Rockwell Automation 14885P User Manual

Installation Instructions
Bulletin 1485P KwikLinkt Lite, Field Network Pressure-Welded Connectors
Power Supply T erminal Block with Terminator and Thin Cable Flat Cable Conversion Connectors
IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE.
Refer to the product catalog pages for additional information.
Safety Precautions
S Do not pull on the connector or the cable. The connector
S To prevent connector damage and broken cable
conductors, install the cable and connector in locations where they will not be stepped on, entangled in people’s legs, or otherwise subjected to excessive strain. If installation in such locations cannot be avoided, install protective covers to protect the connector and cable.
S Do not mate the connector in the wrong direction. The
connector may be damaged.
S Do not use the connector if the lock lever is broken. The
connector may become disconnected, possibly causing machine malfunction.
S When installing the cable, do not bend it past the
specifications given for the cable.
S Do not apply a current exceeding the rated current.
S Do not use pliers or similar tools to remove the connector.
S Hold the connector firmly when working on it, but do not
apply excessive force to it.
S Once a connector has been assembled do not take it apart
and reuse it. If the assembly is not successful, use a new connector to redo the operation.
S This connector is not water-proof. Do not allow it to be
subjected to water or oil during operation.
S Be careful when using a sharp knife to cut the cable.
S Do not use dirty cables, crimp terminals, or cables other
than the specified cables. Doing so may cause contact failure or an increase in ambient temperature.
S Be careful not to injure your fingers when crimping the
cables.
S Be sure to hold the connector firmly in place when
tightening the screws.
Precautions for Correct Use
S Wiring Work
S Do not perform wiring work or connect/disconnect the
connector while the power supply is ON. Electrical shock or machine malfunction may result.
S Wiring the cable according to the wiring diagram for the
machine being used.
S Confirm that there are no short-circuits caused by wires
sticking out of the connector.
S Connecting the Connector
S Always hold onto the body of the connector when
connecting/disconnecting the connector.
S Be sure the connector is connected completely to the
back and then pull in the reverse direction to be sure the connector will not disconnect.
S Confirm that the cable labels and cable colors match
before connecting the cable.
Power Supply Terminal Block with Terminator
Part Names
1485P--K1TLR4
Wiring Procedure for the End that Is Crimped
1. Cutting the Cable
S Cut the cable at a 90angle to the length of the cable.
S To prevent short-circuits, be sure to cut the cable with a
sharp knife and be sure there are no short conductor wires protruding from the inside of the cable sheath.
2. Temporarily Securing the Cover on the Terminal Block
S Fold the cover closed and check that the hooks on the top
and bottom securely fasten into place.
S Temporarily connect the cover to the main unit.
1
3. Attaching the Cable
S Match the cable label with the cable colors and insert the
cable accordingly.
S The back of the main unit acts as a cable stop. Insert the
cable all the way to the cable stop.
4. Crimping the Connector
S Before crimping, be sure that the cable is inserted all the
way to the cable stop with no gaps.
S Crimp at the center of the connectors using the DWT--A01
pliers.
S Aftercrimping,checktobesurethatthecablewas
crimped correctly.
Check to be sure that the housing lock is fully hooked
onto the cover tabs.
After crimping, check to be sure that there are no gaps
between the cover and the main unit.
Wiring Procedure for the End that Is Attached Using Screws
1. Connect the Wires
S Connect the wires with the crimp terminals to the terminals.
S Connect crimp terminals for M3 screws. The appropriate
tightening torque is 0.30.5 Nm(2.6554.425 lbf in). Use a screwdriver that is an appropriate size for the M3 screws.
Thin-Cable Flat-Cable Conversion Connector
Part Names
1485P--K1GK4
Wiring Procedure
1. Cutting the Cable
S Cut the cable at a 90angle to the length of the cable.
S To prevent short circuits, be sure to cut the cable with a
sharp knife and be sure that there are no short conductor wires protruding from inside the cable sheath.
2. Attaching the Cable
S Match the cable label with the cable colors and insert the
cable accordingly.
S The cover is semitransparent, which allows you to check to
be sure that the cable is fully inserted.
3. Crimping the Connector
S Before crimping, be sure that the cable is inserted all the
way to the back and there are no gaps.
S Crimp at the center of the connectors using the
1485AKCRIMP flat cable crimp tool.
2