Rockwell Automation 1440-DYN02-01RJ User Manual

Installation Instructions
XM Dynamic Measurement Module
Catalog Number 1440-DYN02-01RJ
Top ic Page
Important User Information 2 Environment and Enclosure 3 North American Hazardous Location Approval 4 European Hazardous Location Approval 5 Prevent Electrostatic Discharge 6 About the Module 7 Install the Module 8 Set the Node Address 10 Self-Test 12 Status Indicators 13 Specifications 15 Additional Resources 19
2 XM Dynamic Measurement Module

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
) describes some important differences between solid state
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Publication
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.

Environment and Enclosure

XM Dynamic Measurement Module 3
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see:
Industrial Automation Wiring and Grounding Guidelines, for additional installation requirements, Allen-Bradley publication 1770-4.1
NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
.
Publication
ICM-IN002A-EN-P - March 2009
4 XM Dynamic Measurement Module

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating na meplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) m ay be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authorit y Having Jurisdiction at the time of installation.
WARNING
EXPLOSION HAZARD -
• Do not disconnect eq uipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marqua ges sur sa plaque d'identification qui indiquent le code de température pour les environnement s dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (co de de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les comb inaisons d'équipements dans le système sont sujettes à inspection pa r les autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT
RISQUE D’EXPLOSION –
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Publication
XM Dynamic Measurement Module 5

European Hazardous Location Approval

European Zone 2 Certification (The following applies when the product bears the Ex or EEx Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
ATTENTION
WARNING
WARNING
WARNING
WARNING
This equipment is not resistant to sunlight or other sources of UV radiation.
This equipment must be installed in an enclosure providing at least IP54 protection when applied in Zone 2 environments.
This equipment shall be used within its specified ratings defined by Allen-Bradley.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Zone 2 environments.
This equipment must be used only with ATEX certified backplanes.
Publication
ICM-IN002A-EN-P - March 2009
6 XM Dynamic Measurement Module
WARNING
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
WARNING
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.

Prevent Electrostatic Discharge

ATTENTION
ATTENTION
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in
use.
This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
ATTENTION
Publication
Do not remove or replace a Terminal Base unit while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.
XM Dynamic Measurement Module 7

About the Module

The 1440-DYN02-01RJ module is a 2-channel general purpose monitor that supports measurements of dynamic inputs such as vibration, pressure, and strain.The module can be used for monitoring shaft, casing, and pedestal vibration in rotating equipment. Inputs accepted include eddy current probe, standard integrated electronics piezoelectric (IEPE) accelerometer, or voltage output measurement device such as a pressure transducer. The module also accepts a tachometer input to provide speed measurement and order analysis functions. The module can work with most tachometer signal sources such as eddy current probe, unpowered magnetic probe, and other powered and unpowered tachometer sensors.
The module provides onboard processing of critical vibration parameters and advanced alarm and virtual relay logic. It can be integrated with existing automation and control systems, including PLC’s and displays, to provide information to aid in protecting machinery from catastrophic failures.
DYNAMIC MEASUREMENT
1440-DYN02-01RJ
Publication
ICM-IN002A-EN-P - March 2009
8 XM Dynamic Measurement Module

Install the Module

The module mounts on a 1440-TBS-J terminal base unit. We recommend that you insert the module after you have connected the wiring on the terminal base unit. Refer to the XM Dynamic Measurement Terminal Base Installation Instructions, publication
ICM-IN003, for wiring information.
ATTENTION
ATTENTION
WARNING
WARNING
The 1440-DYN02-01RJ module is compatible only with the 1440-TBS-J terminal base unit. The keyswitch on the terminal base unit should be at position 1 for the module.
Do not attempt to install the 1440-DYN02-01RJ module on other terminal base units. Do not change the position of the keyswitch after wiring the terminal base units.
To comply with the CE Low Voltage Directive (LVD), all connected I/O must be powered from a source compliant with the following: Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
To comply with UL restrictions, this equipment must be powered from a source compliant with the following: Class 2.
If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Publication
XM Dynamic Measurement Module 9
1. Make certain the keyswitch (D) on the terminal base unit (E) is at position 1 as required for the module.
C
B
A
G
D
E
F
31886
2. Make certain the side connector (B) is pushed all the way to the left.
You cannot install the module unless the connector is fully extended.
3. Make certain that the pins on the bottom of the module are straight so they will align properly with the connectors in the terminal base unit.
4. Position the module (A) with its alignment bar (G) aligned with the groove (F) on the terminal base.
5. Press firmly and evenly to seat the module in the terminal base unit. The module is seated when the latching mechanism (C) is locked into the module.
6. Repeat the above steps to install the next module in its terminal base.
Publication
ICM-IN002A-EN-P - March 2009
10 XM Dynamic Measurement Module

Set the Node Address

The module has a DIP switch for setting the network node address. DIP switches 5 through 10 set the module’s node address using binary addressing. The module is shipped from the factory with the node address set to 63 (as
shown below).
1440-DYN02-01RJ
TIP
TIP
DYNAMIC MEASUREMENT
DIP switches 1 through 4 are not used.
The node addresses start with 1 for the module closest to the ACNR, and increase for each consecutive module.
Follow the steps below to set the node address.
1. Refer to the table on page 11 for the switch settings of an address.
2. Using a pointed tool, slide switches 5 through 10 to the appropriate positions (1 or 0).
Down position = 0
Up position =1
Publication
XM Dynamic Measurement Module 11
Switch Settings for Node Address
Switch Setting
Node
SW5->SW10
Addr
(1)
000000 16 010000 32 100000 48 110000
0 1 000001 17 010001 33 100001 49 110001 2 000010 18 010010 34 100010 50 110010 3 000011 19 010011 35 100011 51 110011 4 000100 20 010100 36 100100 52 110100 5 000101 21 010101 37 100101 53 110101 6 000110 22 010110 38 100110 54 110110 7 000111 23 010111 39 100111 55 110111 8 001000 24 011000 40 101000 56 111000 9 001001 25 011001 41 101001 57 111001 10 001010 26 011010 42 101010 58 111010 11 001011 27 011011 43 101011 59 111011 12 001100 28 011100 44 101100 60 111100 13 001101 29 011101 45 101101 61 111101 14 001110 30 011110 46 101110 62 111110 15 001111 31 011111 47 101111 63 111111
Node Addr
Switch Setting
SW5->SW10
Node Addr
Switch Setting
SW5->SW10
Node Addr
Switch Setting
SW5->SW10
(1) Do not set the node address to 0. Node addresses start with 1 for the module closest to the ACNR.
Publication
ICM-IN002A-EN-P - March 2009
12 XM Dynamic Measurement Module

Self-Test

The XM module performs a self-test when it powers up. The self-test includes an LED test and a device test. During the LED test, the indicators will turn on independently and in sequence for approximately 0.25 seconds.
The device test occurs after the LED test. The Module Status (MS) indicator is used to indicate the status of the device self-test.
MS Indicator State Description
Flashing Red and Green Device self-test is in progress. Solid Green or Flashing Green Device self-test completed successfully, and
Flashing Red Device self-test completed, the hardware
Solid Red Unrecoverable fault, hardware failure, or Boot
the firmware is valid and running.
is OK, but the firmware is invalid.
The firmware download is in progress.
Loader program may be corrupted.
Publication
XM Dynamic Measurement Module 13

Status Indicators

The module has seven LED indicators on top of the module.
DYNAMIC MEASUREMENT
Status Indicators
1440-DYN02-01RJ
Indicator State Description
Module Status (MS) Off No power applied to the module.
Alternating
Module performing power-up self-test.
Red/Green Flashing Red Application firmware is invalid or not
loaded. Download firmware to the module.
Firmware download is currently in progress.
Solid Red An unrecoverable fault has occurred. The
module may need to be repaired or
replaced. Flashing Green Module operating in Program Mode. Solid Green Module operating in Run Mode.
Publication
ICM-IN002A-EN-P - March 2009
14 XM Dynamic Measurement Module
Indicator State Description
Network Status (NS) Off Module is not online.
Module is autobauding.
No power applied to the module;
look at Module Status LED.
Flashing Red One or more I/O connections are in the
timed-out state. Solid Red Failed communications (duplicate MAC ID
or bus-off). Flashing Green Module is online but no connections are
currently established. Solid Green Module is online with connections
Channel 0 & Channel 1
Tachometer Off Normal operation within alarm limits
Off Normal operation within alarm limits
Solid Yellow Alarm associated with this channel is in
Solid Red Alarm associated with this channel is in
Flashing Red A transducer fault exists on the channel.
Solid Yellow Alarm on Speed or Acceleration is in
Solid Red Alarm on Speed or Acceleration is in
currently established.
on the channel.
No power applied to the module; look at the Module Status LED.
Alert.
Danger.
DC bias is outside the DC Low and High Limits.
on the channel.
No power applied to the module; look at the Module Status LED.
Alert.
Danger.
Publication
XM Dynamic Measurement Module 15
Indicator State Description
Flashing Yellow Tachometer fault other than a transducer
fault (for example no pulse received).
Flashing Red Tachometer signal DC bias is not within
the DC Low and High Limits.
Setpoint Multiplier Off Alarm Limit Multiplier is not in effect.
Solid Yellow Alarm Limit Multiplier is in effect.
Relay Off Virtual relay is not activated.
Solid Red Virtual relay is activated.

Specifications

XM Dynamic Measurement Module - 1440-DYN02-01RJ
Attribute Value
Enclosure Type Rating None (open-style) Input Voltage (mounted in the 1440-TBS-J) 24V DC
Current Draw Max 250 mA Output Voltage -24V DC, 60 mA Max Isolation Voltage Not Rated (Class 2 power source required)
No isolation between I/O or backplane Wire Size Determined by installed terminal base
Wiring Category
(1)
North American Temp Code T4A IEC Temp Code T4
2 - on signal ports
1 - on power ports
2 - on communications ports
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1.
Publication
ICM-IN002A-EN-P - March 2009
16 XM Dynamic Measurement Module
Environmental Specifications
Attribute Value
Operating Temperature IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
Non-Operating Temperature IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
Relative Humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
Vibration IEC 60068-2-6 (Test Fc, Operating):
Operating Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Nonoperating Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Emissions CISPR 11:
ESD Immunity IEC 61000-4-2:
-20…70 °C (-4…158 °F)
-40…85 °C (-40…185 °F)
5…95% non-condensing
5 g @ 10…500 Hz
15 g
20 g
Group 1, Class A
4 kV contact discharges
8 kV air discharges
Publication
XM Dynamic Measurement Module 17
Environmental Specifications
Attribute Value
Radiated RF Immunity IEC 61000-4-3:
EFT/B Immunity IEC 61000-4-4:
Surge Transient Immunity IEC 61000-4-5:
Conducted RF Immunity IEC 61000-4-6:
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication
10V/m with 1 kHz sine-wave 80% AM
from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM
at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM
at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
±4 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports
±2 kV at 5 kHz on communications ports
±1 kV line-line (DM) and ±2 kV line-earth
(CM) on power ports
±1 kV line-line (DM) and ±2 kV line-earth
(CM) on signal ports
±2 kV line-earth (CM) on shielded ports
±2 kV line-earth (CM) on communications
ports
10V rms with 1 kHz sine-wave 80% AM
from 150 kHz…80 MHz
1770-4.1.
Publication
ICM-IN002A-EN-P - March 2009
18 XM Dynamic Measurement Module
Certifications
Certifications
(1)
(when product is marked)
Description
c-UL-us UL Listed Industrial Control Equipment, certified for US and
Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE European Union 2004/108/EC EMC Directive, compliant
with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8,
Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection "n" (II 3 G Ex nA IIC T4 X)
EN 60079-0; General Requirements (Zone 2)
(1)
See the Product Certification link at http:// www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Publication
XM Dynamic Measurement Module 19

Additional Resources

These documents contain additional information concerning related Rockwell Automation products.
Resource Description
XM Dynamic Measurement Module Terminal Base Installation Instructions, publication ICM-IN003
XM Dynamic Measurement Module User Manual, publication ICM-UM002
XM ControlNet Adapter Installation Instructions, publication ICM-IN001
XM ControlNet Adapter User Manual, publication ICM-UM001
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certifications website,
http://ab.com
You can view or download publications at
http://literature.rockwellautomation.com
documentation, contact your local Rockwell Automation distributor or sales representative.
Provides details about how to install the terminal base for the XM Dynamic Measurement module.
Provides details about how to install, wire and configure the Dynamic Measurement module.
Provides details about how to install and wire the adapter, and adapter technical specifications.
Provides details about how to install, use and configure the adapter.
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
. To order paper copies of technical
Publication
ICM-IN002A-EN-P - March 2009
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
United States 1.440.646.3434
Outside United States Please contact your local Rockwell Automation representative for any
Monday – Friday, 8 a.m. – 5 p.m. EST
technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number
Outside United States Please contact your local Rockwell Automation representative for the return
Allen-Bradley, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
(call the phone number above to obtain one) to your distributor in order to complete the return process.
procedure.
, you can find technical
Publication ICM-IN002A-EN-P - March 2009 PN 35149
Copyright © 2009 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...