Rockwell Automation T3468A User Manual

ICS Regent
®
PD-6019
DC Guarded Digital Output Modules
24 VDC, 48 VDC and 120 VDC
(T3461A, T3462A and T3468A)
Issue 1,
DC Guarded output modules provide Guarded switching of user-supplied DC voltages to a maximum of eight field loads. These dual-redundant design ensures that no single fault within the module will inadvertently apply power to an output. Extensive fault detection and redundant critical circuits ensure that each module operates in a fail-safe manner.
modules are called Guarded because each module's
March, 06
Features
·
Eight Guarded output circuits configured as two sepa powered groups of four circuits each.
·
Fault tolerant operation when connected in parallel with an
·
Hot-replaceable.
·
100% self-testing of all critical circuits.
·
Individual front panel indicators on each module show active and fault, shutdown state, blown fuse, and output on/off status (logic side).
·
2500 volt minimum electrical isolation between field and logic circuits.
·
TÜV certified, Risk Class 5.
Two Guard obtain fault tolerant control of power to loads. In this parallel module configuration, either module can be removed and replaced while the other Guarded module continues to control the loads without interruption.
other module of the same type.
ed output modules can be connected in parallel to
rately
1
DC Guarded Digital Output Modules (T3461A, 62A, 68A)

Module Operation

A block diagram of a typical monitored Guarded output module is shown in Figure 1.
The processor modules send triplicated write data commands over the I/O Safetybus to the Guarded output module. Onboard the Guarded output modules the triplicated data are routed to two independent voter and I/O Safetybus logic sections. Each section independently votes the triplicated data and operates one of the two field effect transistor (FET) output control switches. The two FETs are connected in series with the load.
2
Figure 1. Block Diagram of a DC Guarded Output Module.
When both circuits are on, current will flow through the output and energize a field load. If e will not flow through the output and the load will be de
Industrial Control Services
ither switch is off, current
-
(T3461A, 62A, 68A) DC Guarded Digital Output Modules
Case
Commanded
Output St
ate
Switch
Failed
State
Actual
Output
to Load
Remarks
1 On
On On
Continued correct control. Automatic testing detects stuck-on switch. If output is subsequently commanded off, output will turn off.
2 On
Off Off
Fail-safe output. Automatic testing detects stuck-off switch.
3 Off
On
Off
Continued correct control. Automatic testing detects stuck-off switch. If output is subsequently commanded on, output will turn on.
4 Off
Off Off
Fail-safe output. Automatic testing detects stuck-off switch. If ou
tput is subse
­quently commanded on, output will remain off.
energized. This combination of series output switches and independent drive signals produces fail-safe activation of the load. Single failures can only affect one of the output drive signals or switches. A single failure will result in either continued correct control or a fail-safe output as shown in Table 1.
Table 1. Output States After Switch Failure.
PD-6019
Mar-06
To achieve fault tolerance, two Guarded output modules are used with their outputs connected in parallel. This configuration provides for continued correct control even when one output switch fails off (cases two and four in Table 1
). The module failure is automatically detected and the module can be removed and replaced without interrupting output control.

Testing and Diagnostics

The voter and I/O bus interface logic o
f the Guarded output modules is automatically tested by the processor modules. Discrepant data are sent through one of three legs of the I/O Safetybus to determine whether the module’s voters are able to outvote the incorrect data. A failure to return the correct
3
DC Guarded Digital Output Modules (T3461A, 62A, 68A)
majority-voted result to the processors produces an I/O module error indication at the processor modules and a module fault indication at the I/O module.
Each type of module has a unique identification code that is read by the controller. This c
ode lets the controller know which type of module is installed in each I/O chassis slot and how to address that module and its points specifically. If a module is removed, or is replaced with a module of a different type, the processor modules will indicate an I/O module error.
Loopback logic tests periodically write data to the module and then read it back to determine whether the module’s I/O bus interface logic is functioning correctly.
Fuses are checked for continuity. Blown fuse detection is independent of load connection or the output circuit’s on/off state.
To detect a failure in the redundant logic drive circuits, each pair of output switches is checked for state discrepancies. If a discrepancy is detected, a module fault is indicated. These state comparison tests allow for normal variances in FET switching times.
Approximately once every second each FET on the module is tested for its ability to change its current state. During testing, the output state is changed; outputs that are on are turned off and outputs that are off are turned on. The testing time is nominally 0.75 milliseconds, and is insufficient to affect the state of most field loads.
Testing of the output switches is non-overlapping, i.e. no turn on pulse is applied to the load unless one of the switches is shorted. Also, in a dual module configuration, no turn-off pulse is applied to the load unless the asynchronous test pulses between the dual modules overlap, a output switch is open, or a module is removed. In any case, the nomi
nal test pulse duration of 0.75 milliseconds is insufficient to disturb field outputs.
Output circuit test results are not affected by the presence or absence of a load. Output FET current leakage greater than 2 mA is detected as a shorted FET.
4
Industrial Control Services
(T3461A, 62A, 68A) DC Guarded Digital Output Modules
Note:
When an output switch failure or blown fuse is detected a module fault condition is alarmed, resulting in an I/O module error indication at the processor modules and a module fault indication on the I/O module.

Front Panel

Figure 2 shows output modules. The front panel of each module contains a module active and fault status indicator, a shutdown indicator, as well as output fuses, output status indicators, and blown fuse indicators for each output circuit.

Active/Fault Status Indicator

These green and red LEDs indicate the overall health of the module and its field circuits. During normal operation, the green ACTIVE indicator flashes at the controller’s scan rate. If a module fault is detected the red FAULT indicator turns on and the green ACTIVE indicator turns off.

Shutdown Indicator

Upon loss of communications with the controller, output modules enter either a shutdown or hold fault mode. If the I/O unit is set to shutdown, the red SHUTDOWN indicator will turn on when communications with the controller are lost. If the I/O unit is set to hold, the SHUTDOWN indicator will always be off (see page 13, Fault Mode Jumper).
the physical features of the DC Guarded
PD-6019
Mar-06
When the module is installed in the I/O chassis or
power (from the I/O power supply modules) is first applied to the module, it will be in the shutdown mode until the first output scan, regardless of the fault mode jumper settings. Also, removing two I/O transceiver modules, two I/O power supply modules, or two power legs will cause the module to be in the shutdown mode.

Output Status Indicators

The output status indicators are yellow LEDs, located on the front of the module. The state of the output circuit is sensed on the field-side of the c isolated to drive the logic-side LEDs. These indicators are on when the load is energized.
5
ircuit and this status is optically
when logic
DC Guarded Digital Output Modules (T3461A, 62A, 68A)
6
Figure 2. A DC Guarded Output Module.
Industrial Control Services
Loading...
+ 14 hidden pages