Rockwell Automation 1441-DYN25-MRUC User Manual

User Manual
Run Up Coast Down Extension Module for the Dynamix 2500 Data Collector
Catalog Number
1441-DYN25-MRUC
Important User Information
IMPORTANT
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/ important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
) describes some
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, Emonitor, Dynamix, Enpac, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Table of Contents

Preface
Installing Optional Extension Modules
Run Up/Coast Down Extension Module
Index
Optional Extension Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Chapter 1
Install an Extension Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Uninstall Extension Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Manage Extension Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Extension Module Battery Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 2
Set Up Run Up/Coast Down Measurements . . . . . . . . . . . . . . . . . . . . . . . 17
Collect Run Up/Coast Down Measurements. . . . . . . . . . . . . . . . . . . . . . . 19
Displaying Measurements by Using a Bode Plot. . . . . . . . . . . . . . . . . . . . . 22
Set Up the Bode Plot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Display the Bode Plot. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Displaying Measurements Using a Nyquist Plot. . . . . . . . . . . . . . . . . . . . . 25
Set Up the Nyquist Plot. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Display the Nyquist Plot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Displaying Measurements in Table Format . . . . . . . . . . . . . . . . . . . . . . . . . 28
Set Up the Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Display the Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Displaying Measurements Using a Waterfall. . . . . . . . . . . . . . . . . . . . . . . . 31
Set Up the Waterfall. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Display the Waterfall Plot. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Displaying Measurements Using a Spectrogram. . . . . . . . . . . . . . . . . . . . . 36
Set Up the Spectrogram Plot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Display the Spectrogram Plot. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Save Run Up/Coast Down Measurements . . . . . . . . . . . . . . . . . . . . . . . . . 40
Recall a Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Review Run Up/Coast Down Measurements. . . . . . . . . . . . . . . . . . . . . . . 43
Screen Capturing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Delete Run Up/Coast Down Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 3
Table of Contents
Notes:
4 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011

Preface

This manual covers the Dynamix 2500 data collector Run Up Coast Down (RUCD) extension module.
When using the Dynamix 2500 Data Collector Run Up Coast Down Extension Module, you can do the following:
Record and analyze data from intermittent events and transient vibration signals from non-steady state machines.
Analyze a machine’s critical speeds and resonant frequencies.

Optional Extension Modules

These are the optional extension modules for the Dynamix 2500 data collector:
1441-DYN25-4C, 4-channel Activation The 4-channel activation lets you take 3- or 4- channel magnitude, time
waveform, spectra, and Offroute measurements.
1441-DYN25-MBMP Bump Test The Bump test (or hammer test) determines the natural frequencies of a
machine or a structure.
1441-DYN25-MBAL Balancing The Balancing test resolves single-plane, two-plane, and static-couple
balances with high precision.
1441-DYN25-MFRF Frequency Response Function The FRF test lets you determine the natural frequencies of a machine as
well as sophisticated information about the frequency response of the structure being tested.
1441-DYN25-MREC Time Recorder The Time Recorder test uses a the instrument as a data recorder for real-
time data acquisition and analysis.
1441-DYN25-MRUC Run Up Coast Down The RUCD test records and analyzes data from intermittent events and
transient vibration signals from non-steady state machines.
(1)
See Additional Resources on page 6
(1) This is an activation license for the Dynamix 2500 data collector.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 5
for a listing of available publications.
Preface

Additional Resources

These documents contain additional information concerning products from Rockwell Automation.
Resource Description
Dynamix 2500 Data Collector User Manual, publication 1441-UM001
Dynamix 2500 Data Collector Bump Test Extension Module User Manual, publication 1441-UM002
Dynamix 2500 Data Collector Frequency Response Function Extension Module User Manual, publication 1441-UM003
Dynamix 2500 Data Collector Balancing Extension Module User Manual, publication 1441-UM004
Dynamix 2500 Data Collector Time Recorder Extension Module User Manual, publication 1441-UM005
Emonitor User’s Guide, publication
EMONTR-UM001
Dynamix 2500 Data Collector Kit Release Notes, publication 1441-RN001
Dynamix 2500 Data Collector Optional Extension Modules Release Notes, publication 1441-RN002
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certifications website, http://www.ab.com
Describes the Dynamix 2500 data collector which provides predictive maintenance by using noise and vibration analysis.
Describes how determine natural (or resonant) frequencies of a machine or structure.
Describes how to determine the natural frequencies of a machine or structure using modal hammer.
Describes the direct method to balance your rotating machinery in one or two planes.
Describes how to use the data collector as a data recorder for real-time data acquisition, post processing, and analysis.
Describes data management for predictive maintenance services.
Provides important information on the latest updates, for example, firmware, certifications, warnings, and hardware changes for the data collector.
Provides important information on how to install the Optional Extension Modules onto the Dynamix 2500 data collector.
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at http://www.rockwellautomation.com/
literature. To order paper copies of technical documentation, contact your local
Allen-Bradley distributor or Rockwell Automation sales representative.
6 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Chapter
IMPORTANT
IMPORTANT
1

Installing Optional Extension Modules

The data collector uses the Extension Manager to install and uninstall extension modules. These extension modules are licensed and ordered separately from the basic entry level product.
Topic Page
Install an Extension Module 7 Uninstall Extension Modules 9 Manage Extension Modules 12 Extension Module Battery Status Indicators 13
The installation Secure Digital (SD) cards that you receive work with any Dynamix 2500 data collector. Once you have installed an extension module, the card is locked so that it can be used only with that instrument.

Install an Extension Module

One installation SD card is required for each instrument that needs to be upgraded.
You can uninstall extension modules if required. When uninstalling an extension module, you have the option to free up the license so you can install the extension module on another instrument. This makes the extension module available to be transferred between units.
When ever you re-run the OS Loader software, you will re-load only the main OS firmware. The OS loader will backup licence files and data, but not the optional extension modules. Once you have updated the OS firmware, install the latest version of your optional extension modules.
See the Dynamix 2500 Data Collector User Manual, 1441-UM001 more information.
Follow these instructions to install an extension module.
1. Open the base cover at the bottom of the Dynamix 2500 data collector.
2. Place the extension module SD card contact side-up into the unit until it is
firmly seated in place.
, for
3. Close the base cover.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 7
Chapter 1 Installing Optional Extension Modules
Extension Manager
4. Apply power to the data collector.
5. From the Main Menu, select Setup Utility and press Enter.
6. Press 0 (Shift) to display the second set of functions.
The Extension Manager function remains on the screen for about 3seconds after releasing 0 (Shift).
7. Press F1 (Extn Mgr).
The Extension Manager screen appears showing the current extension module installations.
8 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
8. Press 0 (Shift) to display the Install extension function.
9. Press F2 (Install) to install the new extension module.
Installing Optional Extension Modules Chapter 1
Extension Manager
When the installation is complete, a confirmation prompt appears.
10. Press F4 (OK).
The new extension module appears in the list.

Uninstall Extension Modules

11. Press F4 (Esc) to exit the Extension Manager screen.
Follow these instructions to uninstall an extension module.
1. Press 0 (Shift) from the Setup Utility screen to display the Extension
Manager function.
The Extension Manager function remains on the screen for about three seconds after releasing 0 (Shift).
2. Press F1 (Extn Mgr).
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 9
Chapter 1 Installing Optional Extension Modules
This screen lists the extension modules currently installed and the on the unit.
The Extension Manager screen appears.
3. Select the extension module you want to uninstall and press F3 (Select).
F3 (Select) toggles the selection on and off.
10 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Installing Optional Extension Modules Chapter 1
IMPORTANT
A checkmark appears next to that extension module.
4. Press F1 (Uninstall).
A confirmation message appears.
5. Make sure your installation card is inserted into the instrument.
The extension module is uninstalled and the license on the card is released so that the card can be used to install the extension module on another Dynamix 2500 data collector.
If the installation card is not inserted in the instrument and no card, you are is found or the card does not have the extension module license for the unit, you are prompted to insert the correct installation card or continue without freeing the license.
6. Press F2 (Yes) to uninstall the extension module.
7. Press F4 (Esc) to exit the Extension Manager screen.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 11
Chapter 1 Installing Optional Extension Modules
IMPORTANT
TIP
The extension modules that are hidden are shown in [square brackets].

Manage Extension Modules

The Dynamix 2500 data collector lets you to hide installed extension modules from the Main Menu. You may need to hide an advanced extension module icon from an inexperienced user, for example, RUCD and FRF.
Once an extension module is hidden, its icon is not represented on the Main Menu or displayed in the Dynamix 2500 data collector About screen.
Follow these instructions to hide or show an extension module icon on the Main Menu.
1. Press 0 (Shift) on the Setup Utility screen to display the Extension
Manager function.
The Extension Manager function should remain on the screen for approximately three seconds after releasing 0 (Shift).
2. Press F1 (Extn Mgr).
The Extension Manager screen appears. The Extension Manager displays a list of installed extensions module.
12 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
The F2 (Hide) toggles between Hide and Show depending if the selected extension module is hidden or not.
You have to exit and re-enter the Extension Manager after hiding an extension module to have the Show function appear.
Installing Optional Extension Modules Chapter 1
TIP
3. Select the extension module that you want to hide or show and press F2
(Show/Hide).
If you want to show or hide multiple extension modules simultaneously, select each extension module and press F3 (Select).
A checkbox appears next to each selected extension module. If you select multiple extension modules and some are hidden while others are shown, F2 (Show/Hide) reflects the status of the selected extension module.
4. Press F4 (Esc) to exit the Extension Manager.

Extension Module Battery Status Indicators

The battery status icons show the strength of the battery.
Table 1 - Extension Module Battery Icon Descriptions
Battery Icon Meaning
Battery status is good: >30% life remaining.
Battery status is low: >10% life remaining.
Battery status is very low: <10% life remaining.
Battery is charging.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 13
Chapter 1 Installing Optional Extension Modules
Notes:
14 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Chapter
2

Run Up/Coast Down Extension Module

The Run Up/Coast Down (RUCD) extension module is an optional module for the Dynamix 2500 data collector. You install the extension module with the RUCD Secure Digital (SD) card.
See Installing Optional Extension Modules on page 7 instructions.
Topic Page
Set Up Run Up/Coast Down Measurements 17 Collect Run Up/Coast Down Measurements 19 Displaying Measurements by Using a Bode Plot 22 Displaying Measurements Using a Nyquist Plot 25 Displaying Measurements in Table Format 28 Displaying Measurements Using a Waterfall 31 Displaying Measurements Using a Spectrogram 36 Save Run Up/Coast Down Measurements 40 Recall a Setup 41 Review Run Up/Coast Down Measurements 43 Screen Capturing 45 Delete Run Up/Coast Down Files 45
The Run Up/Coast Down extension module lets the data collector record and analyze data from intermittent events and transient vibration signals from non-steady state machines.
for installation
The Run Up/Coast Down extension module is used to record and analyze data from machines where noise or vibration levels are changing with speed or time such as during a run up (increase in speed), coast down (decrease in speed), or other applications causing transient phenomena. You use the data to analyze a machine’s critical speeds and resonant frequencies.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 15
Chapter 2 Run Up/Coast Down Extension Module
Accelerometer
Tri po d
Tachometer
Reflective Tape
The application acquires a simultaneous noise or vibration signal and a tachometer signal.
This example setup includes the following:
• Accelerometer attached to connector A of the Dynamix 2500 data collector
• Optical tachometer signal connected to the POWER/USB/TRIGGER cable
• Tripod for tachometer signal stability
• Speed reference trigger
• Small piece of reflective tape on the part of the shaft can serve as a reference trigger or you can simply pass the laser over a notch in the shaft
This graphic illustrates a typical Run Up/Coast Down setup.
Figure 1 - Run Up/Coast Down Setup
The recorded data is saved in the form of a Microsoft .wav time waveform file. You can analyze this file and viewed in a variety of different formats including:
•Bode Plot
•Nyquist Plot
• Table
•Waterfall
•Spectrogram
16 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
32147-M
Run Up/Coast Down Extension Module Chapter 2

Set Up Run Up/Coast Down Measurements

The first step in the Run Up/Coast Down extension module is to setup how the measurements are taken by the data collector.
1. Select RUCD on the Main Menu and press the Enter.
The RUCD screen appears.
2. Select Setup and press Enter to set up the Run Up/Coast Down
parameters. The RUCD - Setup screen appears.
3. Select a parameter and press the Right arrow to open a list of values.
4. Select or type the parameter value.
5. Press Left arrow to save your selection.
6. Press F2 (Save) to save the current settings to a file.
See Save Run Up/Coast Down Measurements on page 40
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 17
for details.
Chapter 2 Run Up/Coast Down Extension Module
Table 2 - Run Up/Coast Down Setup Parameters
Parameter Description Values/Comments
Transducer Specifies the type of sensor used on Connector A, this is typically
Accel (g). The specified sensor type determines available options and
engineering units for subsequent setup fields.
Sens (mV/EU) The transducer sensitivity in millivolts (MV) per engineering units
(EU).
Range (EU) The expected maximum amplitude range value for the incoming input
signal. The range should accommodate for unexpected events. If you are
unsure about the range value, set the range 10 to 20 times higher than expected.
Max M/c Speed The maximum speed that the shaft will reach in rpm.
This is used with Max No Orders to determine the sampling rate.
Max No Orders The maximum number of shaft orders of interest during analysis.
This is used with Max M/c Speed to determine the sampling rate.
Mode The method for initiating the data collection.
Runup - The data collection starts when the machine speed
rises above Start Spd.
Coast down -The data collection starts when the machine
speed falls below Stop Spd.
Manual - Manually start data collection by pressing F4 (Start).
No tachometer signal is required for this mode.
Use these descriptions to help you configure the parameters in the Run Up/Coast Down Setup screen.
Accel ICP (g) (default) Accel (g)
Accel ICP (m/s2) Accel (m/s2)
Vel ICP (mm/s) Vel (mm/s) Vel ICP (ips) Vel (ips) Disp (mils) Disp (µm) Volts AC User (EU)
1…2000 (mV/EU) 100 (default)
.1 EU .2 EU .5 EU 1 EU 2 EU (default) 5 EU 10 EU 20 EU (default) 50 EU 100 EU 200 EU 500 EU 1000 EU 2000 EU
10…60000 rpm 3600 rpm (default)
1 to 166 32 (default)
Runup (default) Manual Coastdown
18 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Run Up/Coast Down Extension Module Chapter 2
Table 2 - Run Up/Coast Down Setup Parameters
Parameter Description Values/Comments
Pulses/Rev The number of tachometer signal pulses per revolution of the
reference shaft. To acquire a suitable tachometer signal, the tachometer signal must
be approximately 1.5 volts peak-to-peak. The adverse effect of excessively short tachometer pulse widths can be addressed by setting the Max No Order to a higher value to increase the sampling rate.
Start Spd (RPM) Sets the speed at which the unit should start collecting data.
If Mode is set to Runup, this value must be less than the Stop
Spd.
If Mode is set to Coast down, this value must be greater than
the Stop Spd.
This parameter is not available if Mode is set to Manual.
Stop Spd (RPM) Sets the speed at which the unit should stop collecting data.
If Mode is set to Runup, this value must be greater than the
Start Spd.
If Mode is set to Coast down, this value must be less than Start
Spd.
This parameter is not available if Mode is set to Manual.
Save To Sets the location where data is saved.
Save the data to the SD or PC card if the .wav files will be large. Your selection affects the maximum recording time.
Max Acq Time (s) The number of seconds to record the time waveform.
This limit applies only if the run up or coast down takes longer than the time set here.
.1…1000 1 (default) This number can be a multiple or a non-
integer to accommodate, for example, gear ratios.
10…3600 rpm 60 rpm (default)
10…3600 rpm 300 rpm (default)
Internal (default) SD Card
1…1131.65 s
1131.65 s (default)

Collect Run Up/Coast Down Measurements

This section describes the Run Up/Coast Down status indicators and how to collect Run Up/Coast Down data.
Table 3 - RUCD Status Indicators
Indicator Status Description
Red Solid An overload error (clipping or streaming error) has
occurred during data collection.
Amber Solid An error has occurred during data collection The status
indicator turns off when the error condition disappears.
Green Flashing Green No errors occurred during data collection.
Once you have configured the parameters, you can begin collecting data. The data is automatically recorded as a .wav file, which can then be analyzed using several different types of plots.
1. Using the a tachometer cable, connect the reference input device to the
POWER/USB/TRIGGER connector and the transducer to connector A.
2. Align the reference input device (tachometer, optical tachometer, or
strobescope) to capture shaft speed.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 19
Chapter 2 Run Up/Coast Down Extension Module
Current Speed of Machine
Current Overall Vibration Reading
Maximum Acquisition Time in the Armed State Remaining Recording Time in the Acquiring State
Message Area
3. Attach a transducer to the bearing house.
4. Start the machine or stop the machine as needed.
5. From the RUDC Setup screen press F3 (Start).
The RUCD - Taking Data screen appears.
The Dynamix 2500 data collector begins collecting run up or coast down data based on the parameters you selected. The state of the machine is indicated on the screen.
State Description
Armed The machine speed has not reached the Start Spd and data collection has
Acquiring The machine speed has reached the Start Spd and data collection has
Error-Clipped An error occurred during data collection. If a sensor’s Range setting is too
not yet started. At any time during this state, you can press F3 (Start) to manually start
data collection.
started. At any time during this state, you can press F3 (Stop) to manually stop
data collection.
small to accommodate the signal’s amplitude, a message displays in the message error.
Press F4 (Back) to return to the RUCD - Setup screen and increase the Range setting.
Data collection is complete when the specified Stp Speed or Maximum Acquisition Time is reached, or you press F3 (Stop).
20 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Run Up/Coast Down Extension Module Chapter 2
TIP
The resulting time waveform is recorded as a Microsoft Windows .wav file and the Acquisition Completed dialog appears on the screen.
If an error occurs during data collection, a message appears in this dialog box.
6. Press F4 (OK) to continue.
The RUCD - Display Select screen appears.
The Dynamix 2500 data collector provides five different formats for you to use to view the newly recorded time waveform.
7. Select the format and press F3 (Display).
Format Description
Bode Displays the magnitude and phase over a varying rpm.
See Displaying Measurements by Using a Bode Plot on page 22
Nyquist Displays the selected orders as complex data.
See Displaying Measurements Using a Nyquist Plot on page 25
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 21
.
.
Chapter 2 Run Up/Coast Down Extension Module
Format Description
Table Displays the magnitude and phase of selected orders at the varied rpm speeds
Waterfall Displays multiple FFT traces overlaid and offset on one single plot.
Spectrogram Displays multiple FFT traces on one single plot, using color to indicate relative
in a table format. See Displaying Measurements in Table Format on page 28.
See Displaying Measurements Using a Waterfall on page 31
magnitude. See Displaying Measurements Using a Spectrogram on page 36
.
.
8. When you are finished analyzing the time waveform, you can save it to a
file.

Displaying Measurements by Using a Bode Plot

See Save Run Up/Coast Down Measurements on page 40
.
The Bode plot is actually two graphs of 1X rpm amplitude and phase as a function of frequency. The screen shows both plots at the same time. The top plot shows magnitude versus rpm. The bottom plot shows phase versus rpm.
Set Up the Bode Plot
1. Select Bode on the RUCD - Display Select screen and press F3 (Display).
The RUCD - Bode Setup screen appears.
2. Select the parameter and press the Right arrow to open a list of values.
3. Select or type in the parameter value.
4. Press the Left arrow to save your selection.
See Bode Plot Parameters on page 23
22 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
to help you configure the parameters.
Run Up/Coast Down Extension Module Chapter 2
5. When you are finished, press F3 (Display) to display the Bode plot.
See Display the Bode Plot on page 24
.
Table 4 - Bode Plot Parameters
Parameter Description Values/Comments
Start Spd (RPM) Sets the start speed of the recorded data for the Bode plot.
This defaults to the Start Spd value set in the RUCD Setup screen. See Table 2 on page 18.
Stop Spd (RPM) Sets the stop speed of the recorded data for the Bode plot.
This defaults to the Stop Spd value set in the RUCD Setup screen. See Run Up/Coast Down Setup Parameters on page 18
Spacing Controls the spacing between collected spectra.
Δ rpm is a fixed speed change between spectra.
%
Δ rpm is a percentage speed change between spectra.
Δ Time is a fixed time interval between spectra.
Δ rpm + Δ Time is a combination of speed and time interval settings. If
speed stops changing then spectra are calculated using the Time Interval value.
%
Δ rpm + Δ Time is a combination of speed and time interval settings.
If speed stops changing then spectra are calculated using the Time Interval value.
Speed Interval (rpm) Sets the speed interval used in calculating FFT spectra.
This parameter not used when Spacing is set to
Time Interval (sec) Sets the time interval used in calculating FFT spectra.
This parameter is not used when Spacing is set to
Display Units Sets the Y-axis units.
The available units depends on the transducer used to collect data. See Run Up/Coast Down Setup Parameters on page 18.
LF Cutoff Determines whether to apply a low frequency filter (0.3 times the running
Detection Sets the signal detection and scaling display for the Bode plot:
Y-axis Sets the y-axis scaling on the Bode plot:
speed) to the data.
Peak - Measured RMS value multiplied by the square root of two (1.4142).
Pk-Pk - Measured RMS value multiplied by two times the square root of
two (2.8284).
RMS - Root mean squared signal level of the input signal.
Linear - The plot grid centers are linearly spaced in Y between the centers
of the first and last grid.
Log - The plot grid centers are logarithmically spaced in Y between the
centers of the first and last grid.
.
Δ Time.
Δ rpm and % Δ rpm.
10…3600 rpm
10…3600 rpm
Δ rpm
%
Δ rpm Δ Time Δ rpm + Δ Time
%
Δ rpm + Δ Time
Your selection affects the Speed Interval and Time Interval settings.
1…240 rpm or % rpm
Enter a value from .001…604800 s
Accel (g)
2
Accel (m/s Accel (m/s
Vel (mm/s) Vel (ips) Disp (mils) Disp (µm)
Off (default) On
RMS Peak (default) PkPk
Linear (default) Log
)
2
)
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 23
Chapter 2 Run Up/Coast Down Extension Module
TIP
Speed, Magnitude, and Q Factor at Cursor Location
Active Trace
Table 4 - Bode Plot Parameters
Parameter Description Values/Comments
Show Overall Determines whether to display the overall severity as a trace on the Bode plot. Yes (default)
No
Num Traces Sets the number of traces or order tracks to be displayed on the Bode plot:
The number of traces available is determined by the Show Overall
parameter.
Your selection determines the available number of Trace Order
parameters.
Trace Order #1…4 The order numbers to be tracked and displayed on the Bode plot. This value
cannot exceed the Max No Orders value set in the RUCD Setup screen. See Run Up/Coast Down Setup Parameters on page 18
.
1 (default) 2 3 4
.001…166 orders
Display the Bode Plot
When you are done setting up the Bode plot parameters, you can process the data and display the Bode plot by pressing F3 (Display) on the RUCD - Bode Setup screen.
The larger the .wav file, the longer it takes to process the data and display the plot.
The top of the display shows magnitude versus rpm. The bottom of the display shows phase versus rpm:
• To sequence through the traces, press the Up and Down arrows. The order number of the current trace is displayed in the top left corner of
the screen. To move the cursor along the trace, press the Left and Right arrows.
24 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Run Up/Coast Down Extension Module Chapter 2
• From the Bode plot you can also display the data in a Table format or Nyquist plot. To display the data in a table, press 0 (Shift) and F4 (Table).

Displaying Measurements Using a Nyquist Plot

See Display the Table on page 30
• To display the data in a Nyquist plot, press 0 (Shift) and F1 (Nyqst). See Display the Nyquist Plot on page 27
The Nyquist plot is a polar representation of the amplitude and phase angle as a function of frequency. Three variables are combined into a single plot in polar format.
for more information.
for more information.
Set Up the Nyquist Plot
1. Select Nyquist on the RUCD - Display Select screen and press F3
(Display).
The RUCD - Nyquist Setup screen appears.
2. Select the option and press the Right arrow to open a list of values.
3. Select or type in a parameter value.
4. Press the Left arrow to save your selection.
Use the descriptions in Nyquist Plot Parameters on page 26 configure the parameters.
5. When you are finished, press F3 (Display) to display the Nyquist plot.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 25
to help you
Chapter 2 Run Up/Coast Down Extension Module
See Display the Nyquist Plot on page 27.
Table 5 - Nyquist Plot Parameters
Parameter Name Description Values/Comments
Start Spd (RPM) Sets the start speed of the recorded data for the plot.
This defaults to the Start Spd value set in the RUCD Setup screen. See Run Up/Coast Down Setup Parameters on page 18
Stop Spd (RPM) Sets the stop speed of the recorded data for the plot.
This defaults to the Stop Spd value set in the RUCD Setup screen. See Run Up/Coast Down Setup Parameters on page 18
Spacing Controls the spacing between collected spectra:
Δ rpm is a fixed speed change between spectra.
%
Δ rpm is a percentage speed change between spectra.
Δ Time is a fixed time interval between spectra.
Δ rpm + Δ Time is a combination of speed and time interval
settings. If speed stops changing then spectra are calculated using the Time Interval value.
%
Δ rpm + Δ Time is a combination of speed and time interval
settings. If speed stops changing then spectra are calculated using the Time Interval value.
Speed Interval (RPM) Sets the speed interval used in calculating FFT spectra.
This parameter not used when Spacing is set to
Δ Time.
.
.
10…3600 rpm
10…3600 rpm
Δ rpm
Δ rpm
%
Δ Time Δ rpm + Δ Time
Δ rpm + Δ Time
% Your selection affects the Speed Interval
and Time Interval settings.
1… 240 rpm or % rpm
Time Interval (sec) Sets the time interval used in calculating FFT spectra.
This parameter is not used when Spacing is set to
Display Units Sets the Y-axis units.
The available units depends on the transducer used to collect data. See Run Up/Coast Down Setup Parameters on page 18
LF Cutoff Determines whether to apply a low frequency filter (0.3 times the running
speed) to the data.
Detection Sets the signal detection and scaling display for the plot:
Peak - Measured RMS value multiplied by the square root of two
(1.4142).
Pk-Pk - Measured RMS value multiplied by two times the square root
of two (2.8284).
RMS - Root mean squared signal level of the input signal.
Num Traces Sets the number of traces or order tracks to be displayed on the plot.
Your selection determines the available number of Trace Order parameters.
Trace Order #1-#4 The order numbers to be tracked and displayed on the plot.
This value cannot exceed the Max No Orders value set in the RUCD Setup screen.
See Run Up/Coast Down Setup Parameters on page 18
Δ RPM and % Δ RPM.
.
.
.001…604800 s
Off On
RMS Peak PkPk
1 2 3 4
.001…166 orders
26 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Run Up/Coast Down Extension Module Chapter 2
TIP
Speed, magnitude, and Q Factor at Cursor Location
Active Trace
Display the Nyquist Plot
When you are done setting up the plot parameters, you can process the data and display the Nyquist plot by pressing F3 (Display) on the RUCD - Nyquist Setup screen.
The larger the .wav file, the longer it takes to process the data and display the plot.
The display shows the selected orders as complex data with zero degrees along the positive X-axis and 90 degrees along the positive Y-axis:
• To sequence through the traces, press the Up and Down arrows. The order number of the current trace is displayed in the top left corner of the screen. To move the cursor along the trace, press the Left and Right arrows.
• From the Nyquist plot you can display the data in a table or Bode plot, press 0 (Shift) and F4 (Table).
See Display the Table on page 30
for more information.
• To display the data in a Bode plot, press 0 (Shift) and then F1 (Bode). See Display the Bode Plot on page 24
for more information.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 27
Chapter 2 Run Up/Coast Down Extension Module

Displaying Measurements in Table Format

The magnitude and phase of selected orders at the varied rpm speeds are displayed in a table.
Set Up the Table
1. Select Table on the RUCD - Display Select screen and press F3 (Display).
The RUCD - Table Setup screen appears.
2. Select a parameter press the Right arrow to open a list of values.
3. Select or type in a parameter value.
4. Press the Left arrow to save your selection.
Use the descriptions in Table Parameter Descriptions on page 28 you configure the parameters.
5. When you are finished, press F4 (Display) to display the table.
See Display the Table on page 30
Table 6 - Table Parameter Descriptions
Parameter Name Description Values/Comments
Start Spd (RPM) Sets the start speed of the recorded data for the table.
This defaults to the Start Spd value set in the RUCD Setup screen. See Run Up/Coast Down Setup Parameters on page 18
Stop Spd (RPM) Sets the stop speed of the recorded data for the table.
This defaults to the Stop Spd value set in the RUCD Setup screen. See Run Up/Coast Down Setup Parameters on page 18
.
.
.
10…3600 rpm
10…3600 rpm
to help
28 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Run Up/Coast Down Extension Module Chapter 2
Table 6 - Table Parameter Descriptions
Parameter Name Description Values/Comments
Spacing Controls the spacing between collected spectra:
Δ rpm is a fixed speed change between spectra.
%
Δ rpm is a percentage speed change between spectra.
Δ Time is a fixed time interval between spectra.
Δ rpm + Δ Time is a combination of speed and time interval settings.
If speed stops changing then spectra are calculated using the Time Interval value.
%
Δ rpm + Δ Time is a combination of speed and time interval
settings. If speed stops changing then spectra are calculated using the Time Interval value.
Speed Interval (RPM) Sets the speed interval used in calculating FFT spectra.
This parameter not used when Spacing is set to
Δ Time.
Δ rpm
%
Δ rpm Δ Time Δ rpm + Δ Time
%
Δ rpm + Δ Time
Your selection affects the Speed Interval and Time Interval settings.
1…240 rpm or % rpm
Time Interval (sec) Sets the time interval used in calculating FFT spectra.
This parameter is not used when Spacing is set to
Display Units Sets the Y-axis units.
The available units depends on the transducer used to collect data. See Run Up/Coast Down Setup Parameters on page 18.
LF Cutoff Determines whether to apply a low frequency filter (0.3 times the running
speed) to the data.
Detection Sets the signal detection and scaling display for the table:
Peak - Measured RMS value multiplied by the square root of two
(1.4142).
Pk-Pk - Measured RMS value multiplied by two times the square root of
two (2.8284).
RMS - Root mean squared signal level of the input signal.
Num Traces Sets the number of traces or order tracks to be displayed in the table.
Your selection determines the available number of Trace Order parameters. 12
Trace Order #1-#4 The order numbers to be tracked and displayed in the table.
This value cannot exceed the Max No Orders value set in the RUCD Setup screen.
See Run Up/Coast Down Setup Parameters on page 18
Δ RPM and % Δ RPM.
.
.001…604800 s
Off On
RMS Peak PkPk
.001…166 orders
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 29
Chapter 2 Run Up/Coast Down Extension Module
Display the Table
When you are done setting up the table parameters, you can process the data and display the table by pressing F4 (Display) on the RUCD - Table Setup screen.
Up to two orders of the magnitude and phase data set is displayed in the table:
• To scroll through the table, press the Up and Down arrows.
• You can also display the data in a Bode plot. To display the data in a Bode plot or Nyquist plot, press 0 (Shift) and F4 (Bode).
See Display the Bode Plot on page 24
.
• To display the data in a Nyquist plot, press 0 (Shift) and F1 (Nyquist). See Display the Nyquist Plot on page 27
.
30 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Run Up/Coast Down Extension Module Chapter 2

Displaying Measurements Using a Waterfall

The Waterfall plot displays the vibration level in relation to the frequencies at which the vibration occurs. It lets you view several measurements in relationship to each other.
Set Up the Waterfall
1. Select Waterfall on the RUCD - Display Select screen and press F3
(Display).
The RUCD - Waterfall Setup screen appears.
2. Select the option and press the Right arrow to open a list of values.
3. Select or type in the parameter value.
4. Press the Left arrow to save your selection.
Use the descriptions in Waterfall Plot Parameters on page 31 configure the parameters.
5. When you are finished, press F3 (Display) to display the Waterfall plot.
See Display the Waterfall Plot on page 33
Table 7 - Waterfall Plot Parameters
Parameter Name Description Values/Comments
Start Spd (RPM) Sets the start speed of the recorded data for the plot.
This defaults to the Start Spd value set in the RUCD Setup screen. See Run Up/Coast Down Setup Parameters on page 18
Stop Spd (RPM) Sets the stop speed of the recorded data for the plot.
This defaults to the Stop Spd value set in the RUCD Setup screen. See Run Up/Coast Down Setup Parameters on page 18
.
.
.
10…3600 rpm
10…3600 rpm
to help you
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 31
Chapter 2 Run Up/Coast Down Extension Module
Table 7 - Waterfall Plot Parameters
Parameter Name Description Values/Comments
Spacing Controls the spacing between collected spectra:
Δ rpm is a fixed speed change between spectra.
%
Δ rpm is a percentage speed change between spectra.
Δ Time is a fixed time interval between spectra.
Δ rpm + Δ Time is a combination of speed and time interval settings. If
speed stops changing then spectra are calculated using the Time Interval value.
%
Δ rpm + Δ Time is a combination of speed and time interval settings.
If speed stops changing then spectra are calculated using the Time Interval value.
Speed Interval (RPM) Sets the speed interval used in calculating FFT spectra.
This parameter not used when Spacing is set to
Time Interval (sec) Sets the time interval used in calculating FFT spectra.
This parameter is not used when Spacing is set to
Display Units Sets the Y-axis units.
The available units depends on the transducer used to collect data. See Run Up/Coast Down Setup Parameters on page 18.
Detection Sets the signal detection and scaling display for the plot:
Peak - Measured RMS value multiplied by the square root of two (1.4142).
Pk-Pk - Measured RMS value multiplied by two times the square root of
two (2.8284).
RMS - Root mean squared signal level of the input signal.
Lines The number of lines (bins) of resolution for the FFT spectra. The larger the
number of lines, the better the frequency resolution of the measured data in the spectra. Similarly, the higher the number of lines, the longer it takes to display the spectra in the plot.
X-axis Sets the x-axis frequency units for displaying spectra/FFT data:
Hz - Displays spectra in Hertz, cycles per second.
CPM - Displays spectra in cycles per minute.
Orders - Displays spectra in orders of the operating speed.
Δ Time.
Δ RPM and % Δ RPM.
Δ rpm
%
Δ rpm Δ Time Δ rpm + Δ Time
%
Δ rpm + Δ Time
Your selection affects the Speed Interval and Time Interval settings.
1…240 rpm
.001…604800 s
RMS Peak PkPk
100 200 400 800 1600 3200 6400 12800
Hz CPM Orders
Freq. Range (EU) The maximum frequency for the measurement.
The frequency range is determined by the X-axis parameter.
32 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Your selection affects the Freq Range and LF Cutoff parameters.
10…2000 Hz 600…120000 CPM .001…166 Orders
Run Up/Coast Down Extension Module Chapter 2
TIP
Table 7 - Waterfall Plot Parameters
Parameter Name Description Values/Comments
LF Cutoff (EU) Sets a low frequency cutoff filter to remove noise from the analysis.
The available options are determined by the X-axis selection.
Off
21.6 CPM 66 CPM 120 CPM 600 CPM 4200 CPM .36 Hz
1.1 Hz 2 Hz 10 Hz 70 Hz
Display the Waterfall Plot
When you are finished setting up the plot parameters, you can process the spectral data by pressing F3 (Display) on the RUCD - Waterfall Setup screen.
The larger the .wav file, the longer it takes to process the data and display the plot.
Optimize the Waterfall Plot
Additional parameters display on the screen letting you to control how the spectra appear in the waterfall plot.
1. Select the option and press the Right arrow to open a list of values.
2. Select or type in a parameter value.
3. Press the Left arrow to save your selection.
Use the descriptions in Waterfall Plot Setup Parameters on page 34
to help
you configure the parameters.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 33
Chapter 2 Run Up/Coast Down Extension Module
TIP
4. When you are finished and ready to display the waterfall plot, press F3
(Display).
Table 8 - Waterfall Plot Setup Parameters
Parameter Name Description Values/Comments
Z-axis Controls the spacing between the collected spectra.
RPM- FFTs spaced depending on the rpm at which they were recorded.
Timestamp- FFTs spaced depending on the time the data was recorded.
Even Spacing- FFTs spaced evenly along the Z-axis.
No. Spectra Controls the number of spectra to display on the waterfall plot. The spectra
are displayed as follows:
The first spectrum is always displayed.
The last spectrum is always displayed.
The other spectra (No. Spectra minus first and last spectrum) are evenly
distributed on the plot.
Trace Offset Sets the angle of the Z-axis on the plot.
Trace Height Controls the height of the spectra on the plot. Small
Disp. Order Controls the order in which to display the spectra.
Forward- Display spectra from oldest (front of the waterfall) to newest
(rear of the waterfall).
Reverse- Display spectra from newest (front of the waterfall) to oldest
(rear of the waterfall).
Blanking Eliminates the display of data below a certain level on the Y-axis. This setting
helps clarify the presence of machine orders or structural frequencies.
RPM Tim estam p Even Spacing
2…60 spectra
0
° (C)
22.5
° (C)
45
° (C)
Medium Large
Forward Reverse
0%…25%
View the Waterfall Plot
After setting up the Waterfall spectra, press F3 (Display) on the Waterfall Display Setup screen.
At the bottom of the waterfall plot is a display area that indicates the active spectrum, and provides information (number of spacing of spectra, speed) on how the spectra are displayed in the waterfall plot.
If more than sixty spectra were collected, the ticks along the line indicate which spectra were selected to be displayed.
See No. Spectra on page 34
Cursor Movement
Use the Up and Down arrows to sequence through the displayed spectra. The active spectrum displays in green. The zero positions of the X and Y-axis move to
34 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
for more information.
Run Up/Coast Down Extension Module Chapter 2
TIP
TIP
Frequency and Magnitude at Cursor Position
Speed, Time, or Data Collection Number of Rear Spectrum
Number and Spacing of Spectra
Speed
Active Spectrum
be relative to the active spectrum. Use the Left and Right arrows to move the cursor on the active spectrum.
Press P to quickly move the cursor to the next significant peak.
Z-axis Zoom
The Z-axis zoom lets you to zoom in around the current trace. The display area updates to indicate the number and position of the spectra displayed on the screen. The zoom capability is only available when the No. Spectra parameter is set to a number less than the number of extracted spectra.
See No. Spectra on page 34
To use the Z-axis zoom feature, press 0 (Shift) and the +/- key. Repeat this key sequence to continue zooming in. After the highest zoom level is reached, the above procedure will cause you to zoom out.
There are more zoom levels available when there are fewer spectra displayed in the plot.
for more information.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 35
Chapter 2 Run Up/Coast Down Extension Module

Displaying Measurements Using a Spectrogram

The Spectrogram plot is a three-dimensional color intensity plot displaying the amplitude of spectral components as a function of both time and frequency. Typically the horizontal and vertical axes correspond to time and frequency. The intensity corresponds to amplitude.
Set Up the Spectrogram Plot
Follow these instructions to setup the plot.
1. Select Spectrogram on the RUCD - Display Select screen and press F3
(Display).
The RUCD - Spectrogram Setup screen appears.
2. Select a parameter and press the Right arrow to open a list of parameters.
3. Select to type in a parameter value.
4. Press the Left arrow to save your selection.
Use the descriptions in Spectrogram Plot Parameter Descriptions on
page 37 to help you configure the parameters.
5. When you are finished, press F3 (Display) to display the Spectrogram plot.
See Display the Spectrogram Plot on page 38
36 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
for more information.
Run Up/Coast Down Extension Module Chapter 2
Table 9 - Spectrogram Plot Parameter Descriptions
Parameter Name Description Values/Comments
Start Spd (RPM) Sets the start speed of the recorded data for the plot.
This defaults to the Start Spd value set in the RUCD Setup screen. See Run Up/Coast Down Setup Parameters on page 18
Stop Spd (RPM) Sets the stop speed of the recorded data for the plot.
This defaults to the Stop Spd value set in the RUCD Setup screen. See Run Up/Coast Down Setup Parameters on page 18
Spacing Controls the spacing between collected spectra:
Δ rpm is a fixed speed change between spectra.
%
Δ rpm is a percentage speed change between spectra.
Δ Time is a fixed time interval between spectra.
Δ rpm + Δ Time is a combination of speed and time interval settings. If
speed stops changing then spectra are calculated using the Time Interval value.
%
Δ rpm + Δ Time is a combination of speed and time interval
settings. If speed stops changing then spectra are calculated using the Time Interval value.
Speed Interval (RPM) Sets the speed interval used in calculating FFT spectra.
This parameter not used when Spacing is set to
Δ Time.
.
.
10…3600 rpm
10…3600 rpm
Δ rpm
Δ rpm
%
Δ Time Δ rpm + Δ Time
Δ rpm + Δ Time
% Your selection affects the Speed Interval
and Time Interval settings.
1…240 rpm
Time Interval (sec) Sets the time interval used in calculating FFT spectra.
This parameter is not used when Spacing is set to
Display Units Sets the Y-axis units.
The available units depends on the transducer used to collect data. See Run Up/Coast Down Setup Parameters on page 18.
Detection Sets the signal detection and scaling display for the plot:
Peak - Measured RMS value multiplied by the square root of two
(1.4142).
Pk-Pk - Measured RMS value multiplied by two times the square root of
two (2.8284).
RMS - Root mean squared signal level of the input signal.
Lines The number of lines (bins) of resolution for the FFT spectra. The larger the
number of lines, the better the frequency resolution of the measured data in the spectra.
Similarly, the higher the number of lines, the longer it takes to display the spectra in the plot.
X-axis Sets the X-axis frequency units for displaying spectra/FFT data:
Hz - Displays spectra in Hertz, cycles per second.
CPM - Displays spectra in cycles per minute.
Orders - Displays spectra in orders of the operating speed.
Δ RPM and % Δ RPM.
.001…604800 s
RMS Peak PkPk
100 200 400 800 1600 3200 6400 12800
Hz CPM Orders Your selection affects the Freq Range and
LF Cutoff parameters.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 37
Chapter 2 Run Up/Coast Down Extension Module
TIP
Table 9 - Spectrogram Plot Parameter Descriptions
Parameter Name Description Values/Comments
Freq. Range (EU) The maximum frequency for the measurement.
The frequency range is determined by the X-axis parameter.
10…2000 Hz 600…120000 CPM .001…166 Orders
LF Cutoff (EU) Sets a low frequency cutoff filter to remove noise from the analysis.
The available options are determined by your X-axis selection.
Display the Spectrogram Plot
When you are done setting up the plot parameters, you can process the spectral data by pressing F3 (Display) on the RUCD - Spectrogram Setup screen.
The larger the .wav file, the longer it takes to process the data and display the plot.
Off
21.6 CPM 66 CPM 120 CPM 600 CPM 4200 CPM .36 Hz
1.1 Hz 2 Hz 10 Hz 70 Hz
Optimize the Spectrogram Plot
Additional parameters display on the screen letting you to control how the spectra appear in the spectrogram plot.
1. Select a parameter and press the Right arrow to open a list of values.
2. Select or type in a parameter value.
3. Press the Left arrow to save your selection.
Use the descriptions in Spectrogram Plot Setup Parameters on page 39 help you configure the parameters.
4. When you are finished and ready to display data, press F3 (Display) to view
the Spectrogram.
38 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
to
Run Up/Coast Down Extension Module Chapter 2
TIP
Frequency and Magnitude at the Cursor Position
Speed
Cursor
Amplitude Indicator at Cursor Position
Table 10 - Spectrogram Plot Setup Parameters
Parameter Name Description Values/Comments
Y-axis Sets the Y-axis scaling on the spectrogram plot:
Linear - The plot grid centers are linearly spaced in Y between the
centers of the first and last grid.
Log - The plot grid centers are logarithmically spaced in Y between the
centers of the first and last grid.
Z-axis Controls the spacing between the collected spectra:
RPM- FFTs spaced depending on the rpm at which they were recorded.
Timestamp- FFTs spaced depending on the time the data was recorded.
Even Spacing- FFTs spaced evenly along the Z-axis.
Blanking Eliminates the display of data below a certain level on the Y-axis. This
setting helps clarify the presence of machine orders or structural frequencies.
Linear Log
RPM Tim estam p Even Spacing
0%…25%
View the Spectrogram Plot
After setting up the Spectrogram spectra, press F3 (Display) on the Spectrogram Display Setup screen.
The Spectrogram plot uses color to indicate the amplitude of the signals. Red means a higher amplitude and blue means a lower amplitude:
• Use the Up and Down arrows to sequence through the displayed spectra.
• Use the Left and Right arrows to move the cursor on the active spectrum.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 39
Press P to quickly move the cursor to the next significant peak.
Chapter 2 Run Up/Coast Down Extension Module
IMPORTANT

Save Run Up/Coast Down Measurements

The Run Up/Coast Down setup parameters and measurements can be saved to a file which you can recall at a later time. The collected data is saved in the form of a time waveform (.wav file).
You can save the RUCD setup and measurement anytime the Save function is displayed on the screen.
Follow these steps to save a RUCD measurement.
1. Do one of the following:
Press F3 (Save) if you are saving the data from the Setup screen.
Press F4 (Save) if you are saving the recorded data from a plot screen.
The RUCD - Save Data screen appears.
2. Do one of the following:
To save the data to an existing file, highlight the file, and press F4 (Save). Press F2 (Yes) to overwrite the existing file. You can return to the Save screen without overwriting the file by pressing F3 (No).
To save the data to a new file, highlight save reading as and press F4 (Save). Enter a file name using the keypad or accept the default file name (current date timestamp).
3. When the entry is complete, press F4 (OK).
The setup parameters are saved along with the measurement when you press F4 (Save) on the RUCD - Save Data screen.
4. When you are finished, press F1 (Cancel).
40 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Run Up/Coast Down Extension Module Chapter 2

Recall a Setup

You can recall a previously saved setup and use it to collect another measurement. The setup may have been saved only as a setup, or may have been saved with the recorded data.
See Save Run Up/Coast Down Measurements on page 40
Follow these steps to recall a setup.
1. Select RUCD on the Main Menu and press Enter.
The RUCD screen appears.
for more information.
2. Select Recall and press Enter.
The RUCD - Load Setup screen appears.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 41
Chapter 2 Run Up/Coast Down Extension Module
3. Select the filename that you want recall and press F3 (Open).
The RUCD - Setup screen appears.
You can edit the settings or start collecting data:
For information on editing the settings, see Set Up Run Up/Coast
Down Measurements on page 17.
For information on collecting RUCD measurements, see Collect Run
Up/Coast Down Measurements on page 19.
42 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Run Up/Coast Down Extension Module Chapter 2

Review Run Up/Coast Down Measurements

You can review previously saved RUCD measurements with the Dynamix 2500 data collector. The instrument saves the recorded data in the form of a time waveform (.wav file).
Follow these steps to review an RUCD measurement.
1. Select RUCD on the Main Menu and press Enter.
The RUCD screen appears.
2. Select Review Data and press Enter.
The RUCD - Review Data screen appears.
3. Select the filename that you want review and press F3 (Open).
If you select a .wav file, the RUCD - WAV Setup screen appears. Otherwise the appropriate plot setup screen appears.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 43
Chapter 2 Run Up/Coast Down Extension Module
TIP
The RUCD - WAV Setup screen lets you to setup the .wav file parameters.
The instrument reads the .wav file to determine the maximum speed present. If the number of pulses per revolution is not equal to 1, enter the correct value before processing.
4. Select the parameter and press the Right arrow to open a list of values.
5. Select or type in a parameter value.
6. Press the Left arrow to save your selection.
Use the descriptions in WAV Setup Parameter Descriptions on page 44 help you configure the parameters.
7. When you are finished, press F3 (Start).
The Display Select screen appears letting you select the appropriate plot to view the recorded time waveform.
Table 11 - WAV Setup Parameter Descriptions
Parameter Name Description Values/Comments
Max M/c Speed The maximum machine speed in the .wav file.This parameter is set to the
Mode The method used in the .wav file to initiate data collection. When in doubt,
Pulses/Rev The number of tachometer signal pulses per revolution of the reference shaft. This value may affect the Max M/c Speed
Start Spd (RPM) The speed used in the .wav file to start collecting data. These parameters are not available if Stop Spd (RPM) The speed used in the .wav file to stop collecting data.
highest detected m/c speed.
select manual:
Runup - The data collection starts when the machine speed rises above
Start Spd.
Coast down -The data collection starts when the machine speed falls
below Stop Spd.
Manual - Manually start data collection by pressing F4 (Start). No
tachometer signal is required for this mode.
Runup Coast down Manual
value.
Mode is set to Manual.
to
44 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Run Up/Coast Down Extension Module Chapter 2

Screen Capturing

Delete Run Up/Coast Down Files

Screens can be saved as a bitmap (.bmp) image to internal memory or to the Secure Digital (SD) card. Press 0 (Shift) and 7 and follow the instructions.
You can delete a RUCD measurement or setup from the Dynamix 2500 data collector.
Follow these steps to delete a file.
1. Select RUCD on the Main Menu and press Enter.
The RUCD screen appears.
2. Select Review Data to delete a measurement or Recall Data to delete a setup and press Enter.
The RUCD - Review Data screen appears.
3. Select the appropriate filename or select all to delete all the files.
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 45
Chapter 2 Run Up/Coast Down Extension Module
4. Press 0 (Shift) and F4 (Delete) to delete the selected files.
5. Press F2 (Yes) to delete.
46 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011

Index

B
battery
status icons
battery status icons Blanking Bode plot Bode plot parameters
Detection Display Units LF Cutoff 23 Num Traces Show Overall Spacing 23 Speed Interval Start Spd Stop Spd Time Interval Trace Order Y-axis 23
13
13
34, 39
22
23
23
24
24
23
23
23
23
24
C
collecting data
run up/coast down measurements
configure
bode plot parameters nyquist plot parameters run up/coast down parameters spectrogram plot parameters 37, 39 table parameters waterfall plot parameters WAV setup parameters
23
26
28
44
D
Detection 23, 26, 29, 32, 37 Disp. Order Display Units
34
23, 26, 29, 32, 37
E
Extension Manager 7
F
Freq Range 32, 38
I
install extension module 7
L
LF Cutoff 23, 26, 29, 33, 38 license
extension module
32, 37
Lines
11
31, 34
18
17
M
manage extension modules 12
hide and show
Max Acq Time Max M/c Speed Max No Orders Mode
18, 44
12
19
18, 44
18
N
No. Spectra 34 Num Traces Nyquist plot Nyquist plot parameters
Detection Display Units LF Cutoff Num Traces Spacing 26 Speed Interval Start Spd Stop Spd 26 Time Interval Trace Order
24, 26, 29 25
26
26
26
26
26
26
26
26
P
Pulses/Rev 19, 44
R
Range 18 reviewing data
run up/coast down
RUCD - Bode Plot screen RUCD - Bode Setup screen RUCD - Display Select screen RUCD - Nyquist Plot screen RUCD - Review Data screen RUCD - Spectrogram Plot screen RUCD - Spectrogram Setup screen RUCD - Table screen RUCD - Table Setup screen RUCD - Taking Data screen RUCD - Waterfall screen RUCD - Waterfall Setup screen RUCD - WAV Setup screen Run Up/Coast Down
Bode plot Bode plot screen collecting data deleting data Display Select screen Nyquist plot Nyquist plot screen overview recalling setup Review Data screen
22
15
43
24
22
21
27
43
30
28 20
34
31
44
15
24
19
45
21
25
27
41
43
39
36
Rockwell Automation Publication 1441-UM006A-EN-P - May 2011 47
Index
reviewing data 43 save measurement save setup 40 setting up Setup screen Spectrogram Disp. Setup screen Spectrogram plot 36 Spectrogram plot screen Spectrogram Setup screen Table screen 30 Table Setup screen Taking Data screen Waterfall Disp. Setup screen 33 Waterfall plot Waterfall plot screen Waterfall Setup screen 31 WAV Setup screen
Run Up/Coast Down Setup parameters
Max Acq Time Max M/c Speed 18 Max No Orders Mode Pulses/Rev 19 Range Save To Sens 18 Start Spd Stop Spd Transducer 18
17
18
18
19
19
19
40
22
38
39
36
28 20
31
34
44
19
18
S
Save To 19 Sens
18
Show Overall Spacing Spectrogram Disp. Setup screen Spectrogram plot Spectrogram plot parameters
Blanking Detection Display Units Freq Range LF Cutoff Lines Spacing Speed Interval Start Spd Stop Spd Time Interval X-axis Y-axis Z-axis 39
Speed Interval Start Spd Stop Spd
24
23, 26, 29, 32, 37
38
36
39
37
37
38
38
37
37
37
37
37
37 37 39
23, 26, 29, 32, 37
19, 23, 26, 28, 31, 37, 44
19, 23, 26, 28, 31, 37, 44
Detection Display Units LF Cutoff 29 Num Traces Spacing Speed Interval Start Spd 28 Stop Spd Time Interval Trace Order 29
Time Interval Trace Height Trace Offset Trace Order Transducer
29
29
29
29
29
28
29
23, 26, 29, 32, 37
34
34
24, 26, 29
18
U
uninstall extension module 9
W
Waterfall Disp. Setup screen 33 Waterfall plot Waterfall plot parameters
Blanking Detection Disp. Order Display Units 32 Freq Range LF Cutoff Lines 32 No. Spectra Spacing Speed Interval 32 Start Spd Stop Spd Time Interval Trace Height Trace Offset X-axis Z-axis
WAV setup parameters
Max M/c Speed Mode Pulses/Rev Start Spd Stop Spd
31
34
32
34 32
33
34
32
31
31
32
34
34
32
34
44
44
44
44
44
X
X-axis 32, 37
Y
Y-axis 23, 39
T
Table Format 28 Table parameters
48 Rockwell Automation Publication 1441-UM006A-EN-P - May 2011
Z-axis 34, 39
Z
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçereny, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/ application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434 Outside United States or
Canada
Use the Worldwide Locator your local Rockwell Automation representative.
, you can find technical manuals, a knowledge base of FAQs, technical and
.
at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
one) to your distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
, available at http://www.rockwellautomation.com/literature/.
Publication 1441-UM006A-EN-P - May 2011 50 Copyright © 2011 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...