This Analog I/O Conversion Module provides for the conversion of (1) 1771, 16 Channel I/O module to be
converted to (1) 1756, 16 Channel I/O module and consists of the following:
This conversion is accomplished without the removal of any field wires from the existing 1771 Swing Arm. The
existing 1771 Swing Arm fits directly onto the edge connector of the 1492 Conversion Module. On one end of the
1492 Cable is (1) connector for the Conversion Module. On the other end is the Removable Terminal Block (RTB)
for the 1756 I/O module, as shown in the photo below. The I/O signals are routed through the 1492 Conversion
Module and the 1492 Cable to the appropriate terminals on the 1756 I/O module per the Wiring Diagrams in
Section V. As standard, both portions of the 1492 Cables are 0.5M long, but we also offer a 1.0M cable length.
Refer to the footnotes in Table 2 for further details.
WARNING
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E
Printed in U.S.A.
Conversion Compatibility
and Product I.D. Label
25-Pin Connector for cable
1492-CONACAB005
1492-CM1771-LA001 Conversion Module
De-energize and lockout any and all power to all I/O field devices connected to the A-B 1771 I/O chassis,
and the power to the 1771 I/O chassis itself. Ensure all power is de-energized and locked out to any
device in the control cabinet where the conversion is to be performed. Ensure work is performed by
qualified personnel.
A OR -CONACAB005B
II. Installation
The 1492 Conversion Modules must be installed in a 1492 Conversion Mounting Assembly (see Table 1 below). A
complete System Installation Manual ships with the 1492 Conversion Mounting Assembly.
1) Determine the quantity of each type of 1771 I/O modules used in the 1771 I/O Chassis to be converted.
2) Select the applicable 1492 Conversion Modules from Table 2, Section III.
3) Review the Max Slots for I/O and Chassis Width data from the Table 1 below.
4) Select a 1756 I/O Chassis which has enough I/O Slots.
NOTE: (2) I/O slots are required in the 1756 Chassis for conversions where (1) 1771 I/O module converts to (2) 1756 I/O
modules.
5) Select the 1492 Conversion Mounting Assembly which has enough Conversion Module slots.
NOTE: (2) Conversion Module slots are required in the 1492 Conversion Mounting Assembly for conversions where (2)
1771 I/O module convert to (1) 1756 I/O modules.
NOTE: The 1492 Conversion Mounting Assembly has the same Height & Width foot-print as the 1771 Chassis and is
designed to use the same mounting hardware. The combined Depth of the 1492 Conversion Mounting Assembly with the
1756 Chassis mounted on top is 10.25 inches (Controller w/key) or 10.0 inches (Controller w/o key). Dimension drawings
are included in the System Installation Manual that ships with the 1492 Conversion Mounting Assembly.
1771-A3B is not listed as it is used for 19 inch wide instrumentation panels.
Notice that the 1756 Chassis Width sometimes exceeds the 1771 Chassis Width, with or without the Power Supply. The
Cover-Plate of the 1492 Conversion Mounting Assembly allows the 1756 Chassis to be Left justified, Right justified or
Centered. A complete System Installation Manual ships with the 1492 Conversion Mounting Assembly.
To understand any issues concerning I/O module compatibility, refer to the Installation Manuals for the specific
1771 and 1756 I/O modules involved.
The 3 numbers indicate the length of the 1492 Cable. Recommended cable lengths of 0.5M are shown.
Additional cable lengths are as follows:
1.0M = 1492-CONACAB010A
1.0M = 1492-CONACAB010B
IV. Conversion Module Specifications
I/O Conversion Module
1492
Cable
(Operating specifications are when installed in the Conversion System base / cover-plate assembly)
Specification
Dimensions
Approximate Shipping Weight
Storage Temperature -40 to +85°C (-40 to +185°F)
Operating Temperature
Operating Humidity
Shock
Non-operating
Operating
Operating Vibration
Maximum Operating Voltage
Max. Module Operating Current
Per Point:
Per Module:
Agency Certifications
Pollution Degree
Environmental Rating IP20
11.81 in. (height) x 4.38 in. (depth) x 1.5 in. (width)
300 mm. (height) x 111.25 mm (depth) x 38.1 mm (width)
250.6 g (0.55 lbs) (includes carton)
0 to 60°C (32 to 140°F)
5 to 95% at 60°C (non-condensing)
50g
30g
2g at 10 to 500Hz (Agrees with 1756 I/O module specifications)
30 Vdc
2 Amps
12 Amps
UL Classified: Under UL File Number E113724
CSA
CE: compliant for all applicable directives
2
NOTICE
Value
Refer to the Wiring Diagram(s) for
current limits for a specific configuration.
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E
(3)
V. Wiring Diagrams
Conversion: 1771-IFE to 1756-IF16 (Single-ended Current)
Power Supply
WARNING
2-Wire Transmitter
Transmitter
+
-
There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Module Common
Module Common
Module Common
Module Common
Module Common
Channel 9
Channel 10
Channel 11
Channel 12
Channel 13
Channel 14
Channel 15
Channel 16
1771-WG Swing Arm
From 1771-IFE
Conversion Module
1492-CM1771-LA001
1
2
3
4
6
7
8
9
5
10
15
20
21
11
12
13
14
16
17
18
19
1492-CONACAB005B1756-IF16
Black
1
White
2
Red
3
Green
4
Orange
5
Blue
6
White/Black
7
Red/Black
8
Green/Black
9
Orange/Black
10
Blue/Black
11
Black/White
12
13
Green/White
14
Blue/White
15
Black/Red
16
White/Red
17
Orange/Red
18
Blue/Red
19
Red/Green
20
Orange/Green
21
22
23
24
25
SH
Cable
2
4
6
8
12
14
16
18
10
28
20
22
24
26
30
32
34
36
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
IN-0
IN-1
IN-2
IN-3
IN-4
IN-5
IN-6
IN-7
RT N
RT N
IN-8
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15
iRTN-0
iRTN-1
iRTN-2
iRTN-3
RT N
iRTN-4
iRTN-5
iRTN-6
iRTN-7
iRTN-8
iRTN-9
iRTN-10
iRTN-11
RT N
iRTN-12
iRTN-13
iRTN-14
iRTN-15
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
See table 2 for other lengths.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must
remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA001 module.
The pre-wired cable used between the 1492-CM1771-LA001 module and the 1756-IF16 [1492-CONACAB005B] provides a shield ground lug to
ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding
stud.
This design assumes that all inputs on the1771-IFE were connected to current transmitters. If there was a mix of current and voltage
transmitters, then modification of the pre-wired cable [1492-CONACAB005B] will need to occur at the 1756-IF16 terminal block.
Refer to the 1756-IF16 Installation Manual for modification details.
The 1771-IFE analog input ranges were configured via software, as is the input range for the 1756-IF16. Please ensure the correct input range
is configured in the 1756-IF16.
Refer to your 1771-IFE and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring,
features and configuration details. [Reference Doc: 41170-944 (Version 02)]
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E
(4)
V. Wiring Diagrams (Cont’d)
Conversion: 1771-IFE to 1756-IF16 (Single-ended Voltage)
+
Power Supply
WARNING
3-Wire Transmitter
Transmitter
-
There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
See table 2 for other lengths.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must
remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA001 module.
The pre-wired cable used between the 1492-CM1771-LA001 module and the 1756-IF16 [1492-CONACAB005A] provides a shield ground lug to
ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding
stud.
This design assumes that all inputs on the1771-IFE were connected to current transmitters. If there was a mix of current and voltage
transmitters, then modification of the pre-wired cable [1492-CONACAB005A] will need to occur at the 1756-IF16 terminal block.
Refer to the 1756-IF16 Installation Manual for modification details.
The 1771-IFE analog input ranges were configured via software, as is the input range for the 1756-IF16. Please ensure the correct input range
is configured in the 1756-IF16.
Refer to your 1771-IFE and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring,
features and configuration details. [Reference Doc: 41170-945 (Version 02)]
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E
(5)
V. Wiring Diagrams
Conversion: 1771-IFF to 1756-IF16 (Single-ended Current)
Power Supply
WARNING
2-Wire Transmitter
Transmitter
+
-
1771-WG Swing Arm
From 1771-IFF
There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Module Common
Module Common
Module Common
Module Common
Module Common
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
See table 2 for other lengths.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must
remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA001 module.
The pre-wired cable used between the 1492-CM1771-LA001 module and the 1756-IF16 [1492-CONACAB005B] provides a shield ground lug to
ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding
stud.
This design assumes that all inputs on the 1771-IFF were connected to current transmitters. If there was a mix of current and voltage
transmitters, then modification of the pre-wired cable [1492-CONACAB005B] will need to occur at the 1756-IF16 terminal block. Refer to the
1756-IF16 Installation Manual for modification details.
The 1771-IFF analog input ranges were configured via software, as is the input range for the 1756-IF16. Please ensure the correct input range
is configured in the 1756-IF16.
Refer to your 1771-IFF and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring,
features and configuration details. [Reference Doc: 41171-023 (Version 00)]
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E
(6)
V. Wiring Diagrams (Cont’d)
Conversion: 1771-IFF to 1756-IF16 (Single-ended Voltage)
+
Power Supply
WARNING
3-Wire Transmitter
Transmitter
-
There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Module Common
Module Common
Module Common
Module Common
Module Common
Channel 9
Channel 10
Channel 11
Channel 12
Channel 13
Channel 14
Channel 15
Channel 16
Conversion Module
1492-CM1771-LA001
1
2
3
4
6
7
8
9
5
10
15
20
21
11
12
13
14
16
17
18
19
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
24
25
SH
23
1492-CONACAB005A1756-IF16
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
Cable
2
IN-0
4
IN-1
6
IN-2
8
IN-3
12
IN-4
14
IN-5
16
IN-6
18
IN-7
10
RTN
9
RTN
27
RTN
28
RTN
20
IN-8
22
IN-9
24
IN-10
26
IN-11
30
IN-12
32
IN-13
34
IN-14
36
IN-15
1771-WG Swing Arm
From 1771-IFF
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
See table 2 for other lengths.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must
remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA001 module.
The pre-wired cable used between the 1492-CM1771-LA001 module and the 1756-IF16 [1492-CONACAB005A] provides a shield ground lug to
ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding
stud.
This design assumes that all inputs on the1771-IFF were connected to voltage transmitters. If there was a mix of current and voltage
transmitters, then modification of the pre-wired cable [1492-CONACAB005A] will need to occur at the 1756-IF16 terminal block. Refer to the
1756-IF16 Installation Manual for modification details.
The 1771-IFF analog input ranges were configured via software, as is the input range for the 1756-IF16. Please ensure the correct input range
is configured in the 1756-IF16.
Refer to your 1771-IFF and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring,
features and configuration details. [Reference Doc: 41171-024 (Version 00)]
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E
(7)
PN-114287
DIR 10000060098 (Version 01)
Publication 1492-IN045B-EN-E
Printed in U.S.A.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.