Rockwell Automation 800Z User Manual

Touch Button and Guard Installation
(Bulletin 800Z)
WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Protect cables from mechanical damage during installation and use.
ATTENTION: The 800Z touch button is designed to be an ergonomic replacement for a palm button. It is not a safety device by itself. This product may cause personal injury or property damage if not installed and used in accordance with the manufacturer's instructions provided as well as applicable standards and regulations. The user has responsibility to ensure that all local, state, as well as, national laws, codes and regulations relating to the use and installation of this device are satisfied. Furthermore, safety relays should be used in all two-hand control applications. Some U.S. standards applicable to two-hand control systems include: ANSI B11, NFPA 79, and ANSI/RIA R15.06. Some European standards applicable to two-hand control systems include: EN 574, EN 999, EN 60204-1, EN 292-1 and EN 292-2.
ATTENTION: This product has undergone a series change from series B to C. Series C product is RoHS compliant.
Installation
Guard 800Z-G3AG_
Remove Ring For 30mm Mounting
800Z-G3ALC1
Not Used on 22mm Mounting
2.8 Nm (25 LB-IN) 800Z-G_2_ _
3.9 Nm (35 LB-IN) 800Z-G_3_ _
22.3mm (0.878") 800Z-G_2_ _
30.5mm (1.200") 800Z-G_3_ _
1 - 4mm (0.04"- 0.16") With Guard 1 - 9.5mm (0.04"- 0.37") Without Guard
Electrical Connections: 10-40V DC & 20-30V AC, 100-240V AC
Cable Option Quick Disconnect (QD) Option
Operation
1. When the power LED is green, the Touch Button is ready for operation.
2. To enable an output, simply place palm or fingers onto ergonomically contoured surface (see Fig. 1).
3. Touch Button output stays activated as long as the sensor surface remains touched.
4. When the output LED is red, the output is de-energized. When the output LED is green, the output is energized.
Power/Fault LED
Output LED
Diagnostics
Figure 1 Figure 2
Code 1: The Power/Fault LED (see Figure 2) will turn red for 1 second during power-up. After the unit
self-diagnostics have passed, the Power/Fault LED will turn green and the Output LED will turn red. If a fault occurs, the Power/Fault LED will remain red. Code 2: If the device is touched during power-up, the Power/Fault LED will flash red indicating the device has been disabled. It will continue to flash until power is cycled to the unit.
Code 3: If the unit detects an unacceptable level of noise, it will become disabled and the red Power/Fault LED will flash until the noise subsides.
Code 4: If conductive films deposit on the sensor surface over time or if a person attempts to defeat the sensors with foreign objects, the red Power/Fault LED will flash. The fault will disable the unit and it will remain disabled until the fault is cleared. (fast flash) Note: In most applications, the grounded neutral line and/or parasitic capacitance between the input power leads and earth provide(s) sufficient impedance for the device to function properly. If the unit powers up normally without diagnostic fault codes but does not activate, the power source could be ungrounded. For additional information, please contact Rockwell Automation Technical Support by email at raictechsupport@ra.rockwell.com or by phone at 440-646-5800.
Sensor Surface
POWER/FAULT OUTPUT
Cat
800Z-GF3
Ser
C
BROWN (+) L1
BLUE (–) L2
Cable should be protected
BLACK (N.O.)
WHITE (N.C.)
GRAY (COMMON)
Mini QD (30.5mm) Micro QD (22.5mm)
BLACK (1 N.O.)
BLUE (–) L2
1
2
3
(COMMON)
GRAY
WHITE
(1 N.C.)
5
4
BROWN
(+) L1
WHITE (1 N.C.)
BLUE (–) L2
2
5
3
5-Pin Molded Cordsets
Mini QD (30.5mm)
#889N-F5AE-6F #889N-F5AE-12F #889N-F5AE-20F #889N-R5AE-6F #889N-R5AE-12F #889N-R5AE-20F
PN-54018 DIR 10000071388 (Version 01) Printed in U.S.A
Micro QD (22.5mm)
#889D-F5AC-2 #889D-F5AC-5 #889D-F5AC-10
1
4
GRAY
(COMMON)
BROWN
(+) L1
BLACK (1 N.O.)
CODE TYPE
CODE 2 POWER-UP SAFETY
DESCRIPTION
NOISE DETECTIONCODE 3
MARGIN DETECTIONCODE 4
• • • • • • • • •
• • • • • • • • • • • •
Input Voltage: 10-40V DC, 20-30V AC (800Z-GL...)
100-240V AC (800Z-GF...)
Output Rating: Min. Load: 6mA, 12V Inductive: C300, AC-15, Ith=2.5A R300, DC-13, I Resistive (connector option): 4A, 250V AC 4A, 24V DC Resistive (cable option): 3A, 250V AC 3A, 24V DC Overcurrent protection shall be provided: 3A, 250V
Response Time: Off Time Delay: 60 ms (max.) On Time Delay: 76 ms (max.), 60 ms (avg.)
Protection: Type 4/4X/13, IP66,1200 psi Washdown
Agency Certification: UL, cUL, and CE compliant for all applicable directives. CE directives include EN 61000-6-2, EN 50081–2, and EN 60947–5–1. This product is intended for use in an industrial environment.
=1.0A
th
Maintenance
Unit has no customer serviceable parts.
FAULT LED FLASH
SEQUENCE
• • • • • •
111.9mm (4.40")
MIN. CYCLE TIME
CYCLE POWER REQ.
10 SEC.
1.5 SEC.
81.6kg (180 lbs) MAX
69.8mm (2.75")
42.3mm (1.67")
129.3mm
(5.09")