Rockwell Automation Allen-Bradley Kinetix 350 Installation Instructions Manual

Page 1
Installation Instructions
Kinetix 350 Single-axis EtherNet/IP Servo Drives
Catalog Numbers 2097-V31PR0-LM, 2097-V31PR2-LM, 2097-V32PR0-LM, 2097-V32PR2-LM, 2097-V32PR4-LM, 2097-V33PR1-LM, 2097-V33PR3-LM, 2097-V33PR5-LM, 2097-V33PR6-LM, 2097-V34PR3-LM, 2097-V34PR5-LM, 2097-V34PR6-LM
Topi c Pag e
About the Kinetix 350 Drives 1
Important User Information 2
Catalog Number Explanation 3
Before You Begin 4
Safety Information 4
Install the Kinetix 350 Drive 5
Connector Data 7
Power Wiring Requirements 11
Motor Overload Protection 14
Circuit Breaker/Fuse Selection 15
Additional Resources 18

About the Kinetix 350 Drives

Kinetix® 350 single-axis EtherNet/IP servo drives provide an Ethernet-enabled solution for applications with output power requirements in the range of 0.4…3.0 kW (2…12 A rms).
See the Kinetix 350 Single-axis EtherNet/IP Servo Drives User Manual, publication
2097-UM002
and integrate with ControlLogix® or CompactLogix™ controller platforms.
, for detailed information on wire, apply power, troubleshoot,
Page 2
2 Kinetix 350 Single-axis EtherNet/IP Servo Drives
IMPORTANT

Important User Information

Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requi rements associ ated wit h any pa rticu lar ins tallat ion, Ro ckwell Au tomati on, Inc. cannot assum e respon sibili ty or li abilit y for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNIN G: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understand ing of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for exampl e, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Page 3
Kinetix 350 Single-axis EtherNet/IP Servo Drives 3

Catalog Number Explanation

This publication applies to the following Kinetix 350 drives.
Kinetix 350 Drives (single-phase)
Cat. No. Input Voltage
2097-V31PR0-LM
2097-V31PR2-LM 5.7
2097-V32PR0-LM
2097-V32PR2-LM 5.7
2097-V32PR4-LM 11.3
120/240V, 1 Ø
240V, 1 Ø
Kinetix 350 Drives (single- or three-phase)
Cat. No. Input Voltage
2097-V33PR1-LM
2097-V33PR3-LM 5.7
2097-V33PR5-LM 11.3
2097-V33PR6-LM 17.0
120V, 1 Ø 240V, 1 Ø 240V, 3 Ø
Kinetix 350 Drives (three-phase)
Cat. No. Input Voltage
2097-V34PR3-LM
480V, 3 Ø
2097-V34PR6-LM 8.5
Continuous Output Current A (0-pk)
2.8
2.8
Continuous Output Current A (0-pk)
2.8
Continuous Output Current A (0-pk)
2.8
Featu res
120V Doubler mode
Safe torque-off
Integrated AC line filter
Safe torque-off
Featu res
Safe torque-off
Featu res
Safe torque-off2097-V34PR5-LM 5.7
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Page 4
4 Kinetix 350 Single-axis EtherNet/IP Servo Drives
TIP

Before You Begin

Remove all packing material, wedges, and braces from within and around the components. After unpacking, check the item nameplate catalog number against the purchase order.
Parts List
The Kinetix 350 drive ships with the following:
General-purpose power input (IPD) header, back-up power (BP) header, shunt resistor
and DC bus (BC) header, motor power (MP) header, and safe-torque-off (STO) header
A ground clamp that also provides strain relief for motor power cable
These installation instructions, publication 2097-IN008
The connector kit for motor feedback (catalog number 2090-K2CK-D15M) is not provided. Replacement connector sets (catalog number 2097-CONN1) are also available.
See the Kinetix Motion Accessories Specifications Technical Data, publication GMC-TD004, for more information.

Safety Information

SHOCK HAZARD: Capacitors retain
charge for approximately 300 s after power is removed. Disconnect incoming power and wait at least 5 minutes before touching the drive. Failure to observe this precaution could result in severe bodily injury or loss of life.
WARNI NG: The opening of branch-circuit protective device can be an indication that a fault has been interrupted. To reduce the risk of fire or electric shock, parts that carry current and other components of the controller must be examined and replaced if damaged.
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
RISQUE DE CHOC: Les condensateurs restent sous charge pendant environ 300 secondes après une coupure de courant. Couper l’alimentation et patienter pendant au moins 5 minutes avant de toucher l’entraînement. Le non-respect de cette précaution peut entraîner des blessures corporelles graves ou la mort.
AVERTISSEMENT: Le déclenchement du dispositif de protection du circuit de dérivation peut être dû à une coupure qui résulte d’un courant de défaut. Pour limiter le risque d'incendie ou de choc électrique, examiner les pièces porteuses de courant et les autres éléments du contrôle ur et les rempla cer s'ils sont endommagés. En cas de grillage de l'élément traverse par le courant dans un relais de surcha rge, le relais to ut entier doit être remplacé.
Page 5
Kinetix 350 Single-axis EtherNet/IP Servo Drives 5
IMPORTANT
A
More clearance and different hole patterns are required for side mount and rear mount AC line filters. See the table and step 2 for more details.
More clearance is required depending on the other accessory items installed.
More clearance is required for the cable and wires that are connected to the top, front, and bottom of the drive.
An extra 150 mm (6.0 in.) is required when the drive is mounted near noise sensitive equipment or clean wire ways.
See page 6 for Kinetix 350 drive dimensions.
25 mm (1.0 in.) Clearance
for Airflow and Installation
25 mm (1.0 in.) Clearance
for Airflow and Installation
3 mm (0.12 in.)
Side Clearance
3 mm (0.12 in.) Side Clearance

Install the Kinetix 350 Drive

These procedures assume that you have prepared your panel, and understand how to bond your system. For installation instructions regarding equipment and accessories that are not included here, refer to the instructions that came with those products.
SHOCK HAZARD: To avoid hazard of electrical shock, mount and wire of the Kinetix 350 drive before you apply power. Once power is applied, connector terminals can have voltage present even when not in use.
ATTENTION: Plan the installation of your system so that you can cut, drill, tap, and weld with the system removed from the enclosure. Because the system is open-type construction, be careful to keep any metal debris from falling into it. Metal debris or other foreign matter can become lodged in the circuitry and result in damage to components.

Mount the Kinetix 350 Drive

Follow these steps to mount the drive.
1. Observe these clearance requirements when mounting the drive to the panel.
Mount the module in an upright position as shown. Do not mount the module on its side.
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Drive Cat. No.
2097-V31PR0-LM
2097-V31PR2-LM
2097-V32PR0-LM
2097-V32PR4-LM
2097-V33PR1-LM
2097-V33PR3-LM
2097-V33PR5-LM
2097-V33PR6-LM 230 (9.04)
2097-V34PR3-LM
2097-V34PR5-LM
2097-V34PR6-LM 230 (9.04)
(1) If you are using an AC line filter, add
50 mm (2 in.).
Dimensions A
mm (in.)
185 (7.29)
230 (9.04)2097-V32PR2-LM
185 (7.29)
185 (7.29)
(1)
(1)
Page 6
6 Kinetix 350 Single-axis EtherNet/IP Servo Drives
11.8
(0.46)
6.6
(0.26)
7.1
(0.28)
B
38.1 (1.5)
182
(7.18)
190
(7.50)
30.8
(1.21)
Ø 4.57 (0.18) 3x
A
238
(9.37)
61.0
(2.40)
9.7
(0.38)
5.0
(0.19)
Dimensions are in mm (in.).
2090-K2CK-D15M
Low-profile Connector Kit for Bulletin
2090 (flying-lead) Feedback Cable
More clearance below the connector kit is necessary to provide the recommended cable-bend radius.
2. Mount the Kinetix 350 drive to the cabinet subpanel with M4 (#6-32) steel machine screws torqued to 1.1 N•m (9.8 lb•in).
For catalog numbers 2097-V33PR1-LM, 2097-V33PR3-LM, 2097-V33PR5-LM, 2097-V34PR3-LM, and 2097-V34PR5-LM that use an AC line filter, refer to the AC Line Filter Installation Instructions, publication 2097-IN003
, for the subpanel
mounting hole pattern.
Kinetix 350 Drive Mounting Dimensions
Cat. No.
2097-V31PR0-LM 185.1 (7.29) 68.0 (2.68) 2097-V33PR3-LM 185.1 (7.29) 68.5 (2.70)
2097-V31PR2-LM 185.1 (7.29) 68.5 (2.70) 2097-V33PR5-LM 185.1 (7.29) 94.4 (3.72)
2097-V32PR0-LM 229.6 (9.04) 68.0 (2.68) 2097-V33PR6-LM 229.6 (9.04) 68.0 (2.68)
2097-V32PR2-LM 229.6 (9.04) 68.5 (2.70) 2097-V34PR3-LM 185.1 (7.29) 68.5 (2.70)
2097-V32PR4-LM 229.6 (9.04) 86.8 (3.42) 2097-V34PR5-LM 185.1 (7.29) 94.4 (3.72)
2097-V33PR1-LM 185.1 (7.29) 68.0 (2.68) 2097-V34PR6-LM 229.6 (9.04) 68.0 (2.68)
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Dimensions mm (in.)
AB A B
Cat. No.
Dimensions mm (in.)
Page 7
Kinetix 350 Single-axis EtherNet/IP Servo Drives 7
12
11
10
8
7
2
1
9
9
3 4 5
6
13
15
Top Vie w
(2097-V33PR5-LM
Kinetix 350 drive is shown)
Bottom View
(2097-V33PR5-LM
Kinetix 350 drive is shown)
14

Connector Data

To identify the Kinetix 350 drive features and indicators, use this illustration.
Kinetix 350 Drive Features and Indicators
Item Description
1 Data status indicator and diagnostic display
2Memory module socket
3Network status indicator
4 Module status indicator
5Axis status indicator
6 Ethernet communication port (Port 1)
7 I/O (IOD) connector
8 Motor feedback (MF) connector
9 Ground Lug
10 Shunt resistor and DC bus (BC) connector
11 Back-up power (BP) connector
12 Display control push buttons (3)
13 Mains (IPD) connector
14 Motor power (MP) connector
15 Safe torque-off (STO) connector
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Page 8
8 Kinetix 350 Single-axis EtherNet/IP Servo Drives
1
8
Kinetix 350 Drive Connectors
Designator Description Connector
IPD AC mains input power 4-position plug/header
PORT1 Ethernet communication port RJ45 Ethernet
IOD I/O SCSI 50-pin high-density connector
MF Motor feedback 15-pin high-density D-shell (male)
BP Back-up power 2-pin quick-connect terminal block
BC Shunt resistor and DC bus 7-pin quick-connect terminal block
MP Motor power 6-pin quick-connect terminal block
STO Safe torque-off (STO) terminal 6-pin quick-connect terminal block
Mains (IPD) Connector Pinout
IPD Designator Description Signal
L3 AC power in (3-phase models) L3
L2 AC power in L2
L1 AC power in L1
PE Protective earth (ground) PE
Pin Orientation for 8-pin Ethernet Communication Port (port 1)
Port 1 Pin Description Signal
1 Transmit port (+) data terminal + TX
2 Transmit port (-) data terminal - TX
3 Receive port (+) data te rminal + RX
4–
5–
6 Receive port (-) data terminal - RX
7–
8–
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Page 9
Kinetix 350 Single-axis EtherNet/IP Servo Drives 9
I/O (IOD) Connector Pinout
IOD Pin Description Signal
1…4 Reserved
5 Reserved
6 Reserved
7…25 Reserved (not used by Kinetix 350 drives)
26 ± Overtravel, enable and home common COM
27 Negative hardware overtravel NEG_OT
28 Positi ve hardware over travel POS_OT
29 Drive enable ENABLE
30 Home switch HOME_SW
31…35 R eserved
36 Registration common REG_COM
37…38 R eserved
39 Registration input REG
40…42 R eserved
43 Brake release positive BRAKE+
44 Brake release negative BRAKE-
45…50 R eserved
1
25
26
50
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Page 10
10 Kinetix 350 Single-axis EtherNet/IP Servo Drives
Pin 11
Pin 6
Pin 15
Pin 1
Pin 10 Pin 5
ATTENTION: To avoid damage to components, determine which power supply your encoder requires and connect encoder power to either the 5V or 9V supply, but not both.
Motor Feedback (MF) Connector Pinout
MF Pin Description
1 Sine differential input+
2 Sine differential input-
AM+ differential input+
AM- differential input-
3 Cosine differential input+
BM+ differential input+
4 Cosine differential input-
5 Data differential input +
BM- differential input-
Index pulse+
6Common ECOM
7 Encoder power (+9V) EPWR_9V
8 Single-ended 5V Hall effect commutation S3
9 Reserved
10 Data differential input -
Index pulse-
11 Motor thermal switch (normally closed)
12 Single-ended 5V Hall effect commutation S1
13 Single-ended 5V Hall effect commutation S2
14 Encoder power (+5V) EPWR_5V
15 Reserved
(1) D etermine which power supply your encoder requires and connect to only the specified supply. Do not make connections to both. (2) Not applicable unless motor has integrated thermal protect ion.
(1)
Signal
SIN+ AM+
SIN­AM-
COS+ BM+
COS­BM-
DATA+ IM+
(1)
DATA­IM-
(2)
TS
(1)
Control Power Back-up (BP) Pinout
BP Designator Description Signal
+24V Positive 24V DC +24V DC
-24V 24V DC power supply return Return
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Page 11
Kinetix 350 Single-axis EtherNet/IP Servo Drives 11
IMPORTANT
Shunt Resistor and DC Bus (BC) Pinout
BC Designator Description Signal
+
++
SH Shunt resistor SH
––
Positive DC bus and shunt resistor
Negative DC bus
+
Motor Power (MP) Pinout
MP Designator Description Signal
PE Protective earth (ground) PE
W Motor power out W
V Motor power out V
U Motor power out U
Safe Torque-off (STO) Pinout
STO Pin Description Signal
1 +24V DC output from the drive +24V DC control
2 +24V DC output common Control COM
3 Safety status Safety Status
4 Safety input 1 (+24V DC to enable) Safety Input 1
5Safety common Safety COM
6 Safety input 2 (+24V DC to enable) Safety Input 2
The Kinetix 350 drive ships with safe torque-off enabled. To obtain motion, connect safe torque-off inputs to a safety circuit, or install motion-allowed jumpers. See the Kinetix 350 Single-axis EtherNet/IP Servo Drive User Manual, publication 2097-UM002

Power Wiring Requirements

Wire must be copper with 75 °C (167 °F) minimum rating. The phase connections of main AC power are arbitrary and earth-ground connection is required for safe and proper operation.
The National Electrical Code and local electrical codes take precedence over the values and methods provided.
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
, for details.
Page 12
12 Kinetix 350 Single-axis EtherNet/IP Servo Drives
Kinetix 350 Drive Power-wiring Requirements
Torq ue Value
N•m (lb•in)
0.56…0.79 (5.0…7.0)
Cat. No. Description
2097-V31PR0-LM 2097-V32PR0-LM 2097-V32PR2-LM 2097-V33PR1-LM 2097-V33PR3-LM 2097-V34PR3-LM 2097-V34PR5-LM 2097-V34PR6-LM
2097-V32PR4-LM 2097-V33PR5-LM
Mains input power
2097-V31PR2-LM 2097-V33PR6-LM
2097-V31PR0-LM 2097-V32PR0-LM 2097-V32PR2-LM 2097-V32PR4-LM 2097-V33PR1-LM 2097-V33PR3-LM 2097-V33PR5-LM 2097-V34PR3-LM 2097-V34PR5-LM 2097-V34PR6-LM 2097-V31PR2-LM
Motor power
Terminals Recommended
Pin Signal
L3 L2 L1 PE
PE W V U
Strip
Wire Size
2
mm
(AWG)
Length
mm (in.)
2.5 (14) 7 (0.28) 0.5 (4.5)
4.0 (12) 7 (0.28) 0.5 (4.5)
6.0 (10) 7 (0.28)
2.5 (14) 7 (0.28) 0.5 (4.5)
2097-V33PR6-LM 4.0 (12) 7 (0.28) 0.5 (4.5)
2097-V31PR0-LM 2097-V32PR0-LM 2097-V32PR2-LM 2097-V32PR4-LM 2097-V33PR1-LM 2097-V33PR3-LM 2097-V33PR5-LM 2097-V34PR3-LM 2097-V34PR5-LM 2097-V34PR6-LM 2097-V31PR2-LM
Shunt resistor and DC bus
+ +
(1)
SH – –
2.5 (14) 7 (0.28) 0.5 (4.5)
2097-V33PR6-LM 4.0 (12) 7 (0.28) 0.5 (4.5)
(2) (2)
+24V DC Return
+24V DC Control Contro l COM
Safety Status Safety Input 1 Safety COM Safety Input 2
1.5 (16) 6 (0.25) 0.5 (4.5)
2097-V3xPRx-LM Control back-up power
2097-V3xPRx-LM Safe torque-off
(1) Use only for shunt resistor connection. (2) Use only for bypassing the STO circuit.
STO-1 STO-2 STO-3 STO-4 STO-5 STO-6
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Page 13
Kinetix 350 Single-axis EtherNet/IP Servo Drives 13
Bonded Cabinet Ground Bus
Ground Grid or Power Distribution Ground
Braided
Ground Strap
Ground Stud
ATTENTION: To avoid personal injury and equipment damage, verify the following:
Installation complies with specifications regarding wire types, conductor sizes, branch circuit
protection, and disconnect devices. The National Electrical Code (NEC) and local codes outline provisions for safely installing electrical equipment.
Motor power connectors are used only for connection purposes. Do not use motor power
connectors to turn the unit on and off.
Shielded power cables are grounded to prevent potentially high voltages on the shield.

Ground Your Kinetix 350 Drive to the Subpanel

If the Kinetix 350 drive is mounted on a painted subpanel, ground to a bonded cabinet ground bus with a braided ground strap or 4.0 mm2 (12 AWG) solid-copper wire, 100 mm (3.9 in.) long.
Connect the Braided Ground Strap
For dimensions, see Kinetix 350 Drive Mounting Dimensions on page 6.
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Page 14
14 Kinetix 350 Single-axis EtherNet/IP Servo Drives
50…75 (2…3)
50…75 (2…3)
34.0
(1.34)
25
(1.0)
12.7 (0.50)
If panel is painted, remove paint to provide metal-to-metal contact.
Motor Power Ground Clamp
Dimensions are in mm (in.).

Kinetix 350 Drive Motor-power Wire Shielding

A motor-power ground clamp and two #6-32 x 1 screws are supplied with the Kinetix 350 drive.
Install the supplied motor-power ground clamp within 50…75 mm (2…3 in.) of the drive by using the two #6-32 x 1 screws.
Motor Power Ground Clamp Installation

Motor Overload Protection

This servo drive uses solid-state motor overload protection that operates in accordance with UL 508C. Motor overload protection algorithms (thermal memory) that can predict actual motor temperature are based on operating conditions as long as control power is continuously applied. However, when control power is removed, thermal memory is not retained.
This drive also provides an input for an external temperature sensor or thermistor device, which is embedded in the motor, to support the UL requirement for motor overload protection.
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Page 15
Kinetix 350 Single-axis EtherNet/IP Servo Drives 15
The drive supports some motors that do not contain temperature sensors or thermistors; therefore, motor overload protection against excessive consecutive motor overloads followed by power-up is not supported.
This servo drive meets the following UL 508C requirements for solid-state overload protection.
Motor Overload Protection Trip Point Value
Ultimately 100% overload
Withi n 8 minut es 200% overloa d
Withi n 20 seco nds 600% overloa d
ATT EN TI ON : Avoid overheat damage to your motor from excessive and successive motor overload faults by following the motor and drive-combination wiring diagram that is provided in the user manual.
See your servo drive user manual for the interconnect diagram that illustrates the wiring between your motor and drive.

Circuit Breaker/Fuse Selection

The Kinetix 350 drives use internal solid-state motor short-circuit protection. When protected by suitable branch circuit protection, the drives are rated for use on a circuit that can deliver up to 100,000 A.
See Kinetix 350 Drive Power Specifications in Kinetix Servo Drives Specifications Technical Data, publication GMC-TD003 Kinetix 350 drive.
See Circuit Breaker/Fuse Specifications breakers and fuses.
for input current and inrush current specifications for your
on page 16 and page 17 for recommended circuit
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Page 16
16 Kinetix 350 Single-axis EtherNet/IP Servo Drives

Circuit Breaker/Fuse Specifications

These fuses and Allen-Bradley circuit breakers are recommended for use with 2097-VxxPRx-LM drives.
Input Power Circuit-protection Specifications
Cat. No.
2097-V31PR0-LM
2097-V31PR2-LM
2097-V32PR0-LM
2097-V32PR2-LM KTK-R-20 (20A) 1489-M1C200 140M-D8E-C20
2097-V32PR4-LM KTK-R-30 (30A) 1489-M1C300 140M-F8E-C32
2097-V33PR1-LM
2097-V33PR3-LM
2097-V33PR5-LM
2097-V33PR6-LM
2097-V34PR3-LM
2097-V34PR5-LM KTK-R-10 (10A) 1489-M3C100 140M-C2E-C10
2097-V34PR6-LM KTK-R-20 (20A) 1489-M3C200 140M-D8E-C20
(1) Bulletin 1492 and 1489 circuit protection devices have lower short-circuit current ratings than Bulletin 140M devices.
See http://ab.rockwellautomation.com/allenbradley/productdirectory.page? ratings.
(2) For UL applications, Bulletin 140M devices are applied as self-protected combination motor controllers.
Drive Volta ge
120V
120/240V Single-phase KTK-R-10 (10A) 1489-M1C100 140M-C2E-C10
120V
120/240V Single-phase KTK-R-20 (20A) 1489-M1C200 140M-D8E-C20
240V Single-phase
120/240V Single-phase KTK-R-20 (20A) 1489-M1C200 140M-D8E-C20
240V Three-phase KTK-R-15 (15A) 1489-M3C150 140M-D8E-C16
120/240V Single-phase KTK-R-20 (20A) 1489-M1C200 140M-D8E-C20
240V Three-phase KTK-R-15 (15A) 1489-M3C150 140M-D8E-C16
120/240V Single-phase KTK-R-30 (30A) 1489-M1C300 140M-F8E-C32
240V Three-phase KTK-R-20 (20A) 1489-M3C200 140M-D8E-C20
120/240V Single-phase
240V Three-phase KTK-R-30 (30A) 1489-M3C300
480V Three-phase
Phase
Single-phase (voltage doubler)
Single-phase (voltage doubler)
Fuses (Bussmann) Cat. No.
KTK-R-20 (20A) 1489-M1C200 140M-D8E-C20
KTK-R-30 (30A) 1489-M1C300 140M-F8E-C32
KTK-R-20 (20A) 1489-M1C150 140M-D8E-C16
LPJ-40SP (40A) Class J
KTK-R-10 (10A) 1489-M3C100 140M-C2E-C10
Miniature CB Cat. No.
N/A
for product literature with specific short-circuit
Motor Protection CB,
(1)
Self-protected CMC Cat. No.
140M-F8E-C32
(1) (2)
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Page 17
Kinetix 350 Single-axis EtherNet/IP Servo Drives 17
Fuse and Circuit Breaker Specifications IEC (non-UL) Applications
Drive Cat. No.
2097-V31PR0-LM
2097-V31PR2-LM
2097-V32PR0-LM
2097-V32PR2-LM 148 9-M1C200 1492-SPM1D200 140M-D 8E-C20
2097-V32PR4-LM 148 9-M1C300 1492-SPM1D320 140M-F8 E-C32
2097-V33PR1-LM
2097-V33PR3-LM
2097-V33PR5-LM
2097-V33PR6-LM
2097-V34PR3-LM
2097-V34PR5-LM 148 9-M3C100 1492-SPM3D100 140M- C2E-C10
2097-V34PR6-LM 148 9-M3C200 1492-SPM3D200 140M-D 8E-C20
Drive Voltage
120V
120/240V Single -phase 1489-M1C100 1492-SPM1D100 140M-C2E-C10
120V
120/240V Single -phase 1489-M1C200 1492-SPM1D200 140M-D8E-C20
240V Single-phase
120/240V Single -phase 1489-M1C200 1492-SPM1D200 140M-D8E-C20
240V Three-phase 1489-M3C150 1492-SP M3D150 140M-D8E-C16
120/240V Single -phase 1489-M1C200 1492-SPM1D200 140M-D8E-C20
240V Three-phase 1489-M3C150 1492-SP M3D150 140M-D8E-C16
120/240V Single -phase 1489-M1C300 1492-SPM1D300 140M-F8E-C32
240V Three-phase 1489-M3C200 1492-SP M3D200 140M-D8E-C20
120/240V Single -phase N/A N/A
240V Three-phase 1489-M3C300 1492-SP M3D300
480V Three-phase
Phase
Single-phase (voltage doubler)
Single-phase (voltage doubler)
Miniature CB
1489-M1C200 1492-SP M1D200 140M-D8E-C20
1489-M1C300 1492-SP M1D300 140M-F8E-C32
1489-M1C150 1492-SP M1D150 140M-D8E-C16
1489-M3C100 1492-SP M3D100 140M-C2E-C10
Cat. No.
(1)
Motor Protection CB Cat. No.
140M-F8E-C32
(1)
(1) Bulletin 1492 and 1489 circuit protection devices have lower short-circuit current ratings than Bulletin 140M devices.
See http://ab.rockwellautomation.com/allenbradley/productdirectory.page? ratings.
for product literature with specific short-circuit
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Page 18
18 Kinetix 350 Single-axis EtherNet/IP Servo Drives

Additional Resources

These documents contain more information that concerns related products from Rockwell Automation.
Resource Description
Kinetix 350 Single-axis EtherNet/IP Servo D rives User Manual, publication 2097-UM002
Kinetix 300 Shunt Resistor Installation Instructions, publication
2097-IN002
Kinetix 300 AC Line Filter Installation Instructions, publication
2097-IN003
Kinetix 300 I/O Terminal Expansion Block Installation Instructions, publication 2097-IN005
Kinetix 300 Memory Module Installation Instructions, publication 2097-IN007
Kinetix 300 Memory Module Programmer Quick Star t, publication 2097-QS001
Kinetix Servo Drives Specifications Technical Data, publication GMC-TD003
Kinetix Motion Accessories Specifications Technical Data, publication GMC-TD004
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other
Provides information on how to install, configure, start up, and troubleshoot your Kinetix 350 servo drive system.
Provides information on how to install and wire Kinetix 300 shunt resistors.
Provides information on how to install and wire the Kinetix 300 AC line filter.
Provides information on how to install and wire the Kinetix 300 I/O terminal expansion block.
Provides information on how to install the Kinetix 300 memory module.
Provides information on the use of the memory module programmer to duplicate the memory module.
Provides product specifications for Kinetix Integrated Motion over EtherNet/IP, Integrated Motion over SERCOS interface, EtherNet/IP network, and component servo drive families.
Provides product specifications for Bulletin 2090 motor and interface cables, low-profile connector kits, drive power components, and other servo drive accessory items.
Provides general guidelines for installing a Rockwell Automation industrial system.
certification details.
You can view or download publications at http://www.rockwellautomation.com/literature. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Page 19
Notes:
Kinetix 350 Single-axis EtherNet/IP Servo Drives 19
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Page 20
Rockwell Automation Support
(13496814)
Rockwell Automation provides tec hnical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support service packs. You can also visit our Support Center at https://rockwellautomation.custhelp.com/ and forums, technical information, FAQs, and to sign up for product notification updates.
In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/services/online-phone
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada
Use the Worl dwide Locato r
http://www.rockwellautomation.com/rockwellautomation/support/overview.page
local Rockwell Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
you can find technical and application notes, sample code, and links to software
for software updates, support chats
at
, or contact your
.
United States
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
Allen-Bradley, CompactLogix, ControlLogix, Kinetix, Rockwell Sof tware, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Publication 2097-IN008F-EN-P - September 2015
Supersedes Publication 2097-IN008E-EN-P - December 2014 Copyright © 2015 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.