Rockwell Automation 1442 User Manual

User Manual
1442 Eddy Current Probe System
Important User Information
IMPORTANT
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
This manual contains new and updated information. Changes throughout this revision are marked by change bars, as shown to the right of this paragraph.
New and Updated Information
Temperature ranges and wire sizes were corrected as appropriate in this manual.
Top ic Pag e
Corrected temperature range 13, 17
Added Speed Measurements section and relocated speed measurement figure 16
Corrected wire size 37, 51
Rockwell Automation Publication ICM-UM004C-EN-E - February 2014 3
Summary of Changes
Notes:
4 Rockwell Automation Publication ICM-UM004C-EN-E - February 2014

Table of Contents

Preface
Installation
Measurement Principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
System Configuration Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1
Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Driver Installation Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Sensor Installation Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Extension Cable Installation Environment . . . . . . . . . . . . . . . . . . . . . 17
Outer Dimensions and Part Nomenclature. . . . . . . . . . . . . . . . . . . . . . . . . 17
1442 Sensor Outer Dimensions and Part Nomenclature . . . . . . . . . 17
Extension Cable Outer Dimensions and Part Nomenclature . . . . . 22
Driver Outer Dimensions and Part Nomenclature . . . . . . . . . . . . . . 24
Install the Driver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Mount the Driver on the Housing or Panel . . . . . . . . . . . . . . . . . . . . . 25
Mount the Driver to a DIN Rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Install the Sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Use a Sensor Mounting Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Use a Stinger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Adjust the Gap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Connect the Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Connect the Extension Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Connect the Sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Connect the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Verify the Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Set Gap Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Recommended Specifications for the Monitor Cable . . . . . . . . . . . . . . . . 37
Maintenance and Inspection
Individual Characteristic Data
Chapter 2
Periodic Inspection Intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Unit Life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Troubleshoot the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Chapter 3
Characteristic Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Standard Static Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Sensor Temperature Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Driver Temperature Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Static Characteristic Effect Due to Power Source Voltage Variation . 44
Static Characteristic Effect by Target Material . . . . . . . . . . . . . . . . . . 45
Static Characteristic Effect Due to Target Diameter. . . . . . . . . . . . . 46
Static Effect by Target Curved Surface . . . . . . . . . . . . . . . . . . . . . . . . . 47
Static Characteristic Effect Due to Target End Face . . . . . . . . . . . . . 48
Rockwell Automation Publication ICM-UM004C-EN-E - February 2014 5
Table of Contents
Static Characteristic Effect Due to Side Wall. . . . . . . . . . . . . . . . . . . . 49
Frequency Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Appendix A
Wire the Unit to a Monitor System Index
Cable Wiring/Laying Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6 Rockwell Automation Publication ICM-UM004C-EN-E - February 2014

Preface

This manual describes how to install and use the 1442 Series Eddy Current Probe System.
The 1442 Series eddy current probe system performs non-contact measurement of the distance between the sensor and the measured object (target), and outputs a proportional voltage signal. The static component of the measurement is the "gap," the absolute (DC) distance from the target surface to the probe tip. The dynamic component of the measurement is the "vibration," the cyclical (AC) movement of the target toward and away from the probe.
By combining this system with an Allen-Bradley® 1440 or 1444 Series measurement module, you can measure the vibration of a rotating shaft, its eccentricity, thrust position and rotating speed. The system is used for continuous measurement or monitoring of shafts rotating at high speeds, such as turbines, generators, and compressors.

Measurement Principles

The gap between the sensor and the target is found according to the following principles:
When an approximately 1 MHz high frequency current is supplied from the oscillator to the sensor, a high frequency magnetic field is created at the sensor tip.
The inter-linkage of the high frequency magnetic flux on the target induces an eddy current that flows on the target surface.
When the eddy current flows on the target surface, a magnetic field is created at the target side, and the sensor impedance changes.
When this change in output of the oscillator is detected, the distance versus output voltage is made linear by a linearizer circuit, and the result is output.
Rockwell Automation Publication ICM-UM004C-EN-E - February 2014 7
Preface
IMPORTANT
You can find the gap between the sensor and the target by measuring the sensor impedance if the following relationships are identified:
Relationship between the sensor and the target gap.
Relationship of the sensor impedance.

System Configuration Example

This system is designed to fulfill the specifications when used under the following configuration.
Always combine the components of this system (sensor, extension cable, and driver) to configure it as follows. If this system is not configured as shown below, or if the 1442 extension cable is not used in combining the 1442 sensor and driver, the output characteristics will differ dramatically.
Figure 1 - System Configuration Example
Sensor Extension Cable System Cable Length Driver
0.5 m (1.64 ft) + 4.5 m (14.76 ft) = 5.0 m (16.40 ft) 1442-DR-xx50
1.0 m (3.28 ft) + 4.0 m (13.12 ft) = 5.0 m (16.40 ft) 1442-DR-xx50
0.5 m (1.64 ft) + 8.5 m (27.89 ft) = 9.0 m (29.53 ft) 1442-DR-xx90
1.0 m (3.28 ft) + 8.0 m (26.25 ft) = 9.0 m (29.53 ft) 1442-DR-xx90
(1)
(1) Where xx = appropriate code for probe size.
8 Rockwell Automation Publication ICM-UM004C-EN-E - February 2014
Preface

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
1442 Eddy Current Probe Systems Specifications Technical Data, publication 1442-TD001. Provides specifications for the 1442 Eddy Current Probe System.
Turbine Supervisory Instrumentation System Selection Guide, publication GMSI10-
SG002.
Provides details to help you choose a Turbine Supervisory Instrumentation system.
You can view or download Rockwell Automation publications at http://
www.rockwellautomation.com/literature. To order paper copies of technical
documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Rockwell Automation Publication ICM-UM004C-EN-E - February 2014 9
Preface
Notes:
10 Rockwell Automation Publication ICM-UM004C-EN-E - February 2014
Chapter 1
TIP
Installation
This chapter describes how to install a 1442 Series Eddy Current Probe System.
ATTENTION: Always ground the system. Never apply power until all wiring work and connection work has been completed. If this is not followed, there is a possibility of electrocution.
Installation work, wiring, and connections must be performed by a person with knowledge in instrumentation.
ATTENTION: Be sure to adhere to the following guidelines:
Before touching this unit, be sure to touch a metal section near by to
discharge any static electricity. The device can be damaged if exposed to static electricity from a person’s body.
Before applying power, make sure that all wiring is properly connected. There is a possibility of damage to the unit and fire if improperly connected.
Install this unit away from motors and relays.
Install the input/output signal cables away from power system and
control system cables. Noise occurring from the motor or relay can adversely affect the measurement value. We recommend using separate wiring ducts.
Do not pull or bend the sensor cables and extension cables with excessive force. The conductor in the cable can get cut off.
The allowable tension of the sensor cables and extension cables is
98.1 N•m (10 kgf•m). The allowable bend radius is as follows:
Without armored cable: 30 mm (1.18 in.)
With armored cable: 50 mm (1.97 in.)
After completing the installation, make sure all connections are correct
and tight before powering the system.
Refer to Appendix A on page 51 for recommended cable wiring, and installation methods.
Rockwell Automation Publication ICM-UM004C-EN-E - February 2014 11
Chapter 1 Installation
60 mm (2.4 in.)

Installation Environment

Driver Installation Environment
Install the driver in a location that satisfies the following environmental and installation conditions.
Environmental Conditions
Feature Specification
Ambient temperature Must be in a range of -30…80 °C (-22…176 °F) when devices are operating.
Ambient humidity Must be in a range of 30…95% RH (noncondensing) when devices are operating.
Vibration condition Must be 10 m/s
Air cleanliness We recommend an air dust-particle amount of 0.2 mg/m3 or less.
We recommend an especially low amount of corrosive gasses, such as hydrogen sulfide, NOx gas, and chlorine, and conductive particles, such as iron dust and carbon. The allowable amounts of hydrogen sulfide and NOx gas, based on JEIDA­29 (1979) Class S1, are shown below.
JEIDA: Japanese Electronic Industry Development Association
2
(1 g) or less at 10…150 Hz.
JEIDA-29 (1979) CLASS S1 Hydrogen sulfide: 0.01 ppm or less, NOx gas: 0.05 ppm or less (Ambient temperature: 25 °C ± 5 °C (77 °F ± 9 °F), humidity: 40…80%
RH)
Install Conditions
If there are walls or other obstacles at the cable connection surface of the driver, make sure to keep spacing as illustrated below. Take care not to bend the cable excessively.
12 Rockwell Automation Publication ICM-UM004C-EN-E - February 2014
Installation Chapter 1
Do not locate above heat emitting objects.
Sensor Installation Environment
Install the sensor at a location that satisfies the following environmental and installation conditions.
Environmental Conditions
Feature Specification
Ambient temperature ATEX applications must be in a range of -35…80 °C (-31…176 °F) when devices
Ambient humidity Must be in a range of 30…95% RH (noncondensing) when devices are operating.
Vibrational conditions Must be 10 m/s
Air cleanliness We recommend an air dust-particle amount of 0.2 mg/m3 or less.
are operating. CSA applications must be in a range of -35…85 °C (-31…185 °F) when devices
are operating. Other applications must be in a range of -35…177 °C (-31…350 °F) when devices
are operating
2
measurement cannot be made.)
We recommend an especially low amount of corrosive gasses, such as hydrogen sulfide, NOx gas, and chlorine, and conductive particles, such as iron dust and carbon. The allowable amount sof hydrogen sulfide and NOx gas, based on JEIDA­29 (1979) Class S1, are shown below.
JEIDA: Japanese Electronic Industry Development Association
(1 g) or less at 10…150 Hz. (If the sensor vibrates, an accurate
JEIDA-29 (1979) CLASS S1 Hydrogen sulfide: 0.01 ppm or less, NOx gas: 0.05 ppm or less (Ambient temperature: 25 °C ± 5 °C (77 °F ± 9 °F), humidity: 40…80%
RH)
Installation Conditions
Do not install at a location exposed to rain or other moisture. Moisture can lead to reduced sensitivity of the sensor, and reduced insulation.
A target surface area of not less than three times the tip diameter centered on the sensor is required, as illustrated below.
Rockwell Automation Publication ICM-UM004C-EN-E - February 2014 13
Chapter 1 Installation
40 mm (1.57 in.) or more
40 mm (1.57 in.) or more
When placing other sensors next to each other, separate the sensor tops by not less than 10 times the sensor tip diameter to prevent interference.
The sensor must be installed on a surface with adequate rigidity that is not affected by an outside vibration. If the sensor vibrates, an accurate measurement cannot be taken.
For shapes and dimensions around the sensor, refer to the installation examples (1…3) below. If a piece of metal other than the target is near the sensor, an accurate reading cannot be taken.
If it is unavoidable to install the sensor as illustrated in examples 4…7, check the characteristics at the attachment completed conditions.
Table 1 - Installation Examples
Example Description
Example 1 (most recommended) Dimension X is to be not less than 1.2 times the tip
Example 2 (recommended) Dimension X is to be not less than 1.2 times the tip
Example 3 (recommended) After constructing as shown in example 2, the area shown
diameter.
diameter Dimension Y is to be not less than 3 times the tip
diameter.
by the shaded line in the illustration is filled with resin or other insulating material.
14 Rockwell Automation Publication ICM-UM004C-EN-E - February 2014
Installation Chapter 1
Table 1 - Installation Examples
Example Description
Example 4 If dimension X is less than 1.2 times the tip diameter, the
measurement will be affected by the attachment plate.
Example 5 If dimension Y is less than 3 times the tip diameter, the
Example 6 If the attachment plate around the sensor top is
Example 7 If the target and the sensor top are not parallel
measurement will be affected by the attachment plate.
chamfered, it will be affected by the attachment plate.
(dimension X1 and X2 are not the same), it will affect the reading.
Example 8 If dimension X is less than the minimum linear range from
Rockwell Automation Publication ICM-UM004C-EN-E - February 2014 15
sensor tip specification for the sensor, the measurement will not be accurate.
Chapter 1 Installation
The characteristics of output (V) and gap (mm) are as shown in the graph below.
Speed Measurements
Assumes measurements are made with a 5 mm or 8 mm probe.
Figure 2 - Dimension of target (recommended for rotational speed measurement):
D
B
A
C
D D
A
C
B
C
mm mils
Recommended dimension of target (mm)
A 6A ≥ 236
B 7B 275
C 2.5 C 98
D 15 D 590
Recommended set gap (mm) 1.0...1.5 39...59
16 Rockwell Automation Publication ICM-UM004C-EN-E - February 2014
Installation Chapter 1
Extension Cable Installation Environment
Install the extension cable in a location that satisfies the following environmental and installation conditions.
Feature Specification
Ambient temperature Cable must be in a range of -35…177 °C (-31…350 °F) when devices are
Ambient humidity Must be in a range of 30…95% RH (noncondensing) when devices are operating.
operating. Connector must be in a range of -35…125 °C
(-31…257 °F) when devices are operating. ATEX applications must be in a range of -35…80 °C (-31…176 °F) when devices
are operating. CSA applications must be in a range of -35…85 °C (-31…185 °F) when devices
are operating.

Outer Dimensions and Part Nomenclature

1442 Sensor Outer Dimensions and Part Nomenclature
5 mm Sensor
L1 = Unthreaded length
L2 = Case length
L3 = Cable length
Rockwell Automation Publication ICM-UM004C-EN-E - February 2014 17
Loading...
+ 39 hidden pages