Rockwell Automation T3446H User Manual

ICS Regent
®
PD-6017
Relay Output Modules
Low Power and High Power
(T3446L and T3446H)
Issue 1,
Relay output modules provide control of eight user output loads. Two types of relay output modules are available providing dry contact relay closure outputs for switching a variety of AC and DC voltages to field loads. Each module's triplicated I/O Safetybus interface ensures that no Regent system failure can incorrectly apply power to an output and that no failure in the module can affect the operation of the Regent system or other I/O modules in the system.
March, 06
Features
·
Eight isolated, d form-A or Form-B selectable.
·
Hot replaceable.
·
Automatic self-testing of triplicated I/O Safetybus circuits and many simplex logic circuits.
·
High power modules (T3446H) operate up to 250 VAC/125 VDC switching loads rated at 500 VA or 100 Watts.
·
Low power modules (T3446L) operate up to 125 VAC/VDC switching loads rated at 60
·
Individual front panel indicators on each module show active and fault status, shutdown state, and output status (logic side).
·
TÜV certified, Risk Class 5, non-interfering.
ry contact relay outputs: four Form-C, and four
VA or 30 Watts.
1
Relay Output Modules
(T3446L, H)

Module Operation

A block diagram of a typical relay output module is shown in Figure 1.
The processor modules send triplicated write data commands to the output module over the I/O Safetybus. The processors’ addressing data and data write commands are voted by the module (preventing I/O Safetybus failures upstream from the module from affecting module operation). The voted result is then passed to the I/O bus interface logic.
2
Figure 1. Block Diagram of a Relay Output Module.
The voted output data from the I/O bus interface logic is then used to drive the output circuits. Logic output drive signals energize the coils of relays mounted on the printed circuit board. Re devices.
When the output is logically turned on, the relay coil is energized (closing the N.O. contact), and when the output is
lay contacts provide dry-contact switching of load
Industrial Control Services
(T3446L, H)
logically turned off, the relay coil is de-energized (closing the N.C. contact).
The relay provides logic-to-field isolation between the module’s logic and field circuits — protecting the output module from field signal over voltages, transients, and other electrical disturbances.
Both types of relay output module use UL 508 approved relays.
Relay Output Modules

Testing and Diagnostics

Each module’s voter circuits are periodically tested by the processor modules. Discrepant data are sent through one of three legs of the I/O Safetybus to determine whether the module’s voter is able to outvote the incorrect data. A failure to return the correct majority-voted result to the processors produces an I/O module error indication at the processor modules and a module fault indication at the I/O module.
Each type of module has a unique identification code read by the controller. This code lets the controller know which type of module is installed in each I/O chassis slot and how to address that module and its points specifically. If a module is removed, or is replaced with a module of a different type, the processor modules will indicate an I/O module error.
Loopback logic tests periodically write data to the module and then read it back to determine whether the module’s I/O bus interface logic is functioning correctly.

Front Panel Indicators

that is
PD-6017
Mar-06
Th
e relay output module is shown in Figure 2. The front panel contains active and fault status indicators, a shutdown indicator, and output status indicators for each output circuit.

Active and Fault Status Indicators

These green and red LEDs indicate the overall health of the module. During normal operation the green ACTIVE indicator flashes at the controller's scan rate. If a module fault is detected the red FAULT indicator turns on and the green indicator turns off.
3
Note:
Relay Output Modules
(T3446L, H)
Shutdown
Indicator
Upon loss of communications with the controller, output modules enter either a shutdown or hold fault mode. If the I/O assembly is set to shutdown, the red SHUTDOWN indicator will turn on when communications with the controller are lost. If the I/O assembly is set to hold, the SHUTDOWN indicator will always be off (see page 13, Fault Mode Jumper).
When the module is installed in the I/O chassis or when logic power (from the I/O power supply modules) is first applied
to the module, it will be in the shutdown mode until the first output scan, regardless of the fault mode jumper settings. Also, removing two I/O transceiver modules, two I/O power supply modules, or two power legs will cause the module to be in the shutdown mode.

Output Status Indicators

The output status indicators are yellow LEDs located on the logic-side (coil) of the relay output. There are eight output status indicators
— one for each output. These indicators are lit when the output relay coil is energized, closing the normally open contact.
4
Industrial Control Services
(T3446L, H)
Relay Output Modules
PD-6017
Mar-06
Figure 2. Relay Output Module.
5
Relay Output Modules
(T3446L, H)

Application

Simplex Configuration

Relay output modules provide a suitable interface to non critical output devices. These non-critical devices typically include status alarms or other field devices that are not used for primary safety shutdown purposes. Although much of the circuitry on the relay output module is automatically tested, some logic circuits and the field-sid and non-tested. This simplex configuration is illustrated in Figure 3. For safety-critical outputs requiring fail-safe or fault tolerant output configurations, Guarded digital output modules should be used.
-
e output switch are simplex
6
Figure 3. Simplex Relay Output Configuration.

Field Wiring

Field wiring terminal blocks on the I/O chassis are used to connect power sources and loads to the module. The terminal blocks are module is installed. Each terminal block consists of ten #6 wire clamp screw terminals capable of holding two 12 AWG wires.
Each module has two terminals for each Form-A or Form-B selectable relay (channels 1, 2, 7, and 8), and three terminals for each Form-C relay (channels 3, 4, 5, and 6). Figure 4 shows the correct field wiring connections for the relay output modules.
located directly above and below the slot where the
Industrial Control Services
Loading...
+ 14 hidden pages