Rockwell Automation 1440-VST02-01RA User Manual

XM-120 Eccentricity Module
User Guide
Firmware Revision 5
1440-VST02-01RA
Important User Information
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
) describes some important differences between solid state equipment and hard-
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Allen-Bradley, Rockwell Automation, and XM are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Safety Approvals
WARNING
AVERTISSEMENT
IMPORTANT
The following information applies when operating this equipment in hazardous locations.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system arfe subject to investigation by the local Authority Having Jurisdiction at the time of installation.
EXPLOSION HAZARD -
•Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
•Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
•Substitution of components may impair suitability for Class I, Division 2.
•If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
RISQUE D’EXPLOSION –
•Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
•Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
•La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
•S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Wiring to or from this device, which enters or leaves the system enclosure, must utilize wiring methods suitable for Class I, Division 2 Hazardous Locations, as appropriate for the installation in accordance with the product drawings as indicated in the following table.
Model Catalog Number Haz Location Drawings* Model Catalog Number Haz Location Drawings*
w/o Barriers
XM-120 1440-VST0201RA XM-121 1440-VLF0201RA XM-360 1440-TPR0600RE XM-122 1440-VSE0201RA XM-361 1440-TUN0600RE XM-123 1440-VAD0201RA XM-361 1440-TTC0600RE XM-160 1440-VDRS0600RH XM-161 1440-VDRS0606RH XM-441 1440-REX0004RD 48241-HAZ N/A XM-162 1440-VDRP0600RH XM-442 1440-REX0304RG 48642-HAZ N/A XM-220 1440-SPD0201RB 48640-HAZ 48641-HAZ
48178-HAZ 48179-HAZ
51263-HAZ 51264-HAZ
* Drawings are available on the included CD
w/ Barriers
w/o Barriers
XM-320 1440-TPS0201RB 48238-HAZ 48239-HAZ
48295-HAZ 48299-HAZ
XM-440 1440-RMA0004RC 48240-HAZ N/A
w/ Barriers
Introduction
Installing the XM-120 Eccentricity Module

Table of Contents

Chapter 1
Introducing the Eccentricity Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Eccentricity Module Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Using this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Organization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Document Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Chapter 2
XM Installation Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Grounding Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Mounting the Terminal Base Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
DIN Rail Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Interconnecting Terminal Base Units . . . . . . . . . . . . . . . . . . . . . . . 15
Panel/Wall Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Connecting Wiring for Your Module . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Terminal Block Assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Connecting the Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Connecting the Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Connecting the Tachometer Signal. . . . . . . . . . . . . . . . . . . . . . . . . 25
Connecting the Buffered Outputs . . . . . . . . . . . . . . . . . . . . . . . . . 27
Connecting a Non-Contact Sensor . . . . . . . . . . . . . . . . . . . . . . . . . 29
Connecting the Remote Relay Reset Signal . . . . . . . . . . . . . . . . . . 30
Connecting the 4-20 mA Outputs . . . . . . . . . . . . . . . . . . . . . . . . . 32
Serial Port Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
DeviceNet Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Mounting the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Module Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Basic Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Powering Up the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Manually Resetting Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Installing the XM-120 Eccentricity Firmware. . . . . . . . . . . . . . . . . . . . 40
Chapter 3
Configuration Parameters
v Publication GMSI10-UM010C-EN-P - May 2010
Channel Transducer Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Measurement Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Eccentricity Measurement Parameters . . . . . . . . . . . . . . . . . . . . . . 45
Waveform Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Speed Measurement Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Tachometer Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Tachometer Transducer Parameters . . . . . . . . . . . . . . . . . . . . . . . . 47
Tachometer Signal Processing Parameters . . . . . . . . . . . . . . . . . . . 48
Alarm Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Relay Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4-20 mA Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Table of Contents vi
Specifications
DeviceNet Information
I/O Data Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Data Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Monitor Data Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Alarm and Relay Status Parameters . . . . . . . . . . . . . . . . . . . . . . . . 59
Device Mode Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Appendix A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Appendix B
Electronic Data Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Changing Operation Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Transition to Program Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Transition to Run Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
XM Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Invalid Configuration Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Eccentricity I/O Message Formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Poll Message Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
COS Message Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
ADR for XM Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
DeviceNet Objects
Appendix C
Identity Object (Class ID 01H) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
DeviceNet Object (Class ID 03H) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Assembly Object (Class ID 04H) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Class Attribute . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Assembly Instance Attribute Data Format. . . . . . . . . . . . . . . . . . . 82
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Connection Object (Class ID 05H). . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Publication GMSI10-UM010C-EN-P - May 2010
Table of Contents vii
Analog Input Point Object (Class ID 0AH). . . . . . . . . . . . . . . . . . . . . 88
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Parameter Object (Class ID 0FH). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Acknowledge Handler Object (Class ID 2BH) . . . . . . . . . . . . . . . . . . 93
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Alarm Object (Class ID 31DH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Instance Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Device Mode Object (Class ID 320H) . . . . . . . . . . . . . . . . . . . . . . . . . 96
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Relay Object (Class ID 323H) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Spectrum Waveform Measurement Object (Class ID 324H) . . . . . . . 99
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Get_Waveform_Chunk . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Speed Measurement Object (Class ID 325H). . . . . . . . . . . . . . . . . . . 102
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Tachometer Channel Object (Class ID 326H) . . . . . . . . . . . . . . . . . . 103
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Instance Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Transducer Object (Class ID 328H) . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Publication GMSI10-UM010C-EN-P - May 2010
Table of Contents viii
Wiring Connections for Previous Module Revisions
4-20 mA Output Object (Class ID 32AH) . . . . . . . . . . . . . . . . . . . . . 106
Class Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Instances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Instance Attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Appendix D
Terminal Block Assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Connecting the Transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Glossary
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Publication GMSI10-UM010C-EN-P - May 2010
Chapter
IMPORTANT
1

Introduction

This chapter provides an overview of the XM-120 Eccentricity module. It also discusses the components of the module.
For information about See page
Introducing the Eccentricity Module 1 Eccentricity Module Components 2 Using this Manual 3
This manual only describes how to install and use the XM-120 Eccentricity module. For information about the dynamic measurement and low frequency dynamic measurement modules, refer to the XM-120/121 Dynamic Measurement Module User Guide.

Introducing the Eccentricity Module

The XM-120 Eccentricity module is a 2-channel eccentricity monitor. It is a
member of the Allen-Bradley™ XM condition monitoring and protection modules that operate both in stand-alone applications or integrate with Programmable Logic Controllers (PLCs) and control system networks.
Eccentricity is the measure of the amount of bow in a rotor. The lower the eccentricity value the more straight the shaft. Rotor bow can be a fixed mechanical bow, or it can be a temporary bow caused by uneven thermal heating or simply by the weight of the rotor (gravity bow).
The Eccentricity module is suitable for virtually all types of rotating and reciprocating machinery where rotor bow must be measured prior to or during startup. It accepts input from non-contact eddy current probe systems to provide peak-to-peak eccentricity, maximum instantaneous DC voltage (max gap), minimum instantaneous DC voltage (min gap), and instantaneous DC voltage (gap) measurements. In addition to the transducer inputs, the module can accept one tachometer input to provide speed measurement, which can, if desired, be used to disable eccentricity alarms after startup.
®
Series, a family of DIN rail mounted
1 Publication GMSI10-UM010C-EN-P - May 2010
2 Introduction
XM-940 Dynamic Measurement Module Terminal Base Unit
Cat. No. 1440-TB-A
XM-120 Dynamic Measurement Module
Cat. No. 1440-VST02-01RA
IMPORTANT
The Eccentricity module includes a single on-board relay, expandable to five, making it a complete monitoring system. It can operate stand-alone, or it can be deployed on a standard or dedicated DeviceNet network where it can provide real-time data and status information to other XM modules, PLCs, distributed control systems (DCS), and Condition Monitoring Systems.
The Eccentricity module can be configured remotely via the DeviceNet network, or locally using a serial connection to a PC or laptop. Refer to Chapter 3 for a list of the configuration parameters.

Eccentricity Module Components

The Eccentricity module consists of a terminal base unit and an instrument module. The XM-120 Dynamic Measurement Module and the XM-940 Terminal Base are shown below.
Figure 1.1 Eccentricity Module Components
XM-940 Dynamic Measurement Module Terminal Base - A DIN rail
mounted base unit that provides terminations for all field wiring required by XM Dynamic Measurement and Eccentricity modules.
Publication GMSI10-UM010C-EN-P - May 2010
XM-120 Dynamic Measurement Module - The XM-120 mounts on the
XM-940 terminal base via a keyswitch and a 96-pin connector. The XM-120 contains the measurement electronics, processors, relay, and serial interface port for local configuration.
The XM-441 Expansion Relay module may be connected to the XM-120 module via the XM-940 terminal base.
When connected to the module, the Expansion Relay module simply “expands” the capability of the XM-120 by adding four additional epoxy-sealed relays. The module controls the Expansion Relay module by extending to it the same logic and functional controls as the on-board relay.
Introduction 3

Using this Manual

This manual introduces you to the XM-120 Eccentricity module. It is intended for anyone who installs, configures, or uses the XM-120 Eccentricity module.

Organization

To help you navigate through this manual, it is organized in chapters based on these tasks and topics.
Chapter 1 "Introduction" contains an overview of this manual and the XM-120 Eccentricity module.
Chapter 2 "Installing the XM-120 Eccentricity Module" describes how to install, wire, and use the Eccentricity module. It also provides instructions on how to install the Eccentricity firmware.
Chapter 3 "Configuration Parameters" provides a complete listing and description of the Eccentricity parameters. The parameters can be viewed and edited using the XM Serial Configuration Utility software and a personal computer.
Appendix A "Specifications" lists the technical specifications for the Eccentricity module.
Appendix B "DeviceNet Information" provides information to help you configure the module over a DeviceNet network.
Appendix C "DeviceNet Objects" provides information on the DeviceNet objects supported by the XM-120 Eccentricity module.
Appendix D "Wiring Connections for Previous Module Revisions" provides terminal block assignments and wiring diagrams of earlier revisions of the XM-120 module (before revision D01).
For definitions of terms used in this Guide, see the Glossary at the end of the Guide.

Document Conventions

There are several document conventions used in this manual, including the following:
Publication GMSI10-UM010C-EN-P - May 2010
4 Introduction
TIP
EXAMPLE
The XM-120 Eccentricity module is referred to as XM-120, Eccentricity module, device, or module throughout this manual.
A tip indicates additional information which may be helpful.
This convention presents an example.
Publication GMSI10-UM010C-EN-P - May 2010
Chapter
ATTENTION
2

Installing the XM-120 Eccentricity Module

This chapter discusses how to install and wire the XM-120 Eccentricity module. It also describes the module indicators and the basic operations of the modules.
For information about See page
XM Installation Requirements 6 Mounting the Terminal Base Unit 13 Connecting Wiring for Your Module 17 Mounting the Module 35 Module Indicators 37 Basic Operations 39 Installing the XM-120 Eccentricity Firmware 40
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 Industrial environment, in overvoltage Category II applications (as defined in IED publication 60664–1), at altitudes up to 2000 meters without derating.
This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present, and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosures.
5 Publication GMSI10-UM010C-EN-P - May 2010
6 Installing the XM-120 Eccentricity Module
ATTENTION
ATTENTION

XM Installation Requirements

This section describes wire, power, and grounding requirements for an XM system.

Wiring Requirements

Use solid or stranded wire. All wiring should meet the following specifications:
14 to 22 AWG copper conductors without pretreatment; 8 AWG
required for grounding the DIN rail for electromagnetic interference (emi) purposes
Recommended strip length 8 millimeters (0.31 inches)
Minimum insulation rating of 300 V
Soldering the conductor is forbidden
Wire ferrules can be used with stranded conductors; copper ferrules
recommended
See the XM Documentation and Configuration Utility CD for Hazardous Locations installation drawings. The XM Documentation and Configuration Utility CD is packaged with the XM modules.

Power Requirements

Before installing your module, calculate the power requirements of all modules interconnected via their side connectors. The total current draw through the side connector cannot exceed 3A. Refer to the specifications for the specific modules for power requirements.
A separate power connection is necessary if the total current draw of the interconnecting modules is greater than 3 A.
Figure 2.1 is an illustration of wiring modules using separate power connections.
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 7
Any limited power source that satisfies the requirements specified below
Figure 2.1 XM Modules with Separate Power Connections
Power Supply Requirements
XM Power Supply Requirements
Listed Class 2 rated supply, or
Protection
Fused* ITE Listed SELV supply, or
Fused* ITE Listed PELV supply Output Voltage 24 Vdc ± 10% Output Power 100 Watts Maximum (~4A @ 24 Vdc) Static Regulation ± 2% Dynamic Regulation ± 3% Ripple < 100mVpp Output Noise Per EN50081-1 Overshoot < 3% at turn-on, < 2% at turn-off Hold-up Time As required (typically 50mS at full rated load) * When a fused supply is used the fuse must be a 5 amp, listed, fast acting fuse such as
provided by Allen-Bradley part number 1440-5AFUSEKIT
Publication GMSI10-UM010C-EN-P - May 2010
8 Installing the XM-120 Eccentricity Module
IMPORTANT
See Application Technique "XM Power Supply Solutions", publication ICM-AP005A-EN-E, for guidance in architecting power supplies for XM systems.

Grounding Requirements

Use these grounding requirements to ensure safe electrical operating circumstances, and to help avoid potential emi and ground noise that can cause unfavorable operating conditions for your XM system.
DIN Rail Grounding
The XM modules make a chassis ground connection through the DIN rail. The DIN rail must be connected to a ground bus or grounding electrode conductor using 8 AWG or 1 inch copper braid. See Figure 2.2.
Use zinc-plated, yellow-chromated steel DIN rail (Allen-Bradley part no. 199-DR1 or 199-DR4) or equivalent to assure proper grounding. Using other DIN rail materials (e.g. aluminum, plastic, etc.), which can corrode, oxidize, or are poor conductors can result in improper or intermittent platform grounding.
Publication GMSI10-UM010C-EN-P - May 2010
Figure 2.2 XM System DIN Rail Grounding
Power Supply
DYNAMIC MEASUREMENT
1440-VST02-01RA
DYNAMIC MEASUREMENT
1440-VST02-01RA
POSITION
1440-TSP02-01RB
MASTER RELAY
1440-RMA00-04RC
EXPANSION RELAY
1440-REX00-04RD
EXPANSION RELAY
1440-REX00-04RD
EXPANSION RELAY
1440-REX00-04RD
EXPANSION RELAY
1440-REX00-04RD
Power Supply
DYNAMIC MEASUREMENT
1440-VST02-01RA
DYNAMIC MEASUREMENT
1440-VST02-01RA
EXPANSION RELAY
1440-REX00-04RD
EXPANSION RELAY
1440-REX00-04RD
1
1
Installing the XM-120 Eccentricity Module 9
1Use 14 AWG wire.
The grounding wire can be connected to the DIN rail using a DIN Rail Grounding Block (Figure 2.3).
Publication GMSI10-UM010C-EN-P - May 2010
10 Installing the XM-120 Eccentricity Module
Figure 2.3 DIN Rail Grounding Block
Panel/Wall Mount Grounding
The XM modules can also be mounted to a conductive mounting plate that is grounded. See Figure 2.5. Use the grounding screw hole provided on the terminal base to connect the mounting plate the Chassis terminals.
Figure 2.4 Grounding Screw on XM Terminal Base
Publication GMSI10-UM010C-EN-P - May 2010
Figure 2.5 Panel/Wall Mount Grounding
Power Supply
Power Supply
1
1
Installing the XM-120 Eccentricity Module 11
1 Use 14 AWG wire.
Publication GMSI10-UM010C-EN-P - May 2010
12 Installing the XM-120 Eccentricity Module
IMPORTANT
IMPORTANT
24V Common Grounding
24 V power to the XM modules must be grounded. When two or more power supplies power the XM system, ground the 24 V Commons at a single point, such as the ground bus bar.
If it is not possible or practical to ground the -24Vdc supply, then it is possible for the system to be installed and operate ungrounded. However, if installed ungrounded then the system must not be connected to a ground through any other circuit unless that circuit is isolated externally. Connecting a floating system to a non-isolated ground could result in damage to the XM module(s) and/or any connected device. Also, operating the system without a ground may result in the system not performing to the published specifications regards measurement accuracy and communications speed, distance or reliability.
The 24 V Common and Signal Common terminals are internally connected. They are isolated from the Chassis terminals unless they are connected to ground as described in this section. See Terminal Block Assignments on page 18 for more information.
Transducer Grounding
Make certain the transducers are electrically isolated from earth ground. Cable shields must be grounded at one end of the cable, and the other end left floating or not connected. It is recommended that where possible, the cable shield be grounded at the XM terminal base (Chassis terminal) and not at the transducer.
DeviceNet Grounding
The DeviceNet network is functionally isolated and must be referenced to earth ground at a single point. XM modules do not require an external DeviceNet power supply. Connect DeviceNet V- to earth ground at one of the XM modules, as shown in Figure 2.6.
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 13
To Ground Bus
ATTENTION
Figure 2.6 Grounded DeviceNet V- at XM Module
Use of a separate DeviceNet power supply is not permitted. See Application Technique "XM Power Supply Solutions", publication ICM-AP005A-EN-E, for guidance in using XM with other DeviceNet products.

Mounting the Terminal Base Unit

For more information on the DeviceNet installation, refer to the ODVA Planning and Installation Manual - DeviceNet Cable System, which is available on the ODVA web site (http://www.odva.org).
Switch Input Grounding
The Switch Input circuits are functionally isolated from other circuits. It is recommended that the Switch RTN signal be grounded at a single point. Connect the Switch RTN signal to the XM terminal base (Chassis terminal) or directly to the DIN rail, or ground the signal at the switch or other equipment that is wired to the switch.
The XM family includes several different terminal base units to serve all of the XM modules. The XM-940 terminal base, Cat. No. 1440-TB-A, is the only terminal base unit used with the Eccentricity module.
Publication GMSI10-UM010C-EN-P - May 2010
14 Installing the XM-120 Eccentricity Module
ATTENTION
Position terminal base at a slight angle and hook over the top of the DIN rail.
The terminal base can be DIN rail or wall/panel mounted. Refer to the specific method of mounting below.
The XM modules make a chassis ground connection through the DIN rail. Use zinc plated, yellow chromated steel DIN rail to assure proper grounding. Using other DIN rail materials (e.g. aluminum, plastic, etc.), which can corrode, oxidize or are poor conductors can result in improper or intermittent platform grounding.
You can also mount the terminal base to a grounded mounting plate. Refer to Panel/Wall Mount Grounding on page 10.

DIN Rail Mounting

Use the following steps to mount the XM-940 terminal base unit on a DIN rail (A-B pt no. 199-DR1 or 199-DR4).
1. Position the terminal base on the 35 x 7.5 mm DIN rail (A).
2. Slide the terminal base unit over leaving room for the side
connector (B).
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 15
IMPORTANT
3. Rotate the terminal base onto the DIN rail with the top of the rail hooked under the lip on the rear of the terminal base.
4. Press down on the terminal base unit to lock the terminal base on the DIN rail. If the terminal base does not lock into place, use a screwdriver or similar device to open the locking tab, press down on the terminal base until flush with the DIN rail and release the locking tab to lock the base in place.

Interconnecting Terminal Base Units

Follow the steps below to install another terminal base unit on the DIN rail.
Make certain you install the terminal base units in order of left to right.
1. Position the terminal base on the 35 x 7.5 mm DIN rail (A).
2. Make certain the side connector (B) is fully retracted into the base unit.
3. Slide the terminal base unit over tight against the neighboring terminal
base. Make sure the hook on the terminal base slides under the edge of the terminal base unit.
4. Press down on the terminal base unit to lock the terminal base on the DIN rail. If the terminal base does not lock into place, use a screwdriver or similar device to open the locking tab, press down on the terminal base until flush with the DIN rail and release the locking tab to lock the base in place.
Publication GMSI10-UM010C-EN-P - May 2010
16 Installing the XM-120 Eccentricity Module
5. Gently push the side connector into the side of the neighboring terminal base to complete the backplane connection.

Panel/Wall Mounting

Installation on a wall or panel consists of:
laying out the drilling points on the wall or panel
drilling the pilot holes for the mounting screws
installing the terminal base units and securing them to the wall or panel
Use the following steps to install the terminal base on a wall or panel.
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 17
Side Connector
1. Lay out the required points on the wall/panel as shown in the drilling dimension drawing below.

Connecting Wiring for Your Module

2. Drill the necessary holes for the #6 self-tapping mounting screws.
3. Secure the terminal base unit using two #6 self-tapping screws.
4. To install another terminal base unit, retract the side connector into the base unit. Make sure it is fully retracted.
5. Position the terminal base unit up tight against the neighboring terminal
base. Make sure the hook on the terminal base slides under the edge of the terminal base unit.
6. Gently push the side connector into the side of the neighboring terminal base to complete the backplane connection.
7. Secure the terminal base to the wall with two #6 self-tapping screws.
Wiring to the module is made through the terminal base unit on which the module mounts. The XM-120 is compatible only with the XM-940 terminal base unit, Cat. No. 1440-TB-A.
Publication GMSI10-UM010C-EN-P - May 2010
18 Installing the XM-120 Eccentricity Module
ATTENTION
TIP
XM-940 (Cat. No. 1440-TB-A)
Revision number of XM module
Figure 2.7 XM-940 Terminal Base Unit

Terminal Block Assignments

The terminal block assignments and descriptions for the Eccentricity module are shown below.
The terminal block assignments are different for different XM modules. The following table applies only to the XM-120 Eccentricity module revision D01 (and later). If you have an earlier revision of the module, refer to Appendix D for its terminal block assignments.
Refer to the installation instructions for the specific XM module for its terminal assignments.
The XM module’s revision number is on the product label (which is located on the front of the XM module, as shown below).
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 19
WARNING
EXPLOSION HAZARD
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Terminal Block Assignments
No. Name Description
0 Xducer 1 (+) Vibration transducer 1 connection 1 Xducer 2 (+) Vibration transducer 2 connection 2 Buffer 1 (+) Vibration signal 1 buffered output 3 Buffer 2 (+) Vibration signal 2 buffered output 4 Tach/Signal In (+) Tachometer transducer/signal input, positive side 5 Buffer Power 1 IN Channel 1 buffer power input
Connect to terminal 6 for positive biased transducers or terminal 21 for negative biased transducers
6 Positive Buffer Bias Provides positive (-5 V to +24 V) voltage compliance to buffered outputs
Connect to terminals 5 (CH 1) or 22 (CH 2) for positive bias transducers 7 TxD PC serial port, transmit data 8 RxD PC serial port, receive data 9
XRTN
1
Circuit return for TxD and RxD
10 Chassis Connection to DIN rail ground spring or panel mounting hole 11 4-20 mA 1 (+) 4-20 mA output 12 4-20 mA 1 (-)
300 ohm maximum load
13 Chassis Connection to DIN rail ground spring or panel mounting hole 14 Chassis Connection to DIN rail ground spring or panel mounting hole 15 Chassis Connection to DIN rail ground spring or panel mounting hole 16
17
18
Xducer 1 (-)
Xducer 2 (-)
Signal Common
1
1
Vibration transducer 1 connection
Vibration transducer 2 connection
1
Vibration buffered output return
19 TACH Buffer Tachometer transducer/signal output 20 Tachometer (-) Tachometer transducer/signal return, TACH Buffer return 21 Buffer/Xducer Pwr (-) Provides negative (-24 V to +9 V) voltage compliance to buffered outputs
Connect to terminals 5 (CH 1) or 22 (CH 2) for negative bias transducers
Transducer power supply output, negative side; used to power external
sensor (40 mA maximum load)
Publication GMSI10-UM010C-EN-P - May 2010
20 Installing the XM-120 Eccentricity Module
Terminal Block Assignments
No. Name Description
22 Buffer Power 2 IN Channel 2 buffer power input
23 CAN_High DeviceNet bus connection, high differential (white wire) 24 CAN_Low DeviceNet bus connection, low differential (blue wire) 25 +24 V Out Internally connected to 24 V In (terminal 44)
26 DNet V (+) DeviceNet bus power input, positive side (red wire) 27 DNet V (-) DeviceNet bus power input, negative side (black wire) 28
24 V Common
29 4-20 mA 2 (+) 4-20 mA output 30 4-20 mA 2 (-) 31 Chassis Connection to DIN rail ground spring or panel mounting hole 32 Chassis Connection to DIN rail ground spring or panel mounting hole
Connect to terminal 6 for positive biased transducers or terminal 21 for
negative biased transducers
Used to daisy chain power if XM modules are not plugged into each other
1
Internally connected to 24 V Common (terminals 43 and 45)
Used to daisy chain power if XM modules are not plugged into each other
If power is not present on terminal 44, there is no power on this terminal
300 ohm maximum load
33 Chassis Connection to DIN rail ground spring or panel mounting hole 34 Chassis Connection to DIN rail ground spring or panel mounting hole 35 Chassis Connection to DIN rail ground spring or panel mounting hole 36 Chassis Connection to DIN rail ground spring or panel mounting hole 37 Chassis Connection to DIN rail ground spring or panel mounting hole 38 Chassis Connection to DIN rail ground spring or panel mounting hole 39 Not Used 40 Switch RTN Switch return, shared between SetPtMult and Reset Relay 41 Reset Relay Switch input to reset internal relay (active closed) 42 Reserved 43
24 V Common
1
Internally DC-coupled to circuit ground
44 +24 V In Connection to primary external +24 V power supply, positive side 45
24 V Common
1
Connection to external +24 V power supply, negative side (internally
DC-coupled to circuit ground) 46 Relay N.C. 1 Relay Normally Closed contact 1 47 Relay Common 1 Relay Common contact 1 48 Relay N.O. 1 Relay Normally Open contact 1 49 Relay N.O. 2 Relay Normally Open contact 2 50 Relay Common 2 Relay Common contact 2 51 Relay N.C. 2 Relay Normally Closed contact 2
Publication GMSI10-UM010C-EN-P - May 2010
1 Terminals are internally connected and isolated from the Chassis terminals.
Installing the XM-120 Eccentricity Module 21
IMPORTANT
IMPORTANT
ATTENTION

Connecting the Power Supply

Power supplied to the module must be nominally 24 Vdc (±10%) and must be a Class 2 rated circuit.
Wire the DC-input power supply to the terminal base unit as shown in Figure
2.8.
Figure 2.8 DC Input Power Supply Connections
A Class 2 circuit can be provided by use of an NEC Class 2 rated power supply, or by using a SELV or PELV rated power supply with a 5 Amp current limiting fuse installed before the XM module(s).
24Vdc needs to be wired to terminal 44 (+24 V In) to provide power to the device and other XM modules linked to the wired terminal base via the side connector.
The power connections are different for different XM modules. Refer to the installation instructions for your specific XM module for complete wiring information.
Publication GMSI10-UM010C-EN-P - May 2010
22 Installing the XM-120 Eccentricity Module
IMPORTANT
TIP
IMPORTANT

Connecting the Relays

The XM-120 has both Normally Open (NO) and Normally Closed (NC) relay contacts. Normally Open relay contacts close when the control output is energized. Normally Closed relay contacts open when the control output is
energized.
The alarms associated with the relay and whether the relay is normally de-energized (non-failsafe) or normally energized (failsafe) depends on the configuration of the module. Refer to Relay Parameters on page 52 for details.
Table 2.1 shows the on-board relay connections for the module.
All XM relays are double pole. This means that each relay has two contacts in which each contact operates independently but identically. The following information and illustrations show wiring solutions for both contacts; although, in many applications it may be necessary to wire only one contact.
The Expansion Relay module may be connected to the module to provide additional relays. Refer the XM-441 Expansion Relay Module User Guide for wiring details.
The NC/NO terminal descriptions (page 20) correspond to a de-energized (unpowered) relay.
When the relay is configured for non-failsafe operation, the relay is normally de-energized.
When the relay is configured for failsafe operation, the relay is normally energized, and the behavior of the NC and NO terminals is inverted.
Publication GMSI10-UM010C-EN-P - May 2010
Loading...
+ 101 hidden pages