Rockwell Automation 1426-MxE-xxx User Manual

Installation Instructions
IMPORTANT
PowerMonitor 5000 Unit Firmware Revision Update
Catalog Numbers 1426-MxE-xxx
Topi
c
Access Product Firmware Revision 3
Update the Device Firmware Revision with the ControlFLASH Utility 8
Determine Communication Type 13
Catalog Number Format 15
This manual provides instructions for updating the firmware revision for the PowerMonitor™ 5000 unit. Additional information can be found in the Maintenance chapter of the PowerMonitor 5000 Unit User Manual, publication
1426
Pag
e
Before starting, verify that the appropriate network connections are made and that a driver for the network is configured in RSLinx® Classic software.
PowerMonitor 5000 Unit Firmware Revision Update
IMPORTANT

Important User Information

Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
2 Rockwell Automation Publication 1426-IN004A-EN-P - December 2013
PowerMonitor 5000 Unit Firmware Revision Update
1
3
2

Access Product Firmware Revision

All PowerMonitor 5000 firmware release notes are available online with the Product Compatibility and Download Center.
1. From the Quick Links list on http://www.ab.com Compatibility and Download Center.
2. From the Compatibility Scenarios tab or the Get Downloads tab, search for and choose your product.
, choose Product
3. Click the download icon to access product release notes.
4. Select the device catalog number (1).
The chosen catalog number appears under Selections (2).
5. When the correct catalog number appears under Selections, click Find Downloads
(3).
Rockwell Automation Publication 1426-IN004A-EN-P - December 2013 3
PowerMonitor 5000 Unit Firmware Revision Update
6. Under Downloads, click the download icon . .
7. Click the link for the firmware upgrade.
4 Rockwell Automation Publication 1426-IN004A-EN-P - December 2013
PowerMonitor 5000 Unit Firmware Revision Update
8. Log in by using the member email address and password.
9. After reading the Software End-User License Agreement, click I Agre e.
The download box opens.
Rockwell Automation Publication 1426-IN004A-EN-P - December 2013 5
PowerMonitor 5000 Unit Firmware Revision Update
10. Once the download is complete, open the Download folder.
11. In the Download folder, double-click the 1426 Products folder.
6 Rockwell Automation Publication 1426-IN004A-EN-P - December 2013
PowerMonitor 5000 Unit Firmware Revision Update
12. Open the WinZip file in the 1426-Products folder by double-clicking the WinZip filename.
This example shows the 1426_M5_245.zip file.
13. Open the Windows Installer Package file in the WinZip folder by double-clicking the file with the ‘msi’ extension.
This example shows the Windows Installer Package file 1426_M5_v245.msi.
Rockwell Automation Publication 1426-IN004A-EN-P - December 2013 7
PowerMonitor 5000 Unit Firmware Revision Update
IMPORTANT
14. In the WinZip Caution dialog box, click Yes.

Update the Device Firmware Revision with the ControlFLASH Utility

The ControlFLASH™ utility
Directions on updating the firmware revision are found in the Update the
Device Firmware Revision with the ControlFLASH Utility section.
The ControlFLASH utility does not update the firmware if any Class 1 connections (generic or electronic data sheet (EDS) Add-on Profile connections) exist. A connection exists if the Network Status indicator is either solid green (connection active) or blinking red (connection timed out). Use the Studio 5000 Logix Designer™ application to connect to the controller that owns each connection and inhibit the connec tion. After successfully updating the power monitor firmware, you can uninhibit the connections. Note that you can edit connection properties to reflect the new power monitor firmware revision.
When updating the firmware revision, refer to the Access Product Firmware
Revision section for instructions on obtaining the latest firmware revision from
the Rockwell Automation download center.
1. Check Yes, I want to launch ControlFLASH and click Close.
opens.
8 Rockwell Automation Publication 1426-IN004A-EN-P - December 2013
PowerMonitor 5000 Unit Firmware Revision Update
IMPORTANT
2. In the Select FactoryTalk Directory dialog box, click Local.
3. Click
OK.
4. On the Welcome to ControlFLASH dialog box, click Next.
5. Select the current catalog number of the device, based on the communication
type, and click Next:
Refer to the Determine Communication Type
section to find the
relevant catalog number based on the communication type.
Refer to the Catalog Number Format
section for an explanation of the
catalog number format.
There are three catalog number options provided, based on the communication type: Ethernet, ControlNet, and DeviceNet. However, you must select only one option that relates to the communication type in your PowerMonitor 5000 unit. Refer to the Determine Communication Type
section
for more details on how to select the correct catalog number.
Rockwell Automation Publication 1426-IN004A-EN-P - December 2013 9
PowerMonitor 5000 Unit Firmware Revision Update
TIP
TIP
6. In RSLinx software, navigate to the IP address of the device over the Ethernet network, select the device, and click OK.
To update the firmware revision over the ControlNet or DeviceNet network, navigate to the device through the network scanner in the RSLinx software window.
To update the firmware revision via a USB connection, an RNDIS driver must be installed. Refer to the PowerMonitor 5000 USB Driver Installation and Configuration Installation Instructions, publication
1426-IN001,
for directions on installing the driver.
RSLinx Classic Lite software must be installed to continue with the upgrade process.
To access the device IP address, the IP address must be added to the Ethernet device’s driver address list in RSLinx software.
10 Rockwell Automation Publication 1426-IN004A-EN-P - December 2013
PowerMonitor 5000 Unit Firmware Revision Update
TIP
7. Select the new firmware revision number of the device and click Next.
For the ControlFLASH utility, version 11 or later, the firmware revision has the following format, 2.xxx. Therefore, firmware revision 2.50 appears as 2.050 in the ControlFLASH utility.
8. On the Summary dialog box, click Finish.
Rockwell Automation Publication 1426-IN004A-EN-P - December 2013 11
PowerMonitor 5000 Unit Firmware Revision Update
9. On the dialog box regarding updating the target device, click Yes.
10. On the Update Status dialog box, click OK to confirm that the update is
complete.
11. Check the device webpage to confirm that the firmware revision is updated correctly.
12. Exit the ControlFLASH
utility.
12 Rockwell Automation Publication 1426-IN004A-EN-P - December 2013
PowerMonitor 5000 Unit Firmware Revision Update
No network communication card present.
ControlNet network communication card present.

Determine Communication Type

There are two options to determine the catalog number based on the communication type of the device.:
Visual inspection
View the PowerMonitor 5000 webpage
Option 1: Visual Inspec
If there is no communication card present in the card slot, the PowerMonitor 5000 unit has the catalog number format 1426-MxE.
tion
If there is a ControlNet communication card in the card slot, the PowerMonitor 5000 unit has the catalog number format 1426-MxE-CNT.
Rockwell Automation Publication 1426-IN004A-EN-P - December 2013 13
PowerMonitor 5000 Unit Firmware Revision Update
TIP
TIP
DeviceNet network communication card present.
If there is a DeviceNet communication card in the card slot, the PowerMonitor 5000 unit has the catalog number format 1426-MxE-DNT.

Option 2: View the PowerMonitor 5000 Webpage

The PowerMonitor 5000 webpage can be accessed in the following ways:
Ethernet: If the PowerMonitor 5000 unit is able to communicate through an Ethernet network, search for the device’s IP address in an Internet web browser. The catalog number and installed communication type are listed on the home page as shown in Figure 1
.
USB: If the PowerMonitor 5000 unit is connected with a USB cable, search for the default device’s IP address 192.168.169.3 in an Internet web browser. The catalog number and installed communication type are listed on the home page as shown in Figure 1
.
To access the dev ice’s webpage through a USB cable, an RNDIS driver must be installed on the computer. Refer to the PowerMonitor 5000 USV Driver Installation and Configuration Installation Instructions, publication
1426
-IN001, for directions
on installing the driver.
If a field-installed optional communication card is added to the device, the webpage does not reflect the change in communication card information. In this case, use the Option 1: V
isual Inspection method.
14 Rockwell Automation Publication 1426-IN004A-EN-P - December 2013
PowerMonitor 5000 Unit Firmware Revision Update
1426-M5E-CNT
Bulletin
Number
Current Model
Number
Communication
Type
Figure 1 -
PowerMonitor 5000 Webpage

Catalog Number Format

In the ControlFLASH utility, the catalog number options are based on the model number (for example, M5E or M6E) and the communication type: Ethernet (E); ControlNet (CNT ), or DeviceNet (DNT ).
Figure 2 - Catalog Number Exam
ple
Rockwell Automation Publication 1426-IN004A-EN-P - December 2013 15
PowerMonitor 5000 Unit Firmware Revision Update

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.
Re
sourc
e
PowerMonitor 5000 Unit User Manual, publication
1426-UM001
PowerMonitor 5000 USB Driver Installation and Configuration Installation Instructions, publication
1426-IN001
Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other
You can view or download publications at
literature/.
To order paper copies of technical documentation, contact your local
D
esc
ription
Provides information on installing and configuring the PowerMonitor 5000 unit.
Provides instructions for installing the USB driver.
certification details.
http://www.rockwellautomation.com/
Allen-Bradley distributor or Rockwell Automation sales representative.
U.S. Allen-Bradley Drives Technical Support - Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, E-mail: support@drives.ra.rockwell.com Online: www.ab.com/support/abdrives
Allen-Bradley, Rockwell Software, Rockwell Automation, PowerMonitor, RSLinx, Studio 5000 Logix Designer, FactoryTalk, and ControlFLASH are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1426-IN004A-EN-P - December 2013
Copyright © 2013 Rockwell Auto mation, Inc. All rights reserved. Pr inted in the U.S.A.
Loading...