Roper Microwave Hood Combination, 4B75546A, 4358154 Installation Instructions Manual

Microwave Hood Combination
Appliances
IMPORTANT: Read and save these instructions.
IMPORTANT Installer: Leave Installation Instructions with the appliance. Homeowner: Keep Installation Instructions for future reference. Save Installation Instructions for local inspector’s use.
Part No. 4B75546A14358 154
Beforeyoustart...
Remove all contents from the upper cabinet.
Important: Observe all governing codes and ordinances.
Check location where microwave oven will be installed. The wall must be strong enough to support the microwave oven weight of 150 lbs., plus the weight of any items placed inside the microwave or the upper cabinet. The location should be away from strong draft areas, such as windows, doors, and strong heating vents. The microwave oven should be located for convenient use in the kitchen.
Proper installation is the installer’s responsibility. A qualified technician should install this microwave oven. Make sure you have everything necessary for correct installation. It is the responsibility of the installer to comply with the installation clearances specified on the serial/rating plate. The serial/rating plate is located
Excessive Microwave Energy
Exposure
. Do Not attempt to operate this
microwave oven with the door open.
. Do Not tamper with or defeat
the safety interlocks.
. Do Not place objects between
the microwave oven front face and the door.
. Do Not allow soil or cleaner
residue to accumulate on sealing surface of microwave oven door.
. Do Not operate microwave
oven if it is damaged.
. The microwave oven door
must close properly to provide safe operation. Do Not use microwave oven if door is bent; hinges and latches are broken or loose; or door seals, sealing surfaces or glass are broken.
n
The microwave oven should only be adjusted and repaired by a qualified repair person.
. Have a qualified repair person
check for microwave leakage if a repair is made.
Failure to use microwave oven except as instructed may result in exposure to excessive microwave energy.
behind the micr&vave oven door on the front frame of the microwave oven.
Electrical ground is required. See Electrical requirements.
II I
For comer installations, allow
enough clearance to fully open
door so that rack and cooking
utensils can be removed
Y
I-
30” min cabinet
opening width
c
I Y
t
15” minimum’microwave
oven to cooking surface
or countertop
30” min~clearance from
. . .
Wall construction should be a minimum of 2” x 4” wood studding and 3/8” thickness drywall or
Use templates included
with installation
instructions.
Remove all packaging material from inside microwave oven. Check the microwave oven for damage - see WARNING for excessive microwave energy exposure. If any damage is evident, do Not operate the microwave oven until it is checked by an authorized Whirlpool service technician
Personal Injury Hazard Two people are required to lift this microwave oven.
Failure to use more than one person during installation may result in personal injury. . This microwave oven must be
mounted against and supported by a flat, vertical wall.
. This microwave oven must be
attached with two lag screws to a minimum of one, vertical 2” x 4” wall stud.
H Do Not mount microwave oven
to an island or peninsula cabinet.
w The microwave oven top and
rear supporting structures must be capable of supporting 150 lbs., plus the weight of any items placed inside the microwave oven or upper cabinet.
Failure to mount the microwave oven as instructed could result in personal injury and/or property damage.
Electrical Shock Hazard
It is the customer’s responsibility:
. To contact a qualified
electrical installer.
. To assure that the electrical
installation is adequate and in conformance with National Electrical Code, ANSVNFPA 70­latest edition*, and all local codes and ordinances.
Failure to do so could result in fire, electrical shock or other personal injury.
Tools and materials needed
Property Damage Place a portion of carton or another heavy material over the countertop or cooktop before installing the microwave oven. Do Not use a plastic cover.
Failure to protect cooking surface or countertop could result in property damage.
I
NOTE:
Do Not use this microwave oven for commercial purposes. This microwave oven is designed for household use only.
316” and 314”
wood drill bits
Parts supplied for installation:
saber saw V 6-j
,.
//A
m
4, l/4” x 3”
toggle bolts
69
4 spring
toggle-heads
2, l/4” x 2” bolts
m Take special care when drilling
holes into the wall. Electrical wires may be concealed behind the wall covering and contact with them could result in electrical shock.
m Locate any electrical circuits
that could be affected by the installation of this product and
disconnect power circuit. Failure to do so could result in electrical shock.
screwdriver II -
gq
4,114” x 2” lag screws
&
1, power cord clamp and
1, mounting screw
2 tapping screws
(dark-colored)
(bright-colored)
measuring rape
carton or another heavy material
1 power cord
bushing
l
Copies of the standard listed may be obtained from:
National Fire Protection Association Batterymarch Park Quincy, Massachusetts 02269
for covering countertop
Special hardware and tools are required for brick or masonry walls. At least four anchor bolts must be anchored into the wall and the mounting area must be capable of meeting the 150 lb.-weight requirement.
2 filter screens
Panel A
Electrical
Venting
requirements
requirements
Electrical ground is required on this appliance.
Electrical Shock Hazard
w Electrical ground is required on
this appliance.
n
Improper connection of the equipment-grounding conductor can result in electrical shock.
n
Check with a qualified elect& cian if you are in doubt as to whether the appliance is properly grounded.
n
Do Not use au extension cord with this appliance.
Such use may result in a fire, electrical shock or other personal iujury.
n
Do Not have a fuse in the neutral or grounding circuit. A fuse in the neutral or grounding circuit could result in electrical shock.
Failure to follow these instruc­tions could result in electricaI shock or other personal injury.
Instructions for local electrical
A 120-volt, 60-Hz, AC only, 15- or 20-ampere, fused electrical supply (located in the upper cabinet as close as possible to the microwave oven) is required. Time-delay fuse or circuit breaker is recommended. It is recommended that a separate circuit serving only this appliance be orovided.
Recommended grounding method
Do Not, under any circumstances, remove the power supply cord grounding prong.
For your personal safety, this appliance must be grounded. This appliance is equipped with a power supply cord having a 3-prong grounding plug. To minimize possible shock hazard, the cord must be plugged into a mating 3-prong grounding-type wall receptacle, grounded in accordance with the National Electrical Code, ANWNFPA 70-latest edition* and all local codes and ordinances. See Figure 1. If a mating wall receptacle is not available, it is the personal responsibility and obligation of the customer to have a properly grounded, 3-prong wall receptacle installed by a qualified electrician.
3-prong grounding plug
power supply cord
Panel B
3-prong grounding type wall receptacle
Figure 1
Ductwork needed for installation is not included. Wall and roof caps used must have back-draft damper.
Fire Hazard
. Venting system must terminate
to the outside.
n
Do Not terminate the ductwork in an attic or other enclosed space.
. Do Not use 4” laundry-type
wall caps.
n
Do Not use plastic or flexible plastic ductwork.
Failure to follow recommended venting procedures may result in a fire.
Rigid metal ductwork is recommended. Flexible ductwork is Not recommended. If flexible metal ductwork is used, calculate each foot of flexible ductwork as two feet of straight metal ductwork. Flexible elbows count twice as much as standard elbows.
Determine which venting method (roof-venting, wall-venting or ventless) you need to use. This microwave oven is equipped for roof- or wall-venting installation. Some models cannot be installed using the ventless (recirculating) method.
The length of the ductwork and number
of elbows should be kept to a minimum to provide efficient performance. The size of ductwork should be uniform. Do Not install two elbows together. Use duct tape to seal all joints in the duct system. Use caulking to seal exterior wall or roof opening around cap. Figures 2-5 show common venting methods and types of materials needed.
Note: If the rear exhaust method is chosen, be sure that there is proper clearance within the wall for the ductwork.
Roof venting
-- .
Wall venting
Figure 2
roof cap
-
w
3-l/4” x lo”
duct
-l-ll through-the-roof
Figure 3
a wallcap
3-l/4’ x 10 through-the-wall
Figure 4
3-114” to round
duct transition
3-l/4” x 10” to round ductwork transition
wall
7,--q
I
Recommended duct length
Use 3-l/4” x 10” or 6” duct. The total length of the duct system including straight duct, elbows, transitions, wall or roof caps must not exceed the equivalent of 140 feet of 3-l/4” x 10” rectangular or 6” diameter round duct. For best performance, use no more than three 90” elbows. To calculate the length of system you need, add the equivalent feet for each duct piece used in the system. See the following example:
3-l/4” x 10” duct system
3-l/4” x lo” 1
SO”Elbow ,- 6ft.
\q
-.-
II 4
u
2-f%..
+
1 - 6” to 3-l/4’ x 10” 90” elbow = 25 ft. 1 - wall cap
= 40 ft.
8 feet straight
= 8ft. Length of 3-114” x 10” system = 73ft.
6” duct system
wall
caP
6ft. ,,I
tralhtion
1 - transition
= 5ft.
2 - 90” elbows
= 20 ft.
1 - wall
cap = 40 ft.
8 feet straight
= 8ft.
Length of 6” system = 73 ft.
Recommended standard fittings
7
kc3
-
3.114” x lo” to 6” = 5 ft.
a
a
i’
90” elbow = 10 ft.
3.1/4”x 10” I
3-114 x lo”
roof
cap =
24 ft.
90” elbow -25 h
3-114” x10”
wallcap -
40 ft.
3-114” x lo” flat elbow ­10 ft.
If the existing duct is round, a rectangular-to-round adapter must be used and a rectangular 3” extension duct between the damper assembly and the the adapter must be installed to prevent sticking of the exhaust damper.
Venting preparation
Electrical Shock Hazard m Do not pull or stretch blower wiring.
Pulling and stretching blower
wiring could result in electrical shock.
. Reinsert wires in clips before
reinstalling blower unit into microwave oven.
Failure to do so could result in electrical shock.
Figure 5
Loading...
+ 4 hidden pages