Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the
Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales
office or online at http://literature.rockwellautomation.com
wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all
persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or
application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements
associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the
examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in
this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
) describes some important differences between solid state equipment and hard-
WARNING
Identifies information about practices or circumstances that can cause an explosion in a
hazardous environment, which may lead to personal injury or death, property damage, or
economic loss.
IMPORTANT
ATTENTION
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and
recognize the consequence
SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
surfaces may reach dangerous temperatures.
Allen-Bradley, Rockwell Automation, RSLinx, RSLogix 5000, Stratix 8000, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Page 3
Preface
About This Publication
Who Should Use This
Publication
This publication describes the physical and performance characteristics of the
Stratix 8000 Ethernet Managed Switches. In addition, this publication provides
the following:
• Detailed installation information
• How to use the switch
• Troubleshooting information
This guide does not describe system messages that you might receive or how
to configure your switch. For this information, see the Additional Resources
section on page 6.
This guide is for the person installing Stratix 8000 Ethernet Managed Switches.
We assume that you are familiar with the concepts and terminology of the
Ethernet protocol and local area networking.
5Publication 1783-UM002C-EN-P - April 20095
Page 4
Preface
Additional Resources
These documents contain additional information concerning this Rockwell
Automation product.
This chapter provides a functional overview of the switches and covers these
topics.
TopicPage
About the Switches8
Power and Relay Connector11
Console Port12
Dual-Purpose Uplink Ports12
10/100 Ports13
100BASE-FX Ports13
Rear Panel13
Cabling14
Status Indicators15
CompactFlash Memory Card19
7Publication 1783-UM002C-EN-P - April 20097
Page 8
Chapter 1
About the Switches
The Stratix 8000 Ethernet Managed Switches provide a rugged, easy-to-use,
secure switching infrastructure for harsh environments. You can connect these
switches to network devices such as servers, routers, and other switches. In
industrial environments you can connect any Ethernet-enabled industrial
communication devices including programmable logic controllers (PLCs),
human-machine interfaces (HMIs), drives, sensors, and I/O.
You can mount the switches on a DIN rail in an industrial enclosure, on a wall,
or panel.
Available Switches, Expansion Modules, and SFP Modules
Catalog NumberDescription
Switches
1783-MS06T4 10/100BASE-T Ethernet ports and 2 dual-purpose ports, each with a 10/100/1000BASE-T copper port
and an SFP (small form-factor pluggable) module slot
1783-MS10T8 10/100BASE-T Ethernet ports and 2 dual-purpose ports, each with a 10/100/1000BASE-T copper port
and an SFP (small form-factor pluggable) module slot
Expansion Modules
1783-MX08TExpansion module with 8 10/100BASE-T copper Ethernet ports
1783-MX08FExpansion module with 8 100BASE-FX fiber optic Ethernet ports
1606-XL series (recommended)
1606-XLP series (recommended)
Or equivalent
Spare Components
Catalog NumberDescription
1783-MCFCompactFlash card
Class 2, 24V DC output power supplies
The switch front panel contains the ports, the status indicators, and the power
and relay connectors. The following figures show the 1783-MS10T switch and
expansion module front panels.
You connect the DC power and alarm signals to the switch through two front
panel connectors. One connector provides primary DC power (supply A) and
the major alarm signal, and a second connector (supply B) provides secondary
power and the minor alarm signal. The two connectors are physically identical
and are in the upper left side of the front panel, as shown in the figure below.
The switch accessory pack includes the mating power and relay connectors.
These connectors provide screw terminals for terminating the DC power and
alarm wire and plug into the power and relay receptacles on the front panel.
The positive DC power connection is labeled V, and the return is the adjacent
connection labeled RT, as shown in the figure below.
The switch can operate with a single power source or with dual power sources.
When both power sources are operational, the switch draws power from the
DC source with the higher voltage. If one of the two power sources fail, the
other continues to power the switch.
V
RT
A
A
31783-M
WARNING
When you connect or disconnect the power and relay connector
with power applied, an electrical arc can occur. This could
cause an explosion in hazardous area installations. Be sure that
power is removed from the switch and alarm circuit. Be sure
that power cannot be accidentally turned on or verify that the
area is nonhazardous before proceeding.
Failure to securely tighten the power and relay connector
captive screws can result in an electrical arc if the connector is
accidentally removed.
The power and relay connectors also provide an interface for two independent
alarm relays: the major alarm and the minor alarm. The relays can be activated
for environmental, power supply, and port status alarm conditions and can be
configured to indicate an alarm with either open or closed contacts. The relay
itself is normally open, so under power failure conditions, the contacts are
open. From the Command Line Interface (CLI), you can associate any alarm
condition with one alarm relay or with both relays.
Alarm relays often control an external alarm device, such as a bell or a light. To
connect an external alarm device to the relay, you must connect two relay
contact wires to complete an electrical circuit. Both alarm terminals on the
power and relay connector are labeled A. You can connect them without
regard to polarity.
Publication 1783-UM002C-EN-P - April 200911
Page 12
Chapter 1
See the Stratix 8000 Ethernet Managed Switches Software User Manual,
publication 1783-UM003A, for more information on alarm configuration..
For more information about the power and relay connector, see Chapter 4,
Cable and Connectors.
Console Port
Dual-Purpose Uplink Ports
For configuring, monitoring, and managing the switch, you can connect a
switch to a computer through the console port and the supplied RJ45-to-DB-9
adapter cable. If you want to connect a switch to a terminal, you need to
provide an RJ45-to-DB-25 female DTE adapter. For console-port and
adapter-pinout information, see the Two Twisted-pair Straight-through Cable
Schematic on page 76.
WARNING
The two dual-purpose uplink ports may each be configured for RJ45 (copper)
or SFP (fiber) media types. Only one of these connections in each of the
dual-purpose ports can be active at a time. If both ports are connected, the
SFP module port has priority.
If you connect or disconnect the console cable with power
applied to the switch or any device on the network, an electrical
arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the
area is nonhazardous before proceeding.
To verify switch operation, perform POST on the switch in a
nonhazardous location before installation.
You can set the copper RJ45 ports to operate at 10, 100, or 1000 Mb/s in
full-duplex or half-duplex mode. You can configure them as fixed 10, 100, or
1000 Mb/s (Gigabit) Ethernet ports and can configure the duplex setting.
You can use approved Gigabit (or 100 Mbps) Ethernet SFP modules to
establish fiber-optic connections to other switches. These transceiver modules
are field-replaceable, providing the uplink interfaces when inserted in an SFP
module slot. You use fiber-optic cables with LC connectors to connect to a
fiber-optic SFP module. These ports operate in the full duplex mode only.
12Publication 1783-UM002C-EN-P - April 2009
Page 13
Chapter1
10/100 Ports
100BASE-FX Ports
Rear Panel
You can set the 10/100 ports to operate at 10 or 100 Mb/s in full-duplex or
half-duplex mode. You can also set these ports for speed and duplex
autonegotiation in compliance with IEEE 802.3-2002. (The default setting is
autonegotiate.)
When set for autonegotiation, the port senses the speed and duplex settings of
the attached device. If the connected device also supports autonegotiation, the
switch port negotiates the best connection (that is, the fastest line speed that
both devices support and full-duplex transmission if the attached device
supports it) and configures itself accordingly. In all cases, the attached device
must be within 100 m (328 ft.) of the switch.
The IEEE 802.3-2002 100BASE-FX ports (on the 1783-MX08F expansion
module) provide full-duplex 100 Mb/s connectivity over multimode fiber
(MMF) cables. These ports use a built-in, small-form-factor fixed (SFF)
fiber-optic transceiver module that accepts a dual LC connector. The cable can
be up to 2 km (1.24 miles) in length.
The rear panel of the switches and expansion modules have latches for
installation on either a DIN rail or a wall, as shown in the following figure. The
latches slide outward to position the switch over the DIN rail and slide inward
to secure the switch to a DIN rail. The feet must be extended when mounting
the switch on heavy-duty (35 x 15mm) DIN rail or they may be extended for
improved ventilation when wall mounting.
Foot
Latch
31777-M
Publication 1783-UM002C-EN-P - April 200913
Page 14
Chapter 1
Cabling
100BASE-TX traffic requires Category 5 cable. 10BASE-T traffic can use
Category 3 or Category 4 cables.
When connecting the switch to workstations, servers, and routers,
straight-through cables are normally used. However, the automatic
medium-dependent interface crossover (auto-MDIX) feature of the switch is
enabled by default and will automatically re-configure the ports to use either
straight-through or crossover cable type.
Auto-MDIX Feature
The Auto-MDIX feature is enabled by default. When the auto-MDIX feature
is enabled, the switch detects the required cable type (straight-through or
crossover) for copper Ethernet connections and configures the interfaces
accordingly.
You can use the command-line interface (CLI) to disable the auto-MDIX
feature. See the online help for more information.
14Publication 1783-UM002C-EN-P - April 2009
Page 15
Chapter1
Status Indicators
The switches and expansion modules have these status indicators.
Switch and Port Status Indicators
EIP Mod Status Indicator
EIP Net Status Indicator
Setup Status Indicator
PWR B Status Indicator
IndicatorStateDescription
EIP Mod
(EtherNet/IP module status)
OffNo power. Check the power supply and cabling.
Solid greenThe switch is operating properly.
Flashing
greenThe switch has not been configured as a managed switch (for example,
Express Setup was not performed, no IP address, no password). The
switch is operating as an unmanaged switch.
Flashing redA recoverable minor fault, such as an incorrect configuration, has
occurred.
Solid redA non-recoverable major fault has occurred. Cycle power. If the
problem persists, contact Rockwell Automation Technical Support.
PWR A Status
Indicator
VRTAA
Dual-purpose Port
Status Indicator
Port Status Indicator
31793-M
Flashing green/redThe switch is performing a power-on self-test (POST).
EIP Net
OffNo power or no IP address.
(EtherNet/IP network
status)
• Check the power supply and cabling.
• Make sure switch is properly configured.
Solid greenThe device has at least one established EtherNet/IP connection.
Flashing
greenNo EtherNet/IP connection yet, but the switch has obtained an IP
address.
Flashing redEtherNet/IP connection has timed out.
Solid redDuplicate IP address. The switch has detected that its IP address is
already in use.
Flashing green/redThe switch is performing a power-on self-test (POST).
Publication 1783-UM002C-EN-P - April 200915
Page 16
Chapter 1
IndicatorStateDescription
SetupOffSwitch is configured as a managed switch.
Solid greenSwitch is in initial setup.
Flashing
Solid redSwitch failed to start initial setup or recovery because there is no
PWR A and PWR B
(see PWR A and PWR B
Status Indicators, below)
PortOffNo link.
OffPower is not present on the circuit, or power is not applied to the
Solid greenPower is present on the associated circuit.
Solid greenLink present.
greenSwitch is in one of the following states;
• initial setup
• recovery
• initial setup incomplete
available switch port to which to connect the management station.
Disconnect a device from a switch port, and press the Express Setup
button.
system.
Flashing greenActivity. Port is sending or receiving data.
Flashing amberA link blocked by spanning tree violation is sending or receiving data.
Alternating green/amberLink fault. Error frames can affect connectivity, and errors such as
excessive collisions, CRC errors, and alignment and jabber errors are
monitored for a link-fault indication (RJ45 connection only).
Solid amberPort is not forwarding. Port was disabled by management, an address
violation, or spanning tree violation.
After a port is reconfigured, the port status indicator can remain amber
for up to 30 seconds while spanning tree checks the network for
possible loops.
PWR A and PWR B Status Indicators
If the switch has dual power sources (for redundancy), the switch draws power
from the power source with the higher voltage. If one of the DC power
sources fails, the alternate DC power source powers the switch.
IfThe Status Indicator Color Is
Power is present on the PWR A or PWR B
input
Green
Power is not present on the PWR or PWR B
input
16Publication 1783-UM002C-EN-P - April 2009
Red when power is not present, if switch is
configured for dual input power.
Off if the switch is not configured for
dual-input power.
Page 17
StateDescription
Chapter 1
Dual-purpose Port Status Indicators
The status indicators on a dual-purpose port, as shown in the following figure, show whether
the RJ45 connector or an SFP module is active. The port can be configured as either a
10/100/1000 port through the RJ45 connector or as an SFP module, but not both. The status
indicators show which port is being used, and current port activity.
RJ45 Port In-use and Activity
Status Indicator
RJ45 Port
SFP Module Port In-use and Activity Status Indicator
SFP Module Port
OffNo link.
Solid greenLink present.
Flashing greenActivity. Port is sending or receiving data.
Flashing amberA link blocked by spanning tree is sending or receiving data.
Alternating
green/amber
Link fault. Error frames can affect connectivity, and errors such as excessive collisions, CRC errors, and alignment and
jabber errors are monitored for a link-fault indication (RJ45 connection only).
Solid amberPort is not forwarding. Port was disabled by management, an address violation, or spanning tree violation.
After a port is reconfigured, the port status indicator can remain amber for up to 30 seconds while spanning tree
checks the network for possible loops.
Publication 1783-UM002C-EN-P - April 200917
Page 18
Chapter 1
StateDescription
OffNo link.
Solid greenLink present.
Expansion Module Status Indicators
Flashing greenActivity. Port is sending or receiving data.
Flashing amberA link blocked by spanning tree is sending or receiving data.
Alternating
green/amber
Solid amberPort is not forwarding. Port was disabled by management, an address violation, or spanning tree violation.
Link fault. Error frames can affect connectivity, and errors such as excessive collisions, CRC errors, and alignment and
jabber errors are monitored for a link-fault indication (RJ45 connection only).
After a port is reconfigured, the port status indicator can remain amber for up to 30 seconds while spanning tree checks
the network for possible loops.
18Publication 1783-UM002C-EN-P - April 2009
Page 19
Chapter1
CompactFlash Memory
Card
The switch supports a CompactFlash memory card that makes it possible to
replace the switch without reconfiguring the switch. The slot for the
CompactFlash memory card is on the bottom of the switch as shown in the
following figure.
VRTAA
31792-M
Although the switch is shipped with the CompactFlash memory card installed,
you can insert or remove the CompactFlash memory card by grasping the tab
on the card and either inserting it or removing it from the slot at the bottom of
the switch.
TIP
Refer to Install or Remove the CompactFlash Card on page 47
for more information on inserting and removing the
.
CompactFlash memory card.
Publication 1783-UM002C-EN-P - April 200919
Page 20
Chapter 1
Notes:
20Publication 1783-UM002C-EN-P - April 2009
Page 21
Chapter
Install the Switch
This chapter describes how to install your switch, interpret the power-on
self-test (POST), and connect the switch to other devices.
Read these topics, and perform the procedures in this order.
TopicPage
Installation Guidelines 24
Before You Begin 24
Verify Package Contents 26
Add Modules to the Switch 26
Install the Switch 29
Install or Remove the CompactFlash Card 47
2
Set Up the Switch Initially with Express Setup 48
Configure and Manage the Switch 53
Reset the Switch to Factory Defaults 58
Connect to the Switch Ports 58
Verify Port Connectivity 61
Verify Switch Operation 62
Connect a Computer or a Terminal to the Console Port 62
Run a Power-on Self-test (POST) 63
Verify POST Results 63
Verify POST Results 63
Disconnect Power 64
Install and Remove SFP Modules 64
Connect to SFP Modules 67
21Publication 1783-UM002C-EN-P - April 200921
Page 22
Chapter 2
WARNING
This equipment is intended to be grounded. Ensure that the host is connected to earth ground during
normal use.
Before working on equipment that is connected to power lines, remove jewelry (including rings, necklaces,
and watches). Metal objects will heat up when connected to power and ground and can cause serious
burns or weld the metal object to the terminals.
Do not stack the chassis on any other equipment. If the chassis falls, it can cause severe bodily injury and
equipment damage.
An exposed wire lead from a DC-input power source can conduct harmful levels of electricity. Be sure that
no exposed portion of the DC-input power source wire extends from the power and relay connector.
Ultimate disposal of this product should be handled according to all national laws and regulations.
Do not work on the system or connect or disconnect cables during periods of lightning activity.
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Read the installation instructions before you connect the system to its power source.
This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that the
protective device is rated not greater than 5A.
This unit is intended for installation in restricted access areas. A restricted access area can be accessed
only through the use of a special tool, lock and key, or other means of security.
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring.
This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the
absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or
an electrician if you are uncertain that suitable grounding is available.
This unit might have more than one power supply connection. All connections must be removed to
de-energize the unit.
Only trained and qualified personnel should be allowed to install, replace, or service this equipment.
Ultimate disposal of this product should be handled according to all national laws and regulations.
For connections outside the building where the equipment is installed, the following ports must be
connected through an approved network termination unit with integral circuit protection: 10/100/1000
Ethernet
When installing or replacing the unit, the ground connection must always be made first and disconnected
last.
To prevent the system from overheating, do not operate it in an area that exceeds the maximum
recommended ambient temperature of 167 °F (75 °C).
This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is
suitably designed for those specific environmental conditions that will be present and appropriately
designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure
must be accessible only by the use of a tool.
The enclosure must meet IP 54 or NEMA type 4 minimum enclosure rating standards.
22Publication 1783-UM002C-EN-P - April 2009
Page 23
Chapter2
WARNING
This equipment is intended to be grounded to comply with emission and immunity requirements. Ensure
that the switch functional ground lug is connected to earth ground during normal use.
When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable
enclosure with proper wiring method, for all power, input and output wiring, that complies with the
governing electrical codes and in accordance with the authority having jurisdiction over Class I, Division 2
installations.
Use twisted-pair supply wires suitable for 30 °C (86 °F) above surrounding ambient temperature outside
the enclosure.
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category
II applications (as defined in IEC publication 60664-1), and at altitudes up to 2000 m (6,561.68 ft) without
derating.
Installation of the equipment must comply with local and national electrical codes.
To prevent airflow restriction, allow clearance around the ventilation openings to be at least 105 mm (4.13
in.).
ATTENTION
This equipment is only suitable for use in Class I, Division 2,
Groups A, B, C, D, or non hazardous locations.
Connect the unit only to a Class 2 DC power source.
Publication 1783-UM002C-EN-P - April 200923
Page 24
Chapter 2
Installation Guidelines
When determining where to place the switch, observe these guidelines.
Environment and Enclosure Guidelines
Review these environmental guidelines before installation.
• This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC
publication 60664-1), at altitudes up to 3 km (9842 ft) without derating.
• This equipment is considered Group 1, Class A industrial equipment,
according to IEC/CISPR Publication 11. Without appropriate
precautions, there may be potential difficulties ensuring electromagnetic
compatibility in other environments due to conducted as well as radiated
disturbance.
• This equipment is supplied as open-type equipment. It must be
mounted within an enclosure that is suitably designed for those specific
environmental conditions that will be present and appropriately
designed to prevent personal injury resulting from accessibility to live
parts. The enclosure must have suitable flame-retardant properties to
prevent or minimize the spread of flame, complying with a flame-spread
rating of 5VA, V2, V1, V0 (or equivalent) if nonmetallic. The interior of
the enclosure must be accessible only by the use of a tool.
Before You Begin
24Publication 1783-UM002C-EN-P - April 2009
Keep these points in mind when installing the switch.
• Proper ESD protection is required whenever you handle this
equipment. Installation and maintenance personnel should be properly
grounded by using ground straps to eliminate the risk of ESD damage
to the switch.
• Do not touch connectors or pins on component boards. Do not touch
circuit components inside the switch. When not in use, store the
equipment in appropriate static-safe packaging.
• Personnel responsible for the application of safety-related
Programmable Electronic Systems (PES) shall be aware of the safety
requirements in the application of the system and shall be trained in
using the system.
• Unless panel-mounted, this product is grounded through the DIN rail
to chassis ground. Use zinc-plated yellow-chromate steel DIN rail to
assure proper grounding. The use of other DIN rail materials (such as
aluminum, plastic, and so on.) that can corrode, oxidize, or are poor
conductors, can result in improper or intermittent grounding. Secure the
DIN rail to the mounting surface approximately every 200 mm (7.8 in.),
and use end-anchors appropriately.
Page 25
Chapter 2
Place the Switch
When determining where to place the switch, observe these guidelines
• Before attaching the switch to the network, first verify that the switch is
operational by powering it on and running POST. Follow the
procedures in the Verify Switch Operation section on page 62
• For 10/100 ports and 10/100/1000 ports, the cable length from a
switch to an attached device cannot exceed 100 m (328 ft).
• For 100BASE-FX fiber-optic ports, the cable length from a switch to an
attached device cannot exceed 2 km (6562 ft).
• Operating environment is within the ranges listed in the Stratix 8000
Ethernet Managed Switch Installation Instructions, publication
1783-IN005
.
• Clearance to front and rear panels meet these conditions:
– Front-panel status indicators can be easily read.
– Access to ports is sufficient for unrestricted cabling.
– Front-panel direct current (DC) power and relay connector is within
reach of the connection to the DC power source.
•
Airflow around the switch and through the vents is unrestricted. To
prevent the switch from overheating, provide the following minimum
clearances:
– Top and bottom: 105 mm (4.13 in.)
– Exposed side (not connected to the module): 90 mm (3.54 in.)
– Front: 65 mm (2.56 in.)
• Temperature surrounding the unit does not exceed 75 °C (167 °F)
.
ATTENTION
When the switch is installed in an industrial enclosure, the
temperature within the enclosure is greater than normal room
temperature outside the enclosure.
The temperature inside the enclosure cannot exceed 75
o
F), the maximum ambient enclosure temperature of the
(167
o
C
switch.
• Cabling is away from sources of electrical noise, such as radios, power
lines, and fluorescent lighting fixtures.
Publication 1783-UM002C-EN-P - April 200925
Page 26
Chapter 2
Verify Package Contents
Carefully remove the contents from the shipping container, and check each
item for damage. If any item is missing or damaged, contact your Rockwell
Automation representative for assistance.
If you want to connect a terminal to the switch console port, you need to
provide an RJ45-to-DB-25 female DTE adapter. For multimode (MM)
connections, you can connect a 100BASE-FX port to a port on a target device
by using dual-LC connector.
The switch expansion modules are optional, and do not ship with the switch.
You need to order these separately.
To connect the switch functional ground, you need a ring terminal lug
(such as Thomas & Bett part number 10RCR or equivalent).
.
Add Modules to the Switch
The switches can operate as standalone devices with four or eight Fast
Ethernet ports, respectively. To increase the number of Fast Ethernet ports by
8 or 16, you can connect the optional expansion modules. Depending on the
mix of switches and expansion modules, you can have up to 24 Fast Ethernet
ports. The expansion modules cannot operate as standalone devices.
Expansion Module Configurations
To increase the number of ports, add one or two expansion modules to the
switch. If you are installing only one module, it can be either an 1783-MX08T
copper expansion module, or a 1783-MX08F fiber expansion module. If you
are installing two modules, the first must be an 1783-MX08T copper
expansion module, and the second can be either an 1783-MX08T copper
expansion module, or a 1783-MX08F fiber expansion module. You cannot add
two 1783-MX08F fiber expansion modules.
26Publication 1783-UM002C-EN-P - April 2009
Page 27
The following table lists some port combinations using switch and expansion
modules.
Switch and Expansion Module Port Combinations
Port TypeSwitch and Expansion Modules Combination
100FE
(copper)
4one 1783-MS06T switch
8one 1783-MS10T switch
48one 1783-MS06T switch
12one 1783-MS06T switch
88one 1783-MS10T switch
16one 1783-MS10T switch
128one 1783-MS06T switch
20one 1783-MS06T switch
168one 1783-MS10T switch
24one 1783-MS10T switch
100FX
(fiber optic)
Chapter2
one 1783-MX08F expansion module
one 1783-MX08T expansion module
one 1783-MX08F expansion module
one 1783-MX08T expansion module
one 1783-MX08T expansion module
one 1783-MX08F expansion module
two 1783-MX08T expansion modules
one 1783-MX08T expansion module
one 1783-MX08F expansion module
two 1783-MX08T expansion modules
The following figure displays example combinations of the 1783-MS06T
switch and expansion modules. The same combinations of expansion modules
can be used with a 1783-MS10T switch.
Publication 1783-UM002C-EN-P - April 200927
Page 28
Chapter 2
1
2
3
1
11783-MS06T switch with 1783-MX08T and 1783-MX08F expansion modules (12 copper and 8 fiber optic ports)
21783-MS06T switch with one 1783-MX08F expansion module (4 copper and 8 fiber optic ports)
31783-MS06T switch with one 1783-MX08T expansion modules (12 copper ports)
41783-MS06T switch with two 1783-MX08T expansion modules (20 copper ports)
4
28Publication 1783-UM002C-EN-P - April 2009
Page 29
Chapter2
Install the Switch
Perform these procedures to install the switch.
ATTENTION
If you connect or disconnect the communication cable with
power applied to this module or any device on the network, an
electrical arc can occur. This could cause an explosion in
hazardous location installations.
Be sure that power is removed or the area is nonhazardous
before proceeding.
ATTENTION
If you connect or disconnect wiring while the field-side power
is on, an electrical arc can occur. This could cause an explosion
in hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
ATTENTION
To comply with the CE Low Voltage Directive (LVD), this
equipment must be powered from a source compliant with the
safety extra low voltage (SELV) or protected extra low voltage
(PELV).
To comply with UL restrictions, this equipment must be
powered from a source compliant with Class 2 or Limited
Voltage/Current.
Attach Expansion Modules (optional)
IMPORTANT
The switch can operate as a standalone device with two uplink ports and either
four or eight Fast Ethernet ports, or you can increase the number of Fast
Ethernet ports by 8 or 16 by connecting the expansion modules.
If you are adding expansion modules, attach the expansion
modules to the switch before mounting the switch.
Expansion modules are supplied separately.
Publication 1783-UM002C-EN-P - April 200929
Page 30
Chapter 2
You can install one or two expansion modules, limited to these four
combinations:
•
one copper expansion module (1783-MX08T)
• one fiber expansion module (1783-MX08F)
• two copper expansion modules
• one copper and one fiber expansion module
TIP
Only one 1783-MX08F expansion module is allowed per switch.
If a 1783-MX08F fiber expansion module is used in a system
with a 1783-MX08T copper expansion module, the fiber
expansion module must be installed in the right-most position.
Switch
1783-MX08T
Copper
Expansion
Module
1783-MX08F
Fiber
Expansion
Module
Depending on the mix of switches and expansion modules, you can have up to
24 10/100 ports.
Follow these steps to connect the expansion modules to the switch.
IMPORTANT
You must add expansion modules to the base unit before
applying power to the switch. Remove power from the switch
when reconfiguring it.
TIP
If you are not using expansion modules, skip these steps. Go on
to the Mount the Switch section on page 32.
1. Remove the right side panel by firmly grasping both sides of it in the
middle and pulling it outward.
30Publication 1783-UM002C-EN-P - April 2009
Page 31
If necessary, use a screwdriver to pry open the side panel.
31779-M
2. Remove the protective EMI-connector cover from the side panel.
Chapter2
31787-M
3. Push the upper module latches up and the lower module latches down.
Then slide the switch and module together.
31780-M
TIP
The expansion module is shown with the side panel removed.
Do not remove this panel unless you plan to install another
module.
Publication 1783-UM002C-EN-P - April 200931
Page 32
Chapter 2
4. Push the upper and lower module latches in to secure the module to the
switch.
31781-M
5. If you are installing a second module, repeat steps 1...4, but secure the
second module to the right side of the first module.
IMPORTANT
You cannot install an expansion module to the right of
1783-MX08F fiber expansion module.
Mount the Switch
You can mount the switch in one of two ways:
• On a DIN rail
• On a wall or panel
Mount the Switch on a DIN Rail
ATTENTION
When mounting the switch on a DIN rail, you can ground the
switch through the DIN rail to chassis ground. Use zinc plated
yellow-chromate steel DIN rail to assist in proper grounding.
The use of other DIN rail materials (for example, aluminum or
plastic)) that can corrode, oxidize, or are poor conductors, can
impede proper grounding. Secure DIN rail to mounting surface
approximately every 200 mm (7.8 in.) using end-anchors
appropriately and using a washer plate along the entire length
of the DIN rail.
Follow these steps to mount the switch on a DIN rail.
32Publication 1783-UM002C-EN-P - April 2009
Page 33
Chapter2
1. Insert a sharp tool such as a screwdriver in the space next to the tab,
push gently to release the catch, then turn the screwdriver to push the
tab out.
31776-M
2. If you are using a heavy-duty 35 mm x 15 mm (1.38 in. x 0.59 in.) DIN
rail, rotate all feet to the extended positions.
Otherwise, if you are using 35 mm x 7.5 mm (1.38 in. x 0.30 in.) DIN rail,
rotate the feet to the recessed positions.
Foot
Latch
31777-M
3. Position the rear panel of the switch directly in front of the DIN rail,
making sure that the DIN rail fits in the space between the two latches.
DIN Rail
Latch
31778-M
Publication 1783-UM002C-EN-P - April 200933
Page 34
Chapter 2
4. Push the DIN rail latches in after the switch is over the DIN rail to
secure the switch to the rail.
5. Ground the switch.
Refer to
Ground the Switch on page 38.
6. Wire the switch.
Refer to
Wire the DC Power Source on page 40.
34Publication 1783-UM002C-EN-P - April 2009
Page 35
Chapter2
Install the Switch on a Wall or Panel
The switch can be installed on a wall or a panel. To attach the switch to a wall
or a panel, follow these steps.
IMPORTANT
If you are installing expansion modules, attach the expansion
modules to the switch before mounting the switch.
TIP
You will need M5 or #10-24 or #10-32 bolts or screws with 1.27
cm (0.5 in.) O.D. flat washers. This hardware is not provided
with the switch.
1. If the DIN rail latches are pushed out, push them in so they are fully
locked in place.
31777-M
2. Rotate all feet to their recessed positions so that the switch can mount
flat on the wall or panel.
TIP
If greater air circulation around the switch is required, rotate
the feet to their extended positions before mounting the switch
on the wall.
Publication 1783-UM002C-EN-P - April 200935
Page 36
Chapter 2
1. Position the rear panel of the switch against the wall or a panel in the
desired location, as shown in this figure.
rwP)CDV
A
2(
4
V
CD
o
r
4
8
RA
t
n
ojaMlA
r
a
r
m
!
RAW
N
hTim th
i
s
NI
u
n
i
t
G
g
h
p
a
o
v
e
w
e
m
r
o
c
o
er
t
r
h
.d
a
n
T re t
o
no
e
letri s cc
e
c
ud
c
e
h
h
e
o
ris
k
d
kf
p
i
o
s
o
c
w
o
e
n
r
n
e
c
roc
t
d
t
s
b
e
eh
t
f
roi
e
ow
es
vr
c
gni
nu
i
t
.
rwP
B
2(
4
V
D
C
ro
DV
4
8
)C
R
t
n
B
M
i
on
r
A
l
a
mr
E
x
p
r
se
s
S
e
S
y
s
t
me
A
l
a
mr
Spu
te
1
2
1
t
pu
wP
r
A
rwP
B
3
4
siC
oc
C
lata
y
s
t
1. Place M5 or #10-24 or #10-32 bolts or screws with 1.27 cm (0.5 in.)
O.D. flat washers through each DIN rail latch, and screw them into the
wall.
1. Ground the switch.
Refer to
Ground the Switch on page 38.
36Publication 1783-UM002C-EN-P - April 2009
Page 37
Install the SFP Module (optional)
Chapter 2
ATTENTION
SFP modules are static sensitive devices. Always use an ESD
wrist strap or similar individual grounding device when
handling SFP modules.
IMPORTANT
Using an SFP module other than those provided by Rockwell
Automation will disable the switch port.
IMPORTANT
Installing and removing an SFP module can shorten its useful
life. Do not remove and insert SFP modules more often than is
absolutely necessary.
Grasp the module on the sides, and insert it into the switch slot until you feel
the connector snap into place.
31782-M
ATTENTION
Publication 1783-UM002C-EN-P - April 200937
If the SFP module cannot be fully inserted, stop! Do not force the module into
the slot. Rotate the SFP module 180 degrees and try again.
Page 38
Chapter 2
Ground the Switch
Follow these steps to connect the switch to a protective ground.
ATTENTION
For proper grounding, you must always connect the power
supply functional-ground screw when connecting the power
supply. You must provide an acceptable grounding path for each
device in your application. For more information on proper
grounding guidelines, refer to publication 1770-4.1
, Industrial
Automation Wiring and Grounding Guidelines.
ATTENTION
You must use the external grounding screw on the front of the
2
switch to ground the switch. Use a 5.3 mm
(10 AWG) ground
wire.
1. Use a standard Phillips screwdriver or a ratcheting-torque screwdriver
with a Phillips head to remove the ground screw from the front panel of
the switch.
2. Store the ground screw for later use.
3. If your ground wire is insulated, use a wire stripping tool to strip the 5.3
2
(10 AWG) ground wire to 12.7 mm (0.5 in.) ± 0.5 mm (0.02 in.).
mm
12.7 mm (0.5 in.)
31789-M
4. Insert the ground wire into the ring terminal lug.
38Publication 1783-UM002C-EN-P - April 2009
Page 39
Chapter2
5. Using a crimping tool, crimp the ring terminal to the wire.
31790-M
6. Slide the ground screw through the ring terminal.
7. Insert the ground screw into the ground-screw opening on the front
panel.
VRTAA
31791-M
8. Using a ratcheting torque screwdriver, tighten the ground screw and ring
terminal lug to the switch front panel to
0.96 N•m (8.5 lb•in).
9. Attach the other end of the ground wire to a grounded bare-metal
surface, such as a ground bus, or a grounded DIN rail.
Publication 1783-UM002C-EN-P - April 200939
Page 40
Chapter 2
Wire the DC Power Source
WARNING
Before performing any of the following procedures, make sure
that power is removed from the DC circuit or the area is
nonhazardous before proceeding.
ATTENTION
To comply with the CE Low Voltage Directive (LVD), this
equipment must be powered from a source compliant with the
safety extra low voltage (SELV) or protected extra low voltage
(PELV).
To comply with UL restrictions, this equipment must be
powered from a source compliant with Class 2 or Limited
Voltage/Current.
Follow these steps to prepare the DC power cable.
1. Locate the power and alarm relay connector.
V
RT
A
A
31783-M
2. Identify the positive and return DC power connections on the
connector.
The positive DC power connection is labeled V, and the negative DC power
connection is the adjacent connection labeled RT.
TIP
3. Measure a length of 0.82…0.52 mm
Connections labeled A are used for the alarm relay connectors.
2
(18…20 AWG) copper wire long
enough to connect to the DC power source.
4. Using an 18-gauge wire-stripping tool, strip each of the two wires to 6.3
mm (0.25 in.) ± 0.5 mm (0.02 in.).
40Publication 1783-UM002C-EN-P - April 2009
Page 41
Chapter2
Do not strip more than 6.8 mm (0.27 in.) of insulation from the wire. Stripping
more than the recommended amount of wire can leave exposed wire from the
connector after installation.
6.8 mm (0.27 in.)
31784-M
5. Insert the exposed part of the positive wire into the connection labeled
V and the exposed part of the return wire into the connection labeled
RT.
Make sure that you cannot see any wire lead. Only wire with insulation
should extend from the connector.
VRTA A
V
RT
31785-M
6. Use a ratcheting-torque screwdriver to torque the power and relay
connector captive screws (above the installed wire leads) to 0.23 N•m
(2.0 lb•in.).
7. Connect the other end of the positive wire (the one connected to V) to
the positive terminal on the DC power source, and connect the other
end of the return wire (the one connected to RT) to the return terminal
on the DC power source.
TIP
You can use a second power source to provide redundant
power.The alarm relays on the switch can be used to warn you
if one of the power supplies fails. The switch will operate
properly with only one power source connected at either Pwr A
or Pwr B.
8. If you are installing the switch and are using a second power source,
repeat steps 3...7 with a second power and relay connector.
ATTENTION
If multiple power sources are used, do not exceed the specified
isolation voltage.
Publication 1783-UM002C-EN-P - April 200941
Page 42
Chapter 2
Attach the Power and Relay Connector
Follow these steps to connect the DC power and relay connector to the switch:.
ATTENTION
The input voltage source of the alarm circuits must be an
isolated source and limited to less than or equal to 30V DC, 1 A.
1. Insert the power and relay connector into the Pwr A receptacle on the
switch front panel.
VRTA A
31786-M
2. Use a screwdriver to tighten the captive screws on the sides of the power
and relay connector.
42Publication 1783-UM002C-EN-P - April 2009
Page 43
Chapter2
3. If a second power source is required (for redundancy), insert a second
power and relay connector into the Pwr B receptacle on the switch front
panel
.
VRTA A
VRTA A
31788-M
ATTENTION
If multiple power sources are used, do not exceed the specified
isolation voltage.
4. Use a screwdriver to tighten the captive screws on the sides of the
second power and relay connector.
Publication 1783-UM002C-EN-P - April 200943
Page 44
Chapter 2
Wire the External Alarms (Optional)
This procedure is optional.
The alarm relays on the switch are normally open. To connect an external
alarm device to the relays, you must connect two relay contact wires to
complete an electrical circuit. Because each external alarm device requires two
connections to a relay, the switch supports a maximum of two external alarm
devices.
ATTENTION
The input voltage source of the alarm circuits must be an
isolated source and limited to less than or equal to 50Vdc, 1A.
For wire connections to the power and relay connector, you
must use UL and CSA rated, style 1007 or 1569 twisted-pair
copper appliance wiring material (AWM) wire (such as Belden
part number 9318).
To wire the switch to an external alarm device, follow these steps:
1. Measure two strands of twisted-pair wire (18...20 AWG) long enough to
connect to the external alarm device.
2. Use a wire stripper to remove the casing from both ends of each wire to
6.3 mm (0.25 in.) ± 0.5 mm (0.02 in.).
IMPORTANT
Do not strip more than 6.8 mm (0.27 in.) of insulation from the
wires. Stripping more than the recommended amount of wire
can leave exposed wire from the power and relay connector
after installation.
3. Insert the exposed wires for the external alarm device into the two
connections labeled A, as shown in the following figure.
44Publication 1783-UM002C-EN-P - April 2009
Page 45
Chapter2
1
2
6
24
!
!
-
1External device, relay wire A connection 12External device, relay wire A connection 2
4. Use a flat-head screwdriver to torque the power and relay connector
captive screw (above the installed wire leads) to 0.23 N•m (2.0 lb•in.).
VRTA A
V
RT
31785-M
5. Repeat steps 1...4 to insert the input and output wires of an additional
external alarm device into the second power and relay connector.
The following figure shows the completed wiring for two power
supplies and two external alarm devices.
Publication 1783-UM002C-EN-P - April 200945
Page 46
Chapter 2
-
24
!
6
!
24
!
6
!
1
2
3
4
5
6
7
8
1Power source A positive connection5Power source B positive connection
2Power source A return connection6Power source B return connection
3External device 1, relay wire major alarm
connection
4External device 1, relay wire major alarm
connection
7External device 2, relay wire minor alarm
connection
8External device 2, relay wire minor alarm
connection
6. Refer to Attach the Power and Relay Connector on page 42 for
instructions on how to connect the power and relay connector to the
front panel.
46Publication 1783-UM002C-EN-P - April 2009
Page 47
Chapter2
Install or Remove the
CompactFlash Card
Follow this procedure to install or remove the CompactFlash card.
WARNING
When you insert or remove the CompactFlash Card while power
is on, an electrical arc can occur. This could cause an explosion
in hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
Install or remove the CompactFlash card by grasping the tab on the card and
either inserting it or removing it from the slot at the bottom of the switch.
VRTAA
31792-M
IMPORTANT
You can install and remove the CompactFlash card while the
switch is powered. However, If you do not have a CompactFlash
card installed in the switch, you will be unable to do the
following:
• start the Device Manager web interface when you apply power to
the switch
• save configuration changes you made with the AOP via RSLogix
5000 software
• boot up the switch (the POST will not begin)
Publication 1783-UM002C-EN-P - April 200947
Page 48
Chapter 2
Set Up the Switch Initially
with Express Setup
When you first set up the switch, use Express Setup to enter the initial IP
address. Doing this enables the switch to be used as a managed switch. You
can then access the switch through the IP address for additional configuration.
You need this equipment to set up the switch:
• A personal computer with Windows 2000, Windows Vista, Windows
2003, or XP operating system installed.
• A web browser (Internet Explorer 6.0, Internet Explorer 7.0, or Firefox
2.0) with JavaScript enabled.
• A straight-through or crossover Category 5 Ethernet cable to connect
your personal computer to the switch.
Do the following to configure your computer:
• Disable any wireless interface running on your personal computer.
• Disable other networks in your system.
• Set up the DHCP protocol for Auto IP, not static.
• Disable the static DNS server.
• Disable browser proxy settings.
Typically, browser settings are located in Tools>Internet
Options>Connections>LAN Settings.
Follow these steps to run Express Setup.
1. Make sure that at least one switch Ethernet port is available for Express
Setup.
IMPORTANT
During Express Setup, the switch acts as a DHCP server. If your
personal computer has a static IP address, change your personal
computer settings before you begin to temporarily use DHCP.
2. Apply power to the switch.
When the switch powers on, it begins the power-on self-test (POST).
During POST, the status indicators flash while a series of tests verify
that the switch functions properly. Wait for the switch to complete
POST, which takes approximately 3 minutes.
Do not use the console port for Express Setup.
3. Make sure that POST has completed by verifying that the EIP Mod and
Setup status indicators are flashing green.
48Publication 1783-UM002C-EN-P - April 2009
Page 49
Chapter2
If the switch fails POST, the EIP Mod status indicator turns red.
VRTAA
EIP Mod Status Indicator
Setup Status Indicator
31793-M
4. Press and release the Express Setup button. Wait for a few seconds until
the status indicator on one of the unconnected switch ports flashes
green.
This button is recessed 16 mm (0.63 in.) behind the front panel. Use a
small tool, such as a paper clip, to reach the button.
VRTAA
Express Setup
Button
31793-M
5. Connect a Category 5 Ethernet cable (not provided) from the flashing
switch port to the Ethernet port on your personal computer.
VRTAA
31794-M
TIP
If you wait too long to connect the cable, the Setup status
indicator turns off. Go back to step 4 on page 49.
The port status indicators on your personal computer and on the switch
both flash while the switch configures the connection.
Publication 1783-UM002C-EN-P - April 200949
Page 50
Chapter 2
6. While the Setup status indicator flashes green, start an Internet browser
session on the personal computer.
The switch prompts you for the default switch username and password.
7. Leave the username field blank.
8. Enter the default switch password, switch.
The Express Setup dialog box automatically appears.
9. If the window does not appear, do the following:
• enter the URL of a well-known website in your browser to be sure the
browser is working correctly.
Your browser will then automatically be directed to the Express Setup
web page.
• verify that any proxy settings or pop-up blockers are disabled on your
browser.
• verify that any wireless interface is disabled on your personal computer. .
TIP
You may also enter the URL
http://169.254.0.1/express-setup.htm
to access the Express
Setup page directly.
50Publication 1783-UM002C-EN-P - April 2009
Page 51
10. Enter the network settings.
Chapter2
All entries must be English letters and Arabic numbers.
In this fieldDo this
Management Interface (VLAN)The default is VLAN 1. Do not change from the default setting unless instructed to do so by your
IT department. To change to a setting other than the default, use the Device Manager web
interface to avoid losing your switch connection. Do not change the setting until after Express
Setup is complete.
IP Assignment ModeWe recommend using the default, Static, which means that the switch always has the IP
address that you assign. Use the DHCP setting when you want the switch to automatically
obtain an IP address from a DHCP server.
IP AddressEnter the IP address for the switch. (Later, you can use the IP address to access the switch
through the Device Manager web interface.)
Subnet MaskSelect a mask from the pull-down list.
Default Gateway (optional)Enter the IP address of the router.
PasswordEnter a password. The password can be from 1...25 alphanumeric characters, can start with a
number, is case sensitive, but does not allow spaces. In the Confirm Password field, enter the
password again
11. Enter the optional settings now, or enter them later by using the Device
Manager web interface.
Refer to
Use the Device Manager Web Interface on page 53.
In this fieldDo this
Host NameEnter a Host Name for the switch.
Date and Time FieldsThe date and time fields may be populated from your personal computer. If they re not
automatically populated, enter the date and time.
Daylight Saving TimeClick Enable to use Daylight Saving Time.
Publication 1783-UM002C-EN-P - April 200951
Page 52
Chapter 2
TIP
For more information about the optional settings, from the
toolbar, click Help.
1. Click Submit to save the information that you entered and to finish the
basic configuration.
• Once you click Submit, the switch initializes its configuration for
typical industrial EtherNet/IP applications.
The switch then re-directs you to the Device Manager web interface
logon pages. From here, you can continue to launch the Device
Manager web interface for further configuration, or exit.
• If you click Cancel, the fields are cleared, and you can start over.
2. Turn off DC power at the source, disconnect all cables to the switch,
and install the switch in your network.
Refer to
Configure and Manage the Switch on page 53 for information
about configuring and managing the switch.
3. After you complete Express Setup, refresh the personal computer IP
address.
• For a dynamically-assigned IP address, disconnect the personal
computer from the switch, and reconnect the personal computer to
the network. The network DHCP server assigns a new IP address to
the personal computer.
• For a statically-assigned IP address, change it to the previously
configured IP address.
52Publication 1783-UM002C-EN-P - April 2009
Page 53
Chapter2
Configure and Manage the
Switch
After you complete Express Setup, you can further configure and manage the
switch by using one of these options:
• Device Manager web interface (supplied with the switch)
• RSLogix 5000 software, version 16 or later
• Cisco Network Assistant (CNA)
• The switch software’s command line interface (CLI)
• SNMP management applications
Use the Device Manager Web Interface
You can manage the switch by using the Device Manager web interface to
simplify configuration and monitoring of the switch. You can access the
Device Manager web interface from anywhere in your network through a Web
browser.
Follow these steps:
1. Launch a Web browser on your personal computer or workstation.
2. Enter the switch IP address in the web browser, and click Enter.
You see the Device Manager web interface page.
3. Use the Device Manager web interface to perform basic switch
configuration and monitoring.
See the Device Manager web interface online help and the Stratix 8000
Software User Manual, publication 1783-UM003
, for more information.
Publication 1783-UM002C-EN-P - April 200953
Page 54
Chapter 2
Use RSLogix 5000 Software
The RSLogix 5000 software add-on profile (AOP) lets you set up an I/O (CIP)
connection to the switch, and configure and monitor the switch.
Follow this procedure to add the switch to the controller’s I/O tree.
IMPORTANT
These steps are required before you can go online to configure
and monitor the switch.
1. Open the project file for the controller that will be monitoring the
switch.
2. Select the Ethernet module through which the controller will
communicate with the switch.
In this example, the switch communicates through a 1769-L32E
CompactLogix EtherNet/IP controller.
1. Add the switch to the project.
a. Right-click on the Ethernet port you created and choose New
Module.
b. Click Communications.
54Publication 1783-UM002C-EN-P - April 2009
Page 55
Chapter2
c. Click on the + sign and scroll down until you see the Stratix 8000
switch you want to configure.
TIP
If you do not see the switch on the list, you may need to obtain
the AOP from the Rockwell Automation support website.
1. Go to http://www.rockwellautomation.com/support/.
3. Select the 1783-Stratix 8000 Managed Switches Add-on Profile.
d. Click OK.
4. From the Module Properties dialog box, enter this information.
On this tabIn this fieldEnter
GeneralNameA name you choose for the switch
DescriptionA description that helps you remember something important about the
IP AddressEnter the IP address you added when you performed the Express Setup.
Publication 1783-UM002C-EN-P - April 200955
switch
Page 56
Chapter 2
1. Click OK.
The switch is added to the project.
2. Go online with the switch by choosing Communications online.
You can now configure and monitor the switch using the switch AOP.
For more information on using the switch AOP, refer to the Stratix 8000
Managed Ethernet Switch Software User manual, publication
1783-UM003.
Download Cisco Network Assistant
Cisco Network Assistant is a software tool that you download from Cisco.com
and run on your personal computer. It offers advanced options for configuring
and monitoring multiple devices, including switches, switch clusters, switch
stacks, routers, and access points.
Follow these steps to use the software.
1. Go to http://www.cisco.com/go/NetworkAssistant.
You must be a registered Cisco.com user, but you need no other access
privileges.
2. Find the Network Assistant installer.
3. Download the Network Assistant installer, and run it.
You can run it directly from the Web if your browser offers this choice.
4. When you run the installer, follow the displayed instructions.
5. In the final panel, click Finish to complete the Network Assistant
installation.
See the Network Assistant online help for more information.
56Publication 1783-UM002C-EN-P - April 2009
Page 57
Chapter2
Use the Command-Line Interface
You can manage the switch from the command-line interface (CLI) by
connecting your personal computer directly to the switch console port or
through the network by using Telnet. This procedure explains how to access
the CLI through the console port.
1. Connect the supplied RJ45-to-DB-9 adapter cable to the standard 9-pin
serial port on the personal computer.
2. Connect the other end of the cable to the console port on the switch.
WARNING
3. Start a terminal-emulation program on the personal computer.
4. Configure the personal computer terminal emulation software for 9600
bits per second, 8 data bits, no parity, 1 stop bit, and no flow control.
5. Use the CLI to enter commands to configure the switch.
See the Cisco Switch Command Reference Manual, available at
http://www.cisco.com
The console port is intended for temporary local programming
purposes only and not intended for permanent connection. If
you connect or disconnect the console cable with power
applied to this module or the programming device on the other
end of the cable, an electrical arc can occur. This could cause
an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before
proceeding.
for more information.
Use SNMP Management Applications
You can use SNMP management applications such as IntraVue by Network
Vision or HP OpenView to configure and manage the switch.
Publication 1783-UM002C-EN-P - April 200957
Page 58
Chapter 2
Reset the Switch to Factory
Follow this procedure if you need to restore the switch to its factory default settings.
Defaults
Connect to the Switch Ports
This section describes how to connect to these ports.
TIP
1. Remove power from the switch.
2. Reapply power to the switch.
3. While the switch is powering up, press and hold the Express Setup
button.
4. When the EIP Mod, EIP Net and Setup status indictors turn red, release
the Express Setup button.
The switch continues powering up in its factory default state.
5. Follow the Set Up the Switch Initially with Express Setup
page 48
This procedure resets the switch to its original factory settings.
Any configuration changes you may have made will be lost.
procedure on
to reconfigure the switch.
• 10/100 copper ports
• dual-purpose uplink (10/100/1000 and SFP fiber) ports
• 100BaseFX fiber ports
For simplified cabling, the automatic medium-dependent interface crossover
(auto-MDIX) feature is enabled by default on the switch. With auto-MDIX
enabled, the switch detects the required cable type for copper Ethernet
connections and configures the interfaces accordingly. Therefore, you can use
either a crossover or a straight-through cable for connections to a switch
10/100 or 10/100/1000 Ethernet port, regardless of the type of device on the
other end of the connection.
58Publication 1783-UM002C-EN-P - April 2009
Page 59
Chapter2
Connect to 10/100 Copper Ports
1. Insert a straight-through, twisted four-pair, Category 5e or better cable
with an RJ45 connector into the port.
VRTAA
To 10/100 ports
31795-M
2. Insert the other cable end into an RJ45 connector on the other device.
Connect to Dual-purpose Uplink (10/100/1000 and SFP Fiber) Ports
The switches have two dual-purpose uplink ports. Each dual-purpose uplink
port has a 10/100/1000 RJ45 connector for a copper interface, and a slot for
an SFP module.
Only one port of each dual-purpose port can be active at a time. If an SFP
module port is connected, the SFP module port has priority.
Connect to 10/100/1000 Ports
1. Insert a straight-through, twisted four-pair, Category 5e or better cable
with an RJ45 connector into the port.
VRTA A
To 10/100/1000 ports
31795-M
2. Insert the other cable end into an RJ45 connector on the other device.
Publication 1783-UM002C-EN-P - April 200959
Page 60
Chapter 2
Connect to SFP Fiber Ports
Follow this procedure if you have installed an optional SFP module.
ATTENTION
Class 1 laser product. Laser radiation is present when the
system is open and interlocks bypassed. Only trained and
qualified personnel should be allowed to install, replace, or
service this equipment.
TIP
For detailed instructions on installing, removing, and
connecting to SFP modules, see the documentation that
shipped with the SFP module.
1. Insert a fiber optic cable with an LC connector into the SFP module
(installed in the SFP fiber port).
VRTA A
31796-M
2. Insert the other cable end into the other device.
60Publication 1783-UM002C-EN-P - April 2009
Page 61
Connect to 100BaseFX Ports
Chapter 2
ATTENTION
Class 1 laser product. Laser radiation is present when the
system is open and interlocks bypassed. Only trained and
qualified personnel should be allowed to install, replace, or
service this equipment.
1. Insert a fiber optic cable with an LC connector into the 100BASE-FX
port of the 1783-MX08F expansion module.
31797-M
Verify Port Connectivity
2. Insert the other cable end into the other device.
After you connect to the switch port and another device, the port status
indicator turns amber while the switch establishes a link. This process takes
about 30 seconds, and then the status indicator turns green when the switch
and the target device have an established link.
If the status indicator is off, the target device might not be turned on, there
might be a cable problem, or there might be a problem with the adapter
installed in the target device.
Publication 1783-UM002C-EN-P - April 200961
Page 62
Chapter 2
Verify Switch Operation
Connect a Computer or a
Terminal to the Console
Port
Before installing the switch in its final location, you should power on the
switch and verify that the switch passes the power-on self-test (POST). These
sections describe the steps required to connect a personal computer or
terminal to the switch console port, to power on the switch, and to observe
POST results.
•
Connect a Computer or a Terminal to the Console Port, page 62
• Run a Power-on Self-test (POST), page 63
To connect a computer to the console port, use the supplied RJ45-to-DB-9
adapter cable. To connect a terminal to the console port, you need to provide
an RJ45-to-DB-25 female DTE adapter. For console-port and adapter-pinout
information, see Chapter 4, Cable and Connectors
WARNING
If you connect or disconnect the console cable with power
applied to the switch or any device on the network, an electrical
arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the
area is nonhazardous before proceeding.
To verify switch operation, perform POST on the switch in a
nonhazardous location before installation.
.
The computer or terminal must support VT100 terminal emulation. The
terminal-emulation software—frequently a computer application such as
HyperTerminal—makes communication between the switch and your
computer or terminal possible during the POST.
Follow these steps to connect the computer or terminal to the switch.
1. Make sure that your terminal-emulation software is configured to
communicate with the switch using hardware flow control.
2. Configure the communication rate and data format of the personal
computer or terminal to match these console-port default
characteristics.
• 9600 K bps communication rate
• 8 data bits
• 1 stop bit
• no parity
After gaining access to the switch, you can change the port
communication rate. See the switch software configuration guide for
instructions.
62Publication 1783-UM002C-EN-P - April 2009
Page 63
Chapter2
Run a Power-on Self-test
(POST)
Verify POST Results
When the switch powers on, it automatically initiates a POST. The POST runs
a series of tests that verify that the switch functions properly and assures that it
is ready to install.
To test the switch, follow these steps.
1. Apply power to the switch.
2.
Verify POST Results, page 63.
3. Disconnect Power, page 64.
When you apply power the switch, it automatically begins a series of self tests
(POST). During a POST, you see the following.
• All status indicators are off for a few seconds.
• Each status indicator is tested. One at a time, the EIP Mod, EIP Net,
Setup, Pwr A, and Pwr B status indicators each briefly display green,
then red, and then go off.
• The EIP Mod status indicator then blinks green as the boot loader
verifies the basic functionality of the processing and memory hardware.
• Assuming all tests pass, the EIP Mod status indicator blinks green as the
software image loads.
• If the POST fails, the EIP Mod status indicator turns red.
ATTENTION
POST failures are usually fatal. Contact your Rockwell
Automation representative immediately if your switch does not
pass POST.
Publication 1783-UM002C-EN-P - April 200963
Page 64
Chapter 2
Disconnect Power
Install and Remove SFP
Modules
After successfully running POST, follow these steps.
1. Turn off power to the switch.
2. Disconnect the cables.
3. Decide where you want to install the switch.
These sections describe how to install and remove Small Form-factor
Pluggable (SFP) modules. SFP modules are inserted into SFP module slots on
the front of the switch. These field-replaceable modules provide the uplink
optical interfaces, send (TX) and receive (RX).
TIP
Use only Rockwell Automation SFP modules on the switch. Each SFP module
has an internal serial EEPROM that is encoded with security information.
This encoding identifies and validates that the module meets the requirements
for the switch.
SFP modules can be installed and removed under power.
You can use any combination of SFP modules. Each SFP module must be of
the same type as the SFP module (or connection type, if an SFP module is not
installed) on the other end of the cable, and the cable must not exceed the
stipulated cable length for reliable communications. See Fiber-Optic SFP
Module Port Cabling Specifications table on page 80 for cable stipulations for
SFP module connections.
Install SFP Modules into SFP Module Slots
The following figure shows an SFP Module with a bale-clasp latch.
64Publication 1783-UM002C-EN-P - April 2009
Page 65
Chapter2
To insert an SFP module into the SFP module slot, follow these steps:
1. Attach an electrostatic discharge (ESD) preventive wrist strap to your
wrist and to a bare metal surface on the chassis.
2. Find the send (TX) and receive (RX) markings that identify the correct
side of the SFP module.
On some SFP modules, the send and receive (TX and RX) markings
might be replaced by arrows that show the direction of the connection,
either send or receive (TX or RX).
3. Grasp the module on the sides and align it in front of the slot opening.
4. Insert the SFP module into the slot until you feel the connector on the
module snap into place in the rear of the slot.
5. Remove the dust plugs from the SFP module optical ports and store
them for later use.
IMPORTANT
Do not remove the dust plugs from the SFP module port or the
rubber caps from the fiber-optic cable until you are ready to
connect the cable. The plugs and caps protect the SFP module
ports and cables from contamination and ambient light.
6. Insert the LC cable connector into the SFP module.
Remove SFP Modules from SFP Module Slots
To remove an SFP module from a module receptacle, follow these steps:
1. Attach an ESD-preventive wrist strap to your wrist and to a bare metal
surface on the chassis.
2. Disconnect the LC from the SFP module.
3. Insert a dust plug into the optical ports of the SFP module to keep the
optical interfaces clean.
Publication 1783-UM002C-EN-P - April 200965
Page 66
Chapter 2
4. Unlock and remove the SFP module, as shown the following figure.
Bale Clasp Latch
.
5. If the module has a bale-clasp latch, pull the bale out and down to eject
the module.
If the bale-clasp latch is obstructed and you cannot use your index
finger to open it, use a small, flat-blade screwdriver or other long,
narrow instrument to open the bale-clasp latch.
6. Grasp the SFP module between your thumb and index finger, and
carefully remove it from the module slot.
7. Place the removed SFP module in an antistatic bag or other protective
environment.
66Publication 1783-UM002C-EN-P - April 2009
Page 67
Chapter2
Connect to SFP Modules
This section describes how to connect to a fiber-optic SFP port. To connect to
an RJ45 Gigabit Ethernet port instead of a fiber-optic port, see the Connect to
the Switch Ports section on page 58.
Follow these steps to connect a fiber-optic cable to an SFP module:
WARNING
Do not remove the rubber plugs from the SFP module port or the
rubber caps from the fiber-optic cable until you are ready to
connect the cable. The plugs and caps protect the SFP module
ports and cables from contamination and ambient light.
See Chapter 4
for information about the LC on the SFP module.
1. Remove the rubber plugs from the module port and fiber-optic cable,
and store them for future use.
2. Insert one end of the fiber-optic cable into the SFP module port.
LC Connector
.
3. Insert the other cable end into a fiber-optic receptacle on a target device.
Publication 1783-UM002C-EN-P - April 200967
Page 68
Chapter 2
4. Observe the port status indicator.
• The status indicator turns green when the switch and the target device
have an established link.
• The status indicator turns amber while the SFP module discovers the
network topology and searches for loops. This process takes about 30
seconds, then the port status indicator turns green.
• If the status indicator is off, the target device might not be turned on,
there might be a cable problem, or there might be problem with the
adapter installed in the target device. See Chapter 3, Troubleshoot the
Switch for solutions to cabling problems.
5. If necessary, restart the switch or the target device.
68Publication 1783-UM002C-EN-P - April 2009
Page 69
Troubleshoot the Switch
This chapter provides these topics for troubleshooting the switch.
TopicPage
Obtain Troubleshooting Information69
Verify Switch POST Results69
Verify Switch Status Indicators70
Verify Switch Connections70
Verify Switch Performance73
Obtain Configuration Information74
Chapter
3
Obtain Troubleshooting
Information
Verify Switch POST Results
The status indicators on the front panel provide troubleshooting information
about the switch. They show power-on self-test (POST) failures,
port-connectivity problems, and overall switch performance. You can also ge t
statistics from the browser interface, the command-line interface (CLI), or a
Simple Network Management Protocol (SNMP) workstation.
As power is applied to the switch, it begins the POST, a series of tests that runs
automatically to ensure that the switch functions properly. It might take several
minutes for the switch to complete POST.
POST starts with status indicator tests that cycle once through the EIP Mod, EIP
Net, Setup, Pwr A, and Pwr B status in dicators. While POST proceeds, the E IP
Mod status indicator blinks green, and all the other status indicators remain off.
If POST completes successfully, the System status indicator changes to solid
green, and the other status indicators display their n ormal operating status. If th e
switch fails POST, the System status indicator turns red.
ATTENTION
POST failures are usually fatal. Contact your Rockwell
Automation technical support representative if your switch
does not pass POST.
69Publication 1783-UM002C-EN-P - April 200969
Page 70
Chapter 3
View POST Results With a Terminal
If you have a terminal connected to the console port, you can also view POST
status and test results on the terminal.
If the terminal displays garbled characters, you might need to reset the
terminal-emulation software to 9600 bits per second. Refer to
Results on page 63 for more information about viewing results on a terminal.
Verify POST
Verify Switch Status
Indicators
Verify Switch Connections
If you have physical access to the switch, look at the port status indicators for
information about the switch. See the following sources for a description of the
status indicators colors and their meanings:
• The Status Indicators section on page 15 of this manual
Review this section when troubleshooting switch connection problems.
Bad or Damaged Cable
Always make sure that the cable does not have marginal damage or failure. A
cable might be just good enough to connect at the physical layer, but it could
corrupt packets as a result of subtle damage to the wiring or connectors.
70Publication 1783-UM002C-EN-P - April 2009
Page 71
Chapter3
This situation is likely when the port has many packet errors or the port
constantly loses and regains the link. You should:
• Swap the copper or fiber-optic cable with a known, good cable.
• Look for broken, bent, or missing pins on cable connectors.
• Rule out any bad patch panel connections or media convertors between
the source and destination.
If possible, bypass the patch panel, or eliminate faulty media convertors
(fiber-optic-to-copper).
• Try the cable in another port or interface, if possible, to see if the
problem follows the cable.
Ethernet and Fiber Cables
Make sure that you have the correct cable type for the connection.
• Use Category 3 copper cable for 10 Mb/s UTP connections.
• Category 5, 5e, or 6 UTP or STP cable may be used for 10/100 Mbps
connections.
• For 1000 Mbps (1 gigabit per second) connections, use either Category
5e or Category 6 UTP or STP cable.
• For fiber-optic connectors, verify that you have the correct cable for the
distance and the port type.
• Make sure that the connected device ports both match and use the same
type encoding, optical frequency, and fiber type.
Publication 1783-UM002C-EN-P - April 200971
Page 72
Chapter 3
Link Status
Verify that both sides have a network link. A single broken wire or one shut
down port can cause one side to show a link, but not the other side.
A Link status indicator does not guarantee that the cable is fully functional.
The cable might have encountered physical stress that causes it to function at a
marginal level.
If the Link status indicator for the port is not lit, do the following.
• Connect the cable from the switch to a known good device.
• Make sure that both ends of the cable are connected to the correct
ports.
• Verify that both devices have power.
• Verify that you are using the correct cable type.
• Rule out loose connections. Sometimes a cable appears to be seated, but
is not. Disconnect the cable, and then reconnect it.
Transceiver Issues
Use only Rockwell Automation SFP modules on the switch. Each SFP module
has an internal serial EEPROM that is encoded with security information.
This encoding identifies and validates that the module meets the requirements
for the switch. Other manufacturers’ SFP modules will not function correctly.
Check these items.
• Bad or incorrect SFP module.
Exchange the suspect module with a known good module. Verify that
the module is supported on this platform.
• Use the CLI show interfaces command or the CLI show int status
command to verify the port or module error-disabled or shutdown
status. Re-enable the port if needed.
• Make sure that all fiber connections are properly cleaned and securely
connected.
72Publication 1783-UM002C-EN-P - April 2009
Page 73
Chapter3
Port and Interface Settings
A cause of port connectivity failure can be a disabled port. Verify that the port
or interface is not disabled or powered down for some reason. If a port or
interface is manually shut down on one side of the link or the other si de, the link
does not come up until you re-enable the port. Use the CLI show interfaces
privileged EXEC command to ver ify the port or interface error-disabled,
disabled, or shutdown status on both sides of the connection. If needed,
re-enable the port or the interface.
Verify Switch Performance
Review this section when troubleshooting switch performance problems.
Speed, Duplex, and Autonegotiation
If the port statistics show a large amount of alignment errors, frame check
sequence (FCS), or late-collisions errors, this might indicate a speed or duplex
mismatch.
A common issue with speed and duplex occurs when the duplex settings are
mismatched between two switches, between a switch and a router, or between
the switch and a workstation or server. This can happen when manually setting
the speed and duplex or from autonegotiation issues between the two devices.
A mismatch occurs under these circumstances:
• A manually set speed or duplex parameter is different from the manually
set speed or duplex parameter on the connected port.
• A port is set to autonegotiate, and the connected port is set to full
duplex with no autonegotiation.
To maximize switch performance and ensure a link, follow one of these
guidelines when changing the settings for duplex and speed:
• Let both ports autonegotiate both speed and duplex.
• Manually set the same speed and duplex parameters for the ports on
both ends of the connection to the same values.
• If a remote device does not autonegotiate, configure the duplex settings
on the two ports to the same values.
The speed parameter can adjust itself even if the connected port does
not autonegotiate.
Publication 1783-UM002C-EN-P - April 200973
Page 74
Chapter 3
Autonegotiation and Network Interface Cards (NICs)
Problems sometimes occur between the switch and third-party network
interface cards (NICs). By default, the switch ports and interfaces are set to
autonegotiate. It is common for devices like laptops or other devices to be set
to autonegotiate as well, yet sometimes autonegotation issues occur.
To troubleshoot autonegotiation problems, try manually setting both sides of
the connection. If this does not solve the problem, there could be a problem
with the firmware or software on your NIC. You can resolve this by upgrading
the NIC driver to the latest version available from the manufacturer.
Cabling Distance
If the port statistics show excessive FCS, late-collision, or alignment errors,
verify that the cable distance from the switch to the connected device meets
the recommended guidelines. See Chapter 4, Cable and Connectors
cabling guidelines.
for
Obtain Configuration
Information
If you contact Rockwell Automation Technical Support, you may be asked to
provide configuration information for your switch. You can obtain this
information from the Device Manager web interface online help.
Follow this procedure to obtain configuration information for your switch.
1. In the Device Manager web interface, click the Help button.
2. In the left pane, click Support.
3. Click the link labeled Show Information Commonly Needed by TAC.
You see a text file showing configuration information.
4. For future reference, you can save the file (.txt, .mht, .htm, or .html
formats).
TIP
From the Support dialog box, you can also click on a link that
takes you directly to Rockwell Automation technical support.
74Publication 1783-UM002C-EN-P - April 2009
Page 75
Chapter
6
4
Cable and Connectors
This appendix describes the switch ports and the cables and adapters that you
use to connect the switch to other devices.
10/100 and 10/100/1000
Ports
The 10/100 and 10/100/1000 Ethernet ports on switches use standard RJ45
connectors and Ethernet pinouts with internal crossovers.
TIP
The auto-MDIX feature is enabled by default.
The following figure shows the connector pinouts.
10/100 Connector Pinouts
23145678PinLabel
1
2
3
4
5
6
7
8
10/100/1000 Connector Pinouts
RD+
RDTD+
NC
NC
TDNC
NC
H5318
23145678PinLabel
1
2
3
4
5
6
7
8
75Publication 1783-UM002C-EN-P - April 200975
TP0+
TP0TP1+
TP2+
TP2TP1TP3+
TP3-
0915
Page 76
Chapter 4
6
2
H
1
2
3
6
4
5
7
8
Connect to 10BASE-T- and 100BASE-TX-Compatible Devices
When connecting the ports to 10BASE-T- and 100BASE-TX-compatible
devices, such as servers, workstations, and routers, you can use a two or four
twisted-pair, straight-through cable wired for 10BASE-T and 100BASE-TX.
To identify a crossover cable, compare the two modular ends of the cable.
Hold the cable ends side-by-side, with the tab at the back. The wire connected
to the pin on the outside of the left plug should be a different color from the
wire connected to the pin on the inside of the right plug.
The following figures show these schematics:
• two twisted-pair, straight-through cable
• four twisted-pair, straight-through cable
Two Twisted-pair Straight-through Cable Schematic
Switch
3 TD+
TD–
1 RD+
RD–
Router or PC
3 RD+
6 RD–
1 TD+
2 TD–
5578
Four Twisted-pair Straight-through Cable Schematic
SwitchRouter or PC
TPO+
TPOTP1+
TP1-
TP2+
TP2TP3+
TP3-
1 TP1+
2 TP13 TPO+
6 TPO-
4 TP3+
5 TP37 TP2+
8 TP2-
65272
When connecting the ports to 10BASE-T- and 100BASE-TX-compatible
devices, such as switches or repeaters, you can use a two or four twisted-pair,
crossover cable.
The following figures show these schematics:
76Publication 1783-UM002C-EN-P - April 2009
• two twisted-pair, crossover cable schematics
• four twisted-pair, crossover cable schematics
Page 77
Chapter4
6
2
H
1
2
3
6
4
5
7
8
Use a straight-through cable to connect two ports only when one port is
designated with an X. Use a crossover cable to connect two ports when both
ports are designated with an X or when both ports do not have an X.
You can use Category 3, 4, or 5 cabling when connecting to
10BASE-T-compatible devices. You must use Category 5 cabling when
connecting to 100BASE-TX-compatible devices
.
IMPORTANT
Use a four twisted-pair, Category 5 cable when connecting to a
1000BASE-T-compatible device
Two Twisted-pair Crossover Cable Schematic
Switch
3 TD+
TD–
1 RD+
RD–
Four Twisted-pair Crossover Cable Schematic
SwitchSwitch
TPO+
TPOTP1+
TP1-
TP2+
TP2TP3+
TP3-
Switch
3 TD+
6 TD–
1 RD+
2 RD–
1 TP0+
2 TP03 TP1+
6 TP1-
4 TP2+
5 TP27 TP3+
8 TP3-
5579
65274
Publication 1783-UM002C-EN-P - April 200977
Page 78
Chapter 4
5
100BASE-FX Ports
SFP Module Ports
The 100BASE-FX ports use the following:
• LC connectors, as shown in the following figure.
• 50/125- or 62.5/125-micron multimode fiber-optic cables
Fiber-optic SFP Module LC Connector
8476
ATTENTION
Invisible laser radiation may be emitted from disconnected
fibers or connectors. Do not stare into beams or view directly
with optical instruments.
The switch uses SFP modules for fiber-optic uplink ports.
ATTENTION
Invisible laser radiation may be emitted from disconnected
fibers or connectors. Do not stare into beams or view directly
with optical instruments.
78Publication 1783-UM002C-EN-P - April 2009
Page 79
Chapter4
6
Dual-purpose Ports
The Ethernet port on a dual-purpose port uses standard RJ45 connectors. The
following figure shows the pinouts.
Ethernet Port RJ45 Connector
23145678PinLabel
1
2
3
4
5
6
7
8
TP0+
TP0TP1+
TP2+
TP2TP1TP3+
TP3-
The SFP module slot on a dual-purpose port uses SFP modules for fiber-optic
ports.
IMPORTANT
The auto-MDIX feature is enabled by default. For configuration
information for this feature, see the switch software
configuration guide or the switch command reference.
0915
Console Port
The console port uses an 8-pin RJ45 connector. The supplied RJ45-to-DB-9
adapter cable is used to connect the console port of the switch to a console
personal computer. You need to provide an RJ45-to-DB-25 female DTE
adapter if you want to connect the switch console port to a terminal.
Publication 1783-UM002C-EN-P - April 200979
Page 80
Chapter 4
Cable and Adapter
These sections describe the cables and adapters used with the switches.
Specifications
SFP Module Cable Specifications
The following lists the cable specifications for the rugged fiber-optic SFP
module connections. Each port must match the wave-length specifications on
the other end of the cable, and for reliable communications, the cable must not
exceed the rated maximum cable length.
Fiber-Optic SFP Module Port Cabling Specifications
SFP Module
Ty pe
100BASE-FX1783-SFP100FX1310MMF50/125
100BASE-LX1783-SFP100LX1310SMF
1000BASE-SX1783-SFP1GSX850MMF62.5/125
1000BASE-LX/LH1783-SFP1GLX1310SMF
(1)
Modal bandwidth applies only to multimode fiber.
Cat. No.Wavelength
(nm)
Fiber TypeCore Size/Cladding
Size (micron)
62.5/125
G.652
62.5/125
50/125
50/125
G.652
Modal
Bandwidth
(MHz/km)
500
500
2
2
—10 km (32,810 ft)
160
200
400
500
—10 km (32,810 ft)
(1)
Cable Distance
2 km (6,562 ft)
2 km (6,562 ft)
220 m (722 ft)
275 m (902 ft))
500 m (1640 ft)
550 m (1804 ft)
Adapter Pinouts
The following table lists the pinouts for the console port, the RJ45-to-DB-9
adapter cable, and the console device.
Switch Console Port
(DTE)
SignalDB-9 PinSignal
RTS8CTS
DTR6DSR
TxD2RxD
GND5GND
GND5GND
RxD3TxD
DSR4DTR
CTS7RTS
RJ45-to-DB-9
Terminal Adapter
Console Device
The following table lists the pinouts for the console port, RJ45-to-DB-25
female DTE adapter, and the console device.
80Publication 1783-UM002C-EN-P - April 2009
Page 81
Chapter4
The RJ45-to-DB-25 female DTE adapter is not supplied with the switch.
Switch Console
Port (DTE)
RJ45-to-DB-25
Terminal Adapter
Console
Device
SignalDB-25 PinSignal
RTS5CTS
DTR6DSR
TxD3RxD
GND7GND
GND7GND
RxD2TxD
DSR20DTR
CTS4RTS
Publication 1783-UM002C-EN-P - April 200981
Page 82
Chapter 4
Notes:
82Publication 1783-UM002C-EN-P - April 2009
Page 83
How Are We Doing?
Your comments on our technical publications will help us serve you better in the future.
Thank you for taking the time to provide us feedback.
You can complete this form and mail (or fax) it back to us or email us at
RADocumentComments@ra.rockwell.com.
Pub. Title/Type Stratix 8000 Managed Ethernet Switches Hardware User Manual
Cat. No.1
783-MS06T,
1783-MS10T,
1783-MX08T, 1783-MX08F
Pub. No.1783-UM002A-EN-EPub. Date April 2009Part No.
Please complete the sections below. Where applicable, rank the feature (1=needs improvement, 2=satisfactory, and 3=outstanding).
Overall Usefulness123How can we make this publication more useful for you?
Completeness
(all necessary information
is provided)
Technical Accuracy
(all provided information
is correct)
123Can we add more information to help you?
procedure/stepillustrationfeature
exampleguidelineother
explanationdefinition
123Can we be more accurate?
text illustration
Clarity
(all provided information is
easy to understand)
Other CommentsYou can add additional comments on the back of this form.
Your Name
Your Title/FunctionWould you like us to contact you regarding your comments?
Location/Phone
Return this form to:Rockwell Automation Technical Communications, 1 Allen-Bradley Dr., Mayfield Hts., OH 44124-9705
Publication CIG-CO521D-EN-P- July 2007
123How can we make things clearer?
___No, there is no need to contact me
___Yes, please call me
___Yes, please email me at _______________________
___Yes, please contact me via _____________________
bad or damaged cable
connection problems
diagnosing problems
Ethernet and fiber cables
link status
port and interface settings
POST
speed, duplex, and autonegotiation
switch performance
understanding POST results
Rockwell Automation provides technical information on the Web to assist you in using
its products. At http://support.rockwellautomation.com
manuals, a knowledge base of FAQs, technical and application notes, sample code and
links to software service packs, and a MySupport feature that you can customize to
make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and
troubleshooting, we offer TechConnect support programs. For more information,
contact your local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com
.
, you can find technical
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the
information that's contained in this manual. You can also contact a special Customer
Support number for initial help in getting your product up and running.
United States1.440.646.3434
Monday – Friday, 8am – 5pm EST
Outside United
States
Please contact your local Rockwell Automation representative for any
technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational
when shipped from the manufacturing facility. However, if your product is not
functioning and needs to be returned, follow these procedures.
United StatesContact your distributor. You must provide a Customer Support case
number (call the phone number above to obtain one) to your distributor
in order to complete the return process.
Outside United
States
Please contact your local Rockwell Automation representative for the
return procedure.