Rockwell Automation 140G-Rx User Manual

:のため、けまたはのはからりしてく ださい。なケースにけてください。また、がないことを してください。(
:,。 。。(NFPA70E)
140G-R_
3000A ONLY 3000A ONLY
Installation instruction for 140G-R Istruzioni di installazione Installationsanleitung Instructions pour l’installation Instrucciones de instalación
Installation - Installazione - Instalación Instalação - -
WARNING:
installing or servicing. Install in suitable enclosure. Keep free from contaminants. (Follow NFPA70E requirements).
AVVERTENZA:
WARNUNG:
Vermeidung von elektrischen Unfällen trennen. Die Geräte müssen in einem passenden Gehäuse eingebaut und gegen Verschmutzung geschützt werden. (Befolgen Sie die Anforderungen nach NFPA70E).
AVERTISSEMENT:
secteur pour éviter toute décharge. Prévoir une mise en coffret ou armoire appropriée. Protéger le produit contre les environnements agressifs. (Vous devez respecter la norme NFPA70E).
ADVERTENCIA:
del servicio, a fin de impedir sacudidas eléctricas. Instálelo en una caja apropiada. Manténgalo libre de contaminantes. (Cumpla con los requisitos NFPA70E).
ATENÇÃO:
instalação ou a manutenção. Instalar em caixa apropriada. Manter livre de contaminantes. (Cumpra as exigências da norma NFPA70E).
To prevent electrical shock, disconnect from power source before
Per prevenire infortuni, togliere tensione prima dell'installazione o
Vor Installations- oder Servicearbeiten Stromversorgung zur
Avant le montage et la mise en service, couper l'alimentation
Desconéctese de la corriente eléctrica, antes de la instalación o
Para evitar choques, desconectar da corrente elétrica antes de fazer a
Bul. 140G/140MG
3p
4p
のにってください)NFPA70E
X1
X2 X48 X24
DIR 1000682R0002 (L5757)DIR 1000682R0002 (L5757)
X1
X32X64X2
Index
1. Description ................................................................. 3
1.1 General characteristics ......................................................... 3
1.2 External front view of the circuit-breaker ............................. 3
2. Checking on receipt ................................................... 3
3. Storage, lifting and weights ..................................... 3
4. Installation .................................................................. 4
4.1 Installation conditions .......................................................... 4
4.2 Installation of the flange on the compartment door (Fig. 8) . 5
5. Electrical connections ................................................ 5
5.1 Power circuit connections .................................................... 5
5.1.1 Shapes of the terminals ........................................................ 5
5.1.2. Examples of connection busbar layouts depending on the
types of terminals ................................................................ 5
5.2.3 Assembly procedures for the connection busbars .............. 6
5.2 Wiring of the auxiliary circuits of the circuit-breaker ............ 6
6. Putting into service .................................................... 7
6.1 General procedures .............................................................. 7
7. Instructions for use .................................................... 8
7.1 Operating and signalling components ................................ 8
7.2 Circuit-breaker closing and opening procedures ................. 8
11. Protection releases - References ............................. 20
11.1 Safety notes ....................................................................... 20
11.1.1. Notes for dielectric strength tests ...................................... 20
11.2 General characteristics ....................................................... 20
12. Overall dimensions .................................................. 21
13. Circuit diagrams ....................................................... 26
8. Maintenance ............................................................ 10
8.1. Warnings ............................................................................ 10
8.2. Maintenance program ........................................................ 10
8.2.1. Circuit-breaker life .............................................................. 10
8.2.2. Maintenance program ....................................................... 10
8.3. First Level maintenance operations ................................... 11
8.3.1. Preliminary operations: ....................................................... 11
8.3.2. General inspections and cleaning: ..................................... 11
8.3.3. Circuit-breaker connections and connections between
circuit-breaker and switchboard ........................................ 11
8.3.4. Flange and escutcheon plate disassembly operations ...... 11
8.3.5. Mechanical operating mechanism ..................................... 12
8.3.6. Electrical and mechanical accessories .............................. 12
8.3.7. Protection releases ............................................................. 13
8.3.8. Maintenance operations; final inspections ......................... 13
8.4. Second Level maintenance operations .............................. 14
8.4.1. Preliminary operations: ....................................................... 14
8.4.2. General inspections and cleaning: ..................................... 14
8.4.3. Circuit-breaker connections and connections between
circuit-breaker and switchboard ........................................ 14
8.4.4. Flange and escutcheon plate disassembly operations ...... 14
8.4.5. Mechanical operating mechanism ..................................... 15
8.4.6. Electrical and mechanical accessories .............................. 16
8.4.7. Protection releases ............................................................. 16
8.4.8. Maintenance operations; final inspections ......................... 16
9. Measures to be taken if operating faults occur ....... 17
10. Accessories .............................................................. 18
10.1 Electrical accessories ......................................................... 18
10.2 Mechanical locks ................................................................ 19
DIR 1000682R0002 (L5757)
(2)
1. Description
1.1 General characteristics
140G-R circuit-breakers and disconnectors consist of a plastic structure which houses the operating mechanism, the poles and the auxiliary parts. Each pole is insulated from the others and contains the circuit breaking parts and the current sensor of the corresponding phase. The fixed version circuit-breaker has its own terminals for connection to the power circuit.
1.2 External front view of the circuit-breaker
1
2
Fig. 1
1 LSIG electronic microprocessor-based release 2 Operating and control parts of the operating mechanism and release-tripped signals 3 Rating plate
3
2. Checking on receipt
Examine the condition of the material received and make sure that it corresponds to what was ordered. Any damage or non-compliance found when the material has been unpacked, which must be carried out with due care, must be notified within 5 days of receipt and the number of the shipping notice must be indicated on the notification.
3. Storage, lifting and weights
Protected by an external wooden crate, the circuit-breaker is fastened with screws to the pallet used for transport or to the bottom of the pack­ing crate. If the circuit-breaker must be stored for even a short period of time before being put into service, after having been checked on receipt it must be its back into its container and covered with a waterproof tarpaulin.
Caution
– Store the circuit-breaker in a dry, dust-free room well away from aggressive chemicals. – Place the circuit-breaker and any fixed part on a horizontal surface, not in direct contact with the floor but on a suitable support (Fig. 4). – The maximum number of circuit-breakers that can be stacked on top of each other is shown in figure 5. – Keep the circuit-breaker in the open position with the closing springs unloaded to prevent unwarranted stress and the risk of accidents to the
personnel.
Fig. 4
DIR 1000682R0002 (L5757)
Fig. 5
(3)
Comply with the following instructions when lifting the circuit-breaker: the circuit-breakers must be placed on a sturdy surface and preferably lifted with an appropriate fork-lift truck. The use of ropes is, however, permitted: In this case, the lifting ropes ust be attached as shown in the figure.
Fig. 6
Table of circuit-breaker weights (kg)
Circuit-breaker 3 poles 4 poles kg lbs kg lbs
T8 2000 73 161 95 209
T8 2500 73 161 95 209
T8 3000 95 209 125 276
Note
The weights given in the table refer to circuit-breakers complete with LSIG releases and relative current sensors, excluding the accessories.
4. Installation
4.1 Installation conditions
Install the circuit-breaker in a dry, dust-free, non-corrosive place where it will not be subjected to shocks or vibrations. When this is not possible, assemble it inside a switchboard with a suitable degree of protection. For preparation of the installation ambient, refer to the “Overall dimen­sions” chapter, which provides information about the following points:
– minimum installation volumes of the circuit-breakers and derived
versions – clearances to be respected for circuit-breakers in compartments – overall dimensions of the circuit-breakers – drilling holes for fixing purposes – drilling holes in the compartment door
The operations required for installation, putting into service, routine and supplementary maintenance must be performed by skilled personnel with detailed knowledge of the equipment.
To install a circuit-breaker in the switchboard, just fix it to a vertical surface with M8 screws. (fig. 7 )
The circuit-breaker must only be installed in a vertical position.
DIR 1000682R0002 (L5757)
Fig.7
(4)
4.2 Installation of the flange on the compartment door (Fig. 8)
– Drill the holes in the compartment door indicated in the section entitled “Overall dimensions”. – Apply the flange (1) to the front of the compartment door and fix it from the inside with the self-tapping screws (2).
2
1
Fig. 8
5. Electrical connections
5.1 Power circuit connections
Use insulated bars/ perform specific type tests on the installation.
5.1.1 Shapes of the terminals
F ES
Front terminals
Fig. 9
Note
The drawings provide a schematic illustration of the type of terminal. The exact shape of the terminals is given in the chapter entitled “Overall dimensions". The terminals installed on the upper and lower parts (input and output) can be different from each other.
Extended front
terminals
(IEC)
nals for flat bar ( VR for
VR
Adjustable rear termi-
IEC/UL; HR for IEC)
VR
Vertical rear
terminals
5.1.2. Examples of connection busbar layouts depending on the types of terminals
The busbars allow connections to be made between the terminals of the circuit-breaker and the busbars of the switchboard. They must be ac­curately sized by the switchboard design engineer. This section illustrates examples of possible constructions, depending on the shape and size of the circuit-breaker terminals. It is normally advisable to use the entire contact surface of the terminal, thus the width of the busbar should be the same as that of the terminal. Different capacities can be obtained for the connections by adjusting the thickness and number of busbars in parallel. In certain cases, reductions in the width of the connection in relation to that of the terminal can be allowed, as shown in the examples below.
Front terminals Vertical rear terminals
Circuit-breaker Iu [A] Busbar cross-section Busbar cross-section
[mm2]/[in2] [mm2]/[in2]
140G-R 2000 3x(100x5) / 3x(3.94x0.2) 3x(100x5) / 3x(3.94x0.2) 140G-R 2500 4x(100x5) / 4x(3.94x0.2) 4x(100x5) / 4x(3.94x0.2) 140G-R 3000 - 5x(102x6.4) / 5x(4x0.25)
Fig. 10
DIR 1000682R0002 (L5757)
(5)
Positioning the rst anchor plate of the busbars
Anchoring to the switchboard
190
7.48"
190
7.48"
190
7.48"
190 190
7.48"
Fig. 11
190
7.48"
7.48"
5.2.3 Assembly procedures for the connection busbars
Check the state of the contact surfaces of the connections very carefully: they must be very clean and free from burrs, dents and traces of rust
- which must be removed with a fine file or emery cloth to prevent localized increases in temperature. On completion of the operation, remove any traces of grease or dust with a cloth soaked in a suitable solvent. When aluminium connections are used, the contact surfaces must be tin-plated. Make sure that the connections are unable to exert any strain on the terminals in any direction. Always insert a flat washer with a large diameter (to distribute the tightening pressure over the widest possible area) and a spring washer. Establish contact between the connection and terminal and fully tighten the fixing screws. Always use two wrenches (to prevent the insulating parts from being unduly stressed) and apply the tightening torque of the main terminals = 70 Nm/615 lb in for M12 high-strength screws. Check tightness after 24 hours.
5.2 Wiring of the auxiliary circuits of the circuit-breaker
There is a special terminal board fitted with screw terminals for connecting the auxiliary circuits. The terminals are marked with alphanumerical identification codes as indicated in the electrical circuit diagram. The terminal board is accessed immediately when the compartment door is opened.
Fig. 12
DIR 1000682R0002 (L5757)
(6)
6. Putting into service
6.1 General procedures
– Make sure that the power connections to the circuit-breaker terminals are tight – Perform al the preparatory operations on the release – Make sure that the power supply voltage of the auxiliary circuits is between 85% and 110% of the rated voltage of the electrical applications – To avoid temperature rises, make sure that there is sufficient air exchange in the installation area – Also perform the inspections indicated in the following table.
Item inspected
1 Manual operating mechanism
2 Gearmotor (if provided)
3 Undervoltage release (if provided)
4 Shunt closing release (if provided)
5 Shunt opening release (if provided).
6 Lock for circuit-breaker in open position
(key or padlock)
7 Auxiliary circuit-breaker contacts
Procedure
Perform a few opening, closing and release operations (see chap. 7.2).
WARNING When there is an undervoltage release, the cir­cuit-breaker can only be closed after the release itself has been electrically energized.
Supply the spring loading gearmotor at the relative rated voltage.
Perform a few closing and opening operations.
Note. Supply the undervoltage release at the relative rated voltage (if provided).
Supply the undervoltage release at the relative rated voltage and perform the circuit-breaker closing operation.
Turn off the voltage supply to the release. Supply the undervoltage release at the relative rated voltage and perform the circuit-breaker closing operation.
Close the circuit-breaker. Supply the shunt opening release at the relative rated voltage.
Open the circuit-breaker. Power the shunt closing release at the its rated voltage. Open the circuit-breaker, turn the key and remove it. Attempt the circuit-breaker closing operation.
Insert the auxiliary contacts into appropriate signalling circuits. Perform a few circuit-breaker closing and opening operations.
Successful check
The spring loading lever moves normally.
The springs are loaded normally. The signals are normal. The gearmotor stops when the springs have been loaded.
The gearmotor reloads the springs after each
closing operation.
The circuit-breaker closes normally. The signals are normal.
The circuit-breaker opens. The signal changes over.
The circuit-breaker opens normally. The signals are normal.
The circuit-breaker closes normally. The signals are normal.
Both manual and electrical closing are pre­vented.
Signalling occurs normally.
DIR 1000682R0002 (L5757)
(7)
7. Instructions for use
7.1 Operating and signalling components
1 Push-button for the manual opening operation 2 Lever for manual loading of the closing springs 3 Mechanical indicator for circuit-breaker open “O” and closed “I” 4 Mechanical indicator for protection release tripped 5 Pushbutton for the manual closing operation 6 Indicator for springs loaded - unloaded 7 Operation counter (to order) 8 Key lock on the closing operation (to order)
Fig.13
Note
On request, a transparent cover that increases the degree of protection to IP54 can be installed on the front of the circuit-breaker. The cover is equipped with a key lock.
4
8
1
2
3
5
6
7
Fig. 14
7.2 Circuit-breaker closing and opening procedures
Circuit-breaker operation can be either manual or electrical.
a) Manual operation for loading the closing springs
– Make sure that “O” (circuit-breaker open) is displayed by the indicator – Make sure that the indicator (6) is WHITE (springs unloaded) – Repeatedly operate the lever (2) until the colour of the indicator (6)
changes to YELLOW
b) Electrical operation for loading the closing springs
Electrica operation of the circuit-breaker is possible when the following accessories are present (supplied to order): – gearmotor for automatic loading of the closing springs – shunt closing release – shunt opening release. The gearmotor automatically reloads the springs after each closing operation until the yellow indicator appears (6, Fig. 15). If there is a power failure during the loading operation, the gearmotor stops and automatically continues with the spring loading operation once the power returns. However, it is always possible to complete the reloading operation in the manual mode.
Fig. 15
2
3
6
DIR 1000682R0002 (L5757)
(8)
c) Circuit-breaker closing
This operation can only be carried out when the closing springs are fully loaded. Press the push-button (5) marked with the letter “I” for closing in the manual mode. When there is a shunt closing release, the operation can also be carried out in the remote mode by means of the special control circuit. Closing is signalled by the relative indicator (3), which moves to the “I” position. Moreover, the indicator of the state of the springs (6) moves to the WHITE position. The control has enough energy for the opening operation even when the closing springs are unloaded. If present, the gearmotor immediately begins the automatic spring loading operation.
5
3
Fig. 16
d) Circuit-breaker opening
Press the push-button “O” (1) to open the circuit-breaker in the manual mode. When there is a shunt opening release, the operation can also be carried out in the remote mode by means of the special control circuit. The open state is signalled by the appearance of the letter “O” in the indicator (3).
1
3
6
Press
Press
Fig. 17
DIR 1000682R0002 (L5757)
(9)
Loading...
+ 20 hidden pages