Rockwell Automation PanelView 5510 User Manual

User Manual
Original Instructions
PanelView 5510 Terminals
Catalog Numbers 2715P-B7CD, 2715P-B7CD-B, 2715P-B7CD-K, 2715P-T7CD, 2715P-T7CD-B, 2715P-T7CD-K, 2715P-T7WD, 2715P-T7WD-B, 2715P-T7WD-K, 2715P-T9WD, 2715P-T9WD-B, 2715P-T9WD-K, 2715P-B10CD, 2715P-B10CD-B, 2715P-B10CD-K, 2715P-T10CD, 2715P-T10CD-B, 2715P-T10CD-K, 2715P-T12WD, 2715P-T12WD-B, 2715P-T12WD-K, 2715P-B15CD, 2715P-B15CD-B, 2715P-B15CD-K, 2715P-T15CD, 2715P-T15CD-B, 2715P-T15CD-K, 2715P-T19CD, 2715P-T19CD-B, 2715P-T19CD-K
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).

Table of Contents

Preface
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Request Corresponding Source for Open Source Packages . . . . . . . . . 8
Product Firmware and Release Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1
Overview About the PanelView 5510 Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Hardware Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operator Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Touch Gestures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Studio 5000 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
EtherNet/IP Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Typical Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Ethernet Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Install the PanelView 5510 Terminal
Chapter 2
Installation Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Environment and Enclosure Information. . . . . . . . . . . . . . . . . . . . 20
Wiring and Safety Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Outdoor Installation Recommendations . . . . . . . . . . . . . . . . . . . . 21
North American Hazardous Locations. . . . . . . . . . . . . . . . . . . . . . . . . . 23
Required Circuit Port Parameters for USB Peripheral Devices. 24
Mounting Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Mounting Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Panel Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Panel Cutout Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Product Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Prepare for Panel Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Mount the Terminal in a Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Remove and Replace the DC Power Terminal Block . . . . . . . . . . . . . 34
Connect to DC Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Connect to a Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Ethernet Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Device Level Ring Network Topology. . . . . . . . . . . . . . . . . . . . . . . 37
Linear Network Topology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Star Network Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Initial Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Update the Firmware Before You Use the Terminal . . . . . . . . . . 40
Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020 3
Table of Contents
Chapter 3
Configure Terminal Settings Runtime Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Enter Data With Virtual Keyboards . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Specify Keypad or Keyboard Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Log On to the Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Log Off of the Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Settings Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Configure the IP Address of the Terminal. . . . . . . . . . . . . . . . . . . . . . . 51
Use DHCP to Assign an IP Address For the Terminal. . . . . . . . 51
Assign a Static IP Address For the Terminal . . . . . . . . . . . . . . . . . 52
Configure a DNS Address For the Terminal. . . . . . . . . . . . . . . . . . . . . 53
Configure the Ethernet Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
View the Network Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Use the Data Export Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Adjust the Brightness of the Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Modify Screen Color Settings by Using HMI Device Tags . . . . . . . . 58
Configure the Display Screen Saver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Calibrate the Touch Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Disable Downloads to the Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Change the HMI Device Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
View the Firmware Revision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Display Terminal Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Enable the VNC Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Load an Application from Removable Media . . . . . . . . . . . . . . . . . . . . 67
Reboot the Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Change the Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
View Information for the Configured Controller . . . . . . . . . . . . . . . . 70
Chapter 4
Monitor and Manage Control System Alarms
Alarm Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Alarm Help Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
View the Alarm Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Manage the Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Alarm Detail Pane Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Filter the Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
View the Alarm History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Export the Alarm History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Chapter 5
Install and Replace Components
4 Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020
Accessories and Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Voltage Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Electrostatic Discharge Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Connect to USB Ports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
USB Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Insert an SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Replace the Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Table of Contents
Install a Protective Overlay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Clean the Overlay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Remove the Overlay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Chapter 6
Update Firmware Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Firmware Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Get the Terminal Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Install the ControlFLASH Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Update the Firmware by Using ControlFLASH Software . . . . . . . . 95
Verify the Firmware Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Chapter 7
Troubleshooting Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
View Diagnostic Information for the Configured Controller. . . . . 101
Troubleshooting Profiles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Import a Troubleshooting Profile . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Export a Troubleshooting Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Terminal Does Not Start Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Terminal Restarts Intermittently . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Touch Screen Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Display Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Ethernet Issues. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Cannot Download Application to Terminal. . . . . . . . . . . . . . . . . . . . 107
Performance Is Slow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Resistance to Chemicals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Clean the Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Remove Paint and Grease . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Equipment Wash Downs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Ship the Terminal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Restore Factory Defaults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Dispose of the Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020 5
Table of Contents
Notes:
6 Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020

Preface

This manual describes how to install, configure, operate, and troubleshoot the PanelView™ 5510 terminals. This manual does not provide procedures on how to
create applications that run on the terminals, or ladder logic that runs in the controller.
Other tasks that you must do include:
• Configure the Ethernet settings and update the firmware of the terminal.
IMPORTANT You must configure the Ethernet settings and update the firmware
before you can download a View Designer project and use the terminal. See Initial Startup on page 39
• Create a project by using the Studio 5000 View Designer® application.
• Create control logic for the controller by using the Studio 5000 Logix Designer® application.
.

Summary of Changes

Package Contents

This manual contains new and updated information as indicated in the following table.
Top ic Pa ge
Added catalog numbers for the PanelView 5510 conformal-coated terminals to the front cover.
Added a statement about conformal coating to the bulleted list. 11
Updated the Catalog Number Explanation table with conformal coating catalog numbers. 16
Added conformal coating catalog numbers to the Product Selection table. 17
Added instructions on how to configure the keypad size. 46
Added instructions for modifying the PanelView 5000 screen color settings by using HMI device tags. 58
Added instructions on how to load an application from removable media. 67
Added instructions on how to view and export the alarm history. 82
The PanelView 5510 terminals ship with these items.
Item Description
Hardware • Mounting levers for panel installation
• Removable DC power terminal block
Documents • PanelView 5510 Terminals Product Information, publication 2715P-PC001
• Cutout Templates for PanelView 5510 Terminals, publication 2715P-DS001
Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020 7
Preface

Request Corresponding Source for Open Source Packages

Product Firmware and Release Notes

The software included in this product contains copyrighted software that is licensed under one or more open source licenses. Copies of those licenses are included with the software. Corresponding Source for open source packages included in this product can be found at the websites identified in the product documentation.
You can also obtain complete Corresponding Source by contacting Rockwell Automation via our Contact form on the Rockwell Automation website: http://
www.rockwellautomation.com/global/about-us/contact/contact.page. Please
include ‘Open Source’ as part of the request text.
IMPORTANT Do not modify the NVS file. The NVS file is used in firmware updates and a
modified NVS file can cause the firmware update to fail.
Product firmware and release notes are available online at the Product Compatibility and Download Center at
https://compatibility.rockwellautomation.com/Pages/home.aspx
1. On the PCDC home page, search for your product.
.
2. On the search results page, find the firmware and release notes for your product.
See the Product Compatibility and Download Center Quick Start Guide, publication PCDC-QS001 firmware and release notes for the terminal.
, for instructions on how to find and download
8 Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020
Preface

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
PanelView 5510 Terminals Technical Data, publication 2715P-TD001
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Guidelines for Handling Lithium Batteries Technical Data, publication AG-5. 4
Industrial Ethernet Media Brochure, publication
1585-BR001
EtherNet/IP™ Embedded Switch Technology Application Guide, publication ENET-AP005
ControlFLASH Firmware Upgrade Kit User Manual, publication 1756-UM105
Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Controls, publication SGI-1.1
Product Certifications website,
rok.auto/certifications
Provides specifications and cer tifications for the PanelView 5510 terminal.
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides guidelines to store, handle, install, and dispose of lithium batteries.
Provides general guidelines about Ethernet networking and connectivity.
How to install, configure, and maintain linear and device level ring (DLR) networks that use Rockwell Automati on EtherNet/IP devices with embedded switch technology.
Describes how to use the ControlFLASH™ software to upgrade device firmware.
Provides general guidelines for the application, installation, and maintenance of solid-state equipment.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at
http://www.rockwellautomation.com/global/literature-library/overview.page
.
Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020 9
Preface
Notes:
10 Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020
Chapter 1
Overview
Topic Page Topic Page
About the PanelView 5510 Terminals 11 Typical Configuration 16
Hardware Features 12 Catalog Number Explanation 16
Operator Control 12 Product Selection 17
Touch Gestures 14 Accessories 17
Studio 5000 Environment 14 Ethernet Cables 18
EtherNet/IP Communication 16

About the PanelView 5510 Termina ls

The PanelView™ 5510 terminals are operator interface devices that monitor and control devices attached to ControlLogix® L7 or L8 controllers, and CompactLogix™ L1, L2, or L3 controllers over an EtherNet/IP™ network. Animated graphic and text displays provide a view into the operating state of a machine or process. Operators interact with the control system by using the touch screen or keypad of the terminal.
The PanelView 5510 terminals include these features and capabilities:
• Tightly integrated control and design environment allows information to be shared between the PanelView 5510 terminal and the Logix platforms.
• The Studio 5000® environment provides one point of access for both View
(1)
Designer and Logix Designer applications
.
• Connection up to four ControlLogix L7 or L8 controllers, or CompactLogix L1, L2, or L3 controllers.
(2)
• Supports a maximum of 100 user-defined screens.
• Supports a maximum of 4,000 Logix-based alarms
(1)
.
• Ethernet communication that supports Device Level Ring (DLR), linear, or star network topologies.
• High-speed human machine interface (HMI) button control and easily configured navigation menu.
• Conformal coating available for all terminal sizes.
(1) PanelView 5510 firmware can support up to 4,000 Logix-based alarms if you use Studio 5000 View Designer application version 5
and Studio 5000 Logix Designer application version 32 or higher. Earlier versions of the Studio 5000 View Designer or Studio 5000 Logix Designer applications can support up to 1,000 Logix-based alarms. For more information about the Logic-based alarms, see footnote 2.
(2) A combination of up to four of the following Logix controller models: ControlLogix L7 or CompactLogix L1, L2, or L3 controller with
revisio n 31 firmware o r later. NOTE: If the PanelView 5510 terminal supports up to four Logix controllers, then each controller can use a mix (instruction-based and tag-based) of alarms up to 1,000 alarms per controller. If a single Logix controller is supported, then up to 4,000 alarms can be used but only 1,000 of them can be instruction-based.
Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020 11
Chapter 1 Overview
2
36
7
L1
L2
L3
L4
L5
L6
L8
L7
R9
R10
Esc
798
456
123
0
.
R11
R12
R13
R14
R16
R15
1
5
8
9
4

Hardware Features

The PanelView 5510 terminals are fixed hardware configurations that provide a range of display sizes and operator input options.
Table 1 - Hardware Features
Item Feature Description
1 Display/Keypad TFT color graphic displays with a touch screen and navigation button in a range of display sizes. Some models also have a keypad and
2 Power 18…30V DC (isolated)
3 Mounting slot The slots on the top, bottom, and sides of the terminal are used with mounting levers to mount the device to a panel or enclosure. The
4 Ethernet ports Two 10/100Base-T, Auto MDI/MDI-X, EtherNet/IP ports for controller communication that supports DLR network topology.
5 USB host ports Two USB 2.0 high-speed (type A) host ports.
6 USB device port One USB 2.0 high-speed (type B) device port to connect a host computer that is software-feature dependent.
7Audio out IMPORTANT: The audio out feature is not functional. The feature is expected to be available in a future software release.
8 Status indicators Light-emitting diode indicators on back of unit provide status and fault conditions.
9 Secure Digital (SD) card slot One slot that supports an SD™ or SDHC™ card that is recommended in Table 6 on page 18
function keys providing additional operator input options.
• 6.5-in. touch or touch with keypad
• 7-in. wide screen with touch
• 9-in. wide screen with touch
• 10.4-in. touch or touch with keypad
• 12.1-in. wide screen with touch
• 15-in. touch or touch with keypad
• 19-in. touch
number of slots varies by terminal size.
.

Operator Control

All PanelView 5510 terminals have a color display with a touch screen and navigation key, or a touch screen, navigation key, and keypad for operator control.
12 Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020
• Analog, resistive, touch screens provide accurate, durable touch with excellent reliability for control of industrial applications.
• Keypad models are similar except for the number of function keys to the left (L#) and right (R#) of the display. Larger models have more keys.
Overview Chapter 1
4
14
3
2
ATT EN TI ON : The keypad and touch screen support input from a finger, stylus, and gloved hand for operation in dry or wet environments. The plastic stylus must have a minimum tip radius of 1.3 mm (0.051 in.). Any other object or tool can damage the keypad or touch screen.
ATT EN TI ON : Do not perform multiple operations simultaneously. Multiple simultaneous operations can result in unintended operation.
• Touch only one operating element on the screen with one finger at one time.
• Press only one key on the terminal at one time.
L8
The physical keypad on the PanelView 5510 terminal is used during runtime to initiate actions, control navigation, and enter data. The terminal also supports a virtual keyboard and numeric keypad that opens on PanelView 5510 terminal screens during runtime.
The terminal also supports the use of a physical keyboard and mouse when connected to the USB ports.
Table 2 - PanelView 5510 Terminal Keypad
Item Feature Description
1 Navigation button Opens the navigation menu at the bottom of a screen and displays the contents of a project. The menu allows screen navigation and device
2 Numeric keypad Contains numeric, decimal, minus, and these keys:
3 Navigation keys Provides navigation control.
4Function keys
• 6.5-in. terminal
• 10.4-in. terminal
• 15-in. terminal
configuration.
• Backspace - deletes the character to the left of the insertion point.
• Enter - inputs the currently highlighted key or enters a blank line if the insertion point is in the text box of the virtual keyboard.
• Tab-left, Tab-right - selects the previous or next control or input element.
• Esc - cancels or dismisses a dialog.
• Arrow keys - selects a key on the virtual keyboard that is above, below, left, or right of the selected key. Arrow keys also move the cursor if the cursor is in a text box.
• Home/End - moves the insertion point to the beginning or end of a text or numeric entry field.
• Page up/Page down - goes to the next or previous pages of a list.
Performs specific commands when configured for a screen or any of its graphic elements. For example, L1 can be configured to go to another screen.
• L1…L6 and R1…R6
• L1…L8 and R1…R8
• L1…L10 and R1…R10
Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020 13
Chapter 1 Overview

Touch Gestures

Studio 5000 Environment

The PanelView 5510 terminal supports touch gestures to interact with screen elements during runtime. Standard touch gestures include:
Ta p – Briefly touch the target on the HMI screen with your fingertip.
Drag – Move your fingertip over the target on the HMI screen without contact loss.
For a list of actions you can perform by using touch gestures, see the View Designer help.
Use the Studio 5000 environment to create HMI applications for the PanelView 5510 terminal.
The Studio 5000 environment includes these applications:
Vie w Designer – you can create and design a project for a specific PanelView 5510 terminal and download the project to the terminal.
You can create an application for any PanelView 5510 terminal and reuse that same application across the entire platform.
Logix Designer – you can develop control logic for a CompactLogix or ControlLogix controller and download the logic to the controller.
14 Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020
Figure 1 - How Studio 5000 Applications Work Together
1
2
3
4
5
7
6
8
View Designer
Application
Logix Designer
Application
Tag Bro wse r
Offline
ACD Fi le
HMI Project
(VPD File)
HMI Device
Control ler
Runtime
Communication
LINK NET OK
Overview Chapter 1
The table describes how the View Designer and Logix Designer applications work together to create an HMI runtime project.
Table 3 - Studio 5000 Applications and Tools
Item Component Description
1View Designer
application
2 Tag browser A tool that is used to search for and select tags within a Studio 5000 Logix Designer ACD
3Logix Designer
application
4 ACD file An Automation Controller Database (ACD) file. An ACD file is a Logix Designer project file
5 HMI project
(VPD file)
6 HMI device A Human Machine Interface (HMI) device, such as the PanelView 5510 terminal, which
7 Runtime The environment in which the runtime HMI project communicates with the controller.
8 Controller A logic controller such as a ControlLogix or CompactLogix 5370 controller.
A Studio 5000 application that is used to build HMI projects. Studio 5000 View Designer projects are stored as VPD files that can be downloaded to the
PanelView 5510 terminal.
project file. You can bind the tags to graphic element properties and properties of an HMI screen. The Studio 5000 View Designer application uses the tag browser to read data from an ACD file.
A Studio 5000 application that is used to develop control logic for an industrial automation system. Studio 5000 Logix Designer application interfaces with controllers to read and write tag information. Studio 5000 Logix Designer projects are stored as ACD files that can be downloaded to the controller.
that contains the logic or code, including tags and data types, which runs within a controller.
A View Project Database (VPD) file. A VPD project is a file that contains the operator interface application, including HMI screens, controller references, and information about the HMI device to run the application.
runs the HMI project. At runtime, the HMI device communicates directly with the controller.
During runtime, the HMI device runs the downloaded project, exchanges data with the controller, animates displayed data, and responds to operator input.
Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020 15
Chapter 1 Overview

EtherNet/IP Communication

Typical Configuration

Catalog Number Explanation

The PanelView 5510 terminals contain EtherNet/IP embedded switch technology. These terminals communicate with ControlLogix controllers over an Ethernet connection with DLR or linear network topologies. Star technology is also supported when using switches.
The PanelView 5510 terminals can reside on EtherNet/IP networks that run integrated motion and CIP Sync applications without adverse performance. The terminal is not a consumer or producer of CIP Sync or motion packets.
Traditional DLR linear, and star network topologies are supported. See these topics for examples:
Device Level Ring Network Topology on page 37
Linear Network Topology on page 38
Star Network Topology on page 39
This table provides an explanation of the catalog numbers.
Bulletin Input Type Display Size Display Type Power Special Option
||| |||
(1)
2715P- T = Touch 7 = 6.5-in.
B = Keypad with touch 7 = 7-in.
9 = 9-in.
10 = 10.4-in.
12 = 12.1-in.
15 = 15-in.
19 = 19-in.
(1) For the display size/display type combination, 7C designates the 6.5-in. standard display model, and 7W designates the 7-in. wide screen display model. (2) A catalog number with -B at its end (for example, 2715P-T7WD-B) is a terminal without the Allen-Bradley® logo and product identification on the front bezel. (3) A catalog number with -K at its end (for example, 2715P-T7CD-K) is a terminal with conformal coating.
C = Color, standard aspect ratio D = DC isolated B = Without brand identity
(1)
W = Color, wide aspect ratio K = Conformal coating
(2)
(3)
16 Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020
Overview Chapter 1

Product Selection

Cat. No. Display
Touch Key and Touch Size Type Aspect Ratio Pixels (W x H) DLR RAM User
2715P-T7CD 2715P-T7CD-B
2715P-T7CD-K
2715P-T7WD 2715P-T7WD-B
2715P-T7WD-K
2715P-T9WD 2715P-T9WD-B
2715P-T9WD-K
2715P-T10CD 2715P-T10CD-B
2715P-T10CD-K
2715P-T12WD 2715P-T12WD-B
2715P-T12WD-K
2715P-T15CD 2715P-T15CD-B
2715P-T15CD-K
2715P-T19CD 2715P-T19CD-B
2715P-T19CD-K
(1) Non-volatile memory that is available to store projects.
This table provides product selection information.
2715P-B7CD 2715P-B7CD-B
2715P-B7CD-K
7-in. wide WVGA TFT Color 5:3 800 x 480
9-in. wide
2715P-B10CD 2715P-B10CD-B
2715P-B10CD-K
12.1-in.
2715P-B15CD 2715P-B15CD-B
2715P-B15CD-K
19-in. SXGA TFT Color 5:4 1280 x 1024
6.5-in. VGA TFT Color 4:3 640 x 480 DC Yes 1 GB 1 GB
10.4-in. SVGA TFT Color 4:3 800 x 600
WXGA TFT Color 16:10 1280 x 800
wide
15-in. XGA TFT Color 4:3 1024 x 768
Input
Power
Ethernet Memory
(1)

Accessories

Ta b l e 4 through Ta b l e 8 list accessories for the PanelView 5510 terminals.
Table 4 - Protective Overlays
Operator Input
(1)
Cat. No.
2711P-RGT7SP 6.5-in.
2711P-RGB7P
2711P-RGT7W 7-in. wide
2711P-RGT9SP 9-in. wide
2711P-RGT10SP 10.4-in.
2711P-RGB10P
2711P-RGT12SP 12.1-in. wide
2711P-RGT15SP 15-in.
2711P-RGB15P
2711P-RGT19P 19-in.
(1) Three overlays are shipped with each catalog number.
Display Size
Tou ch Ke y and Touc h
Protective overlays help protect your PanelView terminal touch screen and keys from scratches, dust, fingerprints, and external damage from chemicals or abrasive materials.
Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020 17
Chapter 1 Overview
Table 5 - Power Supplies and Power Terminal Blocks
Cat. No. Description Quantity
1606-XLP95E DIN-rail power supply, 24…28V DC output voltage, 95 W 1
1606-XLP100E DIN-rail power supply, 24…28V DC output voltage, 100 W 1
2711P-RSACDIN DIN-rail power supply, AC-to-DC, 100…250V AC, 50…60 Hz 1
2711P-RTBDSP 3-pin DC power terminal block (black with white labels for +, –, and GND) 10
Table 6 - Secure Digital (SD) Cards
Cat. No. Description Quantity
1784-SD1 1-GB SD card 1
1784-SD2 2-GB SD card 1
1784-SDHC8 8-GB SDHC card 1
1784-SDHC32 32-GB SDHC card 1
2711C-RCSD USB to SD adapter for SD card 1
(1) To help reduce the chance of corruption when you use SD Cards or USB drives with the terminal, Rockwell Automation
recommends that you use only the above SD card catalog numbers.
(1)
SD and SDHC accessory cards in Ta b l e 6 have been designed to meet industrial robustness and environmental requirements. Rockwell Automation recommends you use these accessory cards with the terminal to help reduce the chances of corruption. Studio 5000 View Designer software requires the following for SD cards that are inserted into the HMI device:
• 4 GB of free space
• A supported SDHC card type, preferably one listed in Ta b l e 6
• An environmental rating for the PanelView 5000 environment
• A supported format of either FAT32 or ext3
Table 7 - Mounting Hardware
Cat. No. Description Quantity
(1)
2711P-RMCP
(1) Catalog number 2711P-RMCP mounting levers are used with the PanelView 5510 terminals. Do not use gray mounting levers; they
are not compatible with PanelView 5510 terminals.
Mounting levers (black) 16
Table 8 - Battery Replacement
Cat. No. Description Quantity
2711P-RY2032 Lithium coin cell battery, CR2032 equivalent 1

Ethernet Cables

See the Industrial Ethernet Media Brochure, publication 1585-BR001B, for recommended Ethernet cables and media solutions.
18 Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020
Install the PanelView 5510 Terminal
Top ic Pa ge
Installation Precautions 20
North American Hazardous Locations 23
Mounting Considerations 25
Mounting Clearances 25
Panel Guidelines 26
Panel Cutout Dimensions 26
Product Dimensions 27
Prepare for Panel Mounting 28
Mount the Terminal in a Panel 31
Remove and Replace the DC Power Terminal Block 34
Connect to DC Power 35
Connect to a Network 36
Initial Startup 39
Chapter 2
ATT EN TI ON : Do not use a PanelView™ 5510 terminal for emergency stops or other controls critical to the safety of personnel or equipment. Use separate hard-wired operator interface devices that do not depend on solid-state electronics.
Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020 19
Chapter 2 Install the PanelView 5510 Terminal

Installation Precautions

Read and follow these precautions before you install the PanelView 5510 terminal.
Environment and Enclosure Information
ATTENTION: This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6561 ft) without derating. The terminals are intended for use with programmable logic controllers.
This equipment is considered Group 1, Class A industrial equipment according to IEC CISPR 11. Without appropriate precautions, there can be difficulties with electromagnetic compatibility in residential and other environments due to conducted or radiated disturbances.
Korean Radio Wave Suitability Registration - When so marked this equipment is registered for Electromagnetic Conformity Registration as business equipment (A), not home equipment. Sellers or users are required to take caution in this regard.
이 기기는 업무용 (A 급 ) 전자파적합기기로서 판 매자 또 는 사용자는 이 점을 주의하시기 바 라 며 , 가정외의 지역 에서 사용하는 것을 목적으 로 합니다 .
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that can be present, and appropriately designed to help prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. The terminals meet specified NEMA, UL Type, and IEC ratings only when mounted in a panel or enclosure with the equivalent rating. Subsequent sections of this publication can contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 for additional installation requirements.
• NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
,
20 Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020
Wiring and Safety Guidelines
ATTENTION: Use publication NFPA 70E, Electrical Safety Requirements for
Employee Workplaces, IEC 60364 Electrical Installations in Buildings, or other applicable wiring safety requirements for the country of installation when wiring the devices. In addition to the NFPA guidelines, here are some other guidelines to follow:
• Connect the device and other similar electronic equipment to its own branch circuit.
• Protect the input power by a fuse or circuit breaker rated at no more than 15 A.
• Route incoming power to the device by a separate path from the communication lines.
• Cross power and communication lines at right angles if they must cross.
• Communication lines can be installed in the same conduit as low-level DC I/O lines (less than 10V).
• Shield and ground cables appropriately to avoid electromagnetic interference (EMI). Grounding minimizes noise from EMI and is a safety measure in electrical installations.
For more information on grounding recommendations, refer to the National Electrical Code published by the National Fire Protection Association.
Install the PanelView 5510 Terminal Chapter 2
Outdoor Installation Recommendations
When you use a PanelView 5510 terminal outdoors, follow these recommendations to maximize the field life of the front bezel and display:
• Do not expose terminal to direct sunlight
• Add UV protection and/or shielding
• Manage terminal temperature
• Mount terminal in an acceptable position
•Select a proper enclosure
Ultraviolet (UV) and infrared radiation can reduce the field life of any electronic terminal. While the materials used in the terminal bezels provide long field life, that life can be improved by proper installation and by following the suggested guidelines.
UV radiation from the sun causes all plastics to fade or yellow and become brittle over time. Avoid direct sunlight exposure, use a sacrificial antiglare overlay and/or use a shield to shade the terminal to help protect the front of the terminal from direct exposure to UV radiation and greatly increase its field life. See Ta ble 4 on
page 17 for a selection of appropriate protective overlay accessories. When you
install a sun shield that closes over the display, the temperature between the sun shield and the display cannot exceed the maximum temperature of the display, which is 55 °C (131 °F). Adequately ventilate all sun shields to help prevent excess heat rise on the terminal display.
Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020 21
Chapter 2 Install the PanelView 5510 Terminal
Use stirring fans or active cooling in high altitude and high ambient temperature locations to keep the internal enclosure temperature below 55 °C (131 °F).
Verify that the ambient temperature at which the product is operating does not fall below its minimum rated 0 °C (32 °F).
Minimize the temperature differential between the inside of the terminal enclosure and the front panel to help reduce the potential for condensation and possible pressure variation between the inside and outside of the terminal.
If possible, avoid placing the terminal on the south (north in the southern hemisphere) or west side of the cabinet, which helps reduce the heat rise due to solar heating during the hottest part of the day.
Mount the terminal vertically to minimize solar heating on the display. Do not mount the terminal in a sloped enclosure if it exposes the terminal to direct sunlight. For more information, see Mounting Considerations on page 25
.
To help protect the terminal from water and dust, mount it in a proper enclosure by following the instructions in the PanelView 5510 Terminals Product Information, publication 2715P-PC001
. The terminals meet specified NEMA, UL Type, and IEC ratings only when properly mounted in a panel or enclosure with the equivalent rating. Other sections of this publication can contain additional information about specific enclosure type ratings that are required to comply with certain product safety certifications.
ATT EN TI ON : Failure to follow the recommended installation practices for outdoor use can substantially reduce terminal life and void its warranty.
22 Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020

North American Hazardous Locations

Install the PanelView 5510 Terminal Chapter 2
The following information applies when operating this equipment in hazardous locations.
ATTENTION: When marked, these products are suitable for use
in “Class I, Division 2, Groups A, B, C, D”; Class I, Zone 2, Group IIC hazardous locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING: EXPLOSION HAZARD
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components impair suitability for Class I, Division 2.
• Peripheral equipment must be suitable for the location in which it is used.
• The battery in this product must be changed only in an area known to be nonhazardous.
• All wiring must be in accordance with Class I, Division 2 wiring methods of Article 501 of the National Electrical Code and/or in accordance with Section 18-1J2 of the Canadian Electrical Code, and in accordance with the authority having jurisdiction.
Informations sur l’utilisation de cet équipement en environnements dangereux.
ATTENTION: Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne
conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT: RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
• Les équipements périphériques doivent s'adapter à l'environnementdans lequel ils sont utilisés.
• S'assurer que l'environnement est classé non dangereux avant de changer la pile ou le module horloge temps réel de ce produit.
• Tous les systèmes de câblage doivent être de Classe I, Division 2, conformément aux méthodes de câblage indiquées dans les Articles 501 du National Electrical Code (Code Electrique National) et/ou conformément à la Section 18­1J2 du Canadian Electrical Code (Code Electrique Canadien), et en fonction de l'autorité de jurisdiction.
The terminals have a temperature code of T4 when operating in a 55 °C (131 °F) maximum ambient temperature. Do not install product in environments where atmospheric gases have ignition temperatures less than 135 °C (275 °F).
Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020 23
Chapter 2 Install the PanelView 5510 Terminal
Nonincendive Field Wiring Apparatus
Associated Nonincendive Field Wiring Apparatu s
PanelView 5510 Host Product
USB Peripheral Device
USB Peripheral Device
USB Host Port
USB Host Port
Required Circuit Port Parameters for USB Peripheral Devices
This product contains USB host ports that comply with hazardous location environments. Field wiring compliance requirements are provided in compliance with the National Electrical Code, Article 500.
Figure 2 - PanelView 5510 Control Drawing
PanelView 5510 terminals provide two, separately powered USB host ports. Ta b l e 9 defines the circuit parameters of these USB host ports.
Table 9 - Circuit Parameters for USB Host Ports
Parameter Value Parameter Definition
V
I
sc (USB)
C
a (USB)
L
a (USB)
oc (USB)
5.25V DC Open circuit voltage of each host USB port. The maximum applied voltage rating, V than or equal to V
1.68 A Maximum output current of each host USB port. The maximum current, I greater than or equal to I
10 µF This value is the maximum total capacitance that can be connected to each USB host port. The total
capacitance of each USB peripheral device and its associated cable must not exceed the indicated value.
The maximum total capacitance, C device shall be less that or equal to C
15 µH This value is the maximum total inductance that can be connected to each USB host port. The total
inductance of each USB peripheral de vice and its associated cable must not exceed the indicated value. The maximum total inductance, L
device shall be less than or equal to L
oc (USB)
.
max (peripheral)
sc (USB).
max (peripheral)
, to which each USB peripheral device can be subjected, shall be
i (peripheral)
a (USB)
i (peripheral)
a (USB)
, of each USB peripheral device shall be greater
, and cable capacitance of each separate USB peripheral
.
, and cable inductance of each separate USB peripheral
.
V
max (peripheral)
(as appropriate)
I
max (peripheral)
C
L
i (peripheral)
i (peripheral)
+ C
+ L
≥ V
oc (USB)
I
sc (USB)
cable(USB)
cable
≤ L
≤ C
a (USB)
a (USB)
Application Information
Per the National Electrical Code, the circuit parameters of associated field-wiring apparatus for use in hazardous locations shall be coordinated with the host product such that their combination remains nonincendive. PanelView 5510 terminals and the USB peripheral devices shall be treated in this manner.
The USB peripheral devices and their associated cabling shall have circuit parameters with the limits given in Ta b l e 9 them to remain nonincendive when used with the PanelView 5510 USB host ports.
If cable capacitance and inductance are not known, use the following values from ANSI/ISA-RP 12.06.01-2003:
C
= 197 pF/m (60 pF/ft)
cable
L
= 0.7 µH/m (0.20 µH/ft)
cable
Nonincendive field wiring must be wired and separated in accordance with 501.10(B)(3) of the National Electrical Code (NEC) ANSI/NFPA 70 or other local codes as applicable. This associated nonincendive field wiring apparatus has not been evaluated for use in combination with another associated nonincendive field wiring apparatus.
24 Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020
for
Install the PanelView 5510 Terminal Chapter 2
L8
L8
L8
L8
L8
L8
Acceptable Unacceptable
180°
90°

Mounting Considerations

Consider the following when mounting the terminal:
• Mount the terminal at a height suitable for operators. You can mount the cabinet at a level other than the operator floor.
• Use appropriate light. Do not operate the terminal in direct sunlight.
• Terminals are rated to operate at various mounting positions as shown in
Figure 3
Figure 3 - Acceptable and Unacceptable Mounting Positions
.
(1)
ATT EN TI ON : Failure to follow these guidelines can result in personal injury or damage to the panel components.

Mounting Clearances

Plan for adequate space around the terminal, inside the enclosure, for ventilation and cables. Consider the heat from other devices in the enclosure. The ambient temperature around the terminal must be 0…55 °C (32…131 °F)
Table 10 - Minimum Required Clearances
Terminal Area Minimum Clearance
Top 51 mm (2 in.)
Bottom 102 mm (4 in.)
Side 25 mm (1 in.)
Back 0 mm (0 in.)
(1)
.
102 mm (4 in.) is required to insert and remove an SD™ or SDHC™ card, or cable on one side
Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020 25
(1) For terminals with a 15-in. or 19-in. display, the ambient temperature around the terminal must be 0…50 °C (32…122 °F) when
mounted at an angle of less than 45° or greater than 135°.
Chapter 2 Install the PanelView 5510 Terminal

Panel Guidelines

Panel Cutout Dimensions

The terminals are panel-mounted devices that mount in the door or wall of a NEMA, UL Type, or IP rated enclosure:
• Enclosure panels must meet the panel thickness requirements in Table 13
on page 28.
• The material strength and stiffness of the panel must be sufficient to hold the terminal and maintain an appropriate seal against water and dust.
• The panel surface must be flat and free of imperfections to maintain an adequate seal and NEMA, UL Type, or IP ratings.
Use the template that is shipped with your terminal to mark the cutout dimensions.
Table 11 - PanelView 5510 - Panel Cutout Dimensions
Terminal Size Input Type Height, mm (in.) Width, mm (in.)
6.5-in. Keypad and touch 142 (5.59) 237 (9.33)
Touch 142 (5.59) 184 (7.24)
7-in. Touch 150 (5.9) 210 (8.25)
9-in. Touch 162 (6.38) 252 (9.92)
10.4-in. Keypad and touch 224 (8.82) 335 (13.19)
Touch 224 (8.82) 269 (10.59)
12.1-in. Touch 218 (8.58) 312 (12.28)
15-in. Keypad and touch 290 (11.42) 418 (16.46)
Touch 290 (11.42) 353 (13.90)
19-in. Touch 383 (15.08) 457 (17.99)
26 Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020
Install the PanelView 5510 Terminal Chapter 2
L8
A
A
D
BB
C
D
C

Product Dimensions

The table provides product dimensions. The 10.4-inch touch and combination keypad with touch terminals are shown for illustrative purposes. All other terminal sizes look similar.
Figure 4 - PanelView 5510 Terminal Dimensions (the 10.4-in. terminal is Shown)
Table 12 - PanelView 5510 Terminal Dimensions
Ter min al
Size Input Type
6.5-in. Keypad and touch 179 (7.05) 285 (11.22) 69.6 (2.74) 63.6 (2.50)
Touch 170 (6.69) 212 (8.35)
7-in. Touch 178 (7.0) 236 (9.3)
9-in. Touch 190 (7.48) 280 (11.02)
10.4-in. Keypad and touch 252 (9.92) 385 (15.16)
Touch 252 (9.92) 297 (11.69)
12.1-in. Touch 246 (9.69) 340 (13.39)
15-in. Keypad and touch 329 (12.95) 484 (19.06)
Touch 318 (12.52) 381 (15.00)
19-in. Touch 411 (16.18) 485 (19.09)
(1) When mounted in a panel, the front of the bezel extends less than 6.36 mm (0.25 in.) from the front of the panel.
Height
(A)
mm (in.)
Width
(B)
mm (in.)
Overall Depth
(C)
mm (in.)
Mounted Depth
(D)
mm (in.)
(1)
Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020 27
Chapter 2 Install the PanelView 5510 Terminal
6
1
1
2
3
4
5
6
Notch
Alignment Mark
Orientation of Slot Varies

Prepare for Panel Mounting

Before mounting your PanelView 5510 terminal in a panel, read this section and the entire installation procedure on page 31
.
IMPORTANT Catalog number 2711P-RMCP mounting levers (black) are used with PanelView
5510 terminals. Do not use gray mounting levers; they are not compatible with PanelView 5510 terminals.
Mounting levers insert into the slots around the bezel to secure the terminal in the panel. The number of levers varies by terminal size.
Each slot has six notches with alignment marks that are locking positions for a lever. The thickness of the panel in which you mount the terminal determines the locking position that is required to maintain a NEMA, UL Type, or IP seal.
Table 13 - Lever Locking Positions
Mounting Slot
Lever Lock
Position
1
2
3
4
5
6
Panel Thickness Range
1.50…2.01 mm (0.060…0.079 in.) 16
2.03…2.64 mm (0.080…0.104 in.) 14
2.67…3.15 mm (0.105…0.124 in.) 12
3.17…3.66 mm (0.125…0.144 in.) 10
3.68…4.16 mm (0.145…0.164 in.) 8/9
4.19…4.80 mm (0.165…0.188 in.) 7
Typic al
Gauge
Always orient a lever vertically before inserting it into a slot. This orientation is the only way to slide the lever knob within the slot for positioning. After sliding the lever to a specific notch, rotate the lever toward the panel to lock it in position. The flat side of the lever must come into contact with the panel.
28 Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020
Install the PanelView 5510 Terminal Chapter 2
Flat Side Knob on reverse side of lever inserts into large end of slot
1234
The edge of the bezel has alignment indentations to assist with the lever position. The notch on the outside of the lever shows that the lever is locked in position 3.
You can use an erasable marker or grease pencil to mark the indentations for visibility of slot positions.
Inner notch on lever shows current lever position.
1
Initially, you secure the terminal in the panel by sliding each lever to a position that is one or two notches greater than the final lock position. For example, if the final lock position is 3, slide each lever to position 4 or 5.
Follow the locking sequence and lever orientations for each terminal as shown in
Figure 5 on page 30
.
TIP If the lock position is 6, slide lever to large end of slot or insertion hole.
You then adjust each lever to its final lock position in the same sequence as shown in Figure 5 on page 30
.
IMPORTANT This process equalizes the pressure of the levers against the panel at a gradual
rate that reduces the probability of broken clamps.
Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020 29
Chapter 2 Install the PanelView 5510 Terminal
ERR
STS
1
212
5
24
6
6.5-in. Touch Only and 7-in. Touch Only - 6 Levers
6.5-in. Keypad and Touch - 8 Levers
2
7
4
8
8
29
3
10 1
7
5
4
5
9-in. and 10.4-in. Touch Only - 8 Levers
10.4-in. Keypad and Touch, 12.1-Touch Only - 10 Levers
3
1
6
24
5
6
8
7
3
1
6
3
1
29 4
6
12
8
11
5
82 46
11
13
9
10
14
12
15-in. Keypad and Touch - 14 Levers
53 17
1
10
3
7
15-in. Touch Only- 12 Levers
19-in. Touch Only- 16 Levers
53 1 7
82 4 6
11
13
9
15
10
16
12
14
IMPORTANT
The mounting lever orientations that are shown are required to maintain NEMA, UL Type, and IP seals. If you require a NEMA, UL Type, or IP seal, do not use a mounting lever in another orientation than shown.
Figure 5 - Mounting Lever Orientation and Lock Sequence
30 Rockwell Automation Publication 2715P-UM001D-EN-P - May 2020
Loading...
+ 86 hidden pages