Rockwell Automation 1492-CM800-LD011 User Manual

Fused Field Wire Conversion Module for Modicon B838-032 to 1756-OB32
(Cat 1492-CM800-LD011)
10000021898 (Version 00)
Printed in Germany
Local language (French, Italian, German & Spanish) versions of this document can be downloaded by going to www.ab.com. In the left margin click on Publications Library and Literature Library. In the Search Area (right margin), Search by Catalog Number and in the Search box type in the catalog number of the conversion system component.
The 1492-CM800-LD011 conversion module provides field wire signal conversion from a Modicon® B838-032, 20 to 28Vdc, 32-pt output module to a ControLogix 1756-OB32, 10 to 31.2Vdc, 32-pt output module. The conversion module provides the mating connections to the B838-032 swing-arm (terminal block) with the attached field wires. It routes those signals, via its 40-pin connector and a 1492-CABLEZ pre-wired cable to compatible terminals of the 1756-OB32. To maintain the functionality of the B838-032 output module the conversion module provides a mechani­cal fuse for each of the two power supplies (DC-0+ and DC-1+) on the 1756-OB32 (refer to the Wiring Diagram on page 2).
II. Module Installation
The 1492-CM800-LD011 conversion module must be installed in a 1492 conversion base-plate and cover-plate assembly. The installation of the module into the assembly is explained in the Installation Manual that ships with the conversion assembly. For a list of compatible assemblies refer to Appendix A.
III. Conversion Module Compatibility Matrix
This is the cable length in meters and tenths of meters (e.g. 015 = 1.5 meters). Recommended cable
length is 003 (00.3 meters).
40-Pin Connector for 1492-CABLE
Z
Mating Connector for B800 Terminal Block
Conversion Module Compatible 800
Output Module
Compatible 1756
Output Module
Required 1492 Cable
1492-CM800-LD011 B838-032 1756-OB32 1492-CABLEZ
1492-CM800-LD011 Conversion Module
De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to any device in the control cabinet where the conversion is to be performed. Ensure work is performed by qualified personnel.
WARNING
(2)
10000021898 (Version 00)
IV. Conversion Module Wiring Diagram
The following diagram shows the connections from the existing B838-032 swing-arm, through the conversion module, 1492 cable and to the 1756-OB32 output module. The diagram can be used as an aid in possible system troubleshooting.
1756-OB32
1492-CABLE003Z
1492-CM800-LD011
Conversion: B838-032 to 1756-OB32 with 1492-CM800-LD011
B838-032 Swing Arm
Conversion Module Installation and Application Considerations
The B838-032 module output current limits versus 1756-OB32 limits are as follows:
B838-032 1756-OB32 w/ 1492-CABLE003Z
a) Current/Point 0.5A 0.35A b) Current/Group - - 4A c) Current/Module 16A 8A d) Surge Current/Pt 2.5A for 0.5ms 1A for 10ms
The B838-032 has 4 groups (allowing 4 separate power supplies) and the 1756-OB32 has 2 groups. This module/cable combi­nation ties Groups 1 & 2 from the B838-032 to Group 0 on the 1756-OB32 and it ties Groups 3 & 4 from the B838-032 to Group 1 on the 1756-OB32. Field wiring modification must be made to accommodate this if multiple supplies were used. If 4 supplies were used, 2 must be removed. The B838-032 provided a single fuse per group. The 1756-OB32 is NOT fused. The 1492-CM800-LD011 provides a 5x20mm fuse per 1756-OB32 Group. Fuse rating for this configuration is 4 Amps.
The 1492-CABLE003Z current is limited to 2A per pin. Refer to your B838-032 and 1756-OB32 Installation Manual wiring schematics and diagrams.
Ensure 1756 output module
ratings are not exceeded.
[Reference Doc: 41170-761 (Version 03)]
1 2 3
4 1 5 21 6 2 7 22 8 3 9 23 10 4 11 24 12 7 13 27 8 15 28 16 9 17 29 18 10 19 30 20
14
11 21 31 22 12 23 32 24 13 25 33 26 14 27 34 28 17 29 37 30 18 31 38 32 19 33 39 20 35 40 36
26
37
16
38
39
40
34
Output 1
Output 17
Output 2
Output 18
Output 3
Output 19
Output 4
Output 20
Output 5
Output 21
Output 6
Output 22
Output 7
Output 23
Output 8
Output 24
Output 9 Output 25 Output 10 Output 26 Output 11 Output 27 Output 12 Output 28 Output 13 Output 29 Output 14 Output 30 Output 15 Output 31 Output 16 Output 32
36
5
6
18
DC-0(+)
OUT-0
1
OUT-16
19
OUT-1
2
OUT-17
20
OUT-2
3
OUT-18
21
OUT-3
4
OUT-19
22
OUT-4
5
OUT-20
23
OUT-5
6
OUT-21
24
OUT-6
7
OUT-22
25
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
OUT-7
8
DC-1(+)
36
OUT-23
26
OUT-8
9
OUT-24
27
OUT-9
10
OUT-25
28
OUT-10
11
OUT-26
29
OUT-11
12
OUT-27
30
OUT-12
13
OUT-28
31
OUT-13
14
OUT-29
32
OUT-14
15
OUT-30
33
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/White
Green/Black/White
Orange/Black/White
Blue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
OUT-15
16
OUT-31
34 17
White/Red/Blue
Black/White/Green
White/Black/Green
Red/White/Green
35
RTN OUT-0 RTN OUT-1
Group 1(-)
+
-
LOAD
25 15 35
Group 3(-) Group 2(-) Group 4(-)
Group 1(+) Group 3(+) Group 2(+) Group 4(+)
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and output module). Read and understand these considerations before installation. In addition, refer to the current draw requirements of the existing loads for this configuration to ensure they are within the current ratings of the 1756 output module.
WARNING