Rockwell Automation 141A User Manual

MCS™ Star Con guration Software – Tutorial
Table of Contents
Page
Designing a Mounting System Solution Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1. Identify System Loads and Parameters . . . . . . . . . . . . . . . . . 3
2. Enter System Information . . . . . . . . . . . . . . . . . . . . . . . 4
3. Enter Rack Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4. Enter Supply Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
6. Enter Starter Parameters . . . . . . . . . . . . . . . . . . . . . . . .8
7. Copying Components . . . . . . . . . . . . . . . . . . . . . . . . .9
8. Editing Component Attributes . . . . . . . . . . . . . . . . . . . . 10
9. Confi guring a Drive . . . . . . . . . . . . . . . . . . . . . . . . . 11
10. Moving Components . . . . . . . . . . . . . . . . . . . . . . . . . 14
11. Adding Additional Racks . . . . . . . . . . . . . . . . . . . . . . . 15
12. Changing Supply Type . . . . . . . . . . . . . . . . . . . . . . . . 16
13. Adding a Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . 17
14. Confi guring a Soft-starter. . . . . . . . . . . . . . . . . . . . . . . 19
15. Con fi guring  ree Component Starters . . . . . . . . . . . . . . . 21
Additional MCS Star Functionality Adding Busbar Covers. . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Creating Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Locking the Rack Design . . . . . . . . . . . . . . . . . . . . . . . . . 30
Exporting Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Exporting Assembly to TRCS . . . . . . . . . . . . . . . . . . . . . . . 32
Printing and Exporting Data . . . . . . . . . . . . . . . . . . . . . . . 33
User Defi ned Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
 e following tutorial requires that you have the MCS Star Confi guration Software installed on your computer. If you do not have it installed, you can install it from the “Line-to-Load” DVD. Go to: Learning Modules > MCS Star Confi guration Software > and click on Download MCS Star > Follow the prompts to complete the install.
Open MCS Star by double clicking on the short cut from your desktop or by going to the following: Start Menu > Programs > Rockwell Automation > MCS Star When you run MCS Star and are connected to the Internet, select “Yes” in the fi rst popup window.  is will check for updates to the software and prompt you to run Current Program Updater if any updates are available.
In the next popup window, select “Confi gure a Busbar Assembly”;
then select [ OK ] button.
Designing a Mounting System Solution
Introduction
MCS Star is a powerful product selection and system planning software as well as a graphical design tool. It allows the user to confi gure a multitude of starter and loadfeeder variations and then visually represents the confi guration on the graphical interface.  e software can help design systems compliant with UL/CSA or IEC standards. It also calculates wire sizing, support spacing and dimensional restrictions. Once the layout is completed, it can easily be exported to the user’s CAD system. In addition, MCS Star can generate wiring diagrams, dimension drawings and bills of material.
MCS Star Tutorial
2
With MCS Star, there are certain planning steps required before using the software.  e user must fi rst gather information about the assembly they will be creating.  ings such as:
Identifying system parameters and loads
Determining if the assembly will be busbar mount or panel mount
Estimating the total current and dimensional restrictions
Considering the layout of the rack(s)
Determine what electrical standards must be met
Step 1: Identify System Loads and Parameters
Below is the list of motors and loads that will be used in our tutorial. We need to confi gure a horizontally mounted busbar assembly for a line voltage of 480V 60 Hz, control voltage 120V 60 Hz, designed per UL standards, in a 900 mm wide cabinet and have a short-circuit current rating (SCCR) of 5 k A.  e 12 loads are as follows:
Motor 1 DOL 30.0 Hp 40.0 A
Motor 2 DOL 10.0 Hp 14.0 A
Motor 3 DOL 15.0 Hp 21.0 A
Motor 4 Reversing 15.0 Hp 21.0 A
Motor 5 Reversing 1.5 Hp 3.0 A
Motor 6 Drive 0.5 Hp 1.1 A
Resistive 7 Circuit Breaker 40.0 A
Motor 8 Soft Starter 10.0 Hp 14.0 A
Motor 9 DOL w/E1+ OLR 3.0 Hp 4.8 A
Motor 10 DOL w/E3 OLR 3.0 Hp 4.8 A
Motor 11 Reversing w/E1+ OLR 2.0 Hp 3.4 A
Motor 12 Reversing w/E1+ OLR 2.0 Hp 3.4 A
Estimated Total Ampacity: 170.5 A
In North America, busbar should be sized at 125% of the FLA of the largest motor + the sum of all other motor FLAs + 125% of all non-motor loads. Based upon the loads above, the busbar needs to be rated at least 190.5 A. Let’s use the 20x5 busbar rated 320 A.
We also need to decide how we will feed power to the racks, as well as protect them. If we choose a circuit breaker to do both jobs, it will save us time and space. Circuit breakers in North America should be sized at least 125% of the total load and up to 250% of the load. Let’s choose a 250 A circuit breaker for this application.
We now have enough information to design a system using MCS Star.
To save your design, click on the File Menu > Save Project. If you have not saved the project
previously, you will be presented with a standard windows save dialog where you can browse to a folder, specify a fi lename and save your project.
Saving this project will allow you to download the project output to Rockwell Automation Temperature Rise Calculation Software (TRCS).
Be sure to save your project often to ensure that confi guration work is not lost.
3
Step 2: Enter System Information
In the appearing confi gurator window, select the busbar system parameters. Here you specify the electrical standards, the units of measure you prefer to use, supply voltage and SCCR requirements. Enter the “System Information” per the following example.
Step 3: Enter Rack Data
As you scroll down the left hand side of the window, you can now enter the rack data.  is is where you enter the rack orientation, the busbar length and size, and support information. Some items will automatically be completed, based upon previous selections.
Enter “Rack Data” per the following example.
4
Step 4: Enter Supply Data
Finally, you will enter the supply information such as supply type, position and terminal size.
Enter “Supply Data” per the following example.  en select the [ Accept ] button.
You will now confi gure the feeder circuit breaker.
Enter the “Circuit Breaker Data” per the following example.
You will also need lugs on the line side of the circuit breaker for the incoming power.
Enter the “Terminal Lug Data” per the following example.  en select the [ Accept ] button.
5
Step 4: Enter Supply Data
(co ntin ued )
You will now see a graphical representation of the busbar rack. MCS Star adds additional busbar supports if the rack length exceeds the allowable support spacing.  is is based upon the SCCR requirements and the size of the busbar. You will also notice that a bill of material is being created on the left hand side of the window for all the components required to assemble the system.
Note:  e center support was added because of the mechanical strength of the busbar. It is based upon the graph below.
 e force between conductors is proportional to the square of the instantaneous current. In case of a short circuit, which is protected by a short-circuit protective device (SCPD), the maximum force occurs at the peak let-through current of the protective SCPD (circuit breaker or fuse).  e higher the forces during a short-circuit are, the narrower the spacing between busbar supports needs to be. Observe that the peak value of the s-c current is plotted on the y-axis.  e maximum support distances for smaller cross-section conductors are given by pure mechanical considerations, i.e. static loads and plugging forces.
6
Step 5: Con guring Two Component Starters
 e next step is to confi gure two component starters. First, select the [ Product Library ] button in the main tool bar.
In the Product Library window, select the desired starter type. Since Motor 1 requires a DOL starter with no special overload requirements, you can select the Bulletin 103S and
select the [ OK ] button.
You will notice that some parameters may be pre-loaded.  e supply voltage is inherited from the busbar rack parameters. To save time, most other parameters are inherited from previous confi gurations. It is usually good practice to place the largest loads closest to the incoming feed. It will reduce the overall heating aff ect on the busbars.
7
Step 6: Enter Starter Parameters
Here you will enter the control voltage, the type of short-circuit coordination required, the SCCR required, horsepower or motor FLA, the starter style and the type of mounting module desired. Let’s choose a Type F starter which will also require the Type E spacing adapter.  e starter will be mounted on the MCS Iso busbar module.
Enter the “Starter Parameters” for Motor 1 per the following example.
Scrolling down the window, you can now enter the parameters for the contactor, circuit breaker, factory installed options and separate accessories.
Enter the “Control Circuit Data, Circuit Breaker Data and Options” per the following
example. When completed, select the [ Accept ] button.
8
Step 6: Enter Starter Parameters
(co ntin ued )
Once you select the [ Accept ] button below the catalog number, the starter drawing will be added to the rack in the graphical interface, as well as the product detail in the bill of material.
You could confi gure the next starter by repeating the same steps for Motor 2. Since this is a DOL starter, you would choose Bulletin 103S from the Product Library. After entering all the starter parameters for Motor 2, select the [ Accept ] button.  e starter is then added to the rack and BOM.
However, a faster method would be to “copy” the starter confi guration you just created and edit the starter parameters
Step 7: Copying Components
Since all the parameters for the next two starters (Motors 2 & 3) are very similar, you can copy the starter for Motor 1 and edit the horsepower requirements. To copy a starter:
Click on the starter with the mouse cursor
Press and hold the “Control” key and the left mouse button simultaneously
Drag and drop the copy of the starter to the left
Repeat this sequence one more time for Motor 3
9
Step 8: Editing Component Attributes
You can now edit the parameters of the copied starters to match the loads for Motors 2 and 3. To edit the starters:
Right-click on the starter for Motor 2 to show the popup menu
Select “Edit“ to open the confi gurator window or just double click on the starter you wish to edit
Adjust the contactor Hp rating and Frame Size of the circuit breaker according the load list
Horsepower = 10 Hp, Frame Size = 140M-C2E (C-Frame)
Select the “Accept” button
Repeat this sequence for the Motor 3 starter
Horsepower = 15 Hp, Frame Size = 140M-D8E (D-Frame)
For Motors 4 & 5, the application requires reversing starters. Repeat the process you used for
Motor 1, except confi gure Bul. 107S reversing starters, beginning with Step 5.
10
Loading...
+ 28 hidden pages