Rockwell Automation PF6000 Reference Manual

Rockwell Automation PF6000 Reference Manual

Reference Manual

Rockwell Automation Library of Process Objects:

PowerFlex 6000 Drive (P_PF6000)

 

 

 

 

 

 

 

 

 

IMPORTANT

This manual applies to the Rockwell Automation Library of Process Objects version 3.5 or earlier.

 

 

 

 

 

 

For Rockwell Automation Library of Process Objects version 5.0, see

 

 

 

 

 

 

PROCES-RM200

 

 

 

 

 

 

For Rockwell Automation Library of Process Objects version 4.0 or later, use the following manuals:

 

 

 

 

 

 

PROCES-RM013 contains logic instructions

 

 

 

 

 

 

PROCES-RM014 contains display elements

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Important User Information

Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).

Allen-Bradley, ControlLogix, FactoryTalk, Logix5000, PlantPAx, PowerFlex, Rockwell Automation, Rockwell Software, RSLogix, and Studio 5000 Logix Designer are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Table of Contents

Preface

Software Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

PowerFlex 6000 Drive (P_PF6000) Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Required Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Controller File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Visualization Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Controller Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

PowerFlex Drive InOut Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . 12

PowerFlex 6000 Drive Input Structure . . . . . . . . . . . . . . . . . . . . . . 14

PowerFlex 6000 Drive Output Structure . . . . . . . . . . . . . . . . . . . . 19

PowerFlex 6000 Drive Local Configuration Tags. . . . . . . . . . . . . 23

Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Programming Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Display Elements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

State Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Status/Quality Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Mode Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Alarm Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Maintenance Bypass Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Using Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Quick Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

Trends Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

PowerFlex Drive Faceplate Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

3

Table of Contents

Notes:

4

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

Preface

Software Compatibility

This manual describes the Add-On Instruction that controls and monitors a PowerFlex® 6000 Medium Voltage Variable Frequency Drive.

For the latest compatible software information and to download the Rockwell Automation® Library of Process Objects, see the Product Compatibility and Download Center at http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page.

For general library considerations, see Rockwell Automation Library of Process Objects, publication PROCES-RM002.

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.

Table 1 - Additional Resources

Resource

Description

 

 

PlantPAx® Distributed Control System Selection Guide,

Provides information to assist with equipment

publication PROCES-SG001

procurement for your PlantPAx system.

 

 

PlantPAx Distributed Control System Reference Manual,

Provides characterized recommendations for

publication PROCES-RM001

implementing your PlantPAx system.

 

 

Rockwell Automation Library of Process Objects,

Provides general considerations for the PlantPAx system

publication PROCES-RM002

library of process objects.

 

 

FactoryTalk® View Machine Edition User Manual,

Provides details on how to use this software package for

publication VIEWME-UM004

creating an automation application.

 

 

FactoryTalk View Site Edition User Manual,

Provides details on how to use this software package for

publication VIEWSE-UM006

developing and running human-machine interface

 

(HMI) applications that can involve multiple users and

 

servers, distributed over a network.

 

 

PowerFlex 6000 Medium Voltage Variable Frequency Drive

Provides details regarding functions, parameters, and

Parameter Manual, publication 6000-TD004

troubleshooting information for medium voltage

 

PowerFlex 6000 drives.

 

 

Rockwell Automation Library of Process Objects: Common

Details how to monitor an input condition to raise an

Alarm Block (P_Alarm) Reference Manual, publication

alarm. Information includes acknowledging, resetting,

SYSLIB-RM002

inhibiting, and disabling an alarm. Generally the

 

P_Alarm faceplate is accessible from the Alarms tab.

 

 

Rockwell Automation Library of Process Objects: Interlocks

Explains how to collect (sum up) the interlock

with First Out and Bypass (P_Intlk) Reference Manual,

conditions that stop or de-energize a running or

publication SYSLIB-RM004

energized piece of equipment or prevent it from

 

starting or being energized.

 

 

Rockwell Automation Library of Process Objects: Common

Explains how to choose the Mode (owner) of an

Mode Block (P_Mode) Reference Manual, publication

instruction or control strategy. The Mode instruction is

SYSLIB-RM005

usually embedded within other instructions to extend

 

their functionality.

 

 

Rockwell Automation Library of Process Objects: Permissives

Details how to collect permissive conditions to start a

with Bypass (P_Perm) Reference Manual, publication

piece of equipment.

SYSLIB-RM007

 

 

 

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

5

Preface

Table 1 - Additional Resources

Resource

Description

 

 

Rockwell Automation Library of Process Objects: Restart

Explains how to protect a large motor from damage

Inhibit for Large Motor (P_ResInh) Reference Manual,

caused by repeated starts.

publication SYSLIB-RM009

 

 

 

Rockwell Automation Library of Process Objects: Run Time

Explains how to accumulate the total run time and

and Starts (P_RunTime) Reference Manual, publication

count of starts for a motor or other equipment.

SYSLIB-RM010

 

 

 

6

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

Add-On Instruction

Guidelines

PowerFlex 6000 Drive (P_PF6000)

The P_PF6000 (PowerFlex 6000 drive) object is used to operate one variable-speed motor by using a PowerFlex 6000 medium voltage variable frequency AC drive. The drive operates via an add-on EtherNet/IP interface.

The Add-On Instruction controls the drive in various modes and monitors fault conditions. The global objects and faceplate that is shown are examples of the graphical interface tools for this instruction.

Global Objects

Faceplate

This instruction operates a motor connected to a PowerFlex 6000 variable frequency AC drive, which is communicating with the controller over an EtherNet/IP network.

IMPORTANT The drive interface is designed to work with the Studio 5000 Logix Designer® application, Version 20 and later.

The PowerFlex 6000 drive has specific parameter read/write functionality. For details, see Knowledgebase Answer ID 1008677 at https://www.rockwellautomation.custhelp.com.

Do not use this instruction in these situations:

You need to operate a single-speed motor (running and stopped only). Use the P_Motor instruction instead.

You need to operate a two-speed motor (fast, slow, and stopped only). Use the P_Motor2Spd instruction instead.

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

7

PowerFlex 6000 Drive (P_PF6000)

Functional Description

You need to operate a simple reversing motor (forward, reverse, and stopped only). Use the P_MotorRev instruction instead.

You need to operate a motor with multiple discrete speeds. You need specific logic for this motor. The P_PF6000 instruction is designed for motors with continuously variable (analog) speed, not multiple discrete speed selections. You can use the P_D4SD or P_nPos instruction for motors with multiple discrete speeds.

You are using a drive other than the PowerFlex 6000 drive. Instead, use these Add-On Instructions:

P_PF52x for the PowerFlex 523 or PowerFlex 525 drive on an EtherNet/IP network

P_PF753 for the PowerFlex drive with 20-COMM-E EtherNet/IP Interface

P_PF755 for the PowerFlex AC variable frequency drive

P_PF7000 for the PowerFlex 7000 medium voltage AC variable frequency drive with 20-COMM-E EtherNet/IP interface.

P_VSD for third-party drives, drives on other networks, or via hardwired I/O

The P_PF6000 instruction provides the following capabilities:

Ownership of the drive through the standard P_Mode Add-On Instruction and modes.

Ability to start and stop the drive and motor, control the drive speed (via speed reference), and monitor the drive run status and speed feedback to verify whether the drive is running or stopped. Provides alarms and drive shutdown for Fail to Start and Fail to Stop if the feedback does not follow the commanded state within a configured amount of time.

Reading from the drive, the instruction displays drive faults, general drive status data, and a number of operating parameters.

Ability to read fault data from the drive and provide descriptive text with fault codes.

Indication of Warning or Alarm status as received from the drive.

Input and alarm for a drive fault condition and an output to send a drive fault reset to the drive. Provide a configurable time to pulse the drive fault reset output when a reset command is received.

Permissives (bypassable and non-bypassable) that are conditions that enable a drive start and Interlocks (bypassable and non-bypassable) that are conditions that stop the drive and help prevent starting. Provide an alarm when an Interlock stops the drive. Provide maintenance the capability to bypass the bypassable Permissives and Interlocks.

8

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

PowerFlex 6000 Drive (P_PF6000)

Required Files

Maintenance personnel can disable (soft lock out) the drive. This capability is not a substitute for hard lockout/tagout (LOTO) procedures.

Monitor an I/O fault input and a communication watchdog timer, and alarm on an I/O or communication failure. The failure condition can optionally de-energize the outputs to the drive, requiring a reset.

In Override mode, provide an override state input that determines if the override is to run or stop the drive (default = stop), and, if the drive is to run, an override speed reference and direction.

The instruction provides simulation capability. Outputs to the drive are kept de-energized, but the object can be manipulated as if a working drive were present, including a basic ramp-up of speed feedback value on starting and ramp-down on stopping. The simulated ramp-up-to-speed time is configurable. This capability is often used for activities such as system testing and operator training.

Add-On Instructions are reusable code objects that contain encapsulated logic that can streamline implementing your system. This functionality lets you create your own instruction set for programming logic as a supplement to the instruction set provided natively in the ControlLogix® firmware. An Add-On Instruction is defined once in each controller project, and can be instantiated multiple times in your application code as needed.

Controller File

The P_PF6000_3_5-00_RUNG.L5X rung import must be imported into the controller project to be used in the controller configuration. The service release number (boldfaced) can change as service revisions are created.

Visualization Files

This Add-On Instruction has associated visualization files that provide a common user interface. These files can be downloaded from the Product Compatibility and Download Center at http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page.

IMPORTANT The visualization file dependencies require Process Library content imports to occur in a specific order as reflected in the following tables:

Images

Global Objects

Standard Displays

HMI Tags

Macros

Images are external graphic files that can be used in displays. They must be imported for FactoryTalk View software to make use of them.

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

9

PowerFlex 6000 Drive (P_PF6000)

When PNG files are imported, they are renamed by FactoryTalk View software with a .bmp file extension, but retain a .png format.

Table 2 - Visualization Files: Images (.png)

FactoryTalk View SE Software

FactoryTalk View ME Software

Description

 

 

 

All .png files in the images folder

All .png files in the images folder

These are the common icons that are used in the global

 

 

objects and standard displays for all Process Objects.

 

 

 

The Global Object files (.ggfx file type) in the following table are Process Library display elements that are created once and referenced multiple times on multiple displays in an application. When changes are made to a Global Object, all instances in the application are automatically updated.

Table 3 - Visualization Files: Global Objects (.ggfx)

FactoryTalk View SE Software

FactoryTalk View ME Software

Description

 

 

 

(RA-BAS) Common Faceplate Objects

(RA-BAS-ME) Common Faceplate Objects

Global objects used on process object faceplates.

 

 

 

(RA-BAS) P_VSD Graphics Library

(RA-BAS-ME) P_VSD Graphics Library

Drive global object device symbols used to build

 

 

process graphics.

 

 

 

(RA-BAS) Process Alarm Objects

(RA-BAS-ME) Process Alarm Objects

Global objects used for managing alarms on process

 

 

object faceplates.

 

 

 

(RA-BAS) Process Diagnostic Objects

(RA-BAS-ME) Process Diagnostic Objects

Diagnostic global objects used on process

 

 

object faceplates.

 

 

 

(RA-BAS) Process Faceplate Motor Objects

(RA-BAS-ME) Process Faceplate Motor Objects

Motor global objects used on process object faceplates.

 

 

 

(RA-BAS) Process Help Objects

(RA-BAS-ME) Process Help Objects

Global objects used for all process objects help displays.

 

 

 

(RA-BAS) Process Interlock Objects

(RA-BAS-ME) Process Interlock Objects

Global objects used for managing interlocks and

 

 

permissives on process object faceplates.

 

 

 

(RA-BAS) Process Mode Objects

(RA-BAS-ME) Process Mode Objects

Global objects used for managing modes on process

 

 

object faceplates.

 

 

 

The Standard Display files (.gfx file type) in the following table are the Process

Library displays that you see at runtime.

Table 4 - Visualization Files: Standard Displays (.gfx)

FactoryTalk View SE Software

FactoryTalk View ME Software

Description

 

 

 

(RA-BAS) Common-AnalogEdit

N/A

Faceplate used for analog input data entry. The FactoryTalk

 

 

View ME faceplates use the native analog input data entry

 

 

so no file is required.

 

 

 

(RA-BAS) P_Alarm-Faceplate

(RA-BAS-ME) P_Alarm-Faceplate

The faceplate that is used for the object

 

 

 

(RA-BAS) P_Alarm-Help

(RA-BAS-ME) P_Alarm-Help

Alarm Help information that is accessed from the

 

 

P_AIarm faceplate.

 

 

 

(RA-BAS) P_Mode-Config

(RA-BAS-ME) P_Mode-Config

The Configuration Display used to configure the

 

 

P_Mode object.

 

 

 

(RA-BAS) P_Mode-Help

(RA-BAS-ME) P_Mode-Help

Mode Help information that is accessed from the

 

 

Help faceplate.

 

 

 

(RA-BAS) P_PF6000-Faceplate

(RA-BAS-ME) P_PF6000-Faceplate

The faceplate display that is used for the object

 

 

 

(RA-BAS) P_PF6000-Quick

(RA-BAS-ME) P_PF6000-Quick

The Quick display that is used for the object

 

 

 

(RA-BAS) Process Motor Family-Help

(RA-BAS-ME) Process Motor Family-Help

The Help display for Motor objects

 

 

 

10

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

PowerFlex 6000 Drive (P_PF6000)

Table 4 - Visualization Files: Standard Displays (.gfx)

FactoryTalk View SE Software

FactoryTalk View ME Software

Description

 

 

 

(RA-BAS) P_Intlk-Faceplate

(RA-BAS-ME) P_Intlk-Faceplate

Optional

 

 

The interlock faceplate used for the object.

 

 

Use this file if your Discrete Output has an associated

 

 

P_Intlk object and you enable navigation to its faceplate

 

 

from the Discrete Output faceplate.

 

 

 

(RA-BAS) P_Perm-Faceplate

(RA-BAS-ME) P_Perm-Faceplate

Optional

 

 

Permissive faceplate that is used for the object

 

 

Use this file if your object has an associated P_Perm object

 

 

and you enable navigation to the P_Perm faceplate from

 

 

the object faceplate.

 

 

 

(RA-BAS) P_ResInh-Faceplate

(RA-BAS-ME) P_ResInh-Faceplate

Optional

 

 

Restart/inhibit faceplate display that is used for the object

 

 

Use this file if your object has an associated P_ResInh

 

 

object and you enable navigation to the P_ResInh

 

 

faceplate from the object faceplate.

 

 

 

(RA-BAS) P_RunTime-Faceplate

(RA-BAS-ME) P_RunTime-Faceplate

Optional

 

 

RunTime faceplate display that is used for the object

 

 

Use this file if your object has an associated P_RunTime

 

 

object and you enable navigation to the P_RunTime

 

 

faceplate from the object faceplate.

 

 

 

(RA-BAS) Process Interlock Family-Help

(RA-BAS-ME) Process Interlock Family-Help

Optional

 

 

Interlock/permissives help display that is used for

 

 

the object

 

 

Use this file if you use the P_Intlk or P_Perm faceplate.

 

 

 

HMI Tags are created in a FactoryTalk View ME application to support tab switching on Process Library faceplates. The HMI tags can be imported via the comma-separated values file (.csv file type) in the following table.

Table 5 - Visualization Files: HMI Tags (.csv)

FactoryTalk View SE Software

FactoryTalk View ME Software

Description

 

 

 

N/A

FTVME_PlantPAxLib_Tags_3_5_xx.csv

These tags must be imported into the

 

where xx = the service release number.

FactoryTalk View ME project to support switching tabs on

 

 

any Process Object faceplate.

 

 

 

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

11

PowerFlex 6000 Drive (P_PF6000)

Controller Code

This section describes the parameter references for this Add-On Instruction.

 

 

PowerFlex Drive InOut Structure

 

 

InOut parameters are used to link the Add-On Instruction to external tags that

 

 

contain necessary data for the instruction to operate. These external tags must be

 

 

of the data type shown.

Table 6 - P_PF6000 Drive InOut Parameters

 

 

 

 

 

 

 

 

Tag Name

Data Type

 

Description

 

 

 

 

 

Inp

P_PF6000_Inp

 

PowerFlex 6000 input assembly.

 

 

 

 

Out

P_PF6000_Out

 

PowerFlex 6000 output assembly.

 

 

 

 

Ref_FaultCodeList

P_DescList

 

Tag containing list of fault codes (DINT) and descriptions (STRING_40).

 

 

 

 

 

 

 

 

TIP

The user-defined data types (UDTs) and the Array tag containing the list of

 

 

 

 

PowerFlex 6000 fault codes and descriptions are included in the RUNG import

that brings in the P_PF6000 Add-On Instruction. See the programming example on page 28 for details.

The figure shows the drive fault table tags that are in each template.

Make sure the tag 'PF6000_FaultCodeList' is entered in the P_PF6000

Ref_FaultCodeList parameter.

12

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

PowerFlex 6000 Drive (P_PF6000)

Each fault code list provides pre-configured fault codes and descriptions for a given drive family.

For a complete list of fault codes, refer to the PowerFlex 6000 Medium Voltage Variable Frequency Drive Firmware, Parameters, and Troubleshooting Manual, publication 6000-TD004.

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

13

PowerFlex 6000 Drive (P_PF6000)

PowerFlex 6000 Drive Input Structure

Input parameters include the following:

Input data elements (Inp_) are typically used to connect field inputs from I/O modules or signals from other objects.

Configuration data elements (Cfg_) are used to set configurable capabilities and features of the instruction.

Command data elements (PCmd_, OCmd_, MCmd_) are used by program logic, operators, and maintenance personnel to request instruction actions.

Setting data elements (PSet_, OSet_, MSet_) are used by program logic, operators, and maintenance personnel to establish runtime setpoints, thresholds, and so forth. Set_ data elements (without a leading P, O, or M) establish runtime settings regardless of role or mode.

Table 7 - P_PF6000 Drive Input Parameters

Input Parameter

Data

Alias For

Default

Description

 

Type

 

 

 

 

 

 

 

 

 

EnableIn

BOOL

 

1

Ladder Diagram:

 

 

 

 

If the rung-in condition is true, the instruction’s Logic routine executes. If the

 

 

 

 

rung-in condition is false, the instruction’s EnableInFalse routine executes.

 

 

 

 

Function Block Diagram:

 

 

 

 

If true, or not connected, the instruction’s Logic routine executes. If the parameter

 

 

 

 

is exposed as a pin and wired, and the pin is false, the instruction’s EnableInFalse

 

 

 

 

routine executes.

 

 

 

 

Structured Text:

 

 

 

 

No effect. The instruction’s Logic routine executes.

 

 

 

 

 

 

Inp_PermOK

BOOL

 

1

1

= Permissives OK, drive can start.

 

 

 

 

 

 

Inp_NBPermOK

BOOL

 

1

1

= Non-bypassable permissives OK, drive can start.

 

 

 

 

 

 

Inp_IntlkOK

BOOL

 

1

1

= Interlocks OK, drive can start/run.

 

 

 

 

 

 

Inp_NBIntlkOK

BOOL

 

1

1

= Non-bypassable interlocks OK, drive can start/run.

 

 

 

 

 

Inp_Sim

BOOL

 

0

Simulation input. When set to 1, the instruction keeps outputs de-energized

 

 

 

 

(zero) and simulates a working drive. When set to 0, the instruction operates the

 

 

 

 

drive normally.

 

 

 

 

 

 

Inp_Hand

BOOL

 

0

1

= Request to acquire Hand mode.

 

 

 

 

0

= Release Hand mode.

 

 

 

 

 

 

Inp_Ovrd

BOOL

Mode.Inp_Ovrd

0

1

=Request to acquire Override mode.

 

 

 

 

0

= Release Override mode.

 

 

 

 

 

Inp_OvrdCmd

SINT

 

0

Override mode command:

 

 

 

 

0

= None

 

 

 

 

1

= Stop

 

 

 

 

2

= Start

 

 

 

 

 

Inp_OvrdSpeed

REAL

 

0.0

Value to set speed reference in Override mode (SpeedRef engineering units).

 

 

 

 

 

 

Inp_Reset

BOOL

 

0

1

= Reset drive fault conditions and latched alarms.

 

 

 

 

 

 

Cfg_AllowLocal

BOOL

 

0

1

=Allow Local Start/Stop without alarm.

 

 

 

 

0= Start/Stop from HMI/Program only.

 

 

 

 

 

Cfg_HasPermObj

BOOL

 

0

1 = Tells HMI a P_Perm is connected to Inp_Perm.

 

 

 

 

 

 

Cfg_HasIntlkObj

BOOL

 

0

1

=T ells HMI a P_Intlk is connected to Inp_Intlk.

 

 

 

 

 

 

Cfg_HasResInhObj

BOOL

 

0

1

= Tells HMI a P_ResInh Restart Inhibit is connected.

 

 

 

 

 

 

Cfg_HasRunTimeObj

BOOL

 

0

1

=T ells HMI a P_RunTime is connected.

 

 

 

 

 

 

14

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

 

 

 

 

 

PowerFlex 6000 Drive (P_PF6000)

 

 

 

 

 

 

Table 7 - P_PF6000 Drive Input Parameters

 

 

 

 

 

 

 

 

Input Parameter

Data

Alias For

Default

Description

 

Type

 

 

 

 

 

 

 

 

 

 

Cfg_SetTrack

BOOL

 

1

1

= PSets track OSets in Operator, OSets track PSets in Program.

 

 

 

 

0

= No tracking.

 

 

 

 

 

 

Cfg_SetTrackOvrdHand

BOOL

 

0

1

= Program/Operator settings track Override/Hand speed reference.

 

 

 

 

 

Cfg_PCmdClear

BOOL

Mode.Cfg_PCmdClear

1

When this parameter is 1, program commands are cleared once they are acted

 

 

 

 

upon. When set to 0, program commands remain set until cleared by the

 

 

 

 

application program logic.

 

 

 

 

IMPORTANT: Clearing this parameter online can cause unintended program

 

 

 

 

command execution.

 

 

 

 

 

Cfg_ProgDefault

BOOL

Mode.Cfg_ProgDefault

0

This parameter defines the default mode. When this parameter is 1, the mode

 

 

 

 

defaults to Program if no mode is being requested. When this parameter is 0, the

 

 

 

 

mode defaults to Operator if no mode is being requested.

 

 

 

 

IMPORTANT: Changing this parameter online can cause unintended mode

 

 

 

 

changes.

 

 

 

 

 

 

Cfg_OperStopPrio

BOOL

 

0

1

= OCmd_Stop available in any mode.

 

 

 

 

0

= OCmd_Stop only in Operator and Maintenance modes.

 

 

 

 

 

 

Cfg_OCmdResets

BOOL

 

0

1

= New Operator drive command resets fault.

 

 

 

 

0

= Reset required to clear fault.

 

 

 

 

 

 

Cfg_OvrdPermIntlk

BOOL

 

0

1

= Override ignores bypassable permissives/interlocks.

 

 

 

 

0

= Always use permissives/interlocks.

 

 

 

 

 

Cfg_ShedOnFailToStart

BOOL

 

1

1 = Stop motor and alarm on Fail to Start.

 

 

 

 

0

= Alarm only on Fail to Start.

 

 

 

 

IMPORTANT: If a condition is configured to shed the device to the Off state on a

 

 

 

 

fault, a reset is required to clear the shed fault to command the drive to a state

 

 

 

 

other than Off.

 

 

 

 

 

 

Cfg_ShedOnIOFault

BOOL

 

1

1

= Stop motor and alarm on I/O Fault.

 

 

 

 

0

= Alarm only on I/O Fault.

 

 

 

 

IMPORTANT: If a condition is configured to shed the device to the Off state on a

 

 

 

 

fault, a reset is required to clear the shed fault to command the drive to a state

 

 

 

 

other than Off.

 

 

 

 

 

 

Cfg_SimScaleEU

BOOL

 

0

1

= In simulation, scale Speed Ref EU to Speed Fdbk EU.

 

 

 

 

 

 

Cfg_SimScaleRaw

BOOL

 

0

1

= In simulation, scale Speed Ref EU to raw, then raw to Speed Fdbk EU.

 

 

 

 

 

Cfg_HasFailToStartAlm

BOOL

FailToStart.Cfg_Exists

0

These parameters determine whether the corresponding alarm exists and is

 

 

 

 

checked or if the alarm does not exist and is not used. When these parameter are

Cfg_HasFailToStopAlm

 

FailToStop.Cfg_Exists

 

 

 

1, the corresponding alarm exists.

 

 

 

 

 

 

Cfg_HasIntlkTripAlm

 

IntlkTrip.Cfg_Exists

 

 

 

 

 

 

 

 

 

Cfg_HasDriveFaultAlm

 

DriveFault.Cfg_Exists

 

 

 

 

 

 

 

 

 

Cfg_HasIOFaultAlm

 

IOFault.Cfg_Exists

 

 

 

 

 

 

 

 

Cfg_FailToStartResetReqd

BOOL

FailToStart.Cfg_ResetReqd

0

These parameters determine whether a reset is required to clear the alarm status.

 

 

 

 

When these parameters are 1, the alarm is latched ON when the alarm occurs.

Cfg_FailToStopResetReqd

 

FailToStop.Cfg_ResetReqd

 

 

 

After the alarm condition returns to normal, a reset is required to clear the alarm

 

 

 

 

status (for example, PCmd_Reset, OCmd_Reset, or Inp_Reset are required to

Cfg_IntlkTripResetReqd

 

IntlkTrip.Cfg_ResetReqd

 

 

 

clear Alm_FailtoStart after the alarm is set and the value returns to normal).

 

 

 

 

Cfg_DriveFaultResetReqd

 

DriveFault.Cfg_ResetReqd

 

When these parameter are 0, no reset is required and the alarm status is cleared

 

 

when the alarm condition returns to normal.

 

 

 

 

Cfg_IOFaultResetReqd

 

IOFault.Cfg_ResetReqd

 

IMPORTANT: If the reset clears the alarm, it also acknowledges the alarm.

 

 

 

 

 

Cfg_FailToStartAckReqd

BOOL

FailToStart.Cfg_AckReqd

1

These parameters determine whether an acknowledgement is required for an

 

 

 

 

alarm. When these parameters are 1, the acknowledge (ack) bit is cleared when

Cfg_FailToStopAckReqd

 

FailToStop.Cfg_AckReqd

 

 

 

the alarm occurs. An acknowledge command (for example,

 

 

 

 

PCmd_FailtoStartAck) are required to acknowledge the alarm. When set to 0, the

Cfg_IntlkTripAckReqd

 

IntlkTrip.Cfg_AckReqd

 

 

 

Acknowledge bit is set when an alarm occurs indicating an acknowledged alarm

 

 

 

 

Cfg_DriveFaultAckReqd

 

DriveFault.Cfg_AckReqd

 

and no acknowledge command is required.

 

 

 

 

 

 

 

 

 

 

Cfg_IOFaultAckReqd

 

IOFault.Cfg_AckReqd

 

 

 

 

 

 

 

 

 

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

15

PowerFlex 6000 Drive (P_PF6000)

Table 7 - P_PF6000 Drive Input Parameters

Input Parameter

Data

Alias For

Default

Description

 

Type

 

 

 

 

 

 

 

 

Cfg_FailToStartSeverity

INT

FailToStart.Cfg_Severity

1000

These parameters determine the severity of each alarm that gauges the color and

 

 

 

 

symbol that are used to indicate alarm status on the faceplate and global object.

Cfg_FailToStopSeverity

 

FailToStop.Cfg_Severity

1000

 

The following are valid values:

 

 

 

 

Cfg_IntlkTripSeverity

 

IntlkTrip.Cfg_Severity

500

1…250 = Low

 

 

 

 

251…500 = Medium

Cfg_DriveFaultSeverity

 

DriveFault.Cfg_Severity

1000

 

501…750 = High

 

 

 

 

Cfg_IOFaultSeverity

 

IOFault.Cfg_Severity

1000

751…1000 = Urgent

 

 

 

 

IMPORTANT: These severity priorities drive only the indication on the global

 

 

 

 

object and faceplate. The Alarm and Events definition severity drives the color

 

 

 

 

and symbol that is used on the alarm banner. The definition severity also provides

 

 

 

 

an alarm summary and the value returned by the FactoryTalk Alarm and Events

 

 

 

 

software display commands.

 

 

 

 

 

Cfg_MinSpdRef

REAL

 

0.0

Minimum speed reference in engineering units (for limiting).

 

 

 

 

 

Cfg_MaxSpdRef

REAL

 

60.0

Maximum speed reference in engineering units (for limiting).

 

 

 

 

 

Cfg_SpeedRefEUMin

REAL

 

0.0

Speed reference minimum in Engineering units (for scaling).

 

 

 

 

 

Cfg_SpeedRefEUMax

REAL

 

60.0

Speed reference maximum in engineering units (for scaling).

 

 

 

 

 

Cfg_SpeedFdbkEUMin

REAL

 

0.0

Speed feedback minimum in engineering units (for scaling).

 

 

 

 

 

Cfg_SpeedFdbkEUMax

REAL

 

60.0

Speed feedback maximum in engineering units (for scaling).

 

 

 

 

 

Cfg_SimRampT

DINT

 

10

Time to ramp speed feedback when in simulation (seconds).

 

 

 

 

 

Cfg_FailToStartT

DINT

 

15

Time after start to get run feedback before fault (seconds).

 

 

 

 

 

Cfg_FailToStopT

DINT

 

15

Time after stop to drop run feedback before fault (seconds).

 

 

 

 

 

Cfg_ResetPulseT

DINT

 

2

Time to pulse Out_Reset to clear drive fault.

 

 

 

 

 

Cfg_WatchdogT

DINT

 

5

Communication Watchdog Timeout time (sec).

 

 

 

 

 

Cfg_OperKeep

SINT

 

2#0000_0000

Operator keeps control in Program mode:

 

 

 

 

Bit .0 = Reference

 

 

 

 

Bit .1 = Start/stop

 

 

 

 

 

Cfg_ProgKeep

SINT

 

2#0000_0000

Program keeps control in Operator mode:

 

 

 

 

Bit .0 = Reference

 

 

 

 

Bit .1 = Start/stop

 

 

 

 

 

PSet_SpeedRef

REAL

 

0.0

Program setting of speed reference (engineering units).

 

 

 

 

 

PSet_Owner

DINT

 

0

Program Owner Request ID (nonzero) or Release (zero).

 

 

 

 

 

OSet_SpeedRef

REAL

 

0.0

Operator setting of speed reference (engineering units).

 

 

 

 

 

PCmd_Start

BOOL

 

0

When Cfg_PCmdClear is 1:

PCmd_Stop

 

 

 

Set PCmd_Start to 1 to start the Drive

PCmd_Fwd

 

 

 

Set PCmd_Stop to 1 to stop the motor

 

 

 

 

These parameters are reset automatically

 

 

 

 

When Cfg_PCmdClear is 0:

 

 

 

 

Set PCmd_Start to 1 to start the drive

 

 

 

 

Set PCmd_Start to 0 to stop the driver

 

 

 

 

PCmd_Stop is not used

 

 

 

 

These parameters do not reset automatically

 

 

 

 

 

PCmd_Acq

BOOL

Mode.PCmd_Acq

0

When Cfg_PCmdClear is 1:

 

 

 

 

Set PCmd_Acq to 1 to Acquire

PCmd_Rel

 

Mode.PCmd_Rel

 

 

 

Set PCmd_Rel to 1 to Release

 

 

 

 

 

 

 

 

These parameters reset automatically

 

 

 

 

When Cfg_PCmdClear is 0:

 

 

 

 

Set PCmd_Acq to 1 to Acquire

 

 

 

 

Set PCmd_Acq to 0 to Release

 

 

 

 

PCmd_Rel is not used

 

 

 

 

These parameters do not reset automatically

 

 

 

 

 

16

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

PowerFlex 6000 Drive (P_PF6000)

Table 7 - P_PF6000 Drive Input Parameters

Input Parameter

Data

Alias For

Default

Description

 

Type

 

 

 

 

 

 

 

 

PCmd_Lock

BOOL

Mode.PCmd_Lock

0

When Cfg_PCmdClear is 1:

 

 

 

 

Set PCmd_Lock to 1 to Lock

PCmd_Unlock

 

Mode.PCmd_Unlock

 

 

 

Set PCmd_Unlock to 1 to Unlock

 

 

 

 

 

 

 

 

These parameters are reset automatically

 

 

 

 

When Cfg_PCmdClear is 0:

 

 

 

 

Set PCmd_Lock to 1 to Lock

 

 

 

 

Set PCmd_Lock to 0 to Unlock

 

 

 

 

PCmd_Unlock is not used

 

 

 

 

These parameters do not reset automatically

 

 

 

 

 

PCmd_Reset

BOOL

 

0

Set PCmd_Reset to 1 to reset all alarms requiring reset

 

 

 

 

This parameter is always reset automatically

 

 

 

 

 

PCmd_FailToStartAck

BOOL

FailToStart.PCmd_Ack

0

Set PCmd_<Alarm>Ack to 1 to Acknowledge alarm

 

 

 

 

These parameters are reset automatically

PCmd_FailToStopAck

 

FailToStop.PCmd_Ack

 

 

 

 

 

 

 

 

 

PCmd_IntlkTripAck

 

IntlkTrip.PCmd_Ack

 

 

 

 

 

 

 

PCmd_DriveFaultAck

 

DriveFault.PCmd_Ack

 

 

 

 

 

 

 

PCmd_IOFaultAck

 

IOFault.PCmd_Ack

 

 

 

 

 

 

 

PCmd_FailToStartSuppress

BOOL

FailToStart.PCmd_Suppress

0

When Cfg_PCmdClear is 1:

 

 

 

 

Set PCmd_<Alarm>Suppress to 1 to suppress alarm

PCmd_FailToStopSuppress

 

FailToStop.PCmd_Suppress

 

 

 

Set PCmd_<Alarm>Unsuppress to 1 to unsuppress alarm

 

 

 

 

PCmd_IntlkTripSuppress

 

IntlkTrip.PCmd_Suppress

 

These parameters reset automatically

 

 

 

 

When Cfg_PCmdClear is 0:

PCmd_DriveFaultSuppress

 

DriveFault.PCmd_Suppress

 

 

 

Set PCmd_<Alarm>Suppress to 1 to suppress alarm

 

 

 

 

PCmd_IOFaultSuppress

 

IOFault.PCmd_Suppress

 

 

 

Set PCmd_<Alarm>Suppress to 0 to unsuppress alarm

 

 

 

 

PCmd_<Alarm>Unsuppress is not used

PCmd_FailToStartUnsuppress

BOOL

FailToStart.PCmd_Unsuppress

0

These Parameters do not reset automatically

 

 

 

 

PCmd_FailToStopUnsuppress

 

FailToStop.PCmd_Unsuppress

 

 

 

 

 

 

 

PCmd_IntlkTripUnsuppress

 

IntlkTrip.PCmd_Unsuppress

 

 

 

 

 

 

 

PCmd_DriveFaultUnsuppress

 

DriveFault.PCmd_Unsuppress

 

 

 

 

 

 

 

PCmd_IOFaultUnsuppress

 

IOFault.PCmd_Unsuppress

 

 

 

 

 

 

 

PCmd_FailToStartUnshelve

BOOL

FailToStart.PCmd_Unshelve

0

Set PCmd_<Alarm>Unshelve to 1 to Unshelve alarm

 

 

 

 

These parameters are reset automatically

PCmd_FailToStopUnshelve

 

FailToStop.PCmd_Unshelve

 

 

 

 

 

 

 

 

 

PCmd_IntlkTripUnshelve

 

IntlkTrip.PCmd_Unshelve

 

 

 

 

 

 

 

PCmd_DriveFaultUnshelve

 

DriveFault.PCmd_Unshelve

 

 

 

 

 

 

 

PCmd_IOFaultUnshelve

 

IOFault.PCmd_Unshelve

 

 

 

 

 

 

 

OCmd_Start

BOOL

 

0

Operator command to start drive.

 

 

 

 

 

OCmd_Stop

BOOL

 

0

Operator command to stop drive.

 

 

 

 

 

OCmd_Bypass

BOOL

 

0

Operator command to bypass all bypassable interlocks and permissives.

 

 

 

 

 

OCmd_Check

BOOL

 

0

Operator command to check (not bypass) all interlocks and permissives.

 

 

 

 

 

MCmd_Disable

BOOL

 

0

Maintenance command to disable drive.

 

 

 

 

 

MCmd_Enable

BOOL

 

0

Maintenance command to enable (permit to run) drive.

 

 

 

 

 

MCmd_Acq

BOOL

Mode.MCmd_Acq

0

Maintenance Command to Acquire Ownership (Operator/Program/Overload to

 

 

 

 

Maintenance).

 

 

 

 

 

MCmd_Rel

BOOL

Mode.MCmd_Rel

0

Maintenance Command to Release Ownership (Maintenance to Operator/

 

 

 

 

Program/Overload).

 

 

 

 

 

OCmd_AcqLock

BOOL

Mode.OCmd_AcqLock

0

Operator Command to Acquire (Program to Operator)/Lock Ownership.

 

 

 

 

 

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

17

PowerFlex 6000 Drive (P_PF6000)

Table 7 - P_PF6000 Drive Input Parameters

Input Parameter

Data

Alias For

Default

Description

 

Type

 

 

 

 

 

 

 

 

OCmd_Unlock

BOOL

Mode.OCmd_UnlockRel

0

Operator Command to Unlock/Release (Operator to Program) Ownership

 

 

 

 

 

OCmd_Reset

BOOL

 

0

Operator command to reset all alarms requiring reset.

 

 

 

 

 

OCmd_ResetAckAll

BOOL

 

0

Operator command to acknowledge and reset all alarms and latched shed

 

 

 

 

conditions.

 

 

 

 

 

18

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

PowerFlex 6000 Drive (P_PF6000)

PowerFlex 6000 Drive Output Structure

Output parameters include the following:

Value data elements (Val_) are numeric outputs of the instruction for use by the HMI. Values can also be used by other application logic or software packages.

Source and Quality data elements (SrcQ_) are outputs of the instruction used by the HMI to indicate PV source and quality.

Status data elements (Sts_) are bit outputs of the instruction for use by the HMI. Status bits can also be used by other application logic.

Error data elements (Err_) are outputs of the instruction that indicate a particular configuration error. If any Err_ bit is set then the Sts_Err configuration error summary status is set and the Invalid Configuration indicator is displayed on the HMI.

Not Ready data elements (Nrdy_) are bit outputs of the instruction for use by the HMI for displaying the Device Not Ready indicator. Status bits can also be used by other application logic.

Alarm data elements (Alm_) are outputs of the instruction that indicate a particular alarm has occurred.

Acknowledge data elements (Ack_) are outputs of the instruction that indicate the corresponding alarm has been acknowledged.

Ready data elements (Rdy_) are bit outputs of the instruction used by the HMI to enable or disable Command buttons and Setting entry fields.

Table 8 - P_PF6000 Drive Output Parameters

Output Parameter

Data Type

Alias For

Description

 

 

 

 

EnableOut

BOOL

 

Enable output: The EnableOut signal is not manipulated by this instruction. Its output state

 

 

 

always reflects EnableIn input state.

 

 

 

 

Val_SpeedRef

REAL

 

Speed reference (target, in engineering units) to drive.

 

 

 

 

Val_SpeedFdbk

REAL

 

Speed feedback (actual, in engineering units) from drive.

 

 

 

 

Val_SpeedRefRaw

REAL

 

Copy of speed reference output (in raw units) for faceplate.

 

 

 

 

Val_SpeedFdbkRaw

REAL

 

Copy of speed feedback input (in raw units) for faceplate.

 

 

 

 

Val_SpeedRefEUMin

REAL

 

Minimum of speed reference = MIN (Cfg_SpeedFdbkEUMin, Cfg_SpeedFdbkEUMax).

 

 

 

 

Val_SpeedRefEUMax

REAL

 

Maximum of speed reference = MAX (Cfg_SpeedFdbkEUMin, Cfg_SpeedFdbkEUMax).

 

 

 

 

Val_SpeedFdbkEUMin

REAL

 

Minimum of speed feedback = MIN (Cfg_SpeedFdbkEUMin, Cfg_SpeedFdbkEUMax).

 

 

 

 

Val_SpeedFdbkEUMax

REAL

 

Maximum of speed feedback = MAX (Cfg_SpeedFdbkEUMin, Cfg_SpeedFdbkEUMax).

 

 

 

 

Val_MotorCurrent

REAL

 

Drive output current (amps).

 

 

 

 

Val_MotorCurrentPct

REAL

 

Motor current (% full load amps).

 

 

 

 

Val_MotorVoltage

REAL

 

Motor voltage (volts).

 

 

 

 

Val_OutputPower

REAL

 

Drive output power (kW).

 

 

 

 

Val_MotorPowerPct

REAL

 

Motor power (% rated power).

 

 

 

 

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

19

PowerFlex 6000 Drive (P_PF6000)

Table 8 - P_PF6000 Drive Output Parameters

Output Parameter

Data Type

Alias For

Description

 

 

 

 

 

SrcQ_IO

SINT

 

I/O signal source and quality.

 

 

 

 

SrcQ

 

 

Final drive source and quality.

 

 

 

GOOD

0 = I/O live and confirmed good quality

 

 

 

 

 

1 = I/O live and assumed good quality

 

 

 

 

 

2 = No feedback configured, assumed good quality

 

 

 

TEST

8 = Device simulated

 

 

 

 

 

9 = Device loopback simulation

 

 

 

 

 

10 = Manually entered value

 

 

 

UNCERTAIN

16 = Live input, off-specification

 

 

 

 

 

17 = Value substituted at device/bus

 

 

 

 

 

18 = Value substituted by maintenance (Has and not Use)

 

 

 

 

 

19 = Shed, using last good value

 

 

 

 

 

20 = Shed, using replacement value

 

 

 

BAD

32 = Signal failure (out-of-range, NaN, invalid combination)

 

 

 

 

 

33 = I/O channel fault

 

 

 

 

 

34 = I/O module fault

 

 

 

 

 

35 = Bad I/O configuration (for example, scaling parameters)

 

 

 

 

Val_Cmd

SINT

 

Device command:

 

 

 

0

= None

 

 

 

 

1

= Stop

 

 

 

 

2

= Start

 

 

 

 

 

Val_Fdbk

SINT

 

Device feedback:

 

 

 

0

= Stopped

 

 

 

 

1

= Running

 

 

 

 

 

Val_Sts

SINT

 

Device confirmed status:

 

 

 

0

= None

 

 

 

 

1

= Stopped

 

 

 

 

2

= Running

 

 

 

 

6

= Stopping

 

 

 

 

7

= Starting

 

 

 

 

33 = Disabled

 

 

 

 

 

Val_Fault

SINT

 

Device fault status:

 

 

 

0

= None

 

 

 

 

16 = Fail to Start

 

 

 

17 = Fail to Stop

 

 

 

18 = Drive Fault

 

 

 

32 = I/O Fault

 

 

 

 

34 = Configuration error

 

 

 

 

Val_Mode

SINT

Mode.Val

The current mode is shown with status bits and also as an enumeration ‘Val_Mode’ as follows:

 

 

 

0

= No mode

 

 

 

 

1

= Hand

 

 

 

 

2

= Maintenance

 

 

 

3

= Override

 

 

 

 

4

= Program (locked)

 

 

 

5

= Operator (locked)

 

 

 

6

= Program (unlocked, Operator is default)

 

 

 

7

= Operator (unlocked, Program is default)

 

 

 

8

= Program (unlocked, Program is default)

 

 

 

9

= Operator (unlocked, Operator is default)

 

 

 

 

Val_Owner

DINT

 

Current object owner ID (0 = not owned).

 

 

 

 

 

 

20

Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017

Loading...
+ 44 hidden pages