Rockwell Automation T3431-CA User Manual

ICS Regent
®
PD-6024
Thermocouple Input Assembly
Input Module, Mux, Termination Panel and Cable
(T3431-IM, T3431-Mux, T3431-TP and T3431-CA)
Is
sue 1,
March, 06
The thermocouple input assembly consists of a thermocouple input module (T3431-IM), a thermocouple input multiplexer (T3431-MUX), a thermocouple termination panel (T3431-TP), and a thermocouple termination cable (T3431-CA). This equipment provides terminations and temperature conversion for as many as 24 thermocouple inputs, arranged in 3 groups of eight inputs.
Features
·
Twenty-four thermocouple inputs.
·
Configuration options: Thermocouple type: Units: Resolution: Filter response:
·
Complete linearization, cold junction compensation and automatic calibration.
·
Remote terminations up to 50 cable feet from I/O chas
·
2500 volt isolation between Input Module and Mux.
·
High speed acquisition.
·
Hot-replaceable input module and Mux.
·
Extensive fault diagnostics.
·
Thermocouple burnout detection (downscale).
·
TÜV certified, Risk Class 5, non-interfering.
The input module plugs into an I/O chassis slot and receives data from the thermocouple input multiplexer (or Mux). The thermocouple input multiplexer plugs into the termination panel and provides low level signal conditioning,
J, K, S, T (in groups of eight) Degrees F or degrees C Units or tenths 50 Hz, 60Hz rejection
sis.
1
Thermocouple Input Assembly
multiplexing, and analog-to-digital conversion. The termination panel can be located as far as 50 cable feet from the I/O chassis.
Each module’s triplicated I/O Safetybus interface ensures that no failure in the module can affect the operation of the Regent system or other I/O modules in the system. Extensive fault detection and annunciation of critical redundant circuits help prevent the controllers from receiving erroneous data from a faulty input module. The fault tolerant boundary may be extended by using three input modules and three termination panels. A single thermocouple is wired to three different termination panels for fault tolerance. The fault tolerant boundary may be further extended into the process by wiring three separate thermocouples, all measuring the same process parameter, to three separate termination panels. In either triplicated configuration, a failed module or multiplexer can be removed and replaced without interrupting the inpu signals.
(T3431)
t

Module Operation

A simplified block diagram of the thermocouple input assembly is shown in Figure 1.
Thermocouples are terminated at the termination panel. The termination panel routes the thermocouple signals to the Mux for multiplexing, signal conditioning, and A to D conversion. The Mux also senses the cold junction sensor voltages. Cold junction sensors are mounted on the termination panel near the screw terminations.
The termination cable connects the termination panel to the input module. A DC-to-DC converter on the input module shares three power legs from the I/O backplane power and provides isolated power to the Mux over the termination cable. The Mux transmits digitized serial thermocouple data back to the input module. The maximum allowable cable length is 50 feet.
2
Industrial Control Services
Thermocouple Input Assembly
(T3431)
Figure 1. Block Diagram of the Thermocouple Input Assembly.
The Serial data received from the Mux is optically coupled at the input m
odule to provide electrical isolation. The input module's 68000-based microcomputer processes the thermocouple data. This microcomputer’s functions include:
·
Digital filtering
·
Automatic calibration
·
Cold junction compensation
·
Temperature conversion and linearization
·
Diagnostics
The processor modules send triplicated read data req the thermocouple input module over the I/O Safetybus. The processors’ addressing data and data read requests are voted by the module (preventing I/O Safetybus failures upstream from the module from affecting module operations). The voted result is then passed to the I/O bus interface logic.
uests to
PD-6024
Mar-06
3
Thermocouple Input Assembly
After receiving the voted data read request, the microcomputer transmits the conditioned temperature data to the Safetybus interface. This interface places the voted temperature data onto the triplicated Saf Each of the three bus drivers is independently powered and controlled (by the I/O transceiver modules) — preventing failures in a single driver from propagating to the other two I/O busses. The bus drivers then transmit the data via the backplane I/O Safetybus to the I/O transceiver modules which, in turn, transmit the data to the processors.
The thermocouple input data is packaged as a 16-bit word for each input. The format of each word is shown in Figure 2. The most significant bit in the word is used as an alarm bit to indicate an out-of-range thermocouple input signal. The remaining 15 bits contain signed 15-bit integer data representing the temperature in degrees C or F and in units or tenths of degrees, as configured by jumper settings on the Mux.
(T3431)
etybus bus drivers.
Figure 2. Thermocouple Input Data Format.

Testing and Diagnostics

Input Module Testing

Each module’s voter circuits are periodically tested by the p
rocessor modules. Discrepant data are sent through one of three legs of the I/O Safetybus to determine whether the module’s voter is able to outvote the incorrect data. A failure to return the correct majority-voted result to the processors produces an I/O module error indication at the processor modules and a module fault indication at the I/O module.
4
Industrial Control Services
Thermocouple Input Assembly
(T3431)
Each type of module has a unique identification code that is read by the controller. This code lets the controller know which type of module is installed
in each I/O chassis slot and how to address that module and its points specifically. If a module is removed, or is replaced with a module of a different type, the processor modules will indicate an I/O module error.
Loopback logic tests periodically write data to the module and then read it back to determine whether the module’s I/O bus interface logic is functioning correctly.

Multiplexer Testing

The serial communications link to the thermocouple Mux is continuously monitored. Additionally the data r
eceived from the Mux is checked for proper data format, parity and numeric range reasonableness. The cold junction sensor values are monitored and compared to detect a failed cold junction sensor. The precision voltage references on the multiplexer are also checked to verify that the power to the Mux is present and that the voltage references are within tolerance.

Input Module Front Panel Indicators

Figure 3 shows the physical features of the thermocouple input module. The front panel of each module contains status indicators to display the operational status of the input module, multiplexer and cold junction sensors.

Active and Fault Status Indicators

These green and red LEDs indicate the overall health of the module. During normal operation the green ACTIVE indicator flashes at the controller's scan rate. If a module fault occurs the red FAULT indicator turns on and the green ACTIVE indicator turns off.
PD-6024
Mar-06

MUX Fault Indicator

The red MUX FAULT indicator turns on when any following fault conditions are detected:
·
No data received from the Mux.
·
Corrupted data from the Mux.
·
Unreasonable data values from the Mux.
5
of the
Thermocouple Input Assembly
Failure of the DC-to-DC converter supplying power to the termination panel or the receiver circuitry can also result in a MUX fault. Both of these faults are input module faults.
(T3431)

CJ Fault Indicator

There are two cold junction sensors located on the termination panel. The red CJ FAULT indicator turns on when any of the following fault conditions are detected:
·
Either CJ sensor temperature is < -5°
·
Either CJ sensor temperature is > 65° C (149° F)
·
The CJ sensors differ by more than 2.8° C (5° F)
C (23° F)
6
Industrial Control Services
Thermocouple Input Assembly
(T3431)
PD-6024
Mar-06
Figure 3. Thermocouple Input Module.

Termination Panel and Multiplexer

Figure 4 shows the physical features of the Termination Panel and Multiplexer. The multiplexer plugs into the termination panel and is secured in place with two thumb screws located at each end of the multiplexer.
7
Thermocouple Input Assembly
The termination cable plugs into the DB-9 connector located at the upper right corner of the termination panel. Thermocouple inputs are ter located along the bottom of the termination panel. These terminals are arranged in three groups of eight inputs. Two screw terminals are provided for each thermocouple input. Two additional ground terminals within each group are provided to connect thermocouple cable shield wires if desired.
(T3431)
minated at the screw terminals

Termination Panel Indicators

The termination panel has status indicators for power supply voltages, and transmit data. When positive and negative supply voltages are present at the termination panel, the POWER + and POWER -
indicators are on. The TX DATA indicator is on when the Mux is transmitting data to the input module. Normally, all these green indicators should be on.
8
Industrial Control Services
Thermocouple Input Assembly
(T3431)
PD-6024
Figure 4. Thermocouple Termination Panel and Multiplexer.
Mar-06
9
Loading...
+ 18 hidden pages