Rockwell Automation 1492-CM800-LD013 User Manual

Field Wire Conversion Module for Modicon B802-008 to 1756-OA8E
(Cat 1492-CM800-LD013)
10000021908 (Version 00)
Printed in Germany
Local language (French, Italian, German & Spanish) versions of this document can be downloaded by going to www.ab.com. In the left margin click on Publications Library and Literature Library. In the Search Area (right margin), Search by Catalog Number and in the Search box type in the catalog number of the conversion system component.
The 1492-CM800-LD013 conversion module provides field wire signal conversion from a Modicon® B802-008, 80 to 130Vac , 8-pt output module to a ControLogix 1756-OA8E, 74 to 132Vac , 8-pt output module. The conversion module provides the mating connections to the B802-008 swing-arm (terminal block) with the attached field wires. It routes those signals, via its 20-pin connector and a 1492-CABLEU pre-wired cable to compatible terminals of the 1756-OA8E module. NOTE: The B802-008 was mechanically fused per group. The 1756-OA8E is electronically fused per group. Refer to the 1756-OA8E Installation Manual and to the Wiring Diagram on page 2.
II. Module Installation
The 1492-CM800-LD013 conversion module must be installed in a 1492 conversion base-plate and cover-plate assembly. The installation of the module into the assembly is explained in the Installation Manual that ships with the conversion assembly. For a list of compatible assemblies refer to Appendix A.
III. Conversion Module Compatibility Matrix
This is the cable length in meters and tenths of meters (e.g. 015 = 1.5 meters). Recommended cable
length is 003 (00.3 meters).
20-Pin Connector for 1492-CABLE
U
Mating Connector for B800 Terminal Block
Conversion Module Compatible 800
Output Module
Compatible 1756
Output Module
Required 1492 Cable
1492-CM800-LD0013 B802-008 1756-OA8E 1492-CABLE
U
1492-CM800-LD013 Conversion Module
De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to any device in the control cabinet where the conversion is to be performed. Ensure work is performed by qualified personnel.
WARNING
Refer to conversion module Specifications Section: Maximum Operating Voltage
(2)
10000021908 (Version 00)
IV. Conversion Module Wiring Diagram
The following diagram shows the connections from the existing B802-008 swing-arm, through the conversion module, 1492 cable and to the 1756-OA8E output module. The diagram can be used as an aid in possible system troubleshooting.
1756-OA8E
1492-CABLE003U
1492-CM800-LD013
Conversion: B802-008 to 1756-OA8E 1492-CM800-LD013
B802-008 Swing Arm
Conversion Module Installation and Application Considerations
The B802-008 module output current limits versus 1756-OA8E limits are as follows:
B802-008 1756-OA8E w/ 1492-CABLE003U
a) Current/Point 2A 2A b) Current/Module 12A 8A@30°C, 4A@60°C c) Surge Current/Pt 50A for 1 cycle 20A for 43ms
The B802-008 has 4 groups (allowing 4 separate power supplies) and the 1756-OA8E has 2 groups. This module/cable combination ties Groups 1 & 2 from the B802-008 to Group 0 on the 1756-OA8E and it ties Groups 3 & 4 from the B802-008 to Group 1 on the 1756-OA8E. Field wiring modification must be made to accommodate this if multiple supplies were used. If 4 supplies were used, 2 must be removed.
The B802-008 provided a single fuse per group. The 1756-OA8E is electronically fused per point. Refer to the 1756-OA8E
Installation Manual for electronic fusing details.
The 1492-CABLE003U current is limited to 2A per pin.
Refer to your B802-008 and 1756-OA8E Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded.
[Reference Doc: 41170-767 (Version 03)]
1
1
2
2
3
7
4
8
5 6 7
4 8
9
10 10
11
12 14 13 20 11 15 12 16 17 17 18 18
19
20
14
Output 1
Output 3
Output 2
Output 4
LOAD
L1
L2
Hot Grp 1
Hot Grp 2
Hot Grp 3 Hot Grp 4
Output 5
Output 7
Output 6
Output 8
3Neutral Grp 1 9Neutral Grp 2
13Neutral Grp 3 19Neutral Grp 4 5Not Used 6 15 16Not Used
Not Used
Not Used
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
2
L2-0 OUT-0
3
OUT-1
5
OUT-2
7
OUT-3
9
OUT-4
4
OUT-5
6
OUT-6
8
OUT-7
10 12 14 16 18 11 13 15 17
L2-1
19
1
Not Used
20
L1-1
L1-0 L1-0 L1-0 L1-0 L1-1 L1-1 L1-1 L1-1
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and output module). Read and understand these considerations before installation. In addition, refer to the current draw requirements of the existing loads for this configuration to ensure they are within the current ratings of the 1756 output module.
WARNING