Rockwell Automation MSR127RTP User Manual

MSR127RP/TP
Description
The MSR127RTP can be connected in three different input wiring configurations: one normally closed, two normally closed, or with two PNP connections from a light curtain. When connected in the two normally closed fashion, the MSR127RTP checks for cross faults across the two inputs. When connected to light curtains, the light curtain must perform the cross fault detection.
The MSR127RP has a monitored manual reset. The MSR127TP has an automatic/manual reset. Models with automatic/manual reset can have the reset jumpered or can be converted to an unmonitored manual reset by adding a normally open switch in the monitoring loop. Models with monitored manual reset provide checking of the output monitoring circuit.
The outputs include three normally open safety-rated outputs as well as one normally closed auxiliary output. The safety outputs have independent and redundant internal contacts to support the safety function. The auxiliary output is a nonsafety output intended to provide an external signal about the status of the safety outputs.
Features
Category 4 per EN 954-1 Stop category 0 Three safety contacts One auxiliary contact Cross fault monitoring Monitored or automatic reset Removable terminals Light curtain, E-stop or safety gate applications
LED Indicators
Green Power On Green CH1 Closed Green CH2 Closed
Specifications
Safety Ratings
Standards EN 954-1, ISO 13849-1, IEC/EN 60204-1, IEC 60947-4-1, IEC 60947-5-1, ANSI B11.19, AS4024.1 Safety Classification Cat. 4 per EN 954-1 (ISO 13849-1), SIL CL3 per EN IEC 62061, PLe per ISO 13849-1
Functional Safety Data
Note: For up-to-date information, visit
http://www.ab.com/safety/
PFHD: < 1.45 x 10-9 MTTFd: > 398 years
Suitable for performance levels Ple (according to ISO 13849-1:2006) and for use in SIL3 systems (according to IEC 62061) depending on the architecture and application characteristics
Certifications CE Marked for all applicable directives, cULus and BG
Power Supply
Input Power Entry 24V AC/DC, 115V AC or 230V AC 50/60 Hz Power Consumption 2 W
Inputs
Safety Inputs 1 N.C. or 2 N.C. or LC Input Simultaneity Infinite (ch2 before ch1) with Auto Reset Input Resistance, Max. 110 W Reset Auto./Manual or Monitored Manual Power On Delay/
Recovery Time
1 second/100 ms
Response Time 15 ms
Outputs
Safety Contacts 3 N.O. Auxiliary Contacts 1 N.C. Thermal CurrentI
lth
Units with 24V AC/DC supply: 3 x 4 A or 2 x 5 A nonswitching
Units with 115/230V AC supplies: 3 x 3 A or 2 x 4 A or 1 x 5 A nonswitching
Rated Impulse withstand Voltage 2500V Switching Current @ Voltage, Min. 10 mA/10V Fuses, Output External 6 A slow blow or 10 A fast acting Electrical Life (Operations) (With surge suppression)
250V AC/6 A/1500VA cosf = 1…0.1 M
250V AC/2.5 A/625VA cosf = 1…0.5 M
250V AC/1.5 A/375VA cosf = 0.35…0.3 M
250V AC/5 A/1250VA cosf = 0.6…0.1 M
24V DC/2 A/48 W = 1 M
10V DC/0.01 A/0.1 W = 2 M Mechanical Life 2,000,000 operations Utilization Category UL: B300, R300 5 A/250V AC, 24V DC Resistive: AC-1 5 A/250V AC Resistive: DC-1 5 A/24V DC Inductive: AC-15 5 A/250V AC Inductive: DC-13 3 A/24V DC 5 A/24V DC @ 6 ops/min
Environmental and Physical Characteristics
Enclosure Type Rating/ Terminal Protection
IP40 (NEMA 1)/
IP20
Operating Temperature [C (F)] ‐5…+55 ° (23…131 °) Vibration 10…55 Hz, 0.35 mm Shock 10 g, 16 ms 100 shocks Mounting 35 mm DIN Rail Weight [g (lb)] 24V DC: 210 (0.46), 115/230V AC: 260 (0.57) Conductor Size, Max. 0.2…4 mm2 (24…12 AWG)
Usable for ISO 13849‐1:2006 and IEC 62061. Data is based on the following assumptions:
- Mission time/Proof test interval of 20 years
- Functional test at least once within six-month period
Product Selection
Inputs Safety Outputs Auxiliary Outputs Terminals Reset Type Power Supply Cat. No.
1 N.C., 2 N.C., Light Curtain 3 N.O. 1 N.C. Fixed Auto./Manual 24V AC/DC 440R-N23126
Monitored Manual 440R-N23129 Auto./Manual 115V AC 440R-N23125 Monitored Manual 440R-N23128 Auto./Manual 230V AC 440R-N23124 Monitored Manual 440R-N23127
Removable (Screw) Auto./Manual 24V AC/DC 440R-N23132
Monitored Manual 440R-N23135
Removable (Spring Clamp) Auto./Manual 24V AC/DC 440R-N23132S
Monitored Manual 440R-N23135S
Removable (Screw) Auto./Manual 115V AC 440R-N23131
Monitored Manual 440R-N23134 Auto./Manual 230V AC 440R-N23130 Monitored Manual 440R-N23133
Approximate Dimensions
Dimensions are shown in mm (in.). Dimensions are not intended to be used for installation purposes.
Block Diagram
Typical Wiring Diagrams
Light Curtain, Monitored Manual Reset, Monitored Output Single Channel E-Stop, Automatic Reset, No Output Monitoring
Dual Channel E-Stop, Monitored Manual Reset, Monitored Output Dual Channel Safety Gates, Automatic Reset, Monitored Output
Copyright©2013 Rockwell Automation, Inc. All Rights Reserved.