–50 °C) cold temperature★
BR6–76 °F (–60 °C) cold temperature★
HART Revision configuration (requires HART output code A)
(4)
HR5Configured for HART Revision 5★
HR7Configured for HART Revision 7★
Typical model number: 3051CD 2 A 2 2 A 1 A B4
1.Select configuration buttons (option code D4 or DZ) or LOI (option code M4) if local configuration buttons are required.
2.If ordered with Wireless output code X, only range 1–4, 316L SST diaphragm material (code 2), silicone fill fluid (code 1) and wireless housing
(code P) are available.
3.Rosemount 3051CD0 is only available with output code A and X. For output code A, only process flange code 0 (alternate flange H2, H7, HJ, or HK), isolating
diaphragm code 2, O ring code A and bolting option L4 are available. For output code X, only process flange code 0 (alternate flange H2), isolating diaphragm code
2, O ring code A and bolting option L4 are available.
Emerson.com/Rosemount
9
Rosemount 3051
4.O pti on HR 5 co nfig ure s the HAR T out put to HA RT Re vis ion 5 . Op tion HR7 conf igu res t he H ART outp ut to HAR T Rev isio n 7. The devi ce can be field configured to H ART
Revision 5 or 7 if desired. HART Revision 5 is the default HART output.
5.For local addressing and configuration, M4 LOI is required.
7.Only available with C6, E2, E5, I5, K5, KB, and E8 product certifications. Not available with GE, GM, SBS, DA0, M4, D4, DZ, QT, HR5, HR7, CR, CS, and CT.
8.Materials of Construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to
certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
9.Not available with wireless output (code X).
10.Only available with wireless output (code X).
11.Not available with Product certifications options E8, K8, E5, K5, C6, K6, E7, K7, E2, K2, E3, KB, and KD.
12.Only valid with F
13.Only available with HART 4–20 mA output (code A).
14.Requires 0 code in materials of construction for alternate process connection.
15.Not valid with option code P9 for 4500 psi static pressure.
16.“Assemble-to” items are specified separately and require a completed model number.
17.Process flange limited to coplanar (option codes 2, 3, 5, 7, 8) or traditional (option codes H2, H3, H7).
18.Not valid with option code D9 for RC
19.Not valid for option codes DF and D9 for adapters.
20.Panel mounting bolts are not supplied.
21.Dust approval not applicable to output code X. See “Certificate: AG-0226; AG-0454; AG-0477” on page 62 for wireless approvals.
22.Only available with output codes A - 4–20mA HART, F - F
23. Nonincendive certification not provided with Wireless output (code X).
24.Not available with Alloy C-276 isolator (code 3), tantalum isolator (code 5), all cast C-276 flanges, all plated carbon steel (CS) flanges, all DIN flanges, all Level flanges,
assemble-to manifolds (codes S5 and S6), assemble-to seals (codes S1 and S2), assemble-to primary elements (codes S3 and S4), surface finish certification (code
Q16), and remote seal system report (code QZ).
25. Only available with product certifications E7, E8, I1, I7, IA, K7, K8, KD, N1, and N7
26.Not available with F
27.Contact an Emerson representative for availability.
28.Only available with HART 4–20 mA output (code A) and wireless output (code X)
29.The T1 option is not needed with FISCO Product Certifications; transient protection is included in the FISCO product certification codes IA, IB, and IE.
30.Not valid with alternate process connection options S3, S4, S5, and S6.
31.Transmitter is shipped with a 316 SST conduit plug (uninstalled) in place of standard CS conduit plug.
32.Not available with alternate process connection; DIN flanges and level flanges.
33.The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.
34.NACE compliant wetted materials are identified by Footnote 8.
35.Only available on pressure ranges 1–5, with silicone sensor fill fluid and SST or C-276 isolating diaphragms.
OUNDATION Fieldbus output (code F).
1
/2 adapters.
OUNDATION Fieldbus, and W - PROFIBUS PA. Also only available with G
OUNDATION Fieldbus (code F), wireless (code X), or low power (code M).
1
/2 housing thread types.
March 2018
10
Emerson.com/Rosemount
March 2018
Rosemount 3051
Rosemount 3051T In-Line Pressure Transmitter
Rosemount 3051T In-Line Pressure Transmitters are the industry standard for gage and
absolute pressure measurement. The in-line, compact design allows the transmitter to
be connected directly to a process for quick, easy and cost effective installation.
Capabilities include:
Power advisory can proactively detect degraded electrical loop integrity issues
(option code DA0)
LOI with straightforward menus and built-in configuration buttons (option code M4)
See “Specifications” on page 44 and options for more details on each configuration. Specification and selection of product materials,
options, or components must be made by the purchaser of the equipment. See page 53 for more information on material selection.
Table 2. Rosemount 3051T In-Line Pressure Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
(1)
Model
Transmitter type
3051TIn-line pressure transmitter
Pressure type
GGage★
(2)
A
Absolute★
Pressure range
Gage (Rosemount 3051TG)
1–14.7 to 30 psi (–1,01 to 2,06 bar)0 to 30 psia (0 to 2,06 bar)★
2–14.7 to 150 psi (–1,01 to 10,34 bar)0 to 150 psia (0 to 10,34 bar)★
3–14.7 to 800 psi (–1,01 to 55,15 bar)0 to 800 psia (0 to 55,15 bar)★
4–14.7 to 4000 psi (–1,01 to 275,79 bar)0 to 4000 psia (0 to 275,79 bar)★
5–14.7 to 10000 psi (–1,01 to 689,47 bar)0 to 10000 psia (0 to 689,47 bar)★
(4)
6
–14.7 to 20000 psi (–1,01 to 1378,95 bar)0 to 20000 psia (0 to 1378,95 bar)
(3)
Absolute (Rosemount 3051TA)
Transmitter outpu t
(5)
A
FFOUNDATION Fieldbus Protocol★
(6)
W
(7)
X
(8)
M
4–20 mA with digital signal based on HART Protocol★
PROFIBUS PA Protocol★
Wireless (requires wireless options and engineered polymer housing)★
Low-power 1–5 Vdc with digital signal based on HART Protocol
Emerson.com/Rosemount
11
Rosemount 3051
March 2018
Table 2. Rosemount 3051T In-Line Pressure Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Process connection style
2B
(9)
2C
(10)
2F
(11)
61
Isolating diaphragm
2316L SST316L SST★
3Alloy C-276Alloy C-276★
7Gold-plated 316 SST316L SST
1
/2–14 NPT female (range 1–5 only)★
G1/2 A DIN 16288 male (range 1–4 only)★
Coned and threaded, compatible with autoclave type F-250-C (range 5–6 only)
Non-threaded Instrument flange (range 1–4 only)
(12)
Process connection wetted parts material
Sensor fill fluid
1Silicone★
(11)
2
Inert ★
Housing materialConduit entry size
AAluminum
BAluminumM20 x 1.5 ★
EAluminum, ultra low copper
FAluminum, ultra low copperM20 x 1.5
JSST
KSSTM20 x 1.5 ★
(13)
P
(14)
D
(14)
M
Engineered polymerNo conduit entries★
AluminumG1/2
SSTG1/2
1
/2–14 NPT★
1
/2–14 NPT
1
/2–14 NPT★
Wireless options(requires wireless output code X and engineered polymer housing code P)
Wireless transmit rate, operating frequency, and protocol
WP5Internal antenna, compatible with Green Power Module (I.S. Power Module sold separately)★
Options (include with selected model number)
Extended product warranty
WR33-year limited warranty★
WR55-year limited warranty★
12
Emerson.com/Rosemount
March 2018
Rosemount 3051
Table 2. Rosemount 3051T In-Line Pressure Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Plantweb control functionality
(15)
A01FOUNDATION Fieldbus control function block suite★
Plantweb diagnostic functionality
(24)
DA0
(15)
D01
Integral assembly
S5Assemble to Rosemount 306 Integral Manifold ★
Diaphragm seal assemblies
S1Assemble to one Rosemount 1199 seal★
Mounting bracket
B4Bracket for 2-in. pipe or panel mounting, all SST★
Power Advisory HART diagnostic★
FOUNDATION Fieldbus diagnostics suite★
(16)
(16)
(17)
Product certifications
E8ATEX Flameproof and Dust Certification★
(18)
I1
IAATEX Intrinsic Safety for FISCO; for F
N1ATEX Type n Certification and Dust★
K8ATEX Flame-proof, Intrinsic Safety, Type n, Dust (combination of E8, I1, and N1)★
(19)
E4
E5FM Explosion-proof, Dust Ignition-proof ★
(20)
I5
IEFM FISCO Intrinsically Safe; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only★
K5FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2★
C6CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2★
(13)
I6
K6CSA and ATEX Explosion-proof, Intrinsically Safe, and Division 2 (combination of C6, E8, and I1)★
E7IECEx Flameproof, Dust Ignition-proof ★
I7IECEx Intrinsic Safety ★
N7IECEx Type n Certification★
ATEX Intrinsic Safety and Dust ★
OUNDATION Fieldbus or PROFIBUS PA Protocols only★
TIIS Flameproof★
FM Intrinsically Safe, Nonincendive★
CSA Intrinsic Safety★
K7IECEx Flameproof, Dust Ignition-proof, Intrinsic Safety, and Type n (combination of I7, N7, and E7)★
E2INMETRO Flameproof★
I2INMETRO Intrinsic Safety★
IBINMETRO FISCO intrinsically safe; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only★
K2INMETRO Flameproof, Intrinsic Safety★
E3China Flameproof★
Emerson.com/Rosemount
13
Rosemount 3051
March 2018
Table 2. Rosemount 3051T In-Line Pressure Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
I3China Intrinsic Safety★
N3China Type n★
EMTechnical Regulations Customs Union (EAC) Flameproof★
IMTechnical Regulations Customs Union (EAC) Intrinsic Safety★
KMTechnical Regulations Customs Union (EAC) Flameproof and Intrinsic Safety★
KBFM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2 (combination of K5 and C6)★
KDFM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of K5, C6, I1, and E8)★
Drinking water approval
(21)
DWNSF drinking water approval★
Shipboard approvals
(11)
SBSAmerican Bureau of Shipping★
(22)
SBV
Bureau Veritas (BV)★
SDNDet Norske Veritas★
(22)
SLL
Lloyds Register (LR)★
Custody transfer
C5
Measurement Canada Accuracy Approval
(Limited availability depending on transmitter type and range. Contact an Emerson representative.)
Calibration certification
Q4Calibration Certificate★
(23)
QG
Calibration Certificate and GOST Verification Certificate★
QPCalibration Certification and tamper evident seal★
Material traceability certification
Q8Material Traceability Certification per EN 10204 3.1★
Quality certification for safety
(24)
QSPrior-use certificate of FMEDA Data★
QTSafety certified to IEC 61508 with certificate of FMEDA★
Configuration buttons
(24)
D4
DZ
(25)
Analog zero and span ★
Digital zero trim ★
Display and interface options
(26)
M4
LCD display with LOI ★
★
M5LCD display ★
Wireless SST sensor module
(13)
WSMWireless SST sensor module★
14
Emerson.com/Rosemount
March 2018
Rosemount 3051
Table 2. Rosemount 3051T In-Line Pressure Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Conduit plug
(11)(27)
DO316 SST conduit plug★
Transient terminal block
(11)(28)
T1Transient protection terminal block ★
Software configuration
(25)
Custom Software Configuration
C1
(For wired, see the Rosemount 3051 Configuration Data Sheet.
For wireless, see the Rosemount 3051 Wireless Configuration Data Sheet.
★
)
Low power output
C20.8–3.2 Vdc output with digital signal based on HART Protocol (available with output code M only)
Alarm levels
C4Analog output levels compliant with NAMUR recommendation NE 43, alarm high★
CNAnalog output levels compliant with NAMUR recommendation NE 43, low alarm ★
CR
CS
(24)
Custom alarm and saturation signal levels, high alarm
(requires C1 and Rosemount 3051 Configuration Data Sheet
Custom alarm and saturation signal levels, low alarm
(requires C1 and Rosemount 3051 Configuration Data Sheet)
)
★
★
CTRosemount standard low alarm★
Pressure testing
P1Hydrostatic testing with certificate
Cleaning process area
(29)
P2Cleaning for special service
P3Cleaning for <1 PPM chlorine/fluorine
Ground screw
(11)(30)
V5External ground screw assembly★
Surface finish
Q16Surface finish certification for sanitary remote seals★
Toolkit total system performance reports
QZRemote seal system performance calculation report★
Conduit electrical connector
GEM12, 4-pin, male connector (eurofast)★
GMA size mini, 4-pin, male connector (minifast)★
NACE certificate
(31)
(11)
Q15Certificate of Compliance to NACE MR0175/ISO15156 for wetted materials★
Q25Certificate of Compliance to NACE MR0103 for wetted materials★
Emerson.com/Rosemount
15
Rosemount 3051
March 2018
Table 2. Rosemount 3051T In-Line Pressure Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Cold temperature
BR5–50 °F (–58 °C) cold temperature★
BR6–76 °F (–60 °C) cold temperature★
HART Revision configuration (requires HART output code A)
(5)
HR5Configured for HART Revision 5★
HR7Configured for HART Revision 7★
Typical model number: 3051T G 5 F 2A 2 1 A B4
1.Select configuration buttons (option code D4 or DZ) or LOI (option code M4) if local configuration buttons are required.
2.Wireless output (code X) only available in absolute measurement type (code A) in range 1–5 with
(code P). Wireless output and range 6 is only available with coned and threaded process connection (code 2F) and polymer housing.
3.Rosemount 3051TG lower range limit varies with atmospheric pressure.
4.Not available with PROFIBUS PA or low power 1–5 Vdc transmitter output (option code W or M), inert sensor fill fluid (option code 2), NSW drinking water approval
(option code DW), or assemble to manifolds (option code S5).
5.O pti on HR 5 co nfig ure s the HAR T out put to H ART Re vis ion 5. O ptio n HR 7 con figu res the HART out put t o HA RT Re visi on 7 . Th e dev ice can be field configured to HART
Revision 5 or 7 if desired. HART Revision 5 is the default HART output.
6.For local addressing and configuration, M4 LOI is required.
7.Requires wireless options and engineered polymer housing. Available approvals are FM Intrinsically Safe, (option code I5), CSA Intrinsically Safe (option code I6),
ATEX Intrinsic Safety (option code I1), IECEx Intrinsic Safety (option code I7), and EAC Intrinsic Safety (option code IM).
8.Only available with C6, E2, E5, I5, K5, KB, and E8 product certifications. Not available with GE, GM, SBS, DA0, M4, D4, DZ, QT, HR5, HR7, CR, CS, and CT.
9.Wireless output (code X) only available in G
fluid (code 1) and housing (code P).
10.Not available with wireless output for range 5.
11.Not available with wireless (output code X).
12.Materials of construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to
certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
13.Only available with wireless (output code X).
14.Not available with Product certifications options E8, K8, E5, K5, C6, K6, E7, K7, E2, K2, E3, KB, and KD.
15.Only valid with F
16.“Assemble-to” items are specified separately and require a completed model number.
17.Panel mounting bolts are not supplied.
18.Dust approval not applicable to output code X. See “Certificate: AG-0226; AG-0454; AG-0477” on page 62 for wireless approvals.
19.Only available with output codes A - 4–20mA HART, F - F
20. Nonincendive certification not provided with wireless output (code X).
21.Not available with Alloy C-276 isolator (option code 3), assemble-to manifolds (option code S5), assemble-to seals (option code S1), surface finish certification
(option code Q16), and remote seal system report (option code QZ).
22.Only available with product certifications E7, E8, I1, I7, IA, K7, K8, KD, N1, and N7.
23.Contact an Emerson representative for availability.
24.Only available with HART 4–20 mA output (code A).
25.Only available with HART 4–20 mA output (code A) and wireless output (code X).
26.Not available with F
27.Transmitter is shipped with 316 SST conduit plug (uninstalled) in place of standard CS conduit plug.
28.The T1 option is not needed with FISCO Product Certifications; transient protection is included in the FISCO product certification codes IA, IB, and IE.
29.Not valid with alternate process connection S5.
30.The V5 option is not needed with T1 option; external ground screw assembly is included with the T1 option.
31.NACE compliant wetted materials are identified by Footnote 11.
OUNDATION Fieldbus output code F.
OUNDATION Fieldbus (code F) and wireless output (code X) or low power (code M).
1
/2 A DIN 16288 male process connection (code 2C) with range 1–4, 316 SST isolating diaphragm (code 2), silicone fill
OUNDATION Fieldbus, and W - PROFIBUS PA. Also only available with G
1
/2–14 NPT process connection (code 2B), and polymer housing
1
/2 housing thread types.
16
Emerson.com/Rosemount
March 2018
Rosemount 3051
Rosemount 3051CF Flowmeter selection guide
Rosemount 3051CF Flowmeters combine the proven Rosemount 3051 Pressure Transmitter and the latest primary element
technologies. All flowmeters are fully assembled, calibrated, configured, and leak tested for out-of-the-box installation and are
available with wired or wireless capabilities to meet all of your application needs.
Rosemount 3051CFA Annubar Flowmeter
Rosemount Annubar technology minimizes permanent pressure loss
while delivering best in class accuracy.
Lowest material costs for large line sizes
Flo-tap enables installation without process shutdown
Realize up to 96 percent less permanent pressure loss compared to
traditional orifice plate installations
Rosemount 3051CFC Compact Conditioning Flowmeter
Rosemount Compact Conditioning technologies provide
unprecedented performance with minimal straight-run requirements.
Solutions include conditioning orifice plate or Rosemount Annubar
primary elements.
Conditioning Orifice requires only two pipe diameters upstream and
downstream
Eliminate swirl and regular profiles resulting in more stable and
accurate flow measurement
Savings up to 55 percent when compared to a traditional orifice plate
installation can be realized
Emerson.com/Rosemount
Rosemount 3051CFP Integral Orifice Flowmeter
Rosemount Integral Orifice Flowmeters deliver highly accurate
small-bore flow measurement capability with minimal installation and
maintenance requirements.
Best performance for small line sizes
(15 to 40 mm)
Precision honed pipe section and tight machining tolerances deliver
higher installed performance
Reduces uncertainty by up to five percent compared to traditional
orifice plate installation
1
/2- to 11/2-in.
17
Rosemount 3051
March 2018
Rosemount 3051CFA Annubar Flowmeter
The Rosemount 3051CFA Annubar Flowmeter utilizes the T-shaped sensor design that
delivers best in class accuracy and performance while meeting the needs of diverse
process applications, whether it is high accuracy for precision control or high strength
for severe flow applications. Main capabilities include:
Up to 1.8 percent of flow rate accuracy
Available in 2-to 96-in. (50 to 2400 mm) line
Fully assembled and leak tested for out-of-the-box installation
Power advisory can proactively detect degraded electrical loop integrity issues
(option code DA0)
LOI with straightforward menus and built-in configuration buttons
See “Specifications” on page 44 and options for more details on each configuration. Specification and selection of product materials,
options, or components must be made by the purchaser of the equipment. See page 53 for more information on material selection.
Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
(1)
Model
3051CFARosemount Annubar Flowmeter
Product description
Measurement type
DDifferential Pressure ★
Fluid type
LLiquid★
GGas★
SSteam★
Line size
0202-in. (50 mm)★
02521/2-in. (63.5 mm)★
0303-in. (80 mm)★
03531/2-in. (89 mm)★
0404-in. (100 mm)★
0505-in. (125 mm)★
0606-in. (150 mm)★
0707-in. (175 mm)★
0808-in. (200 mm)★
10010-in. (250 mm)★
12012-in. (300 mm)★
14014-in. (350 mm)
16016-in. (400 mm)
18018-in. (450 mm)
20020-in. (500 mm)
18
Emerson.com/Rosemount
March 2018
Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
24024-in. (600 mm)
30030-in. (750 mm)
36036-in. (900 mm)
42042-in. (1066 mm)
48048-in. (1210 mm)
60060-in. (1520 mm)
72072-in. (1820 mm)
78078-in (1950 mm)
84084-in. (2100 mm)
90090-in. (2250 mm)
96096-in (2400 mm)
Rosemount 3051
Pipe I.D. range
CRange C from the Pipe I.D. range codes table★
DRange D from the Pipe I.D. range codes table★
ARange A from the Pipe I.D. range codes table
BRange B from the Pipe I.D. range codes table
ERange E from the Pipe I.D. range codes table
ZNon-standard Pipe I.D. range codes or line sizes greater than 12-in.
Pipe material/mounting assembly material
CCS (A105)★
S316 SST★
0No mounting (customer supplied) ★
GChrome-moly grade F-11
NChrome-moly grade F-22
JChrome-moly grade F-91
Piping orientation
HHorizontal piping★
DVertical piping with downwards flow★
U Vertical piping with upwards flow★
Annubar type
PPak-lok★
FFlanged with opposite side support★
LFlange-lok
GGear-drive flo-tap
MManual flo-tap
Sensor material
S316 SST★
HAlloy C-276
Sensor size
1Sensor size 1 — line sizes 2- to 8-in. (50 to 200 mm)★
2Sensor size 2 — line sizes 6- to 96-in. (150 to 2400 mm)★
3Sensor size 3 — line sizes greater than 12-in. (300 mm)★
Emerson.com/Rosemount
19
Rosemount 3051
March 2018
Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Mounting type
T1Compression or threaded connection★
A1Class 150 RF ANSI★
A3Class 300 RF ANSI★
A6Class 600RF ANSI★
D1DN PN16 flange★
D3DN PN40 flange★
D6DN PN100 flange★
(2)
A9
(2)
AF
(2)
AT
R1Class 150 RTJ flange
R3Class 300 RTJ flange
R6Class 600RTJ flange
(2)
R9
(2)
RF
(2)
RT
Class 900 RF ANSI
Class 1500 RF ANSI
Class 2500 RF ANSI
Class 900 RTJ flange
Class 1500 RTJ flange
Class 2500 RTJ flange
Opposite side support or packing gland
0No opposite side support or packing gland (required for pak-lok and flange-lok models)★
Opposite side support – required for flanged models
CNPT threaded opposite support assembly – extended tip★
DWelded opposite support assembly – extended tip★
Packing gland – required for flo-tap models
Packing gland materialRod materialPacking material
(3)
J
(3)
K
(3)
L
(3)
N
SST packing gland/cage nippleCSPTFE
SST packing gland/cage nippleSSTPTFE
SST packing gland/cage nippleCSGraphite
SST packing gland/cage nippleSSTGraphite
RAlloy C-276 packing gland/cage nippleSSTGraphite
Isolation valve for flo-tap models
0Not applicable or customer supplied★
1Gate valve, CS
2Gate valve, SST
5Ball valve, CS
6Ball valve, SST
Temperature measurement
TIntegral RTD – not available with flanged model greater than Class 600★
0No temperature sensor★
RRemote Thermowell and RTD
20
Emerson.com/Rosemount
March 2018
Rosemount 3051
Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Transmitter connection platform
3Direct-mount, Integral 3-valve manifold– not available with flanged model greater than Class 600★
5Direct -mount, 5-valve manifold – not available with flanged model greater than Class 600★
7Remote-mount NPT connections (1/2-in. NPT)★
6Direct-mount, high temperature 5-valve Manifold – not available with flanged model greater than Class 600
8Remote-mount SW connections (1/2-in.)
Differential pressure range
10 to 25 in H2O (0 to 62,16 mbar)★
20 to 250 in H2O (0 to 621,60 mbar)★
30 to 1000 in H2O (0 to 2,48 bar)★
Transmitter outpu t
(4)
A
FFOUNDATION Fieldbus Protocol★
(5)
W
(6)
X
(7)
M
4–20 mA with digital signal based on HART Protocol★
PROFIBUS PA Protocol★
Wireless (requires wireless options and engineered polymer housing)★
Low-power 1–5 Vdc with digital signal based on HART Protocol
WP5Internal antenna, compatible with Green Power Module (I.S. Power Module sold separately)★
Options(include with selected model number)
Extended product warranty
WR33-year limited warranty★
WR55-year limited warranty★
Emerson.com/Rosemount
21
Rosemount 3051
Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Pressure testing
P1Hydrostatic testing with certificate
PXExtended hydrostatic testing
(10)
March 2018
Special cleaning
P2Cleaning for special services
PACleaning per ASTM G93 Level D (section 11.4)
Material testing
V1Dye penetrant exam
Material examination
V2Radiographic Examination
Flow calibration
W1Flow calibration (Average K)
Special inspection
QC1Visual and dimensional inspection with certificate★
QC7Inspection & performance certificate★
Surface finish
RLSurface finish for low pipe Reynolds number in gas and steam★
RHSurface finish for high pipe Reynolds number in liquid★
Material traceability certification
Q8Material Traceability Certification per EN 10474:2004 3.1★
Code conformance
J2 ANSI/ASME B31.1
J3ANSI/ASME B31.3
Materials conformance
J5NACE MR-0175 / ISO 15156
(12)
(13)
(11)
Country certification
J6European Pressure Directive (PED)★
J1Canadian Registration
Installed in flanged pipe spool section
H3Class 150 flanged connection with Rosemount standard length and schedule
H4Class 300 flanged connection with Rosemount standard length and schedule
H5Class 600 flanged connection with Rosemount standard length and schedule
Instrument connections for remote mount options
G2Needle valves, SST★
G6OS&Y gate valve, SST★
G1Needle valves, CS
G3Needle valves, alloy C-276
G5OS&Y gate valve, CS
G7OS&Y gate valve, alloy C-276
22
Emerson.com/Rosemount
March 2018
Rosemount 3051
Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Special shipment
Y1Mounting hardware shipped separately★
Special dimensions
VMVariable mounting
VTVariable tip
VSVariable length spool section
Plantweb control functionality
(14)
A01FOUNDATION Fieldbus control function block suite★
Plantweb diagnostic functionality
(15)
DA0
D01
(14)
Power Advisory HART diagnostic★
FOUNDATION Fieldbus diagnostics suite★
Product certifications
E8ATEX Flameproof, Dust★
(16)
I1
IAATEX FISCO Intrinsic Safety; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only★
N1ATEX Type n and Dust★
K8ATEX Flameproof, Intrinsic Safety, Type n, Dust (combination of E8, I1 and N1)★
E5FM Explosion-proof, Dust Ignition-proof★
(17)
I5
IEFM FISCO Intrinsically Safe; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only★
K5FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2 (combination of E5 and I5)★
C6CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2★
(8)
I6
K6CSA and ATEX Explosion-proof, Intrinsically Safe, and Division 2 (combination of C6, E8, and I1)★
E7IECEx Flameproof, Dust Ignition-proof★
I7IECEx Intrinsic Safety ★
N7IECEx Type n ★
K7IECEx Flameproof, Dust Ignition-proof, Intrinsic Safety, and Type n (combination of I7, N7, and E7)★
E2INMETRO Flameproof★
I2INMETRO Intrinsic Safety★
IBINMETRO FISCO intrinsically safe; for FOUNDATION Fieldbus or PROFIBUS PA Protocols only★
K2INMETRO Flameproof, Intrinsic Safety★
E3China Flameproof★
I3China Intrinsic Safety★
KBFM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2 (combination of K5 and C6)★
KDCSA, FM, and ATEX Explosion-proof, Intrinsically Safe (combination of K5, C6, I1, and E8)★
ATEX Intrinsic Safety and Dust★
FM Intrinsically Safe, Nonincendive★
CSA Intrinsically Safe★
Sensor fill fluid and O-ring options
(18)
L1
Inert sensor fill fluid (silicone fill fluid is standard)★
L2Graphite-filled (PTFE) O-ring★
(18)
LA
Inert sensor fill fluid and graphite-filled (PTFE) O-ring★
Emerson.com/Rosemount
23
Rosemount 3051
March 2018
Table 3. Rosemount 3051CFA Annubar Flowmeter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Shipboard approvals
(18)
SBSAmerican Bureau of Shipping★
(19)
SLL
Lloyds Register (LR)
Display and interface options
(20)
M4
LCD display with LOI ★
M5LCD display★
Transmitter calibration certification
Q4Calibration certificate for transmitter★
Quality certification for safety
(15)
QSPrior-use certificate of FMEDA data★
QTSafety certified to IEC 61508 with certificate of FMEDA ★
Transient protection
(18)(21)
T1Transient terminal block★
Manifold for remote mount option
F23-valve manifold, SST★
F65-valve manifold, SST★
F13-valve manifold, CS
F33-valve manifold, alloy C-276
F55-valve manifold, CS
F75-valve manifold, alloy C-276
Lower power output
C20.8–3.2 Vdc output with digital signal based on HART Protocol (available with output code M only)
Alarm levels
(15)
C4NAMUR alarm and saturation levels, high alarm★
CNNAMUR alarm and saturation levels, low alarm★
CRCustom alarm and saturation signal levels, high alarm ★
CSCustom alarm and saturation signal levels, low alarm★
CTRosemount standard low alarm★
Configuration buttons
(15)
D4
(22)
DZ
Ground screw
Analog zero and span ★
Digital zero trim ★
(18)(23)
V5External ground screw assembly★
HART Revision configuration (requires HART Protocol output code A)
(4)
HR5Configured for HART Revision 5★
HR7Configured for HART Revision 7★
Typical model number:3051CFAD L 060DC HPS 2T10 003 2AA1
1.Select configuration buttons (option code D4 or DZ) or LOI (option code M4) if local configuration buttons are required.
24
Emerson.com/Rosemount
March 2018
2.Available in remote mount applications only.
3.The cage nipple is constructed of Rosemount 304 SST.
4.O pti on HR 5 co nfig ure s the HAR T out put to HA RT Re vis ion 5. Op tio n HR7 con figu res the H ART outp ut t o HA RT Rev isi on 7 . The dev ice can be field configured to HART
Revision 5 or 7 if desired. HART Revision 5 is the default HART output.
5.For local addressing and configuration, M4 LOI is required.
6.Requires wireless options and engineered polymer housing. Available approvals are FM Intrinsically Safe, (option code I5), CSA Intrinsically Safe (option code I6),
ATEX Intrinsic Safety (option code I1), and IECEx Intrinsic Safety (option code I7).
7.Only available with C6, E2, E5, I5, K5, KB, and E8 approval. Not available with GE, GM, SBS, DA0, M4, D4, DZ, QT, HR5, HR7, CR, CS, and CT.
8.Only available with wireless (code X).
9.Not available with Product certifications options E8, K8, E5, K5, C6, K6, E7, K7, E2, K2, E3, KB, and KD.
10.Applies to assembled flowmeter only, mounting not tested.
11.Instrument connections for remote mount options and isolation valves for flo-tap models are not included in the Material Traceability Certification.
12.Not available with transmitter connection platform 6.
13.Materials of Construction comply with metallurgical requirements within NACE MR0175/ISO for sour oil field production environments. Environmental limits apply
to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments.
14.Only valid with F
15.Only available with 4–20 mA HART (code A).
16.Dust approval not applicable to output code X. See “Certificate: AG-0226; AG-0454; AG-0477” on page 62 for wireless approvals.
17. Nonincendive certification not provided with wireless output (code X).
18.Not available with wireless output (code X).
19. Only available with Product cer tifications E7, E8, I1, I7, IA, K7, K8, KD, N1, and N7
20.Not available with F
21.The T1 option is not needed with FISCO Product Certifications, transient protection is included with the FISCO Product Certification codes IA, IB, and IE.
22.Only available with 4–20 mA HART (output code A) and wireless (output code X).
23.The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.
OUNDATION Fieldbus (code F).
OUNDATION Fieldbus (output code F) or wireless (output code X) or low power (output code M).
Rosemount 3051
Emerson.com/Rosemount
25