Rockwell Automation Library of Process Objects:
PowerFlex 6000 Drive (P_PF6000)
IMPORTANT
This manual applies to the Rockwell Automation Library of Process Objects version 3.5 or earlier.
For Rockwell Automation Library of Process Objects version 5.0, see
• PROCES-RM200
For Rockwell Automation Library of Process Objects version 4.0 or later, use the following manuals:
• PROCES-RM013 contains logic instructions
• PROCES-RM014 contains display elements
Important User Information
IMPORTANT
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, ControlLogix, FactoryTalk, Logix5000, PlantPAx, PowerFlex, Rockwell Automation, Rockwell Software, RSL ogix, and Studio 5000 Log ix Designer are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 20173
Table of Contents
Notes:
4Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017
Preface
This manual describes the Add-On Instruction that controls and monitors a
PowerFlex® 6000 Medium Voltage Variable Frequency Drive.
Software Compatibility
Additional Resources
For the latest compatible software information and to download the Rockwell
Automation® Library of Process Objects, see the Product Compatibility and
Download Center at
For general library considerations, see Rockwell Automation Library of Process
Objects, publication PROCES-RM002
.
These documents contain additional information concerning related products
from Rockwell Automation.
Table 1 - Additional Resources
ResourceDescription
PlantPAx® Distributed Control System Selection Guide,
publication PROCES-SG001
PlantPAx Distributed Control System Reference Manual,
publication PROCES-RM001
Rockwell Automation Library of Process Objects,
publication PROCES-RM002
FactoryTalk® View Machine Edition User Manual,
publication VIEWME-UM004
FactoryTalk View Site Edition User Manual,
publication VIEWSE-UM006
PowerFlex 6000 Medium Voltage Variable Frequency Drive
Parameter Manual, publication 6000-TD004
Rockwell Automation Library of Process Objects: Common
Alarm Block (P_Alarm) Reference Manual, publication
SYSLIB-RM002
Rockwell Automation Library of Process Objects: Interlocks
with First Out and Bypass (P_Intlk) Reference Manual,
publication SYSLIB-RM004
Rockwell Automation Library of Process Objects: Common
Mode Block (P_Mode) Reference Manual, publication
SYSLIB-RM005
Rockwell Automation Library of Process Objects: Permissives
with Bypass (P_Perm) Reference Manual, publication
SYSLIB-RM007
Provides information to assist with equipment
procurement for your PlantPAx system.
Provides characterized recommendations for
implementing your PlantPAx system.
Provides general considerations for the PlantPAx system
library of process objects.
Provides details on how to use this software package for
creating an automation application.
Provides details on how to use this software package for
developing and running human-machine interface
(HMI) applications that can involve multiple users and
servers, distributed over a network.
Provides details regarding functions, parameters, and
troubleshooting information for medium voltage
PowerFlex 6000 drives.
Details how to monitor an input condition to raise an
alarm. Information includes acknowledging, resetting,
inhibiting, and disabling an alarm. Generally the
P_Alarm faceplate is accessible from the Alarms tab.
Explains how to collect (sum up) the interlock
conditions that stop or de-energize a running or
energized piece of equipment or prevent it from
starting or being energized.
Explains how to choose the Mode (owner) of an
instruction or control strategy. The Mode instruction is
usually embedded within other instructions to extend
their functionality.
Details how to collect permissive conditions to start a
piece of equipment.
.
Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 20175
Preface
Table 1 - Additional Resources
ResourceDescription
Rockwell Automation Library of Process Objects: Restart
Inhibit for Large Motor (P_ResInh) Reference Manual,
publication SYSLIB-RM009
Rockwell Automation Library of Process Objects: Run Time
and Starts (P_RunTime) Reference Manual, publication
SYSLIB-RM010
Explains how to protect a large motor from damage
caused by repeated starts.
Explains how to accumulate the total run time and
count of starts for a motor or other equipment.
6Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017
PowerFlex 6000 Drive (P_PF6000)
Add-On InstructionFaceplateGlobal Objects
IMPORTANT
The P_PF6000 (PowerFlex 6000 drive) object is used to operate one
variable-speed motor by using a PowerFlex 6000 medium voltage variable
frequency AC drive. The drive operates via an add-on EtherNet/IP interface.
The Add-On Instruction controls the drive in various modes and monitors fault
conditions. The global objects and faceplate that is shown are examples of the
graphical interface tools for this instruction.
Guidelines
This instruction operates a motor connected to a PowerFlex 6000 variable
frequency AC drive, which is communicating with the controller over an
EtherNet/IP network.
The PowerFlex 6000 drive has specific parameter read/write functionality. For
details, see Knowledgebase Answer ID 1008677 at
https://www.rockwellautomation.custhelp.com
Do not use this instruction in these situations:
• You need to operate a single-speed motor (running and stopped only). Use
• You need to operate a two-speed motor (fast, slow, and stopped only). Use
Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 20177
The drive interface is designed to work with the Studio 5000 Logix Designer®
application, Version 20 and later.
.
the P_Motor instruction instead.
the P_Motor2Spd instruction instead.
PowerFlex 6000 Drive (P_PF6000)
• You need to operate a simple reversing motor (forward, reverse, and
stopped only). Use the P_MotorRev instruction instead.
• You need to operate a motor with multiple discrete speeds. You need
specific logic for this motor. The P_PF6000 instruction is designed for
motors with continuously variable (analog) speed, not multiple discrete
speed selections. You can use the P_D4SD or P_nPos instruction for
motors with multiple discrete speeds.
• You are using a drive other than the PowerFlex 6000 drive. Instead, use
these Add-On Instructions:
– P_PF52x for the PowerFlex 523 or PowerFlex 525 drive on an
EtherNet/IP network
– P_PF753 for the PowerFlex drive with 20-COMM-E EtherNet/IP
Interface
– P_PF755 for the PowerFlex AC variable frequency drive
– P_PF7000 for the PowerFlex 7000 medium voltage AC variable
frequency drive with 20-COMM-E EtherNet/IP interface.
– P_VSD for third-party drives, drives on other networks, or via
hardwired I/O
Functional Description
The P_PF6000 instruction provides the following capabilities:
• Ownership of the drive through the standard P_Mode Add-On
Instruction and modes.
• Ability to start and stop the drive and motor, control the drive speed (via
speed reference), and monitor the drive run status and speed feedback to
verify whether the drive is running or stopped. Provides alarms and drive
shutdown for Fail to Start and Fail to Stop if the feedback does not follow
the commanded state within a configured amount of time.
• Reading from the drive, the instruction displays drive faults, general drive
status data, and a number of operating parameters.
• Ability to read fault data from the drive and provide descriptive text with
fault codes.
• Indication of Warning or Alarm status as received from the drive.
• Input and alarm for a drive fault condition and an output to send a drive
fault reset to the drive. Provide a configurable time to pulse the drive fault
reset output when a reset command is received.
• Permissives (bypassable and non-bypassable) that are conditions that
enable a drive start and Interlocks (bypassable and non-bypassable) that are
conditions that stop the drive and help prevent starting. Provide an alarm
when an Interlock stops the drive. Provide maintenance the capability to
bypass the bypassable Permissives and Interlocks.
8Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017
PowerFlex 6000 Drive (P_PF6000)
IMPORTANT
• Maintenance personnel can disable (soft lock out) the drive. This
capability is not a substitute for hard lockout/tagout (LOTO) procedures.
• Monitor an I/O fault input and a communication watchdog timer, and
alarm on an I/O or communication failure. The failure condition can
optionally de-energize the outputs to the drive, requiring a reset.
• In Override mode, provide an override state input that determines if the
override is to run or stop the drive (default = stop), and, if the drive is to
run, an override speed reference and direction.
• The instruction provides simulation capability. Outputs to the drive are
kept de-energized, but the object can be manipulated as if a working drive
were present, including a basic ramp-up of speed feedback value on
starting and ramp-down on stopping. The simulated ramp-up-to-speed
time is configurable. This capability is often used for activities such as
system testing and operator training.
Required Files
Add-On Instructions are reusable code objects that contain encapsulated logic
that can streamline implementing your system. This functionality lets you create
your own instruction set for programming logic as a supplement to the
instruction set provided natively in the ControlLogix® firmware. An Add-On
Instruction is defined once in each controller project, and can be instantiated
multiple times in your application code as needed.
Controller File
The P_PF6000_3_5-00_RUNG.L5X rung import must be imported into the
controller project to be used in the controller configuration. The service release
number (boldfaced) can change as service revisions are created.
Visualization Files
This Add-On Instruction has associated visualization files that provide a
common user interface. These files can be downloaded from the Product
Compatibility and Download Center at
The visualization file dependencies require Process Library content imports to
occur in a specific order as reflected in the following tables:
• Images
• Global Objects
• Standard Displays
• HMI Tags
• Macros
.
Images are external graphic files that can be used in displays. They must be
imported for FactoryTalk View software to make use of them.
Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 20179
PowerFlex 6000 Drive (P_PF6000)
When PNG files are imported, they are renamed by FactoryTalk View software
with a .bmp file extension, but retain a .png format.
Table 2 - Visualization Files: Images (.png)
FactoryTalk View SE SoftwareFactoryTalk View ME SoftwareDescription
All .png files in the images folderAll .png files in the images folderThese are the common icons that are used in the global
objects and standard displays for all Process Objects.
The Global Object files (.ggfx file type) in the following table are Process Library
display elements that are created once and referenced multiple times on multiple
displays in an application. When changes are made to a Global Object, all
instances in the application are automatically updated.
Table 3 - Visualization Files: Global Objects (.ggfx)
FactoryTalk View SE SoftwareFactoryTalk View ME SoftwareDescription
(RA-BAS) Common Faceplate Objects(RA-BAS-ME) Common Faceplate ObjectsGlobal objects used on process object faceplates.
(RA-BAS) P_VSD Graphics Library(RA-BAS-ME) P_VSD Graphics LibraryDrive global object device symbols used to build
(RA-BAS) Process Alarm Objects(RA-BAS-ME) Process Alarm ObjectsGlobal objects used for managing alarms on process
(RA-BAS) Process Diagnostic Objects(RA-BAS-ME) Process Diagnostic ObjectsDiagnostic global objects used on process
(RA-BAS) Process Faceplate Motor Objects(RA-BAS-ME) Process Faceplate Motor ObjectsMotor global objects used on process object faceplates.
(RA-BAS) Process Help Objects(RA-BAS-ME) Process Help ObjectsGlobal objects used for all process objects help displays.
(RA-BAS) Process Interlock Objects(RA-BAS-ME) Process Interlock ObjectsGlobal objects used for managing interlocks and
(RA-BAS) Process Mode Objects(RA-BAS-ME) Process Mode ObjectsGlobal objects used for managing modes on process
process graphics.
object faceplates.
object faceplates.
permissives on process object faceplates.
object faceplates.
The Standard Display files (.gfx file type) in the following table are the Process
Library displays that you see at runtime.
Table 4 - Visualization Files: Standard Displays (.gfx)
FactoryTalk View SE SoftwareFactoryTalk View ME SoftwareDescription
(RA-BAS) Common-AnalogEditN/AFaceplate used for analog input data entry. The FactoryTalk
(RA-BAS) P_Alarm-Faceplate(RA-BAS-ME) P_Alarm-FaceplateThe faceplate that is used for the object
(RA-BAS) P_Alarm-Help(RA-BAS-ME) P_Alarm-HelpAlarm Help information that is accessed from the
(RA-BAS) P_Mode-Config(RA-BAS-ME) P_Mode-ConfigThe Configuration Display used to configure the
(RA-BAS) P_Mode-Help(RA-BAS-ME) P_Mode-HelpMode Help information that is accessed from the
(RA-BAS) P_PF6000-Faceplate(RA-BAS-ME) P_PF6000-FaceplateThe faceplate display that is used for the object
(RA-BAS) P_PF6000-Quick(RA-BAS-ME) P_PF6000-QuickThe Quick display that is used for the object
(RA-BAS) Process Motor Family-Help(RA-BAS-ME) Process Motor Family-HelpThe Help display for Motor objects
View ME faceplates use the native analog input data entry
so no file is required.
P_AIarm faceplate.
P_Mode object.
Help faceplate.
10Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017
Table 4 - Visualization Files: Standard Displays (.gfx)
FactoryTalk View SE SoftwareFactoryTalk View ME SoftwareDescription
RunTime faceplate display that is used for the object
Use this file if your object has an associated P_RunTime
object and you enable navigation to the P_RunTime
faceplate from the object faceplate.
(RA-BAS) Process Interlock Family-Help(RA-BAS-ME) Process Interlock Family-HelpOptional
Interlock/permissives help display that is used for
the object
Use this file if you use the P_Intlk or P_Perm faceplate.
PowerFlex 6000 Drive (P_PF6000)
HMI Tags are created in a FactoryTalk View ME application to support tab
switching on Process Library faceplates. The HMI tags can be imported via the
comma-separated values file (.csv file type) in the following table.
Table 5 - Visualization Files: HMI Tags (.csv)
FactoryTalk View SE SoftwareFactoryTalk View ME SoftwareDescription
N/AFTVME_PlantPAxLib_Tags_3_5_xx.csv
where xx = the service release number.
These tags must be imported into the
FactoryTalk View ME project to support switching tabs on
any Process Object faceplate.
Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 201711
PowerFlex 6000 Drive (P_PF6000)
TIP
Controller Code
This section describes the parameter references for this Add-On Instruction.
PowerFlex Drive InOut Structure
InOut parameters are used to link the Add-On Instruction to external tags that
contain necessary data for the instruction to operate. These external tags must be
of the data type shown.
Table 6 - P_PF6000 Drive InOut Parameters
Tag NameData TypeDescription
InpP_PF6000_InpPowerFlex 6000 input assembly.
OutP_PF6000_OutPowerFlex 6000 output assembly.
Ref_FaultCodeListP_DescListTag containing list of fault codes (DINT) and descriptions (STRING_40).
The user-defined data types (UDTs) and the Array tag containing the list of
PowerFlex 6000 fault codes and descriptions are included in the RUNG import
that brings in the P_PF6000 Add-On Instruction. See the programming
example on page 28
for details.
The figure shows the drive fault table tags that are in each template.
Make sure the tag 'PF6000_FaultCodeList' is entered in the P_PF6000
Ref_FaultCodeList parameter.
12Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017
PowerFlex 6000 Drive (P_PF6000)
Each fault code list provides pre-configured fault codes and descriptions for a
given drive family.
For a complete list of fault codes, refer to the PowerFlex 6000 Medium Voltage
Variable Frequency Drive Firmware, Parameters, and Troubleshooting Manual,
publication 6000-TD004
.
Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 201713
PowerFlex 6000 Drive (P_PF6000)
Table 7 - P_PF6000 Drive Input Parameters
PowerFlex 6000 Drive Input Structure
Input parameters include the following:
• Input data elements (Inp_) are typically used to connect field inputs from
I/O modules or signals from other objects.
• Configuration data elements (Cfg_) are used to set configurable
capabilities and features of the instruction.
• Command data elements (PCmd_, OCmd_, MCmd_) are used by
program logic, operators, and maintenance personnel to request
instruction actions.
• Setting data elements (PSet_, OSet_, MSet_) are used by program logic,
operators, and maintenance personnel to establish runtime setpoints,
thresholds, and so forth. Set_ data elements (without a leading P, O, or M)
establish runtime settings regardless of role or mode.
Input ParameterData
Type
EnableInBOOL1Ladder Diagram:
Inp_PermOKBOOL11 = Permissives OK, drive can start.
Inp_NBPermOKBOOL11 = Non-bypassable permissives OK, drive can start.
Inp_IntlkOKBOOL11 = Interlocks OK, drive can start/run.
Inp_NBIntlkOKBOOL11 = Non-bypassable interlocks OK, drive can start/run.
Inp_SimBOOL0Simulation input. When set to 1, the instruction keeps outputs de-energized
Inp_HandBOOL01 = Request to acquire Hand mode.
Inp_OvrdBOOLMode.Inp_Ovrd01 =Request to acquire Override mode.
Inp_OvrdCmdSINT0Override mode command:
Inp_OvrdSpeedREAL0.0Value to set speed reference in Override mode (SpeedRef engineering units).
Inp_ResetBOOL01 = Reset drive fault conditions and latched alarms.
Cfg_AllowLocalBOOL01 =Allow Local Star t/Stop without alarm.
Cfg_HasPermObjBOOL01 = Tells HMI a P_Perm is connected to Inp_Perm.
Cfg_HasIntlkObjBOOL01 =T ells HMI a P_Intlk is connected to Inp_Intlk.
Cfg_HasResInhObjBOOL01 = Tells HMI a P_ResInh Restart Inhibit is connected.
Cfg_HasRunTimeObjBOOL01 =T ells HMI a P_RunTime is connected.
Alias ForDefaultDescription
If the rung-in condition is true, the instruction’s Logic routine executes. If the
rung-in condition is false, the instruction’s EnableInFalse routine executes.
Function Block Diagram:
If true, or not connected, the instruction’s Logic routine executes. If the parameter
is exposed as a pin and wired, and the pin is false, the instruction’s EnableInFalse
routine executes.
Structured Text:
No effect. The instruction’s Logic routine executes.
(zero) and simulates a working drive. When set to 0, the instruction operates the
drive normally.
0 = Release Hand mode.
0 = Release Override mode.
0 = None
1 = Stop
2 = Start
0= Start/Stop from HMI/Program only.
14Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017
Table 7 - P_PF6000 Drive Input Parameters
PowerFlex 6000 Drive (P_PF6000)
Input ParameterData
Type
Cfg_SetTrackBOOL11 = PSets track OSets in Operator, OSets track PSets in Program.
Cfg_SetTrackOvrdHandBOOL01 = Program/Operator settings track Override/Hand speed reference.
Cfg_PCmdClearBOOLMode.Cfg_PCmdClear1When this parameter is 1, program commands are cleared once they are acted
Cfg_ProgDefaultBOOLMode.Cfg_ProgDefault0This parameter defines the default mode. When this parameter is 1, the mode
Cfg_OperStopPrioBOOL01 = OCmd_Stop available in any mode.
Cfg_OCmdResetsBOOL01 = New Operator drive command resets fault.
Cfg_ShedOnFailToStartBOOL11 = Stop motor and alarm on Fail to Start.
Cfg_ShedOnIOFaultBOOL11 = Stop motor and alarm on I/O Fault.
Cfg_SimScaleEUBOOL01 = In simulation, scale Speed Ref EU to Speed Fdbk EU.
Cfg_SimScaleRawBOOL01 = In simulation, scale Speed Ref EU to raw, then raw to Speed Fdbk EU.
Cfg_HasFailToStartAlmBOOLFailToStart.Cfg_Exists0These parameters determine whether the corresponding alarm exists and is
Cfg_HasFailToStopAlmFailToStop.Cfg_Exists
Cfg_HasIntlkTripAlmIntlkTrip.Cfg_Exists
Cfg_HasDriveFaultAlmDriveFault.Cfg_Exists
Cfg_HasIOFaultAlmIOFault.Cfg_Exists
Cfg_FailToStar tResetReqdBOOLFailToStart.Cfg_ResetReqd0These parameters determine whether a reset is required to clear the alarm status.
Cfg_FailToStopResetReqdFailToStop.Cfg_ResetReqd
Cfg_IntlkTripResetReqdIntlkTrip.Cfg_ResetReqd
Cfg_DriveFaultResetReqdDriveFault.Cfg_ResetReqd
Cfg_IOFaultResetReqdIOFault.Cfg_ResetReqd
Cfg_FailToStartAckReqdBOOLFailToStart.Cfg_AckReqd1These parameters determine whether an acknowledgement is required for an
Cfg_FailToStopAckReqdFailToStop.Cfg_AckReqd
Cfg_IntlkTripAckReqdIntlkTrip.Cfg_AckReqd
Cfg_DriveFaultAckReqdDriveFault.Cfg_AckReqd
Cfg_IOFaultAckReqdIOFault.Cfg_AckReqd
Alias ForDefaultDescription
0 = No tracking.
upon. When set to 0, program commands remain set until cleared by the
application program logic.
IMPORTANT: Clearing this parameter online can cause unintended program
command execution.
defaults to Program if no mode is being requested. When this parameter is 0, the
mode defaults to Operator if no mode is being requested.
IMPORTANT: Changing this parameter online can cause unintended mode
changes.
0 = OCmd_Stop only in Operator and Maintenance modes.
0 = Reset required to clear fault.
0 = Always use permissives/interlocks.
0 = Alarm only on Fail to Start.
IMPORTANT: If a condition is configured to shed the device to the Off state on a
fault, a reset is required to clear the shed fault to command the drive to a state
other than Off.
0 = Alarm only on I/O Fault.
IMPORTANT: If a condition is configured to shed the device to the Off state on a
fault, a reset is required to clear the shed fault to command the drive to a state
other than Off.
checked or if the alarm does not exist and is not used. When these parameter are
1, the corresponding alarm exists.
When these parameters are 1, the alarm is latched ON when the alarm occurs.
After the alarm condition returns to normal, a reset is required to clear the alarm
status (for example, PCmd_Reset, OCmd_Reset, or Inp_Reset are required to
clear Alm_FailtoStart after the alarm is set and the value returns to normal).
When these parameter are 0, no reset is required and the alarm status is cleared
when the alarm condition returns to normal.
IMPORTANT: If the reset clears the alarm, it also acknowledges the alarm.
alarm. When these parameters are 1, the acknowledge (ack) bit is cleared when
the alarm occurs. An acknowledge command (for example,
PCmd_FailtoStartAck) are required to acknowledge the alarm. When set to 0, the
Acknowledge bit is set when an alarm occurs indicating an acknowledged alarm
and no acknowledge command is required.
Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 201715
PowerFlex 6000 Drive (P_PF6000)
Table 7 - P_PF6000 Drive Input Parameters
Input ParameterData
Cfg_FailToStar tSeverityINTFailToStart.Cfg_Severity1000These parameters determine the severity of each alarm that gauges the color and
Cfg_FailToStopSeverityFailToStop.Cfg_Severity1000
Cfg_IntlkTripSeverityIntlkTrip.Cfg_Severity500
Cfg_DriveFaultSeverityDriveFault.Cfg_Severity1000
Cfg_IOFaultSeverityIOFault.Cfg_Severity1000
Cfg_MinSpdRefREAL0.0Minimum speed reference in engineering units (for limiting).
Cfg_MaxSpdRefREAL60.0Maximum speed reference in engineering units (for limiting).
Cfg_SpeedRefEUMinREAL0.0Speed reference minimum in Engineering units (for scaling).
Cfg_SpeedRefEUMaxREAL60.0Speed reference maximum in engineering units (for scaling).
Cfg_SpeedFdbkEUMinREAL0.0Speed feedback minimum in engineering units (for scaling).
Cfg_SpeedFdbkEUMaxREAL60.0Speed feedback maximum in engineering units (for scaling).
Cfg_SimRampTDINT10Time to ramp speed feedback when in simulation (seconds).
Cfg_FailToStar tTDINT15Time after start to get run feedback before fault (seconds).
Cfg_FailToStopTDINT15Time after stop to drop run feedback before fault (seconds).
Cfg_ResetPulseTDINT2Time to pulse Out_Reset to clear drive fault.
Cfg_WatchdogTDINT5Communication Watchdog Timeout time (sec).
Cfg_OperKeepSINT2#0000_0000Operator keeps control in Program mode:
Cfg_ProgKeepSINT2#0000_0000Program keeps control in Operator mode:
PSet_SpeedRefREAL0.0Program setting of speed reference (engineering units).
PSet_OwnerDINT0Program Owner Request ID (nonzero) or Release (zero).
OSet_SpeedRefREAL0.0Operator setting of speed reference (engineering units).
PCmd_Start
PCmd_Stop
PCmd_Fwd
PCmd_AcqBOOLMode.PCmd_Acq0When Cfg_PCmdClear is 1:
PCmd_RelMode.PCmd_Rel
Type
BOOL0When Cfg_PCmdClear is 1:
Alias ForDefaultDescription
symbol that are used to indicate alarm status on the faceplate and global object.
The following are valid values:
1…250 = Low
251…500 = Medium
501…750 = High
751…1000 = Urgent
IMPORTANT: These severity priorities drive only the indication on the global
object and faceplate. The Alarm and Events definition severity drives the color
and symbol that is used on the alarm banner. The definition severity also provides
an alarm summary and the value returned by the FactoryTalk Alarm and Events
software display commands.
Bit .0 = Reference
Bit .1 = Start/stop
Bit .0 = Reference
Bit .1 = Start/stop
• Set PCmd_Start to 1 to start the Drive
• Set PCmd_Stop to 1 to stop the motor
• These parameters are reset automatically
When Cfg_PCmdClear is 0:
• Set PCmd_Start to 1 to start the drive
• Set PCmd_Start to 0 to stop the driver
• PCmd_Stop is not used
• These parameters do not reset automatically
• Set PCmd_Acq to 1 to Acquire
• Set PCmd_Rel to 1 to Re lease
• These parameters reset automatically
When Cfg_PCmdClear is 0:
• Set PCmd_Acq to 1 to Acquire
• Set PCmd_Acq to 0 to Release
• PCmd_Rel is not used
• These parameters do not reset automatically
16Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017
Table 7 - P_PF6000 Drive Input Parameters
PowerFlex 6000 Drive (P_PF6000)
Input ParameterData
Type
PCmd_LockBOOLMode.PCmd_Lock0When Cfg_PCmdClear is 1:
PCmd_UnlockMode.PCmd_Unlock
PCmd_ResetBOOL0• Set PCmd_Reset to 1 to reset all alarms requiring reset
PCmd_FailToStar tAckBOOLFailToStart.PCmd_Ack0• Set PCmd_<Alarm>Ack to 1 to Acknowledge alarm
PCmd_FailToStopAckFailToStop.PCmd_Ack
PCmd_IntlkTripAckIntlkTrip.PCmd_Ack
PCmd_DriveFaultAckDriveFault.PCmd_Ack
PCmd_IOFaultAckIOFault.PCmd_Ack
PCmd_FailToStar tSuppressBOOLFailToStart.PCmd_Suppress0When Cfg_PCmdClear is 1:
PCmd_FailToStartUnshelveBOOLFailToStart.PCmd_Unshelve0• Set PCmd_<Alarm>Unshelve to 1 to Unshelve alarm
PCmd_FailToStopUnshelveFailToStop.PCmd_Unshelve
PCmd_IntlkTripUnshelveIntlkTrip.PCmd_Unshelve
PCmd_DriveFaultUnshelveDriveFault.PCmd_Unshelve
PCmd_IOFaultUnshelveIOFault.PCmd_Unshelve
OCmd_StartBOOL0Operator command to start drive.
OCmd_StopBOOL0Operator command to stop drive.
OCmd_BypassBOOL0Operator command to bypass all bypassable interlocks and permissives.
OCmd_CheckBOOL0Operator command to check (not bypass) all interlocks and permissives.
MCmd_DisableBOOL0Maintenance command to disable drive.
MCmd_EnableBOOL0Maintenance command to enable (permit to run) drive.
MCmd_AcqBOOLMode.MCmd_Acq0Ma intenance Command to Acquire Ownership (Op erator/Program/Overload to
MCmd_RelBOOLMode.MCmd_Rel0Maintenance Command to Release Ownership (Maintenance to Operator/
OCmd_AcqLockBOOLMode.OCmd_AcqLock0Operator Command to Acquire (Program to Operator)/Lock Ownership.
Alias ForDefaultDescription
• Set PCmd_Lock to 1 to Lock
• Set PCmd_Unlock to 1 to Unlock
• These parameters are reset automatically
• When Cfg_PCmdClear is 0:
• Set PCmd_Lock to 1 to Lock
• Set PCmd_Lock to 0 to Unlock
• PCmd_Unlock is not used
• These parameters do not reset automatically
• This parameter is always reset automatically
• These parameters are reset automatically
• Set PCmd_<Alarm>Suppress to 1 to sup press alarm
• Set PCmd_<Alarm>Unsuppress to 1 to unsuppress alarm
• These parameters reset automatically
When Cfg_PCmdClear is 0:
• Set PCmd_<Alarm>Suppress to 1 to sup press alarm
• Set PCmd_<Alarm>Suppress to 0 to unsuppress alarm
• PCmd_<Alarm>Unsuppress is not used
• These Parameters do not reset automatically
• These parameters are reset automatically
Maintenance).
Program/Overload).
Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 201717
PowerFlex 6000 Drive (P_PF6000)
Table 7 - P_PF6000 Drive Input Parameters
Input ParameterData
Type
OCmd_UnlockBOOLMode.OCmd_UnlockRel0Operator Command to Unlock/Release (Operator to Program) Ownership
OCmd_ResetBOOL0Operator command to reset all alarms requiring reset.
OCmd_ResetAckAllBOOL0Operator command to acknowledge and reset all alarms and latched shed
Alias ForDefaultDescription
conditions.
18Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017
Table 8 - P_PF6000 Drive Output Parameters
PowerFlex 6000 Drive (P_PF6000)
PowerFlex 6000 Drive Output Structure
Output parameters include the following:
• Value data elements (Val_) are numeric outputs of the instruction for
use by the HMI. Values can also be used by other application logic or
software packages.
• Source and Quality data elements (SrcQ_) are outputs of the instruction
used by the HMI to indicate PV source and quality.
• Status data elements (Sts_) are bit outputs of the instruction for use by the
HMI. Status bits can also be used by other application logic.
• Error data elements (Err_) are outputs of the instruction that indicate a
particular configuration error. If any Err_ bit is set then the Sts_Err
configuration error summary status is set and the Invalid Configuration
indicator is displayed on the HMI.
• Not Ready data elements (Nrdy_) are bit outputs of the instruction for use
by the HMI for displaying the Device Not Ready indicator. Status bits can
also be used by other application logic.
• Alarm data elements (Alm_) are outputs of the instruction that indicate a
particular alarm has occurred.
• Acknowledge data elements (Ack_) are outputs of the instruction that
indicate the corresponding alarm has been acknowledged.
• Ready data elements (Rdy_) are bit outputs of the instruction used
by the HMI to enable or disable Command buttons and Setting
entry fields.
Output ParameterData TypeAlias ForDescription
EnableOutBOOLEnable output: The EnableOut signal is not manipulated by this instruction. Its output state
Val_SpeedRefREALSpeed reference (target, in engineering units) to drive.
Val_SpeedFdbkREALSpeed feedback (actual, in engineering units) from drive.
Val_SpeedRefRawREALCopy of speed reference output (in raw units) for faceplate.
Val_SpeedFdbkRawREALCopy of speed feedback input (in raw units) for faceplate.
Val_SpeedRefEUMinREALMinimum of speed reference = MIN (Cfg_SpeedFdbkEUMin, Cfg_SpeedFdbkEUMax).
Val_SpeedRefEUMaxREALMaximum of speed re ference = MAX (C fg_SpeedFdbkEUMin, Cfg_SpeedFdbkEUMax).
Val_SpeedFdbkEUMinREALMinimum of speed feedback = MIN (Cfg_SpeedFdbkEUMin, Cfg_SpeedFdbkEUMax).
Val_SpeedFdbkEUMaxREALMaximum of speed feedback = MAX (Cfg_SpeedFdbkEUMin, Cfg_SpeedFdbkEUMax).
Val_MotorCurrentREALDrive output current (amps).
Val_MotorCurrentPctREALMotor current (% full load amps).
Val_MotorVoltageREALMotor voltage (volts).
Val_Outpu tPowerREALDrive output power (k W).
Val_MotorPowerPctREALMotor power (% rated power).
always reflects EnableIn input state.
Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 201719
PowerFlex 6000 Drive (P_PF6000)
Table 8 - P_PF6000 Drive Output Parameters
Output ParameterData TypeAlias ForDescription
SrcQ_IOSINTI/O signal source and quality.
SrcQFinal drive source and quality.
GOOD 0 = I/O live and confirmed good quality
1 = I/O live and assumed good quality
2 = No feedback configured, assumed good quality
TEST 8 = Device simulated
9 = Device loopback simulation
10 = Manually entered value
UNCERTAIN 16 = Live input, off-specification
17 = Value substituted at device/bus
18 = Value substituted by maintenance (Has and not Use)
19 = Shed, using last good value
20 = Shed, using replacement value
BAD 32 = Signal failure (out-of-range, NaN, invalid combination)
33 = I/O channel fault
34 = I/O module fault
35 = Bad I/O configuration (for example, scaling parameters)
Val_CmdSINTDevice command:
Val_FdbkSINTDevice feedback:
Val_StsSINTDevice confirmed status:
Val_FaultSINTDevice fault status:
Val_ModeSINTMode.ValThe current mode is shown with status bits and also as an enumeration ‘Val_Mode’ as follows:
Val_OwnerDINTCurrent object owner ID (0 = not owned).
0 = No mode
1 = Hand
2 = Maintenance
3 = Override
4 = Program (locked)
5 = Operator (locked)
6 = Program (unlocked, Operator is default)
7 = Operator (unlocked, Program is default)
8 = Program (unlocked, Program is default)
9 = Operator (unlocked, Operator is default)
20Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.