Rockwell Automation 1492-CM800-LA001 User Manual

Field Wire Conversion Module for Modicon B875-111 to 1756-IF16 in Differential Current of Differential Voltage Mode
(Cat 1492-CM800-LA001)
10000021823 (Version 00)
Printed in Germany
Local language (French, Italian, German & Spanish) versions of this document can be downloaded by going to www.ab.com. In the left margin click on Publications Library and Literature Library. In the Search Area (right margin), Search by Catalog Number and in the Search box type in the catalog number of the conversion system component.
I. Module Description
The 1492-CM800-LA001 conversion module provides field wire signal conversion from a Modicon® B875-111, analog, 8-channel, differential current or voltage input module to a ControLogix 1756-IF16, analog, 8-channel, differ­ential current or voltage input module. The conversion module provides the mating connections to the B875-111 swing-arm (terminal block) with the attached field wires. It routes those signals, via its 25-pin, D-shell connector and a 1492-ACABLEUC or 1492-ACABLEUD pre-wired cable to the compatible terminals of the 1756-IF16 (refer to the Wiring Diagrams on pages 2 and 3).
II. Module Installation
The 1492-CM800-LA001 conversion module must be installed in a 1492 conversion base-plate and cover-plate assembly. The installation of the module into the assembly is explained in the Installation Manual that ships with the conversion assembly. For a list of compatible assemblies refer to Appendix A.
III. Conversion Module Compatibility Matrix
This is the cable length in meters and tenths of meters (e.g. 015 = 1.5 meters). Recommended cable
length is 003 (00.3 meters).
25-Pin D-Shell Connector for 1492-ACABLE
UC or ACABLEUD
Mating Connector for B800 Terminal Block
Conversion Module Compatible 800
Input Module
Compatible 1756
Input Module
Required 1492 Cable
1492-CM800-LA001 B875-111 (Diff-V) 1756-IF16 (Diff-V) 1492-ACABLEUC 1492-CM800-LA001 B875-111 (Diff-C) 1756-IF16 (Diff-C) 1492-ACABLEUD
1492-CM800-LA001 Conversion Module
De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to any device in the control cabinet where the conversion is to be performed. Ensure work is performed by qualified personnel.
WARNING
(2)
10000021823 (Version 00)
IV. Conversion Module Wiring Diagram
The following diagrams show the connections from the existing B875-111 swing-arm, through the conversion module, 1492 cable and to the 1756-IF16 analog input module. The diagrams can be used as an aid in possible system trouble-
1756-IF16
1492-ACABLE003UD
1492-CM800-LA001
Conversion: B875-111 to 1756-IF16 (Differential Current) with 1492-CM800-LA001
B875-111 Swing Arm
3
7 8
11 12
15 16
5 9 13 17 25 29
Input 4+ Input 4-
Input 2+
Input 3+
Input 2-
Input 3-
3 2 1 14 15 16 17 18 4 6 8 10 19
12 13 25 24 23 22 20 21
+
-
4
Input 1+ Input 1-
2
Current Input 1
6
Current Input 2
10
Current Input 3
14
Current Input 4
23
27 28
31 32
35 36
Input 8+ Input 8-
Input 6+
Input 7+
Input 6-
Input 7-
24
Input 5+ Input 5-
22
Current Input 5
26
Current Input 6
30
Current Input 7
34
Current Input 8
SH
33 37
Shield 8
Shield 7
Shield 6
Shield 5
Shield 4
Shield 3
Shield 2
Shield 1
1 40 18 19 20 21 38 39
Voltage Reference -
Voltage Reference +
Not Used
Not Used
Not Used
Not Used
Case Ground
Case Ground
2
IN-0 IN-1
4
IN-2
6
IN-3
8
IN-4
12
IN-5
14
IN-6
16
IN-7
18
RTN
10
IN-9
22
IN-8
20
IN-11
26
IN-10
24
IN-15
36
IN-14
34
Red
Black
White
Black
Green
Black
Blue
Black
Red
Green
IN-13
32
IN-12
30
Yellow
Black
Brown
Black
Orange
Black
Red
White
iRTN-2
5
iRTN-0
1
iRTN-6
15
iRTN-4
11
iRTN-10
23
iRTN-8
19
iRTN-14
33
iRTN-12
29
Conversion Module Installation and Application Considerations
 The B875-111 indicated differential inputs. When it was configured for single ended inputs, it was referred to as a B877-111.  SHIELD GROUNDING: For differential current analog inputs the B875-111 recommended grounding the field wiring shield at the B875-111 module. The
1492 conversion module accounts for this shield ground connection. The pre-wired cable used between the 1492-CM800-LA001 and the 1756-IF16 [1492­ACABLE003UD] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected.
The B875-111 recommended placing jumpers from UNUSED to USED analog input channels. These jumpers MUST be removed or they will result in improper operation.
The B75-111 analog input ranges were configured by DIP switches on the module. The appropriate range for the 1756-IF16 is configured by software. This design assumes that all inputs on the B875-111 were connected to current transmitters. If there was a mix of current and voltage transmitters, then modification of the pre-wired cable [1492-ACABLE003UD] will need to occur at the 1756-IF16 terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
CASE GROUND: If connected, remove this wire from the B875-111 terminal block, as it serves no purpose for the 1756-IF16. Refer to your B875-111 and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring, features, and
configuration details.
[Reference Doc: 41170-763 (Version 03)]
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and output module). Read and understand these considerations before installation.
WARNING
(3)
10000021823 (Version 00)
IV. Conversion Module Wiring Diagram (Continued)
Conversion: B875-111 to 1756-IF16 (Differential Voltage) with 1492-CM800-LA001
1756-IF16
1492-ACABLE003UC
1492-CM800-LA001
B875-111 Swing Arm
Conversion Module Installation and Application Considerations
 The B875-111 indicated differential inputs. When it was configured for single ended inputs, it was referred to as a B877-111.  SHIELD GROUNDING: For differential current analog inputs the B875-111 recommended grounding the field wiring shield at the B875-111 module. The
1492 conversion module accounts for this shield ground connection. The pre-wired cable used between the 1492-CM800-LA001 and the 1756-IF16 [1492­ACABLE003UD] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected.
The B875-111 recommended placing jumpers from UNUSED to USED analog input channels. These jumpers MUST be removed or they will result in improper operation.
The B75-111 analog input ranges were configured by DIP switches on the module. The appropriate range for the 1756-IF16 is configured by software. This design assumes that all inputs on the B875-111 were connected to current transmitters. If there was a mix of current and voltage transmitters, then modification of the pre-wired cable [1492-ACABLE003UD] will need to occur at the 1756-IF16 terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
CASE GROUND: If connected, remove this wire from the B875-111 terminal block, as it serves no purpose for the 1756-IF16. Refer to your B875-111 and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring, features, and
configuration details.
[Reference Doc: 41170-766 (Version 03)]
3
7 8
11 12
15 16
5 9 13 17 25 29
Input 4+ Input 4-
Input 2+
Input 3+
Input 2-
Input 3-
2
IN-0 IN-1
4
IN-2
6
IN-3
8
IN-4
12
IN-5
14
IN-6
16
IN-7
18
RTN
10
IN-9
22
IN-8
20
IN-11
26
IN-10
24
IN-15
36
IN-14
34
Red
3 2 1 14 15 16 17 18 4 6 8 10 19
12 13 25 24 23 22 20 21
Black
White
Black
Green
Black
Blue
Black
Red
Green
IN-13
32
IN-12
30
Yellow
Black
Brown
Black
Orange
Black
Red
White
+
-
4
Input 1+ Input 1-
2
Current Input 1
6
Current Input 2
10
Current Input 3
14
Current Input 4
23
27 28
31 32
35 36
Input 8+ Input 8-
Input 6+
Input 7+
Input 6-
Input 7-
24
Input 5+ Input 5-
22
Current Input 5
26
Current Input 6
30Current Input 7
34Current Input 8
SH
2
33 37Shield 8
Shield 7
Shield 6
Shield 5
Shield 4
Shield 3
Shield 2
Shield 1
1 40 18 19 20 21 38 39Voltage Reference -
Voltage Reference +
Not Used
Not Used
Not Used
Not Used
Case Ground
Case Ground
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and output module). Read and understand these considerations before installation.
WARNING
10000021823 (Version 00)
Printed in Germany
Article No. 4351310000
V. 1492-CM800-LA001 Conversion Module Specifications
(Operating specifications are when installed in the Conversion System base / cover-plate assembly)
VI. Appendix A - 800 Housing to 1756 Chassis Conversion System Selection Process
1) Determine the number of 800 I/O modules actually used in the 800 I/O Housing to be converted to 1756 I/O.
2) Review the data in Column 5 from the below table, and select a 1756 I/O Chassis which meets your conversion needs from Step 1. Ensure the information from the I/O Conversion module table is reviewed first since in some cases, two 1756 modules are needed to replace one 800 I/O module.
3) Once the 1756 Chassis is selected, refer to Column 7 and select the Conversion Assembly.
One chassis slot required for the ControlLogix processor or a remote I/O adapter type module. The footprint and mounting dimensions of the 1492 Conversion Assembly (base plate and cover plate) match those of the
Modicon I/O Housing.
Width dimension includes the 1756 Chassis power supply. Surplus Chassis width as compared to the 800 I/O Housing is divided equally when mounting it on the Conversion Assembly. Mounting holes for the 1756 I/O Chassis are pre-drilled and pre-tapped into the Conversion Assembly cover plate.
Modicon is a Registered Trademark of Group Schneider
Specification Value
Dimensions 288.9 mm (height) x 139.7 mm (depth) x 44.5 mm (width)
11.37 in. (height) x 5.5 in. (depth) x 1.75 in. (width) Approximate Shipping Weight 300g (0.66 lbs) (includes carton) Storage Temperature -40 to +85°C (-40 to +185°F) Operating Temperature 0 to 55°C (32 to 131°F) Operating Humidity 5 to 95% at 55°C (non-condensing) Shock Non-operating Operating
50g
30g Operating Vibration 2g @ 10-500Hz Maximum Operating Voltage 60 Vdc Max. Module Operating Current
Per Point: Per Module:
2 Amps (1492-CABLE connection pins are limited to 2A per pin)
12 Amps
Agency Certifications
UL Classified: Under UL File Number E113724
CSA
CE: compliant for all applicable directives Pollution Degree 2 Environmental Rating IP20
AS-H810-xxx
AS-H819-103
AS-H819-209
AS-H819-100
AS-H827-103
AS-H827-209
AS-B827-100
Modicon 800 I/O
Housing Cat Number
1492-MUA4-MB3
1492-MUA7-A10-
MB4679
1492-MUA10-A13-
MB81011
Conversion Assembly
Catalog Number
3
4
6
7
8
10
11
10.25”
17.5”
17.5”
17.5”
27.1”
27.1”
27.1”
10.25”
A7 = 14.49”
A10 = 19.02”
A7 = 14.49”
A10 = 19.02”
A7 = 14.49”
A10 = 19.02” A10 = 19.02”
A13 = 23.15” A10 = 19.02”
A13 = 23.15” A10 = 19.02”
A13 = 23.15”
1756 Chassis
Width 
Dimension
3
A7 = 6, A10=9
A7 = 6, A10=9
A7 = 6, A10=9
A10 = 9, A13=12
A10 = 9, A13=12
A10 = 9, A13=12
1756 I/O Chassis
Catalog Number
1 72 3 654
1756-A4
1756-A7
or
1756-A10
1756-A10
or
1756-A13
Max. Number
of 800 Housing
Slots for I/O
800 Housing
Width
Dimension
Max. Number
of 1756 Chassis
Slots for I/O
Refer to the Wiring Diagram(s) for current limits for a specific configuration.
NOTICE
Loading...