1.1Safety instructions and warnings for user .......................................................................................... 6
1.2Declaration of icons ............................................................................................................................ 7
1.3Intended use ....................................................................................................................................... 7
2Technical data ........................................................................................................................................ 9
2.1Technical data control unit I20 ............................................................................................................ 9
2.2Versions of the control unit I20 ......................................................................................................... 10
3.2System type ...................................................................................................................................... 17
3.3General hints for process reliability .................................................................................................. 19
3.4Control unit ....................................................................................................................................... 20
3.5Parameters of the control unit .......................................................................................................... 20
10.1Replacement of sensors ................................................................................................................ 109
10.2Exchange of control unit ................................................................................................................ 109
10.3Replacement of fuses .................................................................................................................... 110
10.4Data backup via USB interface ...................................................................................................... 110
10.5Firmware update via USB interface ............................................................................................... 111
10.6Spare parts .................................................................................................................................... 111
11Technical records .............................................................................................................................. 113
11.1Exchange of equipment ................................................................................................................. 113
12Order data .......................................................................................................................................... 114
12.1Versions of control unit I20 ............................................................................................................ 115
13.1System configuration form ............................................................................................................. 117
4
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 5
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
Declaration of conformity according to EC directives
Manufacturer: Roland Electronic GmbH
Otto-Maurer-Str. 17
DE 75210 Keltern
Product name:
Product type:
Roland Electronic GmbH declares that the product listed above complies with the requirements of
the EMC directives listed below.
Applied Directives:
2006/95/EG Low Voltage Directive
EN61010-1: 2010
I20
Double Sheet Detector-series I20
Safety advices
2004/108/EG: EMC Directive
EN61000-6-2: 2005-08 EN61000-6-4: 2007-01
Date of mark’s apposition: 12.03.2015
Keltern, 12.03.2015
Place, Date Signature Function of the signer
Managing Director
The declaration confirms the compliance with the cited directives. However, it is not any implied warranty of fitness for a
particular purpose especially as it may relate to product liability.
The safety instructions and warnings must be observed.
ISO 9001 : 2008
Reg.-no. 5152 QM08
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
5
Page 6
Manual
Double Sheet Detector-series I20
Safety advices B0069991 / Rev. 1.7
Blank page
1 Safety advices
1.1 Safety instructions and warnings for user
This handbook contains all information required for the correct operation of the Roland equipment.
It has been written for technically qualified personnel. Unauthorized tampering with the unit,
especially ignoring the warnings in this handbook, can cause malfunction and damage to the unit.
6
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 7
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
Only authorized personnel should be allowed to make changes to the unit and perform cable
connections especially the power supply.
Should it be necessary, e.g. in case of service or repair, to make measurements within the unit,
then all customary accidents prevention procedures should be observed. Only professional
electrical tools should be used.
NoteThe factory pre-settings – especially the upper / lower limit values – have
been chosen such that an optimal machine protection is ensured.
Diverging settings can impair the machine protection.
Safety advice for persons with cardiac pacemakers!
Persons with cardiac pacemakers are to stay away from the sensors!
The strong magnetic / electromagnetic fields of the sensors can cause malfunction
of cardiac pacemakers and other such apparatus!
1.2 Declaration of icons
Warning - general dangers!
Reference to imminent hazards, which can result in severe bodily harm or death.
Warning - dangers by high voltage!
Reference to imminent hazards due to electricity, which can result in severe bodily
harm or death.
Attention - Damage of construction units!
Reference to a potential imminent situation, which can result in damage to the
product or environs.
Note
Useful reference to an application or deepening information.
Safety advices
1.3 Intended use
Flexible Manufacturing Systems in the sheet processing industry require reliable Double Sheet
Control systems in order to protect presses and other sheet processing machines against damage
caused by feeding multiple sheets.
The Double Sheet Detector R1000 I20 was specifically developed for this technical environment.
Depending on the application (type of material, thickness, sensor gap) the I20 can be used with up
to four pairs of sensors. The reliable function of the Double Sheet Detector depends therefore most
importantly on the selection of the correct sensors and the mounting of the sensors.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
7
Page 8
Manual
Double Sheet Detector-series I20
Technical data B0069991 / Rev. 1.7
Blank page
8
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 9
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
2 Technical data
2.1 Technical data control unit I20
Technical data control unit I20
Operating voltage: 24 VDC, +6 V / -4 V
Power consumption: 15 W
Switch on current: 10 A for 1 ms
External fuse: 1 A medium time lag
Ambient temperature: 0 - 50 °C (30 - 122° F)
Wall mount enclosure I20-2-O-S I20-4-O-S
Protection category: IP65
Dimensions, approx.. (W x H x D) mm 225 x 206 x 112 225 x 206 x 112
Dimensions, approx.. (W x H x D) inch 8.9 x 8.1 x 4.4 8.9 x 8.1 x 4.4
Weight, approx 4.0 kg (8.81 lbs)
Valid from SN-No. 104358 delivery date 09/03/2009
Front panel enclosure I20-2-O-S-FP I20-4-O-S-FP
Protection category: IP40 (inside), IP65 (front cover)
Dimensions, approx.. (W x H x D) mm 240 x 240 x 120 240 x 240 x 170
Dimensions, approx.. (W x H x D) inch 9.45 x 9.45 x 4.7 9.45 x 9.45 x 6.7
Weight, approx 2.2 kg (4.85 lbs)
Additional characteristics:
255 parameter sets memory
Programming via front panel keys
10 galvanically isolated
optocoupler inputs 24 VDC with
common external supply
5 potential free outputs
with positive external supply
Virtual RS232 interface (via USB) for data backup
USB interface for Firmware update
AttentionIn order to protect the outputs from damage by inductive spikes, the
Specification:
- min. switching voltage HIGH: 13 VDC
- max. switching voltage HIGH: 30 VDC
- min. switching voltage LOW: 0 VDC
- max. switching voltage LOW: 8 VDC
Specification:
- switching output: unwired Emitter and Collector
- max. switching voltage: 30 VDC
- max. switching current: 500 mA
outputs need to be protected by amply dimensioned flyback diodes.
Technical data
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
9
Page 10
Manual
Double Sheet Detector-series I20
Technical data B0069991 / Rev. 1.7
2.2 Versions of the control unit I20
The control unit article key ist coded as follows:
Control unit I20 with optocoupler interface
I20-2-O-S-FP
A B C D E
Based on the product key shown above, the following versions are available:
I20-2-O-S
I20-4-O-S Control unit for wall mounting, connection of up to 4 sensors,
I20-2-O-S-FP Control unit for front panel mounting, connection of up to 2 sensors,
I20-4-O-S-FP Control unit for front panel mounting, connection of up to 4 sensors,
Data backup
via serial USB
interface
Control unit for wall mounting, connection of up to 2 sensors,
IN/OUT interface
IN/OUT interface
IN/OUT interface
IN/OUT interface
A Type of unit I20
B Number of sensors
C Outputs O Optocouplers
D Connection S pluggable
E Enclosure FP Front panel mounting
2 4 up to 2 sensors
up to 4 sensors
2.3 Sensors
The sensor description has the following code:
IS20-30GS
2.3.1 Sensor pair IS20-30GS / IE20-30GS
A B C D E
Technical data
Application: Double sheet detection
Sheet thickness:
0.05 – 4 mm for steel
0.05 – 10 mm for Aluminum (LW 20 – 30 MS/m):
0.2 – 10 mm for austenitic Stainless steel
Sensor distance: see sensor diagrams
Measurement principle: Eddy current
Protection class: IP54
Weight: ca. 0.25 kg (0.55 lbs)
Material of enclosure: Stainless steel / Brass, Nickel plated
Sensor cable: Quick disconnect
A: Inductive sensor
B: S = transmitter, E = receiver
C: Diameter of sensor head
D: Thread
E: Quick disconnect
at nom. sensor distance (min. / max.)
20 (10 – 40) mm
20 (10 – 40) mm
20 (10 – 40) mm
10
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 11
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
2.3.2 Sensor pair IS42-30GS / IE42-30GS*
Technical data
Application: Double sheet detection
Sheet thickness:
0.15 – 8 mm for steel
0.1 – 10 mm for Aluminum (LW 20 – 30 MS/m):
0.4 – 10 mm for austenitic Stainless steel
Sensor distance: see sensor diagrams
Measurement principle: Eddy current
Protection class: IP54
Weight: ca. 0.45 kg (1 lbs)
Material of enclosure: Stainless steel / Brass, Nickel plated
Sensor cable: Quick disconnect
* Transmitter ISQ42. and receiver IE42-30.. may be also used as a sensor pair. Please refer to
chapter 4.3.1 for an example.
Technical data
Application: Double sheet detection
Sheet thickness:
0.15 – 8 mm for steel
0.1 – 10 mm for Aluminum (LW 20 – 30 MS/m):
0.4 – 10 mm for austenitic Stainless steel
Sensor distance: see sensor diagrams
Measurement principle: Eddy current
Protection class: IP54
Weight: ca. 0.50 kg (1.1 lbs)
Material of enclosure: Plastic
Sensor cable: ISQ / IEQ42S: Quick disconnect
ISQ / IEQ42FS: 0,2 m, cable firmly connected, with cable plug
* Transmitter ISQ42S and receiver IE42-30S, respectively transmitter IS42-30S and receiver
IEQ42S may be also used as a sensor pair. Please refer to chapter 4.3.1 for an example.
Technical data
at nom. sensor distance (min. / max.)
40 (20 – 80) mm
40 (20 – 80) mm
40 (20 – 80) mm
at nom. sensor distance (min. / max.)
40 (20 – 80) mm
40 (20 – 80) mm
40 (20 – 80) mm
2.3.4 Sensor pair ISQ160S / IEQ160S
Technical data
Application:
Sheet thickness: Depending on the application
Sensor distance: 20 – 80 mm (depending on the application)
Measurement principle: Eddy current
Protection class: IP54
Weight: ca. 0.50 kg (1.1 lbs)
Material of enclosure: Plastic
Sensor cable: Quick disconnect
Part inspection, Material inspection, Hardness inspection
NoteThe stated measurement ranges are only valid for systems in „Standard“
setting. For details refer to chapter 3.2.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
11
Page 12
Manual
A
t
Ax /
A
A
A
Double Sheet Detector-series I20
Technical data B0069991 / Rev. 1.7
2.3.5 Sensor diagrams
Sensor diagrams are available for determining the admissible measuring range depending on the
gap between transmitter and receiver (Ax) and the material. Ax is specified as follows:
x
Fig. 1: Transmitter-receiver gap Ax
The marked areas represent the working ranges of the sensors. For all combinations of sheet
thickness and sensor distance Ax within the range a double sheet condition will be reliably
detected, if the switching thresholds are set “tight”.
The working ranges of the sensors depend very much on the material properties, they can deviate
from the sensor diagrams shown below.
NoteThe stated measurement ranges are only valid for units of type
„Standard“. For details refer to chapter 3.2.
Blech
Shee
Ax diagrams for sensors IS / IE20-30GS
mm
Ax (2 n)
Ax (n)
x (½ n)
Ax (2 n)
Ax (n)
x (½ n)
Ax (2 n)
Ax (n)
30
20
10
0
Ax / mm
40
30
20
10
0
0,05
Ax / mm
40
30
20
0,05
STEEL
1
234
Sheet thickness / mm
AL UMINUM
1
2345678910111213141516
STAINLESS STEEL (Austenitic)
Ax(n) = nominal sensor gap
Sheet thickness / mm
x (½ n)
10
0
0,2
1
2345678910111213141516
Sheet thickness / mm
Fig. 2: Sensor diagrams for sensors IS / IE20-30GS
12
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 13
Manual
A
)
A
)
A
)
m
m
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
Ax diagrams for sensors IS / IE42-30GS and ISQ / IEQ42S
Ax (2 n)
Ax ( n)
x (½ n
Ax (2 n)
Ax ( n)
x (½ n
NoteThe stated measurement ranges are only valid for systems in „Standard“
Ax / mm
80
60
40
20
0
Ax / mm
80
70
60
50
40
30
20
STEEL
20,1546 8
135 7
Technical data
setting. For details refer to chapter 3.2.
Ax(n) = nominal sensor gap
She et th ickn ess / mm
ALU MINU M
0
0,1
1
Ax ( 2 n)
Ax ( n)
x (½ n
Ax / mm
80
70
60
50
40
30
20
0
0,4
2345678910111213141516
STAINL ESS ST EEL (Aus te n itic)
1
2345678910111213141516
Sheet thickness / m
Sheet thickness / m
Fig. 3: Sensor diagrams for sensors IS / IE42-30GS / ISQ / IEQ42S
Ax diagrams for sensors ISQ / IEQ160S
The sensors are specifically designed for Monitoring Parts for Hardened / Tempered Properties
and Materials Mix up. The sensor gap can range from 20 to 80 mm depending on the geometry of
the parts to be tested.
NoteIf more than 1 pair of sensors is connected to the system, the sensor
gaps may not deviate from each other more than ±10%. Otherwise the
zero adjustment can be faulty.
Example: S1: 40 mm S2: 42 mm S3: 39 mm S4: 43 mm
All values are within ±10%.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
13
Page 14
Manual
Double Sheet Detector-series I20
Technical data B0069991 / Rev. 1.7
2.4 Dimensions of the sensors
14
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 15
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
Technical data
Fig. 4: Dimensions of IS/IE sensors bis SE75.wmf
2.5 Sensor cables
Cable marking:
The cables have quick disconnects at both ends. The plug at the control unit side is always
straight.
SCI20S-GG with straight cable socket at the sensor
SCI20S-GW with right angle cable socket at the sensor
SCI20S-GG-TE extension cable for sensor cable (also use as quick disconnect)
Applicable to all cables:
Note The sensor cable is an active component of the sensor technology.
Bending radius: 50 mm at fixed installation
100 mm at flexible installation
Cable diameter: 7.1 mm
Suitable for drag chains, oil-proof, PUR jacket
Superflex Tronic(C)PUR TP 4 x 2 x 0.25 mm²
The technical data of the sensors is valid only if the cable specification is
met. A shielded cable must be used.
The cable length can be to up to 50 m. Following the rule "the shorter the
better" generally leads to better measuring results.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
15
Page 16
Manual
Double Sheet Detector-series I20
System description B0069991 / Rev. 1.7
Cable extension SCI20S-GG-TE
The cable extension SCI20S-GG-TE is inserted between the control unit and the existing regular
sensor cable SCI20S-GG, SCI20S-GW.
Note: This cable must be used if the sensors ISQ/IEQ42FS (with firmly
connected cable) are taken.
2.5.1 Allocation of sensor cables SCI20S-GG, SCI20S-GW and SCI20S-GG-TE
Fig. 5: Allocation of sensor cables SCI20S-GG, SCI20S-GW and SCI20S-GG-TE
2.6 Scope of delivery (accessories)
Within the scope of delivery there are accessorial parts, which are separately packaged and put
into the shipment box.
Fig. 6: Accessories, packaged
The volume of accessories depends on
the version of the control unit.
It is shown in Chapter 5.2
“Configuration of connectors“.
16
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 17
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
3 System description
Flexible production systems in the sheet processing industry require automated, reliable double
sheet detection in order to protect presses and other processing machinery from damage by
multiple sheets. The I20 was specifically developed for this technical environment. The I20 is based
on the product platform R1000 and consists in the standard version of three components:
• a control unit
• one pair of sensors (transmitter and receiver)
3.1 Measurement principle
3.2 System type
• one pair of sensor cables
The function of the sensor system is based on the measurement of eddy currents. The sensor
system consists of a transmitter and a receiver.
The transmitter generates an electromagnetic field, which generates eddy currents in the target.
The eddy current loss in the sheet dampens the electromagnetic field. These losses are measured
in the receiver and are a measure of the sheet thickness (see also section ”Sensor diagrams“).
With the system parameter “System type“ the function of the I20 can be fundamentally changed.
Possible choices are:
a) Standard
b) FE + AL 0.5 - 3 mm
c) FE + AL 0.1 - 0,8 mm
d) FE + Austenite 0.1 - 1 mm
f) FE + Austenite 0.5 - 3 mm
g) Frequency
h) Damping mode
With the selections b) – f) the following applications are conceivable:
• Only 2 programs are used, one program for ferrous and the other one for nonferrous
material. With each change of material the program for the corresponding material is
switched and the first sheet is used for Teach-In.
• All programs are used. The Teach-In can be performed with running sheet, without stating
nominal thickness and conductivity.
The selections b) - f) are intended as substitution for the mode “Dimension %“ known from the
I10K.
System description
Here mm or inch can be selected as dimension.
The nominal sheet thickness as well as the material must be entered.
For NF (nonferrous) material the electrical conductivity must be entered,
or the conductivity must be determined at sheet standstill. Only then a
dynamic Teach-In can be performed.
The materials which can be measured depend on the restrictions of the
sensor pair used.
Restricted measurement range !
Here only % can be selected as dimension.
The nominal sheet thickness does not need to (/cannot) be entered.
Only FE (ferrous) and NF (nonferrous) material are available for
selection.
A dynamic Teach-In can be directly performed.
Depending on the selection (b - f) only those materials and thicknesses
can be measured! (restricted measurement range!)
Monitoring Parts for Hardened / Tempered Properties and Materials Mix
up. The input of nominal dimensions is not necessary. The measurement
frequency is adjusted according to the task under consideration (review
the following explanations)
Within the system parameter „System type - Standard“ there will be no
error-free dynamic Teach-In execution in a sophisticated constellation of
work environment. The error message 151 "Sheet too thick" is reported.
This problem occurs especially when using magnetic conveyors. For this
case you must choose the system type “Damping mode“.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
17
Page 18
Manual
Double Sheet Detector-series I20
System description B0069991 / Rev. 1.7
3.2.1 Explanation for System type “Frequency”
This adjustment of the I20 is used for applications to identify non-hardened or defective parts. The
parts are passed through a sensor C-frame in which they are exposed to an eddy current field.
Non-hardened or defective parts have a different field attenuation from good parts and can
therefore be separated.
Roland Electronic supports the use with no charge application tests in order to ensure the feasibility
of the project and obtain the optimum control unit adjustments.
Differences of the Adjustments of the I20 in Comparison to the Standard Use.
Teach-In
• Instead of the single sheet (1-sheet) part A is used for a teach in of 100%
• Instead of two sheets (2 sheets) part B is used for a teach in of 200%
Sensors
• The pair of sensors ISQ160S/IEQS160S is primarily used for the system type "Frequency".
• Depending of the results of the application tests, the transmitter and the receiver are
mounted in line either vertically (0°) or horizontally (90°).
Illustration with 0° and with 90°
18
Fig. 7: Illustration with 0° and 90°
Sensor Gap and Measuring Position
• The sensor gap must remain constant during the operating mode "Frequency".
The sensor bracket must be correspondingly designed for this purpose.
• The measurement position of the part to be tested must be identical during Teach-In and
measurement.
• For this application glass turntables are very well suited, magnetic transportation systems are
not recommended.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 19
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
System description
Fig. 8: Glass turntable
Operation
• Instead of the nominal thickness the test frequency is selected for the adjustment of the
program parameters. The type of material adjustment is not necessary. The optimum test
frequency is determined at no charge in the application lab.
• The Teach in of 1 sheet and 2 sheet is substituted by the Teach-In of part A and part B
respectively. Preferably a good part is being used being used for the Teach-In.
3.3 General hints for process reliability
The process security of the system is influenced by the following factors:
• the stability of the measuring values
• the setting of under-gauge threshold and over-gauge threshold
• the evaluation of the status signals
Stable measuring conditions will result in stable measuring results. Varying measuring results are
undesirable, because in such cases the user is inclined to decrease the under-gauge threshold and
to increase the over-gauge threshold. On doing so, the user puts up with the drastically increasing
risk of not detecting a double sheet.
The following external factors decisively influence the stability of measuring results and need to be
considered for operation of a double sheet detector:
• the magnetic characteristics of the material
• the tolerance in material thickness
• the geometric conditions at the place of measurement and at the sheet
• the pre-magnetization of FE material in case of magnetic transport systems.
• the smooth run of the material, with low vibrations
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
19
Page 20
Manual
Double Sheet Detector-series I20
System description B0069991 / Rev. 1.7
From this, some simple rules can be derived, to enable a high process security when abided by:
• Every different sheet (Thickness, material and contour) is measured with separate
measuring program. For exceptions see chapter 3.6.
• The Teach-In has to be done with the same sheets (Thickness, material and contour)
used when measuring.
• Adjust the switching thresholds as tight as possible!
• Keep the sensor gap constant!
• Ensure for sufficient covering of the measuring target!
• Keep the pre-magnetization of FE material as low as possible (suitable mounting of the
transport magnets)!
• Pass the material guided through the sensor!
Furthermore it is necessary that the machine controls checks all status signals of the I20, also the
0-sheet signal. While measuring, only the 1-sheet signal may occur. If 0-sheet or 2-sheet occurs,
the measured sheet may not be transported on. In such cases, the sheet will usually be removed.
• The machine controls needs to evaluate all status signals !
Checking-up through the 0-sheet signal is to assure that a sheet really is between the sensors
during measuring. If 0-sheet occurs while measuring, the measurement is not correct. For example,
a defective sensor holder might change the sensor gap. Monitoring the sheet thickness would then
only be performed apparently.
In case of double sheet severe consequences could then result.
3.4 Control unit
The I20 is based on the product platform R1000.
Major features of the control unit:
• Programmable for 255 different sheet thicknesses / types of sheets
• Calibration by a Teach-In procedure
• Digital display of sheet thickness and operating parameters
• Monitoring of over gauge and under gauge limits
• Monitoring of operating voltage and sensor gap
• Opto coupler for direct I/O control via the PLC for fast measurement operations
• Software firmware update
• Data backup via USB interface
3.5 Parameters of the control unit
The I20 provides for extensive configuration. So, different customer requirements can be served.
Configuration is performed by setting system parameters and program parameters.
System parameters are set only once during commissioning, and will then remain unchanged.
Program parameters contain items which are material and job depending, and enable individual
adaptation to the measuring task.
20
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 21
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
3.5.1 Adjustment parameters
Adjustment parameters are assigned to the individual system. They apply only for this system and
should not be transferred to another unit (control unit exchange).
“Zero adjust“
Before commissioning a new system, after having exchanged a sensor or a sensor cable or a
control unit, a zero adjust must be performed. This zero adjust eliminates the variation of the
sensors. The sensors will be zero adjusted “all in one stroke“.
• The zero adjustment is valid for all programs and should be performed only once !
“Test sensor distance”
Checks the sensor distances.
“Deviation of distance”
Indicates the deviation from the set sensor distances.
“Sensors distance”
Indicates the determined sensor distances in mm / inch.
“Control sensors”
Test of wiring / allocation of the sensors.
System description
3.5.2 System parameters
“Language“
System languages available for operating the unit via display and keyboard:
German / English / Spanish / Italian / French.
“System type“
Fundamental setting of the system function.
In „Standard“ setting the nominal thickness, the material and the electrical conductivity must be
specified. In the other settings (see chapter 3.2 system type b – f) this specification is not required,
therefore only FE and NF material within the stated thickness range can be measured.
For details refer to chapter 3.2.
The “Frequency” is specially designed for the Monitoring Parts for Hardened / Tempered Properties
and Materials Mix up.
“Damping mode” is a special application. For details refer to chapter 3.2.
“Display value in…“
Switches the indication of the thickness values on the display between mm inch.
“Display time”
Specifies the holding time for the screen display.
Value range 0.0…2 seconds.
“CLR parameter (Clear Program Parameter)“
Deletes all program parameters. For doing so, the parameter needs to be set to “yes“. Executing
the command requires several minutes, because the program memory will completely cleared. All
program parameters will be reset to the default values and existing Teach-In data will be deleted.
Using this function only makes sense if a unit is to be newly used for another machine.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
21
Page 22
Manual
Double Sheet Detector-series I20
System description B0069991 / Rev. 1.7
“Password active“
Switches the password request on/off. If the password request is set “on“, the system / program
parameters can only be changed after the password has been entered.
“Password”
Without password the system data are unprotected against unwanted change. Therefore a
password should be set as soon as the installation is completed and regular operation has
commenced. The factory preset password is “0000”, it can be set to a value between 0000 and
9999.
“Pairs of sensors“
Defines the number of connected sensors. Those sensors are then available for measuring. To a 2channel system I20-2 max. 2 sensors can be connected, at a 4-channel system I20-4 max. 4
sensors can be connected.
“Sensor type“
Currently the sensors IS/IE20-30S or IS/IE42-30S and ISQ/IEQ42FS or ISQ / IEQ160S are
available. For those sensors characteristic curves for linearization purposes exists.
“Default settling time”
Defines the default time which the system requires to achieve stable measurement results, if the
program parameter “settling time” is not available. For details refer to chapter 3.7.2.
“Measurement mode“
Sets how the measuring is to be triggered. The following modes are available:
• Ext. Single (default setting)
Here a single measuring is performed. For doing so, the signal “Measuring start“ must be
externally applied. Another measuring requires a new flank of the “Measuring start“ signal.
• Demo
The demo mode is only intended for test and demonstration purposes. In this mode
measuring is performed until the demo mode is switched off again. For doing so, another
mode must be selected. The repetition time of the measuring is 4 ms.
• Ext. Permanently
Here the measuring is maintained as long as the signal “Measuring start“ is applied.
The repetition time of the measuring is 4 ms.
• Ext. Special
As Ext. Permanently, but: the highest value measured during a measurement cycle is
displayed and maintained until a new measurement cycle is started. This also applies for
the 0-1-2-Warning outputs.
“Hold if 2-sheet“
Selection: “yes” or “no“.
• Yes: The outputs (0-sheet, 1-sheet and 2-sheet) are activated according to the number of
sheets between the sensors. If the equipment detects 2-sheet, the output 2-sheet is
activated and the equipment is blocked until the 2-sheet condition is cleared, see
Section “Mode of operation 2-sheet hold“.
• No: The outputs (0-sheet, 1-sheet and 2-sheet) are activated according to the number of
sheets between the sensors. The equipment does not block the operation if double
sheet is encountered.
22
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 23
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
„Output level 0-1-2-warning“
Sets the output logic (0-sheet, 1-sheet, 2-sheet, warning) to 0V or +24V.
“Automat. prog. select”
Selects the method of program selection. If the program is switched frequently, “no” should be
selected, otherwise the memory would be loaded with frequent writing cycles and its lifetime would
decrease (1.000.000 writing cycles).
“IN / OUT PLC voltage”
Monitores the external PLC voltage. If “monitoring” is set and the PLC voltage is not connected, an
error condition would be detected.
“External Adjust“
Determines whether an external Teach-In / zero adjust is to be possible. If “yes“ is set, the PLC can
trigger the procedure via the inputs “Teach-In 0-, 1-sheet“. Default setting is “no“.
• The external adjust may only be performed under supervision of an operator.
“Internal analog zero”
Only for service personnel.
“Internal analog gain”
Only for service personnel.
“Diagnostic“
Diagnostics of the factors determined during the Teach-In. No default setting.
“Compensation factor”
Projected function.
“System info”
Displays the versions of Software and Hardware as well as the bus information.
Identification of the control unit. These information needs to be at hand for telephone support.
System description
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
23
Page 24
Manual
b
Double Sheet Detector-series I20
System description B0069991 / Rev. 1.7
3.5.3 Program parameters
3.5.3.1 Program parameters for the Double sheet detection
This menu structure is valid for the system types a – f (for details refer to chapter 3.2)
For measuring an eddy current method is used – called “Transmission” measurement. For
linearization purposes there are compensation curves, applicable to various conductivities and
thicknesses. Magnetical materials have their own compensation curves.
To determine the compensation curves a calibration (later merely called “Teach-In“) must be
performed.
In order to avoid frequent Teach-In procedures for different materials and thicknesses, the unit
provides for 255 program memories. Every such memory consists of a data set with the relevant
parameters.
“Program number”
Selects the number of the data set (1…255) which is to be applied for measurement.
“Sensor number“
Input of the selected sensor (/sensor sequence) for multi-channel systems (e.g. I20-4-…).
“Nominal thickness“
Specifies the nominal thickness of the sheets to be measured.
Value range 0.000…15.00 mm (0.000…0.590 in) Default setting 0.00mm / 0.000 inch.
“Material”
Specifies the material to be measured.
Choices: ferromagnetic material, non-magnetic material and non-magnetic material with unknown
conductivity.
“Lower limit TL“ and “upper limit TU“
Changes the limit values for the lower and upper switching threshold. The values can be entered
either in % or in mm/inch. On these thresholds depend the status signals.
In a window comparator the three signals will be generated from the measuring signal. The signal
“0-sheet“ is generated when the measuring signal falls short of the lower switching threshold TL.
The lower switching threshold TL can be set from 1...99%. The signal “2-sheet“ is generated when
the upper switching threshold is exceeded. The upper switching threshold TU can be set from
100...180%. If the measuring value is within both limits, the signal “1-sheet“ is generated.
Obere Schaltschwelle
Upper switching threshold
Signal
Untere Schaltschwelle
Lower switching threshold
2
1
0
Fig. 9: Visualization of switching thresholds
24
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
c
a
Signal range for 0-sheet
Signal range for 1-sheet
Signal range for 2-sheet
Upper switching threshold
Lower switching threshold
a
b
c
TU
TL
Page 25
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
The preset values (TU=120% resp. TL=80%) should only be changed under the following aspects:
1. the 1-sheet range is permanently restricted, since the measuring values are very stable. Thus
the process security increases. The restriction can be done by decreasing the TU value, by
increasing the TL value, or both.
2. the 1-sheet range is temporarily extended. Thus the process security decreases. Such an action
should only be performed in exceptional cases, the user has to decide about that. Extending the
1-sheet range is commonly considered due to mechanical problems (fluttering sheets). This
measure prevents the machine from stoppages, until the mechanical problem is solved.
“Nom./curr. settling time”
Defines the time which the system requires to reach stable measurement results.
For details refer to chapter 3.7.2.
“Teach-In 1-sheet“
The Teach-In calibration has to be executed with the material to be processed.
The calibration applies only to the selected program.
“Teach-In 2-sheet“
Because of the linearization of the sensor it is possible to measure with factory calibration in many
applications, as long as thickness, conductivity and material type are known
For a more precise indication, the system can additionally be calibrated to a 2-sheet condition.
The calibration applies only to the selected program.
System description
3.5.3.2 Program parameters for the Monitoring Parts for Hardened / Tempered Properties and
Materials Mix up
This menu structure is valid for the system types g (for details refer to chapter 3.2) For measuring
an eddy current method is used – called “Transmission” measurement. Compensation curves are
being used for linearization. In order to avoid frequent Teach-In procedures for different materials
and thicknesses, the unit provides for 255 program memories. Every such memory consists of a
data set with the relevant parameters.
“Program number”
Selects the number of the data set (1…255) which is to be applied for measurement.
“Sensor number“
Input of the selected sensor (/sensor sequence) for multi-channel systems (e.g. I20-4-…).
“Frequency”
Adjustment of the measurement frequency for this measurement program.
“Lower limit TL“ and “upper limit TU“
Changes the limit values for the lower and upper switching threshold. The values can be entered
in %. On these thresholds depend the status signals.
In a window comparator the three signals will be generated from the measuring signal. The signal
“0-sheet“ is generated when the measuring signal falls short of the lower switching threshold TL.
The lower switching threshold TL can be set from 1...99%. The signal “2-sheet“ is generated when
the upper switching threshold is exceeded. The upper switching threshold TU can be set from
100...180%. If the measuring value is within both limits, the signal “1-sheet“ is generated.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
25
Page 26
Manual
b
Double Sheet Detector-series I20
System description B0069991 / Rev. 1.7
Obere Schaltschwelle
Upper switching threshold
Signal
Untere Schaltschwelle
Lower switching threshold
Fig. 10: Visualization of switching thresholds
2
1
0
c
a
Signal range for 0-sheet
Signal range for 1-sheet
Signal range for 2-sheet
Upper switching threshold
Lower switching threshold
a
b
c
TU
TL
The switching thresholds should be adjusted corresponding to the application.
“Nom./curr. settling time”
Defines the time within the system must achieve a stable measurement result.
For details refer to chapter 3.7.2.
“Teach-In Part A“
The unit calibrates part A to 100%.
The calibration applies only to the currently selected program.
“Teach-In Part B“
The unit calibrates part B to 200%.
The calibration applies only to the currently selected program.
26
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 27
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
3.6 Application examples
The following are two typical application examples for the use of the I20.
12
Kabel SCI20S
Cable SCI20S
Kabelstecker 2277018
Cable plug 2277018
Kabel SCI20S
Cable SCI20S
System description
21
Kabel SCI20S-GG-TE
Cable SCI20S-GG-TE
Kabel SCI20S-GG-TE
Cable SCI20S-GG-TE
Kabeldose 2276032
Cable socket 2276032
Kabelstecker 2277018
Cable plug 2277018
IS...IE...
Sender
IS...GS
Tran smi tter
ISQ...S
Kabel SCI20S-GG-TE (Verlängerung / Trennstelle)
zwischen Gerät und Sensorkabel
Cable SCI20S-GG-TE (extension / quick disconnect)
between control unit and sensor cable
Empfänger
Receiver
IE...GS
IEQ...S
Kabeldose 2276032
Cable socket 2276032
Kabeldose 2276034
Cable socket 2276034
0,2 Meter
0.2 meters
ISQ...FS
Sender
Transmitter
0,2 Meter
0.2 meters
IEQ...FS
Empfänger
Receiver
For details on the extension cable SCI20S-GG-TE refer to 2.5.1
To the I20-2 up to 2 pairs of sensors of the same type can be directly connected, To the I20-4 up to
4 pairs of sensors.
The system is capable to measure:
a) sequentially by program switching in case of different sheet thickness,
b) simultaneously in case of identical sheet thickness and if the thickness does not exceed a
ratio factor of 2:1 (sequencer).
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
27
Page 28
Manual
Double Sheet Detector-series I20
System description B0069991 / Rev. 1.7
Explanation of summary output 0-sheet, 1-sheet and 2-sheet:
If the unit is used in simultaneous mode (more than 1 sensor in a program e.g. 1+3+4), the
measurement result is formed as summary output (via I/O and via the Fieldbus Byte 8-11). The
priorities are:
2-sheet is issued if at least one sensor detects 2-sheet.
1-sheet is issued if all sensors detect 1-sheet.
0-sheet is issued if no 2-sheet is detected but at least one sensor detects 0-sheet.
Truth table for summary output
Sensor 1 Sensor 2 Sensor 3 Sensor 4
2-sheet is issued if:
2-sheet any condition
any condition 2-sheet any condition
any condition 2-sheet any condition
1-sheet is issued if:
0-sheet is issued if:
1-sheet 1-sheet 1-sheet 1-sheet
0-sheet 0-sheet / 1-sheet
0-sheet / 1-sheet 0-sheet 0-sheet / 1-sheet
0-sheet / 1-sheet 0-sheet 0-sheet / 1-sheet
any condition 2-sheet
0-sheet / 1-sheet 0-sheet
28
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 29
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
Method a) sequentially by program switching
Meaningful, if the sheets to be monitored by the various sensors have different sheet thicknesses.
Also suitable if the nominal thickness changes from cycle to cycle.
For this procedure the respective parameter set (program) must contain nominal thickness and
sensor number. The selection of the program is then performed by the PLC.
The following is a typical application example
System description
Program Thickness Sensor
1 1,5 mm 1
2 0,7 mm 2
3 0,5 mm 3
4 0,8 mm 4
PLC
1. select Prog.1
2. measure Pr.1
3. evaluate result Pr.1
4. select Prog.2
5. measure Pr.2
6. evaluate result Pr.2
7. select Prog.3
8. measure Pr.3
9. evaluate result Pr.3
10. select Prog.4
11. measure Pr.4
12. evaluate result Pr.4
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
29
Page 30
Manual
Double Sheet Detector-series I20
System description B0069991 / Rev. 1.7
Method b) simultaneously (sequencer)
Advantageous when measuring the same sheet thickness with each sensor. Here the addressing
of each sensor is done automatically by the I20. The inquiry of the sensors is predetermined in the
program.
NoteAdvantage: Very fast measurements are possible, smaller software
effort on the PLC side.
Only one output is generated for connected sensors. The summary output is formed with the
following priorities: 2-sheet before 0-sheet, 0-sheet before 1-sheet.
The following is a typical application example
Program Thickness Sensor
1 1,5 mm 1, 2, 3, 4
Start
PLC
1. measure Pr.1
2. evaluate result Pr.1
Note
The simultaneous measurement (sequencer) is also applicable for the
simultaneous measurement of sheets with different thickness, with the
following restrictions:
- the sheet thickness ratio must be less than 2:1
- each sheet thickness is controlled by a sensor pair
- the largest nominal sheet thickness is to be set. This will
issued as measurement at each sensor pair as measured value
- for Teach-In it must be used at each sensor pair a sheet which later
corresponds to the sheet thickness to be measured.
30
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 31
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
System description
Program Thickness Sensor
1 1,0 mm 1, 2, 3, 4
1,5 mm1,5 mm0,6 mm0,6 mm
PLC
1. measure Pr.1
2. evaluate result Pr.1
In addition to the selection by sensor number (see chapter 13 “System Configuration - number of
sensors"), the following combinations of selections are available:
Combinations for 2 channel system Combinations for 4 channel system
Sensor 1
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
31
Page 32
Manual
Double Sheet Detector-series I20
System description B0069991 / Rev. 1.7
Note If all four pairs of sensors are activated (system parameter “pairs of
sensors”, each possible combination with only 2 or 3 sensors can be
selected. On the other hand the combinations for example for the sensor
number 4 cannot be selected, if only 3 sensors are activated.
The following rule applies: The highest sensor number in the combination
determines the minimum number of activated sensors.
NoteThe combination is a program parameter, therefore methods a) and b) can
form a practical combination, for example, two stacks of sheets for instance
left and right blanks with different thicknesses can thus be checked for
double sheet.
The following is a typical application example
Program Thickness Sensor
1 1,5 mm 1, 2
2 1,8 mm 3, 4
Start
PLC
1. select Prog.1
2. measure Pr.1
3. evaluate result Pr.1
4. select Prog.2
5. measure Pr.2
6. evaluate result Pr.2
1,5 mm1,5 mm1,8 mm1,8 m
32
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 33
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
3.7 Tailor Welded Blanks
While processing tailor welded blanks (sheet consists of two or more thicknesses), the nominal
thickness of the thickest sheet will be chosen to be entered.
System description
D2D1
I20-...
Program Parameter:
Lower threshold
80% mm
+
Higher threshold
120% mm
3.8 Design information regarding transporting velocity
3.8.1 Sensor coverage / Measurement target
For details refer to chapter 4.3.2 “Measurement target”
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
33
Page 34
Manual
s
Double Sheet Detector-series I20
System description B0069991 / Rev. 1.7
3.8.2 Settling time ts and measuring time tm
Settling time ts
The settling time t
Zustand “Blech”
Condition “sheet”
Sensorsignal
Sensor signal
Fig. 11: Illustration of settling time
The settling time ts is shown in program parameter 7 as actual / target settling time.
Possible values for the settling time: 2ms, 4ms, 8ms, 15ms, 25ms, 100ms, 250ms. If the achieved
settling time exceeds the desired value, the system selects the next possible higher value.
For details see Chapter 7 „Start-up“, „Program parameter 7“.
Material Thickness range Minimal settling time Damping mode
FE 6 – 8 mm
Aluminum
(LW 20)
Explanation:
For non ferrous material: the thicker the sheet is, the longer the settling time,
the larger the electrical conductivity, the longer the settling time.
is the time required by the system to produce stable measurement results.
s
t
3,5 – 6 mm
2,5 – 3,5 / 4 mm
1,6 – 2,5 mm
1,2 – 1,6 mm
0,8 – 1,2 mm
< 0,8 mm
6,6 – 12 mm
3,3 – 6,6 mm
1,6 – 3,3 mm
< 1,6 mm
NoteGeneral: A longer settling time t
250 ms (only for sensor 42-30)
100 ms (only for sensor 42-30)
25 ms
15 ms
8 ms
4 ms
2 ms
15 ms
8 ms
4 ms
2 ms
will result in more precise
s
250 ms (only for sensor 42-30)
100 ms (only for sensor 42-30)
25 ms
25ms
15ms
0.5 - 1,2mm 8ms
< 0.5mm 4ms
15 ms
8 ms
4 ms
2 ms
measurement results, due to the averaging effect.
The setting of the settling time influences the max. transport velocity of
sheets.
34
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 35
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
System description
Measurement time tm
The measurement time t
is the entire time, which the system requires from „Measurement Start“
m
to delivering of the output signal.
Messung Start
Measurement Start
Ausgangssignal
Output signal
t
m
Fig. 12: Illustration of measurement time
Operation by I/O inputs have a constant measurement time tm of 4 ms. In case of reading out the
measurement result via Fieldbus an extra time of 4 ms is required.
3.8.3 Maximum permissible transportation during double sheet control
The maximum permissible transportation speed of the metal blank depends on the sheet length,
the measurement target and the settling time t
With a upper threshold TU = 130% (see program parameters) the following guide lines apply:
Max. permissible transport speed [m/s] <
with sensor gap < sensor diameter.
.
s
Sheet length [mm] – 3× Sensor diameter [mm]
ts [ms] + 2 [ms]
3.8.4 Measurement at standstill of sheet
For measuring of sheets in standstill condition, the following must be considered:
• The covering of the sensors must be 3 times the sensor diameter.
• The necessary minimum residence time is as long as settling time plus measurement time
3.9 Secondary magnetic flux
Magnetic conveyors can generate a secondary magnetic flux in the transported sheet which can
distort the measured value. The influence of the secondary magnetic flux can the minimized by
mounting the sensors away from the magnets as much as possible and also mounting the magnets
in such a way as to reduce secondary magnetic flux. For details refer to chapter 4.4.
By using the “dynamic Teach-In” function, the system considers this influence.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
35
Page 36
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
Blank page
36
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 37
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
4 Mounting
The mounting of the Double Sheet Detector R1000 I20 determines the measurement accuracy and
the reliability of operation. The system was designed for operating in rough industrial environments.
However, the following mounting instructions should be observed in order to minimize mechanical,
thermal, and electromagnetic influences on the operation.
4.1 General mounting instructions
The enclosure for wall mounting meets IP65 and is designed for mounting the enclosure close to
the sensor location. This results in the use of shorter sensor cables with a corresponding lower
exposure to electromagnetic noise and could therefore result in better measurements.
The control unit should be installed in locations where no vibration exists and no additional heat is
transferred into the system (even better reduce the heat in the control unit). In addition the control
unit should be installed in such a fashion that it can be easily opened for service purposes. During
the operation the control unit and the sensors should be under visual control of the operating
personnel.
Attention Strong vibrations and additional heat can damage the control unit.
Mounting
In case of panels or operator consoles the front panel version may be used.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
37
Page 38
Manual
Double Sheet Detector-series I20
Mounting B0069991 / Rev. 1.7
4.2 Dimensions of the system
4.2.1 Unit in industrial enclosure
2-channel unit I20-2-O-S / 4-channel unit I20-4-O-S
I20-2-O-S
I20-4-O-S
38
All dimensions are in mm. Tolerance ±0,4 mm
Fig. 13: Dimensions of the 2-channel / 4-channel unit in wall mount enclosure
NoteA minimum depth of 120 mm is required for connecting the plugs.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 39
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
4.2.2 Front panel enclosure
I20-2-O-S-FP / I20-4-O-S-FP
220240
Mounting
23
23
Front plate cutout
194 x 194 mm
220
240
All dimensions are in mm. Tolerance: ±0.4 mm
Fig. 14: Dimensions of the front panel enclosure -front view
4 x Ø 4,2 for
Philips head screw
M4 DIN 74
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
39
Page 40
Manual
Double Sheet Detector-series I20
Mounting B0069991 / Rev. 1.7
Fig. 15: Dimensions of the front panel enclosure - side view
Note: A minimum depth of 120 mm is required for connecting the plugs
(see figure on next page).
4.3 Mounting of sensors
40
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
All dimensions are in mm. Tolerance: ±0.4 mm
Page 41
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
The reliable function of the Double Sheet Detector depends to a great degree on the correct
mounting of the sensors. The following mounting rules should be followed:
The sensor pair can be mounted in any direction. Transmitter and receiver must be installed
aligned opposite to each other. The use of a short C-frame is ideal. It provides a good stability and
guarantees a constant distance between transmitter and receiver.
On the rear side the sensors have a mounting thread M30 × 1.5 mm for mounting at holders of all
materials. If the sensors cannot be mounted by means of the mounting thread, they can be fixed by
clamping at the front sleeve, but only by clamp holders made of plastic material.
Fig. 16: External shields to protect the sensor from transferred sheets
Attention If the sensors are mounted by clamping at the front sleeve, no metallic
During the measurement no moving metallic parts should be
present within a radius of 80 mm of the sensor center.
Mounting
If the sensors are mounted protruding, care
must be taken that the running coil cannot
damage the sensors. If necessary, the
sensors must be protected with additional
shields (×) from damage by incoming
sheets.
Recessed mounting of the sensors must be
avoided, because dirt and shavings can
accumulate on the sensor surfaces and
result in reduced measurement security.
The illustration also shows a design
recommendation for a sensor holder.
holder may be used, because the sensor performance can be
considerably reduced.
80 mm
The mounting position must be selected, so that the sensors can be easily changed. Care must be
taken that the once set sensor gap can be easily reproduced in case of sensor change. Only then a
renewed Teach-In of all parameter sets can be avoided.
4.3.1 Possible combinations of transmitter and receiver
It is possible to use following types of transmitter and receiver together:
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
41
Page 42
Manual
Double Sheet Detector-series I20
Mounting B0069991 / Rev. 1.7
Fig. 17: Example of sensor holding with combinations of sensors IE42-30S and ISQ42S
4.3.2 Measurement target
This description is not for the operating mode “Frequency” (Monitoring Parts for Hardened /
Tempered Properties and Materials Mix up)
The sensor coverage (measurement target) must be at least the three times sensor diameter. The
dimension x should ideally correspond to the sensor diameter D (see picture below).
Sensor type IS42-30GS / IE42-30GS or ISQ42S / IEQ42S
Sensor gap
Minimal distance to the sheet edge
“X”
20 mm 36 mm 114 mm
40 mm 42 mm 126 mm
70 mm 63 mm 168 mm
80 mm 73,5 mm 189 mm
Sensor type IS20-30GS / IE20-30GS
Sensor gap
Minimal distance to the sheet edge
“X”
20 mm 31 mm 82 mm
40 mm 38 mm 96 mm
If the coverage is smaller, then the sheets should be transferred with reduced speed through the
sensor gap or measured statically. Precondition is however a constant distance to the sheet edge.
Minimal measurement target diameter
“D”
Minimal measurement target diameter
“D”
42
Fig. 18: Measurement target
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 43
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
4.3.3 Position of the sheet in the sensor gap
Ideally the sheet should be transferred through the middle of the sensor gap. This guarantees
reliable and accurate results of the measurement. The sheet to be measured must be in the same
position in the sensor gap during Teach-In and during the normal operation. If the position of the
sheet changes during normal operation from the Teach-In position then the measured value
changes also. The larger the deviation of the measurement position the larger is the distortion of
the measured value.
4.3.4 Sensor distances
The usable sensor distances can be read from the sensor diagrams.
NoteIf more than 1 sensor pair is connected to the system, the sensor
distances may not deviate from each other for more than ±10%.
Otherwise the zero adjustment can be faulty.
Example: S1: 40mm S2: 42mm S3: 39mm S4: 43mm
All values are within ±10%.
For details refer to chapter 2.3
Mounting
4.3.5 Distance between adjacent pairs of sensors
In order to except adjacent sensor pairs from influencing each other, a distance of the sensor pairs
of min. 120 mm (between the center axis of the sensors) must be kept.
4.3.6 Electromagnetic interference
Electromagnetic interference can affect the measuring accuracy of the sensor. Therefore the
sensors should not be installed close to devices which cause electromagnetic interference. Such
devices are e.g. frequency converters, servo motors or proximity switches on inductive basis.
In case of switching magnets a minimum distance of 30 mm should be respected in order to
avoid feedback. For proximity switches a minimum distance of 120 mm is required.
The sensor cables should not be placed directly adjacent to cables with large interference potential,
e.g. power supply cable. This applies especially to longer cable lengths.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
43
Page 44
Manual
y f
Double Sheet Detector-series I20
Mounting B0069991 / Rev. 1.7
4.4 Sensor mounting in magnetic conveyors
Note If the sheets are transported with magnetic conveyors, then the receiver
sensor should be mounted on the side that is opposite to the magnets.
If electromagnets are used in the conveyor belts, they must be supplied
with DC current. The residual ripple of the supply voltage must not exceed
5%. The supply voltage / current of the electromagnets may not be pulsed
during the measurement, as this distorts the measurement result.
The mounting of the sensors according to the following picture results in reliable double sheet
detection. It is important that the holding magnets are arranged in such a way that no secondary
magnetic flux develops between two magnetic conveyors rails either through the air or the sheet. It
is important that the mounting of the magnets in the conveyor belts results in an opposite magnetic
flux configuration of the type N<-->N or S<-->S.
No secondar
Conveyor railsConveyor rails
lux
AyAy
Primary
flux
N
Ax: see sensor diagram
for the sensor
Ax
Sensor
Transmitter
10 mm
40...60(70) mm
Sensor
Receiver
N
Use plastic brackets with a cap of about 3 mm
to prevent bended sheets from damaging the
sensor
S
Primary
flux
Ay: > 30 mm
10 mm
40...60(70) mm
Fig. 19: Sensor mounting, lateral view
Whenever possible the sensors should not be mounted close to the magnetic rails, but with the
greatest possible distance between the conveyors rails. The mounting brackets should consist of
plastic or stainless steel. Aluminum or materials of high electrical conductivity dampen the sensors
and reduce the performance substantially.
In order to reduce the disturbing effect of the magnets in dynamic measuring mode, we suggest
to mount the receiver at the largest possible distance. As a minimum distance for sensor type
IE42-30GS we require 40 mm.
44
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 45
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
S
N
S
Fig. 20: Sensor mounting, top view (*Sensor)
> 50 cm
S
N
S
N
S
N
S
N
Mounting
S
N
V
N
S
NoteThe sensors should be mounted wherever possible 50 cm after the
.
N
S
N
S
N
S
N
S
start of the magnetic tape drive.
Note If electromagnets are used in the conveyor belts, the
electromagnets must be supplied with DC voltage / current. The
residual ripple of the supply voltage must not exceed 5%. The
supply voltage or the supply current of the electromagnets is not be
clocked during the measurement, as this can affect the
measurement result.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
45
Page 46
Manual
Double Sheet Detector-series I20
Electrical installation B0069991 / Rev. 1.7
Blank page
46
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 47
Manual
2
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
5 Electrical installation
5.1 General instructions
The sensor cables should be kept as short as possible in order to minimize the influence of
electromagnetic noise. Cable shields must be connected according to the connection diagrams
only and should not have any additional connections.
Attention Damaged cable installations can result in additional electrical
connections. This can disturb the measured values.
5.2 Configuration of connectors
5.2.1 Configuration of connectors at the I20-2-O-S / I20-4-O-S
(to connect up to 2 / 4 sensor pairs)
A
Legend
A Central connector
B Grounding screw bolt
S1 Socket f. sensor transmitter 1
E1 Socket f. sensor receiver 1
S2 Socket f. sensor transmitter 2
S1S2S3S4
B
E2 Socket f. sensor receiver 2
S3 Socket f. sensor transmitter 3
E3 Socket f. sensor receiver 3
S4 Socket f. sensor transmitter 4
E4 Socket f. sensor receiver 4
The USB terminals are at the front
plate.
Electrical installation
E3E4
Fig. 21: Connections on 2-channel unit / 4-channel unit
E1E
In case of I20-2-O-S the connections S3, E3, S4 and E4 are omitted.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
47
Page 48
Manual
Double Sheet Detector-series I20
Electrical installation B0069991 / Rev. 1.7
5.2.2 Central connector (connection A)
At the central plug the supply voltage as well as the inputs and outputs of the PLC are connected.
View of connection side
Fig. 22: Central connector
5.2.3 Wiring diagram
PLC
PLC
grounding
point
External
power supply
Central
machine grounding
Measurement start
Program switching
Teach-in 1-sheet
Teach-in range
Zero adjust
Clear 2-sheet / 0-1-2-wa outputs
System test (gap control)
Data OUT
Teach-in 2-sheet
Material detection NF
Reset fault
PLC / COM
+24 VDC / PLC
ENABLE
2-sheet
1-sheet
Data IN
0-sheet
Warn ing
+ 24 VDC
0 VDC
LiYCY 18 x min. 0.25 mm
min. 0.5 mm
min. 0.5 mm
min. 1.5 mm
Central plug
A1
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
2
2
2
2
A2
A3
A4
A5
A6
A7
A8
A9
C1
C2
C3
C4
C5
C6
C7
C8
C9
B2
B3
B4
B5
B6
B7
B8
69
IN1
68
IN2
67
IN3
66
IN4
65
IN5
64
IN6
63
IN7
62
IN8
53
PLC / COM f. IN and OUT
52
PLC + 24 VDC f. IN and OUT
58
OUT0 Enable
56
OUT1 2-sheet
55
OUT2 1-sheet
54
OUT3 0-sheet
57
OUT4 Warning
50
+24 VDC
51
0 VDC
70
IN0
61
IN9
I20
48
Fig. 23: Diagram of wiring between PLC and I20 control unit
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 49
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
5.2.4 Pin configuration of control unit – opto coupler outputs
Data inputs PLC – Central plug at I20
PLC Central plug
Function Pin no. Input Specification
Measurement start B 7 IN 0
Measuring menu
selection = 0
Teach-In 1-sheet Bit 0 A 2 IN 2
Teach-In range Bit 1 A 3 IN 3
Zero adjust Bit 2 A 4 IN 4
Confirm 2-sheet (CLR outputs) Bit 3 A 5 IN 5
System test (gap control) Bit 4 A 6 IN 6
Teach-In 2-sheet Bit 5 A 7 IN 7
Material detection NF Bit 6 A 8 IN 8
Reset fault Bit 7 B 8 IN 9
PLC / COM A 9 Common 0V DC for IN and OUT
Data outputs PLC – Central plug at I20
PLC Central plug
Function Pin no. Outputs Specification
+24 VDC voltage supply for opto couplers from PLC interface C 1
Output is HIGH if ENABLE is active (unit o.k.) C 2 OUT 0
Output is LOW if 2-sheet is detected C 4 OUT 1
Output is LOW if 1-sheet is detected C 6 OUT 2
Output is LOW if 0-sheet is detected C 8 OUT 3
Output is LOW if Warning is detected C 9 OUT 4
Output current: absolute max. 500 mA / continuous max. 300 mA
Supply voltage External power supply – Central plug at I20
External power supply Central plug
Voltage Pin no. Specification
24 VDC B2 24 VDC +6 V / –4 V / min. 0.5 mm2
0 VDC B3 min. 0.5 mm2
Central machine grounding Grounding min. 1,5 mm2
Measuring menu
selection = 1
A 1 IN 1
+24 VDC ± 4 VDC
Electrical installation
Sinking
input
LOW: 0-8V,
HIGH: 13-30V
for IN and OUT
Sourcing
output
5.2.5 Connection of machine earth ground (connection B)
For earth ground connection, the enclosure of the R1000 has an M6 threaded screw. Here the
grounding cable (copper) of at least 1.5 mm² cross section must be connected to the earth ground
of the machine. The connection is obligatory!
Attention The positive supply voltage +24 VDC should not be connected to machine ground.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
49
Page 50
Manual
Double Sheet Detector-series I20
Electrical installation B0069991 / Rev. 1.7
5.2.6 Voltage supply
The supply cable for the voltage supply should be kept as short as possible. For cable lengths up
to 20 m the cable should have 2×0.5 mm
be accordingly increased. For power consumption of the system please refer to section “technical
data”.
Attention The positive supply voltage +24 VDC should not be connected to machine ground.
2
, for larger lengths the cross section of the cable needs to
5.2.7 Sensor connection (connections S1–4 and E1–4)
The sensor cable SCI20-S is connected at the control unit by plug.
Because of the special wiring of the sensor cable SCI20S it is no longer necessary to avoid mixing
transmitter and receiver cable. When using the SCI20S cable the transmitting sensor and the
receiving sensor will automatically be connected to the appropriate sockets of the control unit.
Note The sensor cable is an active part of the sensor. The performance
data is therefore based on the compliance with cable specification.
Allocation of sensor connections
Connector at control unit (pos. S1-4, E1-4)
View: Plug side
Suppliers / types / notes: ODU, Mini-Snap, Series K
5.3 Connecting diagram - examples
All sensor pairs are connected in the same manner.
Because of the special wiring of the sensor cable SCI20S it is no longer necessary to avoid mixing
transmitter and receiver cable. When using the SCI20S cable the transmitting sensor and the
receiving sensor will automatically be connected to the appropriate sockets of the control unit.
Socket insert 7-pin, size 2
Pin 1 +8V
Pin 2 -8V
Pin 3 GND
Pin 4 Transmitter 1
Pin 5 Transmitter 2
Pin 6 Receiver 1
Pin 7 Receiver 2
50
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 51
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
5.3.1 Connecting diagram I20-2 with one sensor pair
12
Kabelstecker 2277018
Cable plug 227701 8
Electrical installation
Kabel SCI20S
Cable SCI20S
Empfänger
Receiver
IE...GS
IEQ...S
Kabeldose 2276032
Cable socket 2276032
Kabeldose 2276032
Cable socket 2276032
Fig. 24: I20 with one sensor pair
Kabel SCI20S
Cable SCI20S
IS...GS
ISQ...S
Transmitter
IS...IE...
Sender
Cable extension SCI20S-GG-TE
The cable extension SCI20S-GG-TE is inserted between the control unit and the existing regular
sensor cable SCI20S-GG / SCI20S-GW.
NoteIf the sensors ISQ/IEQ42FS (with firmly attached cable) are used,
this cable must be used for extending the sensor cable.
For details refer to chapter 2.5.1.
Kabelstecker 2277018
Cable plug 2277018
Kabel SCI20S-GG-TE (Verlängerung / Trennstelle)
zwischen Gerät und Sensorkabel
Cable SCI20S-GG-TE (extension / quick disconnect)
between control unit and sensor cable
Fig. 25: Cable extension SCI20S-GG-TE
Kabeldose 2276034
Cable socket 2276034
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
51
Page 52
Manual
G
G
Double Sheet Detector-series I20
Electrical installation B0069991 / Rev. 1.7
0,2 Meter
21
Kabel SCI20SCable SCI20S-
0,2 Meter
0.2 meters
Kabel SCI20S-GG-TE
Cable SCI20S-GG-TE
Kabel SCI20S
Cable SCI20S
12
Kabel SCI20S-GG-TE
Cable SCI20S-GG-TE
Kabelstecker 2277018
Cable plug 2277018
Kabel SCI20S
Cable SCI20S
Kabel SCI20S-GG-TE
Cable SCI20S-GG-TE
0.2 meters
Kabeldose 2276032
Cable socket 2276032
IS...GS
ISQ...S
Fig. 26: I20 with one sensor pair and cable extension SCI20S-GG-TE
IS...IE...
Sender
Transmitter
Empfänger
Receiver
Kabeldose 2276032
Cable socket 2276032
IE...GS
IEQ...S
ISQ...FS
Sender
Transmitter
IEQ...FS
Empfänger
Receiver
52
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 53
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
5.3.2 Connecting diagram I20-4 with four sensor pairs
1234
Electrical installation
Fig. 27: I20-4 with four sensor pairs
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
53
Page 54
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
Blank page
54
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 55
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
6 Communication with the PLC
The I20 has 10 galvanically isolated (opto coupled) inputs and 5 galvanically isolated (opto
coupled) outputs.
6.1 PLC inputs
If different functions are performed at the same time, an fault message will be generated.
The following functions are possible:
1. Measurement Start / Stop
2. System test (gap control sensors)
3. Program switching
4. Clear 2-sheet / Clear 0-1-2-wa outputs
5. Zero adjust (not active by default)
6. Material detection NF (with first selected sensor)
7. Teach-In 1-sheet (not active by default)
8. Teach-In 2-sheet (not active by default)
9. Reset Fault
Communication with the PLC
6.2 PLC output signals
The following signals are available as outputs:
Signal Meaning Note
OUT3 0-sheet output Standard 0 V active (selectable in system configuration)
OUT2 1-sheet output Standard 0 V active (selectable in system configuration)
OUT1 2-sheet output Standard 0 V active (selectable in system configuration)
OUT0 ENABLE output Standard 24 V active (not selectable, for safety reasons)
OUT4 Warning Standard 0 V active (selectable in system configuration)
Attention If the external outputs or inputs are used, then the supply voltage for
6.2.1 Signal „Enable“
The signal ENABLE is always 24V active
The signal is LOW (0V)
• during system operation via keyboard
• in case of system fault
• during a system test
The signal is HIGH (24V)
• when the system is operational
Opto coupler outputs
the outputs / inputs needs to be connected.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
55
Page 56
Manual
Double Sheet Detector-series I20
Communication with the PLC B0069991 / Rev. 1.7
6.2.2 Signal "Warning"
The “Warning“ signal is an additional output signal with fixed evaluation thresholds.
The signal becomes activated if the measurement result is below 80% or above 120% of the preset
nominal value.
Application: If the warning signal is activated though a sheet is between the sensors, measuring
problems might have been occurred:
• Sensor distance changed
• Sheet too close to the transmitter / receiver
• Wrong type of sheet
• Sensor covering not sufficient (3 × sensor diameter)
NoteIf these requirements are met, but a warning signal is issued, then the
Teach-In must be repeated. The requirements from section “4.3 Sensor
mounting“ should be observed.
NoteThe signal will also be activated if measurements without a sheet
(measurement value below 80%) are performed.
56
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 57
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
6.3 Timing diagrams
Notes for the following diagrams and descriptions
For all following diagrams and explanations, in the configuration menu item 11 the setting
”Level 0-1-2” has been selected “0V”.
If “24V” has been selected the outputs OUT1…OUT4 are inverted. Enable OUT0 will not be
influenced by this.
6.3.1 External Single measurement
The measurement result remains frozen until a new action is initiated.
At the moment of changing the output signals, an undefined condition can occur at the outputs, i.e.
all outputs or none can be active. If this condition occurs the outputs have to be interrogated again.
OUT 0
Enable
IN 1-9
Communication with the PLC
Meas. start
IN 0
OUT 1
0-sheet
1-sheet
2-sheet
warning
OUT 3
OUT 2
OUT 4
1
min. 10ms max.4ms
4
min. 4ms
23
5
1 Check whether the output OUT0 “Enable” has been switched to HIGH, otherwise a fault condition is
existing.
2 Before starting a measurement all inputs must be LOW for 10ms.
3 Switch the input IN0 “Measurement Start” to HIGH for at least 4 ms.
4 After max. 4ms the measurement result is available at the outputs OUT1…OUT3.
5 After point 4 or 4 ms after point 3 switch the input IN0 “Measurement Start” to LOW.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Note In case of fault the signal “Enable” will be switched to LOW.
57
Page 58
Manual
Double Sheet Detector-series I20
Communication with the PLC B0069991 / Rev. 1.7
6.3.2 External Continuous measurement / External Special
The control unit measures continuously as long as the signal “Measurement Start” is switched to
HIGH. If the signal “Measurement Start” is switched to LOW, the measurement is aborted and the
last measuring result is frozen until a new cycle is initiated.
When approaching the sheet, the outputs signals switch from 0-sheet to 1-sheet (or 1-sheet to 2sheet respectively). An undefined condition can occur at the outputs, i.e. all outputs or none can be
active. If this condition occurs the outputs have to be interrogated again.
IN 0
Enable
Meas. start
0-sheet
OUT 0
IN 1-9
OUT 3
OUT 1
1-sheet
2-sheet
warning
1
min.10ms
2
max.4ms1 ms1 ms
456
min. 4ms
3
7
OUT 2
OUT 4
1Check whether the output OUT0 “Enable” has been switched to HIGH (ready for operation), otherwise a
fault condition is existing.
2 Before starting a measurement all inputs must be LOW for 10ms.
3 Switch the input IN0 “Measurement Start” to HIGH.
4 After max. 4ms the measurement result is available at the outputs OUT1…OUT3.
5 The measurement result of the second measurement is available at the outputs.
The measurement starts again.
6The measurement result of the third measurement is available at the outputs.
The measurement starts again.
7Switch the input IN0 “Measurement Start” to LOW.
The measurement is aborted, the last measurement result is now available at the outputs OUT1…OUT3.
The measurement result is frozen until a new cycle is initiated.
58
Note In case of fault the signal “Enable” will be switched to LOW.
Note In the “extern special” measurement mode the highest measured
value will be displayed and held at the outputs until a new
measurement is started.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 59
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
6.3.3 System test (Sensor gap control)
In order to check the function of the unit it is possible to check the sensor gap. This test can also be
used as functional check.
No sheet must be present during this test. If the sensor gap has changed, then the unit reports an
error and the output OUT0 “Enable” remains LOW. If the gap is the same as during Teach-In and
the unit is working properly, then the sensor gap control will be performed fault free.
IN0-5, 7-9
IN6
OUT0
OUT4, 3, 2, 1
1
Check whether the output OUT0 “Enable” has been switched to HIGH (ready for operation), otherwise a
fault condition is existing.
All inputs must be LOW for 10 ms before “Test Sensor gap” is activated. No sheet must be present
2
between the sensors.
Switch input IN6 “Test Sensor gap” to HIGH.
3
4
Within 10ms all outputs are switched to LOW.
The system now performs a sensor gap test. The test will be finished within 300ms.
The system now waits for the input IN6 being switched to LOW.
Switch the input IN6 “Test Sensor gap” to LOW.
5
6
All outputs are switched to HIGH. In case of fault the ouput OUT0 “Enable” switches to LOW.
If “Measurement: Demo mode” is configured it is not possible to interrogate the outputs OUT1…OUT4,
because the measurement restarts automatically after finishing the test. Therefore the unit must be
configured to “Measurement: external”.
System test
Enable
0-1-2-sheet; Warning
1
min. 10ms
2
max.10ms
3
4
min. 10ms
Communication with the PLC
max. 10-300ms
5
6
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
59
Page 60
Manual
g
Double Sheet Detector-series I20
Communication with the PLC B0069991 / Rev. 1.7
6.3.4 Program switching
All 255 measuring programs can be selected via the PLC inputs IN1 to IN9.
Attention: The inputs IN2 to IN9 are used also for functions other then the selection of the
measuring programs. This means that the timing has to be followed exactly.
OUT0
IN1
IN2-9
IN0
OUT1, 2, 3, 4
1
Check whether the output OUT0 “Enable” has been switched to HIGH (ready for operation), otherwise a
fault condition is existing.
Before selecting a measuring program all inputs must be switched to LOW for 10 ms.
2
3
Switch the input IN1 “program selection” to HIGH.
4 Simultaneously with 3 or delayed switch the binary value to IN2…IN9.
5 Max. 10ms after having switched IN1 “Program selection” the outputs OUT1…OUT4 are switched to
LOW.
After the binary value has been present for a minimum of 10 ms, switch the input IN1 “Program
6
selection” to LOW.
Simultaneously with 6 or delayed switch back the binary values at IN2…IN9 (switch to LOW).
7
8
After a maximum time of 250ms the outputs OUT1…OUT3 are switched to HIGH.
If the configuration “Measurement: Demo mode” has been selected, measurement will re-start
automatically (if a valid program has been selected). If the configuration “Measurement external” has
been selected, the operation of the unit is then performed via the PLC.
Note:
Program-No. Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
In case of double sheet detection clearing is possible only if the unit is adjusted to “Hold 2-Sheet”.
IN 5
OUT 3
OUT 2
Enable
Clear 2-sheet /
Clear outputs
0-sheet
1-sheet
OUT 0
IN 0-4, 6-9
Communication with the PLC
2-sheet
OUT 1
Warni ng
OUT 4
1
min.10ms
2
1 Check whether the output OUT0 “Enable” has been switched to HIGH (ready for operation),
otherwise a fault condition is existing.
2 All inputs must be LOW for 10ms before “Clear 2-Sheet” is activated.
3 Switch input IN5 "Clear 2-Sheet" to HIGH.
4 Within 10ms the outputs OUT1…OUT4 are set to HIGH.
5 After a minimum time of 10ms switch the input IN5 “Clear 2-Sheet” to LOW.
6 Within 10ms the unit can be operated via the inputs.
max.10msmax.10ms
4
min.10ms
3
5
6
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
61
Page 62
Manual
Double Sheet Detector-series I20
Communication with the PLC B0069991 / Rev. 1.7
6.3.6 Zero adjust
For performing a zero adjust no sheet must be present between the sensors.
Enable
OUT 0
IN 0-9
(without IN 3/4)
Te ac h -i n
IN 3
range
Zero adjust
IN 4
OUT 4, 3, 2, 1
0-1-2-sheet; warning
1
min.10ms max.10ms
2
3
4
min.10ms
5
max.150sec.
6
1 Check whether the output OUT0 “Enable” has been switched to HIGH (ready for operation),
otherwise a fault condition is existing.
2 Before initiating the zero adjust all inputs must be switched to LOW for 10ms.
No sheet must be present between the sensors.
3 Switch the input IN4 “zero adjust” to HIGH.
Then the system performs the zero adjust, which will be completed within 15 seconds.
Now the system waits for the input IN4 to be switched to LOW:
4 Within 10ms the outputs OUT1…OUT4 are switched to LOW.
5 After point 4 or 10ms after point 3 switch the input IN4 “zero adjust” to LOW.
6 The outputs OUT1…OUT4 switch to HIGH.
62
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 63
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
6.3.7 Material detection NF
For performing a “Material detection NF”, a non-ferrous sheet with nominal thickness must be
present between the sensors.
Enable
OUT 0
IN 0-9
(without IN 3/8)
Teach-in
IN 3
range
Material detection NF
IN 8
OUT 4, 3, 2, 1
0-1-2-sheet; warning
Communication with the PLC
1
min.10ms
2
max.10ms
3
4
min.10ms
5
max.7sec.
6
1 Check whether the output OUT0 “Enable” has been switched to HIGH (ready for operation), otherwise a
fault condition is existing.
2Before initiating the material detection, all inputs must be switched to LOW for 10ms.
A sheet of nominal thickness must be present between the sensors.
3 Switch the input IN8 “material detection” to HIGH.
4 Within 10ms the outputs OUT1…OUT4 are switched to LOW.
Now the system determines the electrical conductivity of the NF material. Within 7 seconds the material
detection is completed. Now the system waits for the input IN8 “material detection” being switched to
LOW.
5 After point 4 or 10ms after point 3 switch the input IN8 “material detection” to LOW.
6 The outputs OUT1…OUT4 switch to HIGH.
Note: If “FE” (ferromagnetic material) or operating mode “Frequency” is set, then the material
detection for NF will also be performed, but will be without any effect. There will also no
fault message be displayed.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
63
Page 64
Manual
Double Sheet Detector-series I20
Communication with the PLC B0069991 / Rev. 1.7
6.3.8 Static Teach-In 1-sheet (Part A)
During the static Teach-In one sheet of nominal thickness must be present between the sensors.
In the operating mode "Frequency" (Monitoring Parts for Hardend / Tempered Properties and
Materials Mix up) part A must be placed in the sensor gap.
Enable
OUT 0
IN 0-9
(without IN 2/3)
Teach-in
IN 3
range
Teach-in
IN 2
1-sheet
OUT 4, 3, 2, 1
0-1-2-sheet; warning
1
min.10ms
2
max.10ms
3
4
min.10ms
5
max.7sec.
6
1 Check whether the output OUT0 “Enable” has been switched to HIGH (ready for operation), otherwise a
fault condition is existing.
2Before initiating the static Teach-In 1-sheet, all inputs must be switched to LOW for 10 milliseconds.
One sheet of nominal thickness must be present between the sensors.
3 Switch the input IN2 “Teach-In 1-sheet” to HIGH.
4 Within 10ms the outputs OUT1…OUT4 are switched to LOW.
Then the system performs a Teach-In 1-sheet, which will be completed after max. 7 seconds.
Now the system waits for the input IN2 “Teach-In 1-sheet” being switched to LOW.
5 After point 4 or 10ms after point 3 switch the input IN2 “Teach-In 1-sheet” to LOW.
6 The outputs OUT1…OUT4 switch to HIGH.
64
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 65
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
6.3.9 Dynamic Teach-In 1-sheet (Part A)
During the dynamic Teach-In one sheet of nominal thickness must be driven through the sensors.
In the operating mode "Frequency" (Monitoring Parts for Hardend / Tempered Properties and
Materials Mix up) part A must be drive through the sensor gap.
OUT 0
IN 0-9
(without IN 2/3)
IN 3
IN 2
Enable
Teach-in
range
Teach-in
1-sheet
Communication with the PLC
OUT 4, 3, 2, 1
0-1-2-sheet; warning
1
min.10ms
2
min.10ms
3
4
max.
10ms
5
Teach-in
range
6
>= ms
0,5sec.
78
1 Check whether the output OUT0 “Enable” has been switched to HIGH (ready for operation), otherwise a
fault condition is existing.
2 Before initiating the Teach-In 1-sheet all inputs must be switched to LOW for 10ms.
3 The Teach-In is selected by switching the input IN3 to HIGH.
4 Switch the input IN2 “Teach-In 1-sheet” to HIGH.
5 Within 10ms the outputs OUT1…OUT4 are switched to LOW.
6 After the sheet has been driven through the sensors the input IN3 is switched to LOW.
7 Now switch the input IN2 “Teach-In 1-sheet” to LOW.
8 The Teach-In is completed within 0,5s and the outputs OUT1…OUT4 switch to HIGH.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
65
Page 66
Manual
Double Sheet Detector-series I20
Communication with the PLC B0069991 / Rev. 1.7
6.3.10 Static Teach-In 2-sheet (Part B)
During the static Teach-In two sheets of nominal thickness must be present between the sensors.
In the operating mode "Frequency" (Monitoring Parts for Hardened / Tempered Properties and
Materials Mix up) part B must be placed in the sensor gap.
Enable
OUT 0
IN 0-9
(without IN 3/7)
Teach-in
IN 3
range
Teach-in
IN 7
2-sheet
OUT 4, 3, 2, 1
0-1-2-sheet; warning
1
min.10ms max.10ms
2
3
4
min.10ms
5
max.1sec.
6
1 Check whether the output OUT0 “Enable” has been switched to HIGH (ready for operation), otherwise a
fault condition is existing.
2Before initiating the Teach-In 2-sheet all inputs must be switched to LOW for 10ms.
Two sheets of nominal thickness must be placed between the sensors.
3 Switch the input IN7 “Teach-In 2-sheet” to HIGH.
4 Within 10ms the outputs OUT1…OUT4 are switched to LOW.
Then the system performs the Teach-In procedure, which will be completed within 7 seconds.
Now the system waits for the input IN7 being switched to LOW.
5 After point 4 or 10ms after point 3 switch the input IN7 “Tech-In 2-Sheet” to LOW.
6 The outputs OUT1…OUT4 switch to HIGH.
66
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 67
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
6.3.11 Dynamic Teach-In 2-sheet (Part B)
During the dynamic Teach-In two sheets of nominal thickness must be driven through the sensors.
In the operating mode "Frequency" (Monitoring Parts for Hardened / Tempered Properties and
Materials Mix up) part B must be drive through the sensor gap.
OUT 0
IN 0-9
(without IN 3/7)
IN 3
IN 7
Enable
Teach-in
range
Teach-in
2-sheet
Communication with the PLC
OUT 4, 3, 2, 1
0-1-2-sheet: warning
1
min.10ms
2
min.10ms
3
4
max.
10ms
5
Teach-in
range
>=0ms0,5sec.
6
78
1 Check whether the output OUT0 “Enable” has been switched to HIGH (ready for operation), otherwise a
fault condition is existing.
2 Before initiating the Teach-In 2-sheet all inputs must be switched to LOW for 10ms.
3 The Teach-In is selected by switching the input IN3 to HIGH.
4 Switch the input IN7 “Tech-In 2-sheet” to HIGH.
5 Within 10ms the outputs OUT1…OUT4 are switched to LOW.
6 After the sheet has been driven through the sensors the input IN3 is switched to LOW.
7 Now switch the input IN7 “Tech-In 2-sheet” to LOW.
8 The Teach-In is completed within 0,5s and the outputs OUT1…OUT4 switch to HIGH.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
67
Page 68
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
6.3.12 Reset error
With the “Reset error” function uncritical faults can be redressed.
Critical errors like “cable rupture” can only be redressed with the control unit keys.
1 Before the “Reset error” is initiated, all inputs must be LOW for 10 ms.
2 Switch input IN9 “Reset error” to HIGH.
3 Within 10ms all outputs are switched to LOW.
If the fault can be reset, the output OUT0 will be set to HIGH.
4 Switch the input IN9 “Reset error” to LOW.
5 Within 10ms all outputs are switched to HIGH.
6.4 Internal control (Demo mode)
In this operating mode the system continuously executes measurements and activates
OUT0 … OUT4.
In general, this operating mode is suitable for demonstration purposes only.
Prerequisites:
• Supply voltage applied
• System parameter “Measurement mode” set to “demo”
• Teach-In has been executed
68
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 69
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
7 Start-up
7.1 Initially applying power to the system
The I20 is designed for an operating voltage of 24 VDC (+6 V / -4 V). This voltage is to be checked
before applying power. The control unit is automatically switched on by applying the power.
After applying power, the type of system and the version number are briefly displayed. Then the
system switches into that measurement menu, which was active before the unit was switched off.
If the equipment does not power up, the fuse should be checked.
7.2 Start screen
After applying the supply voltage to the system, the start screen will be shown until the unit has
initialized.
ROLAND ELECTRONIC
I20
SV: 21
Fig. 28: Start screen
It shows the type of system and the software version.
After the control unit is fully operational, the Start screen is replaced by the operations screen.
Start-up
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
69
Page 70
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
7.3 Operation
Note: The system is factory adjusted for “external continuous measurement“.
After applying power to the system and the version number are briefly displayed. Afterwards the
system switches into that measurement menu which was active before the unit was switched off.
Therefore the system functions only if the signal “measurement start“ is
activated via the PLC input. The modification of the configuration is
described in the following sections.
Fig. 29: Frontal view of the I20 with enlarged display detail
LED functions (symbols above the keys)
<
Norm
>
Enable
ON, if the measured value reaches (or falls short of) the lower limit value.
ON, if the measured value is within the lower and upper limit values.
ON, if the measured value reaches (or exceeds) the upper limit value.
- blinks, if a fault is present
- ON, if the equipment is in measurement mode
- OFF, during parameter programming with the keyboard
Key functions (symbols belo w the keys)
▲
▼
Enter
Menu
Changes the parameters (forward)
Changes the parameters (backwards)
Selects a parameter for changing and confirming the change
Activates the menu level, for deleting a fault message and exiting the menu level.
70
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 71
Manual
s
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
7.4 Configuration menu
7.4.1 Main menu structure
Button
MENU
Config.
Review
Program parameter
System adjustment
System configuration
change
(password)
Button
ENTER
Unit-information
7.7
Parameters of the respective measurement program
7.8
Adjustment of this system / sensors
7.9
General system configuration
Start-up
Data backup
Firmware update
Fig. 30: Main structure of configuration menu
7.10
Backup of the data stored in the system
via virtual RS232 (USB)
7.11
Updating the firmware of the system
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
71
Page 72
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
7.4.2 Sub structure “Program parameters” (details in 7.7)
7.4.2.1 Sub structure “Program parameters” (except in operating mode “frequency)
0.000 … 15.00 mm (only in operating mode „Standard)
– FE
– NF (non-ferrous, with conductivity value)
– NF (non-ferrous, without conductivity, unit detects it)
TL% (0-99%) and absolute
Upper limit value TU
Settling time desired / actual2 / 4 / 8 / 15 / 25 / 100 / 250 ms
Teach-in 1-sheet
Teach-in 2-sheet
Fig. 31: Sub structure „program parameters“
TU% (100-180%) and absolute
– ok
– missing
– dynamic all / single
– static all / single
– no
– dynamic all / single
– static all / single
72
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 73
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
7.4.2.2 Sub structure “Program parameters” of the operating mode “Frequency”
(Monitoring Parts for Hardened / Tempered Properties and Materials Mix up)
ext. single meas. / demo mode / ext. c ontinuous meas. / ext. special
yes / no
0VDC / +24VDC
monitoring
– no monitoring
yes / no
only for Service personnel
only for Service personnel
Diagnosticfactor / thickness range
Compensation factor
System infoversions of Software, Hardware-Proc.-board, Hardware-Analog-boar
scheduled
Fig. 34: Sub structure configuration
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
75
Page 76
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
7.5 General information regarding the configuration
Note The correct configuration depends on the communication with the PLC,
The following rules apply to the operation in the configuration mode:
• The configuration mode is activated (while in measurement mode) by pressing the MENU key.
• The configuration mode is terminated or cancelled by pressing the MENU key.
• The selected / set parameters can be changed when the items are blinking in the display.
• The selected / set parameters are activated by pressing the ENTER key.
Note The systems info and bus info is displayed by pressing the ENTER key in
the base menu (compare also system parameter 27).
on the measurement task and the connected components.
7.6 Changing, setting-up or checking the configuration
In order to select, set-up or check the system / program parameters, press the MENU key.
Here either reviewing or changing the configuration can be selected.
Configuration review: The program / adjust / system parameters cannot be changed.
The measurement mode is not interrupted.
configuration
review
Fig. 35: Indication after calling-up the menu
Configuration change: All program / adjust / system parameters can be changed after
entering the password. The following menu option is shown.
76
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 77
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
configuration
change
Fig. 36: Selecting the configuration mode
Available configuration modes:
• Configuration program parameter
• Configuration adjustment parameters
• Configuration system adjust
• Data backup
• Firmware update
Program parameters are application specific adjustments (e.g. input of nominal sheet thickness).
Adjustment parameters are parameter, which are only valid for this individual system; they cannot
be transferred to other systems.
System parameters are general adjustments (e.g. language).
Start-up
Note After exiting the configuration mode the password remains active for five
minutes. Thus other configuration adjustments can be made, without reentering the password. If no key is pressed for five minutes (while in the
menu level), then the program changes to the measurement mode.
For changing parameters, the password must be entered.
password
xxxx
Fig. 37: Password request
Each blinking digit can be changed with the arrow keys and confirmed with ENTER. After having
entered the correct password, the following menu appears for the adjustment of the configuration
mode. The password is factory set to “0000”.
If the entered password is incorrect then the cursor returns to the first digit of the password and the
input must be repeated. The input of the password can be aborted by pressing the MENU button.
Note A fault is generated if PLC commands are executed while entering the
password or changing parameters.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
77
Page 78
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
7.7 Program parameters
7.7.1 Program parameters for the double sheet detection
This menu structure is valid for the system types a – f (For details refer to chapter 3.2)
The program parameters contain the information required for the various measurement programs.
For accessing the program parameters, select the mode “configuration program parameter“ and
confirm with ENTER.
Program parameter 1: Selecting the measuring program to be configured.
Program Parameter: 1
Program Number
1
Fig. 38: Selecting the program to be configured
Here the measuring program (1-255) to be configured is selected. All following adjustments apply
to the selected program.
Program parameter 2: Selecting the sensors to be used for measurement.
Program Parameter: 2
Sensor no./Sequence
Fig. 39: Sensor number / Sequence
Here the sensor pair /sensor pairs is / are selected, which are to be used for measurement.
Possible choices:
• 1 / 2 / 3 / 4
• 1+2 / 1+3 / 1+4 / 2+3 / 2+4 / 3+4
• 1+2+3 / 1+2+4 / 1+3+4 / 2+3+4 / 1+2+3+4
Program parameter 3: Specifying the nominal thickness and material of the sheet to be
measured in mm or inch.
Program Parameter: 3
nominal thickness
0.90mm
This parameter is only in the operating mode
„Standard” available.
Fig. 40: Adjusting the nominal thickness
Here the nominal thickness of the sheet to be measured is specified. Normally, the nominal
thickness is the sheet thickness used for Teach-In.
AttentionA change of the nominal thickness deletes the values
determined during Teach-In. A new Teach-In is required.
78
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 79
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
Program parameter 4: Specifying the material of the sheets to be measured.
Program Parameter: 4
Material
ferrous steel
Fig. 41: Selection of material to be measured
Possible choices:
• Fe (ferrous): Magnetic material.
• NF (non-ferrous): Nonmagnetic material (e.g. Aluminum, austenitic Stainless Steel)
with known conductivity.
• NF?: Nonmagnetic material (e.g. Aluminum, austenitic Stainless Steel)
with unknown conductivity. During Teach-In, the system determines
by itself the conductivity of the material between the sensors.
The user will be asked whether the conductivity is to be determined
Program parameter 5: Setting the percentage threshold of the lower limit value.
now or at a later time.
Start-up
Program Parameter: 5
lower threshold
80% 6.608 mm
Fig. 42: Adjusting the upper limit
Value range: between 0% and 99% of the nominal value, with simultaneously displaying the
absolute limit value.
Program parameter 6: Setting the percentage threshold of the upper limit value.
Program Parameter: 6
upper threshold
120% 12.390 mm
Fig. 43: Adjusting the lower limit
Value range: between 100% and 180% of the nominal value, with simultaneously displaying the
absolute limit value.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
79
Page 80
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
Program parameter 7: Adjusting the nominal settling time and indicating the actual settling time.
Program Parameter: 7
Settling time
desired value:250ms
actual value: 250ms
Fig. 44: Adjusting the nominal settling time
In the upper line the „desired value“ of the settling time must be entered. If the achievable settling
time exceeds the „desired value“, the system selects the next larger possible value and indicates
this value in the line below.
Possible choices:
• 2 / 4 / 8 / 15 / 25 / 100 / 250 ms
In general, the „desired value“ should be set such that it fits the transportation speed and the sheet
length.
• Fast transportation and short sheets require shorter measurement times
Program parameter 8: Teach-In for 1-sheet
Program Parameter: 8
Teach-In 1-sheet
ok
Fig. 45: Status of Teach-In
Possible indications:
• missing: A Teach-In for 1-sheet has not been performed
• OK: A Teach-In for 1-sheet was already performed
• statical: A static Teach-In for 1-sheet will be performed
• dynamical: A dynamic Teach-In for 1-sheet will be performed
80
Note In order to use a parameter set for measurement, a Teach-In for
1-sheet must have been performed.
If no Teach-In is present or if a Teach-In for 1-sheet must be repeated, select “statical“/“dynamical”.
• Statical: The system will perform a punctual Teach-In for 1-sheet.
• Dynamical: The sheet with nominal thickness is moved through the sensor gap while
performing the Teach-In for 1-sheet.
NoteThe position of the sheet for Teach-In for 1-sheet must match with
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
the position in measurement operation. Otherwise the
measurement result can become faulty.
Page 81
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
Static Teach-In 1-sheet:
Program Parameter: 8
Teach-In 1-sheet
feed 1-sheet
then press ENTER
Fig. 46: Teach-In procedure for 1-sheet
The sheet must be moved into mid-position between the sensors. With the ENTER key the
Teach-Infor 1-sheet will be performed.
Dynamic Teach-In 1-sheet:
Program Parameter: 8
Teach-In 1-sheet
drive 1-sheet through
then press ENTER
Fig. 47: Teach-In procedure for 1-sheet
The sheet must be moved through the sensor gap in mid position. With the ENTER key the
measurement value will be stored.
The dynamical Teach-Infor 1-sheet is suitable especially for magnetical conveyor belt applications.
After the Teach-Infor 1-sheet the following message is shown:
Start-up
Program Parameter: 8
Teach-In 1-sheet
finished
push ENTER
Fig. 48: Teach-In finished
Program parameter 9: Teach-In for 2-sheet
Program Parameter: 9
Teach-In 2-sheet
ok
Fig. 49: Status of Teach-In
Possible indications:
• no: No Teach-In for 2-sheet is to be performed
• static: A statical Teach-In for 2-sheet will be performed
• dynamic: A dynamical Teach-In for 2-sheet will be performed
If a Teach-In for 2-sheet is to be repeated, select “statical“ resp. “dynamical”.
• Static: The system will perform a punctual Teach-In for 2-sheet.
• Dynamic: The double sheet with nominal thickness is moved through the sensor gap
while performing the Teach-In for 2-sheet.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
81
Page 82
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
Note The position of the sheet for Teach-In for 2-sheet must match with the
Static Teach-In 2-sheet:
position in measurement operation. Otherwise the measurement result can
become faulty.
Program Parameter: 9
Teach-In 2-sheet
feed 2-sheet
then press ENTER
Fig. 50: Teach-In procedure for 2-sheet
The double sheet must be moved into mid-position between the sensors. With the ENTER key the
Teach-Infor 2-sheet will be performed.
Dynamic Teach-In 2-sheet:
Program Parameter: 9
Teach-In 2-sheet
drive 2-sheet through
then press ENTER
Fig. 51: Teach-In procedure for 2-sheet
The double sheet must be moved through the sensor gap in mid position. With the ENTER key the
measurement value will be stored.
The dynamical Teach-Infor 2-sheet is suitable especially for magnetical conveyor belt applications.
After the Teach-Infor 2-sheet the following message is shown:
Program Parameter: 9
Teach-In 2-sheet
finished
push ENTER
Fig. 52: Teach-In finished
82
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 83
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
7.7.2 Program parameters for the (Monitoring parts for hardened / tempered
properties and materials mix up)
This menu structure is valid for the system type g (for details refer to chapter 3.2)
The program parameters contain the information required for the various measurement programs.
For accessing the program parameters, select the mode “configuration program parameter“ and
confirm with ENTER.
Program parameter 1: Selecting the measuring program to be configured.
Program Parameter: 1
Program Number
1
Fig. 53: Selecting the program to be configured
Here the measuring program (1-255) to be configured is selected. All following adjustments apply
to the selected program.
Program parameter 2: Selecting the sensors to be used for measurement.
Start-up
Program Parameter: 2
Sensor no./ Sequence
Fig. 54: Sensor number / Sequence
Here the sensor pair /sensor pairs is / are selected, which are to be used for measurement.
Possible choices:
• 1 / 2 / 3 / 4
• 1+2 / 1+3 / 1+4 / 2+3 / 2+4 / 3+4
• 1+2+3 / 1+2+4 / 1+3+4 / 2+3+4 / 1+2+3+4
Program parameter 3: Setting the measuring frequency
Program Parameter: 3
frequency
320 Hz
Fig. 55: Setting the measuring frequency
According the measuring task is selected here the frequency. Different frequencies are available,
depending on the sensor type.
Note A change deletes the values determined during the Teach-In and
therefore requires a new Teach-In.
Program parameter 4: not available
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
83
Page 84
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
Program parameter 5: Setting the percentage threshold of the lower limit value.
Program Parameter: 5
lower threshold
80%
Fig. 56: Adjusting the upper limit
Value range: between 0% and 99%
Program parameter 6: Setting the percentage threshold of the upper limit value.
Program Parameter: 6
upper threshold
120%
Fig. 57: Adjusting the lower limit
Value range: between 100% and 180%
Program parameter 7: Adjusting the nominal settling time and indicating the actual settling time.
Program Parameter: 7
settling time I20
desired value:250ms
actual value: 250ms
Fig. 58: Adjusting the nominal settling time
In the upper line the „desired value“ of the settling time must be entered. If the achievable settling
time exceeds the „desired value“, the system selects the next larger possible value and indicates
this value in the line below.
Possible choices:
• 2 / 4 / 8 / 15 / 25 / 100 / 250 ms
In general, the „desired value“ should be set such that it fits the transportation speed and the sheet
length.
• Fast transportation and short sheets require shorter measurement times
Program parameter 8: Teach-In for Part A
Program Parameter: 8
Teach-In part A
ok
Fig. 59: Status of Teach-In Part A
Possible indications:
• missing: A Teach-In for Part A has not been performed
• OK: A Teach-In for Part A was already performed
• static: A static Teach-In for Part A will be performed
• dynamic: A dynamic Teach-In for Part A will be performed
84
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 85
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
If no Teach-In is present or if a Teach-In for Part A is to be repeated, select “statical“ / “dynamical”.
• Static: The system will perform a punctual Teach-In for Part A.
• Dynamic: Part A is moved through the sensor gap during Teach-In.
Static Teach-In Part A:
Program Parameter: 8
search max/min:XXXXX
feed part A
then press ENTER
Fig. 60: Teach-In procedure for Part A
Place part A into the sensor gap. With the value shown in the display the position with the largest
value (positive) or respectively with the smallest value (negative) can be determined (depending on
the application). The Teach-In for part A is completed by pushing the Enter Key.
Dynamic Teach-In Part A:
Note In order to use a parameter set for measurement, a Teach-In for
Part A must have been performed.
Note The position of the Part A for Teach-In must match with the
position in measurement operation. Otherwise the measurement
result can become faulty.
Start-up
Program Parameter: 8
Teach-In part A
drive part A through
then press ENTER
Fig. 61: Teach-In procedure for Part A
The Part A must be moved through the sensor gap in mid position. With the ENTER key the
measurement value will be stored.
After the Teach-Infor Part A the following message is shown:
Program Parameter: 8
Teach-In part A
finished
push ENTER
Fig. 62: Teach-In finished
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
85
Page 86
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
Program parameter 9: Teach-In for Part B
Program Parameter: 9
Teach-In part B
ok
Fig. 63: Status of Teach-In Part B
Possible indications:
• no: No Teach-In for Part B is to be performed
• static: A static Teach-In for Part B will be performed
• dynamic: A dynamic Teach-In for Part B will be performed
If a Teach-In for Part B is to be repeated, select “static“ resp. “dynamical”.
• Static: The system will perform a punctual Teach-In for Part B.
• Dynamic: Part B is moved through the sensor gap during Teach-In.
Note The position of the Part B for Teach-In must match with the
position in measurement operation. Otherwise the measurement
result can become faulty.
Static Teach-In Part B:
Program Parameter: 9
search max/min:XXXXX
feed part B
then press ENTER
Fig. 64: Teach-In procedure for Part B
Place part B into the sensor gap. With the value shown in the display the position with the largest
value (positive) or respectively with the smallest value (negative) can be determined (depending on
the application). The Teach-In for part B is completed by pushing the Enter Key.
Dynamic Teach-In Part B:
Program Parameter: 9
Teach-In part B
drive part B through
then press ENTER
Fig. 65: Teach-In procedure for 2-sheet
The Part B must be moved through the sensor gap in mid position. With the ENTER key the
measurement value will be stored.
After the Teach-Infor Part B the following message is shown:
Program Parameter: 9
Teach-In part B
finished
push ENTER
Fig. 66: Teach-In finished
86
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 87
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
7.8 Adjustment parameters
Adjustment parameters are parameters, which are only valid for this individual system; they cannot
be transferred to other systems.
Adjustment parameter 1: Zero adjust
The Zero adjust procedure must be performed at commissioning and after having exchanged a
sensor.
Attention Before performing a Zero adjust procedure, verify carefully that no
sheet is in the sensor gap.
Adjust Parameter: 1
Zero adjust
no
Fig. 67: Status of Zero adjust
Possible choices:
• no: no Zero adjust to be performed.
• all / yes: All sensors are zero adjusted at the same time.
During the zero adjust the following message is shown:
Start-up
Adjust Parameter: 1
Zero adjust
Zero adjust active
Maximum time 150 sec.
Fig. 68: Display during zero adjust
Note Fault messages are described in the chapter “9 Fault messages“.
When the zero adjust is completed, the following message appears:
Adjust Parameter: 1
Zero adjust
no
Fig. 69: Zero adjust successfully completed
The zero adjust is now completed.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
87
Page 88
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
Adjustment parameter 2: Selection of sensor test.
Adjust Parameter: 2
test Sensor distance
no
Fig. 70: Selection of sensor test
Possible choices:
• no: No sensor test will be performed.
• yes: The operator will be requested to remove all sheets. Then the system performs the
sensor test. If the test was done error-free, “Sensor distance OK“ is displayed. If the
test shows faulty results, “Sensor distance too small” or “Sensor distance too large”
will be shown. Then the sensor distance should be checked / corrected.
Adjustment parameter 3: Indication of the deviation of the sensor distances found.
Adjust Parameter: 3
deviation distance
Fig. 71: Sensor distances
By pressing the ENTER key the deviation of the investigated sensor distances are indicated (when
in „change“ mode).
Fig. 72: Indication of deviation of sensor distances
Adjustment parameter 4: Calculation of the sensor distances.
Adjust Parameter: 4
distance sensors
Fig. 73: Scheduled parameter
By pressing the ENTER key the distance is calculated (in mm / inch).
Adjustment parameter 5: Control of sensors.
Adjust Parameter: 5
control sensors
no
Fig. 74: Control of sensors
Possible choices:
• no: The sensor allocation will not be tested.
• yes: The sensors are checked for correct wiring / allocation.
In case of fault-free test result „Sensor control OK“ will be shown.
88
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 89
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
7.9 System parameters
Note The selected system configuration should be documented in the form
The general adjustments are specified by configuring the system parameters.
For accessing, select the “system parameter configuration“ mode and confirm with ENTER.
System parameter 1: Setting the dialogue language.
System Parameter: 1
language
english
Fig. 75: Selecting the dialogue language
Possible choices:
• English
• German
• Italian
• French
• Spanish
System parameter 2: Determining the type of system.
“System configuration“ in the chapter 13 “Appendix“ or in the equipment
documentation. This information is required in case a system needs to be
exchanged.
Start-up
System Parameter: 2
system type
standard
Fig. 76: system type
Possible choices:
• Standard
• FE + AL 0,5 - 3 mm
• FE + AL 0,1 - 0,8 mm
• FE + Austenit 0,1 - 1 mm
• FE + Austenit 0,5 - 3 mm
• Frequency
• Damping mode
Note The measurement range can be determined in the sensor diagram for the
respective sensor (see chapter 2.3 “Sensors”).
For explanation of “System type” see chapter 3.2.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
89
Page 90
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
System parameter 3: Selecting the dimensions for the display (mm / inch).
When changing the measurement dimensions, then the sheet metal thicknesses of the stored
program parameters are also converted into the new dimension.
System Parameter: 3
display value in
mm
Fig. 77: Selecting the dimension for the display
Possible choices:
• mm / inch only if system type is “standard”.
• %mm / %inch only if system type is not “standard”.
System parameter 4: not available
System parameter 5: Setting the display time
System Parameter: 5
display time
2.0 s
Fig. 78: Setting the display time
The maximal measured values (peak values) will be indicated for the time specified here (holding
time). This time is only for the display.
System parameter 6: not available
System parameter 7: not available
System parameter 8: Deleting all measuring programs.
90
System Parameter: 8
clear prog. param.
no
Fig. 79: Deleting of measuring programs
Possible choices:
• yes
• no
Attention The deletion cannot be undone.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 91
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
System parameter 9: Switching the password function on / off.
System Parameter: 9
no
Fig. 80: Switching the password on / off
Possible choices:
• yes
• no
System parameter 10: Determining a password.
password active
Attention If password protection is not activated, then all parameters can be
Start-up
accessed at any time. This is recommended only during starting-up
the system. For daily operation the password function should be
activated.
System Parameter: 10
set password I20
0000
Fig. 81: Determining a password
The factory setting of the password is “0000”.
System parameter 11: Specifying the number of connected sensors.
System Parameter: 11
pairs of sensors
1
Fig. 82: Specifying the number of sensors for a 4-channel unit
Possible choices:
• 1 pair of sensors
• 2 pairs of sensors
• 3 pairs of sensors
• 4 pairs of sensors
AttentionChanging the current configuration will delete all stored program
parameters. This means that for all types of sheets the nominal
thickness values must be re-entered and the Teach-In must be
performed again.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
91
Page 92
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
System parameter 12: Specifying the type of sensor.
System Parameter: 12
sensor type
IS42-30 / IE42-30
Fig. 83: Specifying the type of sensor
Possible choices:
• IS42-30GS / IE42-30GS (also for ISQ42S / IEQ42S)
• IS20-30GS / IE20-30GS
• ISQ160S / IEQ160S
System parameter 13: Specifying the settling time.
System Parameter: 13
default settlingTime
250 ms
Fig. 84: Specifying the settling time
The settling time is entered here, which will be preset as “desired” settling time in the “Clear
program parameters” step. This time will be used if the existing settling time is lost due to deletion
of the program parameters and a usable setting is no longer available.
System parameter 14: Adjusting the measuring mode.
System Parameter: 14
measure mode
extern continuous
Fig. 85: Adjusting the measuring mode
Possible measurement modes:
• external single: The system measures once if the “Measurement start“ signal is applied
via the external PLC input. Each measurement must initiated
separately. The notes in chapter 6.3.2 „timing diagram single
measurement“ must be observed.
• demonstration:This mode of operation is intended for equipment demonstrations, but
not for normal process operation. The system executes measurements
continuously.
• external continuous: The system executes measurements, as long as
the “Measurement start“ signal is applied via the external PLC input.
external special:As for “external continuous”, but: The highest value reached during a
measurement cycle is displayed and maintained at the outputs until a
new measurement is started.
This also applies for the outputs 0-1-2-Warning.
92
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 93
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
System parameter 15: Specifying the system reaction when 2-sheet is detected.
System Parameter: 15
hold if 2-sheets
no
Fig. 86: Adjusting the 2-sheet reaction
Possible choices:
• no: The outputs (0-sheet, 1-sheet and 2-sheet) are activated according to the number of
sheets between the sensors. The equipment does not block operation if double
sheet is encountered.
• yes: The outputs (0-sheet, 1-sheet and 2-sheet) are activated according to the number of
sheets between the sensors. If double sheet is detected, the output “2-sheet“ is
activated and the equipment is blocked until the 2-sheet condition is cleared.
This condition can be cleared
- through the PLC (clear 2-sheet)
- through the keyboard
System parameter 16: not available
System parameter 17: Setting the output logic (0-sheet, 1-sheet, 2-sheet and warning outputs).
Start-up
System Parameter: 17
Output 0-1-2-warning
24V active
Fig. 87: Setting the output logic
Possible choices:
• 0 V: As shown in the timing diagrams and the wiring diagrams
• +24 V: The outputs 0-sheet, 1-sheet, 2-sheet and warning are inverted, i.e. the respective
signals in the timing diagrams and wiring diagrams must be seen inverted.
NoteThe output “Enable“ is not affected thereby.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
93
Page 94
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
System parameter 18: Setting the method of program selection.
System Parameter: 18
automat.Prog.select.
no
Fig. 88: Setting the method of program selection
Possible choices:
• no: When the program is switched via Fieldbus or I/O, the program number will not be
stored. So the system always starts up with the program which was last selected by
keyboard operation.
• yes: When the program is switched via Fieldbus or I/O, the program number will be
stored. After applying power the system always starts up with the program which
was stored last.
AttentionIf the program is switched often, the memory becomes loaded with
frequent writing cycles and thus becomes destroyed during the
time (lifetime approx. 1.000.000 write cycles).
In this case „no“ should be selected here.
System parameter 19: Setting the monitoring of the PLC voltage.
System Parameter: 19
IN/OUT PLC Voltage
no monitoring
Fig. 89: Setting the monitoring of the PLC voltage
Possible choices:
• no monitoring
• monitoring
If the parameter is set to “monitoring“ and the PLC voltage is not connected, a respective fault
message will be indicated.
Remedy: connect the voltage and then confirm the fault message.
System parameter 20: Deactivating / activating the external adjust via fieldbus.
System Parameter: 20
external adjust
no
Fig. 90: Deactivating / activating the external adjust
Here the external adjust, which is possible via fieldbus with the signals “Teach-In“ and “zero
adjust“, can be deactivated / activated.
Possible choices:
• yes
• no
94
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 95
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
System parameter 21: Setting the internal system zeroing.
System Parameter: 21
Internal analog Zero
no
Fig. 91: Setting the internal system zeroing
This parameter is only for the Service personnel.
System parameter 22: Setting the internal system gain.
System Parameter: 22
Internal analog Gain
Fig. 92: Setting the internal system gain
This parameter is only for the Service personnel.
System parameter 23: not available
System parameter 24: not available
System parameter 25: Diagnostic
Start-up
no
System Parameter: 25
diagnostic
Fig. 93: Diagnostic factors (fixed)
This system param. is used for the equipment diagnostics and shouldn´t be changed by the user.
System parameter 26: Strength of compensation:
System Parameter: 26
compensation factor
0
Fig. 94: Compensation strength
Projected parameter.
System parameter 27: System info:
I20-PR-S-4(1)SV: 1 HVH: 0 HVA: 0
IN/OUT (no Bus) Unit
Fig. 95: System info
1st line: Indication of the system type. The bracketed numeral is the number of activated
sensors, the numeral before is the number of measurement channels (2-channel or 4-
nd
2
line Indication of the versions of Software (SV) and Hardware (Processor board und Analog
This info field can also be displayed during the regular operation by pressing the ENTER key.
channel).
board).
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
95
Page 96
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
7.10 Data backup
For better prevention off loss of data, a data backup procedure is available for the system
configuration and the parameter sets. The backup is made via the upper USB interface on the front
panel. The secured data can be transferred to spare units in case of exchange after a failure.
The data backup is accomplished with the RPP7 software available from ROLAND
(for Win2000 / XP / Vista).
The data backup procedure can be selected in the menu configuration. The following menu is
displayed during the data backup.
Parameter backup
active
Fig. 96: Status of data backup
For backup of data, the upper USB slot on the front panel must be used.
7.11 Firmware update
Roland systems are permanently enhanced. In order to use new functions, firmware update is
required.
For firmware update use the lower front panel USB slot.
Note The firmware update may be performed only by qualified personnel.
On the PC used for firmware update, the actual RPP7 software must be
installed, and the desired firmware version (.bin file) must be available.
The RPP7 software can be found on the supplied CD.
For performing the update, connect the Double Sheet Detector to the lower front panel USB
interface of the PC, using the supplied cable. Then select “Firmware Update” in the configuration
mode.
FIRMWARE UPDATE
connect USB(FLASH)
Fig. 97: Indication for activating firmware update
96
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 97
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
After the USB terminal has been connected to the computer, the following is shown.
FIRMWARE UPDATE
start pressing key
Fig. 98: Messages for activating firmware update
Simultaneously pressing the keys arrow and ENTER activates the firmware update.
Bootloader active
Fig. 99: Start firmware update
The update will then be executed via the RPP7 software.
For operating the RPP7 software please refer to chapter 10, “Maintenance”.
UP and ENTER
FIRMWARE UPDATE
Attention By pressing the both keys the program memory is deleted.
The firmware update must then be performed without disturbance,
in order to keep the system operational.
Start-up
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
97
Page 98
Manual
Double Sheet Detector-series I20
Start-up B0069991 / Rev. 1.7
Blank page
98
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 99
Manual
Double Sheet Detector-series I20
B0069991 / Rev. 1.7
8 Operation
8.1 Abbreviated operating instructions
Note The system is factory adjusted for “external continuous measurement“.
After applying power to the system and the version number are briefly displayed. Afterwards the
system switches into that measurement menu which was active before the unit was switched off.
Therefore the system functions only if the signal “measurement start“ is
activated via the PLC input. The modification of the configuration is
described in the following sections.
Operation
Fig. 100: Frontal view of the I20 with enlarged display detail
LED functions (symbols above the keys)
ON, if the measured value reaches (or falls short of) the lower limit value.
<
Norm
Enable
ON, if the measured value is within the lower and upper limit values.
ON, if the measured value reaches (or exceeds) the upper limit value.
>
- blinks, if a fault is present
- ON, if the equipment is in measurement mode
- OFF, during parameter programming with the keyboard
Key functions (symbols belo w the keys)
▲
▼
Enter
Menu
Changes the parameters (forward)
Changes the parameters (backwards)
Selects a parameter for changing and confirming the change
Activates the menu level, for deleting a fault message and exiting the menu level.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
99
Page 100
Manual
Double Sheet Detector-series I20
Operation B0069991 / Rev. 1.7
In the measuring mode the measured value can be read in the display. The control unit
automatically compares the measured value with the adjusted thresholds. The result is transmitted
via the interface to the PLC and also to the front panel LED's.
During the normal measurement process no further actions on the control units are necessary with
the following few exceptions. The following situations require action directly at the control unit or an
action via the field bus interface:
• Clear fault and error messages (see to chapter “9. Error messages, causes and remedies“)
• Teaching of new types of metal and sheet metal thicknesses
(see section “7.7 Configuration of the program parameters“)
• Clearing a 2-sheet condition (if configured)
The following notes for the measuring operations should be observed:
Note Do not adjust the upper limit (“TU“) above 150 %.
8.2 Entering a measurement program
8.2.1 Entering a measurement program for the double sheet detection
1 Push the MENU key, switch to "change" with the keys and confirm with ENTER key
2 Enter the password (if active)
3 Switch to "program parameter" and confirm with ENTER key
4 Select the desired program number at the control unit
5 Select the active sensor
6 Enter the nominal dimension (nominal thickness of the sheet to be processed)
(only for system type “standard”)
7 Specify the material (if required, perform auto detect for NF material)
8 Adjust lower limit (“low“) to 80% (default setting)
9 Adjust upper limit (“up“) to 120% (default setting)
10 Perform a Teach-In
11 Return into the measurement mode with the MENU key
8.2.2 Entering a measurement program for the system type “Frequency”
(Monitoring Parts for Hardened / Tempered Properties and Materials Mix up)
1 Push the MENU key, switch to "change" with the keys and confirm with ENTER key
2 Enter the password (if active)
3 Switch to "program parameter" and confirm with ENTER key
4 Select the desired program number at the control unit
5 Select the active sensor
6 Select Frequency
7 Adjust lower limit (“low“) to 80% (default setting)
8 Adjust upper limit (“up“) to 120% (default setting)
9 Perform a Teach-In
10 Return into the measurement mode with the MENU key
100
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.