Rockwell Automation T3441A User Manual

ICS Regent
®
PD-6015
DC Digital Output Module
24 VDC
(T3441A)
Issue 1,
The DC digital output module provides cont output loads. One type of module is available to interface to outputs powered from a nominal 24 VDC field power supply. Each module's triplicated I/O Safetybus interface ensures that no Regent system failure can incorrectly apply power to an output, and that no failure in the module can affect the operation of the Regent system or other I/O modules in the system.
rol of 16 user
March, 06
Features
·
Sixteen output circuits, configured as two isolated groups of eight circuits each.
·
Hot-replaceable.
·
Automatic self-testing of triplicated I/O Safetybus circuits and many simplex logic circuits.
·
2 amp output circuits.
·
Individual front panel indicators on each module show active/fault, shutdown, blown fuse, and output on/off status (field side).
·
2500 volt minimum electrical isolation between field and logic circuits.
·
TÜV certified, Risk Class 5, non-interfering.
1
DC Digital Output Module
(T3441A)

Module Operation

A block diagram of a typical 24 VDC digital output module is shown in Figure 1.
The processor modules send triplicated write data commands to the output module over the I/O Safetybus. The processors’ addressing data and data write commands are voted by the module (preventing I/O Safetybus failures upstream from the module from affecting module operation). The voted result is then
passed to the I/O bus interface logic.
2
Figure 1. Block Diagram of 24 VDC Digital Output Module.
The voted output data from the I/O bus interface logic is then used to drive the output circuits. Power MOSFETs are used on the outputs to convert the logic level output drive signals to switch 24 VDC power to load devices. These output circuits provide a very low on state voltage drop and low off state leakage.
Industrial Control Services
(T3441A)
DC Digital Output Module
When the output is logically turned on, th energized, and when the output is logically turned off, the field device is de-energized.
Optical isolation between the module’s logic and field circuits provides logic-to-field isolation module from field signal over voltages, transients, and other electrical disturbances. It also provides a safety barrier between the primary field voltages and user accessible circuits.
Each output is individually fused to protect the circuits from short circuit conditions in ou

Testing and Diagnostics

Each module’s voter circuits are periodically tested by the processor modules. Discrepant data are sent through one of three legs of the I/O Safetybus to determine whether the module’s voter is able to outvote the incorrect data. A failure to return the correct majority-voted result to the processors produces an I/O module error indication at the processor modules and a module fault indication at the I/O module.
— protecting the output
tput wiring and field devices.
e field device is
Each type of module has a unique ide read by the controller. This code lets the controller know which type of module is installed in each I/O chassis slot and how to address that module and its points specifically. If a module is removed, or is replaced with a module of a different type, the processor modules will indicate an I/O module error.
Loopback logic tests periodically write data to the module and then read it back to determine whether the module’s I/O bus interface logic is functioning correctly.
Fuses are must be connected to the output module in order for it to detect a blown fuse.

Front Panel Indicators

The 24 VDC digital output module is shown in Figure 2. The front panel contains active and fault status indicators, a shutdown indicator, blown fuse indicators (one per output group) and an output status indicator for each output circuit.
continually checked for continuity. Field power
ntification code that is
PD-6015
Mar-06
3
Note:
DC Digital Output Module
(T3441A)

Active and Fault Status Indicators

These green and red LEDs indicate the overall health of the module. During normal operation, the green ACTIVE indicator flashes at the controller’s scan rate. If a module fault is detected the red FAULT indicator turns on and the green ACTIVE indicator turns off.

Shutdown Indicator

Upon loss of communications with the controller, output modules enter either a shutdown or hold fault mode. If the I/O unit is set to shutdown, the red SHUTDOWN indicator will turn on when communications with the controller are lost. If the I/O unit is set to hold, the SHUTDOWN always be off (see page 8, Fault Mode Jumper).
indicator will
When the module is installed in the I/O chassis or when logic
power (from the I/O power supply modules) is first applied to the module, it will be in the shutdown mode until the first output scan, regardless of the fault mode jumper settings. Also, removing two I/O transceiver modules, two I/O power supply modules, or two power legs will cause the module to be in the shutdown mode.

Output Status Indicators

The output status indicators are yellow LEDs, located on the field side of the output. There are 16 output status indicators, — one for each output. These indicators are lit when the output FET is energized to turn on the load.

Blown Fuse Indicators

The red BLOWN FUSE indicators turn on when one of the fuses in the corresponding output group opens. A blown fuse will also cause the module’s FAULT indicator to turn on.
Field power must be connected to the module for it to detect a blown fuse. Refer to Maintena replacement instructions.
nce, page 12, for fuse
4
Industrial Control Services
(T3441A)
DC Digital Output Module
PD-6015
Mar-06
Figure 2. 24 VDC Digital Output Module.
5
Loading...
+ 9 hidden pages