Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application,
Installation and Maintenance of Solid State Controls (publication SGI-1.1
available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com
) describes some important
differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of
uses for solid state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this
equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for
indirect or consequential damages resulting from the use or application of
this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with
any particular installation, Rockwell Automation, Inc. cannot assume
responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to
use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware
of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause
an explosion in a hazardous environment, which may lead to personal
injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
Identifies information that is critical for successful application and
understanding of the product.
Identifies information about practices or circumstances that can lead
to personal injury or death, property damage, or economic loss.
Attentions help you identify a hazard, avoid a hazard, and recognize
the consequence
SHOCK HAZARD
Labels may be located on or inside the equipment, for example, a drive
or motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be located on or inside the equipment, for example, a drive
or motor, to alert people that surfaces may be dangerous
temperatures.
Allen-Bradley, Rockwell Automation, ControlLogix, Powermonitor 3000, MicroLogix, PanelView 550, PanelBuilder32, and RSLinx
are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of Contents
Preface
General Information
Installation
Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . 3
Serial Base Unit with Serial HMI 1413-CAP-MS-PS A . . . . 62
Serial Base Unit with Ethernet HMI 1413-CAP-MS-PE A . . 62
Ethernet Base Unit with Ethernet HMI 1413-CAP-ME-PE A 62
Glossary
Index
Publication 1413-UM001C-EN-P - May 2006
Preface
Read this to familiarize yourself with the rest of the manual. It
provides information concerning:
• who should use this manual.
• where to go for more information.
Who Should Use This
Manual
Additional Resources
Use this manual if you are responsible for designing, installing,
programming, or troubleshooting the Capacitor Bank Controller
system.
You should have a basic understanding of electrical circuitry and
familiarity with relay logic. If you do not, obtain the proper training
before using this product.
Please refer to the following publications for additional information on
how to assemble, install, connect, operate and maintain your
capacitor bank controller.
The capacitor bank controller is a replacement for standard,
fixed-function capacitor controllers currently on the market. The
controller consists of standard, off-the-shelf, Allen-Bradley hardware
with the application ladder code necessary to perform power factor
correction. The controller is designed to provide the same base
functionality as a fixed-function capacitor bank controller. Also, you
may add additional code to the controller to fit its functionality to
special circumstances.
The capacitor bank controller is a pre-engineered control system
containing a MicroLogix 1500 controller, a standard data access
terminal (DAT), one or more Powermonitor 3000 modules, and an
optional additional human-machine interface (HMI). Pre-engineered
ladder logic code in the controller gathers real and reactive power
data from up to four power feeds (utility feeds and/or generators).
The logic operates on the data in standard engineering units of kVAR
and kW and acts to minimize imported and exported reactive power
by switching up to 10 steps of capacitance. This strategy controls
power factor while reducing the likelihood of voltage surge caused by
excessive kVAR export.
Functions
• Auto configure
• Manual configure
• Discharge timer on each step
• Selectable operating modes
– Manual operation
– Linear, last-in, first-out
– Balanced, level-out usage of capacitor steps
– Optimal, finds best match of capacitor step to system kVAR
needs
– Special, customer-defined
– %THD, Linear mode with a voltage %THD setpoint
5Publication 1413-UM001C-EN-P - May 2006
6 General Information
• Alarms
– Bad step, indicates blown fuse, capacitor failure
– Target power factor not achieved
– High / Low voltage
– %THD High
– Current unbalance
– Metering
• Powermonitor data concentrated into the MicroLogix 1500
controller
• Phase current, line voltage, frequency, real and reactive power,
power factor and THD
Options
• Up to three additional Powermonitor meters to aggregate up to
four total feeds
• PanelView 550 keypad HMI terminal with serial or Ethernet
communications
• Ethernet Powermonitor meters to produce power and energy
data via your local area network
Publication 1413-UM001C-EN-P - May 2006
Chapter
Installation
The capacitor bank controller system is supplied as a number of
components that you assemble, install, and connect in a suitable
enclosure.
2
System Components
All Configurations
KeyQuantityPart NumberDescription
111764-24BWAMicroLogix 1500 base unit with: 120/240V ac control power,
211764-LRPMicroLogix 1500 enhanced processor
311764-DATMicroLogix 1500 data access tool
411761-NET-AICAdvanced interface converter (used for PM comms)
511761-CBL-AC00MicroLogix controller to AIC+ cable, 9-pin D-shell to 9-pin D-shell,
611404-DMPowermonitor 3000 display unit with 3 m (9.84 ft) cable
Base Unit with Serial Meter 1413-CAP-MSA
KeyQuantityPart NumberDescription
711413-M5000 APowermonitor 3000-M5 meter with RS-485 communications port
The key number in the component lists are referenced in the
illustrations that follow.
(12) 24V dc inputs, and (12) relay outputs
45
cm (17.1 in.) long
including programmed MicroLogix 1500 8 k memory module with
real-time clock (1764-MM1RTC)
Base Unit with Ethernet Meter 1413-CAP-MEA
KeyQuantityPart NumberDescription
711413-M5ENT APowermonitor 3000-M5 meter with Ethernet communications port
including programmed MicroLogix 1500 8 k memory module with
real-time clock (1764-MM1RTC)
7Publication 1413-UM001C-EN-P - May 2006
8 Installation
Optional Serial HMI, Serial Meter 1413-CAP-MS-PSA
KeyQuantityPart NumberDescription
711413-M5000NM APowermonitor 3000-M5 meter with RS-485 communications port
including programmed memory module with real-time clock
(1764-MM1RTC) and programmed 2 MB flash memory card
(2711-NM13)
812711-NC21PanelView terminal to MicroLogix communication cable
912711-K5A16PanelView 550 operator terminal with RS-232 DF1 serial
communications
Optional Serial HMI, Ethernet Meter 1413-CAP-ME-PSA
KeyQuantityPart NumberDescription
711413-M5ENTNM APowermonitor 3000-M5 meter with RS-485 and Ethernet
communications ports including programmed memory module with
real-time clock (1764-MM1RTC) and programmed 2 MB flash
memory card (2711-NM13)
812711-NC21PanelView terminal to MicroLogix controller communication cable
912711-K5A16PanelView 550 operator terminal with RS-232 DF1 serial
communications
Optional Ethernet HMI 1413-CAP-ME-PEA
KeyQuantityPart NumberDescription
711413-M5ENTNM APowermonitor 3000-M5 meter with RS-485 and Ethernet
communications ports including programmed memory module with
real-time clock (1764-MM1RTC) and programmed 2 MB flash
memory card (2711-NM13)
1011761-NET-ENIWMicroLogix Ethernet interface module with Web interface
1111761-CBL-AM00MicroLogix controller to AIC+ cable, 8-pin DIN to 8-Pin DIN, 45 cm
(17.1 in.) long
1213.05 m (10 ft) CAT5 Ethernet crossover cable
1312711-K5A20PanelView 550 operator terminal with Ethernet/IP communications
Optional Additional Powermonitor Meters
Publication 1413-UM001C-EN-P - May 2006
The controller is designed to operate with up to three additional
Powermonitor meters. Additional Powermonitor meters must be
ordered separately. Please contact your local Allen-Bradley distributor
for information.
Installation 9
System Architecture
This section illustrates the base system with the serial and Ethernet
options.
Base System with Serial Options
4
2
F10
7 8 9
4 5 6
1 2 3
. 0 -
<--
^
<>
v
9
PanelView 550
<-------'
8
3
Allen-Bra dle y
F1F6F2F7F3F8F4F9F5
5
1
Optional Serial HMI
6
25.04M
WATT
Powermonitor 3000Allen-Bradley
L1
25.04M
WATT
Powermonitor 3000Allen-Bradley
L1
25.04M
WATT
Powermonitor 3000Allen-Bradley
L1
25.04M
WATT
Powermonitor 3000Allen-Bradley
L1
7
Allen-Bradley Powermonitor 3000Allen-Bradley P owermonitor 3000Allen-Bradley Powermonitor 3000Allen-Bradley Powermonitor 3000
Optional Additional Powermonitor Meters
Publication 1413-UM001C-EN-P - May 2006
10 Installation
Base System with Ethernet Options
4
2
3
11
10
13
F10
7 8 9
4 5 6
1 2 3
. 0 -
<--
^
<>
v
PanelView 550
<-------'
Allen-Bradley
F1F6F2F7F3F8F4F9F5
5
1
12
Optional Ethernet HMI
Ethernet Local Area Network by Customer
6
25.04M
WATT
Powermonitor 3000Allen-Bradley
L1
25.04M
WATT
Powermonitor 3000Allen-Bradley
L1
25.04M
WATT
Powermonitor 3000Allen-Bradley
L1
25.04M
WATT
Powermonitor 3000Alle n-Bradley
L1
7
Allen-Bradley Po wermonit or 3000Allen-Bradley Powermonitor 3000Allen-Bradley Powermonitor 3000Allen-Bradley Powermonitor 3000
Publication 1413-UM001C-EN-P - May 2006
Optional Additional Powermonitor Meters
TIP
Ethernet crossover cable (12) is used if there is no connection to
a local area network.
Installation 11
Assemble, Mount, and
Connect Your Controller
This section describes how to mount the MicroLogix 1500 controller
and connect it to an AIC+ interface and PanelView module for use
with the capacitor bank controller.
MicroLogix 1500 Controller (All Configurations)
TIP
1. Mount the MicroLogix 1500 base unit (1).
Please refer to Publication 1746-UM001, Chapter 2, for
information on performing these tasks.
Mounting Template
2. Install the MicroLogix 1500 processor module (2).
Publication 1413-UM001C-EN-P - May 2006
12 Installation
3. Install the MicroLogix memory module (7a).
This module may be found packaged with the Powermonitor
meter (7).
4. Install the data access terminal (3).
Publication 1413-UM001C-EN-P - May 2006
5. Connect the MicroLogix 1500 controller to 120V ac control
power, earth ground, capacitor step contactors (or interposing
relays as required), and an alarm circuit as shown in the wiring
diagram.
Wire the Controller
Fault-protection relays can be used to immediately discharge all or
specific capacitor steps during a fault occurrence. Input 0 is wired to a
normally closed fault-protection relay and discharges all capacitor
steps during a fault occurrence (low-state condition). Inputs 1… 10
are wired to normally closed fault-protection relays, and discharges its
respective capacitor step during a fault occurrence (low-state
condition). If fault protection is not being used for a specific capacitor
step, then that respective input is wired closed using the controller
supplied 24V dc power.
A normally-open momentary pushbutton is wired to Input 11. This
pushbutton is used to reset the controller after a fault occurrence.
Fault Relay Power
Installation 13
Output 0 is used as an alarm relay and is wired normally open to an
external alarm indicator. Output 1…10 is wired to normally-open
contactors for each respective capacitor step.
Controller Wiring Diagram
Capacitor Step Contractors or Interposing Relays
Inputs
1764-24BWA
Outputs
24V dc
to AIC+
85-265
VAC
L1
120V ac
Control
Power
Isolated Alarm Output
DC
POWER
OUT
L2
VDC 0
Ground
Capacitor Step
Control Power
VAC
COM
VDC 1
VAC
Master Fault Relay
Group 0
DC
COM 0
I / 0
VAC
VDC 2
O / 1O / 0 O / 2
Group 1
1
Fault Relay 2
Fault Relay 1
I / 1
I / 2
VAC
VDC 3
Group 2
2
Fault Relay 3
I / 3
DC
COM 1
VAC
VDC 4
O / 3
Group 3
3
Fault Relay 4
I / 4
I / 5
O / 5
O / 4
Group 4
4
Fault Relay 6
Fault Relay 5
Fault Relay 7
Group 1
I / 6
O / 6O / 9
Group 2
DC
COM 2
I / 7
O / 7O / 8
VAC
VDC 5
Group 5
5
6
Fault Relay 8
I / 9
I / 8
7
Fault Relay 9
Fault Relay 10
I / 11
I / 10
O / 10
O / 11
8
Reset
24BWA
24BWA
Spare Output
9
10
Capacitor Step Contractors or Interposing Relays
Publication 1413-UM001C-EN-P - May 2006
14 Installation
AIC + Interface Converter (All Configurations)
1. Mount the AIC+ communications converter (4) within 45 cm
(18 in.) of the left edge of the MicroLogix 1500 controller.
5
4
1
2. Connect the DB9 to DB9 cable (5) between Port 1 of the AIC+
(4) and Channel 1 of the MicroLogix 1500 controller (1).
3. Connect a source of 24V dc to the control power terminals on
the bottom of the AIC+.
The 24V dc power may be obtained from the DC Power Out
terminals on the MicroLogix 1500 controller.
4. Verify that the DC Source switch is in the External position and
that the Baud Rate selector is set to ‘Auto’.
Publication 1413-UM001C-EN-P - May 2006
Powermonitor Meter (All Configurations)
1. Mount the Powermonitor meter (7) within 1200 m (4000 ft) of
the AIC+ communications converter (4).
2. Use a 2-conductor shielded cable, that you provide, to connect
the AIC+ RS-485 port to the Powermonitor RS-485 port.
Installation 15
AIC+
24 V Power
Supply
Blue
CLR
SHLD
Powermonitor 3000 Device
SHLD
RS-485
Red
Black
_
+
AIC+Powermonitor 3000 Meter
A-
B+
SHLDSHLD
Blue
CLR
SHLD
3. Connect any additional, optional Powermonitor meters RS-485
ports in a daisy-chain fashion, + to +, - to -, Shld to Shld.
In certain cases, terminating resistors may improve
communications robustness.
Refer to publication 1404-IN007 for more information.
4. Connect the Powermonitor meter to the power circuit, control
power, and earth ground.
See the instructions found in publication 1404-IN007.
Publication 1413-UM001C-EN-P - May 2006
16 Installation
PanelView 550 Serial Terminal (Serial HMI options)
1. Mount the PanelView 550 HMI terminal in a suitable cutout
within 5 m (16 ft) of the MicroLogix controller.
Refer to publication 2711-IN009 for detailed installation
instructions.
Mounting Studs
(3 Top / 3 Bottom)
Protective Installation Label
Self-locking Nuts
(6 used, 8 provided)
2. Install the memory card and retainer.
Memory Card
Retainer
Retainer Base
Base Mounting Screws
Publication 1413-UM001C-EN-P - May 2006
3. Connect 120V ac control power and earth ground.
Installation 17
Power Terminal Block (fixed)
120/240V ac, 3 Wire,
U.S. Color Code
L1
L2
GNDGND
Green
Black (Line)
White
(Neutral)
Green
(Earth Ground)
(Earth Ground )
To P ower Sou rc e
120/240V ac,
3 Wire, European
Harmonized Color Code
L1
L2
Brown (Line)
Blue
(Neutral)
Green/Yellow
(Protective Earth)
To Power Source
4. Connect the communications cable between the MicroLogix
1500 controller Channel 0 and the PanelView 550 terminal serial
port.
1. Mount the PanelView 550 HMI terminal in a suitable cutout
within 100 m (328 ft) of the MicroLogix controller.
Refer to publication 2711-IN009 for detailed installation
instructions.
Mounting Studs
(3 Top / 3 Bottom)
Protective Installation Label
Self-locking Nuts
(6 used, 8 provided)
2. Install the memory card (7b, packed with the Powermonitor
meter) and retainer.
Memory Card
Retainer
Retainer Base
Base Mounting Screws
Publication 1413-UM001C-EN-P - May 2006
3. Connect 120V ac control power and earth ground.
Installation 19
Power Terminal Block (fixed)
120/240V ac, 3 Wire,
U.S. Color Code
L1
L2
GNDGND
Green
Black (Line)
White
(Neutral)
Green
(Earth Ground)
(Earth Ground )
To P owe r S our ce
120/240V ac,
3 Wire, European
Harmonized Color Code
L1
L2
Brown (Line)
Blue
(Neutral)
Green/Yellow
(Protective Earth)
To Power Source
4. Install the Ethernet interface module (9) within 45 cm (18 in.) of
the Channel 0 connector on the MicroLogix 1500 controller (1).
To Ethernet LAN
ETHERNET
RS232
FAULT
NET
TX/RX
TX/RX
IP
PWR
CABLE
EXTERNAL
5. Verify that the DC Source switch on the Ethernet interface
module is in the Cable position.
6. Connect the cable (11) between Channel 0 of the MicroLogix
1500 controller and the Ethernet interface module.
7. Connect the PanelView 550 terminal to the Ethernet interface
module using the Ethernet crossover cable (12) if the system will
not be connected to a local area network.
8. Connect both the PanelView 550 terminal and the Ethernet
interface module to the Ethernet local area network via a
suitable hub or switch using user-provided CAT5 Ethernet cables
if the system will be connected to a local area network.
Publication 1413-UM001C-EN-P - May 2006
20 Installation
Configuration
The capacitor bank controller base unit has been set up to require
minimal out-of-box configuration.
The base system has default communications settings. Certain
circumstances and options require additional configuration of
communications, which may include the use of programming software
not included with the controller.
You are required to configure the Powermonitor meters to coordinate
them to the power circuit in the base unit and all options.
Configuration of the Powermonitor meter is performed using the
display module.
The controller requires configuration to coordinate it to the number
and size of steps that exist in the capacitor bank being controlled, as
well as the desired operating mode and other selections. Use the data
access terminal (DAT) or the optional PanelView 550 operator
terminal to configure the controller.
ATTENTION
Do not operate the capacitor bank controller without first
configuring it to suit the controlled capacitor bank and system
options. Unpredictable operation, including undesirable power
system effects, may result.
Communications
Configuration
Publication 1413-UM001C-EN-P - May 2006
The following sections provide information on configuring
communications for the components.
Base Unit
Communications settings are factory configured. The MicroLogix 1500
controller settings are contained in the EEPROM memory module.
Powermonitor meter settings are stored in onboard non-volatile
memory (NVRAM). Configuration settings are listed below.
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.