Rockwell Automation T3464 User Manual

ICS Regent
®
PD-6021
AC Guarded Digital Output Module
110 VAC
(T3464)
Issue 1,
AC Guarded digital output modules provide guarded switching of user-supplied 110 AC voltages to a maximum of sixteen field loads. These modules are called Guarded because no single fault within a module will inadvertently apply power to an output. Extensive fault detection and critical redundant circuits ensure that the module operates in a fail-safe manner.
Features
March, 06
·
Sixteen Guarded output circuits configured as two separately powered groups of eight circuits each.
·
Fault tolerant operation when connected in parallel with another module of the same type.
·
Hot-replace
·
100% self-test of all critical circuits.
·
Zero-cross load switching.
·
Individual front panel indicators on each module show active/fault and output on/off status (field side). A diagnostic message display provides additional status indicators.
·
Fuses accessible from front panel.
·
2500 volt minimum electrical isolation between field and l circuits.
·
TÜV certified, Risk Class 5, see Safety Considerations.
Two Guarded output modules can be connected in parallel to obtain fault tolerant control of power to loads. In this parallel module configuration, either module can be removed and
able.
ogic
1
AC Guarded Digital Output Module
replaced while the other Guarded module continues to control the loads without interruption.
(T3464)

Module Operation

A block diagram of a typical AC Guarded digital output module is shown in Figure 1.
The processor modules send triplicated write data commands over the I/O Safetybus to the Guarded output module. Onboard the Guarded output modules the triplicated data are routed to two independent voter and microcomputer sections. Each section independently votes the triplicated data to generate a logic output drive signal. The two logic drive signals are ANDed to control the output TRIAC.
2
Figure 1. Block Diagram of the AC Guarded Output Module.
The TRIAC will normally be energized only when both microcomputer sections command the output to be on. If either microcomputer section commands the output to be off,
Industrial Control Services
(T3464)
AC Guarded Digital Output Module
the TRIAC will be de-energized. If the TRIAC itself fails shorted when commanded off, either microcomputer section can trigger an internal crowbar switch that disables the output by blowing the fuse for that circuit.
The combination of dual independent drive signals, a TRIAC, and a crowbar circuit provides fail-safe activation of the load devices. No s
ingle failure can prevent the output from being turned off when commanded. Single failures result in either continued correct control or a fail-safe output as shown in Table 1.
To achieve fault tolerance, two Guarded output modules are used with their outputs connected in parallel. This configuration provides for continued correct control even when an output TRIAC fails open (class 2 and 5 in Table 1). The module failure is automatically detected and th
e failed module can be removed and replaced without interrupting output control.
PD-6021
Mar-06
3
Case
Commanded
Output State
Single
Failure
Actual
Output
to Load
Remarks
1 On
TRIAC
short
On
Continued correct control. Automatic testing of crowbar circuit ensures that output will be able to switch off. If output is subsequently commanded off, crowbar switch is energized to blow fuse and turn off output (fuse blows 200 msec after output is commanded off).
2 On
TRIAC
open
Off
Fail-safe output. Automatic testing detects failed TRIAC.
3 On
Crowbar
fault
On
Continued correct control. Automatic testing detects failed crowbar circuit. If output is subsequently commanded off, TRIAC will turn off.
4
Off
TRIAC
short
200 msec bump
A one-time, 200 msec maximum on-state bump occurs when the TRIAC shorts. Automatic testing detects shorted TRIAC and crowbar switch is activated to blow fuse. This one-time bump may not be suitable for certain energize-to-trip applicatio
ns.
5
Off
TRIAC
open
Off
Fail-safe output. Automatic testing detects failed TRIAC. If output is subsequently commanded on, output will remain off.
6
Off
Crowbar
fault
Off
Continued correct control. Automatic testing detects failed crowbar circuit. If output is subsequently commanded on, TRIAC will turn on.
AC Guarded Digital Output Module
(T3464)
Table 1. Output States After Switch Failure.
4

Testing and Diagnostics

The voter and I/O bus interface logic of the Guarded output modules is automatically tested by the processor modules. Discrepant data are sent through one of three legs of
the I/O Safetybus to determine whether the module’s voters are able to outvote the incorrect data. A failure to return the correct majority-voted result to the processors produces an I/O
Industrial Control Services
(T3464)
AC Guarded Digital Output Module
module error indication at the processor modules and a module fault indication at the I/O module.
Each type of module has a unique identification code that is read by the controller. This code lets the controller know which type of module is installed in each I/O chassis slot and how to address that module and its points
specifically. If a module is removed, or is replaced with a module of a different type, the processor modules will indicate an I/O module error.
Loopback logic tests periodically write data to the module and then read it back to determine whether the module’s I/O bus interface logic is functioning correctly.
Fuses are periodically checked for continuity. Blown fuse detection is independent of load connection or output circuit’s on/off state.
Incoming AC field power is checked for proper frequency, stabili
ty, and phase. Tests that depend on AC power timing information, such as turn-on testing, will not execute if the AC power is unacceptable. However, crowbar switch activation is not dependent on these power conditions.
Approximately every 2 seconds, output circuits commanded to be off are tested for their ability to turn on. Three test pulses are applied on successive AC voltage phase zero crossings to verify the output switch's ability to conduct bi-directional current flow. The pulses are limited to 5
0 volts with a maximum duration of 1 millisecond. This energy is insufficient to drive most field loads.
Output TRIACs commanded to be on (output switch closed) are not tested for their ability to turn off. Instead, the crowbar circuit is periodically tested for its ability to turn on. If a TRIAC fails to tuns off when commanded, either microcomputer can energize the crowbar switch and remove power from the load by blowing the fuse for that circuit. In this way, an output’s inability to turn off is not discovered until the switch is commanded to turn off. The result is a maximum time to switch off a shorted output (blow the fuse) of 200 milliseconds.
Outputs commanded to be on are occasionally tested for open load and open circuit (faulty output switch) conditions. If load current is below the minimum requirements, the module tests
PD-6021
Mar-06
5
AC Guarded Digital Output Module
the output switch's ability to conduct current (through an internal dummy load). If current is conducted, the fault is in the load. If no current is conducted, the fault is switch circuit. Healthy outputs commanded to be on but not wired to an external load will always cause an open load condition to be displayed.
(T3464)
in the output

Front Panel

Figure 2 shows the physical features of the AC Guarded output modules. The front panel contains an active and fault status indicator, a diagnostic message display, as well as status indicators and fuses for each output circuit.

Active/Fault Status Indicator

These green and red LEDs indicate the overall health o
f the module and its field circuits. During normal operation, the green ACTIVE indicator flashes at the controller’s scan rate. If a module fault occurs the red FAULT indicator turns on and the green ACTIVE indicator turns off.

Output Status Indicators

The output status indicators are yellow LEDs, located on the field side of the output circuit, in parallel with the load. These indicators are on when the load is energized.
6
Industrial Control Services
(T3464)
AC Guarded Digital Output Module
PD-6021
Mar-06
Figure 2. AC Guarded Output Mod
7
ule.
Loading...
+ 15 hidden pages