Rockwell Automation 1440-VST02-01RA User Manual

XM-120 Eccentricity Module
User Guide
Firmware Revision 5
1440-VST02-01RA
Important User Information
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
) describes some important differences between solid state equipment and hard-
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Allen-Bradley, Rockwell Automation, and XM are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Safety Approvals
WARNING
AVERTISSEMENT
IMPORTANT
The following information applies when operating this equipment in hazardous locations.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system arfe subject to investigation by the local Authority Having Jurisdiction at the time of installation.
EXPLOSION HAZARD -
•Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
•Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
•Substitution of components may impair suitability for Class I, Division 2.
•If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
RISQUE D’EXPLOSION –
•Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
•Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
•La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
•S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Wiring to or from this device, which enters or leaves the system enclosure, must utilize wiring methods suitable for Class I, Division 2 Hazardous Locations, as appropriate for the installation in accordance with the product drawings as indicated in the following table.
Model Catalog Number Haz Location Drawings* Model Catalog Number Haz Location Drawings*
w/o Barriers
XM-120 1440-VST0201RA XM-121 1440-VLF0201RA XM-360 1440-TPR0600RE XM-122 1440-VSE0201RA XM-361 1440-TUN0600RE XM-123 1440-VAD0201RA XM-361 1440-TTC0600RE XM-160 1440-VDRS0600RH XM-161 1440-VDRS0606RH XM-441 1440-REX0004RD 48241-HAZ N/A XM-162 1440-VDRP0600RH XM-442 1440-REX0304RG 48642-HAZ N/A XM-220 1440-SPD0201RB 48640-HAZ 48641-HAZ
48178-HAZ 48179-HAZ
51263-HAZ 51264-HAZ
* Drawings are available on the included CD
w/ Barriers
w/o Barriers
XM-320 1440-TPS0201RB 48238-HAZ 48239-HAZ
48295-HAZ 48299-HAZ
XM-440 1440-RMA0004RC 48240-HAZ N/A
w/ Barriers
Introduction
Installing the XM-120 Eccentricity Module

Table of Contents

Chapter 1
Introducing the Eccentricity Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Eccentricity Module Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Using this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Organization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Document Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Chapter 2
XM Installation Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Grounding Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Mounting the Terminal Base Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
DIN Rail Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Interconnecting Terminal Base Units . . . . . . . . . . . . . . . . . . . . . . . 15
Panel/Wall Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Connecting Wiring for Your Module . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Terminal Block Assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Connecting the Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Connecting the Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Connecting the Tachometer Signal. . . . . . . . . . . . . . . . . . . . . . . . . 25
Connecting the Buffered Outputs . . . . . . . . . . . . . . . . . . . . . . . . . 27
Connecting a Non-Contact Sensor . . . . . . . . . . . . . . . . . . . . . . . . . 29
Connecting the Remote Relay Reset Signal . . . . . . . . . . . . . . . . . . 30
Connecting the 4-20 mA Outputs . . . . . . . . . . . . . . . . . . . . . . . . . 32
Serial Port Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
DeviceNet Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Mounting the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Module Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Basic Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Powering Up the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Manually Resetting Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Installing the XM-120 Eccentricity Firmware. . . . . . . . . . . . . . . . . . . . 40
Chapter 3
Configuration Parameters
v Publication GMSI10-UM010C-EN-P - May 2010
Channel Transducer Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Measurement Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Eccentricity Measurement Parameters . . . . . . . . . . . . . . . . . . . . . . 45
Waveform Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Speed Measurement Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Tachometer Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Tachometer Transducer Parameters . . . . . . . . . . . . . . . . . . . . . . . . 47
Tachometer Signal Processing Parameters . . . . . . . . . . . . . . . . . . . 48
Alarm Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Relay Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4-20 mA Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Table of Contents vi
Specifications
DeviceNet Information
I/O Data Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Data Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Monitor Data Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Alarm and Relay Status Parameters . . . . . . . . . . . . . . . . . . . . . . . . 59
Device Mode Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Appendix A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Appendix B
Electronic Data Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Changing Operation Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Transition to Program Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Transition to Run Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
XM Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Invalid Configuration Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Eccentricity I/O Message Formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Poll Message Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
COS Message Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
ADR for XM Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
DeviceNet Objects
Appendix C
Identity Object (Class ID 01H) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
DeviceNet Object (Class ID 03H) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Assembly Object (Class ID 04H) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Class Attribute . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Assembly Instance Attribute Data Format. . . . . . . . . . . . . . . . . . . 82
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Connection Object (Class ID 05H). . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Publication GMSI10-UM010C-EN-P - May 2010
Table of Contents vii
Analog Input Point Object (Class ID 0AH). . . . . . . . . . . . . . . . . . . . . 88
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Parameter Object (Class ID 0FH). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Acknowledge Handler Object (Class ID 2BH) . . . . . . . . . . . . . . . . . . 93
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Alarm Object (Class ID 31DH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Instance Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Device Mode Object (Class ID 320H) . . . . . . . . . . . . . . . . . . . . . . . . . 96
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Relay Object (Class ID 323H) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Spectrum Waveform Measurement Object (Class ID 324H) . . . . . . . 99
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Get_Waveform_Chunk . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Speed Measurement Object (Class ID 325H). . . . . . . . . . . . . . . . . . . 102
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Tachometer Channel Object (Class ID 326H) . . . . . . . . . . . . . . . . . . 103
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Instance Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Transducer Object (Class ID 328H) . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Publication GMSI10-UM010C-EN-P - May 2010
Table of Contents viii
Wiring Connections for Previous Module Revisions
4-20 mA Output Object (Class ID 32AH) . . . . . . . . . . . . . . . . . . . . . 106
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Appendix D
Terminal Block Assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Connecting the Transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Glossary
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Publication GMSI10-UM010C-EN-P - May 2010
Chapter
IMPORTANT
1

Introduction

This chapter provides an overview of the XM-120 Eccentricity module. It also discusses the components of the module.
For information about See page
Introducing the Eccentricity Module 1 Eccentricity Module Components 2 Using this Manual 3
This manual only describes how to install and use the XM-120 Eccentricity module. For information about the dynamic measurement and low frequency dynamic measurement modules, refer to the XM-120/121 Dynamic Measurement Module User Guide.

Introducing the Eccentricity Module

The XM-120 Eccentricity module is a 2-channel eccentricity monitor. It is a
member of the Allen-Bradley™ XM condition monitoring and protection modules that operate both in stand-alone applications or integrate with Programmable Logic Controllers (PLCs) and control system networks.
Eccentricity is the measure of the amount of bow in a rotor. The lower the eccentricity value the more straight the shaft. Rotor bow can be a fixed mechanical bow, or it can be a temporary bow caused by uneven thermal heating or simply by the weight of the rotor (gravity bow).
The Eccentricity module is suitable for virtually all types of rotating and reciprocating machinery where rotor bow must be measured prior to or during startup. It accepts input from non-contact eddy current probe systems to provide peak-to-peak eccentricity, maximum instantaneous DC voltage (max gap), minimum instantaneous DC voltage (min gap), and instantaneous DC voltage (gap) measurements. In addition to the transducer inputs, the module can accept one tachometer input to provide speed measurement, which can, if desired, be used to disable eccentricity alarms after startup.
®
Series, a family of DIN rail mounted
1 Publication GMSI10-UM010C-EN-P - May 2010
2 Introduction
XM-940 Dynamic Measurement Module Terminal Base Unit
Cat. No. 1440-TB-A
XM-120 Dynamic Measurement Module
Cat. No. 1440-VST02-01RA
IMPORTANT
The Eccentricity module includes a single on-board relay, expandable to five, making it a complete monitoring system. It can operate stand-alone, or it can be deployed on a standard or dedicated DeviceNet network where it can provide real-time data and status information to other XM modules, PLCs, distributed control systems (DCS), and Condition Monitoring Systems.
The Eccentricity module can be configured remotely via the DeviceNet network, or locally using a serial connection to a PC or laptop. Refer to Chapter 3 for a list of the configuration parameters.

Eccentricity Module Components

The Eccentricity module consists of a terminal base unit and an instrument module. The XM-120 Dynamic Measurement Module and the XM-940 Terminal Base are shown below.
Figure 1.1 Eccentricity Module Components
XM-940 Dynamic Measurement Module Terminal Base - A DIN rail
mounted base unit that provides terminations for all field wiring required by XM Dynamic Measurement and Eccentricity modules.
Publication GMSI10-UM010C-EN-P - May 2010
XM-120 Dynamic Measurement Module - The XM-120 mounts on the
XM-940 terminal base via a keyswitch and a 96-pin connector. The XM-120 contains the measurement electronics, processors, relay, and serial interface port for local configuration.
The XM-441 Expansion Relay module may be connected to the XM-120 module via the XM-940 terminal base.
When connected to the module, the Expansion Relay module simply “expands” the capability of the XM-120 by adding four additional epoxy-sealed relays. The module controls the Expansion Relay module by extending to it the same logic and functional controls as the on-board relay.
Introduction 3

Using this Manual

This manual introduces you to the XM-120 Eccentricity module. It is intended for anyone who installs, configures, or uses the XM-120 Eccentricity module.

Organization

To help you navigate through this manual, it is organized in chapters based on these tasks and topics.
Chapter 1 "Introduction" contains an overview of this manual and the XM-120 Eccentricity module.
Chapter 2 "Installing the XM-120 Eccentricity Module" describes how to install, wire, and use the Eccentricity module. It also provides instructions on how to install the Eccentricity firmware.
Chapter 3 "Configuration Parameters" provides a complete listing and description of the Eccentricity parameters. The parameters can be viewed and edited using the XM Serial Configuration Utility software and a personal computer.
Appendix A "Specifications" lists the technical specifications for the Eccentricity module.
Appendix B "DeviceNet Information" provides information to help you configure the module over a DeviceNet network.
Appendix C "DeviceNet Objects" provides information on the DeviceNet objects supported by the XM-120 Eccentricity module.
Appendix D "Wiring Connections for Previous Module Revisions" provides terminal block assignments and wiring diagrams of earlier revisions of the XM-120 module (before revision D01).
For definitions of terms used in this Guide, see the Glossary at the end of the Guide.

Document Conventions

There are several document conventions used in this manual, including the following:
Publication GMSI10-UM010C-EN-P - May 2010
4 Introduction
TIP
EXAMPLE
The XM-120 Eccentricity module is referred to as XM-120, Eccentricity module, device, or module throughout this manual.
A tip indicates additional information which may be helpful.
This convention presents an example.
Publication GMSI10-UM010C-EN-P - May 2010
Chapter
ATTENTION
2

Installing the XM-120 Eccentricity Module

This chapter discusses how to install and wire the XM-120 Eccentricity module. It also describes the module indicators and the basic operations of the modules.
For information about See page
XM Installation Requirements 6 Mounting the Terminal Base Unit 13 Connecting Wiring for Your Module 17 Mounting the Module 35 Module Indicators 37 Basic Operations 39 Installing the XM-120 Eccentricity Firmware 40
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 Industrial environment, in overvoltage Category II applications (as defined in IED publication 60664–1), at altitudes up to 2000 meters without derating.
This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present, and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosures.
5 Publication GMSI10-UM010C-EN-P - May 2010
6 Installing the XM-120 Eccentricity Module
ATTENTION
ATTENTION

XM Installation Requirements

This section describes wire, power, and grounding requirements for an XM system.

Wiring Requirements

Use solid or stranded wire. All wiring should meet the following specifications:
14 to 22 AWG copper conductors without pretreatment; 8 AWG
required for grounding the DIN rail for electromagnetic interference (emi) purposes
Recommended strip length 8 millimeters (0.31 inches)
Minimum insulation rating of 300 V
Soldering the conductor is forbidden
Wire ferrules can be used with stranded conductors; copper ferrules
recommended
See the XM Documentation and Configuration Utility CD for Hazardous Locations installation drawings. The XM Documentation and Configuration Utility CD is packaged with the XM modules.

Power Requirements

Before installing your module, calculate the power requirements of all modules interconnected via their side connectors. The total current draw through the side connector cannot exceed 3A. Refer to the specifications for the specific modules for power requirements.
A separate power connection is necessary if the total current draw of the interconnecting modules is greater than 3 A.
Figure 2.1 is an illustration of wiring modules using separate power connections.
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 7
Any limited power source that satisfies the requirements specified below
Figure 2.1 XM Modules with Separate Power Connections
Power Supply Requirements
XM Power Supply Requirements
Listed Class 2 rated supply, or
Protection
Fused* ITE Listed SELV supply, or
Fused* ITE Listed PELV supply Output Voltage 24 Vdc ± 10% Output Power 100 Watts Maximum (~4A @ 24 Vdc) Static Regulation ± 2% Dynamic Regulation ± 3% Ripple < 100mVpp Output Noise Per EN50081-1 Overshoot < 3% at turn-on, < 2% at turn-off Hold-up Time As required (typically 50mS at full rated load) * When a fused supply is used the fuse must be a 5 amp, listed, fast acting fuse such as
provided by Allen-Bradley part number 1440-5AFUSEKIT
Publication GMSI10-UM010C-EN-P - May 2010
8 Installing the XM-120 Eccentricity Module
IMPORTANT
See Application Technique "XM Power Supply Solutions", publication ICM-AP005A-EN-E, for guidance in architecting power supplies for XM systems.

Grounding Requirements

Use these grounding requirements to ensure safe electrical operating circumstances, and to help avoid potential emi and ground noise that can cause unfavorable operating conditions for your XM system.
DIN Rail Grounding
The XM modules make a chassis ground connection through the DIN rail. The DIN rail must be connected to a ground bus or grounding electrode conductor using 8 AWG or 1 inch copper braid. See Figure 2.2.
Use zinc-plated, yellow-chromated steel DIN rail (Allen-Bradley part no. 199-DR1 or 199-DR4) or equivalent to assure proper grounding. Using other DIN rail materials (e.g. aluminum, plastic, etc.), which can corrode, oxidize, or are poor conductors can result in improper or intermittent platform grounding.
Publication GMSI10-UM010C-EN-P - May 2010
Figure 2.2 XM System DIN Rail Grounding
Power Supply
DYNAMIC MEASUREMENT
1440-VST02-01RA
DYNAMIC MEASUREMENT
1440-VST02-01RA
POSITION
1440-TSP02-01RB
MASTER RELAY
1440-RMA00-04RC
EXPANSION RELAY
1440-REX00-04RD
EXPANSION RELAY
1440-REX00-04RD
EXPANSION RELAY
1440-REX00-04RD
EXPANSION RELAY
1440-REX00-04RD
Power Supply
DYNAMIC MEASUREMENT
1440-VST02-01RA
DYNAMIC MEASUREMENT
1440-VST02-01RA
EXPANSION RELAY
1440-REX00-04RD
EXPANSION RELAY
1440-REX00-04RD
1
1
Installing the XM-120 Eccentricity Module 9
1Use 14 AWG wire.
The grounding wire can be connected to the DIN rail using a DIN Rail Grounding Block (Figure 2.3).
Publication GMSI10-UM010C-EN-P - May 2010
10 Installing the XM-120 Eccentricity Module
Figure 2.3 DIN Rail Grounding Block
Panel/Wall Mount Grounding
The XM modules can also be mounted to a conductive mounting plate that is grounded. See Figure 2.5. Use the grounding screw hole provided on the terminal base to connect the mounting plate the Chassis terminals.
Figure 2.4 Grounding Screw on XM Terminal Base
Publication GMSI10-UM010C-EN-P - May 2010
Figure 2.5 Panel/Wall Mount Grounding
Power Supply
Power Supply
1
1
Installing the XM-120 Eccentricity Module 11
1 Use 14 AWG wire.
Publication GMSI10-UM010C-EN-P - May 2010
12 Installing the XM-120 Eccentricity Module
IMPORTANT
IMPORTANT
24V Common Grounding
24 V power to the XM modules must be grounded. When two or more power supplies power the XM system, ground the 24 V Commons at a single point, such as the ground bus bar.
If it is not possible or practical to ground the -24Vdc supply, then it is possible for the system to be installed and operate ungrounded. However, if installed ungrounded then the system must not be connected to a ground through any other circuit unless that circuit is isolated externally. Connecting a floating system to a non-isolated ground could result in damage to the XM module(s) and/or any connected device. Also, operating the system without a ground may result in the system not performing to the published specifications regards measurement accuracy and communications speed, distance or reliability.
The 24 V Common and Signal Common terminals are internally connected. They are isolated from the Chassis terminals unless they are connected to ground as described in this section. See Terminal Block Assignments on page 18 for more information.
Transducer Grounding
Make certain the transducers are electrically isolated from earth ground. Cable shields must be grounded at one end of the cable, and the other end left floating or not connected. It is recommended that where possible, the cable shield be grounded at the XM terminal base (Chassis terminal) and not at the transducer.
DeviceNet Grounding
The DeviceNet network is functionally isolated and must be referenced to earth ground at a single point. XM modules do not require an external DeviceNet power supply. Connect DeviceNet V- to earth ground at one of the XM modules, as shown in Figure 2.6.
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 13
To Ground Bus
ATTENTION
Figure 2.6 Grounded DeviceNet V- at XM Module
Use of a separate DeviceNet power supply is not permitted. See Application Technique "XM Power Supply Solutions", publication ICM-AP005A-EN-E, for guidance in using XM with other DeviceNet products.

Mounting the Terminal Base Unit

For more information on the DeviceNet installation, refer to the ODVA Planning and Installation Manual - DeviceNet Cable System, which is available on the ODVA web site (http://www.odva.org).
Switch Input Grounding
The Switch Input circuits are functionally isolated from other circuits. It is recommended that the Switch RTN signal be grounded at a single point. Connect the Switch RTN signal to the XM terminal base (Chassis terminal) or directly to the DIN rail, or ground the signal at the switch or other equipment that is wired to the switch.
The XM family includes several different terminal base units to serve all of the XM modules. The XM-940 terminal base, Cat. No. 1440-TB-A, is the only terminal base unit used with the Eccentricity module.
Publication GMSI10-UM010C-EN-P - May 2010
14 Installing the XM-120 Eccentricity Module
ATTENTION
Position terminal base at a slight angle and hook over the top of the DIN rail.
The terminal base can be DIN rail or wall/panel mounted. Refer to the specific method of mounting below.
The XM modules make a chassis ground connection through the DIN rail. Use zinc plated, yellow chromated steel DIN rail to assure proper grounding. Using other DIN rail materials (e.g. aluminum, plastic, etc.), which can corrode, oxidize or are poor conductors can result in improper or intermittent platform grounding.
You can also mount the terminal base to a grounded mounting plate. Refer to Panel/Wall Mount Grounding on page 10.

DIN Rail Mounting

Use the following steps to mount the XM-940 terminal base unit on a DIN rail (A-B pt no. 199-DR1 or 199-DR4).
1. Position the terminal base on the 35 x 7.5 mm DIN rail (A).
2. Slide the terminal base unit over leaving room for the side
connector (B).
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 15
IMPORTANT
3. Rotate the terminal base onto the DIN rail with the top of the rail hooked under the lip on the rear of the terminal base.
4. Press down on the terminal base unit to lock the terminal base on the DIN rail. If the terminal base does not lock into place, use a screwdriver or similar device to open the locking tab, press down on the terminal base until flush with the DIN rail and release the locking tab to lock the base in place.

Interconnecting Terminal Base Units

Follow the steps below to install another terminal base unit on the DIN rail.
Make certain you install the terminal base units in order of left to right.
1. Position the terminal base on the 35 x 7.5 mm DIN rail (A).
2. Make certain the side connector (B) is fully retracted into the base unit.
3. Slide the terminal base unit over tight against the neighboring terminal
base. Make sure the hook on the terminal base slides under the edge of the terminal base unit.
4. Press down on the terminal base unit to lock the terminal base on the DIN rail. If the terminal base does not lock into place, use a screwdriver or similar device to open the locking tab, press down on the terminal base until flush with the DIN rail and release the locking tab to lock the base in place.
Publication GMSI10-UM010C-EN-P - May 2010
16 Installing the XM-120 Eccentricity Module
5. Gently push the side connector into the side of the neighboring terminal base to complete the backplane connection.

Panel/Wall Mounting

Installation on a wall or panel consists of:
laying out the drilling points on the wall or panel
drilling the pilot holes for the mounting screws
installing the terminal base units and securing them to the wall or panel
Use the following steps to install the terminal base on a wall or panel.
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 17
Side Connector
1. Lay out the required points on the wall/panel as shown in the drilling dimension drawing below.

Connecting Wiring for Your Module

2. Drill the necessary holes for the #6 self-tapping mounting screws.
3. Secure the terminal base unit using two #6 self-tapping screws.
4. To install another terminal base unit, retract the side connector into the base unit. Make sure it is fully retracted.
5. Position the terminal base unit up tight against the neighboring terminal
base. Make sure the hook on the terminal base slides under the edge of the terminal base unit.
6. Gently push the side connector into the side of the neighboring terminal base to complete the backplane connection.
7. Secure the terminal base to the wall with two #6 self-tapping screws.
Wiring to the module is made through the terminal base unit on which the module mounts. The XM-120 is compatible only with the XM-940 terminal base unit, Cat. No. 1440-TB-A.
Publication GMSI10-UM010C-EN-P - May 2010
18 Installing the XM-120 Eccentricity Module
ATTENTION
TIP
XM-940 (Cat. No. 1440-TB-A)
Revision number of XM module
Figure 2.7 XM-940 Terminal Base Unit

Terminal Block Assignments

The terminal block assignments and descriptions for the Eccentricity module are shown below.
The terminal block assignments are different for different XM modules. The following table applies only to the XM-120 Eccentricity module revision D01 (and later). If you have an earlier revision of the module, refer to Appendix D for its terminal block assignments.
Refer to the installation instructions for the specific XM module for its terminal assignments.
The XM module’s revision number is on the product label (which is located on the front of the XM module, as shown below).
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 19
WARNING
EXPLOSION HAZARD
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Terminal Block Assignments
No. Name Description
0 Xducer 1 (+) Vibration transducer 1 connection 1 Xducer 2 (+) Vibration transducer 2 connection 2 Buffer 1 (+) Vibration signal 1 buffered output 3 Buffer 2 (+) Vibration signal 2 buffered output 4 Tach/Signal In (+) Tachometer transducer/signal input, positive side 5 Buffer Power 1 IN Channel 1 buffer power input
Connect to terminal 6 for positive biased transducers or terminal 21 for negative biased transducers
6 Positive Buffer Bias Provides positive (-5 V to +24 V) voltage compliance to buffered outputs
Connect to terminals 5 (CH 1) or 22 (CH 2) for positive bias transducers 7 TxD PC serial port, transmit data 8 RxD PC serial port, receive data 9
XRTN
1
Circuit return for TxD and RxD
10 Chassis Connection to DIN rail ground spring or panel mounting hole 11 4-20 mA 1 (+) 4-20 mA output 12 4-20 mA 1 (-)
300 ohm maximum load
13 Chassis Connection to DIN rail ground spring or panel mounting hole 14 Chassis Connection to DIN rail ground spring or panel mounting hole 15 Chassis Connection to DIN rail ground spring or panel mounting hole 16
17
18
Xducer 1 (-)
Xducer 2 (-)
Signal Common
1
1
Vibration transducer 1 connection
Vibration transducer 2 connection
1
Vibration buffered output return
19 TACH Buffer Tachometer transducer/signal output 20 Tachometer (-) Tachometer transducer/signal return, TACH Buffer return 21 Buffer/Xducer Pwr (-) Provides negative (-24 V to +9 V) voltage compliance to buffered outputs
Connect to terminals 5 (CH 1) or 22 (CH 2) for negative bias transducers
Transducer power supply output, negative side; used to power external
sensor (40 mA maximum load)
Publication GMSI10-UM010C-EN-P - May 2010
20 Installing the XM-120 Eccentricity Module
Terminal Block Assignments
No. Name Description
22 Buffer Power 2 IN Channel 2 buffer power input
23 CAN_High DeviceNet bus connection, high differential (white wire) 24 CAN_Low DeviceNet bus connection, low differential (blue wire) 25 +24 V Out Internally connected to 24 V In (terminal 44)
26 DNet V (+) DeviceNet bus power input, positive side (red wire) 27 DNet V (-) DeviceNet bus power input, negative side (black wire) 28
24 V Common
29 4-20 mA 2 (+) 4-20 mA output 30 4-20 mA 2 (-) 31 Chassis Connection to DIN rail ground spring or panel mounting hole 32 Chassis Connection to DIN rail ground spring or panel mounting hole
Connect to terminal 6 for positive biased transducers or terminal 21 for
negative biased transducers
Used to daisy chain power if XM modules are not plugged into each other
1
Internally connected to 24 V Common (terminals 43 and 45)
Used to daisy chain power if XM modules are not plugged into each other
If power is not present on terminal 44, there is no power on this terminal
300 ohm maximum load
33 Chassis Connection to DIN rail ground spring or panel mounting hole 34 Chassis Connection to DIN rail ground spring or panel mounting hole 35 Chassis Connection to DIN rail ground spring or panel mounting hole 36 Chassis Connection to DIN rail ground spring or panel mounting hole 37 Chassis Connection to DIN rail ground spring or panel mounting hole 38 Chassis Connection to DIN rail ground spring or panel mounting hole 39 Not Used 40 Switch RTN Switch return, shared between SetPtMult and Reset Relay 41 Reset Relay Switch input to reset internal relay (active closed) 42 Reserved 43
24 V Common
1
Internally DC-coupled to circuit ground
44 +24 V In Connection to primary external +24 V power supply, positive side 45
24 V Common
1
Connection to external +24 V power supply, negative side (internally
DC-coupled to circuit ground) 46 Relay N.C. 1 Relay Normally Closed contact 1 47 Relay Common 1 Relay Common contact 1 48 Relay N.O. 1 Relay Normally Open contact 1 49 Relay N.O. 2 Relay Normally Open contact 2 50 Relay Common 2 Relay Common contact 2 51 Relay N.C. 2 Relay Normally Closed contact 2
Publication GMSI10-UM010C-EN-P - May 2010
1 Terminals are internally connected and isolated from the Chassis terminals.
Installing the XM-120 Eccentricity Module 21
IMPORTANT
IMPORTANT
ATTENTION

Connecting the Power Supply

Power supplied to the module must be nominally 24 Vdc (±10%) and must be a Class 2 rated circuit.
Wire the DC-input power supply to the terminal base unit as shown in Figure
2.8.
Figure 2.8 DC Input Power Supply Connections
A Class 2 circuit can be provided by use of an NEC Class 2 rated power supply, or by using a SELV or PELV rated power supply with a 5 Amp current limiting fuse installed before the XM module(s).
24Vdc needs to be wired to terminal 44 (+24 V In) to provide power to the device and other XM modules linked to the wired terminal base via the side connector.
The power connections are different for different XM modules. Refer to the installation instructions for your specific XM module for complete wiring information.
Publication GMSI10-UM010C-EN-P - May 2010
22 Installing the XM-120 Eccentricity Module
IMPORTANT
TIP
IMPORTANT

Connecting the Relays

The XM-120 has both Normally Open (NO) and Normally Closed (NC) relay contacts. Normally Open relay contacts close when the control output is energized. Normally Closed relay contacts open when the control output is
energized.
The alarms associated with the relay and whether the relay is normally de-energized (non-failsafe) or normally energized (failsafe) depends on the configuration of the module. Refer to Relay Parameters on page 52 for details.
Table 2.1 shows the on-board relay connections for the module.
All XM relays are double pole. This means that each relay has two contacts in which each contact operates independently but identically. The following information and illustrations show wiring solutions for both contacts; although, in many applications it may be necessary to wire only one contact.
The Expansion Relay module may be connected to the module to provide additional relays. Refer the XM-441 Expansion Relay Module User Guide for wiring details.
The NC/NO terminal descriptions (page 20) correspond to a de-energized (unpowered) relay.
When the relay is configured for non-failsafe operation, the relay is normally de-energized.
When the relay is configured for failsafe operation, the relay is normally energized, and the behavior of the NC and NO terminals is inverted.
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 23
Table 2.1 Relay Connections for XM-120
Configured for
Failsafe Operation Relay 1 Terminals
Nonalarm Alarm Wire Contacts Contact 1 Contact 2
Closed Opened COM 47 50
NO 48 49
Opened Closed COM 47 50
NC 46 51
Configured for
Non-failsafe Operation Relay 1 Terminals Nonalarm Alarm Wire Contacts Contact 1 Contact 2
Closed Opened COM 47 50
NC 46 51
Opened Closed COM 47 50
NO 48 49
Figures 2.9 and 2.10 illustrate the behavior of the NC and NO terminals when the relay is wired for failsafe, alarm or nonalarm condition or non-failsafe, alarm or nonalarm condition.
Figure 2.9 Relay Connection - Failsafe, Nonalarm Condition
Non-failsafe, Alarm Condition
Publication GMSI10-UM010C-EN-P - May 2010
24 Installing the XM-120 Eccentricity Module
Figure 2.10 Relay Connection - Failsafe, Alarm Condition
Non-failsafe, Nonalarm Condition
Alternate Relay Wiring
Figures 2.11 and 2.12 show how to wire both ends of a single external indicator to the XM terminal base for failsafe, nonalarm or alarm condition or non-failsafe, nonalarm or alarm condition.
Figure 2.11 Relay Connection - Failsafe, Nonalarm Condition
Non-failsafe, Alarm Condition
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 25
IMPORTANT
Figure 2.12 Relay Connection - Failsafe, Alarm Condition
Non-failsafe, Nonalarm Condition

Connecting the Tachometer Signal

The XM-120 provides a single tachometer input signal. The signal processing performed on the tachometer signal depends on the configuration of the
module. See page 47 for a description of the tachometer parameters.
If you are not using the tachometer input, set the Pulses Per Revolution parameter to zero (0). This will disable the tachometer measurement and prevent the module from indicating a tachometer fault (TACH indicator flashing yellow). A tachometer fault occurs when no signal pulses are received on the tachometer input signal for a relatively long period.
Publication GMSI10-UM010C-EN-P - May 2010
26 Installing the XM-120 Eccentricity Module
Connecting a Magnetic Pickup Tachometer
Figure 2.13 shows the wiring of a magnetic pickup tachometer to the terminal base unit.
Figure 2.13 Magnetic Pickup Tachometer Signal Connection
Connecting a Hall Effect Tachometer Sensor
Figure 2.14 shows the wiring of a Hall Effect Tachometer Sensor, Cat. No. EK-44395, to the terminal base unit.
Figure 2.14 Hall Effect Tachometer Signal Connection
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 27
S
I
G
-
2
4
COM
Signal Common
Tach Input Signal
-24V DC
Shield
S hield Floating
Isolated Sensor Driver
20 21 31
4
18
Connecting a Non-Contact Sensor to the Tachometer Signal
Figure 2.15 shows the wiring of a non-contact sensor to the tachometer input signal.
Figure 2.15 Non-Contact Sensor to Tachometer Signal Connection

Connecting the Buffered Outputs

The XM-120 provides buffered outputs of all transducer input signals. The buffered output connections may be used to connect the module to portable data collectors or other online systems.
Figure 2.16 shows the buffered output connections for the modules.
Publication GMSI10-UM010C-EN-P - May 2010
28 Installing the XM-120 Eccentricity Module
IMPORTANT
Table 2.2 Configuring Buffered Output Input Range
Transducer Input Range Channel Connect Terminal To Terminal
Negative Bias -24 to +9 V 1 5 21
222 21
Positive Bias -5 to +24 V 1 5 6
222 6
Non-Bias -5 to +9 V 1 ---- ----
2 ---- ----
Figure 2.16 Buffered Output Connections
Applies only to XM-120 module revision D01 (and later).
The voltage operating range of the buffered outputs must be configured to coincide with the corresponding transducer bias range. This operating range is configured by placing a jumper from terminal 5 (channel 1) and terminal 22 (channel 2) to either terminal 6 (Positive Buffer Bias) or terminal 21 (Buffer -), depending on the transducer. See Table 2.2. Note the buffered output operating range is configured independently per channel.
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 29
IMPORTANT
ATTENTION
IMPORTANT
TYPICAL WIRING FOR NON-CONTACT SENSOR
TO XM-120 ECCENTRICITY MODULE CHANNEL 1
COM
SIG
-24
Channel 1 Input Signal
-24V DC
0
16
Signal Common
21
5
Jumpering terminal 5 to terminal 21 configures CH 1 buffer for -24V to +9V (See Table 2.1)
Isolated Sensor Driver
Shield
Shield Floating
37

Connecting a Non-Contact Sensor

The Eccentricity module accepts input from any Allen-Bradley non-contact eddy current probe. The figures below show the wiring of a non-contact eddy probe to the terminal base unit.
Figures 2.17 and 2.18 show the wiring to the XM-120 module revision D01 (and later). If you have an earlier revision of the module, refer to Appendix D for wiring information.
You may ground the cable shield at either end of the cable. Do not ground the shield at both ends. Recommended practice is to ground the cable shield at the terminal base and not at the transducer. Any convenient Chassis terminal may be used (see Terminal Block Assignments on page 18).
The internal transducer power supply is providing power to the non-contact sensor.
Figure 2.17 Non-contact Sensor to Channel 1 Wiring
Publication GMSI10-UM010C-EN-P - May 2010
30 Installing the XM-120 Eccentricity Module
TYPICAL WIRING FOR NON-CONTACT SENSOR
TO XM-120 ECCENTRICITY MODULE CHANNEL 2
COM
SIG
-24
Channel 2 Input Signal
-24V DC
1
17
22
Signal Common
21
Jumper ing terminal 21 to terminal 22 configures CH 2 buffer for -24V to +9V (See Table 2.1)
Isolated Sensor Driver
Shield
Shield Floating
38
TIP
TIP
Figure 2.18 Non-contact Sensor to Channel 2 Wiring

Connecting the Remote Relay Reset Signal

If you set the module relay to latching and the relay activates, the relay stays activated even when the condition that caused the alarm has ended. The remote relay reset signal enables you to reset your module relay remotely after you have corrected the alarm condition. This includes latched relays in the Expansion Relay module when it is attached to the XM-120.
If you set a module relay to latching, make sure that any linked relays, such as relays in an XM-440 Master Relay Module, are not configured as latching. When both relays are set to latching, the relay in each module will have to be independently reset when necessary.
You can discretely reset a relay using the serial or remote configuration tool.
Wire the Remote Relay Reset Signal to the terminal base unit as shown in Figure 2.19.
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 31
ATTENTION
ATTENTION
Figure 2.19 Remote Relay Reset Signal Connection
The Switch Input circuits are functionally isolated from other circuits. It is recommended that the Switch RTN signal be grounded at a signal point. Connect the Switch RTN signal to the XM terminal base (Chassis terminal) or directly to the DIN rail, or ground the signal at the switch or other equipment that is wired to the switch.
A single switch contact can also be shared by multiple XM modules wired in parallel as shown in Figure 2.20.
The relay reset connections may be different for different XM modules. Figure 2.20 applies only to the XM-120 module. Refer to the installation instructions for the module for its terminal assignments.
Figure 2.20 Typical Multiple XM Modules Remote Relay Reset Signal Connection
Publication GMSI10-UM010C-EN-P - May 2010
32 Installing the XM-120 Eccentricity Module
ATTENTION
-

Connecting the 4-20 mA Outputs

The module includes an isolated 4-20 mA per channel output into a maximum load of 300 ohms. The measurements that the 4-20 mA output tracks and the signal levels that correspond to the 4 mA and 20 mA are configurable. Refer to 4-20 mA Output Parameters on page 55 for details.
Wire the 4-20 mA outputs to the terminal base unit as shown in Figure 2.21.
Figure 2.21 4-20mA Output Connections
The 4-20 mA outputs are functionally isolated from other circuits. It is recommended that the outputs be grounded at a single point. Connect the 4-20 mA (-) to the XM terminal base (Chassis terminal) or directly to the DIN rail, or ground the signal at the other equipment in the 4-20 mA loop.

Serial Port Connection

The XM-120 includes a serial port connection that allows you to connect a PC to it and configure the module’s parameters. There are two methods of connecting an external device to the module’s serial port.
Ter mi na l Ba s e U n it - There are three terminals on the terminal base
unit you can use for the serial port connection. They are TxD, RxD, and RTN (terminals 7, 8, and 9, respectively). If these three terminals are wired to a DB-9 female connector, then a standard RS-232 serial cable with 9-pin (DB-9) connectors can be used to connect the module to a PC (no null modem is required).
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 33
mini connector
WARNING
IMPORTANT
The DB-9 connector should be wired to the terminal block as shown.
XM-120 Terminal Base Unit (Cat. No. 1440-TB-A)
TX Terminal (terminal 7) ---------------------- Pin 2 (RD - receive data) RX Terminal (terminal 8) ---------------------- Pin 3 (TD - transmit data) RTN Terminal (terminal 9) --------------------- Pin 5 (SG - signal ground)
DB-9 Female Connector
Mini Connector - The mini connector is located on the top of the
module, as shown below.
Figure 2.22 Mini Connector
A special cable (Cat. No. 1440-SCDB9FXM2) is required for this connection. The connector that inserts into the PC is a DB-9 female connector, and the connector that inserts into the module is a USB Mini-B male connector.
If you connect or disconnect the serial cable with power applied to the module or the serial device on the other end of the cable, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
If 24 V Common is not referenced to earth ground, we recommend you use an RS-232 isolator, such as Phoenix PSM-ME-RS232/RS232-P (Cat. No. 1440-ISO-232-24), to protect both the XM module and the computer.
Publication GMSI10-UM010C-EN-P - May 2010
34 Installing the XM-120 Eccentricity Module
IMPORTANT
ATTENTION
ATTENTION

DeviceNet Connection

The XM-120 includes a DeviceNet™ connection that allows the module to communicate with a programmable controller, DCS, or another XM module.
DeviceNet is an open, global, industry-standard communications network designed to provide an interface through a single cable from a programmable controller to a smart device such as the XM-120. As multiple XM modules are interconnected, DeviceNet also serves as the communication bus and protocol that efficiently transfers data between the XM modules.
Connect the DeviceNet cable to the terminal base unit as shown.
Connect To Terminal
Red Wire DNet V+ 26 (optional—see note) White Wire CAN High 23 Bare Wire Shield (Chassis) 10 Blue Wire CAN Low 24 Black Wire DNet V- 27
The DeviceNet power circuit through the XM module interconnect, which is rated at only 300 mA, is not intended or designed to power DeviceNet loads. Doing so could damage the module or terminal base.
To preclude this possibility, even unintentionally, it is recommended that DeviceNet V+ be left unconnected.
You must ground the DeviceNet shield at only one location. Connecting the DeviceNet shield to terminal 10 will ground the DeviceNet shield at the XM module. If you intend to terminate the shield elsewhere, do not connect the shield to terminal 10.
The DeviceNet network must also be referenced to earth at only one location. Connect DNet V- to earth or chassis at one of the XM modules.
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 35
ATTENTION
IMPORTANT
IMPORTANT
ATTENTION
ATTENTION
The DNet V+ and DNet V- terminals are inputs to the XM module. Do not attempt to pass DeviceNet power through the XM terminal base to other non-XM equipment by connecting to these terminals. Failure to comply may result in damage to the XM terminal base and/or other equipment.
Terminate the DeviceNet network and adhere to the requirements and instructions in the ODVA Planning and Installation Manual - DeviceNet Cable System, which is available on the ODVA web site (http://www.odva.org).
The devices are shipped from the factory with the network node address (MAC ID) set to 63. The network node address is software settable. You can use the XM Serial Configuration Utility or RSNetWorx™ for DeviceNet (Version 3.0 or later) to set the network node address. Refer to the appropriate documentation for details.

Mounting the Module

The baud rate for the XM-120 is set by way of “baud detection” (Autobaud) at power-up.
The XM-120 mounts on the XM-940 terminal base unit, Cat. No. 1440-TB-A. We recommend that you mount the module after you have connected the wiring on the terminal base unit.
The XM-120 module is compatible only with the XM-940 terminal base unit. The keyswitch on the terminal base unit should be at position 1 for the modules.
Do not attempt to install XM-120 modules on other terminal base units.
Do not change the position of the keyswitch after wiring the terminal base.
This module is designed so you can remove and insert it under power. However, when you remove or insert the
module with power applied, I/O attached to the module can change states due to its input/output signal changing conditions. Take special care when using this feature.
Publication GMSI10-UM010C-EN-P - May 2010
36 Installing the XM-120 Eccentricity Module
WARNING
IMPORTANT
When you insert or remove the module while power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Install the overlay slide label to protect serial connector and electronics when the serial port is not in use.
1. Make certain the keyswitch (A) on the terminal base unit (C) is at position 1 as required for the module.
Publication GMSI10-UM010C-EN-P - May 2010
2. Make certain the side connector (B) is pushed all the way to the left. Yo u cannot install the module unless the connector is fully extended.
3. Make sure that the pins on the bottom of the module are straight so they
will align properly with the connector in the terminal base unit.
4. Position the module (D) with its alignment bar (E) aligned with the groove (F) on the terminal base.
5. Press firmly and evenly to seat the module in the terminal base unit. The module is seated when the latching mechanism (G) is locked into the module.
6. Repeat the above steps to install the next module in its terminal base.
Installing the XM-120 Eccentricity Module 37

Module Indicators

Eccentricity LED
Module Indicators
The Eccentricity module has seven LED indicators, which include a module status (MS) indicator, a network status (NS) indicator, a status indicator for each channel (CH1, CH2, and TACH), an activation indicator for Eccentricity, and a status indicator for the Relay. The LED indicators are located on top of the module.
Figure 2.23 LED Indicators
The following tables describe the states of the LED status indicators.
Module Status (MS) Indicator
Color State Description
No color Off No power applied to the module. Green Flashing Red Module performing power-up self test.
Flashing
Solid
Module operating in Program Mode
Module operating in Run Mode
Red Flashing Application firmware is invalid or not loaded.
Download firmware to the module.
Firmware download is currently in progress.
Solid An unrecoverable fault has occurred. The module may
need to be repaired or replaced.
1
.
2
.
1 Program Mode - Typically this occurs when the module configuration settings are being updated with the XM
Serial Configuration Utility. In Program Mode, the module does not perform its normal functions. The signal processing/measurement process is stopped, and the status of the alarms is set to the disarm state to prevent a false alert or danger status.
2 Run Mode - In Run Mode, the module collects measurement data and monitors each vibration measurement
device.
Publication GMSI10-UM010C-EN-P - May 2010
38 Installing the XM-120 Eccentricity Module
Network Status (NS) Indicator
Color State Description
No color Off Module is not online.
Module is autobauding.
No power applied to the module, look at Module
Status LED.
Green Flashing Module is online (DeviceNet) but no connections are
currently established.
Solid Module is online with connections currently
established.
Red Flashing One or more I/O connections are in the timed-out state.
Solid Failed communications (duplicate MAC ID or Bus-off).
1 Normal condition when the module is not a slave to an XM-440, PLC, or other master device.
1
Channel 1, Channel 2, and Tachometer Status Indicators
Color State Description
No color Off Normal operation within alarm limits on the channel.
No power applied to the module, look at Module
Status LED.
Yellow Solid An alert level alarm condition exists on the channel
(and no transducer fault, tachometer fault, or danger level alarm condition exists).
Flashing Tach LED
Flashing CH1/2 LED
Red Solid A danger level alarm condition exists on the channel
Flashing A transducer fault condition exists on the channel.
A tachometer fault (no transducer fault) condition exists on the tachometer channel
A tachometer fault condition exists and the channel’s alarm speed range is enabled (and no transducer fault on the channel’s transducer).
(and no transducer fault or tachometer fault condition exists).
Publication GMSI10-UM010C-EN-P - May 2010
Eccentricity Indicator
Color State Description
Yellow Off Either alarm is actively monitoring the eccentricity
measurement.
Solid Neither alarm is actively monitoring the eccentricity
measurement. This occurs when both alarms have the status of DISARM (alarms are disabled, the machine speed is outside of the alarm’s speed range, or the module is in Program mode).
Installing the XM-120 Eccentricity Module 39
Relay Indicator
Color State Description
Red Off On-board relay is not activated.
Solid On-board relay is activated.

Basic Operations

Powering Up the Module

The module performs a self-test at power-up. The self-test includes an LED test and a device test. During the LED test, the indicators will be turned on independently and in sequence for approximately 0.25 seconds.
The device test occurs after the LED test. The Module Status (MS) indicator is used to indicate the status of the device self-test.
MS Indicator State Description
Flashing Red and Green Device self-test is in progress. Solid Green or Flashing Green Device self-test completed successfully,
and the firmware is valid and running.
Flashing Red Device self-test completed, the hardware is
OK, but the firmware is invalid. Or, the firmware download is in progress.
Solid Red Unrecoverable fault, hardware failure, or
Boot Loader program may be corrupted.
Refer to Module Indicators on page 37 for more information about the LED indicators.

Manually Resetting Relays

The XM-120 has an external reset switch located on top of the module, as shown in Figure 2.24.
Publication GMSI10-UM010C-EN-P - May 2010
40 Installing the XM-120 Eccentricity Module
IMPORTANT
Press the Reset Switch to reset the relays
TIP
Figure 2.24 Reset Switch
The switch can be used to reset all latched relays in the module. This includes the relays in the Expansion Relay Module when it is attached to the XM-120.

Installing the XM-120 Eccentricity Firmware

The Reset switch resets the relays only if the input is no longer in alarm or the condition that caused the alarm is no longer present.
Before you can use the XM-120 Eccentricity module, you must install the Eccentricity firmware onto the XM-120 Dynamic Measurement module. The Eccentricity firmware is provided on the XM Documentation and Configuration Utility CD (version 3.10 or later) that is packaged with the XM modules.
XM firmware update files are available for download from the XM Firmware Update page at http://support.rockwellautomation.com
Complete the following steps to install the XM-120 Eccentricity firmware.
1. Make certain you have installed the XM Serial Configuration Utility onto the computer that will be connected directly to the XM-120 module. Refer to the XM-12X Dynamic Measurement Modules Installation Instructions for assistance.
Publication GMSI10-UM010C-EN-P - May 2010
2. Insert the XM Documentation and Configuration Utility CD into the CD-ROM drive of the computer.
3. Connect the computer to the XM-120 module using the special serial cable. Refer to Serial Port Connection on page 32.
Installing the XM-120 Eccentricity Module 41
Click this button to update the device with the Eccentricity firmware
4. Power up the XM-120 module if you haven’t already done so, and start the XM Serial Configuration Utility program. Click the Start program, and then select Programs > Entek > XM > Serial Config Utility.
5. Click the Configure button on the XM Serial Configuration Utility screen. The XM-120 Dynamic Measurement Module Configuration Tool sc reen a ppea rs.
6. Click the Module tab.
7. In the Firmware Update group, click Update Firmware to initiate the firmware update. The Open dialog box appears.
8. Navigate to the Firmware directory on the CD and select the
"xm12E.nvs" file.
Publication GMSI10-UM010C-EN-P - May 2010
42 Installing the XM-120 Eccentricity Module
TIP
TIP
9. Click Open to start the firmware update and click Yes to confirm. The Configuration Tool begins the update and shows its progress in the
Progress dialog box.
10. When the update completes, the message "The module is configured
with the factory defaults. You need to download a configuration." appears. Click OK.
11. Click OK again to return to the XM Serial Configuration Utility screen. Notice that the XM Module icon displays XM-12E instead of XM-120.
12. You are now ready to configure the Eccentricity module. Click the Configure button to display the Eccentricity parameters in the
Configuration Tool. Refer to Chapter 3 for a complete list of the Eccentricity configuration parameters.
Review and edit the Eccentricity parameters as necessary. When you are finished, download the parameters to the module. The module will remain in Program mode until you download a configuration.
For assistance on how to use the XM Serial Configuration Utility, refer to the online help.
Publication GMSI10-UM010C-EN-P - May 2010
Chapter
IMPORTANT
3

Configuration Parameters

This chapter provides a complete listing and description of the Eccentricity parameters. The parameters can be viewed and edited using the XM Serial Configuration Utility software and a personal computer. If the module is installed on a DeviceNet network, configuring can also be performed using a network configuration tool such as RSNetWorx (Version 3.0 or later). Refer to your configuration tool documentation for instructions on configuring a device.
For information about See page
Channel Transducer Parameters 44 Measurement Parameters 45 Tachometer Parameters 47 Alarm Parameters 49 Relay Parameters 52 4-20 mA Output Parameters 55 I/O Data Parameters 56 Data Parameters 57 Device Mode Parameters 60
The appearance and procedure to configure the parameters
The
may differ in different software.
43 Publication GMSI10-UM010C-EN-P - May 2010
44 Configuration Parameters
TIP
Channel Transducer
The channel transducer parameters define the characteristics of the transducers you will be using with the module. Use the parameters to
Parameters
configure the transducer sensitivity, and operating range. There are two instances of the channel transducer parameters, one for each channel.
The Channel LED will flash red when a transducer fault condition exists on the channel even if you are not using the channel. You can keep the Channel LED from flashing red on unused channels by setting the unused channel’s Fault High and Fault Low to greater than zero and less than zero, respectively. For example, set Fault High to +18 volts and set Fault Low to -18 volts.
Transducer Parameters
Parameter Name Description Values/Comments Channel Name (XM Serial
Configuration Utility only) Sensitivity The sensitivity of the transducer in millivolts per
Eng. Units Defines the native units of the transducer. Options: mils
A descriptive name to help identify the channel in the XM Serial Configuration Utility.
Eng. Unit.
Maximum 18 characters
The sensitivity value is included with the transducer’s documentation or it may be imprinted on the side of the transducer.
µm
Fault Low The minimum, or most negative, expected DC
voltage from the transducer.
Fault High The maximum expected DC bias voltage from the
transducer.
Measured DC Bias (EDS File only) Shows the measured DC offset of the transducer
signal. This value is compared with Fault High and Fault Low to determine whether the transducer is working properly.
Transducer Status (EDS File only) States whether a transducer fault exists on the
associated channel.
Volts
Note: A voltage reading outside this range constitutes a transducer fault.
Possible status values: No Fault
Fault
Publication GMSI10-UM010C-EN-P - May 2010
Configuration Parameters 45
TIP

Measurement Parameters

Eccentricity Measurement Parameters

Use these parameters to configure the engineering units and update rate for the eccentricity measurements. There are two instances of the eccentricity measurement parameters, one for each channel.
The Eccentricity Update Rate parameter is for installations where the tachometer signal is not available.
Eccentricity Measurement Parameters
Parameter Name Description Values/Comments Eccentricity Units The data units of the measured values. Options: mils
Eccentricity Update Rate The update rate for the eccentricity, min gap, and
max gap measurements.
Enter a value from 1 to 255 seconds.
Note: This value is used when the tachometer is disabled (Pulses Per Revolution set to zero) or a fault condition exists on the tachometer channel.
µm

Waveform Parameters

There are two instances of the waveform parameters, one for each channel. Use these parameters to set up the waveform measurements.
Waveform Parameters
Parameter Name Description Values/Comments Waveform Period The total period of the waveform measurement. Seconds Number of Points The number of samples in the waveform
measurement.
Options: 256
512 1024 2048
Publication GMSI10-UM010C-EN-P - May 2010
46 Configuration Parameters
TIP
Number of Points
Requested Period(s)
256 512 1024 2048
Actual Sampling Rate
Actual Period
Actual Sampling Rate
Actual Period
Actual Sampling Rate
Actual Period
Actual Sampling Rate
Actual Period
5 51.2 5.0 187.5 2.73 187.5 5.46 187.5 10.92 10 25.6 10.0 51.2 10.0 187.5 5.46 187.5 10.92 25 10.24 25.0 20.48 25.0 40.96 25.0 81.92 25.0
100 2.56 100.0 5.12 100.0 10.24 100.0 20.48 100.0 800 0.32 800 0.64 800.0 1.28 800.0 2.56 800.0
The Wavefor m Period and the Number of Points must be configured such that the sampling rate (Number of Points/Wavefor m Period) is from 0.32 Hz to 187.5 Hz. The module will automatically use 187.5 Hz when the sampling rate is above 93.75, resulting in waveforms collected with a different period than specified.
The table below shows examples. The entries in the table are the actual sampling rate (samples per second) and period corresponding to the waveform period and number of points.
Publication GMSI10-UM010C-EN-P - May 2010
Note that the signal processing hardware applies a low pass filter of 20 Hz to the input signal. Therefore the eccentricity measurements taken at sampling rates above
51.2 samples/second will reflect this low pass filter.
Configuration Parameters 47
Time Constant (milliseconds)
-3dB Frequency (Hz)
Settling Time
(milliseconds)
5 31.8310 11 10 15.9155 22 20 7.9577 44 50 3.1831 110
100 1.5915 220
1200 0.1326 2640

Speed Measurement Parameter

Use the speed measurement parameter to configure the filtering performed on the speed measurement.
Speed Measurement Parameter
Parameter Name Description Values/Comments Exponential Averaging Time
Constant
Sets the 3-dB bandwidth for the digital filter used to calculate the Speed Value. The 3-dB bandwidth is roughly equal to 1 / (2 Time Constant). The greater the value entered, the longer the response of the measured Speed Value to a change in the input signal (less sensitive to noise in the signal). See example table below.
π x Exponential Averaging
Milliseconds

Tachometer Parameters

Tachometer Transducer Parameters

Parameter Name Description Values/Comments Tachometer Name (XM Serial
Configuration Utility only) Fault Low The minimum, or most negative, expected DC
Fault High The maximum expected DC voltage from the
Transducer 3 Status (EDS File only)
The tachometer parameters define the characteristics of the tachometer and determine the signal processing that will be performed on the tachometer signal.
Tachometer Transducer Parameters
A descriptive name to help identify the tachometer in the XM Serial Configuration Utility software.
voltage from the transducer.
transducer. States whether a transducer fault condition exists on
the tachometer channel. If a fault exists, the speed value may not be accurate.
Maximum 18 characters
Volts
Note: A voltage reading outside this range constitutes a transducer fault.
Possible status values: No Fault
Fault
Publication GMSI10-UM010C-EN-P - May 2010
48 Configuration Parameters
IMPORTANT
XM Configuration Utility
EDS File
Auto Trigger Trigger
Mode
XM Configuration Utility
EDS File
Check = Auto Mode Auto Clear = Manual
Mode
Manual

Tachometer Signal Processing Parameters

If you are not using the tachometer channel, set the Pulses per Revolution to zero. This will disable the tachometer
measurement, and prevent the module from indicating a tachometer fault.
Tachometer Signal Processing Parameters
Parameter Name Description Values/Comments Pulses Per Revolution The number of tachometer signal pulses per
revolution of the shaft (number of gear teeth). This setting is useful if a proximity probe located over a gear or shaft with a multi-toothed speed sensing surface is used to generate the input signal.
Fault Time-Out The number of seconds the module should wait after
the last valid tach pulse before it indicates a tachometer fault.
Sets the trigger mode. In Auto Trigger mode, the minimum signal amplitude for triggering is 2 volts peak-to-peak and minimum frequency is 6 CPM (0.1 Hz).
In Manual Trigger mode, the value entered in Trigger Threshold is used as the trigger point. Minimum signal amplitude for triggering is 500 millivolts peak-to-peak and minimum frequency is 1 CPM.
Enter zero if you are not using the tachometer channel to disable the tachometer measurement.
Note: The Eccentricity, Min Gap, and Max Gap measurements will be updated after the number of Pulses per Revolution has occurred on the tachometer channel. If Pulses Per Revolution is set to zero, the measurements will be updated after the Eccentricity Update Rate has elapsed.
Enter a value from 1 to 64 seconds.
Trigger Hysteresis The amount of hysteresis around the trigger
Trigger Threshold
Publication GMSI10-UM010C-EN-P - May 2010
threshold. In Auto Trigger mode, the value entered is a percentage of the peak-to-peak input signal. This value can range from 0 to 50%.
In Manual Trigger mode, the value entered is a voltage level. The hysteresis voltage is added to or subtracted from the threshold voltage to determine the hysteresis range. The minimum value is 0.12 volts.
The signal level to be used as the trigger value when in Manual Trigger mode.
% in Auto Trigger mode Volts in Manual Trigger mode
Enter a value from +16 to -16 volts dc.
Note: This value is not used in Auto Trigger mode.
Configuration Parameters 49
XM Configuration Utility
EDS File
Check to Enable Enabled Clear to Disable Disabled
Tachometer Signal Processing Parameters
Parameter Name Description Values/Comments Trigger Slope The input signal slope to be used as the trigger value
when in Manual Trigger mode.
Options: Positive
Negative
Note: This value is not used in Auto Trigger mode.

Alarm Parameters

The Alarm parameters control the operation of the alarms (alert and danger level) and provide alarm status. The Eccentricity module provides two alarms, one per eccentricity channel. Use the parameters to configure which eccentricity measurement the alarm is associated with, as well as the behavior of the alarm.
Alarm Parameters
Parameter Name Description Values/Comments Number (1-2) (XM Serial
Configuration Utility only)
Name (XM Serial Configuration Utility only)
Enable Enable/disable the selected alarm.
The alarm to be configured in the XM Serial Configuration Utility. There are two alarms in the Eccentricity module, one for each eccentricity channel.
A descriptive name to identify the alarm in the XM Serial Configuration Utility.
Note: The Alarm Status is set to "Disarm" when the alarm is disabled.
Options: 1 (Channel 1 alarm)
Maximum 18 characters
2 (Channel 2 alarm)
Publication GMSI10-UM010C-EN-P - May 2010
50 Configuration Parameters
Alarm Parameters
Parameter Name Description Values/Comments Condition Controls when the alarm should trigger.
Options: Greater Than
Greater than - Triggers the alarm when the
measurement value is greater than or equal to the Alert and Danger Threshold values.
The Danger Threshold value must be greater than or equal to the Alert Threshold value for the trigger to occur.
Less than - Triggers the alarm when the
measurement value is less than or equal to the Alert and Danger Threshold values.
The Danger Threshold value must be less than or equal to the Alert Threshold value for the trigger to occur.
Inside range - Triggers the alarm when the
measurement value is equal to or inside the range of the Alert and Danger Threshold values.
The Danger Threshold (High) value must be less than or equal to the Alert Threshold (High) value AND the Danger Threshold (Low) value must be greater than or equal to the Alert Threshold (Low) value for the trigger to occur.
Outside range - Triggers the alarm when the
measurement value is equal to or outside the range of the Alert and Danger Threshold values.
The Danger Threshold (High) value must be greater than or equal to the Alert Threshold (High) value, AND the Danger Threshold (Low) value must be less than or equal to the Alert Threshold (Low) value for the trigger to occur.
Less Than Inside Range Outside Range
Publication GMSI10-UM010C-EN-P - May 2010
Configuration Parameters 51
XM Configuration Utility
EDS File
Check to Enable Enabled Clear to Disable Disabled
Alarm Parameters
Parameter Name Description Values/Comments Alert Threshold (High)
The threshold value for the alert (alarm) condition.
Note: This parameter is the greater threshold value
Same measurement unit as the Eccentricity Unit selection for the specified channel.
when Condition is set to "Inside Range" or "Outside Range."
Danger Threshold (High) The threshold value for the danger (shutdown)
condition.
Note: This parameter is the greater threshold value when Condition is set to "Inside Range" or "Outside Range."
Alert Threshold (Low) The lesser threshold value for the alert (alarm)
condition.
Note: This parameter is not used when Condition is set to "Greater Than" or "Less Than."
Danger Threshold (Low) The lesser threshold value for the danger (shutdown)
condition.
Note: This parameter is not used when Condition is set to "Greater Than" or "Less Than."
Hysteresis The amount that the measured value must fall
(below the threshold) before the alarm condition is cleared. For example, Alert Threshold = 120 and Hysteresis = 2. The alarm (alert) activates when the measured value is 120 and will not clear until the measured value is 118.
Note: The Alert and Danger Thresholds use the same hysteresis value.
Note: For the Outside Range condition, the hysteresis value must be less than Alert Threshold
(High) – Alert Threshold (Low).
Speed Range Enable Controls whether the alarm is enabled only when the
measured speed is within a machine speed range. Enter the machine speed range in Speed Range
High and Speed Range Low.
Note: The tachometer must be
enabled (Pulses Per Revolution set to 1 or more) and a tachometer signal must be provided at the tachometer input when Speed Range Enable is enabled.
Publication GMSI10-UM010C-EN-P - May 2010
52 Configuration Parameters
IMPORTANT
Alarm Parameters
Parameter Name Description Values/Comments Speed Range Low
Speed Range High The greater threshold of the machine speed range.
The lesser threshold of the machine speed range. This value must be less than the Speed Range High value.
This parameter is not used when Speed Range Enabled is disabled.
This value must be greater than the Speed Range Low value.
This parameter is not used when Speed Range Enabled is disabled.
RPM

Relay Parameters

The Relay parameters control the operation of the on-board relay, as well as the relays on the Expansion Relay (XM-441) module. Use these parameters to configure which alarm(s) the relay is associated with, as well as the behavior of the relay.
A relay can be defined, regardless of whether or not it is physically present. A non-physical relay is a virtual relay. When a relay (physical or virtual) activates, the module sends a Change of State (COS) message to its master, which acts on the condition as necessary. An XM-440 Master Relay Module can activate its own relays in response to a relay (physical or virtual) activation at any of its slaves.
Relay Parameters
Parameter Name Description Options/Comments Number (XM Serial Configuration
Utility only)
Sets the relay to be configured in the XM Serial Configuration Utility.
Relay Number 1 is the on-board relay. Numbers 2 through 5 are either relays on the Expansion Relay module when it’s connected to the module or virtual relays.
Virtual relays are non-physical relays. Use them when you want the effect of the relay (monitor alarms, delay, and change status) but do not need an actual contact closure. For example, a PLC or controller monitoring the relay status.
Publication GMSI10-UM010C-EN-P - May 2010
Note: The Relay Installed parameter indicates whether a relay is a virtual relay or a physical relay on a module.
Configuration Parameters 53
XM Configuration Utility
EDS File
Check to Enable Enabled Clear to Disable Disabled
XM Configuration Utility
EDS File
Latching Latching
Option
XM Configuration Utility
EDS File
Check means latching (relay must be explicitly reset)
Latching
Clear means non-latching (relay is reset once the alarm condition has passed)
Nonlatching
XM Configuration Utility
EDS File
Activation Logic Logic
XM Configuration Utility
EDS File
Alarm A/B Alarm
Identifier A/B
Relay Parameters
Parameter Name Description Options/Comments Name (XM Serial Configuration
Utility only)
A descriptive name to help identify the relay in the XM Serial Configuration Utility.
Maximum 18 characters
Enable Enable/disable the selected relay.
Note: The Relay Current Status is set to "Not
Activated" when the relay is disabled. See page 57.
Controls whether the relay must be explicitly reset after the alarm subsides.
Activation Delay Enter the length of time for which the Activation
Logic must be true before the relay is activated. This
reduces nuisance alarms caused by external noise and/or transient vibration events.
Sets the relay activation logic.
A or B - Relay is activated when either Alarm A or
Alarm B meets or exceeds the selected Alarm Status condition(s).
A and B - Relay is activated when both Alarm A
and Alarm B meet or exceed the selected Alarm Status condition(s).
A Only - Relay is activated when Alarm A meets
or exceeds the selected Alarm Status condition(s).
Sets the alarm(s) that the relay will monitor. The alarm must be from the same device as the relay. When the Activation Logic is set to "A and B" or "A or B," you can select an alarm in both Alarm A and Alarm B. The system monitors both alarms. When the Activation Logic is set to "A Only," you can select an alarm only in Alarm A.
Enter a value from 0 to 25.5 seconds, adjustable in increments of 0.1 seconds.
Default is 1 second Options: A only
A or B A and B
Alarm Number 1 or 2
Note: You can only select an alarm that is enabled.
Publication GMSI10-UM010C-EN-P - May 2010
54 Configuration Parameters
XM Configuration Utility
EDS File
Alarm Status to Activate On
Alarm Levels
XM Configuration Utility
EDS File
Check = Physical Relay
Installed = Physical Relay
Clear = Virtual Relay Not Installed =
Virtual Relay
Relay Parameters
Parameter Name Description Options/Comments
Sets the alarm conditions that will cause the relay to
Options: Normal
activate. You can select more than one.
Normal - The current measurement is not within
excess of any alarm thresholds.
Alert - The current measurement is in excess of
the alert level threshold(s) but not in excess of the danger level threshold(s).
Danger - The current measurement is in excess of
the danger level threshold(s).
Check to enable. Clear to disable.
Disarm-The alarm is disabled or the device is in
Program mode.
Xdcr Fault - A transducer fault is detected on the
associated transducer.
Module Fault - Hardware or firmware failure, or
an error has been detected and is preventing proper operation of the device.
Ta ch o Fault - A required tachometer signal has
not been detected. Note that there is no transducer fault either.
Relay Installed Indicates whether the relay is a physical relay on a
module or a virtual relay. If the relay is a physical relay, then you can set the Failsafe parameter.
Danger Xdcr Fault Tacho Fault Alert Disarm Module Fault
If the relay is a virtual relay, the Failsafe parameter is not used or it is disabled.
Publication GMSI10-UM010C-EN-P - May 2010
Configuration Parameters 55
XM Configuration Utility
EDS File
Failsafe Relay Failsafe
Option
XM Configuration Utility
EDS File
Check means failsafe
Failsafe
Clear means non-failsafe
Nonfailsafe
XM Configuration Utility
EDS File
Check to enable Enabled Clear to disable Disabled
Relay Parameters
Parameter Name Description Options/Comments
Determines whether the relay is failsafe or non-failsafe.
Failsafe operation means that when in alarm, the relay contacts are in their "normal," de-energized, or "shelf-state" positions. In other words, normally closed relays are closed in alarm, and normally open relays are open in alarm. With failsafe operation, a power failure equals an alarm.
The following are true of a relay in failsafe operation:
The relay is energized when power is applied to
the module.
The relay in a nonalarmed condition has power
applied to the coil.
In alarm condition, power is removed from the
relay coil, causing the relay to change state.
For non-failsafe operation, the following are true:
Under nonalarm conditions, the relay closes the
circuit between the common and the N.C. (normally closed) terminals.
Under alarm conditions, the relay changes state to
close the circuit between the common and the N.O. (normally open) terminals.

4-20 mA Output Parameters

4-20 mA Parameters
Parameter Name Description Options/Comments Enable Enables/disables the 4-20 mA output.
Min Range The measured value associated with the 4 mA. Same measurement unit as the Max Range The measured value associated with the 20 mA.
For failsafe operation, the following are true:
Under nonalarm (with power applied to the unit)
conditions, the relay closes the circuit between the common and the N.O. terminals.
Under alarm or loss-of-power conditions, the relay
changes state to close the circuit between the common and the N.C. terminals.
The 4-20 mA output parameters define the characteristics of the two 4-20 mA output signals. The parameters are the same for each output.
Eccentricity Unit selection for the specified channel.
Publication GMSI10-UM010C-EN-P - May 2010
56 Configuration Parameters
IMPORTANT
IMPORTANT
IMPORTANT
Measured values between Min Range and Max Range are scaled into the range from 4.0 to 20.0 to produce the output value. The Min Range value does not have to be less than the Max Range value. If the Min Range value is greater than the Max Range value, then the output signal is effectively inverted from the input signal.
The 4-20 mA outputs are either on or off. When they are on, the 4-20 mA outputs overshoot the 4 and 20 mA limits by 10% when the measurement exceeds the minimum and maximum range. This means the minimum current produced is 3.6 mA and the maximum current produced is 22 mA.
When the 4-20 mA outputs are off, they produce a current approximately 2.9 mA. The 4-20 mA outputs are off under the following conditions:
The 4-20 mA outputs are set to "Disable" (see Enable on the previous page).

I/O Data Parameters

The module is in Program mode.
A transducer fault or tachometer fault occurs that affects
the corresponding measurement.
The I/O data parameters are used to configure the content and size of the DeviceNet I/O Poll response message.
The XM-120 must be free of Poll connections when configuring the Poll Output (Poll Response Assembly) and Poll Size. Any attempt to download the parameters while a master device has established the Poll connection with the Eccentricity module will result in an error.
To close an existing Poll connection with an XM-440, switch the XM-440 from Run mode to Program mode. Refer to Changing Operation Modes on page 67.
To close an existing Poll connection with other master devices, remove the module from the scan list or turn off the master device.
Publication GMSI10-UM010C-EN-P - May 2010
I/O Data Parameters
Parameter Name Description Values/Comments COS Size (XM Serial
Configuration Utility only)
The size (number of bytes) of the Change of State (COS) message.
The COS Size cannot be changed.
Configuration Parameters 57
XM Configuration Utility
EDS File
Poll Output Poll
Response Assembly
TIP
I/O Data Parameters
Parameter Name Description Values/Comments COS Output (XM Serial
Configuration Utility only)
Poll Size Sets the size (number of bytes) of the Poll response
The Assembly instance used for the COS message. The COS message is used to produce the Alarm and Relay status for the module.
message. Decreasing the maximum size will truncate data from the end of the Assembly structure.
Important: If you set the Poll Output to "Custom Assembly," the poll size is automatically set to the actual size of the customized Poll response.
The COS Output cannot be changed. Refer to COS Message Format on page 73 for more information.
The minimum size is 4 bytes and the maximum size is 124 bytes.
Assembly Instance Table (XM Serial Configuration Utility only)
Custom Assembly (XM Serial Configuration Utility only)

Data Parameters

Sets the Assembly instance used for the Poll response message. Each Assembly instance contains a different arrangement of the Poll data.
The Poll response message is used by the XM module to produce measured values. It can contain up to 31 REAL values for a total of 124 bytes of data.
Displays the format of the currently selected COS or Poll Assembly instance.
Defines a custom data format for the Poll response. The custom assembly can contain any of the measurement parameters included in Assembly instance 101, as well as alarm and relay configuration parameters.
Options: Assembly Instance 101
Assembly Instance 102 Assembly Instance 103 Assembly Instance 104 Custom Assembly
Refer to Poll Message Format on page 71 for more information.
The highlighted (yellow) Assembly structure bytes are included in the I/O message.
You can select up to 20 parameters.
Refer to Poll Message Format on page 71 for the more information.
The Data parameters are used to view the measured values of the input channels, as well as to monitor the status of the channels, alarms, and relays.
To view all the data parameters in the XM Serial Configuration Utility, click the View Data tab.
Publication GMSI10-UM010C-EN-P - May 2010
58 Configuration Parameters
XM Configuration Utility
EDS File
Xdcr DC Bias Transducer 3
Measured DC Bias

Monitor Data Parameters

Monitor Data Parameters
Parameter Name Description Values/Comments Channel Status (XM Serial
Configuration Utility only)
Eccentricity Shows the measured eccentricity value. These values get updated after: Maximum Gap The maximum measured transducer gap value. Minimum Gap The minimum measured transducer gap value.
Gap Value Shows the measured transducer gap value. This
Speed Status (XM Serial Configuration Utility only)
States whether a fault condition exists on the associated channel. If a fault exists, the eccentricity measurement may not be accurate.
The following conditions can cause a fault:
a transducer fault on the associated channel
no tachometer signal or a transducer fault exists
on the tachometer channel
the module is in Program mode
value is compared with Fault High and Fault Low to determine whether the transducer is working properly.
States whether a fault condition (no tachometer signal or transducer fault) exists on the tachometer channel. If a fault exists, the speed and DC Bias values may not be accurate.
Shows the measured average DC offset of the tachometer signal. This value is compared with Fault High and Fault Low to determine whether the tachometer is working properly.
Possible status values: No Fault
the number of Pulses per
Revolution has occurred, or
the Eccentricity Update Rate has
elapsed
Possible status values: No Fault
Fault
Fault
Speed Value Shows the measured speed value.
Publication GMSI10-UM010C-EN-P - May 2010
Configuration Parameters 59
XM Configuration Utility
EDS File
Alarm Alarm Status

Alarm and Relay Status Parameters

Alarm and Relay Status Parameters
Parameter Name Description Values/Comments
States the current status of the alarm. Possible status values:
Normal - The alarm is enabled, the
device is in Run mode, there is no transducer fault, and the current measurement is not within the Alert or Danger Threshold value(s).
Alert - The alarm is enabled, the
device is in Run mode, there is no transducer fault, and the current measurement is in excess of the Alert Threshold value(s) but not in excess of the Danger Threshold value(s).
Danger - The alarm is enabled, the
device is in Run mode, there is no transducer fault, and the current measurement is in excess of the Danger Threshold value(s).
Disarm-The alarm is disabled or the
device is in Program mode.
Transducer Fault - The alarm is
enabled, the device is in Run mode, and a transducer fault is detected on the associated transducer.
Tachometer Fault - The alarm is
enabled, the device is in Run mode, a tachometer fault exists, but there is no transducer fault.
Module Fault - Hardware or
firmware failure, or an error has been detected and is preventing proper operation of the device.
Relay Status States the current status of the relay. Possible status values: Activated
Not Activated
Publication GMSI10-UM010C-EN-P - May 2010
60 Configuration Parameters
IMPORTANT

Device Mode Parameters

The Device Mode parameters are used to control the functions and the behavior of the device.
The XM Serial Configuration Utility handles these parameters automatically and transparently to the user.
Device Mode Parameters
Parameter Name Description Values/Comments Device Mode Sets the current operation mode of the device. Refer
to Changing Operation Modes on page 67 for more information.
Autobaud Enables/disables autobaud.
When autobaud is set to "Enabled," the module will listen to other devices on the network to determine the correct baud rate to use for communications. When autobaud is set to "Disabled," the module baud rate must be set manually.
Options: Run Mode
Options: Enabled
Program Mode
Disabled
Publication GMSI10-UM010C-EN-P - May 2010
Appendix
A

Specifications

The Appendix lists the technical specifications for the Eccentricity module.
XM-120 Eccentricity Technical Specifications
Product Feature Specification
Communications
DeviceNet
Standard DeviceNet protocol for all functions
NOTE: The XM-120 uses only the DeviceNet protocol, not power. Module power is provided independently.
Available Electronic Data Sheet (EDS) file provides support for most DeviceNet compliant systems Baud rate automatically set by bus master to 125 kb, 250 kb, 500 kb Configurable I/O Poll Response message helps optimize space utilization within scanner input tables.
Selectable Poll Response Assembly Selectable Poll Response Size (bytes)
Side Connector
Serial
All XM measurement and relay modules include side connectors that allow interconnecting adjacent modules, thereby simplifying the external wiring requirements. The interconnect provides primary power, DeviceNet communication, and the circuits necessary to support expansion modules, such as the XM-441 Expansion Relay module.
RS-232 via mini-connector or terminal base unit
Baud rate fixed at 19200.
NOTE: Local configuration via Serial Configuration Utility.
61 Publication GMSI10-UM010C-EN-P - May 2010
62 Specifications
XM-120 Eccentricity Technical Specifications
Product Feature Specification
Inputs
2 Channels
Eddy current transducer signals
Tachometer
Outputs
Transducer Power
Voltage Range
Sensitivity
Input Impedance
1 Tachometer Input
Input Impedance
Speed/Frequency Range
Speed Measurement Error
4-20 mA Outputs
Constant voltage (+24V dc)* None (voltage input)
*Tachometer may be powered, constant voltage,
or configured as voltage input.
Selectable in software as 0 to ±20 V (min) 40 V max. peak-to-peak
User configurable in software
Greater than 100kohms
±25 V (50 V max. peak to peak) 1 to 50,000 events per revolution
120 kohms minimum
1 to 1,200,000 RPM
0.0167 to 20,000 Hz
1 to 12,000 RPM* +/- 1 RPM 12,001 to 120,000 RPM* +/- 6 RPM 120,001 to 1,200,000 RPM* +/- 50 RPM
* Exponential Averaging Time Constant
parameter set to 120ms
Two isolated outputs (one per eccentricity channel) 300 ohm max load
Publication GMSI10-UM010C-EN-P - May 2010
Indicators
Buffered Outputs
7 LEDs Module Status - red/green
1 active buffer per vibration input channel Resistive buffer for tachometer
Network Status - red/green Channel 1 Status - yellow/red Channel 2 Status - yellow/red Tachometer Status - yellow/red Eccentricity -yellow Relay - red
XM-120 Eccentricity Technical Specifications
Product Feature Specification
Signal Conditioning
Frequency Response
Peak-to-peak Eccentricity, Max Gap, Min Gap: 0.0039 to 20 Hz (0.235 to 1200 cpm) Gap: 0 to 20 Hz (0 to 1200 cpm)
Specifications 63
Accuracy
±1% of measurement Noise Floor: 8 mV RMS Specified at ambient temperature of +25°C (+77°F)
Gap Resolution
Waveform
5.2mV
Block Size: 256, 512, 1024, 2048 Periods: 5 to 800 seconds
Amplitude Range
±21 V Complex Data Waveform (asynchronous) Measured Parameters
Speed
Peak-to-peak eccentricity
RPM
Peak-to-peak eccentricity is the difference
between the positive and the negative
extremes of the rotor bow.
µm or mils
Gap (or transducer bias voltage)
Min Gap
Max Gap
Volts
Volts
Volts Alarms
Number
2 alarm and danger pairs (one each for the
eccentricity measurements)
Operators
Hysteresis
Speed Inhibit
Greater than
Less than
Inside range
Outside range
User configurable in software
A speed range may be specified for each
alarm. When applied, the alarm is disabled
when speed is outside of the defined range.
Publication GMSI10-UM010C-EN-P - May 2010
64 Specifications
XM-120 Eccentricity Technical Specifications
Product Feature Specification
Relays
Number
Single on-board relay, two sets of contacts -
DPDT (2 Form C)
Four additional relays when interconnected
to an XM-441 Expansion Relay module, or
Four virtual relays whose status can be
used by remote Control Systems or the
XM-440 Master Relay module
On-board Relay Rating
Failsafe
Latching
Time Delay
Voting Logic
Reset
Maximum Voltage: 120V dc, 125V ac
Maximum Current: 3.5 A*
Minimum Current: 0
Maximum Power: 60 W, 62.5 VA
*Max current is up to 40°C, then derates to 2 A
at 65°C
Agency Rating:
120V ac @ 0.5 A
110V dc @ 0.3 A
30V dc @ 1.0 A
Normally energized (failsafe), or
Normally de-energized (non-fail-safe)
Latching, or
Non-latching
0 to 25.5 seconds, adjustable in 100msec
increments
Single or paired "And" or "Or" logic applied
to any alarm
Local reset switch on top of module
Remote reset switch wired to terminal base
Digital reset command via serial or
DeviceNet interface
Publication GMSI10-UM010C-EN-P - May 2010
Activation On
Alarm Status:
Normal Alert Danger Disarm Transducer fault Module fault Tacho fault
Specifications 65
XM-120 Eccentricity Technical Specifications
Product Feature Specification
Non-Volatile Configuration A copy of the module configuration is
retained in non-volatile memory from where
it is loaded upon power up*.
*The configuration stored in non-volatile
memory can be deleted only by a module-reset command sent via the serial interface, using the Serial Configuration Utility, or via DeviceNet from any compliant software application.
Accuracy (minimum) ±1% of full scale range for the channel
±1% of alarm setpoint for speed Power
Module
+21.6 to +26.4V dc
Environmental
Physical
Consumption
Heat Production
Transducer
Operating Temperature
Storage Temperature
Relative Humidity
Conformal Coating
Dimensions
Terminal Screw Torque
Maximum: 300 mA
Typical: 175 mA
Maximum: 7 Watts (24 BTU/hr)
Typical: 4 Watts (14 BTU/hr)
Isolated 24V dc, user configurable with
wiring
-20 to +65°C (-4 to +149°F)
-40 to +85°C (-40 to +185°F)
95% non-condensing
All printed circuit boards are conformally
coated in accordance with IPC-A-610C.
Height: 3.8 in (97 mm)
Width: 3.7 in (94 mm)
Depth: 3.7 in (94 mm)
7 pound-inches (0.6 Nm)
Publication GMSI10-UM010C-EN-P - May 2010
66 Specifications
UL UL Listed for Ordinary
Locations
UL UL Listed for Class I, Division 2
Group A, B, C, and D Hazardous Locations
CSA CSA Certified Process Control
Equipment
CSA CSA Certified Process Control
Equipment for Class I, Division 2 Group A, B, C, and D Hazardous Locations
EEX* European Union 94/9/EEC ATEX
Directive, compliant with EN 50021; Potentially Explosive Atmospheres, Protection “n”
CE* European Union 89/336/EEC
EMC Directive
C-Tick* Australian
Radiocommunications Act, compliant with: AS/NZS 2064, Industrial Emissions
XM-120 Eccentricity Technical Specifications
Product Feature Specification
Approvals (when product or packaging is marked)
Publication GMSI10-UM010C-EN-P - May 2010
*See the Product Certification link at
www.rockwellautomation.com for Declarations of Conformity, Certificates and other certification details.

DeviceNet Information

IMPORTANT
Appendix
B

Electronic Data Sheets

Changing Operation Modes

Electronic Data Sheet (EDS) files are simple text files used by network configuration tools such as RSNetWorx (Version 3.0 or later) to help you identify products and easily commission them on a network. The EDS files describe a product’s device type, product revision, and configurable parameters on a DeviceNet network.
The EDS files for the XM modules are installed on your computer with the XM configuration software. The latest EDS files can also be obtained at http://www.ab.com/networks/eds/ or by contacting your local Rockwell Automation representative.
Refer to your DeviceNet documentation for instructions on registering the EDS files.
XM modules operate in two modes.
Mode Description
Run The XM measurement modules collect measurement data and
monitor each measurement device. The XM-440 establishes I/O connections with the XM measurement modules in its scan list and monitors their alarms, and controls its own relay outputs accordingly.
Program The XM module is idle.
The XM measurement modules stop the signal processing/measurement process, and the status of the alarms is set to the disarm state to prevent a false alert or danger status. The XM-440 closes the I/O connections with the XM measurement modules in its scan list and stops monitoring their alarms, relays are deactivated unless they are latched. Configuration parameters can be read, updated and downloaded to the XM module.
To change the operation mode of the module, use the Device Mode parameter in the EDS file. Note that the Stop and Start services described on page 69 can also be used to change the operation mode.
The XM Serial Configuration Utility software automatically puts XM modules in Program mode and Run mode without user interaction.
67 Publication GMSI10-UM010C-EN-P - May 2010
68 DeviceNet Information
TIP
TIP
TIP
TIP

Transition to Program Mode

Parameter values can only be downloaded to an XM module while the module is in Program mode. Any attempt to download a parameter value while the module is in Run mode will result in a Device State Conflict error.
To transition an XM module from Run mode to Program mode on a DeviceNet network, set the Device Mode parameter to "Program mode" and click Apply. Note that you cannot change any other parameter until you have downloaded the Program mode parameter.
The Module Status indicator flashes green when the module is in Program mode.
Refer to your DeviceNet documentation for specific instructions on editing EDS device parameters.
You can also use the Stop service described on page 69 to transition XM modules to Program mode.

Transition to Run Mode

In order to collect data and monitor measurement devices, XM modules must be in Run mode. To transition an XM module from Program mode to Run mode on a DeviceNet network, set the Device Mode parameter to "Run mode" and click Apply.
The Module Status indicator is solid green when the module is in Run mode.
Refer to your DeviceNet documentation for specific instructions on editing EDS device parameters.
You can also use the Start service described on page 69 to transition XM modules to Run mode.
Publication GMSI10-UM010C-EN-P - May 2010
DeviceNet Information 69

XM Services

XM Services
Action
Transition to Run Mode Start
Transition to Program Mode Stop
Save configuration to non-volatile memory (EEPROM)
Delete saved configuration from non-volatile memory (EEPROM)
Reset a specific latched relay Reset
Reset all latched relays Reset
The table below defines services supported by the XM modules. The table includes the service codes, classes, instances, and attributes by their appropriate hexadecimal codes. Use the Class Instance Editor in RSNetWorx to execute these services, as illustrated in the example below.
Service Code (Hex)
(06)
(07) Save
(16) Delete
(09)
(05)
(05)
Class (Hex) Instance Attribute Data
Device Mode Object (320)
Device Mode Object (320)
Device Mode Object (320)
Device Mode Object (320)
Relay Object (323)
Relay Object (323)
1 None None
1 None None
1 None None
1 None None
Relay number 1-C for XM-440, 1-5 for XM-12X, XM-320 and XM-220, 1-8 for XM-36X and XM-16X
0 None None
None None
Reset the Peak Speed (XM-12X only)
Close the virtual setpoint multiplier switch to activate the alarm setpoint multipliers (not applicable to all XM modules)
Open the virtual setpoint multiplier switch to start the setpoint multiplier timers and eventually cancel alarm setpoint multiplication (not applicable to all XM modules)
Reset (05)
Other (33)
Other (32)
Speed Measurement Object (325)
Discrete Input Point Object (08)
Discrete Input Point Object (08)
1, 2 for XM-220 None None
1 None None
1 None None
Publication GMSI10-UM010C-EN-P - May 2010
70 DeviceNet Information
Select the Save
service code
Clear Send the attribute ID and then enter the Class (320
hex
) and
Instance (1)
Click Execute to initiate the action
Example
To save the configuration parameters to the non-volatile memory (EEPROM), fill in the Class Instance Editor as shown below.

Invalid Configuration Errors

A Start or Save service request to an XM module may return an Invalid Device Configuration error when there is a conflict amongst the configuration settings.
The general error code for the Invalid Device Configuration error is D0
hex
.
An additional error code is returned with the general error code to specify which configuration settings are invalid. The table below lists the additional error codes associated with the Invalid Device Configuration error.
Additional Error Codes returned with the Invalid Device Configuration Error (0xD0)
Error Code (Hex) Description
01 No specific error information is available. 02 Mismatched transducer, channel, and/or measurement unit. 03 Inverted transducer fault high/low values. 04 Alarm thresholds conflict with the alarm condition. 05 Alarm speed range is invalid. 06 Band minimum frequency is greater than maximum frequency. Or,
07 Relay is associated with an alarm that is not enabled. 08 Tachometer must be enabled for alarm or channel settings. 09 A senseless speed range is enabled on a speed alarm.
maximum frequency is greater than FMAX.
Publication GMSI10-UM010C-EN-P - May 2010
DeviceNet Information 71
Additional Error Codes returned with the Invalid Device Configuration Error (0xD0)
Error Code (Hex) Description
0A Too many alarms associated with a single measurement. 0B Invalid node address in the alarm list. 0C Too many alarms in the alarm list. Or, no alarms in the alarm list. 0D Alarm levels cannot be zero for alarms that are enabled. 0E Too many slaves in the scanner’s input data table. 0F The FMAX and Number of Lines do not yield correct vector calculations. 10 Phase (vector) alarms prohibited with synchronous sampling and more
than 1 tachometer pulse per revolution. 11 Can’t have order based band on asynchronous channel. 12 Unsupported Sensor Type and Channel ID combination. 13 Invalid Alarm Type for the associated measurement ID. 14 Synchronous sampling is required for alarm on synchronous
measurements. 15 Integration is not supported with the Bypass High Pass Filter option.

Eccentricity I/O Message Formats

The Eccentricity module supports Poll and Change of State (COS) I/O messages. The Poll response message is used by the XM module to produce measured values and the COS message is used to produce the Alarm and Relay
Status.

Poll Message Format

The Eccentricity module Poll request message contains no data. The Poll response message can contain up to 31 REAL values for a total of 124 bytes.
The Eccentricity module provides four pre-defined (static) data formats of the Poll response, as defined in Assembly instance 101–104. It also provides a dynamic Assembly instance, instance 199, with which you can define a custom data format for the Poll response. The dynamic Assembly instance can contain any of the measurement parameters included in Assembly instance 101, as well as several of the alarm and relay configuration parameters.
The default Assembly instance is 101 and the default size is 36 bytes. You can change the Assembly instance and define the custom Assembly instance using the configuration software. Refer to I/O Data Parameters on page 56 for details.
Publication GMSI10-UM010C-EN-P - May 2010
72 DeviceNet Information
The Poll response data can also be requested explicitly through Assembly Object (Class ID 0x4), Instance 101 (0x65), Data Attribute (3).
The following tables show the static data format of Assembly instances 101–
104.
Eccentricity Assembly Instance 101 Data Format
Byte Definition
0–3 Speed 4–7 Channel 1 Eccentricity value 8–11 Channel 2 Eccentricity value 12–15 Channel 1 Gap value 16–19 Channel 2 Gap value 20–23 Channel 1 Maximum Gap value 24–27 Channel 2 Maximum Gap value 28–31 Channel 1 Minimum Gap value 32–35 Channel 2 Minimum Gap value
Eccentricity Assembly Instance 102 Data Format
Byte Definition
0–3 Channel 1 Gap value 4–7 Channel 2 Gap value 8–11 Channel 1 Maximum Gap value 12–15 Channel 2 Maximum Gap value 16–19 Channel 1 Minimum Gap value 20–23 Channel 2 Minimum Gap value 24–27 Channel 1 Eccentricity value 28–31 Channel 2 Eccentricity value 32–35 Speed
Eccentricity Assembly Instance 103 Data Format
Byte Definition
0–3 Channel 1 Eccentricity value 4–7 Channel 2 Eccentricity value 8–11 Channel 1 Minimum Gap value 12–15 Channel 2 Minimum Gap value 16–19 Speed 20–23 Channel 1 Gap value
Publication GMSI10-UM010C-EN-P - May 2010
Eccentricity Assembly Instance 103 Data Format
Byte Definition
24–27 Channel 2 Gap value 28–31 Channel 1 Maximum Gap value 32–35 Channel 2 Maximum Gap value
Eccentricity Assembly Instance 104 Data Format
Byte Definition
0–3 Channel 1 Eccentricity value 4–7 Channel 1 Gap value 8–11 Channel 1 Minimum Gap value 12–15 Channel 1 Maximum Gap value 16–19 Speed 20–23 Channel 2 Eccentricity value 24–27 Channel 2 Gap value 28–31 Channel 2 Minimum Gap value 32–35 Channel 2 Maximum Gap value
DeviceNet Information 73

COS Message Format

The Eccentricity COS message contains five bytes of data as defined in the table below. The COS data can also be requested explicitly through Assembly Object (Class ID 0x4), Instance 100 (0x64), Data Attribute (3).
XM-120 COS Message Format
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Relay 1
Status
1 Relay 2
Status
2 Relay 3
Status
3 Relay 4
Status
4 Relay 5
Status
Reserved
Alarm 2 Status Alarm 1 Status
Reserved Reserved Reserved
Reserved Reserved Reserved
Reserved Reserved Reserved
Reserved Reserved Reserved
Publication GMSI10-UM010C-EN-P - May 2010
74 DeviceNet Information
IMPORTANT
XM Status Values
The following tables describe the XM Status values that are included in the COS messages.
Alarm Status Descriptions
Alarm Status Value Description
0Normal 1Alert 2 Danger 3Disarm 4 Transducer Fault (Sensor OOR) 5 Module Fault 6 Tachometer Fault 7 Reserved
Relay Status Descriptions

ADR for XM Modules

Relay Status Value Description
0 Not Activated 1 Activated
Automatic Device Replacement (ADR) is a feature of an Allen-Bradley DeviceNet scanner. It provides a means for replacing a failed device with a new unit, and having the device configuration data set automatically. Upon replacing a failed device with a new unit, the ADR scanner automatically downloads the configuration data and sets the node address.
It is recommended that ADR not be used in safety related applications. If the failure of the ADR server, and a subsequent power cycle, would result in the loss of protection for a machine, then ADR should not be implemented.
ADR can be used with XM modules but keep the following in mind when setting up the XM modules.
Publication GMSI10-UM010C-EN-P - May 2010
DeviceNet Information 75
TIP
The ADR scanner can not download the configuration data to an XM
module if the module has a saved configuration in its non-volatile memory. This happens because the saved configuration is restored and the module enters Run mode when the power is cycled. (Configuration parameters cannot be downloaded while an XM module is in Run mode.) XM modules must be in Program mode for the ADR configuration to be downloaded and this occurs only when there is no saved configuration.
To delete a saved configuration from non-volatile memory, use the Delete service in RSNetWorx for DeviceNet or perform the following steps in the XM Serial Configuration Utility.
1. Save the current configuration to a file. From the File menu, click Save As and enter a file name for
the configuration.
2. Reset the module to factory defaults. Click the Module tab and click the Reset button.
3. Reload the saved configuration. From the File menu, click Open and select the configuration file.
4. Make certain to disable auto save. From the Device
menu, clear the Auto Save Configuration check mark.
An XM module will enter Run mode automatically after the ADR
scanner restores the module’s configuration only if the module is in Run mode at the time the configuration is saved to the scanner. If the module is in Program mode when the configuration is saved, then the module will remain in Program mode after the configuration is downloaded by the ADR scanner.
The ADR scanner saves and restores only the configuration parameters
contained in the module’s EDS file. Some XM parameters are not included in the EDS file because they are not supported by either the EDS specification or the tools that read the EDS files, for example RSNetWorx for DeviceNet. These configuration parameters will not be restored with ADR.
Below is a list of the configuration parameters that are not included in the EDS file and can not be saved or restored with ADR.
Channel Name
Tachometer Name
Alarm Name
Relay Name
All Triggered Trend related parameters
Publication GMSI10-UM010C-EN-P - May 2010
76 DeviceNet Information
All SU/CD Trend related parameters
Custom Assembly structure (see page 56)
The ADR and trigger group functions cannot be used together. A
module can have only one primary master so a module cannot be both configured for ADR and included in a trigger group. The ADR scanner must be the primary master for the modules configured for ADR. The XM-440 Master Relay module must be the primary master for modules included in a trigger group.
Publication GMSI10-UM010C-EN-P - May 2010
Appendix
TIP
C

DeviceNet Objects

Appendix C provides information on the DeviceNet objects supported by the Eccentricity module.
For information about See page
Identity Object (Class ID 01H) 78 DeviceNet Object (Class ID 03H) 80 Assembly Object (Class ID 04H) 81 Connection Object (Class ID 05H) 86 Analog Input Point Object (Class ID 0AH) 88 Parameter Object (Class ID 0FH) 90 Acknowledge Handler Object (Class ID 2BH) 93 Alarm Object (Class ID 31DH) 94 Device Mode Object (Class ID 320H) 96 Relay Object (Class ID 323H) 97 Spectrum Waveform Measurement Object (Class ID 324H) 99 Speed Measurement Object (Class ID 325H) 102 Tachometer Channel Object (Class ID 326H) 103 Transducer Object (Class ID 328H) 105 4-20 mA Output Object (Class ID 32AH) 106
Refer to the DeviceNet specification for more information about DeviceNet objects. Information about the DeviceNet specification is available on the ODVA web site (http://www.odva.org).
77 Publication GMSI10-UM010C-EN-P - May 2010
78 DeviceNet Objects
Identity Object (Class ID 01
)
H
The Identity Object provides identification and general information about the device.

Class Attributes

The Identity Object provides no class attributes.

Instance Attributes

Table C.1 Identity Object Instance Attributes
Access
Attr ID
1 Get Vendor ID UINT 668 = Entek 2 Get Device Type UINT 109 (Specialty I/O) 3 Get Product Code UINT 33 (0x21) 4 Get Revision:
5 Get Status WORD
Rule Name Data Type Default Value
STRUCT OF Major Minor
USINT
USINT
Value varies with each firmware revision. Value varies with each firmware revision.
6 Get Serial Number UDINT 7 Get Product Name SHORT_
STRING

Status

The Status is a 16 bit value. The following bits are implemented.
Table C.2 Identity Object Status
Bit Name Description
0 Owned TRUE indicates that the module has an owner. More
specifically, the Predefined Master/Slave Connection Set
has been allocated to a master. 1 Reserved, set to 0 2 Configured This bit is set whenever a saved configuration is
successfully loaded from non-volatile memory. This bit is
cleared whenever the default configuration is restored or
loaded. 3 Reserved, set to 0
"XM-120 Eccentricity Module"
Publication GMSI10-UM010C-EN-P - May 2010
DeviceNet Objects 79
Table C.2 Identity Object Status
Bit Name Description
4 Boot Program Vendor-specific, indicates that the boot program is
running. The Main Application must be corrupt or
missing. 5 - 7 Vendor-specific, not implemented 8 Minor Recoverable
Set whenever there is a transducer or tachometer fault.
Fault
9 Minor Unrecoverable
Not implemented
Fault
10 Major Recoverable
Fault
Set when the module detects a major problem that the
user may be able to recover from. The Module Status
LED will flash red. An example of this condition is when
the boot program is running. 11 Major Unrecoverable
Fault
Set when there is a module status fault (Module Status
LED is solid red). 12 - 15 Reserved, set to 0

Services

Table C.3 Identity Object Services
Service Code Class/Instance Usage Name
01 05 0E 10
h
h
h
h
Instance Get_Attributes_All Instance Reset Instance Get_Attribute_Single Instance
Set_Attribute_Single
1
1 Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
Publication GMSI10-UM010C-EN-P - May 2010
80 DeviceNet Objects
DeviceNet Object (Class ID 03
)
H
Table C.4 DeviceNet Object Class Attributes
Attr ID
1 Get Revision UINT 2
Table C.5 DeviceNet Object Instance Attributes
Attr ID
1 Get/Set
2 Get/Set
3 Get Bus-Off Interrupt BOOL 0 4 Get/Set Bus-Off Counter USINT 0
The DeviceNet Object is used to provide the configuration and status of a physical attachment to DeviceNet.

Class Attributes

Access Rule Name Data Type Default Value

Instance Attributes

Access Rule Name Data Type Default Value
1
MAC ID
Baud Rate
2
USINT 63
USINT 0
5 Get Allocation Information STRUCT of
BYTE USINT
100 Get/Set Autobaud Disable BOOL 0 (Ignore attribute 2 and always autobaud)
1 Setting the MAC ID causes the device to reset automatically, after which it will go online with the new MAC
ID.
2 The Baud Rate setting can not be set while Autobaud Disable is equal to 0. Applying the Baud Rate does not
occur until the Reset service to the Identity Object.
0 255
The MAC ID, Baud Rate, and Autobaud Disable settings are stored in non-volatile memory so they do not reset to the default with each power cycle. The Baud Rate attribute supports the following settings:
0 = 125 kbps
1 = 250 kbps
2 = 500 kbps
The Baud Rate setting is used only when automatic baud rate detection is disabled (Autobaud Disable = 1). When Autobaud Disable is set to zero (0), the module ignores its Baud Rate setting and performs automatic baud
Publication GMSI10-UM010C-EN-P - May 2010
DeviceNet Objects 81
rate detection instead. This means that the module will determine the network baud rate by listening for network traffic before attempting to go online.
Services
Table C.6 DeviceNet Object Services
Service Code Class/Instance Usage Name
0E 10
h
h
Class/Instance Get_Attribute_Single Instance
Set_Attribute_Single
1

Assembly Object (Class ID 04H)

Table C.7 Assembly Object Class Attributes
Attr ID
1 Get Revision UINT Revision of the
4B
h
4C
h
1 Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
Instance Allocate_Master/Slave_Connetion_Set Instance Release_Group_2_Identifier_Set
The Assembly Object binds attributes of multiple objects to allow data to or from each object to be sent or received in a single message.
The Eccentricity module provides both static and dynamic assemblies.

Class Attribute

Access Rule Name Data Type Description Semantics
2
implemented object.

Instances

Table C.8 Assembly Object Instances
Instance Name Type Description
100 Default COS Message Input Alarm and Relay Status values
Publication GMSI10-UM010C-EN-P - May 2010
82 DeviceNet Objects
Table C.8 Assembly Object Instances
Instance Name Type Description
101 Default Poll Response
Message
102 - 106 Alternate Poll Response
Message
Input Measurement values
Input Measurement values
199 Alternate Dynamic Poll
Response Message
Input User configurable
measurement values and configuration parameters

Instance Attributes

Table C.9 Assembly Object Instance Attributes
Access
Attr ID
1 Get Number of Members in list UINT Only supported for Dynamic Assembly
2 Set Member List Array of STRUCT: Only supported for Dynamic Assembly
3 Get Data Defined in tables
Rule Name Data Type Value
instance
instance Member Data Description UINT Size of member data value in bits Member Path Size UINT Member Path Packed EPATH
on the following pages.
Table C.10 Instance 100 Data Format (Alarm and Relay Status Values Assembly)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Relay 1
Status
1 Relay 2
Status
Publication GMSI10-UM010C-EN-P - May 2010
0 Alarm 2 Status Alarm 1 Status
00 0

Assembly Instance Attribute Data Format

Instance 100 - Eccentricity Module Alarms
This assembly is sent using COS messaging when any of the Alarm or Relay Status values change.
DeviceNet Objects 83
Table C.10 Instance 100 Data Format (Alarm and Relay Status Values Assembly)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
2 Relay 3
Status
3 Relay 4
Status
00 0
00 0
4 Relay 5
Status
00 0
Instance 101 - Eccentricity Module Measurements
This is the default assembly that is sent within the I/O Poll Response message when an I/O Poll Request is received from a DeviceNet master.
Table C.11 Instance 101 Data Format (Measurement Values Assembly)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 - 3 Speed 4 - 7 Channel 1 Eccentricity value 8 - 11 Channel 2 Eccentricity value 12 - 15 Channel 1 Gap value 16 - 19 Channel 2 Gap value 20 - 23 Channel 1 Max Gap value 24 - 27 Channel 2 Max Gap value 28 - 31 Channel 1 Min Gap value 32 - 35 Channel 2 Min Gap value
Instance 102 - Eccentricity Module Measurements
This is an alternate assembly for the I/O Poll Response message.
Table C.12 Instance 102 Data Format (Measurement Values Assembly)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 - 3 Channel 1 Gap value 4 - 7 Channel 2 Gap value 8 - 11 Channel 1 Max Gap value 12 - 15 Channel 2 Max Gap value 16 - 19 Channel 1 Min Gap value 20 - 23 Channel 2 Min Gap value 24 - 27 Channel 1 Eccentricity value 28 - 31 Channel 2 Eccentricity value 32 - 35 Speed
Publication GMSI10-UM010C-EN-P - May 2010
84 DeviceNet Objects
Table C.13 Instance 103 Data Format (Measurement Values Assembly)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 - 3 Channel 1 Eccentricity value 4 - 7 Channel 2 Eccentricity value 8 - 11 Channel 1 Min Gap value 12 - 15 Channel 2 Min Gap value 16 - 19 Speed 20 - 23 Channel 1 Gap value 24 - 27 Channel 2 Gap value 28 - 31 Channel 1 Max Gap value 32 - 35 Channel 2 Max Gap value
Instance 103 - Eccentricity Module Measurements
This is an alternate assembly for the I/O Poll Response message.
Instance 104 - Eccentricity Module Measurements
This is an alternate assembly for the I/O Poll Response message.
Table C.14 Instance 103 Data Format (Measurement Values Assembly)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 - 3 Channel 1 Eccentricity value 4 - 7 Channel 1 Gap value 8 - 11 Channel 1 Min Gap value 12 - 15 Channel 1 Max Gap value 16 - 19 Speed 20 - 23 Channel 2 Eccentricity value 24 - 27 Channel 2 Gap value 28 - 31 Channel 2 Min Gap value 32 - 35 Channel 2 Max Gap value
Instance 199 - Dynamic Assembly
This Assembly instance can be created and configured with the XM Serial Configuration Utility or RSMACC Enterprise Online Configuration Utility. Using the configuration software, you determine the format of the data. This assembly instance can be selected to be sent in response to an I/O Poll request from a Master.
Publication GMSI10-UM010C-EN-P - May 2010
The dynamic Assembly can include all of the measurement values included in Assembly instance 101. In addition, the dynamic Assembly can include the following configuration parameters.
Table C.15 Instance 199 Component Mapping
DeviceNet Objects 85
EPATH (where ii = instance number)
Class Name
Class Number
21 1D 03 24 ii 30 04 Alarm 31D 21 1D 03 24 ii 30 07 Alarm 31D 21 1D 03 24 ii 30 08 Alarm 31D 21 1D 03 24 ii 30 09 Alarm 31D
21 1D 03 24 ii 30 0A Alarm 31D 21 1D 03 24 ii 30 0B Alarm 31D 21 1D 03 24 ii 30 0C Alarm 31D 21 1D 03 24 ii 30 0F Alarm 31D 21 1D 03 24 ii 30 10 Alarm 31D 21 1D 03 24 ii 30 11 Alarm 31D 21 23 03 24 ii 30 04 Relay 323 21 23 03 24 ii 30 05 Relay 323 21 23 03 24 ii 30 06 Relay 323 21 23 03 24 ii 30 07 Relay 323 21 23 03 24 ii 30 09 Relay 323 21 0F 00 24 ii 30 01 Param 0F
21 0F 00 24 ii 30 01 Param 0F
21 23 03 24 ii 30 0C Relay 323 21 23 03 24 ii 30 0E Relay 323
Instance Number
h
h
h
h
1 - 2 Alarm Enable 4 BOOL 1 - 2 Condition 7 USINT 1 - 2 Alert Threshold (High) 8 REAL 1 - 2 Danger Threshold
Attribute Name
Attribute Number
9REAL
(High)
h
h
1 - 2 Hysteresis 12 REAL
h
h
h
h
h
h
1 - 5 Failsafe Enable 6 BOOL
h
h
h
h
1 - 2 Alert Threshold Low 10 REAL 1 - 2 Danger Threshold Low 11 REAL
1 - 2 Speed Range Enable 15 BOOL 1 - 2 Speed Range High 16 REAL 1 - 2 Speed Range Low 17 REAL 1 - 5 Relay Enable 4 BOOL 1 - 5 Latch Enable 5 BOOL
1 - 5 Delay 7 UINT 1 - 5 Alarm Level 9 BYTE 7 - 11 Parameter Value
1USINT
(Alarm Identifier A)
h
12 - 16 Parameter Value
1USINT
(Alarm Identifier B)
h
h
1 - 5 Logic 12 USINT 1 - 5 Relay Installed 14 BOOL
Data Ty pe
The dynamic Assembly instance must be instantiated with a call to the class level Create service. Then the structure can be defined with the Set_Attribute_Single service for the Member List attribute. Only one dynamic Attribute instance is supported so subsequent calls to the Create service will return a Resource Unavailable (0x02) error. The Delete service can be used to destroy the dynamic Assembly instance so that it can be re-created.
Publication GMSI10-UM010C-EN-P - May 2010
86 DeviceNet Objects

Services

Table C.16 Assembly Object Services
Service Code Class/Instance Usage Name
0E 10 08 09
h
h
h
h
Class/Instance Get_Attribute_Single Instance Set_Attribute_Single Class Create Instance Delete
Connection Object (Class ID 05
)
H
The Connection Object allocates and manages the internal resources associated with both I/O and Explicit Messaging Connections.

Class Attributes

The Connection Object provides no class attributes.

Instances

Table C.17 Connection Object Instances
Instance Description
1 Explicit Message Connection for pre-defined connection set 2 I/O Poll Connection 4 I/O COS (change of state) Connection 11 - 17 Explicit Message Connection
Table C.18 Connection Object Instance Attributes
Access
Attr ID
1 Get State USINT State of the object. 2 Get Instance Type USINT Indicates either I/O or Messaging
3 Get Transport Class Trigger BYTE Defines behavior of the Connection.
Publication GMSI10-UM010C-EN-P - May 2010
Rule Name Data Type Description

Instance Attributes

Connection.
DeviceNet Objects 87
Table C.18 Connection Object Instance Attributes
Access
Attr ID
Rule Name Data Type Description
4 Get Produced Connection ID UINT Placed in CAN Identifier Field when the
Connection transmits.
5 Get Consumed Connection IDUINT CAN Identifier Field value that denotes
message to be received.
6 Get Initial Comm
Characteristics
BYTE Defines the Message Group(s) across
which productions and consumptions
associated with this Connection occur.
7 Get Produced Connection
Size
UINT Maximum number of bytes transmitted
across this Connection.
8 Get Consumed Connection
Size
UINT Maximum number of bytes received across
this Connection.
9 Get/Set Expected Packet Rate UINT Defines timing associated with this
Connection.
12 Get/Set Watchdog Time-out
Action
13 Get Produced Connection
Path Length
14 Get Produced Connection
Path
USINT Defines how to handle Inactivity/Watchdog
timeouts.
UINT Number of bytes in the
production_connection_path attribute.
Array of USINT
Specifies the Application Object(s) whose
data is to be produced by this Connection
Object. See DeviceNet Specification
Volume 1 Appendix I.
15 Get Consumed Connection
Path Length
16 Get Consumed Connection
Path
UINT Number of bytes in the
consumed_connection_path attribute.
Array of USINT
Specifies the Application Object(s) that are
to receive the data consumed by this
Connection Object. See DeviceNet
Specification Volume 1 Appendix I.
17 Get Production Inhibit Time UINT Defines minimum time between new data
production.
Publication GMSI10-UM010C-EN-P - May 2010
88 DeviceNet Objects

Services

Table C.19 Connection Object Services
Service Code Class/Instance Usage Name
05 0E 10
h
h
h
Instance Reset Instance Get_Attribute_Single Instance Set_Attribute_Single
Analog Input Point Object (Class ID 0A
)
H
Table C.20 Analog Input Point Object Class Attributes
Access
Attr ID
1 Get Revision UINT Revision of the
Rule Name Data Type Description Semantics
The Analog Input Point Object is used to model the Eccentricity measurements made by the Eccentricity module.

Class Attributes

2
implemented object.

Instances

Table C.21 Analog Input Point Object Instances
Instance Name Description
1 Eccentricity 1 Eccentricity measurement for Channel 1 2 Eccentricity 2 Eccentricity measurement for Channel 2 3 Min Gap 1 Min Gap for Channel 1
Publication GMSI10-UM010C-EN-P - May 2010
4 Min Gap 2 Min Gap for Channel 2 5 Max Gap 1 Max Gap for Channel 1 6 Max Gap 2 Max Gap for Channel 2
DeviceNet Objects 89

Instance Attributes

Table C.22 Analog Input Point Object Class Attributes
Access
Attr ID
3 Get Value REAL Measurement value The measured vale in units
4 Get Status BOOL Indicates if a fault or
8 Get Value Data Type USINT Determines the data type
147 Get Data Units ENGUNIT The units context of the
Rule Name Data Type Description Semantics
specified by the Data Units attribute.
0 = Operating without alarms or
alarm has occurred.
faults 1 = Alarm or fault condition exists. The Value attribute may not represent the actual field value.
1 = REAL
of the Value.
See DeviceNet Specification
Value attribute.
Volume 1 Appendix K.
Valid values for eccentricity: mils = 0800 hex µm = 2204 hex
Fixed for Min/Max Gap Volt = 2D00 hex

Services

Table C.23 Analog Input Point Object Services
Service Code Class/Instance Usage Name Description
0E
10
h
h
Class/Instance Get_Attribute_Single Returns the contents of the
specified attribute.
Instance Set_Attribute_Single Sets the contents of the
specified attribute.
1 Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
1
Publication GMSI10-UM010C-EN-P - May 2010
90 DeviceNet Objects
Parameter Object (Class ID 0F
)
H
Table C.24 Parameter Object Class Attributes
Attr ID
2 Get Max Instance UINT Maximum instance
8 Get Parameter Class
9 Get Config.
The Parameter Object provides the interface to the Eccentricity configuration data. There are 18 Parameter Object instances implemented in the Eccentricity module.
Instances 1-4 and 7-16 are implemented to provide an alternate method of setting the configuration parameters with ENGUNIT or EPATH data type. And Parameter Object instances 17 and 18 provide an alternate method for setting the Produced Connection Size and Produced Connection Path attributes for the Poll Connection because these attributes can be difficult to get/set directly through the Connection Object.
Parameter Object instances 5 and 6 are for setting the update rate of the eccentricity measurements. The eccentricity update rate is used in place of the
tachometer when no tachometer is available.
Access Rule Name Data Type Description Semantics
Total number of parameter
Descriptor
Assembly Instance
number of an object in this class.
WORD Bits that describe the
parameter.
UINT Set to 0
object instances.
Bit 0 Supports Parameter Instances Bit 1 Supports Full Attrib. Bit 2 Must do non-volatile store Bit 3 Params in non-volatile

Instances

There are 18 instances of this object.
Table C.25 Parameter Object Instances
Read
Instance
1 No Transducer 1 Sensitivity Units USINT 0 = mils
2 No Transducer 2 Sensitivity Units USINT 0 = mils
3 No Eccentricity Measurement 1
4 No Eccentricity Measurement 2
Publication GMSI10-UM010C-EN-P - May 2010
Only Name Data Type Valid Values Default Value
USINT 0 = mils
Units
USINT 0 = mils
Units
0
1 = µm
0
1 = µm
0
1 = µm
0
1 = µm
DeviceNet Objects 91
Table C.25 Parameter Object Instances
Read
Instance
Only Name Data Type Valid Values Default Value
5 No Eccentricity 1 Update Rate USINT 1-255 seconds 60 6 No Eccentricity 2 Update Rate USINT 1-255 seconds 60 7 No Relay 1 Alarm Identifier A USINT 0 = Alarm 1
0
1 = Alarm 2
8 No Relay 2 Alarm Identifier A USINT 0 = Alarm 1
0
1 = Alarm 2
9 No Relay 3 Alarm Identifier A USINT 0 = Alarm 1
1 = Alarm 2
10 No Relay 4 Alarm Identifier A USINT 0 = Alarm 1
1 = Alarm 2
11 No Relay 5 Alarm Identifier A USINT 0 = Alarm 1
1 = Alarm 2
12 No Relay 1 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
13 No Relay 2 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
14 No Relay 3 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
15 No Relay 4 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
16 No Relay 5 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
17 No Poll Connection Produced
Connection Path
1
18 No Poll Connection Produced
Connection Size
1
USINT 101-104 (Assembly Object
instance number)
UINT 4 - 124 36
0
0
0
0
0
0
0
0
101
1 The Poll Connection Produced Connection Path and Size parameters cannot be set while the Poll connection is
already established with a master/scanner. Attempting to do so will result in an “Object State Conflict” error (error code 0xC). These Parameter instances are a little more flexible than the actual Connection Object attributes because they can be set while the connection is in the NON=EXISTENT state (before the master/ scanner allocated the connection).
Publication GMSI10-UM010C-EN-P - May 2010
92 DeviceNet Objects
Table C.26 Parameter Object Instance Attributes
Attr ID
1 Set Parameter
2 Get Link Path Size USINT Size of Link Path 0 (These Parameter instances do
3
4 Get Descriptor WORD Description of Parameter Bit 0 = Settable Path support
5 Get Data Type EPATH Data Type Code See DeviceNet Specification
6 Get Data Size USINT Number of Bytes in

Instance Attributes

Access Rule Name Data Type Description Semantics
Actual value of parameter See Table C.25 for a list of valid
Get
Value
Link Path ARRAY of
DeviceNet path
Segment Type/
BYTE See DeviceNet
Port
Segment Address
DeviceNet path to the object for the Parameter value.
Specification Volume 1 Appendix I for format.
See DeviceNet Specification Volume 1 Appendix I for format.
Parameter value.
values for each instance.
not link directly to another object attribute.)
Bit 1 = Enum Strings support Bit 2 = Scaling support Bit 3 = Scaling Links support Bit 4 = Read Only Bit 5 = Monitor Bit 6 = Ext. Prec. scaling
Volume 1 Appendix J, Section J-6.
Table C.27 Parameter Object Services
Service Code Class/Instance Usage Name Description
0E
h
10
h
Publication GMSI10-UM010C-EN-P - May 2010

Services

Class/Instance Get_Attribute_Single Returns the contents of the
specified attribute.
Class Set_Attribute_Single Sets the contents of the
specified attribute.
1 Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
1
Loading...