Rockwell Automation 140U Q User Manual

Q and M-Frame Circuit Breakers
Instruction Leaflet for Electronic RMS Trip Unit Installation and Operation
Table
of
Contents
Description Page
1
.O
1.1
UL Listed Devices
2.0
Installation
3.0
Preparation (All Trip Units)
3.1
4-Pole Trip Unit Installation
3.2
Ground Fault Trip Unit Installation
3.3
General
3.3.1
Installation
3.3.2
3-Pole (Non-Ground Fault) Trip Unit Installation
3.4
Final Installation Instructions (All Trip Units)
3.5
Principle of Operation
4.0
General
4.1
Overload Trip
4.2
Short Delay/lnstantaneous Trip
4.3
Ground Fault Protection
4.4
Protection Settings
5.0
General
5.1
Short Delay Pick-up Settings
5.2
Short Delay Time Settings
5.3
Instantaneous Pickup Setting
5.4
Ground Fault Pick-up Setting
5.5
Ground Fault Time Settings
5.6
Testing
6.0
Functional Field Testing
6.1
Performance Testing for Ground Fault Trip Units
6.2
6.2.1
Code Requirements Standards Requirements
6.2.2
6.2.3
General Test Instructions
7.0
Rating Plug References
8.0
Q-Frame Molded Case
8.1
Circuit Breakers Internal Accessories
8.2
..............................................................
.............................................................
..................................................................
.............................................................
..................................................................
..................................................................
...................................................................
..........................................................
..........................................................
...............................................
..................................................
.....................................
.....................................
..........................
.....
...........
............................................
.........................................................
..............................
.........................................
.................................................
.................................
.....................................
................................
.................................
...................................
.........................................
-
....
...............................................
.......................................
.......................................
...................................................
............................................
12 12
12 12
Bul. 140U
PRESENT BEFORE PROCEEDING AND ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY PROCEDURES.
1
ALLEN
1
MISAPPLICATION
2
PRODUCTS.
2 2
The user is cautioned to observe all recommendations,
2
warnings, and cautions relating to the safety of personnel
3
and equipment as well as all general and local health and
3
safety laws, codes, and procedures.
3
The recommendations and information contained herein
5
are based on Allen
6
but should not be considered to be all
6
ing every application or circumstance which may arise. If
7
any questions arise, contact Allen-Bradley for further
7
information or instructions.
7 7 7 7 7 7 7 7
8 8 8 8 8 9 9
Fig.
1
-BRADLEY
1
Electronic RMS Trip Unit M Frame Circuit Breaker
.O
GENERAL INFORMATION
IS
NOT LIABLE FOR THE
OR MISINSTALLATION
-Bradley experience and judgement,
-
for
OF ITS
inclusive or cover
3-Pole Q-Frame &
-
A
A
DEATH, SEVERE PERSONAL INJURY,
SUBSTANTIAL PROPERTY DAMAGE CAN RESULT
FROM CONTACT WITH ENERGIZED EQUIPMENT. DO NOT
AlTEMPTTO INSTALL
MAINTENANCE ON EQUIPMENT WHILE IT ENERGIZED. ALWAYS VERIFY THAT NO VOLTAGE
40752-072(2) Effective
WARNING
OR
6/02
OR
PERFORM
IS
IS
1.1
Protection
The Electronic RMS, illustrated in Figure tronic trip unit that incorporates a microprocessor-based custom application specific integrated circuit design for
use with Q
Circuit Breakers. The Electronic RMS Trip Unit
sensing for proper correlation with thermal characteristics of conductors and equipment. Interchangeable rating plugs
-
Frame and M Frame Molded Case
provides true RMS current
1,
is an elec
-
Page
2
are provided to establish the continuous current rating of each circuit breaker.
The Electronic RMS Trip Unit is completely self tained and when the circuit breaker is closed, requires no external power to operate its protection systems. It operates from current signal levels and control power derived through current sensors integrally mounted in the trip unit.
Electronic applications only. For DC applications, a thermal trip unit should be used.
The Electronic RMS Trip Unit is available in 4 different types, (see Table 1 delay time function (adjusted by changing the rating plug), and may be equipped with a maximum of two phase and two ground (time application requirements. The types of adjustments available for each model include the following:
Adjustment
1)
Short Delay Pick-up
2) Short Delay Pick-up/Short DelayTime
3)
Short Delay Pick-Up/Ground Fault
Pick-up/Ground Fault Time
2.0 UL LISTED DEVICES
The Electronic RMS Trip Unit is listed in accordance with Underwriters Laboratories, Inc. Standard UL489 and satisfies the applicable requirements of the International Electrotechnical Commission (IEC) recommendations for molded case circuit breakers.
Fig.
RMS Trip Units are suitable for 50/60
-
1). Each trip unit contains a fixed long
-
current) adjustments to meet specific
Retaining Screw
KPlaces)\
-
2
-
\Trip Unit
Preliminary Alignment Sensor
-
Tm
LS
LSI
LSG
Current
Sensor
L
of
Trip Unit and Current
-
-
Retaining
Screw
Secondary Winding Connector
con
-
Hz
AC
magnetic
3
.O
INSTAL LATlO N
3.1 Preparation
The installation procedure consists of inspecting and installing the trip unit and rating plug. To install the trip unit, perform the following steps.
Note: If required, internal accessory installation should be done before the circuit breaker is mounted and connected. Refer to individual accessory instruc tion leaflets.
Make sure that the trip unit is suitable for the intended installation by comparing nameplate data with any existing equipment and system requirements. Inspect the trip unit for completeness, and check for damage before installing it in the circuit breaker frame.
Note:Trip unit center retaining screw is captive in the
trip unit conductor; the remaining retaining screws are supplied with the frame.
Remove circuit breaker pan To continue installation, proceed to the section applicable
to the trip unit being installed:
UnitTvpe Section
Trip
4
-
pole Type Trip Unit 3.2
3
-
pole Ground Fault Trip Unit
3
-
pole Non-Ground Fault Trip Unit
4-PoleTrip Unit Installation
3.2
Remove the three screws for the left fourth pole contact bases (Fig. 3) from the hardware bag.
Place the trip unit and fourth pole current sensor side by side on a flat surface. (See Fig. 2)
Remove the CAUTION tag from the current sensor secondary winding leads.
Note: Secondary winding connector is not polarized.
Plug the current sensor secondary winding connector into the receptacle in the side of the trip unit. Either polarity is acceptable.
Note:The two trip unit outer retaining screws and
fourth pole sensor retaining screw may be placed in the trip unit conductor holes at this time. If preferred, the 5/16 inch hexagonal position the screws when the trip unit is in the base.
Position trip unit and fourth pole current sensor in base. Make sure latch bracket pin is properly seated in slots in side plates (see Fig. 4). If necessary, push circuit breaker handle towards the closed position to help seat trip unit.
(AllTrip Units)
-
head cover screws, and cover.
-
head wrench may be used to
3.3
3.4
-
and right-pole and
-
40752-072(2) Effective 6/02
Page
3
-
Contact
Base
-
Load
Copper
Fig.
3
Contact Bases and Load Copper
LINE
END
Side Plate
Trigger
Trip
Unit and Current Sensor
Retaining Screws
Fourth
Pnh
. -.
-
Current Sensor
Fig.
Unit
4
Trip Unit Installed in Circuit Breaker
a
END
LOAD
CAUTION
DO NOT EXCEED A TORQUE OF 12 LB-FT (16.27 N.M). EXCESSIVE TORQUING WILL SHEAR SCREWS.
FAILURE TO APPLY THE REQUIRED TORQUE
MAY LEAD TO EXCESSIVE HEATING AND CAUSE NUISANCE TRIPPING
OFTHE CIRCUIT BREAKER.
Screw in and tighten three trip unit retaining screws
(center first) and the screw for the fourth pole current
sensor.Torque to 12 Ib-ft (16.27 N.m) (see Fig. 4).
-
Finish installation of the 4
pole Trip Unit by following the
instructions in Section 3.5.
3.3 Ground
FaultTrip Unit Installation
3.3.1 General Ground fault trip units are supplied from the factory with a
wire harness with pigtail lead connections for a neutral current sensor (white and grey wires) and a ground fault alarm relay (yellow and green wires). A neutral current sensor is provided with each trip unit, and the ground fault alarm relay is ordered and shipped separately if required.
If the alarm relay is not required, the green and yellow leads should be cut off before the trip unit is installed in
the breaker.
Electroni
c RMS
Ground Fault Trip Units detect ground fault currents through Residual Sensing. They are not designed to use source ground or zero sequence ground fault sensing methods. If the system neutral is grounded, but no phase to neutral loads are used, the neutral current sensor is not necessary. In that case, the white and grey
leads on the trip unit should be cut off before installation. If the system neutral is grounded and phase to neutral
loads are used, then the neutral current sensor (see Fig.
5)
must be used. It should be connected to the breaker
according to the diagram in Fig. 6. It has the same turns
ratio as the phase current sensors in the trip unit.
Note: The polarity of the sensor connections is
critical. Always observe the polarity markings on the
installation drawings. The polarity markings are identified as white dots on the
transformer.To insure
correct ground fault equipment performance, conduct field tests to comply with National Electric Code requirements under article
230-95(C). See Section 6.2
for testing instructions.
The optional “Internal Accessories” listed in Section 8.2 are available for installation in a Electronic RMS
Fault Trip
Unit.These items, if required, must be ordered
Ground
separately.
3.3.2 Installation
Plug the wire harness supplied for the neutral current sensor and ground fault alarm relay (white, grey, yellow and green wires) into the connector located in the right pole of the trip unit. With the correct polarity the harness should snap into place. Do not force the harness into the connector with the wrong polarity.
Remove trip unit outer pole screws and red plastic washers from the breaker frame. Discard red plastic washers (fig. 7). For the M
-
frame, also remove the load
end trip unit mounting screws from the frame
(fig.
7a).
40752-072(2) Effective
6/02
Page
4
Fig.
Fig.
5
.Aux~Iiary
6
switch
shown m the
"
Breaker
SOURCE
LOAD
Canlacis
Open''
pmilmn
Fig. 7a
M-Frame
Trip
Unit Installation
-
COVER
TORQUE
9
9
SCREWS
20-22
-1b
40752-072(2) Effective 6/02
Lefl
Contact Base
Right Contact Base
Page
Position trip unit in base. Make sure latch bracket pin is properly seated in slots in side plates (see Fig. 8). If
necessary, move latch toward load end of circuit breaker to seat trip unit.
Screw in and tighten three trip unit retaining screws
(centerfirst).Torque to 12 Ib-ft (16.27 N.m) (see Fig. 8).
A
A
DO NOT EXCEED A TORQUE OF 12 LB-FT (16.27 n.m.) EXCESSIVE TORQUING WILL SHEAR SCREWS.
FAILURE TO APPLY THE REQUIRED TORQUE MAY
LEADTO EXCESSIVE HEATING AND CAUSE
NUISANCE TRIPPING OF THE CIRCUIT BREAKER.
For an M-Frame, also screw in and torque the load end screws to 6
-
8 Ib-ft. (8.14-10.85 N.m.).
CAUTION
5
Fig.
7
Left- and Right-Pole Contact Bases
Circuit Latch Breaker
Handle
Side Trip Side
Plate Unit Plate
Fig.
8
Trip Unit Installed in Circuit Breaker
Note: The two placed preferred, the 5/16 inch hexagonal be used the base.
in
trip
unit
the trip
to
unit
position the screws when the
Retaining Screws
outer retaining screws may be
conductor holes at
this
time. If
-
head wrench may
trip
unit
is
3.4 3-Pole (Non-Ground FauIt)Trip Unit Installation
Remove trip unit outer pole screws and red plastic washers from the breaker frame. Discard red plastic washers (fig. 7). For the M end trip unit mounting screws from the frame
(fig.
7a).
NOTE: The two
be placed
If preferred, the 5/16 inch hexagonal
be used the base.
Position trip unit in base. Make sure latch bracket pin is properly seated in slots in side plates (see Fig. 8). If
necessary, move latch toward load end of circuit breaker to seat trip unit.
Screw in and tighten three trip unit retaining screws
(centerfirst).Torque to 12 Ib-ft (16.27 N.m) (see Fig. 8).
in
the trip
to
position the screws when the
A
DO NOT EXCEED A TORQUE OF 12 LB (16.27 SCREWS.
FAILURE TO APPLY THE REQUIRED TORQUE MAY
in
LEADTO EXCESSIVE HEATING AND CAUSE
N.M). EXCESSIVE TORQUING WILL SHEAR
NUISANCE TRIPPING OF THE CIRCUIT BREAKER.
-F
rame, also remove the load
trip
unit
outer retaining screws may
unit
conductor holes at
CAUTION
-
head wrench may
trip
-
FT
this
unit
time.
is
in
40752-072(2) Effective
6/02
Page
6
For an M-Frame, also screw in and torque the load end screws to 6
3.5
Final Installation Instructions (All Trip Units)
Install accessory(ies), instruction leaflet listed in Section 8.2. Where accessories are not required, install protective barriers supplied with the trip unit in accessory retaining slots in left hand poles of trip unit and in fourth pole current sensor applicable.
Make sure interphase barriers and sliding handle barrier are in place.
Install circuit breaker covers and pan shown in Fig.
THE RATING PLUG MECHANICALLY INTERLOCKS WITH THE TRIP UNIT. IF RATING PLUG CORRECTLY INSTALLED, THE CIRCUIT BREAKER CANNOT BE RESET
POSITION
-
8 Ib-ft. (8.14-10.85 N.m.)
if
required, using the appropriate
9.
a
CAUTION
OR
PLACED IN THE ON
-
and right
-
head screws as
IS
NOT
-
if
until the arrow points to ENGAGED. If an adjustable rating plug is used, four continuous current settings are possible. Set the switch marked A, B, C, D to the current rating desired.
Note: The reverse procedure rating plug. Turn the Push remove breaker to button and gently pull. A small screwdriver placed under the left edge of the rating plug will assist in removal.
Reset circuit breaker by moving handle to the reset position. Move handle to the handle should remain at the
Press Push tripping of the circuit breaker.
position.This action will cause the circuit
trip.Then grasp the lip of the Push-to-Trip
-to-
Trip button (in rating plug) to check manual
is
used to remove the
-to-
Trip button to the
ON
position. Circuit breaker
ON
position.
Torque 20-22 IN-LB
Fourth
9
Fig.
Note: Before attempting to install the rating plug, the arrow must be pointing toward the REMOVE can be done with a small screwdriver.
Install rating plug. Position the rating plug as shown in Fig.
10. Insert the rating plug in the trip plunger must align correctly with the matching receptacles and slot in the trip unit. After the rating plug is pressed into position, depress the Push screwdriver and turn it clockwise one quarter of a turn
Cover Screw
in
the Push-to-Trip button portion of the plug
Installation Positions
position.This
unit.The pins and
-to-
Trip button with a small
Trip
Unit
Fig.
10
Installing Rating Plug
4.0
PRINCIPLE OF OPERATION
In open air at 40"C, an Q-Frame circuit breaker with an
Electronic RMS
up to 800 amperes without exceeding a 50°C rise at the terminals. The calibration of the trip unit is insensitive to ambient temperatures over a range of However, the trip unit contains thermal temperature protective circuitry that initiates a trip operation for self protection if the internal ambient temperature at the printed circuit board (PCB) reaches approximately 100°C. This may occur for open air temperatures above 40°C with circuit breaker currents near full load.
Trip Unit installed will carry continuously
-20"
to +55"C.
-
40752-072 (2) Effective
6/02
Page
7
For ambient conditions above 40°C and where the
maximum ampere rating plug has been installed, derating of the circuit breaker frame should be considered to avoid exceeding a safe terminal temperature operating range. Consult A
4.1 General
llen-Bradley for recommendations.
The Electronic RMS Trip Unit provides a tripping signal to the flux transfer shunt trip when current and time delay settings are exceeded. This is accomplished by employing the Allen
-Bradley custom designed integrated circuit
SpreTMchip, which includes a microcomputer to perform
its numeric and logic functions.
In the Electronic RMS
Trip Unit, all required sensing and tripping power to operate its protection function is derived from the current sensors in the circuit breaker. The secondary currents from these sensors provide the correct input information for the protection functions, as well as tripping power, whenever the circuit breaker is carrying current. These current signals develop analog voltages across the appropriate calibrating resistors.
The microcomputer, in cyclic fashion, repeatedly scans the voltage values across each calibrating resistor and enters these values into memory. These data are used to calculate true RMS current values, which are then repeat edly compared with the protection function settings and other operating data stored in the memory. The software program then determines whether to initiate protection functions, including tripping the breaker through the flux transfer shunt trip device in the circuit breaker.
4.2 Overload Trip:
In accordance with standards require
ments, the trip unit initiates a trip of the circuit breaker within two hours for an overload of 135 percent, and will trip in less time for higher overload currents.
A
“Thermal Memory” effect prevents the breaker from
being re
-
energized immediately after an overload.
A
“cooling off” period of up to 5 minutes is required, which allows time for cabling to cool off.
4.3 Short Delay/lnstantaneous Trip:
conditions that exceed the short delay pick
For short circuit
-
up settings,
the trip unit initiates a trip after a delay prescribed by the
I2t ramp function for trip units with catalog number suffixes
LS, LSG.
A
flat response time delay action
is provided by trip units with catalog number suffixes LSI,
(I)
and LSIG unless the instantaneous
setting
is selected.
4.4 Ground Fault Protection:
fault pick
-
up and time delay settings shown in Table 1-2
When selected, ground
allow selective ground fault coordination with other circuit protection devices.
5.0
PROTECTION SETTINGS
5.1 General
Prior to placing any circuit breaker in operation, each trip
unit protection setting must be set to the values specified by the engineer responsible for the installation. The available settings along with the effect of changing the settings are illustrated in Figures 12
-
1 to 12-3.
The installed rating plug establishes the maximum
(I,)
continuous current rating
of the circuit breaker. Short
delay current settings are defined in multiples of ln. One to four time and pick-up adjustment settings are
available depending on the particular trip unit purchased.
A
rotary switch is provided for each setting. The rotary
switch is adjusted using a small flatblade screwdriver
(Figure 11).
5.2 Short Delay Pick-up Setting
Seven settings are available that range from 2 to shown in Figure 12
Electronic RMS
5.3 Short DelayTime Settings
-
1. This feature is included on all
Trip Units.
For catalog number LS and LSG the short time delay is an
-
ramp configuration with the actual time delay a
function of the trip current involved.
For catalog number LSI and LSIG the short time delay
is a flat response. Four settings (I,.1, .2, .3 second)
are available (see Figure 12-2). The "I" setting
-
gives a trip response with no intentional delay
(Instantaneous).
5.4 Instantaneous Pickup Setting
For catalog number LSI and LSIG Instantaneous Pickup
is achieved by setting Short Delay Time to "I"
(Instantaneous.) Short Delay Pickup (see paragraph 5.2)
then becomes Instanta
5.5
Ground Fault Pick-up Setting
Five settings ranging from 1 through
(see Figure 12
-
3) and correspond to the fixed ampere
neous Pickup.
5 (xlG)
are available
values listed on the trip unit nameplate and in Table 1.2.
Note: These ampere values are always the same no matter what rating plug is installed in the circuit breaker.
8
, .
(I,)
as
40752-072(2) Effective 6/02
5.6 Ground FaultTime Settings
The ground fault time delay is a flat response with four settings
I
setting gives a trip response with no intentional delay
(I,
.15, .3,
.5
second) available (Figure 12-3).The
(Instantaneous). This option is available on Catalog Nos.
LSG and LSIG.
Page
8
6.OTESTING
6.1 Functional Field Testing
A test receptacle is built into each trip unit to allow use of the STK2 Test Kit. The Test Kit performs a test of the Long Delay, Short Delay and Ground Fault functions.
Performance Testing for Ground Fault Trip Units
6.2
6.2.1 Code Requirements
The National Electrical Code under Article 230-95-C requires that any ground
-
fault protection system be performance tested when first installed. The test shall be conducted in accordance with approved instructions
Fig.
I\
Remove-
11
Adjustment Switches and Test Points
Short
Delay Pickup
(Multiples
I
3@7
of
5
Rated
Current
I
I
\
LTest
Jacks
I
Ih
1
Ilh
W
E
+
1,)
5
Short Delay Pick-up (Multiples
of
Rated
Cu
irrent)
Fig.
12-1
Short Delay Trip Current Adjustment and Curve Details
40752-072(2) Effective
6/02
Current
Fig.
Current
12-2
Short Delay Trip Current and Short Delay Trip Time Adjustment and Curve Details
Page
9
300\(!&
I
’*+
I
L
t
L
Time
Ms
Current
Fig. 12-3 Ground Fault Trip Current, and Ground Fault Trip
Time Adjustments and Curve Details
provided with the equipment. A written record of this test shall be made and shall be available to the authority
having inspection jurisdiction.
6.2.2 Standards Requirements
As
a follow-up to the basic performance requirements
stipulated by the
1053 requires that certain minimum instructions must accompany each ground fault protection system. These following statements plus a copy of the test record form
illustrated in Fig. 16 are shipped with each Elect RMS
Trip Unit.
6.2.3 General Test Instructions
The interconnected system shall be evaluated in accor dance with the equipment assembler’s detailed instruc tions by qualified personnel.
The polarity of the neutral sensor connections (if used)
must agree with equipment assembler’s detailed instruc tions to avoid improper operations following apparently correct simulated test operations. Where a question exists, consult the specifying engineer and/or equipment assembler.
The grounding points of the system shall be verified to determine that ground paths do not exist that would bypass the sensors. The use of high
resistance bridges may be used.
N.E.C.
as stated above, UL Standard
ronic
-
voltage testers and
No.
-
-
-
8
.-
i
+
2x-Ex
2x-8x 2x.8~ 2x-Ex
See
Fig.
2-7
and Continuation of Short Time Instantaneous Portions of Curves
Fig.
Current
Rating Plug Setting (Amperes)
2-8
for
Fig. 13 Optional Adjustable Ampere Setting Rating
Plug Used in
THERE
BURN WHENEVER WORKING IN ELECTRICAL EQUIPMENT. ALWAYSTURN OFF POWER SUPPLYING BREAKER BEFORE
CONDUCTING TESTS.
Note: Since the Electronic RMS their operating power from the phase currents, and not from the neutral current, passing current through the neutral sensor only will not properly test the ground fault feature.
Using a low voltage (0-24 volt), high current, apply a test current of 125% of the Electronic RMS Ground of the circuit breaker, as shown in Fig. 14 cause the breaker to trip in less than 1 second, and alarm indicator is supplied, it should operate. Reset the breaker and the alarm indicator. Repeat the test on the other two phases.
IS
A HAZARD OF ELECTRICAL SHOCK
FaultTrip Unit pick-up setting through one phase
Electronic RMS
a
WARNING
Trip Unit
OR
OR
AROUND
Trip Units derive
AC
source,
-
1 .This should
if
an
40752-072(2) Effective
6/02
69
Source
1
Load Current-Lim
Resisto!
(if required1
voltage
i
iring
Source
Load
Nl
Current Limiting Resistor (if
required)
Page
10
Fig. 14-1 Connections for Ground Fault
Voltage
Source
Current Limiting Resistor
(if
required)
Trip
Test
Fig. 14-2 Connections for Ground Fault No-Trip Test, with
a Four
-
Wire System
Fig. 15 Typical Rating Plug
Fig. 14-3 Connections for Ground Fault No-Trip Test, with
a Three
40752-072(2) Effective
-
Wire System
6/02
Page
11
GROUND FAULT
Ground Fault Test Record should be Retained Installation in order to be available
Test Date
Circuit Breaker Number
to
TEST
RECORD FORM
by
the Authority having Jurisdiction.
Those in Charge
Results
of
the Building's Electrical
Tested By:
Fig.
16
Typical Performance Test Record Form
40752-072(2) Effective
6/02
Page
12
If the system is a 4-wire system with a neutral current sensor, apply the same current as described above through one phase of the breaker, returning through the neutral sensor, as shown in Fig. not trip, and the alarm indicator,
operate. Repeat the test on the other two phases.
If the system is a 3 sensor, apply the same current as described above through any two phases of the breaker, with the connec tions exactly as shown in Fig. 14-3. The breaker should not trip, and the alarm indicator, operate. Repeat the test using the other two combinations of breaker phases.
FIELDTESTING SHOULD BE USED FOR FUNCTIONALTESTING AND NOT FIELD
CALIBRATION OF THE ELECTRONIC RMS GROUND
FAULTTRIP UNIT.
ANY TEMPORARY CONNECTION MADE PURPOSE OF CONDUCTING TESTS SHOULD BE RESTOREDTO PROPER OPERATING CONDITIONS BEFORE
The results of the test are to be recorded on the test form provided with the equipment.
7.0
The rating plug, as illustrated in Figure 15, is used to establish the continuous ampere rating of the related circuit breaker.
RETURNINGTHE BREAKERTO SERVICE.
RATING PLUG
-
wire system with no neutral current
a
CAUTION
14-2.The breaker should
if
supplied, should not
-
if
supplied, should not
FORTHE
For adjustable rating plugs (Table 1 current carrying conductors used with the breaker must be sized to correspond with the maximum setting of the rating plug, in accordance with National Electric Code requirements.
The Long Delay protection function of the trip unit is set at the rating plug value neous protection functions are set as a multiple of In.The Ground Fault protection function is independent of
Different rating plugs are available (Table 1-2) to match the desired current rating and type of circuit breaker into which the trip unit is to be installed.
Complete catalog descriptions of all available rating plugs are given in the applicable circuit breaker supplementary instruction leaflets (see Section
8.0 REFERENCES
8.1 Q
-
Frame Molded Case Circuit Breakers
40752-078
Contact AB
8.2 Internal Accessories:
accessories, which mount on the trip unit, are available for use. The number of the instruction leaflet covering the installation of each accessory is shown.
.
Alarm (Signal)/Lockout (ASL) Switch
.
Auxiliary Switch
.
ShuntTrip
Undervoltage Release Mechanism (Handle Reset
.................................................... 40752-075
........................................................... 40752-070
((,).The Short Delay and Instanta
Frame Instruction Leaflet
Typical Time
curves for L Frame Breakers
The following types of internal
........................................... 40752-074
-2), the primary
8.0).
-
Current Characteristic
...........40752-076
-
In.
40752-072(2) Effective 6/02
Trip Unit Functions
Long Delay Fixed Ampere Rating¬ with Fixed Long Delay
Table 1-1. Electronic RMS Trip Units
3 Pole
Electronic RMS Trip Unit type Catalog Numbers
LS LSI LSG LSIG
l
l
Page 13
l
l
Adjustable ampere Setting with fixed
Long Delay Short Delay Adjustable Short
Delay Pick-up with Short Delay Time
2
l
t Ramp
Adjustable Short Delay Time® with Adjustable Short Delay Pick-up, or
Adjustable Instantaneous Pick-up®
Instant Fixed
Instantaneous (Override)¯
Ground Adjustable Ground Fault Fault Pick-up with
Adjustable Ground
Fault Time Fourth 100% rating for Pole fourth pole Protection
60% rating for
fourth pole
l
l
l
l
l
l
l
l
l
l
ll ll
ll
Fourth pole
unprotected ¬ Fixed rating plugs available, see Table 1-2
Optional four-setting adjustable rating plugs available, see Table 1-2 ® Using trip unit with adjustable short delay time (LSI, LSIG), instantaneous pick-up is achieved when the lowest time delay setting
(1) is selected. ¯ A non-adjustable override setting is set at the frame withstand rating.
40752-072(2) Effective 6/02
Page
14
Table 1-2. Electronic RMS Trip Unit
Trio Function Ampere Rating
Fixed at 100%
Adjustable Long
-
Delay Pick
Short Delay Pick-up (Adjustable)
Short (Fixed)
Short
(Adlustable)
Instantaneous
Pick-upO
Ground Fault
Ground Fault Time
0
O
up
DelayTime
DelayTime
-
up
Pick (Adjustable)
Delay
Not UL Listed Occurs with short delay time adjustment set at
Function and Rating Settings
RatinalSettina Descriotion
Fixed rating plugs available
Trip Unit Fixed Rating Plugs
Amoere Ratina
600A
630A
800A
Trip Unit
Ampere Rating
600A
630A
800A
In
(I,)
IZt ramp configuration
Flat response with time delay settings at 100 ms
Trip Unit
Ampere Rating
600A 800A
Settinas at instantaneous
300A, 350A, 400A, 500A, 600A 300A, 315AO, 350A, 400A, 500A, 600A, 630AO
400A. 500A. 600A. 700A. 800A
Adjustable Rating Plugs
300A-400A-500A-600A
31 5A-400A-500A-630A
400A-500A-630A-800A
multiples
of
with marks at 2-3-4-5-6-7-8x
installed rating plug amperes
200
ms and 300 ms
Settings
120A, 240A, 360A, 480A, and 600A 160A, 320A, 480A, 640A, and 800A
(1).
I
(I,)
(IJO
fI I or 400A-500A-600A-800A
150ms. 300ms. and 500ms
(I,)
(I-!
(I,)
fI
I
40752-072(2) Effective 6/02
Printed in U.S.A./TQC
Loading...