Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Connected Components Workbench, Control Tower, Guardmaster, GuardShield, Lifeline, PHOTOSWITCH, PowerFlex, Rockwell Software, SensaGuard, Trojan, and Zero-Force Touch Buttons are
trademarks of Rockwe ll Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Page 3
Preface
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
Product Certifications website, http://www.ab.com
Provides general guidelines for installing a Rockwell
Automation industrial system.
Provides declarations of conformity, certificates, and
other certification details.
You can view or download publications at
http:/www.rockwellautomation.com/literature/
. To order paper copies of
technical documentation, contact your local Allen-Bradley® distributor or
Rockwell Automation sales representative.
Rockwell Automation Publication 440C-WD001A-EN-P - November 20143
Page 4
Preface
Notes:
4Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 5
Preface
Cat 1 Stop with Guardlocking
Interlock (TLS-ZR or 440G-LZ)
Cat 1 Stop with GuardShield Light
Curtain, T-15 Interlock, E-Stop, and
PowerFlex 525
Rockwell Automation Publication 440C-WD001A-EN-P - November 20143
Page 8
Table of Contents
Notes:
4Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 9
Chapter 1
Cat 1 Stop with Guardlocking Interlock
(TLS-ZR or 440G-LZ)
This example application shows how to configure the CR30 for a Guardlocking
application that requires a Category 1 stop function.
A TLS-ZR guardlocking interlock, which has OSSD outputs, locks a guard to
prevent full body access to the hazard. A PowerFlex® 525 is controlling a motor
that is considered the hazard. A selector switch requests access to the hazard area.
A push button locks access to the hazard. The CR30 performs the logic that
monitors the interlock and the drive, and allows access to the hazard under safe
conditions.
For partial body access, the 440G-LZ can be substituted for the TLS-ZR.
Product Overview
Figure 1 - Overview
Rockwell Automation Publication 440C-WD001A-EN-P - November 20145
Page 10
Chapter 1Cat 1 Stop with Guardlocking Interlock (TLS-ZR or 440G-LZ)
05
CR30
02010003 04
A11520 21160618A2
07190810 11
12 13 14
09
17
+24 VDC
24V DC Com
Reset
Red
Pink
Green
White
Blue
Grey
Yellow
Brown
Safety
Gate
Safety
TLS-ZR
440G-TZS21UPRH
889D-F8AC-2
440C-CR30-22BBB
Gate
Unlocked
Gate
Lock/
Unlock
Gate control
power supply
Gate control
circuit
M
4 Gnd
S1
S2
1 Stop
L1 L2 L3
PowerFlex
525
2 Start
R5
R6
RTS
UWV
Schematic
Figure 2 - Schematic
PowerFlex PF525 Settings
Ta b l e 1 shows a list of some of the parameter settings for this application. The list
is not a complete list of the parameters for the PF525. You may set many other
parameters to make this application successful.
Table 1 - Parameter Settings
ParameterNameValueUnit/Description
P042Decel Time3Seconds
P045Stop Mode0Stop and Clear Fault
P046Start Source2Digital Input Terminal Block
P047Speed Reference 11Drive Pot
T081Relay 2 2Motor Running
6Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
T105Safety Open En1Fault Disable
Motor is receiving power from the drive.
Page 11
Cat 1 Stop with Guardlocking Interlock (TLS-ZR or 440G-LZ)Chapter 1
Connected Components
Workbench™
Figure 3 - Connected Components Workbench Example
Circuit Status
Operational Sequence
The gate switch is closed and locked. The safety signals to the PF2525 drive are
off, and the drive is disabled. The motor is off.
Table 2 -
Action TakenResults
1. Momentarily press the reset button.The safety outputs at terminal 17, 18 and 19 turn ON.
2. Press the drive Start button.The motor turns ON. The drive can now be used for normal
3. Rotate the Unlock request to the Unlock (closed)
position.
4. Open the gate switch.The operator can access the hazard area.
5. Close the gate.
6. Rotate the Unlock switch to the locked (open) position. This locks the gate and the safety system is ready for reset.
production processes.
The speed of the motor is controlled by the Drive Pot,
located on the front of the PF525.
The power is immediately removed from terminals 17,
and the drive executes a ramp to stop command in 3
seconds (P042 is configured for 3s).
After a 5 second delay, the gate switch is unlocked and the
safety outputs to the drive open.
Go to Step 1.
Rockwell Automation Publication 440C-WD001A-EN-P - November 20147
Page 12
Chapter 1Cat 1 Stop with Guardlocking Interlock (TLS-ZR or 440G-LZ)
Metal, maintained, black, standard knob, standard orientation,
1 N.O. contact block, standard pack
5800FM-F611MX10800F Push Button
Metal, flush, blue, R, metal latch mount, 1 N.O. contact, 0 N.C.
contacts, standard, standard pack
624B-V2P5A104AA-ND-P3PowerFlex 525 Pre-engineered FasTrac, with Embedded
EtherNet/IP™ and Safety
120VAC, 1-phase, 0.5 Hp, 0.4 kW normal duty; 0.5 Hp, 0.4 kW heavy
duty, Type 1 / IP20, no filter, without bypass, without reactor, motor
circuit protector (-P3)
7800FM-F301800F Push Button
Metal, flush, green, START, standard pack
8800FM-E402800F Push Button
Metal, extended, red, STOP, standard pack
1
1
1
1
1
1
1
1
1
Safety Rating
The safety function that is performed by the guard locking interlock meets the
safety performance requirements of SIL CL2 per IEC 61061:2012 and SIL 2 per
IEC 61508:2005 and has a Category 3 structure that can be used in systems
requiring Performance Levels up to PLd per ISO 13849-1: 2006. The circuit
executes a Category 1 stop.
8Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 13
Chapter 2
Cat 1 Stop with GuardShield™ Light Curtain, T-15
Interlock, E-Stop, and PowerFlex 525
This example application shows how to configure the CR30 for a guarding
application that requires a Category 1 stop function.
A light curtain is used where an operator frequently accesses the hazard area. A
mechanical tongue interlock switch is mounted on a gate where infrequent access
to the hazard. Both the light curtain and gate are located far enough away from
the hazard so the operator cannot reach the hazard until it has reached a safe state.
An E-stop button is also available at the control panel. Any of the three devices
must cause the machine to go to a safe OFF state.
Product Overview
Figure 4 - Overview
Rockwell Automation Publication 440C-WD001A-EN-P - November 20149
Page 14
Chapter 2Cat 1 Stop with GuardShield™ Light Curtain, T-15 Interlock, E-Stop, and PowerFlex 525
05
CR30
02010003 04
A11520 21160618A2
07190810 11
12 13 14
09
17
+24 VDC
Gate control
power supply
Gate control
circuit
M
4 Gnd
S1
S2
1 Stop
L1 L2 L3
PowerFlex
525
2 Start
RTS
UWV
24V Com
1
2
6
5
3
7
3
Pink
Receiver
Brown
Brown
Transmitter
Grey
Blue
Green
Blue
111221
22
Schematic
Figure 5 - Schematic
PowerFlex PF525 Settings
Ta b l e 4 shows a list of some of the parameter settings for this application. The list
is not a complete list of the parameters for the PF525. You may set many other
parameters to make this application successful.
Table 4 - Parameter Settings
ParameterNameValueUnit/Description
P042Decel Time1Seconds
P045Stop Mode0Stop and Clear Fault
P046Start Source2Digital Input Terminal Block
P047Speed Reference 1 1Drive Pot
T081Relay 2 2Motor Running
Motor is receiving power from the drive.
T105Safety Fault En0Fault Enable
10Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 15
Cat 1 Stop with GuardShield™ Light Curtain, T-15 Interlock, E-Stop, and PowerFlex 525Chapter 2
Connected Components
Workbench
Figure 6 - Connected Components Workbench Example
Circuit Status
Operational Sequence
The light curtain is clear. The gate switch is closed. The E-stop is reset. The
CR30 safety outputs at terminal 17, 18, and 19 are ON. The PF525 shows an
F059 fault. The motor is off.
Table 5 - Operational Sequence
Action TakenResults
1. Press the drive Stop button.The F059 Fault on the PF25 is cleared. The motor is ready
2. Press the drive Start button.The motor turns ON. The drive can now be used for normal
3. Do any of the following actions:
– Block the light curtain,
– Open the gate switch, or
– Press the E-stop.
4. Do the opposite action from Step 2:
– Clear the light curtain,
– Close the gate switch, or
– Release the E-stop.
to run.
Normally, the motor would be stopped by the machine
control system, which is not shown in the schematic.
production processes.
The speed of the motor is controlled by the Drive Pot,
located on the front of the PF525.
The power is immediately removed from terminals 17,
and the drive executes a ramp to stop command in 1
seconds (P042 is configured for 1s). One second later,
terminals 18 and 19 turn off, and the PF525 executes a
safe torque off function. The PF525 shows an F059 fault in
its display.
The CR30 safety outputs at terminal 17, 18 and 19 are ON.
The PF525 still shows an F059 fault. The motor remains
off.
Go to Step 1.
Rockwell Automation Publication 440C-WD001A-EN-P - November 201411
Page 16
Chapter 2Cat 1 Stop with GuardShield™ Light Curtain, T-15 Interlock, E-Stop, and PowerFlex 525
Contacts (safety and aux): 2 N.C., BBM
Preference: N/A
Actuator: Fully-flex
Model Type: GD2 front entry
Conduit Entry: 1/2in NPT conduit
4800FM-LMT64800F Illuminated Mushroom Operators
Illuminated, twis t-to-release, 60 mm, round metal (Type 4/13, IP66),
red, standard pack (Qty. 1)
5800F-X01L22.5 mm Push Button
No latch, screw contact block, 1 N.C.L.B.
6800F-ALMMetal Latch1
7800F-X01S22.5 mm PB
No latch, screw contact block, 1 N.C. self-monitoring
8800F-N3RIntegrated LED
Latch mount, 24V AC/DC, red LED
9800F-X1022.5 mm Push Button
No latch, screw contact block, 1 N.O.
10800FM-F301800F Push Button
Metal, flush, green, START, standard pack (Qty. 1)
11800FM-E402800F Push Button
Metal, extended, red, STOP, standard pack (Qty. 1)
1224B-V2P5A104AA-ND-P3PowerFlex 525 Pre-engineered FasTrac, with Embedded
EtherNet/IP and Safety
120V AC, 1-phase, 0.5 Hp, 0.4 kW normal duty; 0.5 Hp, 0.4 kW heavy
duty, Type 1 / IP20, no filter, without bypass, without reactor, motor
circuit protector (-P3)
1
1
1
1
1
1
1
1
1
1
1
1
1
Safety Rating
The safety function that is initiated by the light curtain can meet up to Cat 3 PLd
per IS013849-1, SIL CL2 per IEC 62061, and SIL 2 per IEC 61508. It does not
achieve Cat 4 PLe due to the rating of the PF5252 drive
The safety function that is initiated by the gate interlock switch can meet up to
Cat 3 PLd per IS013849-1, SIL CL2 per IEC 62061, and SIL 2 per IEC 61508
when using fault exclusion as described in ISO 14119.
The safety function that is initiated by the E-stop can meet up to Cat 3 PLd per
IS013849-1, SIL CL2 per IEC 62061, and SIL 2 per IEC 61508.
12Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 17
Chapter 3
Safety Mats - Two Zones
This application demonstrates two zones using safety mats and E-stop push
buttons. Each zone is controlled by a safety mat and an E-stop push button. In
this example, a sequential manufacturing process has two zones. If an operator
enters the first zone, that zone stops while the second zone continues to function.
If an operator enters zone 2, then both zones 1 and 2 must stop. An indicator
lamp shows which zone is not operating, and the user is allowed to enter for
normal production type operations.
The safety mats for each zone can be single mats or multiple mats that are
connected in series. The safety mats must be connected to pulse tested outputs to
operate properly with the CR30. In this example, the Zone 1 mats use pulses
from 12 and 13 and Zone 2 uses pulses from 16 and 17.
Product Overview
The two E-stop buttons use the same test pulses, from terminals 14 and 15 - this
arrangement is preferred. Alternatively, the E-stops can be powered directly by
the 24V DC supply, but powering directly from 24V does not provide cross
channel fault detection.
Note: The outputs of the CR30 are driving 100S contactors. Due to the
inrush current limitations of the CR30, the CR30 can only switch the
100S-C09EJ contactors. The CR30 cannot switch the C43EJ contactors.
Figure 7 - Overview
Rockwell Automation Publication 440C-WD001A-EN-P - November 201413
Page 18
Chapter 3Safety Mats - Two Zones
05
CR30
02010003 04
A11520 21160618A2
07190810 11
12 13 14
09
17
K2
K1
K4
K3
440C-CR30-22BBB
24V Com
+ 24V DC
Mat
E-StopE-Stop
Mat
K1 K2 K3 K4
K2
K1
K4
K3
Reset
Zone 1
Zone 1 Zone 2
Zone 2
Zone 1
O
Zone 2
O
Reset
COMI-02 I-03
COMI-00 I-01
2080-IQ4OB4
-24DC O-02 O-03
+24DC O-00 O-01
L1 L2 L3L1 L2 L3
M1M2
Schematic
Figure 8 - Schematic
14Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 19
Safety Mats - Two ZonesChapter 3
Connected Components
Workbench
Figure 9 - Connected Components Workbench Example
Rockwell Automation Publication 440C-WD001A-EN-P - November 201415
Page 20
Chapter 3Safety Mats - Two Zones
Circuit Status
Operational Sequence
Example Bill of Materials
No presence is sensed on both mat systems. All four contactors are off, and both
motors (hazards) are off. The system is ready for reset.
Press Reset 1 to enable the start of Zone 1. Press Reset to enable the start of
Zone2.
To gain access to either zone, the operator steps on the mat or presses the E-stop
button. Both devices initiate an immediate stop command to its associated
hazard. An indicator at Plug-in terminal P200 and P201 show when someone or
something is on the mat or if the E-stop is pressed for that zone.
If the operator enters Zone 1, then only Zone 1 stops and Zone 2 continues to
run. If the operator enters Zone 2, then both zones stop.
After leaving the Zone 2, the operator must press the reset button to enable the
restart of Zone 2. After leaving Zone 1, the operator must press the reset buttons
for both Zone 1 and 2 to enable the restart the machine.
Table 7 - Bill of Materials
ItemProductDescriptionQty
12080-IQ4OB44-ch Digital Input/Output Combination Module1
Twist-to-release, 40 mm, round metal (Type 4/13, IP66), red,
standard pack (Qty. 1)
4.1800F-ALMMetal Latch2
4.2800F-X01S22.5 mm PB No Latch
Screw contact block, 1 N.C. self-monitoring
5440F-M2036BYNNSafety Mat
Yellow, 1000 x 1800 mm, two 4.5 m (15 ft) 2-wire cables, exit out “B”
corners, no trim, no controller
6440F-T2036Trim Kit
Standard trim, 1000 x 1800 mm
7100S-C09EJ14BCMCS 100S-C Safety Contactor
9A, 24V DC (with elec. coil), bifurated contact
8800FM-P7MN3W800F Pilot Light
Rd. metal (IP66, 4/13, IP66), clear, standard pack (Qty. 1)
1
2
2
4
2
2
4
2
Safety Rating
The safety function that is initiated by the safety mats can meet up to Cat 3 PLd
per IS013849-1, SIL CL2 per IEC 62061, and SIL 2 per IEC 61508.
The safety function that is initiated by the E-stops can meet up to Cat 4, PLe and
SIL3 per IEC61508 and SIL CL3 per IEC 62061.
16Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 21
Chapter 4
Enabling Switch (GripSwitch) with Jog Function
The GripSwitch is a hold-to-run enabling device. While holding the GripSwitch
in the center (enabled) position, the operator then presses and holds the jog
switch to operate the PowerFlex drive for a specified duration.
This example requires a two-position selector switch. The position of the selector
switch determines whether the gate switch is used or the GripSwitch is used.
This application has four distinct safety-related functions:
1. Interlock 'Logic' Drive
2. Enabling Switch 'Logic' Drive
3. Selector switch 'Logic' Drive
Product Overview
4. Jog Switch 'Logic' Drive
Figure 10 - Overview
Rockwell Automation Publication 440C-WD001A-EN-P - November 201417
Page 22
Chapter 4Enabling Switch (GripSwitch) with Jog Function
05
CR30
02010003 04
A11520 21160618A2
07190810 11
12 13 14
09
17
+24 VDC
Gate control
power supply
Gate control
circuit
M
4 Gnd
S1
S2
1 Stop
L1 L2 L3
PowerFlex
525
2 Start
8 Jog
7 Clear Fault
RTS
UWV
24V Com
Brown
Blue
White
Red
Yellow
SensaGuard
Integrated
Latch
Grey
GripSwitch
Gate Switch
Pink
Jog
Gate
Open
GripSwitch
12
7
8
34
Schematic
Figure 11 - Schematic
18Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 23
Enabling Switch (GripSwitch) with Jog FunctionChapter 4
Connected Components
Workbench
Figure 12 - Connected Components Workbench Example
Circuit Status
Logic Level B1 block is an XOR, rather than a simple OR. The Selector switch
chooses either the gate interlock switch or GripSwitch. If a short circuit to 24V
occurs on terminal 5, and the gate closed behind the operator, the GripSwitch
would be bypassed if the simple OR block were used. To avoid a potential bypass
situation, an XOR block is used. The SOF1 output block turns off if both the
gate switch and GripSwitch were both on.
The SOF2 jog output is only enabled when the GripSwitch is both selected and
enabled. Therefore, when the Selector switch is set to the gate switch, the jog
button is disabled. The jog parameter is set to 50 (50 x 50 ms), which is
2.5seconds. When the jog switch is held down, the PF525 jogs the motor for 2.5
seconds. If the jog button is released sooner than 2.5 seconds, the motor stops
immediately.
The safety gate is closed. The selector switch is set to Gate Switch. The
GripSwitch is off and the Jog switch is off. The PF525 is off.
Rockwell Automation Publication 440C-WD001A-EN-P - November 201419
Page 24
Chapter 4Enabling Switch (GripSwitch) with Jog Function
Operational Sequence
Example Bill of Materials
Table 8 - Operational Sequence
Action TakenResults
1. Press the drive Stop button.This clears faults in the drive. Fault F059 may be present,
due to its safety inputs being off.
2. Press the drive Start button.The motor turns ON. The drive can now be used for normal
production processes. Normally, the motor would be
stopped by the machine control system.
3. Rotate the Selector switch to GripSwitch.The operator must hold the GripSwitch in the center
position to prevent the drive from going to a fault
condition.
4. Open the guard (opens the gate interlock switch).The operator can access the hazard area.
5. Grab the GripSwitch and squeeze to the center ON
position.
6. Momentarily press the jog button.This clears the F059 fault on the PpwerFlex 525.
7. Press and hold the jog button.The PF525 turns on the motor for 2.5 seconds.
To get the PF525 to jog again, the operator can release the
jog button and then depress it again.
8. Set the selector switch to Gate Switch.
9. Press the Stop button.This clears the F059 fault on the PF525.
10.The PF525 is ready for normal producti on operations.
Table 9 - Bill of Materials
ItemProductDescriptionQty
12080-IQ4OB44-ch Digital Input/Output Combination Module1
Twist-to-release, 40 mm, round metal (Type 4/13, IP66), red,
standard pack (Qty. 1)
4.1800F-ALMMetal Latch
4.2800F-X01S22.5 mm Push Button
No latch, screw contact block, 1 N.C. self-monitoring
5440F-M2036BYNNSafety Mat
Yellow, 1000 x 1800 mm, two 4.5 m (15 ft) 2-wire cables, exit out “B”
corners, no trim, no controller
6440F-T2036Trim Kit
Standard trim, 1000 x 1800 mm
7100S-C09EJ14BCMCS 100S-C Safety Contactor
9 A, 24V DC (with elec. coil), bifurated contact
8800FM-P7MN3W800F Pilot Light
Rd. metal (IP66, 4/13, IP66), clear, standard pack (Qty. 1)
20Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 25
Enabling Switch (GripSwitch) with Jog FunctionChapter 4
Safety Rating
This application has four distinct safety-related functions:
1. Interlock -> Logic -> Drive
The safety function that is performed by the gate switch can meet the
requirements up to Cat 3 PLd per ISO13849-1, SIL CL2 per IEC62061,
and SIL 2 per IEC61508.
2. Enabling Switch -> Logic -> Drive
The safety function that is performed by the enabling switch can meet the
requirements up to Cat 3 PLd per ISO13849-1, SIL CL2 per IEC62061,
and SIL 2 per IEC61508.
3. Selector switch -> Logic -> Drive
The safety function that is performed by the enabling switch can meet the
requirements up to Cat 3 PLd per ISO13849-1, SIL CL2 per IEC62061,
and SIL 2 per IEC61508.
4. Jog Switch-> Logic -> Drive
The safety function that is performed by the jog switch can meet the
requirements up to Cat 2 PLc per ISO13849-1, SIL CL1 per IEC62061,
and SIL 1 per IEC61508.
Rockwell Automation Publication 440C-WD001A-EN-P - November 201421
Page 26
Chapter 4Enabling Switch (GripSwitch) with Jog Function
Notes:
22Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 27
Chapter 5
MS1 MS2
LC
Muting Lamp
Material
Conveyor Flow
Hazard AreaNon-hazard Area
Muting 2-Sensor L-Type Unidirectional
The CR30 has a function block that supports 2-sensor L-type muting. With this
function block, the material can only move in one direction: from the hazard area
to the non-hazard area. The two muting sensors are located within the hazard
area, and the material must be large enough to block both sensors and the light
curtain. The function block contains timing parameters that allow you to
accommodate a wide range of operating speeds.
Product Overview
Machine Layout
Figure 13 - Overview
The material can only flow from the hazard area to the non-hazard area. The
material must be large enough to concurrently block muting sensor 1, muting
sensor 2, and the light curtain.
Figure 14 - Machine Layout
Rockwell Automation Publication 440C-WD001A-EN-P - November 201423
Page 28
Chapter 5Muting 2-Sensor L-Type Unidirectional
+24V DC
Muted
Light Curtain
24V Com
AB
Pink OSSD A
Grey OSSD B
BlueBlue
Override
Contactors
for Conveyor
Power
Muting
Lamp
05
CR30
02010003 04
A11520 21160618A2
07190810 11
12 13 14
09
17
K2K1
Black
Brown
Brown
Blue
Blue
K2
K1
3 4 11 3
Black
Brown
Brown
Brown
Brown
Blue
Blue
Muting
Sensor 1
Muting
Sensor 2
3 4 1
6
5
7
21
3
Schematic
The example schematic is set up to agree with the terminals shown in the
Connected Components Workbench™ and the example bill of materials.
Figure 15 - Example Schematic
24Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 29
Muting 2-Sensor L-Type UnidirectionalChapter 5
Connected Components
Workbench
Figure 16 - Connected Components Workbench Example
Circuit Status
The circuit is ready to run. The muting sensors are clear and the light curtain is
clear.
Rockwell Automation Publication 440C-WD001A-EN-P - November 201425
Page 30
Chapter 5Muting 2-Sensor L-Type Unidirectional
LC
Muting sensor 1
Muting sensor 2
Muting lamp
t > 30ms
t > 30ms
t > 50ms
30ms <= t
t < synchronization
time
30ms <= t
t < synchronization
time
t < muting time
muted
Operational Sequence
The muting sensors and the light curtain participate in the sequence of events to
achieve the muting. The material must move past the sensors and into the light
curtain within the synchronization times, which are set in the Connected
Components Workbench function block. In addition, the material must move
through the light curtain within the muting time, which is also set in the
Connected Components Workbench function block.
Figure 17 - Operational Sequence
As the material moves out of the hazard area, it first breaks muting sensor 1
(MS1). The material continues to move and must break muting sensor 2 (MS2)
within the first synchronization time, which is set on the Connected
Components Workbench to 1 second. Then, the muting lamp turns ON and the
light curtain is muted. The material continues to move and must break the light
curtain within the second muting time, which is also set on the Connected
Components Workbench to 1 second. Finally, the material must move through
the light curtain within the muting time, which is configured on the Connected
Components Workbench to 10 seconds.
26Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
If the material movement exceeds one of the synchronization times or the muting
time, the conveyor stops. An operator can press and hold down the override
button for the duration of the override time. The conveyor contactors turn on
until the override time expires (or the operator releases the button).
5855T-BPM10CControl Tower™ Stack Light Mounting Base
10 cm pole mount, black housing, cap included
6855T-B24TL7Control Tower Stack Light
Black housing, 24V AC/DC full voltage, clear steady LED
(socket mount)
7800FM-F1800F Push Button
Metal, flush, white, no legend, standard pack (Qty. 1)
8800F-MX10Metal Latch Mount
1 N.O. contact(s), 0 N.C. contact(s), standard
9100S-C09EJ304BCMCS 100S-C Safety Contactor
9 A, 24V DC (with elec. coil), bifurcated contact
1
1
1
1
2
2
2
2
1
1
1
1
2
Safety Rating
The 2-sensor L-type muting meets the performance requirements of Cat 4, PLe
per ISO13849-1, SIL CL3 per IEC 62061, and SIL 3 per IEC 61508.
Rockwell Automation Publication 440C-WD001A-EN-P - November 201427
Page 32
Chapter 5Muting 2-Sensor L-Type Unidirectional
Notes:
28Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 33
Chapter 6
Muting 2-Sensor T-Type Bidirectional
The CR30 has a function block that supports 2-sensor T-type muting. With this
function block, the material can only move in either direction: from the hazard
area to the non-hazard area or reverse. The two muting sensors are arranged so
that their beams form an “X” pattern where the crossover occurs very close to the
light curtain beam. The shape of the material must be such that it breaks the
muting sensor and light curtain beams in a specific pattern. The function block
contains timing parameters that allow you to accommodate a wide range of
operating speeds.
Product Overview
Figure 18 - Overview
Rockwell Automation Publication 440C-WD001A-EN-P - November 201429
Page 34
Chapter 6Muting 2-Sensor T-Type Bidirectional
Hazard AreaNon-hazard Area
Machine
MS1MS2
LC
Muting Lamp
Material
Conveyor
+24V DC
Muted
Light Curtain
24V Com
AB
Pink OSSD A
Grey OSSD B
BlueBlue
Override
Contactors
for Conveyor
Power
Muting
Lamp
05
CR30
02010003 04
A11520 21160618A2
07190810 11
12 13 14
09
17
K2K1
Black
Brown
Brown
Blue
Blue
K2
K1
3 4 11 31 3
Black
Brown
Brown
Brown
Brown
Blue
Blue
Muting
Sensor 1
Muting
Sensor 2
3 4 1
6
5
7
21
3
Machine Layout
Schematic
The material can flow in either direction: to the hazard area from the non-hazard
area or reverse. The shape of the material must be such that it blocks both muting
sensors before it blocks the light curtain. The order in which the muting sensors
are blocked is not critical, but the synchronization time (time between blocking
one sensor and the other sensor) must be met.
Figure 19 - Machine Layout
The example schematic is set up to agree with the terminals shown in the
Connected Components Workbench and the example bill of materials.
Figure 20 - Example Schematic
30Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 35
Muting 2-Sensor T-Type BidirectionalChapter 6
Connected Components
Workbench
Figure 21 - Connected Components Workbench Example
Circuit Status
The circuit is ready to run. The muting sensors are clear and the light curtain is
clear.
Rockwell Automation Publication 440C-WD001A-EN-P - November 201431
Page 36
Chapter 6Muting 2-Sensor T-Type Bidirectional
Operational Sequence
The muting sensors and the light curtain participate in the sequence of events to
achieve the muting. The material must move past the sensors and into the light
curtain within the synchronization times, which are set in the Connected
Components Workbench function block. In addition, the material must move
through the light curtain within the muting time, which is also set in the
Connected Components Workbench function block.
Figure 22 - Operational Sequence
LC
Muting sensor 1
Muting sensor 2
Muting lamp
30ms <= t
t < synchronization
time
t > 30ms
t > 50ms
muted
t < muting time
t > 30ms
30ms <= t
t < synchronization
time
As the material moves, it must block both muting sensors within their
synchronization times, which are configured in the Connected Components
Workbench function block for 3seconds. The light curtain is then muted. The
material must move through the light curtain within the specified muting time,
which is configured in the Connected Components Workbench to be 10
seconds.
If the material movement exceeds one of the synchronization times or the muting
time, the conveyor stops. An operator can press and hold down the override
button for the duration of the override time. The conveyor contactors turn on
until the override time expires (or the operator releases the button).
32Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
5855T-BPM10CControl Tower Stack Light Mounting Base
10 cm pole mount, black housing, cap included
6855T-B24TL7Control Tower Stack Light
Black housing, 24V AC/DC full voltage, clear steady LED
(socketmount)
7800FM-F1800F Push Button
Metal, flush, white, no legend, standard pack (Qty. 1)
8800F-MX10Metal Latch Mount
1 N.O. contact(s), 0 N.C. contact(s), standard
9100S-C09EJ304BCMCS 100S-C Safety Contactor
9 A, 24V DC (with elec. coil), bifuracated contact
1
1
1
1
2
2
2
2
1
1
1
1
2
Safety Rating
The 2-sensor T-type muting meets the performance requirements of Cat 4, PLe
per ISO13849-1, SIL CL3 per IEC 62061, and SIL 3 per IEC 61508.
Rockwell Automation Publication 440C-WD001A-EN-P - November 201433
Page 38
Chapter 6Muting 2-Sensor T-Type Bidirectional
Notes:
34Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 39
Chapter 7
Muting 4-sensor T-type Bidirectional
The CR30 has a function block that supports 4-sensor T-type muting. With this
function block, the material can only move in either direction: from the hazard
area to the non-hazard area or reverse. The four muting sensors are arranged so
that their beams cross orthogonally across the conveyor: two inside the hazard
area and two outside the hazard area. The length of the material must be such
that it breaks all four muting sensors and light curtain beams simultaneously. The
function block contains timing parameters that allow you to accommodate a
wide range of operating speeds.
Product Overview
Figure 23 - Overview
Rockwell Automation Publication 440C-WD001A-EN-P - November 201435
Page 40
Chapter 7Muting 4-sensor T-type Bidirectional
Hazard AreaNon-hazard Area
Machine
MS1MS2MS3MS4
LC
Muting Lamp
Material
Muted LC
Conveyor
+24V DC
Muted
Light Curtain
24V Com
AB
Pink OSSD A
Grey OSSD B
BlueBlue
Override
Contactors
for Conveyor
Power
Muting
Lamp
05
CR30
02010003 04
A11520 21160618A2
07190810 11
12 13 14
09
17
K2K1
Black
Brown
Brown
Blue
Blue
K2
K1
3 4 11 3
Black
Brown
Brown
Brown
Brown
Blue
Blue
Muting
Sensor 3
Muting
Sensor 4
3 4 1
6
5
7
21
3
Black
Brown
Brown
Blue
Blue
3 4 11 3
Black
Brown
Brown
Blue
Blue
Muting
Sensor 1
Muting
Sensor 2
3 4 1
Machine Layout
Schematic
The material can flow in either direction: to the hazard area from the non-hazard
area or reverse. The shape of the material must be such that it blocks both muting
sensors before it blocks the light curtain. The order in which the muting sensors
are blocked is not critical, but the synchronization time (time between blocking
one sensor and the other sensor) must be met.
Figure 24 - Machine Layout
The example schematic is set up to agree with the terminals shown in the
Connected Components Workbench and the example bill of materials.
Figure 25 - Schematic
36Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 41
Muting 4-sensor T-type BidirectionalChapter 7
Connected Components
Workbench
Figure 26 - Connected Components Workbench Example
Circuit Status
Operational Sequence
The circuit is ready to run. The muting sensors are clear and the light curtain is
clear.
The muting sensors and the light curtain participate in the sequence of events to
achieve the muting. The material must move past the sensors and into the light
curtain within the synchronization times, which are set in the Connected
Components Workbench function block. In addition, the material must move
through the light curtain within the muting time, which is also set in the
Connected Components Workbench function block.
Rockwell Automation Publication 440C-WD001A-EN-P - November 201437
Page 42
Chapter 7Muting 4-sensor T-type Bidirectional
Figure 27 - Operational Sequence
LC
Muting sensor 1 (4)
Muting sensor 2 (3)
Muting sensor 3 (2)
Muting sensor 4 (1)
Muting lamp
muted
t > 30ms
t < muting time
t > 30ms
30ms <= t
t < synchronization
time
30ms <= t
t < synchronization
time
t > 30ms
t > 50ms
As the material moves, it must block both muting sensors within their
synchronization times, which are configured in the Connected Components
Workbench function block for 3seconds. The light curtain is then muted. The
material must move through the light curtain within the specified muting time,
which is configured in the Connected Components Workbench to be 10
seconds.
If the material movement exceeds one of the synchronization times or the muting
time, the conveyor stops. An operator can press and hold down the override
button for the duration of the override time. The conveyor contactors turn on
until the override time expires (or the operator releases the button).
38Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
5855T-BPM10CControl Tower Stack Light Mounting Base
10 cm pole mount, black housing, cap included
6855T-B24TL7Control Tower Stack Light
Black housing, 24V AC/DC full voltage, clear steady LED
(socketmount)
7800FM-F1800F Push Button
Metal, flush, white, no legend, standard pack (Qty. 1)
8800F-MX10Metal Latch Mount
1 N.O. contact(s), 0 N.C. contact(s), standard
9100S-C09EJ304BCMCS 100S-C Safety Contactor
9 A, 24V DC (with elec. coil), bifuracated contact
1
1
1
1
4
4
4
4
1
1
1
1
2
Safety Rating
The 2-sensor L-type muting meets the performance requirements of Cat 4, PLe
per ISO13849-1, SIL CL3 per IEC 62061, and SIL 3 per IEC 61508.
Rockwell Automation Publication 440C-WD001A-EN-P - November 201439
Page 44
Chapter 7Muting 4-sensor T-type Bidirectional
Notes:
40Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 45
Chapter 8
Single-wire Safety
This example application focuses on the single-wire safety (SWS) feature built
into the CR30. TheCR30 has two input terminals that can be configured to use
single wire safety and two output terminals that can be configured to use single
wire safety.
Products that have single-wire safety outputs can be connected to the inputs of
the CR30. This application example shows a CR30 and SI as the single-wire
safety inputs of a CR30. On the output side, the CR30 is driving another CR30
and an EM relay using the single-wire safety output.
Two SensaGuard™ non-contact switches with integrated latch are included in the
example to show that the SWS signals can be incorporated into the logic that is
performed by the CR30.
Product Overview
Figure 28 - Overview
Rockwell Automation Publication 440C-WD001A-EN-P - November 201441
Page 46
Chapter 8Single-wire Safety
+24V DC
24V Com
AB
Reset
#1
#1#2
#1#2
Reset
#2
SWS IN
SWS OUT
05
CR30
02010003 04
A11520 21160618A2
07190810 11
12 13 14
09
17
05
CR30
02010003 04
A11520 21160618A2
07190810 11
12 13 14
09
17
SensaGuard
#1
SensaGuard
#2
OSSD A
OSSD B
OSSD A
OSSD B
A1
L11
X32
L121434 4424
1333 4323
A2
EM
440R-EM4R2
05
CR30
02010003 04
A11520 21160618A2
07190810 11
12 13 14
09
17
RESET
0
MM
AM
A1
S11 S21S12S22
Y32L11
13142324S34
A2
SI
440R-S12R2
Schematic
A partial schematic is shown in Figure 29 to highlight the SWS connections.
Figure 29 - Schematic
Connected Components
Workbench
The Connected Components Workbench shows two safety functions:
42Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
1. SWS In #1 & Gate #1 → SWS Out #1 (Immediate OFF).
2. SWS In #2 & Gate #2 → SWS Out #2 (Delayed OFF).
Page 47
Figure 30 - Connected Components Workbench Example
Single-wire SafetyChapter 8
Circuit Status
Operational Sequence
The safety gates are closed and the SWS safety inputs are active.
Press Reset #1 to activated SWS output #1 (terminal 20).
Press Reset #2 to activate SWS output #2 (terminal 21).
Deactivating SWS In #1 on terminal 10 or opening Gate #1 turns off SWS
output #1.
Deactivating SWS In #2 on terminal 11 or opening Gate #2 turns off WS
output#2.
Rockwell Automation Publication 440C-WD001A-EN-P - November 201443
Expansion module (single-wire safe is only input), 1 N.C. solid-state
auxiliary outputs
4440N-Z21SS2HSensaGuard
Plastic rectangular, 2 x PNP, 0.2 A, max safety output, 6 in. pigtail,
8pin micro (M12)
4.1889D-F8AB-5DC Micro (M12), Female, Straight
8-pin, PVC cable, yellow, unshielded, 24 AWG, IEC color coded, no
connector, 5 m (16.4 ft)
5800FM-F611MX10800F Push Button
Metal, flush, blue, R, metal latch mount, 1 N.O. contact(s), 0 N.C.
contact(s), standard, standard pack (Qty. 1)
3
1
1
2
2
2
The safety ratings of the two safety functions depend on additional components
that are not included in the example. The SWS portion of the circuit can be used
in applications up to Cat 4 PLe and SIL3.
44Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 49
Chapter 9
Lifeline Cable Pull
Lifeline™ cable pull switches are emergency stop devices with mechanical
contacts. The application uses pulse testing to check for potential short circuits to
24V, ground and across channels. Manual monitored reset prevents the outputs
from turning ON when Lifeline switches are reset.
Product Overview
Figure 31 - Overview
Rockwell Automation Publication 440C-WD001A-EN-P - November 201445
Page 50
Chapter 9Lifeline Cable Pull
+24V DC
24V Com
Reset
AB
05
CR30
02010003 04
A11520 21160618A2
07190810 11
12 13 14
09
17
K2K1
K2
K1
12
22
11
21
32
31
44
43
12
22
11
213231
44
43
Cable
Schematic
Connected Components
Workbench
Figure 32 - Schematic
The Lifeline 4 switches are emergency stop devices. The emergency stop function
blocks are ANDed as both must be closed for the Immediate Safety Output to
turn ON. When either Lifeline switch opens, the Safety Output turns OFF
immediately.
Circuit Status
Operational Sequence
Example Bill of Materials
Both Lifeline switches are closed. The contactors are OFF.
Press the reset button to turn both contactors ON. Pull on the cable to turn the
contactors OFF.
PLe SIL 3, 22 Safety I/O, embedded serial port, USB programming
port, 2 plugin slots, 24V DC
2440E-L13043440E Emergency Stop Device
2.1440E-A13085Installation Kit
75 m
3440E-L13043440E Emergency Stop Device
4800FM-F611MX10800F Push Button
5100S-C09EJ23BCMCS 100S-C Safety Contactor
Metal, flush, blue, R, metal latch mount, 1 N.O. contact(s), 0 N.C.
contact(s), standard, standard pack (Qty. 1)
9 A, 24V DC (with elec. coil), bifurcated contact
1
Safety Rating
46Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
The safety rating that is initiated by either cable pull switch meets the
requirements of Cat 4 PLe and SIL3.
Page 51
Chapter 10
24V Com
+24V DC
AB
05
CR30
02010003 04
A11520 21160618A2
07190810 11
12 13 14
09
17
K2K1
K2
K1
K4
K3
S1
S2
BrownBlue
Blue
White
Black
Brown
White
Black
Grey
Grey
S3S4
BrownBlue
White
Black
BrownBlue
White
Black
K3 K4
Two-hand Control
This application example shows the setup for two separate 2-hand controls each
that meets ISO 13851 Type IIIC. One uses mechanical outputs, and the other
uses OSSD outputs. Each of the 800Z Zero-Force Touch Buttons™ have a
normally open and normally closed contact. The two systems operate
independently of each other.
Product Overview
Schematic
Figure 33 - Overview
Figure 34 - Schematic
Rockwell Automation Publication 440C-WD001A-EN-P - November 201447
Page 52
Chapter 10Two-hand Control
Connected Components
Workbench
Figure 35 - Connected Components Workbench Example
Circuit Status
Operational Sequence
48Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
In both circuits, there are no hands on the buttons. All four output contactors are
off.
The two circuits work independently.
You must simultaneously press S1 and S2 (or S3 and S4) to turn on contactors K1
and K2 (or K3 and K4), where simultaneously means within a half second of each
other. You must maintain their hands on both buttons to maintain the contactors
in the ON state. Removing your hands from either button causes the contactors
to turn OFF.
PLe SIL 3, 22 Safety I/O, embedded serial port, USB programming
port, 2 plugin slots, 24V DC
2800Z-GL3Q5 30.5 mm Type 4/4X/13 IP66 Zero-Force Momentary General
Purpose Touch Button
10…40V DC and 20…30V AC input, relay output - 5-pin QD
2.1800Z-G3AH1Plastic Mounting Kit
For 30.5 mm holes, (GP)
2.2889N-F5AE-12F5-Pin Straight QD Cable
30.5 mm mounting hole, 12 ft length
3800Z-G3AG2 Guard
Black, 22.5 mm/30.5 mm mounting, (GP)
4800Z-GP3Q4 30.5 mm Type 4/4X/13 IP66 Zero-Force Momentary General
Purpose Touch Button
10…30V DC, PNP (sourcing output), 4-pin QD
4.1800Z-G3AH1Plastic Mounting Kit
For 30.5 mm holes, (GP)
4.2889D-F4AE-54-Pin Straight QD Micro Cable
30.5 mm mounting hole, 12 ft length
5100S-C09EJ23BCMCS 100S-C Safety Contactor
9 A, 24V DC (with elec. coil), bifurcated contact
1
Safety Rating
Although the wiring is a little different, both 2-hand control systems meet
ISO13851 Type IIIC.
Rockwell Automation Publication 440C-WD001A-EN-P - November 201449
Page 54
Chapter 10Two-hand Control
Notes:
50Rockwell Automation Publication 440C-WD001A-EN-P - November 2014
Page 55
Page 56
Rockwell Automation Support
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support
software service packs. You can also visit our Support Center at https://rockwellautomation.custhelp.com/
updates, support chats and forums, technical information, FAQs, and to sign up for product notification updates.
In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more
information, contact your local distributor or Rockwell Automation representative, or visit
If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada1.440.646.3434
Outside United States or CanadaUse the Wor ldw ide L ocat or
Rockwell Automation representative.
at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local
New Product Satisfaction Return
you can find technical and application notes, sample code, and links to
for software
.
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United StatesContact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
Outside United StatesPlease contact your local Rockwell Automation representative for the return procedure.
distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002
Rockwell Automation maintains current product environmental information on its website at