Rockwell Automation 1492-CM1771-LA005 User Manual

Analog I/O Conversion Module
(Cat 1492-CM1771-LA005)
I. Description
This Analog I/O Conversion Module provides for the conversion of (1) 1771, 8 Channel Thermocouple Input module to be converted to (1) 1756, 6 or 8 Channel Thermocouple Input module and consists of the following:
(1) 1771 Thermocouple Module (8ch) to (1) 1756 Thermocouple Module (8ch)
(1) 1492-CM1771-LA005 (Series B) (1) Cable: 1492-CONACAB005G8 (1) Conversion Mounting Assembly: 1492-MUA… (Table 1)
(1) 1771 Thermocouple Module (8ch) to (1) 1756 Thermocouple Module (6ch)
(2) Conversion Module: 1492-CM1771-LA005 (1) Cable: 1492-CONACAB005G (1) Conversion Mounting Assembly: 1492-MUA… (Table 1)
This conversion is accomplished without the removal of any field wires from the existing 1771 Swing Arm. The existing 1771 Swing Arm fits directly onto the edge connector of the 1492 Conversion Module. On one end of the 1492 Cable is (1) connector for the Conversion Module. On the other end is the Removable Terminal Block (RTB) for the 1756 I/O module, as shown in the photo below. The I/O signals are routed through the 1492 Conversion Module and the 1492 Cable to the appropriate terminals on the 1756 I/O module per the Wiring Diagrams in Section V. As standard, both portions of the 1492 Cables are 0.5M long, but we also offer a 1.0M cable length. Refer to the footnotes in Table 2 for further details.
WARNING
PN-114291 DIR 10000060102 (Version 02)
Publication 1492-IN049B-EN-E
Printed in U.S.A.
Conversion Compatibility and Product I.D. Label
25-Pin Connector for cable 1492-CONACAB005
G
1492-CM1771-LA005 Conversion Module
De-energize and lockout any and all power to all I/O eld devices connected to the A-B 1771 I/O chassis, and the power to the 1771 I/O chassis itself. Ensure all power is de-energized and locked out to any device in the control cabinet where the conversion is to be performed. Ensure work is performed by qualied personnel.
II. Installation
The 1492 Conversion Modules must be installed in a 1492 Conversion Mounting Assembly (see Table 1 below). A complete System Installation Manual ships with the 1492 Conversion Mounting Assembly.
1) Determine the quantity of each type of 1771 I/O modules used in the 1771 I/O Chassis to be converted.
2) Select the applicable 1492 Conversion Modules from Table 2, Section III.
3) Review the Max Slots for I/O and Chassis Width data from the Table 1 below.
4) Select a 1756 I/O Chassis which has enough I/O Slots. NOTE: (2) I/O slots are required in the 1756 Chassis for conversions where (1) 1771 I/O module converts to (2) 1756 I/O modules.
5) Select the 1492 Conversion Mounting Assembly which has enough Conversion Module slots. NOTE: (2) Conversion Module slots are required in the 1492 Conversion Mounting Assembly for conversions where (2) 1771 I/O module convert to (1) 1756 I/O modules. NOTE: The 1492 Conversion Mounting Assembly has the same Height & Width foot-print as the 1771 Chassis and is designed to use the same mounting hardware. The combined Depth of the 1492 Conversion Mounting Assembly with the 1756 Chassis mounted on top is 10.25 inches (Controller w/key) or 10.0 inches (Controller w/o key). Dimension drawings are included in the System Installation Manual that ships with the 1492 Conversion Mounting Assembly.
Table 1: Bulletin 1771 to 1756 Chassis Conversion
1771 Chassis 1756 Chassis Conversion Mounting Assembly
Max
Cat. No.
1771-A1B 4 9.01 12.61
1771-A2B 8 14.01 17.61
1771-A3B1
1771-A4B 16 24.01
Slots
for
I/O
12 19.01
Chassis Width
without
Power
Supply
with
Power
Supply
Cat. No.
1756-A4 1756-A7
1756-A7
1756-A10
1756-A10 1756-A13
1756-A13 1756-A17
Max
Slots
Chassis for I/O
12 23.15
12 23.15 16 29.06
Width
3 10.35 6 14.49
6 14.49 9 19.02
9 19.02
Max Slots
Cat. No.
1492-MUA1B-A4-A7 4 9.01
1492-MUA2B-A7-A10 8 14.01
1492-MUA3-A10-A13 12 19.01
1492-MUA4-A13-A17 16 24.01
for
Conversion
Modules
Chassis
Width
1771-A3B is not listed as it is used for 19 inch wide instrumentation panels.
Notice that the 1756 Chassis Width sometimes exceeds the 1771 Chassis Width, with or without the Power Supply. The
Cover-Plate of the 1492 Conversion Mounting Assembly allows the 1756 Chassis to be Left justified, Right justified or Centered. A complete System Installation Manual ships with the 1492 Conversion Mounting Assembly.
PN-114291 DIR 10000060102 (Version 02)
Publication 1492-IN048B-EN-E
(2)
III. Compatibility
es:
1771
1492
Analog I/O Module
Analog I/O Module
1756
1771-IXE 1756-IT6I2 (6 channels) 1492-CM1771-LA005 1492-CONACAB005G 1771-IXHR
1756-IT6I2 (6 channels) 1492-CM1771-LA005 1492-CONACAB005G
1771-IXHR 1756-IRT81I (8 channels) 1492-CM1771-LA005 (B) 1492-CONACAB005G8 1771-IXHR
1756-IRT81I (8 channels) 1492-CM1771-LA005 (B) 1492-CONACAB005G8
t Not
To understand any issues concerning I/O module compatibility, refer to the Installation Manuals for the specific
1771 and 1756 I/O modules involved.
The 3 numbers indicate the length of the 1492 Cable. Recommended cable lengths of 0.5M are shown.
Additional cable lengths are as follows:
1.0M = 1492-CONACAB010G
IV. Conversion Module Specifications
(Operating specifications are when installed in the Conversion System base / cover-plate assembly)
I/O Conversion Module
1492
Cable
Specification Value
Dimensions
Approximate Shipping Weight Storage Temperature -40 to +85 C (-40 to 185° F) Operating Temperature 0 to 60 C (32 to 40° F) Operating Humidity 5 to 95% at 60° C (non-condensing) Shock Non-operating Operating Operating Vibration 2g at 10 to 500Hz (Agrees with 1756 I/O module specification) Maximum Operating Voltage 30 Vdc Max. Module Operating Current
Per Point: Per Module:
Agency Certifications
Pollution Degree 2 Environmental Rating IP20
11.81 in. (height) x 4.38 in. (depth) x 1.5 in. (width) 300 mm. (height) x 111.25 mm (depth) x 38.1 mm (width)
X g (Y lbs) (includes carton)
50g 30g
2 Amps 12 Amps
NOTICE
NOTICE
UL Classified: Under UL File Number E113724 CSA CE: compliant for all applicable directives
Refer to the Wiring Diagram(s) for current limits for a specic congura-
PN-114291 DIR 10000060102 (Version 02)
Publication 1492-IN048B-EN-E
(3)
V. Wiring Diagrams
Conversion: 1771-IXE to 1756-IT6I2
WARNING
Thermocouple
There are several key application considerations and system specications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module 1492-CM1771-LA005
1492-CONACAB005G
+
-
Input 1+ 5 Input 1­Input 2+ Input 2-
Input 3+ Input 3­Input 4+ Input 4-
Input 5+ Input 5­Input 6+
Input 6-
18 17 16
15 14 13 12 11
10 9
T
8
7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5
4 3 2 1
SH
Orange/Red White/Red Black/Red Blue/White Green/White Red/White Black/White Blue/Black Orange/Black Green/Black Red/Black White/Black Blue Orange
Cable
6 7 8 9 10 11 12 13 14 15 16 3 4
1756-IT6I2
IN-0 RTN-0 IN-1 RTN-1 IN-2 RTN-2 IN-3 RTN-3 IN-4 RTN-4 IN-5 RTN-5 CJC+ CJC-
1771-WI Swing Arm From 1771-IXE
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IT6I2 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must
remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA005 module. The pre-wired cable used between the 1492-CM1771-LA005 module and the 1756-IT6I2 [1492-CONACAB005G] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
The 1771-IXE has 8 input channels. The 1756-IT6I2 only has 6 input channels. This module combination can only be used to convert the
signals if 6 or less channels were used on the 1771-IXE.
The 1771-IXE has built CJC (cold junction compensation) into the swing-arm. The conversion module [1492-CM1771-LA005] passes this CJC
signal to the 1756-IT6I2. Ensure that the 1756-IT6I2 is configured for external CJC.
The 1771-IXE input configuration was software configured, as is the 1756-IT6I2. Please ensure the correct configuration in the 1756-IT6I2.
Refer to your 1771-IXE and 1756-IT6I2 Installation and User Manuals for additional information concerning comparisons of module wiring,
features and configuration details. [Reference Doc: 41170-951 (Version 02)]
PN-114291 DIR 10000060102 (Version 02)
Publication 1492-IN048B-EN-E
(4)
V. Wiring Diagrams (Cont’d)
Conversion: 1771-IXHR to 1756-IT6I2
WARNING
Thermocouple
+
-
There are several key application considerations and system specications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module 1492-CM1771-LA005
Cable
1492-CONACAB005G 1756-IT6I2
Input 1+ 5 Input 1­Input 2+
Input 2­Input 3+
Input 3­Input 4+ Input 4-
Input 5+
Input 5­Input 6+ Input 6-
18 17 16
15 14 13 12 11
10 9
T
8
7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10
9 8 7 6 5
4 3 2 1
SH
Orange/Red White/Red Black/Red Blue/White Green/White Red/White Black/White Blue/Black Orange/Black Green/Black Red/Black White/Black Blue Orange
6 7 8 9 10 11 12 13 14 15 16 3 4
IN-0 RTN-0 IN-1 RTN-1 IN-2 RTN-2 IN-3 RTN-3 IN-4 RTN-4 IN-5 RTN-5 CJC+ CJC-
1771-WI Swing Arm From 1771-IXHR
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IT6I2 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA005 module. The pre-wired cable used between the 1492-CM1771-LA005 module and the 1756-IT6I2 [1492-CONACAB005G] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
The 1771-IXHR has 8 input channels. The 1756-IT6I2 only has 6 input channels. This module combination can only be used to convert the signals if 6 or less channels were used on the 1771-IXHR.
The 1771-IXHR has built CJC (cold junction compensation) into the swing-arm. The conversion module [1492-CM1771-LA005] passes this CJC signal to the 1756-IT6I2. Ensure that the 1756-IT6I2 is configured for external CJC.
The 1771-IXHR input configuration was software configured, as is the 1756-IT6I2. Please ensure the correct configuration in the 1756-IT6I2.
Refer to your 1771-IXHR and 1756-IT6I2 Installation and User Manuals for additional information concerning comparisons of module wiring,
features and configuration details. [Reference Doc: 41171-035 (Version 00)]
PN-114291 DIR 10000060102 (Version 02)
Publication 1492-IN048B-EN-E
(5)
V. Wiring Diagrams (Cont’d)
Conversion: 1771-IXHR (1) to 1756-IRT8I (1)
Thermocouple
+
-
WARNING
In_CH0+ In_CH0­In_CH1+ In_CH1­In_CH2+ In_CH2­In_CH3+ In_CH3-
CJC+ CJC-
In_CH4+ In_CH4­In_CH5+ In_CH5­In_CH6+ In_CH6-
In_CH7+ In_CH7-
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module
1492-CM1771-LA005 SER “B”
18 17 16
15 14 13 12 11
10 9
T
8
7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5
4 3 2 1
1492-CONACAB005G8
Orange/Red White/Red Black/Red Blue/White Green/White Red/White Black/White Blue/Black Orange/Black Green/Black Red/Black White/Black Blue Orange
Red/Black White/Black Blue Orange
Cable
1756-IRT8I
3
In_CH0+
4
In_CH0-
7
In_CH1+
8
In_CH1-
11
In_CH2+
12
In_CH2-
15
In_CH3+
16
In_CH3-
19
In_CH4+
20
In_CH4-
23
In_CH5+
24
In_CH5-
1
CJC+
2
CJC-
27
In_CH6+
28
In_CH6-
31
In_CH7+
32
In_CH7-
SH
5 6
9
10 13 14
17
1771-WI Swing Arm From 1771-IXHR
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
This Bul. 1492 cable consists of a cable wired to one 1756-IRT8I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M).
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA005 SER”B” module. The pre-wired cable used between the 1492-CM1771-LA005 SER”B” module and the 1756-IRT8I [1492-CONACAB005G8] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
The 1771-IXHR has built CJC (cold junction compensation) into the swing-arm. The conversion module [1492-CM1771-LA005 SER”B”]
passes this CJC signal to the 1756-IRT8I. Ensure that the 1756-IRT8I is configured for external CJC.
The 1771-IXHR input configuration was software configured, as is the 1756-IRT8I. Please ensure the correct configuration
in the 1756-IRT8I.
Refer to your 1771-IXHR and 1756-IRT8I Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.
N.C. N.C.
N.C. N.C. N.C. N.C.
N.C.
18 21 22 25
26 29 30
N.C. N.C. N.C. N.C. N.C. N.C. N.C.
PN-114291 DIR 10000060102 (Version 02)
Publication 1492-IN048B-EN-E
Printed in U.S.A.
(6)
V. Wiring Diagrams (Cont’d)
Conversion: 1771-IXE (1) to 1756-IRT8I (1)
Thermocouple
+
-
WARNING
There are several key application considerations and system specications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module
Cable
1756-IRT8I
3
In_CH0+
4
In_CH0-
7
In_CH1+
8
In_CH1-
11
In_CH2+
12
In_CH2-
15
In_CH3+
16
In_CH3-
19
In_CH4+
20
In_CH4-
23
In_CH5+
24
In_CH5-
1
CJC+
2
CJC-
27
In_CH6+
28
In_CH6-
31
In_CH7+
32
In_CH7-
In_CH0+ In_CH0­In_CH1+ In_CH1­In_CH2+ In_CH2­In_CH3+ In_CH3-
CJC+ CJC-
In_CH4+ In_CH4­In_CH5+ In_CH5­In_CH6+ In_CH6-
In_CH7+ In_CH7-
1492-CM1771-LA005 SER “B”
18 17 16
15 14 13 12 11
10 9
T
8
7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10
9 8 7 6 5
4 3 2 1
1492-CONACAB005G8
Orange/Red White/Red Black/Red Blue/White Green/White Red/White Black/White Blue/Black Orange/Black Green/Black Red/Black White/Black Blue Orange
Red/Black White/Black Blue Orange
SH
5 6
9
10 13 14
17
1771-WI Swing Arm From 1771-IXE
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
This Bul. 1492 cable consists of a cable wired to one 1756-IRT8I RTB. Recommended cable lengths of
0.5M or 1.0M (005=0.5M, 010=1.0M).
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was
the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA005 SER”B” module. The pre-wired cable used between the 1492-CM1771-LA005 SER”B” module and the 1756-IRT8I [1492-CONACAB005G8] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
The 1771-IXE has built CJC (cold junction compensation) into the swing-arm. The conversion module [1492-CM1771-LA005 SER”B”]
passes this CJC signal to the 1756-IRT8I. Ensure that the 1756-IRT8I is configured for external CJC.
The 1771-IXE input configuration was software configured, as is the 1756-IRT8I. Please ensure the correct configuration
in the 1756-IRT8I.
Refer to your 1771-IXE and 1756-IRT8I Installation and User Manuals for additional information concerning comparisons
of module wiring, features and configuration details.
N.C. N.C.
N.C. N.C. N.C. N.C.
N.C.
18 21 22 25
26 29 30
N.C. N.C. N.C. N.C. N.C. N.C. N.C.
PN-114291 DIR 10000060102 (Version 02)
Publication 1492-IN048B-EN-E
Printed in U.S.A.
(7)
PN-114291 DIR 10000060102 (Version 02)
Publication 1492-IN048B-EN-E
Printed in U.S.A.
Loading...