(2)
10000021908 (Version 00)
IV. Conversion Module Wiring Diagram
The following diagram shows the connections from the existing B802-008 swing-arm, through the conversion module, 1492
cable and to the 1756-OA8E output module. The diagram can be used as an aid in possible system troubleshooting.
1756-OA8E
1492-CABLE003U
1492-CM800-LD013
Conversion: B802-008 to 1756-OA8E 1492-CM800-LD013
B802-008 Swing Arm
Conversion Module Installation and Application Considerations
The B802-008 module output current limits versus 1756-OA8E limits are as follows:
B802-008 1756-OA8E w/ 1492-CABLE003U
a) Current/Point 2A 2A
b) Current/Module 12A 8A@30°C, 4A@60°C
c) Surge Current/Pt 50A for 1 cycle 20A for 43ms
The B802-008 has 4 groups (allowing 4 separate power supplies) and the 1756-OA8E has 2 groups. This module/cable
combination ties Groups 1 & 2 from the B802-008 to Group 0 on the 1756-OA8E and it ties Groups 3 & 4 from the B802-008 to
Group 1 on the 1756-OA8E. Field wiring modification must be made to accommodate this if multiple supplies were used. If 4
supplies were used, 2 must be removed.
The B802-008 provided a single fuse per group. The 1756-OA8E is electronically fused per point. Refer to the 1756-OA8E
Installation Manual for electronic fusing details.
The 1492-CABLE003U current is limited to 2A per pin.
Refer to your B802-008 and 1756-OA8E Installation Manual wiring schematics and diagrams for more details. Ensure 1756
output module ratings are not exceeded.
[Reference Doc: 41170-767 (Version 03)]
1
1
2
2
3
7
4
8
5
6
7
4 8
9
10 10
11
12
14 13
20
11 15
12 16
17 17
18 18
19
20
14
Output 1
Output 3
Output 2
Output 4
LOAD
L1
L2
Hot Grp 1
Hot Grp 2
Hot Grp 3
Hot Grp 4
Output 5
Output 7
Output 6
Output 8
3Neutral Grp 1
9Neutral Grp 2
13Neutral Grp 3
19Neutral Grp 4
5Not Used
6
15
16Not Used
Not Used
Not Used
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
2
L2-0
OUT-0
3
OUT-1
5
OUT-2
7
OUT-3
9
OUT-4
4
OUT-5
6
OUT-6
8
OUT-7
10
12
14
16
18
11
13
15
17
L2-1
19
1
Not Used
20
L1-1
L1-0
L1-0
L1-0
L1-0
L1-1
L1-1
L1-1
L1-1
There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and output module). Read and understand these
considerations before installation. In addition, refer to the current draw requirements of the existing
loads for this configuration to ensure they are within the current ratings of the 1756 output module.
WARNING