Important User Information2
Environment and Enclosure3
North American Hazardous Location Approval4
European Hazardous Location Approval5
Prevent Electrostatic Discharge6
About the Module7
Install the Module8
Set the Node Address10
Self-Test12
Status Indicators13
Specifications15
Additional Resources19
2 XM Dynamic Measurement Module
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1 available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com
equipment and hard-wired electromechanical devices. Because of this difference, and also because of
the wide variety of uses for solid state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in
a hazardous environment, which may lead to personal injury or death, property
damage, or economic loss.
) describes some important differences between solid state
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Publication
Identifies information that is critical for successful application and understanding of
the product.
Identifies information about practices or circumstances that can lead to personal
injury or death, property damage, or economic loss. Attentions help you identify a
hazard, avoid a hazard and recognize the consequences.
Labels may be on or inside the equipment (for example, drive or motor) to alert people
that dangerous voltage may be present.
Labels may be on or inside the equipment (for example, drive or motor) to alert people
that surfaces may reach dangerous temperatures.
ICM-IN002A-EN-P - March 2009
Environment and Enclosure
XM Dynamic Measurement Module 3
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC
publication 60664-1), at altitudes up to 2000 meters (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according
to IEC/CISPR Publication 11. Without appropriate precautions, there may be
potential difficulties ensuring electromagnetic compatibility in other
environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The enclosure must have
suitable flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if
non-metallic. The interior of the enclosure must be accessible only by the use
of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, for additional
installation requirements, Allen-Bradley publication 1770-4.1
• NEMA Standards publication 250 and IEC publication 60529, as
applicable, for explanations of the degrees of protection provided by
different types of enclosure.
.
Publication
ICM-IN002A-EN-P - March 2009
4 XM Dynamic Measurement Module
North American Hazardous Location Approval
The following information applies when
operating this equipment in hazardous
locations.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for
use in Class I Division 2 Groups A, B, C, D, Hazardous
Locations and nonhazardous locations only. Each product is
supplied with markings on the rating na meplate indicating
the hazardous location temperature code. When
combining products within a system, the most adverse
temperature code (lowest "T" number) m ay be used to help
determine the overall temperature code of the system.
Combinations of equipment in your system are subject to
investigation by the local Authorit y Having Jurisdiction at
the time of installation.
WARNING
EXPLOSION HAZARD -
• Do not disconnect eq uipment unless
power has been removed or the
area is known to be nonhazardous.
• Do not disconnect connections to
this equipment unless power has
been removed or the area is known
to be nonhazardous. Secure any
external connections that mate to
this equipment by using screws,
sliding latches, threaded
connectors, or other means
provided with this product.
• Substitution of components may
impair suitability for Class I,
Division 2.
• If this product contains batteries,
they must only be changed in an
area known to be nonhazardous.
Informations sur l’utilisation de cet
équipement en environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements de
Classe I Division 2 Groupes A, B, C, D dangereux et non
dangereux. Chaque produit est livré avec des marqua ges sur
sa plaque d'identification qui indiquent le code de
température pour les environnement s dangereux. Lorsque
plusieurs produits sont combinés dans un système, le code de
température le plus défavorable (co de de température le plus
faible) peut être utilisé pour déterminer le code de
température global du système. Les comb inaisons
d'équipements dans le système sont sujettes à inspection pa r
les autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT
RISQUE D’EXPLOSION –
• Couper le courant ou s'assurer
que l'environnement est classé
non dangereux avant de
débrancher l'équipement.
• Couper le courant ou s'assurer
que l'environnement est classé
non dangereux avant de
débrancher les connecteurs. Fixer
tous les connecteurs externes
reliés à cet équipement à l'aide
de vis, loquets coulissants,
connecteurs filetés ou autres
moyens fournis avec ce produit.
• La substitution de composants
peut rendre cet équipement
inadapté à une utilisation en
environnement de Classe I,
Division 2.
• S'assurer que l'environnement est
classé non dangereux avant de
changer les piles.
Publication
ICM-IN002A-EN-P - March 2009
XM Dynamic Measurement Module 5
European Hazardous Location Approval
European Zone 2 Certification (The following applies when the product bears the
Ex or EEx Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by
European Union Directive 94/9/EC and has been found to comply with the Essential Health
and Safety Requirements relating to the design and construction of Category 3 equipment
intended for use in potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 60079-15 and EN 60079-0.
ATTENTION
WARNING
WARNING
WARNING
WARNING
This equipment is not resistant to sunlight or other sources of UV radiation.
This equipment must be installed in an enclosure providing at least IP54
protection when applied in Zone 2 environments.
This equipment shall be used within its specified ratings defined by
Allen-Bradley.
Provision shall be made to prevent the rated voltage from being exceeded by
transient disturbances of more than 40% when applied in Zone 2
environments.
This equipment must be used only with ATEX certified backplanes.
Publication
ICM-IN002A-EN-P - March 2009
6 XM Dynamic Measurement Module
WARNING
Secure any external connections that mate to this equipment by using screws,
sliding latches, threaded connectors, or other means provided with this
product.
WARNING
Do not disconnect equipment unless power has been removed or the area is
known to be nonhazardous.
Prevent Electrostatic Discharge
ATTENTION
ATTENTION
This equipment is sensitive to electrostatic discharge, which can cause
internal damage and affect normal operation. Follow these guidelines when
you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in
use.
This product is grounded through the DIN rail to chassis ground. Use zinc
plated yellow-chromate steel DIN rail to assure proper grounding. The use of
other DIN rail materials (for example, aluminum or plastic) that can corrode,
oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately.
ATTENTION
Publication
Do not remove or replace a Terminal Base unit while power is applied.
Interruption of the backplane can result in unintentional operation or machine
motion.
ICM-IN002A-EN-P - March 2009
XM Dynamic Measurement Module 7
About the Module
The 1440-DYN02-01RJ module is a 2-channel general purpose monitor that
supports measurements of dynamic inputs such as vibration, pressure, and
strain.The module can be used for monitoring shaft, casing, and pedestal
vibration in rotating equipment. Inputs accepted include eddy current probe,
standard integrated electronics piezoelectric (IEPE) accelerometer, or voltage
output measurement device such as a pressure transducer. The module also
accepts a tachometer input to provide speed measurement and order analysis
functions. The module can work with most tachometer signal sources such as
eddy current probe, unpowered magnetic probe, and other powered and
unpowered tachometer sensors.
The module provides onboard processing of critical vibration parameters and
advanced alarm and virtual relay logic. It can be integrated with existing
automation and control systems, including PLC’s and displays, to provide
information to aid in protecting machinery from catastrophic failures.
DYNAMIC MEASUREMENT
1440-DYN02-01RJ
Publication
ICM-IN002A-EN-P - March 2009
8 XM Dynamic Measurement Module
Install the Module
The module mounts on a 1440-TBS-J terminal base unit. We recommend that
you insert the module after you have connected the wiring on the terminal
base unit. Refer to the XM Dynamic Measurement Terminal Base Installation
Instructions, publication
ICM-IN003, for wiring information.
ATTENTION
ATTENTION
WARNING
WARNING
The 1440-DYN02-01RJ module is compatible only with the 1440-TBS-J
terminal base unit. The keyswitch on the terminal base unit should be at
position 1 for the module.
Do not attempt to install the 1440-DYN02-01RJ module on other
terminal base units.
Do not change the position of the keyswitch after wiring the terminal
base units.
To comply with the CE Low Voltage Directive (LVD), all connected I/O must be
powered from a source compliant with the following: Safety Extra Low Voltage
(SELV) or Protected Extra Low Voltage (PELV).
To comply with UL restrictions, this equipment must be powered from a source
compliant with the following: Class 2.
If you insert or remove the module while backplane power is on, an electrical
arc can occur. This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
If you connect or disconnect wiring while the field-side power is on, an
electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
before proceeding.
Publication
ICM-IN002A-EN-P - March 2009
XM Dynamic Measurement Module 9
1. Make certain the keyswitch (D) on the terminal base unit (E) is at
position 1 as required for the module.
C
B
A
G
D
E
F
31886
2. Make certain the side connector (B) is pushed all the way to the left.
You cannot install the module unless the connector is fully
extended.
3. Make certain that the pins on the bottom of the module are straight so
they will align properly with the connectors in the terminal base unit.
4. Position the module (A) with its alignment bar (G) aligned with the
groove (F) on the terminal base.
5. Press firmly and evenly to seat the module in the terminal base unit.
The module is seated when the latching mechanism (C) is locked into
the module.
6. Repeat the above steps to install the next module in its terminal base.
Publication
ICM-IN002A-EN-P - March 2009
10 XM Dynamic Measurement Module
Set the Node Address
The module has a DIP switch for setting the network node address. DIP
switches 5 through 10 set the module’s node address using binary addressing.
The module is shipped from the factory with the node address set to 63 (as
shown below).
1440-DYN02-01RJ
TIP
TIP
DYNAMIC MEASUREMENT
DIP switches 1 through 4 are not used.
The node addresses start with 1 for the module closest to the ACNR, and
increase for each consecutive module.
Follow the steps below to set the node address.
1. Refer to the table on page 11 for the switch settings of an address.
2. Using a pointed tool, slide switches 5 through 10 to the appropriate
positions (1 or 0).
(1) Do not set the node address to 0. Node addresses start with 1 for the module closest to the ACNR.
Publication
ICM-IN002A-EN-P - March 2009
12 XM Dynamic Measurement Module
Self-Test
The XM module performs a self-test when it powers up. The self-test includes
an LED test and a device test. During the LED test, the indicators will turn
on independently and in sequence for approximately 0.25 seconds.
The device test occurs after the LED test. The Module Status (MS) indicator
is used to indicate the status of the device self-test.
MS Indicator StateDescription
Flashing Red and GreenDevice self-test is in progress.
Solid Green or Flashing GreenDevice self-test completed successfully, and
Flashing Red• Device self-test completed, the hardware
Solid RedUnrecoverable fault, hardware failure, or Boot
the firmware is valid and running.
is OK, but the firmware is invalid.
• The firmware download is in progress.
Loader program may be corrupted.
Publication
ICM-IN002A-EN-P - March 2009
XM Dynamic Measurement Module 13
Status Indicators
The module has seven LED indicators on top of the module.
DYNAMIC MEASUREMENT
Status Indicators
1440-DYN02-01RJ
IndicatorStateDescription
Module Status (MS)OffNo power applied to the module.
Alternating
Module performing power-up self-test.
Red/Green
Flashing Red• Application firmware is invalid or not
loaded. Download firmware to the
module.
• Firmware download is currently in
progress.
Solid RedAn unrecoverable fault has occurred. The
module may need to be repaired or
replaced.
Flashing GreenModule operating in Program Mode.
Solid GreenModule operating in Run Mode.
Publication
ICM-IN002A-EN-P - March 2009
14 XM Dynamic Measurement Module
IndicatorStateDescription
Network Status (NS)OffModule is not online.
• Module is autobauding.
• No power applied to the module;
look at Module Status LED.
Flashing RedOne or more I/O connections are in the
timed-out state.
Solid RedFailed communications (duplicate MAC ID
or bus-off).
Flashing GreenModule is online but no connections are
currently established.
Solid GreenModule is online with connections
Channel 0 &
Channel 1
TachometerOff• Normal operation within alarm limits
Off• Normal operation within alarm limits
Solid YellowAlarm associated with this channel is in
Solid RedAlarm associated with this channel is in
Flashing RedA transducer fault exists on the channel.
Solid YellowAlarm on Speed or Acceleration is in
Solid RedAlarm on Speed or Acceleration is in
currently established.
on the channel.
• No power applied to the module; look
at the Module Status LED.
Alert.
Danger.
DC bias is outside the DC Low and High
Limits.
on the channel.
• No power applied to the module; look
at the Module Status LED.
Alert.
Danger.
Publication
ICM-IN002A-EN-P - March 2009
XM Dynamic Measurement Module 15
IndicatorStateDescription
Flashing YellowTachometer fault other than a transducer
fault (for example no pulse received).
Flashing RedTachometer signal DC bias is not within
the DC Low and High Limits.
Setpoint MultiplierOffAlarm Limit Multiplier is not in effect.
Solid YellowAlarm Limit Multiplier is in effect.
RelayOffVirtual relay is not activated.
Solid RedVirtual relay is activated.
Specifications
XM Dynamic Measurement Module - 1440-DYN02-01RJ
AttributeValue
Enclosure Type RatingNone (open-style)
Input Voltage (mounted in the 1440-TBS-J)24V DC
Current Draw Max 250 mA
Output Voltage-24V DC, 60 mA Max
Isolation VoltageNot Rated (Class 2 power source required)
No isolation between I/O or backplane
Wire SizeDetermined by installed terminal base
Wiring Category
(1)
North American Temp CodeT4A
IEC Temp CodeT4
2 - on signal ports
1 - on power ports
2 - on communications ports
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication
XM ControlNet Adapter User Manual,
publication ICM-UM001
Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1
Product Certifications website,
http://ab.com
You can view or download publications at
http://literature.rockwellautomation.com
documentation, contact your local Rockwell Automation distributor or sales
representative.
Provides details about how to install the
terminal base for the XM Dynamic
Measurement module.
Provides details about how to install, wire
and configure the Dynamic Measurement
module.
Provides details about how to install and
wire the adapter, and adapter technical
specifications.
Provides details about how to install, use
and configure the adapter.
Provides general guidelines for installing a
Rockwell Automation industrial system.
Provides declarations of conformity,
certificates, and other certification details.
. To order paper copies of technical
Publication
ICM-IN002A-EN-P - March 2009
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using
its products. At http://support.rockwellautomation.com
manuals, a knowledge base of FAQs, technical and application notes, sample code and
links to software service packs, and a MySupport feature that you can customize to
make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and
troubleshooting, we offer TechConnect support programs. For more information,
contact your local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the
information that's contained in this manual. You can also contact a special Customer
Support number for initial help in getting your product up and running.
United States1.440.646.3434
Outside United StatesPlease contact your local Rockwell Automation representative for any
Monday – Friday, 8 a.m. – 5 p.m. EST
technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational
when shipped from the manufacturing facility. However, if your product is not
functioning and needs to be returned, follow these procedures.
United StatesContact your distributor. You must provide a Customer Support case number
Outside United StatesPlease contact your local Rockwell Automation representative for the return
Allen-Bradley, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
(call the phone number above to obtain one) to your distributor in order to
complete the return process.