Rockwell Automation T3464 User Manual

ICS Regent
®
PD-6021
AC Guarded Digital Output Module
110 VAC
(T3464)
Issue 1,
AC Guarded digital output modules provide guarded switching of user-supplied 110 AC voltages to a maximum of sixteen field loads. These modules are called Guarded because no single fault within a module will inadvertently apply power to an output. Extensive fault detection and critical redundant circuits ensure that the module operates in a fail-safe manner.
Features
March, 06
·
Sixteen Guarded output circuits configured as two separately powered groups of eight circuits each.
·
Fault tolerant operation when connected in parallel with another module of the same type.
·
Hot-replace
·
100% self-test of all critical circuits.
·
Zero-cross load switching.
·
Individual front panel indicators on each module show active/fault and output on/off status (field side). A diagnostic message display provides additional status indicators.
·
Fuses accessible from front panel.
·
2500 volt minimum electrical isolation between field and l circuits.
·
TÜV certified, Risk Class 5, see Safety Considerations.
Two Guarded output modules can be connected in parallel to obtain fault tolerant control of power to loads. In this parallel module configuration, either module can be removed and
able.
ogic
1
AC Guarded Digital Output Module
replaced while the other Guarded module continues to control the loads without interruption.
(T3464)

Module Operation

A block diagram of a typical AC Guarded digital output module is shown in Figure 1.
The processor modules send triplicated write data commands over the I/O Safetybus to the Guarded output module. Onboard the Guarded output modules the triplicated data are routed to two independent voter and microcomputer sections. Each section independently votes the triplicated data to generate a logic output drive signal. The two logic drive signals are ANDed to control the output TRIAC.
2
Figure 1. Block Diagram of the AC Guarded Output Module.
The TRIAC will normally be energized only when both microcomputer sections command the output to be on. If either microcomputer section commands the output to be off,
Industrial Control Services
(T3464)
AC Guarded Digital Output Module
the TRIAC will be de-energized. If the TRIAC itself fails shorted when commanded off, either microcomputer section can trigger an internal crowbar switch that disables the output by blowing the fuse for that circuit.
The combination of dual independent drive signals, a TRIAC, and a crowbar circuit provides fail-safe activation of the load devices. No s
ingle failure can prevent the output from being turned off when commanded. Single failures result in either continued correct control or a fail-safe output as shown in Table 1.
To achieve fault tolerance, two Guarded output modules are used with their outputs connected in parallel. This configuration provides for continued correct control even when an output TRIAC fails open (class 2 and 5 in Table 1). The module failure is automatically detected and th
e failed module can be removed and replaced without interrupting output control.
PD-6021
Mar-06
3
Case
Commanded
Output State
Single
Failure
Actual
Output
to Load
Remarks
1 On
TRIAC
short
On
Continued correct control. Automatic testing of crowbar circuit ensures that output will be able to switch off. If output is subsequently commanded off, crowbar switch is energized to blow fuse and turn off output (fuse blows 200 msec after output is commanded off).
2 On
TRIAC
open
Off
Fail-safe output. Automatic testing detects failed TRIAC.
3 On
Crowbar
fault
On
Continued correct control. Automatic testing detects failed crowbar circuit. If output is subsequently commanded off, TRIAC will turn off.
4
Off
TRIAC
short
200 msec bump
A one-time, 200 msec maximum on-state bump occurs when the TRIAC shorts. Automatic testing detects shorted TRIAC and crowbar switch is activated to blow fuse. This one-time bump may not be suitable for certain energize-to-trip applicatio
ns.
5
Off
TRIAC
open
Off
Fail-safe output. Automatic testing detects failed TRIAC. If output is subsequently commanded on, output will remain off.
6
Off
Crowbar
fault
Off
Continued correct control. Automatic testing detects failed crowbar circuit. If output is subsequently commanded on, TRIAC will turn on.
AC Guarded Digital Output Module
(T3464)
Table 1. Output States After Switch Failure.
4

Testing and Diagnostics

The voter and I/O bus interface logic of the Guarded output modules is automatically tested by the processor modules. Discrepant data are sent through one of three legs of
the I/O Safetybus to determine whether the module’s voters are able to outvote the incorrect data. A failure to return the correct majority-voted result to the processors produces an I/O
Industrial Control Services
(T3464)
AC Guarded Digital Output Module
module error indication at the processor modules and a module fault indication at the I/O module.
Each type of module has a unique identification code that is read by the controller. This code lets the controller know which type of module is installed in each I/O chassis slot and how to address that module and its points
specifically. If a module is removed, or is replaced with a module of a different type, the processor modules will indicate an I/O module error.
Loopback logic tests periodically write data to the module and then read it back to determine whether the module’s I/O bus interface logic is functioning correctly.
Fuses are periodically checked for continuity. Blown fuse detection is independent of load connection or output circuit’s on/off state.
Incoming AC field power is checked for proper frequency, stabili
ty, and phase. Tests that depend on AC power timing information, such as turn-on testing, will not execute if the AC power is unacceptable. However, crowbar switch activation is not dependent on these power conditions.
Approximately every 2 seconds, output circuits commanded to be off are tested for their ability to turn on. Three test pulses are applied on successive AC voltage phase zero crossings to verify the output switch's ability to conduct bi-directional current flow. The pulses are limited to 5
0 volts with a maximum duration of 1 millisecond. This energy is insufficient to drive most field loads.
Output TRIACs commanded to be on (output switch closed) are not tested for their ability to turn off. Instead, the crowbar circuit is periodically tested for its ability to turn on. If a TRIAC fails to tuns off when commanded, either microcomputer can energize the crowbar switch and remove power from the load by blowing the fuse for that circuit. In this way, an output’s inability to turn off is not discovered until the switch is commanded to turn off. The result is a maximum time to switch off a shorted output (blow the fuse) of 200 milliseconds.
Outputs commanded to be on are occasionally tested for open load and open circuit (faulty output switch) conditions. If load current is below the minimum requirements, the module tests
PD-6021
Mar-06
5
AC Guarded Digital Output Module
the output switch's ability to conduct current (through an internal dummy load). If current is conducted, the fault is in the load. If no current is conducted, the fault is switch circuit. Healthy outputs commanded to be on but not wired to an external load will always cause an open load condition to be displayed.
(T3464)
in the output

Front Panel

Figure 2 shows the physical features of the AC Guarded output modules. The front panel contains an active and fault status indicator, a diagnostic message display, as well as status indicators and fuses for each output circuit.

Active/Fault Status Indicator

These green and red LEDs indicate the overall health o
f the module and its field circuits. During normal operation, the green ACTIVE indicator flashes at the controller’s scan rate. If a module fault occurs the red FAULT indicator turns on and the green ACTIVE indicator turns off.

Output Status Indicators

The output status indicators are yellow LEDs, located on the field side of the output circuit, in parallel with the load. These indicators are on when the load is energized.
6
Industrial Control Services
(T3464)
AC Guarded Digital Output Module
PD-6021
Mar-06
Figure 2. AC Guarded Output Mod
7
ule.
Note:
AC Guarded Digital Output Module
(T3464)

Diagnostic Message Display

This four-digit display provides additional fault diagnostics (such as blown fuse, AC power problems, wiring faults, etc.). If one or more fault conditions are present, the fault messages are displayed in rotation for approximately one second each. These fault messages are self-clearing (which means, for example, that replacing a blown fuse will clear the blown fuse message). However, the module’s FAULT indicator can only be cleared by a voted reset.
Indicator messages are described in the section Maintenance, beginning on page 18.

Shutdown Indication

Upon loss of communications with the controller, output modules enter either a shutdown or hold fault mode. If the I/O unit is set to shutdown, the diagnostic message display will show Shud when communications with the controller are lost. If the I/O unit is set to hold, diagnostic message display will not display this message (see page 14, Fault Mode Jumper).

Application

When the module is installed in the I/O chassis or when logic
power (from the I/O power supply modules) is first applied to the module, it will be in the shutdown mode until the first output scan, regardless of the fault mode jumper settings. Also, removing two I/O transceiver modules, two I/O power supply modules, or two power legs will cause the module to be in the shutdown mode.
Each module has separate power terminals for switch groups 1-8 and groups 9-16. The two groups are electrically isolated from each o difference between separate power sources cannot be guaranteed to be less than one degree, both groups should be wired to the same AC circuit. The microcomputers monitor this phase difference to validate timing data derived from the AC power.
When a crowbar circuit blows a fuse, approximately 16 additional amps of current flows through both the line and neutral circuits until the fuse opens. Normally, only a small
ther by a minimum of 2500 volts. If the phase
8
Industrial Control Services
(T3464)
AC Guarded Digital Output Module
current flows through the neutral wire, so it
is important to size both the line and neutral wiring to enable them to handle this fault current.
Modules report a open load fault when an output is commanded on and no user load is connected. All output circuits in service must have load connections for proper diagnostic operation. Unused outputs can be left unconnected so long as they are never commanded to be on. These modules do not test for load faults when an output circuit is commanded off.
Blown fuse detection is independent of user load connec
tion or output circuit on/off state. However; when operating in a fault tolerant configuration, the module will report an “OC” (open circuit) fault instead of a “BF” (blown fuse) fault if both outputs are on and only one of the two outputs has a blown fuse.
The module should not be used in applications where a one
-
time 200 millisecond load bump (turn-on) cannot be tolerated.

Fail-Safe Configuration

As shown in Figure 3, the fail-safe configuration uses a single Guarded module. will cause the output to fail to the off state.
In this configuration, the worst case failure
In a fail-safe configuration, removing the module disables all outputs.
PD-6021
Mar-06
Figure 3. Fail-Safe Configuration.
9
AC Guarded Digital Output Module
(T3464)

Fault Tolerant Configuration

For fault tolerant operation, two Guarded modules are connected in parallel as shown in Figure 4. In this configuration, operation continues even if one module fails.
In the fault tolerant configuration, a failed module can be removed and replaced without interrupting operation of the loads.
Figure 4. Fault Tolerant Configuration.

Fault Tolerant Configuration with Redundant Actuators

When redundant actuators are installed in the field, the level of fault protection can be extended to include the field wiring and actuators. Each actuator should be connected to an individual guarded output module as shown in Figure 5.
In this configuration continuous operation can be maintained even if a module, field wiring or load fault occurs.
10
Industrial Control Services
(T3464)
AC Guarded Digital Output Module
Figure 5. Fault Tolerant Configuration with Redundant

Field Wiring

Actuators.
Field wiring terminal blocks on the I/O chassis are used to connect power sources and loads to the module. The terminal blocks are located directly above and below the slot where the module is installed. Each terminal block consists of ten #6 wire clamp screw terminals capable of holding two 12-AWG wires.
Each module has separate power line and neutral terminals for each output group (group 1: channels 1-8, group 2: channels 9-16). The two groups are electrically isolated from each other (2500 volts minimum). Figure 6 shows the proper field wiring for a single module and Figure 7 shows the field wiring for fault tolerant modules connected in parallel.
PD-6021
Mar-06
11
AC Guarded Digital Output Module
(T3464)
12
Figure 6. Fail-Sa
fe Field Wiring.
Industrial Control Services
(T3464)
AC Guarded Digital Output Module
PD-6021
Mar-06
Figure 7. Fault Tolerant Field Wiring.
13
Module
Upper
Connector
Lower
Connector
T3464
17
3
AC Guarded Digital Output Module
(T3464)

Fault Mode Jumper

The fault mode jumper is located behind the ID switch cover in the lower left-hand corner of each I/O chassis. The position of the fault mode jumper determines the module's response to system level faults. The fault mode jumper’s position will cause all output modules in the I/O chassis to either shutdown (turn off all outputs) or to hold (hold the last state) after a system level f failure is the failure of two processor modules.

Keying

The I/O chassis can be physically keyed to prevent accidental damage caused by inserting a module into a slot wired for a different module type. Figure 8 illustrates how the slot keys are installed on the I/O chassis slot field wiring connectors. The slot key positions for the AC Guarded output module are listed in Table 2.
ailure occurs. An example of a system level
Table 2. Slot Key Positions.
14
Industrial Control Services
(T3464)
AC Guarded Digital Output Module
PD-6021
Mar-06
Figure 8. Installing Slot Keys.

Configuration

Each output module is configured using the
W
INTERPRET
Configuration Editor. In the editor you will perform the three steps described below to configure the output module.
I/O
15
AC Guarded Digital Output Module
(T3464)
1) Set the Module Type:
Position the cursor on the module slot you wish to define. Choose Set Module Type from the Edit Menu and select the relay output module from the list.
2) Edit the Module Definition:
Choose Edit Module Definition from the Edit Menu. A dialog box will open where you can define the output point definitions.
Figure 9. AC Guarded Output Module Definition.
3) Edit each point:
Choose Edit from the Module Definition dialog box to define a name and description for each output point. In the Digital Output Point dialog, enter names and values for the configuration fields as described below.
Figure 10. Defining a Guarded Digital
Output Point.
16
Industrial Control Services
(T3464)
AC Guarded Digital Output Module

Name

Also called the tag name, this is the name used in the application program to reference the output point. The name can be up to 12 characters long.

Description

This 40-character field provides a place to describe the output point definition. The description is used to help document your system (it does not affect application program operation).

Comm Protect

Marking the Comm Protect check box protects the point from changes by communications functions such as data write, forcing, and load initial value when Comm Protect is enabled.

Initial Value

The initial value for the output is loaded to the Regent when you load the I/O configuration and also when you load the application program that controls the output.

Final Value

The final value for the output is loaded to the Regent when the application program that controls the output is deleted. Unless special circumstances exist, you should always enter zero, so that the output is turned off when you delete the application program that control

Output Module Definition

s it.
In addition to configuring output point definitions, you can configure an output module definition to represent the combined state of all 16 output points. The module definition represents the 16 output point definitions as signed, 16-bit integers. In this format, output 1 is the least significant bit (LSB) and output point 16 is the most significant bit (MSB).

Programming

Outputs are controlled by writing application programs that solve for output values. For example, placing an output tag name on a coil in ladder logic will cause the output to turn on when there is power flow to the coil in the ladder logic rung.
PD-6021
Mar-06
17
AC Guarded Digital Output Module
To program fault tolerant outputs two output coils driven by the same control logic are used as shown in Figure 11.
(T3464)

Maintenance

Figure 11. Programming Fault Tolerant Outputs.
In this illustration A, B, C, D represent various logic elements used to drive the outputs; XV103A represents the output on on
e Guarded output module; and XV103B represents the
output on the other Guarded output module.
No periodic maintenance or calibration is required for this module.
Fuses can be removed and replaced without removing the module from the I/O chassis. Turning the fuse holder one quarter turn from its locked position releases the fuse holder, extending the fuse and allowing it to be removed.
To prevent damage to the module, replacement fuses must be of the same rating and type (see Specifications, bel

Diagnostic Messages

-
ow).
18
When the module is first inserted into an I/O chassis or when system power is applied, the display will go through the initialization sequence shown in Table 3.
Industrial Control Services
(T3464)
Step Display
Description
1
8.8.8.8.
Display test. Displayed for 1 second.
2
AFO
RAM test. Displayed for 1 second. If this test fails, the testing stops and the AFO message remains on.
3
PF
PROM test. Displayed briefly. If this test fails
, the testing stops and the PF message remains on.
4
. . . . .
Normal display mode. Decimal points blink to indicate processor activity.
5
- -
.
-
Decimal point number three should be illuminated constantly after about 15 seconds. This indicates the AC power source is stable and output circuits are being tested.
AC Guarded Digital Output Module
The diagnostic messages displayed as the module operates are used together with the module’s active and fault indicators.
A red FAULT indication on the module together with a diagnostic message can be caused by either a power, wiring, or load problem or by a module fault or failure.
Table 3. Initialization Sequence.
A red FAULT indication
without
a diagnostic message display can indicate either a failed module or a fault that has already been corrected. If the fault has been corrected, the diagnostic message display will clear itself; however the module’s FAULT indicator must be cleared by a voted reset. If the FAULT indicator does not clear after a voted reset it is because the module itself has failed and must be replaced.
PD-6021
Mar-06
19
Display
Description
AC
AC quality problem (i.e. frequency is out of tolerance, frequency is unstable, or phase difference between output groups 1-8 and 9-16).
AC.ab
AC power failure at field terminals A/B (output group 1-8).
AC.cd
AC power failure at field terminals C/D (output group 9-16).
Shud
Outputs are shut down (off). Caused by the loss of controller communications or the module is not configured in the system.
Hold
Outputs are held at last stat
e. Caused by the loss of controller
communications.
BFnn
Blown fuse on output nn.
OLnn
Open load on output nn. Displayed only when output is on.
OCnn
Open circuit on output nn. Switch is not able to close.
SCnn
Short circuit on output nn. Switch is not able to open. The crowbar switch was activated to blow the fuse. Blown fuse message is suppressed.
Safetybus Power
1.5 load units
Number of Inputs
16 circuits divided into two groups of eight
Voltage Range
90 to 130 VAC
Frequency Range
47 to 63 Hz
Phase Difference
1º maximum between group 1-8 and group 9-16
AC Guarded Digital Output Module
Ta
ble 4. Operating Diagnostic Messages.
(T3464)

Safety Considerations

Specifications

Although the AC Guarded output modules provide extensive
diagnostics and testing features, they have only been TÜV certified to Risk Class 5 as non-interfering. For safety systems that require TÜV approved equipment, the T3484 Monitored Guarded output module is recommended.
20
Industrial Control Services
(T3464)
Load Current (maximum)
1 amp maximum per output 0°
to 40° C, derated linearly
to 0.5 amp at 60° C 16 amps maximum per
module at 0° C, derated linearly to 8 amps at 60° C
Load Current (minimum)
Guarded mode: Fault tolerant mode:
50 mA 150 mA
Line Current
Load current plus 16 amps transient during crowbar actuation
Neutral Current
16 amps maximum transient during crowbar actuation
On State Drop
1.6 V, maximum
Surge Current
10 amps for 20 msec
Output Leakage
Guarded mode: Fault tole
rant mode:
5 mA maximum at 60 Hz 10 mA maximum at 60 Hz
Fusing
One 2 A, 250 V, fast acting (3AG) per output, front panel mounted
Turn-On Delay
1 AC cycle maximum
Turn-Off Delay
1.5 AC cycle maximum
Over Voltage Protection
160 VAC, continuous
Load Bump
(Turn-on)
70 V peak for 1.1 msec, 3
pulses, repeating once per 2 seconds. 130 VAC for 200 msec, one
­time for shorted output circuit
Heat Dissipation
33 Watts, 111 BTUs/hour
AC Guarded Digital Output Module
PD-6021
Mar-06
21
Isolation
2500 volts minimum (field wiring to control logic) 2500 volts minimum
(output group 1-8 to output group 9-16)
Operating Temperature
0°
to 60° C
(32° to 140° F)
Storage Temperature
-40°
to 85° C
(-40°
to 185° F)
Operating Humidity
0 to 95% relative humidity, non-condensing
Vibration
10 to 55 Hz:
±0.15mm
Shock
Operating:
15 g, ½ sine wave, 11 msec
Electromagnetic Interference
IEC 801 Part 2 - Electrostatic Discharges
IEC 801 Part 3 - Radiated Electromagnetic Fields
ANSI/IEEE C37.90 - Surge Withstand Capability
Level 3: Contact discharge of 6 kV Level 3: 10 V/M, 27 MHz ­500 MHz
1 kV damped 1 MHz sine wave
Safety
Certified to DIN V VDE 0801 for Risk Class 5, non
­interfering. Also designed to meet UL 508 and CSA 22.2, No. 142-M1981
Dimensions
Height: Width: Depth:
12.6" (320 mm)
1.27" (32 mm)
10.12" (257 mm)
Weight
5.0 lbs (2.3 kg)
AC Guarded Digital Output Module
(T3464)
22
Industrial Control Services
Loading...