Rockwell Automation 8-545 User Manual

INSTALLATION INSTRUCTIONS
PHOTOSWITCH
IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. FOR ADDITIONAL INFORMATION REFER TO PUBLICATION PGĆ9000
PLUG IN SOLID STATE RELAY, BULLETIN 8-545/8-585
BULLETIN NUMBER TYPE VOLTAGE SUPPLY LOAD CURRENT LEAKAGE
8-545 Triac 75-140-VAC 1A 6 mA 8 ms
8-585 F.E .T 0-120 VAC/DC 30mA 10 µA 1 ms
8-545
SPECIFICATIONS
Line Transient Protection MOV varistor. . . . . . . . . . . . . . . . . . .
Approvals UL Listed and CSA Certified. . . . . . . . . . . . . . . . . . . .
Contracts 1 Normally Open. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ambient Temperature Range –20°F to 135°F (–28°C to 57°C). . Load Current
Continuous 1 A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50% (Max) Duty Cycle 2 A. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10% (Max) Duty Cycle 4 A. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Surge 1% (Max) Duty Cycle 10 A. . . . . . . . . . . . . . . . . . . . . . . .
Input (control) voltage to operate 14–30VDC. . . . . . . . . . . . . . . .
Input (control) current to operate 3 – 6 mA. . . . . . . . . . . . . . . .
Input to output isolation 1000 Megohms and 1500 VAC. . . . . . .
EXTERNAL CONNECTION DIAGRAM
ALL 22 SERIES BASES ALL 42RL SERIES CONTROLS
TERMINALS
1C
TERMINALS
2C
SPECIFICATIONS
Overvoltage Protection MOV varistor. . . . . . . . . . . . . . . . . . . . .
Approvals UL Listed and CSA Certified. . . . . . . . . . . . . . . . . . . .
Contracts Form A (SPST) Normally Open. . . . . . . . . . . . . . . . . . .
Ambient Temperature Range –40°F to 150°F (–40°C to 65°C). .
Maximum Operating Voltage ± 200VDC or Peak AC. . . . . . . . .
Maximum Continuous Load Current 30mA. . . . . . . . . . . . . . . .
Maximum Peak Load Current 100mA. . . . . . . . . . . . . . . . . . . . .
Short Circuit Load Protection None. . . . . . . . . . . . . . . . . . . . . .
Minimum Load Current None. . . . . . . . . . . . . . . . . . . . . . . . . . .
Maximum On Resistance 70 Ohms. . . . . . . . . . . . . . . . . . . . . . . . .
Minimum Voltage Input for Reliable Operation 17VDC. . . . . . .
Input Current Drain 25 mA at 30VDC. . . . . . . . . . . . . . . . . . . . .
Isolation Voltage 2500 VAC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EXTERNAL CONNECTION DIAGRAM
ALL 22 SERIES BASES
1C
1NO
(off State)
8-585
TO PROGRAMMABLE
CONTROLLER
INTERFACE
1NO
1NC
INPUT OUTPUT
14V MIN
LOAD LOAD
LOAD 75-140 VAC
INTERNAL SCHEMATIC
+
B
N.O.
-
A
2NO
2NC
10A FUSE
LOAD 75-140 VAC
6
TO
TERMINALS
9
1NC
ALL 42RL SERIES CONTROLS
AND 60-1691 MULTI-MODULE OUTPUT BASE
(+)
(-)
2C
2NO
2NC
INTERNAL SCHEMATIC
B
A
TO PROGRAMMABLE
CONTROLLER
INTERFACE
6
N.O.
9
TO
TERMINALS
Publication PA–9208(A)
November 1992
Supercedes Publication PA–7920, PA–8106