Rockwell Automation 1492-CM1771-LD001 User Manual

Digital I/O Conversion Module
(Cat 1492-CM1771-LD001)
I. Description
This Digital I/O Conversion system provides for the conversion of (1) 1771, 16 point I/O modules to be converted to (1) 1756, 16 point I/O module and consists of the following:
(1) 1771 Modules (16pt) to (1) 1756 Module (16pt)
(2) Conversion Modules: 1492-CM1771-LD001 (1) Cable: 1492-CONCAB005X (Table 2) (1) Conversion Mounting Assembly: 1492-MUA… (Table 1)
This conversion is accomplished without the removal of any field wires from the existing 1771 Swing Arm. The existing 1771 Swing Arm fits directly onto the edge connector of the 1492 Conversion Module. On one end of the 1492 Cable is (1) connector for the Conversion Module. On the other end is the Removable Terminal Block (RTB) for the 1756 I/O module, as shown in the photo below. The I/O signals are routed through the 1492 Conversion Module and the 1492 Cable to the appropriate terminals on the 1756 I/O module per the Wiring Diagrams in Section V. As standard, both portions of the 1492 Cables are 0.5M long, but we also offer a 1.0M cable length. Refer to the footnotes in Table 2, Section III for further details.
WARNING
Conversion Compatibility and Product I.D. Label
25-Pin Connector for cable 1492-CONCAB005
1492-CM1771-LD001 Conversion Module
De-energize and lockout any and all power to all I/O field devices connected to the A-B 1771 I/O Chassis, and the power to the 1771 I/O Chassis itself. Ensure all power is de-energized and locked out to any device in the control cabinet where the conversion is to be performed. Ensure work is performed by qualified personnel.
X
PN-114270 DIR 10000060084 (Version 01)
Publication 1492-IN035B-EN-E
Printed in U.S.A.
II. Installation
The 1492 Conversion Modules must be installed in a 1492 Conversion Mounting Assembly (see Table 1 below). A complete System Installation Manual ships with the 1492 Conversion Mounting Assembly.
1) Determine the quantity of each type of 1771 I/O modules used in the 1771 I/O Chassis to be converted.
2) Select the applicable 1492 Conversion Modules from Table 2, Section III.
3) Review the Max Slots for I/O and Chassis Width data from the Table 1 below.
4) Select a 1756 I/O Chassis which has enough I/O Slots. NOTE: (2) I/O slots are required in the 1756 Chassis for conversions where (1) 1771 I/O module converts to (2) 1756 I/O modules.
5) Select the 1492 Conversion Mounting Assembly which has enough Conversion Module slots. NOTE: (2) Conversion Module slots are required in the 1492 Conversion Mounting Assembly for conversions where (2) 1771 I/O module convert to (1) 1756 I/O modules. NOTE: The 1492 Conversion Mounting Assembly has the same Height & Width foot-print as the 1771 Chassis and is designed to use the same mounting hardware. The combined Depth of the 1492 Conversion Mounting Assembly with the 1756 Chassis mounted on top is 10.25 inches (Controller w/key) or 10.0 inches (Controller w/o key). Dimension drawings are included in the System Installation Manual that ships with the 1492 Conversion Mounting Assembly.
Table 1: Bulletin 1771 to 1756 Chassis Conversion
1771 Chassis 1756 Chassis Conversion Mounting Assembly
Max
Cat. No.
1771-A1B 4 9.01 12.61
1771-A2B 8 14.01 17.61
1771-A3B1 12 19.01
1771-A4B 16 24.01
Slots
for
I/O
Chassis Width
without
Power
Supply
with
Power
Supply
Cat. No.
1756-A4
1756-A7
1756-A7
1756-A10
1756-A10 1756-A13
1756-A13
1756-A17
Max
Slots
Chassis
for
I/O
3 10.35
6 14.49
6 14.49 9 19.02
9 19.02
12 23.15
12 23.15
16 29.06
Width
Cat. No.
1492-MUA1B-A4-A7 4 9.01
1492-MUA2B-A7-A10 8 14.01
1492-MUA3-A10-A13 12 19.01
1492-MUA4-A13-A17 16 24.01
Max Slots
for
Conversion
Modules
1771-A3B is not listed as it is used for 19 inch wide instrumentation panels.
Notice that the 1756 Chassis Width sometimes exceeds the 1771 Chassis Width, with or without the Power
Supply. The Cover-Plate of the 1492 Conversion Mounting Assembly allows the 1756 Chassis to be Left justified, Right justified or Centered. A complete System Installation Manual ships with the 1492 Conversion Mounting Assembly.
Chassis
Width
PN-114270 DIR 10000060084 (Version 01)
Publication 1492-IN035B-EN-E
(2)
III. Compatiblity
es:
.
Table 2: Bulletin 1771 to 1756 Conversion Modules and Cables
1771
Digital I/O Module
1756
Digital I/O Module
Conversion Module
1492
1492
Cable
1771-IAD 1756-IA16 1492-CM1771-LD001 1492-CONCAB005X 1771-IBD 1756-IB16 1492-CM1771-LD001 1492-CONCAB005X 1771-ICD 1756-IC16 1492-CM1771-LD001 1492-CONCAB005X 1771-IND 1756-IN16 1492-CM1771-LD001 1492-CONCAB005X 1771-IND1 1756-IN16 1492-CM1771-LD001 1492-CONCAB005X
t Not
To understand any issues concerning I/O module compatibility, refer to the Installation Manuals for the specific
771 and 1756 I/O modules involved
The 3 numbers indicate the cable length of each portion of the 1492 Cable. Recommended cable lengths of 0.5M
are shown. Additional cable lengths are as follows:
.0M = 1492-CONCAB010X
IV. Conversion Module Specifications
(Operating specifications are when installed in the Conversion System base / cover-plate assembly)
Specification
Dimensions
Approximate Shipping Weight Storage Temperature -40 to +85°C (-40 to +185°F)
Operating Temperature Operating Humidity Shock Non-operating Operating
Operating Vibration Maximum Operating Voltage 132 Vac at 47 to 63Hz or 132 Vdc Max. Module Operating Current
Per Point: Per Module:
Agency Certifications
Pollution Degree
Environmental Rating
11.81 in. (height) x 4.38 in. (depth) x 1.5 in. (width) 300 mm. (height) x 111.25 mm (depth) x 38.1 mm (width)
258.3 g (0.59 lbs) (includes carton)
0 to 60°C (32 to 140°F) 5 to 95% at 60°C (non-condensing)
50g 30g
2g at 10 to 500Hz (Agrees with 1756 I/O module specifications)
2 Amps 2 Amps
UL Classified: Under UL File Number E113724 CSA CE: compliant for all applicable directives
2
IP20
NOTICE
Refer to the Wiring Diagram(s) for current limits for a specific configuration.
PN-114270 DIR 10000060084 (Version 01)
Publication 1492-IN035B-EN-E
(3)
V. Wiring Diagrams
Conversion: 1771-IAD to 1756-IA16
WARNING
L1
L2
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module
1492-CM1771-LD001
Terminal A
Terminal B Terminal C Terminal D
Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17
Terminal E
A B C D 00 01 02 03 04 05 06 07
1 2 3 4 5 6 7 8 9 10 1110 1211 1312
13
14 1514 1615
1716 17 18 E
19
20
21
22
23
24
25
1492-CONCAB005X
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Cable
10 9 1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 20 19
1756-IA16
L2-0 L2-0 IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 L2-1 L2-1
1771-WH Swing Arm From 1771-IAD
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IA16 RTB. Recommended cable lengths of 0.5M or 1.0M
(005=0.5M, 010=1.0M). See table 2 for other lengths.
The input delay times for the 1771-IAD module versus the 1756-IA16 module are as follows: 1771-IAD 1756-IA16 w/ 1492-CONCAB005X a) Off-to-On Delay 5ms (+/-3ms) @120VAC 10ms max (plus selectable filter) b) On-to-Off Delay 25ms (+/-5ms) 8ms max (plus selectable filter)
The 1771-IAD module is rated 79V to 138V AC or DC. The 1756-IA16 module is rated 74V to 132V AC. If the input
source voltage is DC use a 1756-IH16l and 1492-CM1771-LD002 conversion module.
Refer to your 1771-IAD and 1756-IA16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-925 (Version 02)]
PN-114270 DIR 10000060084 (Version 01)
Publication 1492-IN035B-EN-E
(4)
V. Wiring Diagrams (Continued)
Conversion: 1771-IBD to 1756-IB16
WARNING
+
-
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module 1492-CM1771-LD001
Terminal A Terminal B Terminal C Terminal D
Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17
Terminal E
A B C D 00 01 02 03 04 05 06 07
1 2 3 4 5 6 7 8 9 10 1110
1211 12 13
13
14
1514
1615 16
17 17 18 E
19
20
21
22
23
24
25
1492-CONCAB005X
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Cable
10 9 1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 20 19
1756-IB16
GND-0 GND-0 IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 GND-1 GND-1
1771-WH Swing Arm From 1771-IBD
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IB16 RTB. Recommended cable lengths of 0.5M or
1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
The input delay times for the 1771-IBD module versus the 1756-IB16 module are as follows: 1771-IBD 1756-IB16 w/ 1492-CONCAB005X a) Off-to-On Delay 1ms 1ms (plus selectable filter) b) On-to-Off Delay 1ms 2ms (plus selectable filter)
Refer to your 1771-IBD and 1756-IB16 Installation Manual wiring Schematics and diagrams for more details.
[Reference Doc: 41170-926 (Version 02)]
PN-114270 DIR 10000060084 (Version 01)
Publication 1492-IN035B-EN-E
(5)
V. Wiring Diagrams (Continued)
Conversion: 1771-ICD to 1756-IC16
WARNING
+
--
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module 1492-CM1771-LD001
Terminal A
Terminal B Terminal C Terminal D
Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17
Terminal E
A B C
D
00 01 02 03 04 05 06 07
12 13
16 17 18 E
1492-CONCAB005X 1756-IC16
1
Black
2
White
Red
3
Green
4
Orange
5
Blue
6 7
White/Black
8
Red/Black
Green/Black
9 10
Orange/Black
Blue/Black
1110
Black/White
1211
Red/White
13
Green/White
14
Blue/White
1514
Black/Red
1615
White/Red
17
Orange/Red
Blue/Red
19
Red/Green
20
21 22 23 24 25
Cable
10 9 1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 20 19
RTN RTN IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 RTN RTN
1771-WH Swing Arm From 1771-ICD
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IC16 RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
The input delay times for the 1771-ICD module versus the 1756-IC16 module are as follows:
1771-ICD 1756-IC16 w/ 1492-CONCAB005X a) Off-to-On Delay 6ms (+/-2ms) 1ms max (plus selectable filter) b) On-to-Off Delay 20ms (+/-1ms) 4ms max (plus selectable filter)
The 1771-ICD module is rated 20V to 60V AC or DC. The 1756-IC16 module is rated 30V to 60V DC.
Refer to your 1771-ICD and 1756-IC16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41171-001 (Version 00)]
PN-114270 DIR 10000060084 (Version 01)
Publication 1492-IN035B-EN-E
(6)
V. Wiring Diagrams (Continued)
Conversion: 1771-IND to 1756-IN16
L1
L2
WARNING
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module 1492-CM1771-LD001
Terminal A
Terminal B Terminal C Terminal D
Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17
Terminal E
A B C
D
00 01 02 03 04 05 06 07
12 13
16 17 18 E
1 2 3 4 5 6 7 8 9 10 1110 1211 13 14 1514 1615 17
19 20 21 22 23 24 25
1492-CONCAB005X
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Cable
10 9 1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 20 19
1756-IN16
L2-0 L2-0 IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 L2-1 L2-1
1771-WH Swing Arm From 1771-IND
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IN16 RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
The input delay times for the 1771-IND module versus the 1756-IN16 module are as follows:
1771-IND 1756-IN16 w/ 1492-CONCAB005X a) Off-to-On Delay 35ms (+/-10ms) @24V AC 10ms max (plus selectable filter) b) On-to-Off Delay 45ms (+/-15ms) 10ms max (plus selectable filter)
The 1771-IND module is rated 24V AC or DC. The 1756-IN16 module is rated 10V to 30V AC.
Refer to your 1771-IND and 1756-IN16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-002 (Version 00)]
PN-114270 DIR 10000060084 (Version 01)
Publication 1492-IN035B-EN-E
(7)
V. Wiring Diagrams (Continued)
Conversion: 1771-IND1 to 1756-IN16
L1
L2
WARNING
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module 1492-CM1771-LD001
Terminal A Terminal B
Terminal C Terminal D
Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17
Terminal E
A B C D 00 01 02 03 04 05 06 07
1 2 3 4 5 6 7 8 9 10 1110 1211 1312
13
14 1514 1615
1716 17 18 E
19
20
1492-CONCAB005X
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
21 22 23 24 25
Cable
10 9 1 2 3 4 5 6 7 8 11 12 13 14 15 16 17 18 20 19
1756-IN16
L2-0 L2-0 IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 L2-1 L2-1
1771-WH Swing Arm From 1771-IND1
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IN16 RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
The input delay times for the 1771-IND1 module versus the 1756-IN16 module are as follows:
1771-IND1 1756-IN16 w/ 1492-CONCAB005X
a) Off-to-On Delay 25ms (+/-5ms) @48V AC 10ms max (plus selectable filter) b) On-to-Off Delay 35ms (+/-10ms) 10ms max (plus selectable filter)
The 1771-IND1 module is rated 48V AC. The 1756-IN16 module is rated 10V to 30V AC.
Refer to your 1771-IND1 and 1756-IN16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-003 (Version 00)]
PN-114270 DIR 10000060084 (Version 01)
Publication 1492-IN035B-EN-E