Robur GAHP-GS, GAHP-WS, GAHP-A HT S1, GAHP-A HT S, GAHP-A HT Installation, User And Maintenance Manual

...
Page 1
Installation, user and maintenance manual
GAHP-GS/WS
water/water gas absorption heat pump
powered by gas and renewable energy
Page 2
Revision: M Code: D-LBR509
This manual has been drawn up and printed by Robur S.p.A.; whole or partial reproduction of this manual is prohibited. The original is filed at Robur S.p.A. Any use of this manual other than for personal consultation must be previously authorised by Robur S.p.A. The rights of those who have legitimately filed the registered trademarks contained within this publication are not affected. With the aim of continuously improving the quality of its products, Robur S.p.A. reserves the right to modify the data and contents of this manual without prior notice.
Page 3
Installation, user and maintenance manual – GAHP-GS/WS
3
Index of Contents
1 PRefACe ������������������������������������������������������������������������������������������������������������4 2 sAfetY WARnInGs ������������������������������������������������������������������������������������������5 3 oVeRVIeW And teCHnICAL feAtURes ��������������������������������������������������������8
3.1 GENERAL INFORMATION ............................................................................................................................................................8
3.2 NOTES ON OPERATION OF THE APPLIANCE ......................................................................................................................10
3.3 TECHNICAL MANUFACTURING CHARACTERISTICS.........................................................................................................11
3.4 TECHNICAL DATA ........................................................................................................................................................................12
3.5 DIMENSIONS AND SERVICE PANEL .......................................................................................................................................15
4 noRMAL oPeRAtIon ������������������������������������������������������������������������������������17
4.1 START UP (AND SHUT DOWN) ................................................................................................................................................17
4.2 ON-BOARD ELECTRONICS ........................................................................................................................................................19
4.3 RESET OPERATIONS ....................................................................................................................................................................22
4.4 OPERATING SETTINGS ...............................................................................................................................................................23
4.5 PROLONGED PERIODS OF DISUSE ........................................................................................................................................24
5 HYdRAULIC InstALLAtIon ��������������������������������������������������������������������������26
5.1 GENERAL INSTALLATION PRINCIPLES ..................................................................................................................................26
5.2 POSITION OF THE APPLIANCE ................................................................................................................................................26
5.3 HYDRAULIC CONNECTIONS ....................................................................................................................................................28
5.4 GAS SUPPLY...................................................................................................................................................................................30
5.5 CONDENSATE DISCHARGE .......................................................................................................................................................31
5.6 FILLING OF HYDRAULIC CIRCUIT ...........................................................................................................................................34
5.7 EXHAUST FLUE GAS ....................................................................................................................................................................37
5.8 PROGRAMMING OF HYDRAULIC PARAMETERS................................................................................................................42
5.9 SAFETY VALVE DISCHARGE ROUTING ..................................................................................................................................43
6 eLeCtRICAL InstALLAtIon ��������������������������������������������������������������������������45
6.1 ELECTRICAL DIAGRAM OF THE APPLIANCE .......................................................................................................................49
6.2 HOW TO CONNECT THE APPLIANCE ELECTRICALLY .......................................................................................................50
6.3 TYPE A (COMFORT CONTROL PANEL) ..................................................................................................................................50
6.4 TYPE B (DDC) ................................................................................................................................................................................60
6.5 TYPE C (Consent switch) ...........................................................................................................................................................70
6.6 HOW TO RESET THE FLAME CONTROLLER FROM REMOTE ..........................................................................................71
7 InItIAL ACtIVAtIon And MAIntenAnCe ��������������������������������������������������73
7.1 PROCEDURE FOR FIRST START UP .........................................................................................................................................73
7.2 MAINTENANCE .............................................................................................................................................................................77
7.3 CHANGE OF GAS TYPE ..............................................................................................................................................................78
8 ACCessoRIes ��������������������������������������������������������������������������������������������������81 9 oPeRAtInG Codes/tRoUBLesHootInG ���������������������������������������������������82
9.1 OVERVIEW AND OPERATING CODES/TROUBLESHOOTING ..........................................................................................82
DECLARATION OF CONFORMITY ����������������������������������������������������������������������95
Page 4
4
1 PREFACE
This Installation, user and maintenance manual is a guide to the installation and opera­tion of the Air-Water gas absorption heat pump GAHP-GS/WS. This manual is specifically intended for:
final users for the operation of the appliance according to their own • requirements; Installation technicians (hydraulic and electrical) for a correct installation of the • appliance.
The manual also contains:
a section that describes all the operations necessary for the “first start-up” and for • the “gas change” of the appliance, as well as the main maintenance operations; an "ACCESSORIES" section with a description of accessories available and their re-• spective reference codes. (IN CASE) one or more APPENDIX sections in which are reported some "specific" • information for a particular country.
References
If the appliance is connected to a Comfort Control Panel (see detail CCP in Figure 6.4 Comfort Control Panel e Accessory → 48) it is switched on and controlled by the Comfort Control Panel. In this case, refer to the manual supplied with it. If the appliance is connected to a Direct Digital Controller (see Figure 6.3 CCI/DDC → 47) and the DDC is in controller mode, activation and control of the appliance will occur ex­clusively by operating the DDC. In this case, refer to the manual supplied with it.
Definitions, terms and icons
APPLIANCE: this term refers to the gas absorption heat pump GAHP-GS and/or gas ab­sorption heat pump GAHP-WS. CCP: "Comfort Control Panel". CCI: "Comfort Control Interface" device. DDC: digital control panel (Direct Digital Controller). TAC: Technical Assistance Centre (authorised by Robur S.p.A.). SYSTEM COLD SIDE: this term refers to the renewable source plant (geothermal probes or ground water). SYSTEM HOT SIDE: this term refers to the primary hot water distribution system. The icons in the edge of the manual have the following meanings:
= DANGER
= WARNING
= NOTE
= START OF OPERATING PROCEDURE
= REFERENCE to another part of the manual or other document
Page 5
Installation, user and maintenance manual – GAHP-GS/WS
5
2 SAFETY WARNINGS
Packing items (plastic bags, polystyrene foam, nails, etc.) must be kept out of the reach of children, as they are potentially dangerous.
The appliance must only be used for the purposes for which it has been designed. Any other use is considered inappropriate and therefore dangerous. The manufacturer does not accept any contractual or extra-contractual liability for any damage caused by im­proper use of the appliance.
The appliance is not intended to be used by persons (including children) whose physical, sensory and mental capacities are impaired, or who lack the necessary experience and knowledge, unless they are supervised or instructed in its use by persons responsible for their safety. Children must be supervised to ensure that they do not play with the appliance.
The unit uses a water/ammoniac absorption cycle for hot/cold water production. The am­moniac is in water solution inside a sealed circuit tested for tightness by the manufac­turer. In case of coolant leaks, switch off the electrical power and gas supplies only if this can be done in total safety. Contact your Authorised Service Centre.
If installed indoors, the safety valve must be ducted. Refer to Chapter 5.9 SAFETY VALVE DISCHARGE ROUTING → 43 of this manual for instructions. The unit MAY NOT BE OPER­ATED if the safety valve is not ducted.
Frequent topping up of the hydraulic with water can result in damage due to scale and corrosion, depending on the quality of the water being used. Make sure the system is water tight and that the expansion tank is operational.
Concentrations of chlorides or free chlorine in the circuit above the values given in Table
5.1 Chemical and physical parameters of water → 29 will damage the unit's water/am­monia exchanger.
Close the gas supply before working on the gas circuit. On completing work on the gas circuit, check for leakages as required by established regulations.
Do not operate the appliance if dangerous conditions exist: odour of gas in the grid or near the appliance; problems with the electrical/gas grid or hydraulic circuit; parts of the appliance submerged in water or otherwise damaged; controls or safety compo­nents bypassed or defective. In these cases, ask for assistance to professionally qualified personnel.
If you smell gas:
Page 6
6
do not use electrical devices such as telephones, multimeters or other equipment • that can cause sparks next to the appliance; shut off gas supply closing the isolation valve;• cut off electrical power opening the main breaker upstream of the appliance (to be • provided by the electrical installer in an appropriate panel); ask for assistance to professionally qualified personnel from a telephone distant • from the appliance.
Moving parts, also during the appliance's start-up and shut-down cycles. Do not remove guards. Make sure the appliance cannot be started up inadvertently.
POISONING HAZARD
Make sure the flue gas components are tight and compliant with established regulations. After any intervention on these parts, check for tightness.
If the appliance is installed indoors, insufficient or non-conforming ventilation (see instal­lation instructions) can result in hazardous leaks of combusted gases.
Make sure the ventilation and aeration outlets conform to the installation • instructions. If the non-conformity cannot be resolved immediately, do not start up the • appliance. Notify the plant operator of the non-conformity and any attendant hazards.•
BURN HAZARD
The appliance contains numerous hot parts. Do not open up the appliance or touch the fumes outlet pipe. If necessary, contact your Technical Assistance Centre.
The appliance has a sealed circuit classified as pressure equipment, i.e. with internal pres­sure higher than atmospheric pressure. The fluids contained in the sealed circuits are harmful if swallowed or inhaled, or if they come into contact with the skin. Do not carry out any operation on the sealed circuit or on its valves.
ELECTROCUTION HAZARD
Use only approved components for the electrical connections, as specified by the • manufacturer. Disconnect the electrical power supply before working on the appliance's internal • electrical equipment (electrical panel, motors, control board, etc.). Make sure the appliance cannot be started up inadvertently.•
The electrical safety of the appliance is ensured only when it is correctly connected to an efficient grounding system, compilant with current safety regulations.
DAMAGE DUE TO AGGRESSIVE SUBSTANCES IN THE AIR SUPPLY
Hydrogenated hydrocarbons, which contain chlorine and fluorine compounds, will in­crease the corrosion of the unit.
Page 7
Installation, user and maintenance manual – GAHP-GS/WS
7
Make sure the air supply is free of aggressive substances.
ACID CONDENSATE
Drain out the condensate produced during combustion as indicated in paragraph 5.5 CONDENSATE DISCHARGE → 31.
EXPLOSIVE/FLAMMABLE MATERIALS HAZARD
Do not use or store flammable materials (paper, solvents, paint, etc.) in the vicinity of the appliance.
SUGGESTIONS FOR THE CLIENT
Stipulate a maintenance contract with an authorised specialist contractor for the annual inspection of the appliance and maintenance when needed. Maintenance and repairs may only be done a contractor legally authorised to work on gas appliances and equipment. Only accept and use original spare parts.
Page 8
8
3 OVERVIEW AND TECHNICAL FEATURES
In this section you will find general information, hints on the operating principle of the appliance and its manufacturing features. This section also contains technical data and dimensional drawings of the appliance.
3.1 GENERAL INFORMATION
This manual is an integral and essential part of the product and must be delivered to the user together with the appliance.
Conformity to CE standards
The absorption heat pumps of the GAHP series are certified as conforming to standard EN 12309-1 and -2 and comply with the essential requirements of the following Directives:
Gas Directive 90/396/EEC and subsequent modifications and additions.• Efficiency Directive 92/42/EEC and subsequent modifications and additions.• Electromagnetic Compatibility Directive 89/336/EEC and subsequent modifica-• tions and additions. Low Voltage Directive 89/336/EEC and subsequent modifications and additions.• "Machinery Directive" 2006/42/EC.• Pressurised Equipment Directive 97/23/EEC and subsequent modifications and • additions. UNI EN 677 Specific requirements for condensing boilers with nominal thermal ca-• pacity up to 70 kW. EN 378 Refrigerating systems and heat pumps.•
The emission values of nitrogen oxides (NOx) of gas absorption heat pumps of the GAHP series are lower than 60 mg/kWh, in compliance with the requirements of the standard RAL UZ 118 "Blauer Engel".
Information regarding the above EC certifications is given in Paragraph 3.4 TECHNICAL DATA → 12, as well as on the Nameplate of the appliance itself.
Installation and regulatory references
On receiving the appliance at the installation site, before placing into final position, check there are no signs of transportation damages of the external panels or packaging.
Packing materials must be removed only after the appliance has been positioned on site. After removing the packing materials, ensure that the appliance is intact and complete.
Installation of the appliance may only be carried out by professionally qualified personnel by i.e. firms qualified according to the current legislation of the country of installation.
"Professionally qualified personnel" means personnel with specific technical competence in the sector of heating/cooling installations and gas appliances.
Installation of the appliance must be carried out in compliance with current local and national regulations regarding the design, installation and maintenance of heating and cooling installations and in accordance with the manufacturer's instructions. In particular, current regulations regarding the following aspects must be respected:
Gas equipment.• Electrical equipment.• Heating installations and heat pumps•
Page 9
Installation, user and maintenance manual – GAHP-GS/WS
9
Every other standard and regulation concerning the installation of equipment for •
summer and winter air conditioning using gas fuel. The manufacturer does not accept any contractual or extra-contractual liability for any damage caused by errors in installation and/or failure to observe the abovementioned regulations and the instructions supplied by the manufacturer itself.
Once the appliance is installed
The installer must provide the owner with a Declaration stating that the installation has been completed in compliance with state-of-the-art practices, current national and local regulations, and recommendations by the manufacturer.
Before contacting Technical Assistance for commissioning and first start-up, the installer must ensure that:
the electricity and gas grids characteristics correspond to the specifications on the •
nameplate of the appliance;
the gas supply pressure is compliant with the value reported in Table 5.2 Network •
gas pressure → 31 (considering a tolerance of ±15%);
the appliance is fed by the type of gas for which it is designed;•
the gas supply system and water distribution system are sealed;•
the gas and electricity supply systems are properly rated for the capacity required •
by the appliance and are equipped with all safety and control devices required by
current regulations
Check that no safety and control devices are excluded, by-passed or not properly working.
Initial activation procedure
The complete procedure for the first start up of the appliance must be carried out by an authorized technician according to the instructions supplied by the manufacturer. To carry out entire procedure correctly, follow the instructions in Paragraph 7.1 PROCE­DURE FOR FIRST START UP → 73.
Warranty could be invalidated if the first start up is not carried out and validated by an authorized technician.
Operation and maintenance of the appliance
To ensure the correct operation of the appliance and to avoid failures, control of the switching on and off of the appliance must be done in line with the requirements of the various types of installation.
If the appliance is connected to the Comfort Control Panel (see Figure 6.4 Comfort •
Control Panel e Accessory → 48 detail CCP), the appliance may be switched on and
off exclusively by the CCP itself.
If the appliance is connected to the DDC (see Figure 6.3 CCI/DDC • → 47), the appli-
ance may be switched on and off exclusively by the DDC itself.
If the appliance is NOT connected to a CCP/DDC, the appliance may be switched •
on and off exclusively by a switch on the consent circuit.
Page 10
10
The appliance must never normally be switched on and off by shutting off the power supply upstream of the Controle Device (CCP, DDC or consent switch) before having used the latter first and waited for the shutdown cycle to end (approximately 7 minutes). The shutdown cycle terminates when the hydraulic pump switches off (no parts in motion).
Shutting off the power supply while the appliance is running can cause permanent dam­ages to internal components!
If the appliance fails to operate correctly, with the consequent indication of the Ma­chine code, follow the instructions of Paragraph 9.1 OVERVIEW AND OPERATING CODES/ TROUBLESHOOTING → 82.
In the event of failure of the appliance and/or breakage of any component, do not at­tempt to repair and/or restore operation; proceed as follows:
shut off the appliance immediately (if possible and if no dangerous condition ex-• ists) through the controls (CCP, DDC or permissive switch) and wait for the end of the cooling down cycle (around 7 minutes); immediately get in touch with Technical Assistance.•
Proper ordinary maintenance ensures the efficiency and good operation of the appli­ance over time. Carry out maintenance operations according to the instructions supplied by the manufacturer. For the maintenance of internal components of the appliance, contact Technical Assist­ance; for other maintenance requirements, see Paragraph 7.2 MAINTENANCE → 77. Any repair of the appliance must be carried out by Technical Assistance, using only origi­nal spare parts.
Failure to observe the indications above may compromise the operation and safety of the appliance, and may invalidate warranty.
If the appliance is to be disposed of, contact the manufacturer for its correct disposal.
If the appliance is to be sold or transferred to another owner, ensure that this “Installation, user and maintenance manual” is handed over to the new owner and installer.
3.2 NOTES ON OPERATION OF THE APPLIANCE
The appliance uses the water/ammoniac absorption thermodynamic cycle (H20 – NH3) to produce hot water, drawing the required energy from the ground (GAHP-GS) or, in the case of the GAHP-WS, from ground water. The water/ammonia thermodynamic cycle used in the unit GAHP-GS/WS is realized in a hermitically sealed circuit, directly verified by the manufacturer to ensure the perfect tightness of all joints, thus making refrigerant top-ups completely unnecessary.
Description and general characteristics
The GAHP-GS/WS is a modulating condensation heat pump: the thermal power modu­lates from 100% to 50% depending on load, to ensure optimal comfort. The water/water gas absorption heat pump GAHP-WS produces hot water to +65°C for heating purposes and up to +70°C for sanitary hot water. The geothermal absorption heat pump GAHP-GS is available in the following versions:
Page 11
Installation, user and maintenance manual – GAHP-GS/WS
11
Version • HT: optimised for high temperature heating systems (radiators, fan coils);
it produces hot water to +65°C for heating purposes and up to +70°C for sanitary
hot water.
Version • LT: optimised for low temperature distribution systems (heating floor, low
temperature radiators); it produces hot water up to +55°C in heating mode and up
to +70°C in Domestic Hot Water mode. The modulating function (both in terms of combustion and flow rate) combined with fumes condensation results in efficiencies of up to 172%. The GAHP-GS/WS can operate in ambient temperatures of 0°C to +45°C. The GAHP heat pump can be controlled with the CCP/DDC or with a switch on the con­sent circuit. During operation, combustion products are exhausted via the discharge terminal at the left side of the appliance (see Figure 3.1 Size → 15). The fumes outlet must be connected to a flue (for further details, see Paragraph 5.7 EXHAUST FLUE GAS → 37). The appliance powered by 230 V 1N 50 Hz electrical power - .
3.3 TECHNICAL MANUFACTURING CHARACTERISTICS
The appliance is supplied with the following technical manufacturing characteristics, control and safety components:
Steel sealed circuit, externally treated with epoxy paint.•
Sealed combustion chamber suited for type C installation.•
Metal mesh radiant burner equipped with ignition electrodes and flame detection •
managed by an electronic flame control box.
Titanium stainless steel shall-and-tube heat exchanger, with external insulation.•
Tube coil heat recovery [AISI 304L] (for acid condensate).•
Control and safety components
S61 electronic board with integrated microprocessor, LCD display and control •
knob, complete with Mod10 auxiliary card to control thermal capacity and prima-
ry pump modulation (see Figures 6.1 Electronic board S61 → 46 and 6.2 Mod10
controller → 47).
Primary circuit water flowmeter (hot side).•
Plant water flowmeter (cold side).•
Sealed circuit high temperature limit thermostat, with manual reset.•
Flue temperature thermostat 120 °C, with manual reset.•
Sealed circuit safety relief valve.•
Safety by-pass valve, between high and low pressure parts of the sealed circuit.•
Antifreeze functions for hydraulic circuit.•
Ionization flame control box.•
Double shutter electric gas valve.•
Condensate discharge sensor.•
Page 12
12
3.4 TECHNICAL DATA
Table 3.1 – GS HT/LT technical data
GAHP GS LT GAHP GS HT
OPERATION WHEN HEATING
OPERATING POINT B0W50* (Brine inlet 0°C, hot Water outlet +50°C)
G.U.E. gas usage efficiency % 150 (1) 149 (1) Thermal power delivered kW 37,7 (1) 37,6 (1) Power recovered from
renewable source
kW 12,4 12,6
OPERATING POINT B0W35* (Brine inlet 0°C, hot Water outlet +35°C)
G.U.E. gas usage efficiency % 170 (1) -­Thermal power delivered kW 42,6 (1) -­Power recovered from
renewable source
kW 17,0 --
OPERATING POINT B0W65* (Brine inlet 0°C, hot Water outlet +65°C)
G.U.E. gas usage efficiency % -- 125 (1) Thermal power delivered kW -- 31,5 (1) Power recovered from
renewable source
kW -- 7,9
Thermal capacity
Nominal (1013 mbar - 15°C) kW 25,7
true peak kW 25,2 NOx emission class 5 NOx emission ppm 25 CO emission ppm 36
Hot water delivery temperature
maximum for heating °C 55 65
maximum for DHW °C 70
Hot water return temperature
maximum heating °C 45 55
maximum for DHW °C 60
minimum temperature in
continuous operation**
°C 20 30
Hot water flow rate
nominal l/h 3250 3170
maximum l/h 4000
minimum l/h 1400
Hot water pressure drop
for nominal water flow
(B0W50)
bar 0,49 (2)
Ambient air temperature (dry bulb)
maximum °C 45
minimum °C 0 Thermal differential nominal °C 10
gas consumption
methane G20 (nominal) m3/h 2,72 (3)
G30 (nominal) kg/h 2,03 (4)
G31 (nominal) kg/h 2,00 (4)
RENEWABLE SOURCE OPERATING CONDITIONS
Renewable source water flow rate (with 25% glycol)
nominal (B0W50) l/h 3020
maximum l/h 4000
minimum l/h 2000 Renewable source pressure drop at nominal flow rate bar 0,51 (2) Renewable source water return temperature maximum °C 45 Renewable source delivery water temperature minimum °C -10 -5
ELECTRICAL SPECIFICATIONS
Power supply
Voltage V 230
TYPE SINGLE PHASE
Frequency
50 Hz
supply
50
Electrical power absorption nominal kW 0,47 (5) Degree of protection IP X5D
INSTALLATION DATA
Level of acoustic pressure at 10 meters (maximum) dB(A) 39 (7) Minimum storage temperature °C -30 Maximum operating pressure bar 4 Maximum condensation water flow rate l/h 4,0
Water content inside the apparatus
HOT SIDE l 4
COLD SIDE l 3
Water fitting
TYPE F
thread " G 1 1/4
Gas fitting
TYPE F
thread " G 3/4 Safety valve outlet channel fitting " G 1 1/4
Fume outlet
Diameter (∅) mm 80
Residual head Pa 80
Product configuration C63
Page 13
Installation, user and maintenance manual – GAHP-GS/WS
13
GAHP GS LT GAHP GS HT
Size
width mm 848 (6) height mm 1278 depth mm 690
Weight In operation kg 300
GENERAL INFORMATION
INSTALLATION MODE C13, C33, C43, C53, C63, C83, B23P, B33
COOLING FLUID
AMMONIA R717 kg 7 WATER H2O kg 10
MAXIMUM PRESSURE OF THE COOLING CIRCUIT bar 35
* data tested by VDE and DVGW-Forschungsstelle. ** in transient operation, lower temperatures are allowed
Notes:
As per EN12309-2 evaluated on actual thermal capacity. For operating conditions 1. other than nominal, refer to the Design Manual. For flow rates different from the nominal refer to the Design Manual.2. PCI 34.02 MJ/m3 (1013 mbar – 15 ° C).3. PCI 46.34 MJ/kg (1013 mbar – 15 ° C).4. ± 10% depending on power voltage and absorption tolerance of electric motors.5. Overall dimensions excluding fumes pipes (see Figure 3.1 Size 6. → 15). Free field, frontal, directionality factor 2.7.
Table 3.2 – WS technical data
GAHP WS
OPERATION WHEN HEATING
OPERATING POINT W10W50
G.U.E. gas usage efficiency % 166 (1) Thermal power delivered kW 41,6 (1) Power recovered from
renewable source
kW 16,6
OPERATING POINT W10W65
G.U.E. gas usage efficiency % 143 (1) Thermal power delivered kW 35,8 (1) Power recovered from
renewable source
kW 11,5
Thermal capacity
Nominal (1013 mbar - 15°C) kW 25,7
true peak kW 25,2 NOx emission class 5 NOx emission ppm 25 CO emission ppm 36
Hot water delivery temperature
maximum for heating °C 65
maximum for DHW °C 70
Hot water return temperature
maximum heating °C 55
minimum temperature in
continuous operation**
°C 20
Hot water flow rate
nominal l/h 3570
maximum l/h 4000
minimum l/h 1400
Hot water pressure drop
for nominal water flow
rate(W10W50)
bar 0,57 (2)
Ambient air temperature (dry bulb)
maximum °C 45
minimum °C 0 Thermal differential nominal °C 10
gas consumption
methane G20 (nominal) m3/h 2,72 (3)
G30 (nominal) kg/h 2,03 (4)
G31 (nominal) kg/h 2,00 (4)
RENEWABLE SOURCE OPERATING CONDITIONS
Renewable source water flow rate
nominal (W10W50) l/h 2850
maximum l/h 4700
minimum l/h 2300 Renewable source pressure drop at nominal flow rate bar 0,38 (2) Renewable source water return temperature maximum °C 45 Renewable source delivery water temperature minimum °C 3
ELECTRICAL SPECIFICATIONS
Page 14
14
GAHP WS
Power supply
Voltage V 230 TYPE SINGLE PHASE
Frequency
50 Hz
supply
50
Electrical power absorption nominal kW 0,47 (5) Degree of protection IP X5D
INSTALLATION DATA
Level of acoustic pressure at 10 meters (maximum) dB(A) 39 (7) Minimum storage temperature °C -30 Maximum operating pressure bar 4 Maximum condensation water flow rate l/h 4,0
Water content inside the apparatus
HOT SIDE l 4 COLD SIDE l 3
Water fitting
TYPE F thread " G 1 1/4
Gas fitting
TYPE F thread " G 3/4
Safety valve outlet channel fitting " G 1 1/4
Fume outlet
Diameter (∅) mm 80 Residual head Pa 80 Product configuration C63
Size
width mm 848 (6) height mm 1278 depth mm 690
Weight In operation kg 300
GENERAL INFORMATION
INSTALLATION MODE
C13, C33, C43, C53, C63,
C83, B23P, B33
COOLING FLUID
AMMONIA R717 kg 7,7 WATER H2O kg 10
MAXIMUM PRESSURE OF THE COOLING CIRCUIT bar 35
** in transient operation, lower temperatures are allowed.
Notes:
As per EN12309-2 evaluated on actual thermal capacity. For operating conditions 1. other than nominal, refer to the Design Manual. For flow rates different from the nominal refer to the Design Manual.2. PCI 34.02 MJ/m3 (1013 mbar – 15 ° C).3. PCI 46.34 MJ/kg (1013 mbar – 15 ° C).4. ± 10% depending on power voltage and absorption tolerance of electric motors.5. Overall dimensions excluding fumes pipes (see Figure 3.1 Size 6. → 15). Free field, frontal, directionality factor 2.7.
Table 3.3 – PED data
GAHP GS LT GAHP GS HT GAHP WS
PED data
COMPONENTS UNDER PRESSURE
Generator l 18,6 Leveling chamber l 11,5 Evaporator l 3,7 Cooling volume transformer l 4,5 Absorber/condenser l 3,7 Cooling absorber solution l 6,3
Solution pump l 3,3 TEST PRESSURE (IN AIR) bar g 55 SAFETY VALVE PRESSURE CALIBRATION bar g 35
FILLING RATIO
kg of
NH3/l
0,137 0,159
"SEALED SYSTEM" TARE kg 165 FLUID GROUP GROUP 1°
Page 15
Installation, user and maintenance manual – GAHP-GS/WS
15
3.5 DIMENSIONS AND SERVICE PANEL
Figure 3.1 – Size
LEGEND
A Fumes outlet dia 80 B Combustion air intake dia 80 C Manual reset fumes thermostat D Power cable input E Cooling fan F Appliance on indicator
G Gas fitting dia. ¾" H Hot water return dia. 1"¼ L Renewable source water return dia. 1"¼ M Renewable source water delivery dia. 1"¼ N Hot water delivery dia. 1"¼ Q Safety valve outlet ducting dia. 1"¼
Page 16
16
Figure 3.2 – Outdoor unit dimensions
LEGEND
A Fumes outlet dia 80 B Combustion air intake dia 80 C Manual reset fumes thermostat D Power cable input E Cooling fan
F Appliance on indicator G Gas fitting dia. ¾" H Hot water return dia. 1"¼ L Renewable source water return dia. 1"¼ M Renewable source water delivery dia. 1"¼ N Hot water delivery dia. 1"¼
Page 17
Installation, user and maintenance manual – GAHP-GS/WS
17
4 NORMAL OPERATION
In this section you will find all the indications necessary for the activation, regulation and control of operation of the appliance depending on the type of installation and control setup.
• TYPE A: controlled by CCP (see Figure 6.4 Comfort Control Panel e Accessory → 48, detail CCP).
• TYPE B: controlled by DDC (see Figure 6.3 CCI/DDC → 47).
• TYPE C: controlled by consent switch (e.g. on-off switch, ambient thermostat, tim- er, etc.).
4.1 START UP AND SHUT DOWN
Efficient operation and long life of the appliance depend largely on its correct use!
Before activating the appliance, check that:
the gas valve is open;• the appliance is powered electrically: the general electrical switch (GS) must be in • the «ON» position; power supply to the CCP/DDC (if provided) is on;• the installation technician has ensured that the hydraulic circuit is supplied in the • correct conditions.
If these conditions are satisfied, it is possible to proceed with activation.
TYPE A: APPLIANCE CONNECTED TO COMFORT CONTROL PANEL (CCP)
If the appliance is connected to a Comfort Control Panel (see detail CCP in Figure 6.4 Comfort Control Panel e Accessory → 48) it is switched on and controlled by the Comfort Control Panel. In this case, refer to the manual supplied with it.
The appliance must never normally be switched on and off by shutting off the power supply upstream of the Comfort Control Panel before having used the latter first and waited for the shutdown cycle to end (approximately 7 minutes). The shutdown cycle terminates when the hydraulic pump switches off (no parts in motion).
Shutting off the power supply while the appliance is running can cause permanent dam­ages to internal components!
TYPE B: APPLIANCE CONNECTED TO A DIRECT DIGITAL CONTROLLER (DDC)
If the appliance is connected to a Direct Digital Controller (see Figure 6.3 CCI/DDC → 47) and the DDC is in controller mode, activation and control of the appliance will occur ex­clusively by operating the DDC. In this case, refer to the manual supplied with it.
The appliance must never normally be switched on and off by shutting off the power supply upstream of the DDC before having used the latter first and waited for the shut­down cycle to end (approximately 7 minutes). The shutdown cycle terminates when the hydraulic pump switches off (no parts in motion).
Shutting off the power supply while the appliance is running can cause permanent dam­ages to internal components!
Page 18
18
TYPE C: STANDALONE APPLIANCE
Standalone appliances must be activated and deactivated only by means of the consent switch provided by the electrical installation technician. According to requirements, this consent switch may be an on/off button, an ambient thermostat, a programmable timer, or one or more voltage free contacts controlled by another process. For details about the type of on/off command installed, contact the plant’s electrical installation technician.
The appliance must never normally be switched on and off by shutting off the power supply upstream of the Controle Device (CCP, DDC or consent switch) before having used the latter first and waited for the shutdown cycle to end (approximately 7 minutes). The shutdown cycle terminates when the hydraulic pump switches off (no parts in motion).
Shutting off the power supply while the appliance is running can cause permanent dam­ages to internal components!
Start up
Switch on the appliance by means of the on/off command (placing it in the "ON" position).
Shut down
Switch off the appliance via the on/off command (placing it in the "OFF" position).
The shutdown cycle takes approximately 7 minutes to complete.
The on/off command is essential! Do not switch the appliance on or off by connecting it to or disconnecting it from the power supply directly, as this may be a source of danger and in any case damage the appliance or the plants connected to it.
Visualising and clearing of operating codes
Operating codes can be generated:
by the S61 on-board controller;•
by the CCP/DDC (if present).• The operating codes generated by the S61 controller are displayed on its screen and can also be viewed on the CCI (if present) or DDC (if present). Operating codes generated by the controller can be cleared through the board itself or from the CCI/DDC (if fitted and allowed).
For a description of the operating codes generated by the electronic board and how to reset them, refer to the list of operating codes contained in Table 9.1 TABLE OF OPERAT­ING CODES generated by the S61 electronic board (firmware version 3.024) → 82.
The controller (see Figure 6.1 Electronic board S61 → 46) is located inside the electrical panel of the appliance and the display may be viewed through the viewing hole on the front panel of the unit itself.
The Machine Codes generated by the CCI/DDC may only be viewed on the display of the CCI/DDC and may be cleared only through the CCI/DDC.
Page 19
Installation, user and maintenance manual – GAHP-GS/WS
19
For the operating codes generated by the CCP/DDC, refer to the manuals supplied with the unit.
Operating codes generated by the electronic board during the start-up of the appliance
If the appliance remains inactive for a prolonged period, it is possible that air is present in the gas pipes. In this case, activation fails and the appliance reports the operating code: "u_12" - flame controller arrest (temporary) (see Paragraph 9.1 OVERVIEW AND OPERAT­ING CODES/TROUBLESHOOTING → 82) and after a brief interval the appliance automati­cally launches the start up procedure again. If code (u_12) is signalled 3 times on succes­sive activation attempts, the code persists, the appliance locks out the flame controller and displays the following operating code: "E_12" - flame controller arrest (see Paragraph
9.1 OVERVIEW AND OPERATING CODES/TROUBLESHOOTING → 82). In this case reset is not automatic. To restore operation of the appliance, carry out a reset of the flame control unit via menu 2 of the controller: the procedure is illustrated in Paragraph 4.3 RESET OPERATIONS → 22. After it is reset, the appliance will make a new attempt to activate. If the appliance locks out several times, contact a Robur TAC by calling the Technical Serv- ice Department of Robur S.p.A. (tel. +39.035.888111). When activation is successful, the appliance is managed by the on-board controller (see following paragraph).
4.2 ONBOARD ELECTRONICS
The following descriptions refer to the S61 controller with firmware version 3.024.
The appliance is fitted with an S61 microprocessor controller with Mod10 modulation controller mounted above it (see Figure 4.1 On-board controller → 20). The S61 controller, in the electrical panel, controls the appliance and displays data, mes­sages and operating codes. Programming, control and monitoring of the appliance take place by interacting with the display A and knob B shown in Figure 4.1 On-board controller → 20. The CAN-BUS port connects one or several appliances to the CCP (if present) or a DDC (if present). The Mod10 controller (detail D in Figure 4.1 On-board controller → 20) is used for com- bustion modulation and variable rate pump control.
Page 20
20
Figure 4.1 – On-board controller
S61 + Mod10
LEGEND
A 4 digit display B Knob C CAN port D Mod10 controller
Description of menu of S61 controller
The parameters and settings of the appliance are grouped in the menus shown on the controller’s display:
Table 4.1 – Menu of electronic board
MENU MENU DESCRIPTION THE DISPLAY SHOWS
Menu 0 VIEW DATA (TEMPERATURE, VOLTAGE, PUMP SPEED, ECC...) 0. Menu 1 VIEW ALL PARAMETERS 1. Menu 2 ENTER ACTIONS 2. Menu 3 USER SET TINGS (THERMOSTATING, SET-POINT, T. DIFFERENTIAL) 3. Menu 4 INSTALLATION TECHNICIAN SETTINGS 4. Menu 5 TECHNICAL ASSISTANCE CENTRE SETTINGS 5. Menu 6 TECHNICAL ASSISTANCE CENTRE SETTINGS (MACHINE TYPE) 6. Menu 7 VIEW DIGITAL IMPUTS 7. Menu 8 (MENU NOT USED) 8. E EXIT MENU E.
Menu list of electronic board
Menus 0, 1 and 7 are Viewing Menus: they only allow the information displayed to be read, and not modified. Menu 0 shows the appliance operating data in real time. Menu 1 shows the parameters that characterise the operation of the appliance and their current values.
Menu 7 is to be used ONLY by the Robur TAC.
To view the information contained in these menus, proceed as illustrated in the para­graph "How to acces the menus". Menu 2 is an execution menu: it allows the operations of resetting the flame control unit, error reset and the manual defrosting command to be performed. To perform these procedures, see Paragraph 4.3 RESET OPERATIONS → 22. Menu 3 is a Settings Menu: it allows the values displayed to be set. The correct values of these parameters, for optimum performance of the appliance with the plant to be used
Page 21
Installation, user and maintenance manual – GAHP-GS/WS
21
connected, have already been set during installation. To set new values for the param­eters, see Paragraph 5.8 PROGRAMMING OF HYDRAULIC PARAMETERS → 42. Menus 4, 5, 6 and 7 exclusively concern the installation technician and Robur’s author­ized Technical Assistance Centre. Menu 8 may currently be selected, but not used.
Display and knob
The controller’s display can be viewed through the glass of the viewing aperture on the front panel of the appliance. Upon activation, all of the LEDs of the display light up for approximately three seconds, and then the name of the board, S61, appears. After around 15 seconds after the appli­ance powers up, the appliance starts running if the required consent is available. During correct operation the display shows, alternately, the following information: outlet water temperature, inlet water temperature, and the difference between the two water temperatures (see Table 4.2 Operating information → 21).
Table 4.2 – Operating information
OPERATING MODE: HEATING PARAMETER THE DISPLAY SHOWS
Hot outlet water temperature 50.0 Hot inlet water temperature 40.0 Differential Temperature (outlet - inlet) 10.0
Example of data visualised on display: water temperature and differential
If there are operating problems, the display shows, sequentially, the operating codes cor­responding to the problem detected. A list of these codes with their description and the procedure to follow to bring the appliance back to correct operation is provided in Para­graph 9.1 OVERVIEW AND OPERATING CODES/TROUBLESHOOTING → 82. The knob is used to display or set parameters, or to execute actions/commands (e.g.: a function or reset), when permitted.
HOW TO ACCESS THE MENUS
To use the knob with the special key supplied with the appliance:•
You will need: the appliance's electrical power switches set to "ON"; the controller's dis­play sequentially shows the operating data (temperature, delta T) regarding the current mode (e.g.: heating) and any active operating codes ("u/E...").
Remove the front panel by removing the fixing screws.1. Remove the cover of the electrical panel to access the knob.2. Use the special key through the hole to operate the knob and access the control-3. ler’s menus and parameters. To display the menus just press the knob once: the display shows the first menu: 4. "0." (= menu 0). The display shows “0.”. To display the other menus, turn the knob clockwise; The 5. display will read, in order: "1.", "2.", "3.", "4.", "5.", "6.", "7.", "8." and "E" (see Table 4.1 Menu of electronic board → 20). To display the parameters in a given menu (for example, menu 0), turn the knob 6. until it displays the menu in question (in the example: "0.") and press the knob: the display will show the first of the menu’s parameters, in this example "0.0" or "0.40" (= menu 0, parameter "0" or "40").
Page 22
22
In the same way: 7. turn the knob to scroll through content (menus, parameters, ac-
tions), press the knob to select/confirm the content (access a menu, display/set
a parameter, execute an action, quit or return to the previous level). For example,
to quit the menus, turn the knob to scroll through menus "0.", "1.", "2." etc. until the
controller displays the quit screen "E"; now press the knob to quit.
In the case of menus 0 and 1, the user can view any parameter. For information about menu 2, refer to Paragraph 4.3 RESET OPERATIONS → 22. To set the parameters of me nu 3, refer to Paragraph 5.8 PROGRAMMING OF HYDRAULIC PARAMETERS → 42. The other menus are not for the User: the information in these menus is dealt with in the sections dedicated to the installation technician or Robur TAC.
The special key allows the knob of the electronic board to be operated without opening the cover of the electrical panel, so that operators are protected from live components. When the necessary settings have been completed, put away the special key, replace the cap on the aperture of the electrical panel and refit the front panel of the appliance.
4.3 RESET OPERATIONS
There are several possible reasons why the appliance may have error status and therefore its operation arrested; such an error situation does not necessarily correspond to damage or malfunction on the part of the appliance. The cause that has generated the error may be temporary: for example, presence of air in the gas supply line or temporary power failure. The appliance can be reset with controller menu 2, the Comfort Control Panel (if present) or the DDC (if present). In these two latter cases, refer to their documentation.
Reset appliance controller
The Table 4.3 Menu 2 → 22 shows the actions available in menu 2.
For regulatory reasons, the flame controller reset is in a dedicated voice of menu.
Table 4.3 – Menu 2
ACTION REQUIRED FOR EXECUTION SHOWN ON DISPLAY AS
0 Reset flame controller arrest 2. 0 1 Reset other operating codes 2. 1 3 Timed forcing to minimum power 2. 3 4 Timed forcing to maximum power 2. 4 5 Regulation of power 2. 5 E (EXIT MENU) 2. E
The general operating codes of the unit's controller can be reset with actions "0" and "1". Actions "3", "4" and "5" are used to regulate the combustion parameters or for gas type changeovers, and are thus for use only by the installation technician or Robur TAC (for other information refer to Paragraph 7.1 PROCEDURE FOR FIRST START UP → 73).
RESET FLAME CONTROLLER (ACTION "0"):
Reset flame controller arrest; this may be used when the appliance is first activated, see Paragraph 4.1 START UP (AND SHUT DOWN) → 17, when the appliance is in a permanent locked condition or after a long period of disuse (see Paragraph 4.5 PROLONGED PERI­ODS OF DISUSE → 24).
You will need: access to the electrical panel, see Paragraph “Display and knob”.
Page 23
Installation, user and maintenance manual – GAHP-GS/WS
23
To reset the flame control unit select menu 2, as indicated in the Paragraph "Accessing the Menus"; then proceed as follows:
The display shows: "2." press the knob to access the menu. The display initially 1. shows item "2. 0". Press the knob to display the flashing reset request: "reS1".2. Press the knob again to reset the flame controller. The reset request stops flashing, 3. and again the display shows "2. 0". The reset operation has been performed. To quit the menu, turn the knob clockwise until the "2. E" is displayed. Now press 4. the knob to return to menu selection: "2.". To exit the menu selection and return to the normal visualisation of the parameters 5. of the appliance, turn the knob clockwise until "E" displays; press the knob to quit.
At this point, if the display does not signal any other operating codes, put away the spe­cial key, replace the electrical panel cover and refit the front panel.
RESET OTHER OPERATING CODES (ACTION "1"):
Reset other appliance errors; this is required to reset any errors which may occur during operation.
You will need: access to the electrical panel, see Paragraph “Display and knob”.
To reset the controller errors, select menu 2, as indicated in the Paragraph "Accessing the Menus"; Then:
The display shows: "2." press the knob to access the menu. The display initially 1. shows item "2. 0". Turn the knob clockwise to display item "2. 1".2. Press the knob to display the flashing reset request: "rEr1".3. Press the knob again to perform a board error reset. The reset request stops flash-4. ing, and the again display shows "2. 1". The reset operation has been performed. To quit the menu, turn the knob clockwise until the "2. E" is displayed. Now press 5. the knob to return to menu selection: "2.". To exit the menu selection and return to the normal visualisation of the parameters 6. of the appliance, turn the knob clockwise until "E" displays; press the knob to quit.
At this point, if the display does not signal any other operating codes, put away the spe­cial key, replace the electrical panel cover and refit the front panel.
4.4 OPERATING SETTINGS
The operations described require basic knowledge of the plant installed and of the S61 controller fitted to the appliance; before proceeding, you must acquire this informa tion, Paragraph 4.2 ON-BOARD ELECTRONICS → 19.
At the moment of installation, the appliance is set up by the installation technician for best operation according to the type of plant installed. Subsequently it is possible to modify the operating parameters, but this is not recommended if not in possession of the necessary knowledge and experience in order to do so. In any case, to set new op­erating parameters for the appliance see Paragraph 5.8 PROGRAMMING OF HYDRAULIC PARAMETERS → 42.
Page 24
24
4.5 PROLONGED PERIODS OF DISUSE
When the appliance is to be inactive for a long period, it is necessary to disconnect the appliance before the period of disuse and reconnect it before it is used again. To carry out these operations, contact a reputable hydraulic system installation technician.
Disconnecting the appliance
You will need: the appliance connected to the power/gas supply. Necessary equip ment
and materials.
If the appliance is in operation, switch it off with the CCP (if present) or DDC (if 1.
present), or the consent switch and wait for the shutdown cycle to terminate com-
pletely (approximately 7 minutes).
Disconnect the appliance from the power supply, putting the external disconnec-2.
tion switch in the OFF position (see GS in Figure 6.6 Electrical wiring diagram → 50)
provided in the appropriate panel by the installation technician.
Close the gas valve.3.
Do not leave the appliance connected to power and gas supply if it is expected to remain inactive for a long period.
If you wish to disconnect the appliance during the winter, one of the following two con­ditions must be met:
make sure that the hydraulic plant connected to the appliance contains an ad-1.
equate percentage of glycol antifreeze (see Paragraph 5.6 FILLING OF HYDRAULIC
CIRCUIT → 34 and Table 5.3 Technical data for filling the hydraulic circuit → 36);
activate the antifreeze function, which runs the circulation pumps and the appli-2.
ance when water temperature is below 4°C or in case the outdoor temperature is
lower than 2 °C. To do this, contact your installer. This function requires the appli-
ance to be ALWAYS powered up (electricity and gas) and power failures excluded.
Otherwise the manufacturer declines all contractual and extra-contractual li-
ability for consequent damage. Connecting the appliance before it is used again (to be carried out by the instal ler)
Before starting this procedure, the hydraulic system installation technician must:
ascertain whether the appliance requires any maintenance operations (con-•
tact your authorised Robur Technical Assistance Centre or consult Paragraph 7.2
MAINTENANCE → 77);
check that the water content of the plant is correct; if necessary, top up the cir-•
cuit to at least the minimum quantity (see Paragraph 5.6 FILLING OF HYDRAULIC
CIRCUIT → 34);
if necessary add, to the water of the system (free of impurities), inhibited monoeth-•
ylene glycol antifreeze in a quantity in proportion to the MINIMUM winter temper-
ature in the area of installation (see Table 5.3 Technical data for filling the hydraulic
circuit → 36);
bring the plant to the correct pressure, making sure that the pressure of the water •
in the plant is not less than 1 bar and not over 2 bar;
Page 25
Installation, user and maintenance manual – GAHP-GS/WS
25
In case of winter saesonal switch-off or long period of stopping, we suggest to not emp­ty the hydraulic circuit: in that case possible oxidation process can occur.This oxidation process could damage both the hydraulic system and also the Robur heat pump.It’s im­portant to verify that no leakages occur in the hydraulic circuit that may empty part of the system. The above recommendation is necessary in order to avoid to fill continuously with water that may imply the additional introduction of oxygen and the consequent dilution of the used inhibitor, for ex glycol. In case of precence of glycol, Robur advices to use inhibited glycol. Galvanized pipes are not recommended, as they are not compatible with glycol.
You will need: the appliance disconnected from the electricity/gas supply
open the plant gas supply valve to the appliance and make sure that there is no 1. smell of gas (indicating possible leaks);
if you smell gas, close the gas valve again immediately without operating any oth­er electrical device and, from a safe place, request the assistance of professionally qualified personnel.
If no smell of gas is detected, connect the appliance to the electricity supply mains 2. via the external circuit breaker provided by the installation technician in the ap­propriate panel (set the "GS" circuit breaker to the "ON" position, see Figure 6.6 Electrical wiring diagram → 50); power up the CCP (if present) or DDC (if present);3. check that the hydraulic circuit is charged;4. check that the condensate siphon is NOT empty or blocked (see Paragraph 5.5 5. CONDENSATE DISCHARGE → 31); check that inlet/outlet ducts are correctly connected and NOT obstructed.6. switch on the appliance by means of the on/off command (or DDC if present and 7. in control mode, or via CCP, if present).
Page 26
26
5 HYDRAULIC INSTALLATION
In this section you will find all the instructions necessary for installing the appliance from a hydraulic viewpoint. The hydraulic system installation technician must consult the elec­trical system installation technician in order to decide upon the correct sequence of the operations to be carried out.
Before realizing hydraulic system and gas supply for the appliance, the professionally qualified personnel is advised to read Paragraph 3.1 GENERAL INFORMATION → 8, pro­viding important recommendations about safety and references to current regulations.
5.1 GENERAL INSTALLATION PRINCIPLES
Prior to installation, carry out careful internal cleaning of all pipes and every other com­ponent to be used both on the hydraulic system and on the fuel supply, in order to re­move any debris that may compromise the operation of the appliance.
Installation of the appliance must be carried out in compliance with current regulations regarding design, installation and maintenance of heating and cooling plants and must be undertaken by professionally qualified personnel in accordance with the manufac­turer’s instructions. During the installation stage, observe the following indications:
Check that there is an adequate mains gas supply, in accordance with the manu-•
facturer’s specifications; see Table 5.2 Network gas pressure → 31 for the correct
supply pressures.
The appliance must be installed inside the building in a suitable room (see EN378). •
The machine room must be protected from freezing.
• The appliance is not designed for outdoors installation. The appliance must
not be exposed to rain and must be installed in a ventilated location in line
with the safety and installation standards applicable to this type of device.
ONLY the outdoor version (see Figure 3.2 Outdoor unit dimensions • → 16) can be
installed outdoor and does not need any specific protection against the weather
and against freezing.
The front of the appliance must be at least 80 cm away from walls or other fixed •
constructions; the right and left sides must have a minimum clearance of 45 cm;
the minimum rear clearance from walls is 20 cm (see Figure 5.2 Clearances → 28).
The appliance must be installed in such a way that the exhaust flue gas outlet is •
not in proximity of any external air inlet of a building. Respect current regulations
regarding the exhaust flue gas outlet.
Fit a gas cock on the gas supply line.•
Fit antivibration joints on the hydraulic connections.•
5.2 POSITION OF THE APPLIANCE
Lifting the appliance and placing it in position
Do not remove packaging during handling on the installation site.
Packing must only be removed upon final installation.
If the appliance has to be lifted, pass slings into the openings in the base supports and use spreader bars to prevent the slings from damaging the casing during handling (see Figure 5.1 Lift GS/WS → 27).
Page 27
Installation, user and maintenance manual – GAHP-GS/WS
27
The lifting crane and all accessory devices (braces, cables, bars) must be suitable sized for the load to be lifted. For the weight of the appliance, consult Table 3.1 GS HT/LT technical data → 12 and Table 3.2 WS technical data → 13.
The manufacturer cannot be held responsible for any damage occurring during the installation of the appliance.
Figure 5.1 – Lift GS/WS
MOUNTING BASE
Always place the appliance on a levelled flat surface made of fireproof material and able to support the weight of the appliance. If a horizontal support base is unavailable (see also "SUPPORTS and LEVELLING" below), it is necessary to create a flat level base in concrete which is larger than the dimensions of the base of the appliance by at least 100-150 mm on each side. The dimensions and weight of the appliance are given in Table 3.1 GS HT/LT technical data → 12 and in Table 3.2 WS technical data → 13. Although the appliance produces only moderate vibrations, the use of anti-vibration supports (available as accessories, see SECTION 8 ACCESSORIES → 81) is especially rec­ommended in cases in which resonance phenomena may occur. Moreover, it is advisable to use flexible connections (anti-vibration joints) between the appliance and the hydraulic and gas supply pipes.
SUPPORTS AND LEVELLING
The appliance must be correctly levelled by placing a spirit level on the upper part. If necessary, level the appliance with metal shimming; do not use wooden spacers as these deteriorate quickly.
CLEARANCES AND WARNINGS
Position the appliance so as to maintain minimum clearances from combustible sur­faces, walls or other appliances, as illustrated in Figure 5.2 Clearances → 28.
Page 28
28
Minimum clearances are necessary in order to be able to carry out maintenance operations.
The fumes outlet terminals must be installed in such a way that they do not allow the fumes to collect or return to the circuit in the unit's installation area. The outlet terminal must be constructed in conformity with established regulations.
Figure 5.2 – Clearances
Place the appliance preferably far from environments where silence is required, such as bedrooms, meeting rooms, etc. Evaluate the noise impact of the appliance in consideration of the installation site: avoid installing the appliance in positions that could amplify its running noise (reverb effect).
5.3 HYDRAULIC CONNECTIONS
General indications
The hydraulic installation may be realized using pipes in stainless steel, black steel, •
copper or crosslinked polyethylene for heating/cooling applications. All water
pipes and pipe connections must be properly insulated in compliance with cur-
rent regulations to prevent heat losses and outer condensation.
To prevent icing in the primary circuit during winter time, the appliance is provided •
with antifreeze functions activating the water circulation pump of the primary cir-
cuit (if controlled by the appliance) and the burner of the appliance itself (when
necessary). It is therefore necessary to ensure a permanent supply of electricity
and gas to the appliance throughout the whole winter period. If it is not possible
to ensure a permanent supply of electricity and gas to the appliance, use glycol
antifreeze of the inhibited monoethylene type.
If glycol antifreeze is to be used (see Paragraph 5.6 FILLING OF HYDRAULIC CIR-•
CUIT → 34), DO NOT USE galvanised pipes, as they are potentially subject to corro-
sion phenomena in the presence of glycol.
If using rigid pipes, use vibration damping couplings at the water and gas connec-•
tions on the appliance's service plate to prevent vibration. As other hydronic appliances, Robur heating and cooling systems operate with grid-wa­ter of good quality. In order to prevent any possible problem of operation or reliability caused by filling or top-up water, please refer to codes and norms about water treatment for thermo-hydraulic installations in civil or industrial applications. Parameters indicated in Table 5.1 Chemical and physical parameters of water → 29 must be complied with.
Page 29
Installation, user and maintenance manual – GAHP-GS/WS
29
Table 5.1 – Chemical and physical parameters of water
CHEMICAL AND PHYSICAL PARAMETERS OF WATER IN HEATING/COOLING SYSTEMS PARAMETER UNIT OF MEASUREMENT ALLOWABLE RANGE
pH \ >7
(1)
Chlorides mg/l < 125
(2)
Total hardness (CaCO3)
°f < 15 °d < 8,4
Iron mg/kg < 0,5
(3)
Copper mg/kg < 0,1
(3)
Aluminium mg/l < 1 Langelier’s index \ 0-0,4
HARMFUL SUBSTANCES
Free chlorine mg/l < 0,2
(3)
Fluorides mg/l < 1 Sulphides ABSENT
1 with aluminium or light alloys radiators, pH must also be lower than 8 (in compliance with applicable rules) 2 value referred to the maximum water temperature of 80 °C 3 in compliance with applicable rules
Water quality can be measured through parameters like acidity, hardness, conductivity, chlorides content, chlorine content, iron content and the like.
The presence of free chlorine in the water, in particular, can jeopardize parts of the instal­lation and Robur units. Therefore, please make sure that free chlorine content and total hardness are compliant with the allowable ranges reported in Table 5.1 Chemical and physical parameters of water → 29.
The way the installation is operated can be the cause of possible degradation of water quality. Moreover, abnormally massive water top-up or reintegration can cause a drift of chemical or physical above-mentioned parameters. Reintegration should not exceed 5% per year of the total amount of water. It is advised to check regularly the water quality, especially in case of automatic or periodic top-up. In case water treatment is needed, this operation should be carried out by a professional or competent person, following strictly the instructions by the manufacturer or supplier of the chemical substances for the treatment, since dangers could arise for health, for the environment and for Robur appliances. Several products for water treatment are available on the market. Robur does not perform detailed market surveys. Therefore Robur suggests to contact Companies which are specialized in water treatments. They will be able to suggest the best way how to proceed according to the type of installation. In case washing of the pipes is needed, this operation should be carried out by a profes­sional or competent person, following strictly the instructions by the manufacturer or supplier of the chemical substances for the washing, avoiding the use of substances ag­gressive for stainless steel or containing/releasing free chlorine. Please make sure the pipes are properly rinsed in order to remove any residue of chemi­cal substances from the pipes. Robur is not liable for ensuring that water quality is always compliant with what reported in Table 5.1 Chemical and physical parameters of water → 29. Non-compliance with in­dications above may jeopardize the proper operation, integrity and reliability of Robur appliances, invalidating the warranty. For any further detail, please contact directly Robur S.p.A. (tel.+39 035.888.111). The components below are always to be fitted in proximity to the appliance:
FLEXIBLE JOINTS on water and gas connections of the appliance.• PRESSURE GAGES on the inlet and outlet water pipes.•
Page 30
30
FLOW REGULATION VALVE on the water inlet pipe (only if the appliance is control-•
led by a CCP/DDC).
WATER FILTER installed on the water inlet pipe.•
ISOLATION BALL VALVE on the water and gas pipes of the installation.•
3 BAR SAFETY VALVE installed on the outlet water pipe.•
PLANT EXPANSION TANK installed in the appliance outlet water pipe.•
EXPANSION TANK for the individual appliance, installed on the water outlet pipe •
(primary side). Provide a plant expansion tank in any case (secondary side), in-
stalled in the water outlet pipe.
The appliance is not equipped with an expansion tank; therefore it is necessary to install a suitable expansion tank, sized for the maximum temperature range and maximum op­erating water pressure of the plant.
variable rate WATER CIRCULATION PUMP, FOR PLANT WITH A SINGLE APPLIANCE, •
located on the water inlet pipe of the appliance, flowing towards the appliance.
variable rate WATER CIRCULATION PUMP, FOR PLANT WITH A SEVERAL APPLIANCES •
(each appliance have is pump), flowing towards the appliance.
PLANT FILLING SYSTEM: if automatic filling systems are used, a seasonal check of •
the percentage of monoethylene glycol in the plant is recommended.
For other components to be installed in the system, refer to "Design Manual". For fur­ther information or technical support in this regard, contact Robur S.p.A.'s Presales Office (tel.+39 035.888.111) or visite site www.robur.it.
The operations necessary for the First Activation or Regulation of the appliance must be carried out exclusively by an authorised Robur Technical Assistance Centre (TAC). These operations are described in Section 7 INITIAL ACTIVATION AND MAINTENANCE → 73.
The products' guarantee is void if initial activation is not carried out by a Robur TAC.
5.4 GAS SUPPLY
The installation of gas supply pipes must be compliant with current regulations and norms. The gas supply pressure must be in the range given in Table 5.2 Network gas pressure → 31.
Supplying gas to the appliance at pressures higher than those indicated above can dam­age the gas valve, resulting in dangerous situations.
LPG systems must be equipped with a first stage pressure reducer close to the LPG stor­age tank, in order to reduce the gas pressure to 1,5 bar, and a second stage pressure reducer, close to the unit, in order to reduce pression from 1,5 bar to the value in agree­ment with the gas network pressure of the country of installation (see Table 5.2 Network gas pressure → 31).
Exemple for the Italian market: for the G30 gas, from 1,5 bar to 0,030 bar (30mbar); for the G31 gas, from 1,5 bar to 0,037 bar (37mbar).
Page 31
Installation, user and maintenance manual – GAHP-GS/WS
31
LPG may cause corrosion; piping and fitting materials must be resistant to this corrosion.
Vertical gas pipes must be equipped with a siphon and provided with a drain for the con­densate that may form inside the pipe during cold periods. It may also be necessary to insulate the gas pipe to prevent the formation of excessive condensate.
In any case, provide an isolation valve (ball valve) on the gas supply line, to isolate the appliance when required.
Table 5.2 – Network gas pressure
E3-GS; E3-WS; E3-A; GAHP-GS; GAHP-WS; GAHP-A Gas supply pressure Product categories Countries of destination G20 [mbar] G25 [mbar] G30 [mbar] G31 [mbar] G25.1 [mbar] G27 [mbar] G2,350 [mbar]
II
2H3B/P
AL, BG, CY, CZ, DK, EE, FI, GR, HR, IT, LT, MK, NO, RO, SE, SI, SK, TR
20 30 30
AT, CH 20 50 50
II
2H3P
AL, BG, CZ, ES, GB, HR, IE, IT, LT, MK, PT, SI, SK, TR
20 37
RO 20 30
II
2ELL3B/P
DE 20 20 50 50
II
2Esi3P
FR 20 25 37
II
2HS3B/P
HU 25 30 30 25
II
2E3P
LU 20 50
II
2L3B/P
NL 25 50 50
II
2E3B/P
PL
20 37 37
II
2ELwLs3B/P
20 37 37 20 13
II
2ELwLs3P
20 37 20 13
I
2E(R)B ; I3P
BE 20 25 37
I
3P
IS 30
I
2H
LV 20
I
3B/P
MT
30 30
I
3B
30
For data regarding hourly fuel consumption of the appliance, refer to Tables 3.1 GS HT/LT technical data → 12 and 3.2 WS technical data → 13.
5.5 CONDENSATE DISCHARGE
INDOORS UNITS
The fumes condensate outlet is on the left of the appliance. The appliance is equipped with a siphon with a piece of pipe connected. If you wish to use the pipe supplied with the unit, proceed as follows:
Connect the pipe to a plastic discharge manifold of the proper length.1. The connection between the pipe and the manifold must remain visible.2.
Page 32
32
Figure 5.3 – Position of condensate discharge and manual reset fumes thermostat
Position of condensate discharge and manual reset fumes thermostat
LEGEND
D Condensate discharge E Hose connecting to condensate siphon F Fumes outlet G Fumes thermostat manual reset
The condensate discharge to the sewer must be:
sized so as to discharge the maximum condensation flow (see Table 3.1 GS HT/LT •
technical data → 12 and Table 3.2 WS technical data → 13 under the respective
heading);
made of materials resistant to acidity with pH 3 to 5;•
sized to ensure a slope of 10 mm per metre of length; if this slope cannot be •
achieved, a condensate pump must be installed near to the discharge;
realized in such a way as to prevent icing of the condensate;•
mixed, for example, with domestic effluents (washing machine, dishwasher, etc.), •
usually alkaline, acting as a buffer solution before discharging into the sewer.
Do not discharge the condensate into the guttering, since it may ice and corrode the materials normally used for gutters.
CHARGING THE SIPHON
To charge the siphon, proceed as follows:
Connect the condensate discharge pipe to a drain.1.
Remove the bottom left side panel to access the siphon.2.
3. If no fumes exhaust equipment has been installed: pour 0.2 litres of water di-
rectly into the plastic pipe (detail F in Figure 5.3 Position of condensate discharge
and manual reset fumes thermostat → 32 and check that it is full. Then proceed to
point 6.
4. If the fumes exhaust equipment has already been installed: remove the clamp
securing the plastic pipe E to the siphon (see Figure 5.3 Position of condensate
discharge and manual reset fumes thermostat → 32), disconnect the plastic pipe E
from the siphon and fill it with 0.2 litres of water.
Page 33
Installation, user and maintenance manual – GAHP-GS/WS
33
Reconnect the plastic pipe E and secure it with its clamp.5. Fit the bottom left side panel.6.
If the appliance is operated with the siphon empty, there is a risk of leaks of exhaust flue gas.
OUTDOORS UNITS
The fumes condensate outlet is on the left of the appliance.
The distance L between the coupling and the base may not exceed 110 mm.
The condensate discharge corrugated pipe, coming out from the side of the un-1. derbase left support, must be connected to a proper discharge header. The connection between the pipe and the manifold must remain visible.2.
Figure 5.4 – Position of condensate discharge outdoors units
Position of condensate discharge outdoors units
LEGEND
A Condensate discharge hose
D Corrugated hose
The condensate discharge to the sewer must be:
sized so as to discharge the maximum condensation flow (see Table 3.1 GS HT/LT • technical data → 12 and Table 3.2 WS technical data → 13 under the respective heading); made of materials resistant to acidity with pH 3 to 5;•
Page 34
34
sized to ensure a slope of 10 mm per metre of length; if this slope cannot be •
achieved, a condensate pump must be installed near to the discharge;
realized in such a way as to prevent icing of the condensate;•
mixed, for example, with domestic effluents (washing machine, dishwasher, etc.), •
usually alkaline, acting as a buffer solution before discharging into the sewer.
Do not discharge the condensate into the guttering, since it may ice and corrode the materials normally used for gutters.
5.6 FILLING OF HYDRAULIC CIRCUIT
After having completed all hydraulic, gas and electrical connections, the installer can proceed filling the hydraulic circuit, observing the following steps:
You will need: the appliance connected hydraulically and electrically.
COLD CIRCUIT GAHP-GS
Check that the system delivery and return are correctly connected to the appli-1.
ance’s respective fittings (see Figure 3.1 Size → 15).
Activate the automatic air purging valves of the plant and open all thermostatic 2.
valves.
Fill the hydraulic circuit to at least the minimum amount and add inhibited mo-3.
noethylene glycol to a volume percentage of 25% (obligatory minimum required
for correct system operation) or greater depending on the minimum winter tem-
perature in the installation area (see Table 5.3 Technical data for filling the hydraulic
circuit → 36). Robur recommends using inhibited corrosion resistant monoethyl-
ene glycol.
Check the filter on the return pipe for impurities; clean it if necessary.4.
Check that the siphon on the drainage condenses has been filled with water as 5.
indicated in the relative paragraph.
Bring the plant to the correct pressure, making sure that the water pressure is not 6.
less than 1 bar and not over 2 bar, and run the circu lation pump for at least 30 min-
utes. Check the water filter again and clean it if necessary.
The technical data (Tables 3.1 GS HT/LT technical data → 12 and 3.2 WS technical da­ta → 13) regarding the cold circuit refer to water with 25% glycol content, so that no correction factor need to be applied to Table 5.3 Technical data for filling the hydraulic circuit → 36.
To facilitate the operation of bleeding air from the hydraulic circuit, the appliance is equipped with an additional manual air bleeding valve.
COLD CIRCUIT GAHP-WS
Check that the system delivery and return are correctly connected to the appli-1.
ance’s respective fittings (see Figure 3.1 Size → 15).
Activate the automatic air purging valves of the plant and open all thermostatic 2.
valves.
Page 35
Installation, user and maintenance manual – GAHP-GS/WS
35
Fill the hydraulic circuit to at least the minimum amount and add inhibited mo-3. noethylene glycol to a volume percentage in proportion to the minimum winter temperature in the installation area (see Table 5.3 Technical data for filling the hy­draulic circuit → 36). Robur recommends using inhibited corrosion resistant mo­noethylene glycol.
Glycol antifreeze may not be used on condition that the antifreeze function, which runs the circulation pumps, is activated at the CCI/DDC. This function requires the appliance to be ALWAYS powered up (electricity and gas) and power failures ex­cluded, otherwise the manufacturer declines all contractual and extra-con-
tractual liability for consequent damage.
Check the filter on the return pipe for impurities; clean it if necessary.4. Bring the plant to the correct pressure, making sure that the water pressure is not 5. less than 1 bar and not over 2 bar, and run the circu lation pump for at least 30 min­utes. Check the water filter again and clean it if necessary.
The technical data (Tables 3.1 GS HT/LT technical data → 12 and 3.2 WS technical da­ta → 13) regarding the cold circuit refer to water with 25% glycol content, so that no correction factor need to be applied to Table 5.3 Technical data for filling the hydraulic circuit → 36.
To facilitate the operation of bleeding air from the hydraulic circuit, the appliance is equipped with an additional manual air bleeding valve.
HOT CIRCUIT (Heating, sanitary hot water)
Check that the system delivery and return are correctly connected to the appli-1. ance’s respective fittings (see Figure 3.1 Size → 15). Activate the automatic air purging valves of the plant and open all thermostatic 2. valves. Fill the hydraulic circuit to at least the minimum amount and add inhibited mo-3. noethylene glycol to a volume percentage in proportion to the minimum winter temperature in the installation area (see Table 5.3 Technical data for filling the hy­draulic circuit → 36). Robur recommends using inhibited corrosion resistant mo­noethylene glycol.
Glycol antifreeze may not be used on condition that the antifreeze function, which runs the circulation pumps and the appliance, is activated at the CCI/DDC. This function requires the appliance to be ALWAYS powered up (electricity and gas) and power failures excluded, otherwise the manufacturer declines all contractual
and extra-contractual liability for consequent damage.
Check the filter on the return pipe for impurities; clean it if necessary.4. Check that the siphon on the condensate discharge has been filled with water as 5. indicated in Paragraph 5.5 CONDENSATE DISCHARGE → 31 under "Loading the siphon". Bring the plant to the correct pressure, making sure that the pressure of the water 6. in the plant is not less than 1 bar and not over 2 bar, and run the circulation pump for at least 30 minutes. Check the water filter again and clean it if necessary.
Page 36
36
To facilitate the operation of bleeding air from the hydraulic circuit, the appliance is equipped with an additional manual air bleeding valve.
Use of glycol antifreeze
Glycols, normally used to lower the freezing point of water, are substances in an inter­mediate state of oxidation which, in the presence of oxidising agents such as oxygen, are transformed into corresponding acids. This transformation into acids increases the corrosive nature of the fluid contained in the circuit. For this reason, mixtures that are commercially available almost always contain inhibiting substances that are able to con­trol the pH of the solution. A condition necessary for the oxidation and degradation of glycol is the presence of an oxidising agent such as oxygen. In closed circuits in which no replenishment of water (and therefore of oxygen) occurs over time, once the oxygen ini­tially present has reacted, the degenerative phenomenon of glycol is hugely inhibited. Most circuits, however, are of the non-sealed type, and therefore receive a more or less continuous supply of oxygen. Therefore it is essential, whatever type of glycol is in question, to verify that it is ade­quately inhibited and that the necessary checks are regularly performed during its entire period of use.
Antifreeze liquids for cars, which do not contain inhibiting components other than ethyl­ene glycol, are not recommended for cooling and heating plants.
The manufacturer does not accept any contractual or extra-contractual liability for damages caused by the use or disposal of glycol antifreeze.
It is equally important to recall that the use of monoethylene glycol modifies the ther­mophysical characteristics of the water in the plant, and in particular its density, viscosity and average specific heat. Always check the date of expiry and/or degradation of the product with the supplier.
The technical data (Tables 3.1 GS HT/LT technical data → 12 and 3.2 WS technical da­ta → 13) regarding the hot circuit refer to non-glycolised water, so that the correction factors of Table 5.3 Technical data for filling the hydraulic circuit → 36 must be applied to obtain the consequent increased load drop of the system and penalisation of unit ef­ficiency in relation to the percentage of monoethylene glycol used.
Table 5.3 Technical data for filling the hydraulic circuit → 36 should be taken into account for the sizing of the pipes and the circulation pump (for calculation of internal pressure drops of the appliance, refer to Tables 3.1 GS HT/LT technical data → 12 and 3.2 WS tech­nical data → 13). Nevertheless, it is advisable to consult the technical specifications of the monoethylene glycol used. If automatic loading systems are used, a seasonal check of the quantity of glycol present in the plant is also necessary.
Table 5.3 – Technical data for filling the hydraulic circuit
% of MONOETHYLENE GLYCOL 10 15 20 25 30 35 40
WATER-GLYCOL MIXTURE FREEZING TEMPERATURE -3°C -5°C -8°C -12°C -15°C -20°C -25°C PERCENTAGE OF INCREASE IN PRESSURE DROPS -- 6% 8% 10% 12% 14% 16% LOSS OF EFFICIENCY OF UNIT -- 0,5% 1% 2% 2,5% 3% 4%
If the percentage of glycol is ≥ 30% (for ethylene glycol) or ≥ 20% (for propylene glycol):
then parameter 182 in menu 4 must be set to “1” (at the installer’s care).•
Page 37
Installation, user and maintenance manual – GAHP-GS/WS
37
5.7 EXHAUST FLUE GAS
The appliance is homologated for configuration as a type C and B installation. The follow­ing installations are possible: C13, C33, C43, C53, C63, C83, B23P and B33. The appliance is supplied in configuration C63. We list below the various types of installation and the necessary accessories.
For the sizing of the fumes exhaust pipe and the combustion air pipe, refer to Table 5.9 Fumes temperature and flow → 41.
In case of installation of more than one unit GS/WS connected to one flue pipe, it’s neces­sary to insert one clapet valve for each installed unit, in order to avoid the reflux of the flue through the unit that is not working.
Figure 5.5 – C13 type installation
Wall mounted co-axial outlet DN80/125 or DN60/100
LEGEND
See table below
The following table indicates which accessories are required for the installation shown in Figure 5.5 C13 type installation → 37
Table 5.4 – C13 type installation: wall mounted co-axial terminal
DN Re f. Description
80/125
A DN80/125 2xDN80 double fitting B Co-axial wall terminal DN80/125
E Co-axial pipe 80/125 L=1 m E Co-axial pipe 80/125 L=2 m F Co-axial bend 90° 80/125 F Co-axial bend 45° 80/125
60/100
A DN60/100 2xDN80 double fitting B Co-axial wall terminal DN60/100
E Co-axial pipe 60/100 L=1 m E Co-axial pipe 60/100 L=2 m F Co-axial bend 90° 60/100 F Co-axial bend 45° 60/100
Page 38
38
Figure 5.6 – C33 type installation
Roof mounted co-axial outlet DN80/125 or DN60/100
LEGEND
See table below
The following table indicates which accessories are required for the installation shown in Figure 5.6 C33 type installation → 38.
Table 5.5 – C33 type installation: roof mounted co-axial terminal
DN Re f. Description
80/125
A DN80/125 2xDN80 double fitting B Co-axial roof terminal 80/125 C Tile adaptor for sloped roof D Tile adaptor for flat roof E Co-axial roof pipe 80/125 L=1 m E Co-axial roof pipe 80/125 L=2 m F Co-axial bend 90° 80/125 F Co-axial bend 45° 80/125
60/100
A DN60/100 2xDN80 double fitting B Co-axial roof terminal 60/100 C Tile adaptor for sloped roof D Tile adaptor for flat roof E Co-axial roof pipe 60/100 L=1 m E Co-axial roof pipe 60/100 L=2 m F Co-axial bend 90° 60/100 F Co-axial bend 45° 60/100
Page 39
Installation, user and maintenance manual – GAHP-GS/WS
39
Figure 5.7 – C43 type installation
Fumes/combustion air collective pipes
LEGEND
See table below
The following table indicates which accessories are required for the installation shown in Figure5.7 C43 type installation → 39
Table 5.6 – C43 installation.
DN Re f. Description
80/125
A DN80/125 2xDN80 double fitting B Wall duct DN 80/125 C Flue mount kit DN80 D Flue cover DN80 with terminal
E Co-axial bend 90° 80/125 E Co-axial bend 45° 80/125 F Co-axial pipe DN80/125 L=1 m
F Co-axial pipe DN80/125 L=2 m G Pipe DN 80 L=1 m G Pipe DN 80 L=2 m H Bend 90° DN80
L Bend 45° DN80
60/100
A DN60/100 2xDN80 double fitting B Wall duct DN 60/100 C Flue mount kit DN60 D Flue cover DN60 with terminal
E Co-axial bend 90° DN60/100
E Co-axial bend 45° DN60/100
F Co-axial pipe DN60/100 L=1 m
F Co-axial pipe DN60/100 L=2 m G Pipe DN 60 L=1 m G Pipe DN 60 L=2 m H Bend 90° DN60
L Bend 45° DN60
Page 40
40
Figure 5.8 – C53 type installation
Roof mounted flue, wall mounted air intake
LEGEND
See table below
The following table indicates which accessories are required for the installation shown in Figure 5.8 C53 type installation → 40
Table 5.7 – C53 type installation: Roof mounted flue, wall mounted combustion air intake
DN Re f. Description
80
A
Double intake/exhaust kit DN80B C D Flue cover DN80 with terminal E Flue mount kit DN80 F Pipe DN80 L = 1 m F Pipe DN80 L = 2 m G Bend 90° DN80 H Bend 45° DN80
Page 41
Installation, user and maintenance manual – GAHP-GS/WS
41
Figure 5.9 – C53 type installation
Double wall mounted exhaust
LEGEND
See table below
The following table indicates which accessories are required for the installation shown in Figure 5.9 C53 type installation → 41
Table 5.8 – C53 type installation
DN Ref Description
80
B
Wall mounted terminal kit DN80C
D
F Pipe DN80 L=1 m
F Pipe DN80 L=2 m G Bend 90° DN80 H Bend 45° DN80
Double wall mounted exhaust
Table 5.9 – Fumes temperature and flow
Gas type Thermal capacity CO2 (%) TF (C°) Fumes flow (kg/h) Prevalenza residua (Pa)
G20
Nominal 9,10 65 42 80
Minimum 8,90 46 21 80
G25
Nominal 9,10 63,6 42 80
Minimum 8,90 45,7 21 80
G25.1
Nominal 10,10 65 45 80
Minimum 9,60 46 23 80
G27
Nominal 9,0 64 42 80
Minimum 8,5 46 21 80
G2.350
Nominal 9,00 62,7 42 80
Minimum 8,70 46,8 22 80
G30
Nominal 10,40 65 43 80
Minimum 10,10 46 22 80
G31
Nominal 9,10 65 48 80
Minimum 8,90 46 24 80
Page 42
42
5.8 PROGRAMMING OF HYDRAULIC PARAMETERS
The operations described in this paragraph are necessary only if the appliance is not con­nected to a DDC or to a CCP.
If the appliance is connected to a CCP/DDC, follow the instructions given in the CCP/DDC manuals exclusively.
This paragraph explains how to set the hydraulic parameters on the electronic board of the appliance. Users not familiar with the basic procedures for the use of the board should refer to Paragraph 4.2 ON-BOARD ELECTRONICS → 19. To configure the appliance, access menu 3 of the electronic board. With regard to the hydraulic configuration, six parameters may be set: select the letter E to exit to the previous menu.
Table 5.10 – Parameters for hydraulic configuration
HYDRAULIC PARAMETER THE DISPLAY SHOWS
Select cold water thermostating 3. 73 Cold water set-point 3. 75 Cold water temperature differential 3. 76 Hot water thermostat control selection 3.160 Hot water setpoint 3.161 Hot water temperature differential 3.162 (EXIT MENU) 3. E
Menu 3 parameters.
Description of parameters:
Water thermostat control, parameters 73 and 160. This parameter takes two val-• ues: "0" and "1". Value "0" indicates that the appliance's "activation/deactivation" temperature is to be read by the water probe at the appliance’s INTAKE. Value "1" indicates that the appliance’s "activation/deactivation" temperature is to be read by the water probe at the appliance’s OUTLET. Water set-point, parameters 75 and 161: these parameters set the water tempera-• ture that, when reached, causes the appliance to be deactivated (when the power modulation is not active - parameter 181). Water differential, parameters 76 and 162: these parameters represent an interval • in degrees that, when added to the set-point, defines the temperature at which the appliance is reactivated. These parameters are used only if the power modulation
is NOT active (parameter 181). The appliance functions by heating/cooling the water until it reaches the set-point tem­perature. At this point, if the power modulation is not active (parameter 181), it switches off. The temperature of the water goes down again until it reaches the temperature cor­responding to "set-point + differential"; when this is reached the appliance switches on again. Example (heating): Thermostating: reading from inlet sensor. Parameter 181: 0 (power modulation NOT active) Set-point: +40.0°C Differential: - 2.0° C
The appliance is functioning: the water in the plant heats up until it reaches the •
set-point temperature = +40°C.
Page 43
Installation, user and maintenance manual – GAHP-GS/WS
43
The appliance switches off: the water in the plant, returning from use, becomes • progressively cooler, until it reaches a temperature of 38°C = 40°C - 2°. The appliance switches on again, and the plant water heats up again.•
The cycle is repeated.• The following procedure illustrates in detail how to configure the parameters on the elec­tronic board inside the appliance.
If the procedures for how to access the knob and menus are not familiar, see paragraphs "Display and knob" and "How to access the menus" and following.
To set the parameters of menu 3:
You will need: the appliance on and access to the electrical panel, see "Display and knob".
Access menu 3. The display shows the first parameter of the menu, number 73.
Turn the knob clockwise to scroll through the parameters: 3.73, 3.75, 3.76, 3.160, 1.
3.161, 3.162; lastly the letter E is shown.
Press the knob when a parameter is displayed to select it, or when E is displayed to 2.
exit the menu.
For example, to set parameter 161 (hot water set-point), proceed as follows:3.
· Select the parameter: turn the knob until the display shows 3.161;
· Press the knob to access the value of the parameter; the display shows the previ-
ously set value, which flashes, for example 40.0 °C;
· Turn the knob to modify the value of the parameter;
· Press the knob to confirm the value selected; the display shows the current pa-
rameter again, 3.161. The new value for this parameter has been set.
If other parameters are to be modified, proceed as described previously, and then 4.
exit from the menu by pressing the knob on the letter E. To exit the menu, turn the knob clockwise until E is displayed, then press it to confirm. For details regarding the codes displayed by the appliance during operation, see Paragraph
9.1 OVERVIEW AND OPERATING CODES/TROUBLESHOOTING → 82.
5.9 SAFETY VALVE DISCHARGE ROUTING
Standard EN378-3 requires that potential leaks of refrigerant be discharged outside the machine room. To meet this requirement, the appliance has an outlet on its top panel (detail Q of Figure
3.1 Size → 15) to which a pipe can be fitted to route the refrigerant vented by the safety valve on the sealed circuit out of the machine room.
DO NOT fit any check equipment (valve, etc.) between outlet Q (Figure 3.1 Size → 15) and the external discharge of the evacuation pipe. The manufacturer does not accept any contractual or extra-contractual liability for any damage caused by improper use of the said pipe.
The missing right installation of the canalization of the security valve might cause dan­gerous situations inside the installation room. The unit can be switched-on only if the right canalitation is installed, as indicated in the following.
Install the pipe as instructed below.
Page 44
44
You will need: the appliance in its permanent location.
Remove the plastic cap on the top panel (detail Q of Figure 3.1 Size 1. → 15). Connect a carbon steel pipe to the Q outlet, which must have an initial straight 2. tract of at least 30 cm. The maximum length of the pipe is indicated in Table 5.11 Maximum coolant pipe length → 44). Fix the pipe to the nut on the outlet (5.10 Over-pressure valve 3. → 44) and make sure to fit the Teflon gasket provided with the appliance for this purpose.
Figure 5.10 – Over-pressure valve
Position of the valve
LEGEND
Detail of the refrigerant flexible ducting pipe
The evacuation terminal must be outside the machine room, away from doors, 4. windows and ventilation openings; the terminal must be located at a height such as to prevent any leaks of refrigerant fluid being inhaled by persons walking in the vicinity of the terminal itself.
The refrigerant discharge pipe MUST be in carbon steel. NEVER use copper or derivate alloys such as brass for this purpose.
The missing canalitation of the security valve might cause danger conditions inside the installation room.
Table 5.11 – Maximum coolant pipe length
Diameter DN Maximum length (m) 1" 1/4 32 30 2" 52 60
Maximum coolant pipe length
Page 45
Installation, user and maintenance manual – GAHP-GS/WS
45
6 ELECTRICAL INSTALLATION
This section illustrates the operations to perform for the correct electrical installation of the appliance, and contains electrical diagrams that may be of use in the event of main­tenance operations.
Installation of the appliance may only be carried out by firms that are qualified in accord­ance with current legislation in the country of installation, i.e. by professionally qualified personnel.
Before proceeding with operations to create the electrical plant of the appliance, the professionally qualified personnel concerned are advised to read Paragraph 3.1 GENERAL INFORMATION → 8: it provides important information regarding installation safety and references to current norms.
Installation that is incorrect or that does not comply with current legislation may cause damage to people, animals or things; Robur S.p.A. is not responsible for any damage caused by installation that is incorrect or that does not comply with current legislation.
Figure 6.1 Electronic board S61 → 46 and Table 6.1 S61 electronic controller + Mod10 legend → 46 provide details of input and ouput of the S61 electronic board. The auxiliary electronic card Mod10 is shown in detail in Figure 6.2 Mod10 controller → 47. The appliance and the system can be controlled and regulated in one of the following ways depending on the type of installation and control system selected:
• TYPE A: controlled by CCP (see Figure 6.4 Comfort Control Panel e Accessory → 48,
detail CCP).
• TYPE B: controlled by DDC (see Figure 6.3 CCI/DDC → 47).
• TYPE C: controlled by consent switch (e.g. on-off switch, ambient thermostat, tim-
er, etc.).
In Paragraph 6.1 ELECTRICAL DIAGRAM OF THE APPLIANCE → 49 may be found the Elec- trical diagrams of the appliance.
Page 46
46
Figure 6.1 – Electronic board S61
SCH S61
LEGEND
See table below
Table 6.1 – S61 electronic controller + Mod10 legend
CODE DESCRIPTION SCH1 Electronic board S61 SCH3 Mod10 electronic controller (see figure for further details) A1, A2 Auxiliary inputs ENC Knob F1 Fuse T 2A F2 Fuse F 10A F3 Fuse T 2A F4 Fuse T 3.15A FAN (BK, WH, BR) Cooling fan output FL Flow switch input FS5 (24V AC) Controller power 24-0-24 Vac IGN.BOX (L, N) Flame controller power 230 V AC J1 CAN BUS jumper J10 Jumper N.O. contact J82 W10 board connector (on Mod10) JP10 6-pole flame controller connector JP12 Fumes sensor or generator fin sensor input JTA G S61 controller programming connector MAIN 230V (L,N) S61 controller power 230 V AC N.O. contact Pump contact, N.O. P7 (R, W, Y, o) Consent inputs P8 (GND, L, H) CAN BUS connector PUMP 230V (L,N) Hydraulic pump power output SPI Communication port with Mod10 controller SRT1 Hydraulic pump rotation sensor input SRT2 Hot water flowmeter input TA Ambient temperature probe input TA1 Hot water delivery temperature probe input TA2 Hot water return temperature probe input TCN Combustive air temperature probe input TF Exhausted gas thermostat input
Page 47
Installation, user and maintenance manual – GAHP-GS/WS
47
CODE DESCRIPTION TG Generator temperature probe input THMF Cold water delivery temperature probe input THRF Cold water return temperature probe input TL Generator limit thermostat input
Figure 6.2 – Mod10 controller
Mod10 controller
LEGEND
HFLOW Not used CFLOW Condensation water sensor control J51 SPI connector HPMP Primary circuit hot water pump control
output (0-10 V) [A/GS/WS]
CPMP Cold side water pump control output
[GS/WS] NC1-C1 Status indication of locking warnig/error CN5 Blower control J82 W10 auxiliary controller connector J83 W10 cable shielding connection W10 CN1 Inputs 0-10V (not used)
Figure 6.3 – CCI/DDC
Page 48
48
Figure 6.4 – Comfort Control Panel e Accessory
LEGEND
CCP Comfort Control Panel Components componing the CCP AVS37 Comfort Control Siemens RVS61 System controller and set-point CCI Comfort Control Interface PLC Programmable Logic Control AVS75 Expansion
Optional components to predict QAA55 Base room unit QAA75 Room unit QAA78 Radio room unit ASV71 Antenna AVS13 Transmitter QAC34 External temperature probe LPS Central communications for remote control
Page 49
Installation, user and maintenance manual – GAHP-GS/WS
49
6.1 ELECTRICAL DIAGRAM OF THE APPLIANCE
Figure 6.5 – Appliance internal wiring diagram
LEGEND
SCH1 S61 circuit board
SCH2 W10 circuit board
SCH3 Mod10 circuit board
TER Appliance power terminal block
CNTBOX Flame controller
PWRTR Board transformer
BLW Blower
PMP Hydraulic pump
IGNTR Ignition transformer
IGN Ignition electrodes
FLS Flame sensor
LS Gas valve ON indicator lamp
GV Gas solenoid valve
THMF Cold water delivery temperature sensor
THRF Cold water return temperature sensor
TMIX Combustion air temperature sensor
TA Ambient air temperature sensor
TG Generator temperature sensor
THMC Hot water delivery temperature sensor
THRC Hot water return temperature sensor
REED Hydraulic pump rotation sensor
TF Fumes temperature sensor or generator fin sensor
TC Manual fumes thermostat
TL Generator limit thermostat
FM Hot side flowmeter
FL Renewable source water flow switch
CWS Condensation water sensor
MA Terminal block
TK Condensate discharge heating element thermostat
FS Condensate hose heating element
Page 50
50
6.2 HOW TO CONNECT THE APPLIANCE ELECTRICALLY
Before making electrical connections, make sure not to work on live elements.
You will need: the appliance in its permanent location.
Use a cable type FG7(O)R 3Gx1.5 for the power supply to the appliance.1. Connect power supply with the cable indicated at point 1, fitting close to the appli-2. ance a two-pole isolator switch with 3 mm distance between contacts (see detail «GS» in Figure 6.6 Electrical wiring diagram → 50) and two 5A fuses type T or a 10A magnetothermic breaker. Prepare the electrical connection in such a way that the ground wire is longer than 3. the live wires. In this way it will be the last wire to be torn away if the cable is ac­cidentally pulled off; this will ensure the ground connection.
Electrical safety is ensured only when the appliance is correctly connected to an efficient grounding system, realized according to current safety regulations. Do not use gas pipes as grounding.
Figure 6.6 – Electrical wiring diagram
Example of connection of appliance to 230 V 1 N - 50 Hz electricity supply
LEGEND
TER terminal board L phase N neutral Components NOT SUPPLIED GS general switch
6.3 TYPE A COMFORT CONTROL PANEL
This paragraph illustrates the operations to be performed when one or more appliances are connected to a Comfort Control Panel (CCP). In particular:
What is the CAN BUS cable.1. How to connect the CAN BUS cable to the appliance's electronic board2. How to connect the CAN BUS cable to the Comfort Control Panel3. How to connect the Comfort Control Panel4. How to connect the system water circulation pumps5.
For specific information regarding the operation and programming of the CCP, refer to the specific manuals supplied with it.
The appliance and the CCP communicate with each other via a CAN bus network.
Page 51
Installation, user and maintenance manual – GAHP-GS/WS
51
The CAN bus network is characterized by a series of elements (appliances or CCPs) called nodes, connected to each other by a three-wire cable. The nodes are of two types: termi­nal nodes and intermediate nodes.
Terminal nodes are appliances or CCPs that are connected to one other element • only. Intermediate nodes are appliances or controllers which are connected to two other •
elements. The diagram in Figure 6.7 Example of CAN BUS → 51 gives an example of a CAN BUS network: 3 appliances are connected to each other and to 1 CCP. Appliance D and the CCP (A) are terminal nodes, while appliances C and B are intermediate nodes as they are connected to 2 elements.
One CCP can control up to 3 appliances of the same type.
Figure 6.7 – Example of CAN BUS
Terminal nodes and intermediate nodes
LEGEND
A Controller
B-C-D Appliance 1-4 Terminal nodes
2-3 Intermediate nodes
What is the CAN BUS cable
The cable to be used must be suitable for CAN BUS applications.
The following table gives details of some types of CAN BUS cables, grouped according to the maximum distance covered by each single type.
Table 6.2 – CAN BUS cables type
CABLE NAME SIGNAL / COLOR MAX LENGTH Note Robur
Ordering Code O-CVO008
ROBUR NETBUS H= BLACK L= WHITE GND= BROWN 450 m
Honeywell SDS 1620
In all cases the fourth conductor should not be used
BELDEN 3086A
H= BLACK L= WHITE GND= BROWN 450 m
TURCK type 530
DeviceNet Mid Cable
TURCK type 5711 H= BLUE L= WHITE GND= BLACK 450 m
Honeywell SDS 2022
TURCK type 531 H= BLACK L= WHITE GND= BROWN 200 m
Example types of cables used to connect the CAN network.
For total distances lower than 200 m and networks with a maximum of 4 nodes (example: up to 3 GAHP + 1 controller) a simple shielded cable 3x0.75 mm may be used.
Page 52
52
As shown in Table 6.2 CAN BUS cables type → 51, the CAN connection requires a CAN BUS cable with 3 cores. If the cable available has more than 3 coloured wires, use the wires with the colours indicated in 6.2 CAN BUS cables type → 51 and cut the remaining ones. The ROBUR NETBUS cable is available as an accessory, see Section 8 ACCESSORIES → 81.
How to connect the CAN BUS cable to the appliance's electronic board
The CAN BUS cable must be connected to the dedicated terminals on the appliance’s electronic board, as shown below (see Figure 6.8 CAN BUS cable connection → 52).
Figure 6.8 – CAN BUS cable connection
Example of a single CAN bus cable connected to the board
LEGEND
A protective isolating tape B shielding of CAN BUS cable (pre-
wired to last unit)
C cable bracket (the CAN BUS cables
of an intermediate node are present) D CAN BUS/circuit board connector E wires (6) of the CAN BUS cable
(intermediate node)
A
A
B
C
E
D
Before working on the electrical panel of the appliance, make sure that power supply is off.
Cut a length of cable long enough to allow installing it without kinking.1. On one end of the cable, remove the jacket for a length of approximately 70-80 2. mm, taking care not to cut the shielding (metal mesh and/or aluminium sheet and, if present, the bare connector in touch with the shield) and the wires contained within. If the cable is too thin to be held in place in the cable holding bracket (detail C in 3. Figure 6.8 CAN BUS cable connection → 52), make it thicker by wrapping insulat­ing tape around the jacket close to the stripped part (to an approximate diameter of 12-13 mm). Pull back the shielding on the jacket; apply isolating tape to the end of the shield-4. ing as pulled back (detail A, Figure 6.8 CAN BUS cable connection → 52). If the appliance is a 5. terminal node of the network connect the three coloured wires to the orange connector as shown in detail "A" of Figure 6.9 Electrical wir­ing diagram → 53. Respect the correct indications L, H, GND provided in Table 6.2 CAN BUS cables type → 51, on the figure and on the electronic board below the connector. If the appliance is an 6. intermediate node repeat the operations from step 2 to step 5 for the other cables required (in this way you will have two cable lengths each one without the jacket on one end). Twist together the cores with the same color and connect them to the orange connector, as shown in detail "B" of Figure 6.9 Electrical wiring diagram → 53.
Page 53
Installation, user and maintenance manual – GAHP-GS/WS
53
Fix the CAN BUS cable (or two cables, according to the type of node being con-7. nected) to the holding bracket in the upper part of the electrical panel so that the pulled-back shielding is in solid touch with the metal bracket. The cables must be firmly held in place by the bracket if pulled. In order to position the jumpers on the electronic board according to the type of node being configured: If the appliance is a • terminal node on the network (i.e. 3 wires are inserted in the orange connector on the board): set the jumpers as shown in detail "A" of Figure
6.9 Electrical wiring diagram → 53: If the appliance is an • intermediate node on the network (i.e. 6 wires are inserted in the orange connector on the board); set the jumpers as shown in detail "B" of Figure 6.9 Electrical wiring diagram → 53:
Figure 6.9 – Electrical wiring diagram
Connection cable CAN BUS to electronic board: detail A case "terminal node", detail B case "intermediate node"
LEGEND
SCH electronic board GND Common data L Data signal LOW
H Data signal HIGH J1 Jumper CAN-BUS in board A Detail case "terminal node" (3 wires;
J1=jumper "closed")
B Detail case "intermediate node" (6
wires; J1=jumper "open")
P8 Port can/connector
After finished with all the above operations, close the electrical panel and refit the 8. front panel of the appliance.
How to connect the CAN BUS cable to the Comfort Control Panel
The CAN bus cable is connected to the specific orange connector (P8) supplied with the CCP in a bag.
Before working on the Comfort Control Panel, make sure that it is off.
The CCP, like the controller on the appliance, has jumpers that must be moved so that it can be configured as an intermediate or terminal node. The position of the jumpers on a new CCP is CLOSED.
To connect the CAN bus cable to a CCP:
You will need: the Comfort Control Panel not powered up.
Open the Comfort Control Panel’s electrical panel with the handle on its left.1.
Page 54
54
Depending on the type of node being configured, set the CCI’s jumpers J21 as 2. shown in detail "A" or detail "B" in Figure 6.11 Connection of CCI to CAN-BUS net­work → 55. If necessary, open the CCI’s back panel (4 screws); after jumpers J21 have been correctly positioned, close the cover again and retighten the 4 bolts. Cut a length of cable long enough to allow installing it without kinking.3. Remove the sheath for a length of approximately 70-80 mm, taking care not to cut 4. the shielding (metallic shield and/or aluminium sheet and, if present, the bare con­nector in contact with the shield) and wires contained inside. Roll the shielding and connect it to a 4-mm eyelet terminal, as illustrated in Figure 5.
6.10 Connection from CAN BUS to connector P8 → 55, details C and D. Now pro­ceed as follows: If the CCP is a 6. terminal node of the network connect the three coloured wires to the orange connector "P8", as shown in detail "A" of Figure 6.11 Connection of CCI to CAN-BUS network → 55. Observe the terminal markings L, H, GND (on the CCI's board at the base of the socket "P8") which are given both in Table 6.2 CAN BUS cables type → 51 and in the example. If the CCP is an 7. intermediate node repeat the operations from step 2 to step 4 for the other length of CAN bus cable required. Connect the six coloured wires to the orange connector "P8", following the instruction provided in detail "B" of Figure
6.11 Connection of CCI to CAN-BUS network → 55. Observe the terminal markings L, H, GND (on the CCI's board at the base of the socket "P8") which are given both in Table 6.2 CAN BUS cables type → 51 and in the example. Insert the orange connector "P8" with the wires first into the opening prepared in 8. the cover of the CCI, and then into the appropriate socket on the CCI itself, making sure it is correctly inserted. Use the rear cover bolts located near the CAN BUS socket to secure the 4-mm 9. eyelet (or 2 eyelets) (detail D, Figure 6.10 Connection from CAN BUS to connector P8 → 55). The cable should be secured against pulling out.
The CCI has jumpers J21: the position of the jumpers, depends if the CCI is an interme­diate or terminal node, must be as shown in Figure 6.11 Connection of CCI to CAN-BUS network → 55.
The CCI is equipped with a backup battery which retains the memory settings in case of power failure. The backup battery lasts approximately 7 years, after which time it must be replaced by an authorised Robur Technical Assistance Centre.
Page 55
Installation, user and maintenance manual – GAHP-GS/WS
55
Figure 6.10 – Connection from CAN BUS to connector P8
Connection detail of cable CAN BUS.
LEGEND
A Insulating tape to protect board/shield B CAN BUS cable wires C CAN bus cable shield D terminal and screw for fixing

Figure 6.11 – Connection of CCI to CAN-BUS network
Jumpers J21 closed
LEGEND
CCI Comfort Control Interface P8 Orange connector J21 Jumpers CAN-BUS on CCI board
A detail of "terminal node" case (3 wires; J21=jumper "closed") B Detail of "intermediate node" case (6 wires; J21=jumper "open") H,L,GND Data signal wires
The following wiring diagrams show the connection of the CCI to 1 appliance (Figure 6.12 Connection of CCI to 1 appliance → 56) and 3 appliances (Figure 6.13 Connection of CCI to 3 appliances → 57) respectively.
Page 56
56
Figure 6.12 – Connection of CCI to 1 appliance
Connection of CCI to 1 appliance
LEGEND
SCH S61 controller
CCI Comfort Control Interface
Page 57
Installation, user and maintenance manual – GAHP-GS/WS
57
Figure 6.13 – Connection of CCI to 3 appliances
Connection of CCI to 3 appliances
LEGEND
SCH S61 controller
CCI Comfort Control Interface
How to connect the Comfort Control Panel
You will need: the appliance disconnected from the electricity supply
Page 58
58
The Comfort Control Panel’s power cord must be type tipo FG7 3Gx2.5mm1.
2
. the power supply is 230V AC 1N 50Hz. Cut a suitable length of cable.2. The cable must be connected to the terminal block on the bottom right of the 3. Comfort Control Panel. First make a hole in the electrical cabinet near to the termi­nal block and pass the cable through it. Connect the cable to the terminal block as given in Figure 6.6 Electrical wiring dia-4. gram → 50 and fit a 10 A thermal cut out upstream of the Comfort Control Panel.
How to connect the system water circulation pumps
Before making the electrical connections, make sure that work is not carried out on live elements.
To optimise the operation of the appliance install, on the primary circuit, variable rate WILO STRATOS PARA pumps (see Section 8 ACCESSORIES → 81), which are controlled and modulated with the Robur Mod10 controller.
No other models pump are supported.
The instruction for connecting the WILO STRATOS PARA pumps are given below (see Sec­tion 8 ACCESSORIES → 81). Each WILO pump includes its power cord (length 1.5 metres) and cable for connection to the appliance’s controller (1.5 metres). For longer cable runs, use a shielded 2x0.75 mm2 0-10V signal cable and a FG7 3Gx2.5mm2 power cord.
You will need: the appliance in its permanent location.
Check that power supply is off.1. Remove the front panel of the appliance and the cover of the electrical panel.2. Connect the brown wire of the WILO STRATOS PARA pump on the cold side to the 3. terminal "-" of connector CPMP on the Mod10 board. Connect the white wire of the WILO STRATOS PARA pump on the cold side to the terminal "+" of the connector CPMP on the Mod10 board. Insulated black and blue wires (see Figure 6.14 Wiring diagram for connection of Wilo variable rate pumps → 59). Connect the brown wire of the WILO STRATOS PARA pump on the hot side to the 4. terminal "-" of connector HPMP on the Mod10 board. Connect the white wire of the WILO STRATOS PARA pump on the hot side to the terminal "+" of the connector HPMP on the Mod10 board. Insulated black and blue wires (see Figure 6.14 Wiring diagram for connection of Wilo variable rate pumps → 59). Collegare la pompa alla rete elettrica prevedendo a monte un interruttore esterno 5. bipolare (vedi particolare IP di Figura 6.14 Wiring diagram for connection of Wilo variable rate pumps → 59) con fusibile da 2 A ritardato oppure collegarla ai mor­setti interni al quadro elettrico dell’unità (vedi particolare MA di Figura 6.15 Wiring diagram for hooking up the Wilo variable rate pump powered by the unit → 60). After finished with all the above operations, close the electrical panel and refit the 6. front panel of the appliance.
NEVER switch on or off the WILO STRATOS PARA pump through the switch on the power supply.
Page 59
Installation, user and maintenance manual – GAHP-GS/WS
59
Figure 6.14 – Wiring diagram for connection of Wilo variable rate pumps
Wiring diagram for connection of Wilo variable rate pumps
LEGEND
IP Two-position pump power switch F Fuse PMW Hot side water circulation pump (primary circuit) PMY Cold side water circulation pump
Pump signal 0-10V wire colours brown connect to -ve white white connect to +ve black isolate blue isolate
Page 60
60
Figure 6.15 – Wiring diagram for hooking up the Wilo variable rate pump powered by the unit
Wiring diagram for hooking up the Wilo variable rate pump powered by the unit
LEGEND
PMW Hot side water circulation pump
(primary circuit) PMY Cold side water circulation pump MA Unit terminal block
Pump signal 0-10V wire colours brown connect to -ve white connect to +ve black isolate blue isolate
6.4 TYPE B DDC
This paragraph illustrates the operations to be performed when one or more appliances are connected to a Direct Digital Controller (DDC). In particular:
What is the CAN BUS cable.1. How to connect the CAN BUS cable to the appliance's electronic board2. How to connect the CAN BUS cable to the DDC.3. How to connect the DDC.4. How to connect the plant water circulation pump.5.
For specific information regarding the DDC, refer to the specific manuals supplied with it.
The appliance and the DDC communicate with each other via a CAN bus network. The CAN bus network is characterized by a series of elements (appliances or DDCs) called nodes, connected to each other by a three-wire cable. The nodes are of two types: termi­nal nodes and intermediate nodes.
Page 61
Installation, user and maintenance manual – GAHP-GS/WS
61
Terminal nodes are appliances or DDCs that are connected to one other element • only. Intermediate nodes are appliances or DDCs that are connected to two other •
elements. The diagram in Figure 6.7 Example of CAN BUS → 51 gives an example of a CAN BUS network:3 appliances are connected to each other and to 1 DDC. Appliance D and the DDC (A) are terminal nodes, while appliances C and B are intermediate nodes as they are connected to 2 elements.
It is possible to place one DDC at any point of the CAN bus network: appliances and DDCs may act equally as terminal or intermediate nodes. One DDC can control and monitor up to 16 appliances. If there are more than 16 appliances on the network, it is necessary to connect more than one DDC on the same network, up to a maximum of 3.
What is the CAN BUS cable
The cable to be used must be suitable for CAN BUS applications.
Table 6.2 CAN BUS cables type → 51 gives details of some types of CAN bus cable, grouped according to the maximum distance covered by each single type.
For overall distances to cover of ≤200 m and networks with a maximum of 6 nodes (a typ­ical example: up to 5 GAHP + 1 DDC) a simple shielded cable 3x0.75 mm may be used.
As shown in Table 6.2 CAN BUS cables type → 51, the CAN connection requires a CAN bus cable with 3 wires. If the available cable has more than 3 coloured wires, use the wires with the colours indicated in 6.2 CAN BUS cables type → 51 and cut the remaining ones. The ROBUR NETBUS cable is available as an accessory, see Section 8 ACCESSORIES → 81.
How to connect the CAN BUS cable to the appliance's electronic board
The CAN BUS cable must be connected to the dedicated terminals on the appliance’s electronic board, as shown below (see Figure 6.8 CAN BUS cable connection → 52).
Before working on the electrical panel of the appliance, make sure that power supply is off.
Cut a length of cable long enough to allow installing it without kinking.1.
On one end of the cable, remove the jacket for a length of approximately 70-80 2.
mm, taking care not to cut the shielding (metal mesh and/or aluminium sheet and,
if present, the bare connector in touch with the shield) and the wires contained
within.
If the cable is too thin to be held in place in the cable holding bracket (detail C in 3.
Figure 6.8 CAN BUS cable connection → 52), make it thicker by wrapping insulat-
ing tape around the jacket close to the stripped part (to an approximate diameter
of 12-13 mm).
Pull back the shielding on the jacket; apply isolating tape to the end of the shield-4.
ing as pulled back (detail A, Figure 6.8 CAN BUS cable connection → 52).
If the appliance is a 5. terminal node of the network connect the three coloured
wires to the orange connector as shown in detail "A" of Figure 6.9 Electrical wir-
ing diagram → 53. Respect the correct indications L, H, GND provided in Table 6.2
CAN BUS cables type → 51, on the figure and on the electronic board below the
connector.
Page 62
62
If the appliance is an 6. intermediate node repeat the operations from step 2 to step 5 for the other cables required (in this way you will have two cable lengths each one without the jacket on one end). Twist together the cores with the same color and connect them to the orange connector, as shown in detail "B" of Figure 6.9 Electrical wiring diagram → 53. Fix the CAN BUS cable (or two cables, according to the type of node being con-7. nected) to the holding bracket in the upper part of the electrical panel so that the pulled-back shielding is in solid touch with the metal bracket. The cables must be firmly held in place by the bracket if pulled. In order to position the jumpers on the electronic board according to the type of node being configured: If the appliance is a • terminal node on the network (i.e. 3 wires are inserted in the orange connector on the board): set the jumpers as shown in detail "A" of Figure
6.9 Electrical wiring diagram → 53: If the appliance is an • intermediate node on the network (i.e. 6 wires are inserted in the orange connector on the board); set the jumpers as shown in detail "B" of Figure 6.9 Electrical wiring diagram → 53: After finished with all the above operations, close the electrical panel and refit the 8. front panel of the appliance.
How to connect the CAN BUS cable to the DDC
The CAN bus cable is connected to the specific orange connector (P8) supplied with the DDC in a bag.
Before working on the DDC, make sure that it is off.
The DDC, like the controller on the appliance, has jumpers that must be moved so that it can be configured as an intermediate or terminal node. The position of the jumpers on a new DDC is CLOSED.
To connect the CAN bus cable to a DDC
You will need: DDC not powered up.
Depending on the type of node being configured, set the DDC's jumpers J21 as 1. shown in detail "A" or detail "B" in Figure 6.16 detail wires and jumpers J21 - termi­nal/intermediate node CCI/DDC → 63. If necessary, open the DDC's back pa nel (4 screws); after jumpers J21 have been correctly positioned, close the cover again and retighten the 4 screws. If the DDC is an • intermediate node on the network (with no. 6 wires in the or- ange connector "P8"): set the jumpers "J21" as shown in detail "B" of Figure 6.16 detail wires and jumpers J21 - terminal/intermediate node CCI/DDC → 63: Jump­ers OPEN. If the DDC is an • terminal node on the network (with no. 3 wires in the orange con- nector "P8"): set the jumpers "J21" as shown in detail "A" of Figure 6.16 detail wires and jumpers J21 - terminal/intermediate node CCI/DDC → 63: Jumpers CLOSED. Prepare the orange CAN bus connector, from the supplied sleeve.2. Cut a length of cable long enough to allow installing it without kinking.3. Remove the sheath for a length of approximately 70-80 mm, taking care not to cut 4. the shielding (metallic shield and/or aluminium sheet and, if present, the bare con­nector in contact with the shield) and wires contained inside.
Page 63
Installation, user and maintenance manual – GAHP-GS/WS
63
Roll the shielding and connect it to a 4-mm eyelet terminal, as illustrated in Figure 5.
6.10 Connection from CAN BUS to connector P8 → 55, details C and D. Now pro-
ceed as follows:
If the DDC is an 6. terminal node connect the three coloured wires to the orange
connector "P8", following the diagram provided in detail "A" of Figure 6.16 detail
wires and jumpers J21 - terminal/intermediate node CCI/DDC → 63. Observe the
terminal markings L, H, GND (on the DDC at the base of the socket "P8") which are
given both in Table 6.2 CAN BUS cables type → 51 and in the example.
If the DDC is an 7. intermediate node repeat the operations from step 2 to step 4 for
the other length of CAN bus cable required. Connect the six coloured wires to the
orange connector "P8", following the diagram provided in detail "B" of Figure 6.16
detail wires and jumpers J21 - terminal/intermediate node CCI/DDC → 63. Observe
the terminal markings L, H, GND (on the DDC at the base of the socket "P8") which
are given both in Table 6.2 CAN BUS cables type → 51 and in the example.
Insert the orange connector ("P8") with the wires first into the opening prepared in 8.
the cover of the DDC, and then into the appropriate socket on the DDC itself, mak-
ing sure it is correctly inserted.
Use the rear cover bolts located near the CAN BUS socket to secure the 4 mm 9.
eyelet (or 2 eyelets) (detail D, Figure 6.10 Connection from CAN BUS to connector
P8 → 55). The cable should be secured against pulling out.
Figure 6.16 – detail wires and jumpers J21 - terminal/intermediate node CCI/DDC
Detail terminal and intermediate node: jumpers position J21: "closed" - "open".
LEGEND
DDC CCI/DDC J21 Jumper CAN-BUS in CCI/DDC board
A detail case "terminal node" (3 wires; J21=jumper "closed") B detail case "intermediate node" (6 wires; J21=jumper "open") H,L,GND data signal wires
How to connect the DDC
The DDC requires a low voltage power supply (24 V) with a 230/24 V AC, 50 Hz safety transformer; the minimum power requirement is 20 VA. For the connection use a cable with the minimum specifications 2 x 0.75 mm2.
Page 64
64
Connect the DDC to the transformer via the 4-pole connector provide for this, following the diagram in Figure 6.17 CCI/DDC - electric supply → 64. Pass the cable through the opening in the cover before fixing the wires to the connector. To power up the DDC, proceed as follows.
You will need: the appliance disconnected from the electricity supply
Remove the DDC's back panel by undoing the 4 bolts securing it.1. Cut a suitable length of power cord (minimum 2x0.75 mm2.
2
). Pass the power cord (DDC side) through the hole in the DDC's cover and hook up 3. as shown in the example, with the following polarities: terminal 1 = 24 V; terminal 2 = 0 V; terminal 3 = ground.
Make the grounding connection on the transformer terminal connected to termi­nal 2 of the 4-pole connector (EP) of the DDC. Terminal 2 is connected internally to terminal 3, and is thus grounded; if the transformer already has one wire grounded, it must be connected to this terminal. Terminal 3 of the DDC’s 4 pole connector must always be grounded (r ≤ 0.1Ω).
On completion, close the DDC's back panel with the 4 bolts.4.
The DDC is equipped with a backup battery which retains the memory settings in case of power failure. The backup battery lasts approximately 7 years, after which time it must be replaced by an authorised Robur Technical Assistance Centre.
Figure 6.17 – CCI/DDC - electric supply
CCI/DDC electric supply from external transformer.
LEGEND
DDC CCI/DDC AL supply 4 poles connector 1 clamp and wire for 24 Vac supply 2 clamp and wire for 0 Vac supply 3 clamp and wire for ground contact (required connection) DDCTR safety transformer
- (230/24 Vac 50/60 Hz)
The following wiring diagrams show the connection of the DDC to 1 appliance (Figure
6.18 Connexion câble CAN BUS for plants with one unit → 65) and 2 appliances (Figure
6.19 Connexion câble CAN BUS for plants with more unit → 66) respectively.
Page 65
Installation, user and maintenance manual – GAHP-GS/WS
65
Figure 6.18 – Connexion câble CAN BUS for plants with one unit
Connexion câble CAN BUS between one DDC and one unit
LEGEND
DDC direct digital control SCH electronic board S61 J1 Jumper CAN-BUS in board S61 J21 Jumper CAN-BUS in board DDC A terminal nodes connection - (3 wires; J1 e J21 = "closed") H,L,GND data signal wires (rif. cables table)
Page 66
66
Figure 6.19 – Connexion câble CAN BUS for plants with more unit
Connexion câble CAN BUS between one DDC and more unit
LEGEND
DDC direct digital control
SCH electronic board S61
J1 Jumper CAN-BUS in board S61
J21 Jumper CAN-BUS in board DDC
A terminal nodes connection - (3 wires; J1 e J21 = "closed")
B intermediate node connection - (6 wires; J1="open")
H,L,Gnd data signal wires (rif. cables table)
How to connect the system water circulation pumps
Control of the plant water circulation pump from the appliance’s controller depends on the power rating of the pump itself. 2 cases may be distinguished:
Page 67
Installation, user and maintenance manual – GAHP-GS/WS
67
Direct control from the controller with power absorbed by the pump less than 700 • W. If the power absorbed by the pump is less than 700 W, make the connection as shown in Figure 6.20 Electrical wiring diagram → 67 and check that the jumper J10 and J1 are CLOSED, as shown in detail A. Direct control from the controller with power absorbed by the pump of more than • 700 W. If the power absorbed by the pump is more than or equal to 700 W, make the connection as shown in Figure 6.21 Electrical wiring diagram → 68 using a control relay. In this case it is necessary to OPEN the jumper J1 and J10 positioning its as shown in detail A and B of the Figure.
Figure 6.20 – Electrical wiring diagram
Connection of plant water circulation pumps (power absorption less than 700W), controlled directly by the appliance.
LEGEND
SCH electronic board SCH2 electronic board J10 J1 - jumper closed N.O. CONTACT clean exit normally open MA Unit terminal block L phase N neutral Components NOT SUPPLIED PMW Hot side water pump <700W PMY Cold side water pump <700W
Page 68
68
Figure 6.21 – Electrical wiring diagram
Connection of plant water circulation pumps (power absorption equal or more than 700W), controlled directly by the appliance.
LEGEND
SCH electronic board SCH2 electronic board J10 J1 - jumper open N.O. CONTACT clean exit normally open MA Unit terminal block L phase N neutral Components NOT SUPPLIED PMW Hot side water pump ≥700W PMY Cold side water pump ≥700W KPW Hot side pump control relay KPY Cold side pump control relay
If several appliances are connected on the same hydraulic circuit, it is always necessary to provide a safety transformer (secondary SELV) and a respective control relay; make the connections according to the diagram in Figure 6.22 Electrical wiring diagram → 69.
Page 69
Installation, user and maintenance manual – GAHP-GS/WS
69
Figure 6.22 – Electrical wiring diagram
Example of pump/appliance electrical connection with 230 Vac pump, controlled directly by the appliance through a relay and a SELV safety transformer
LEGEND
SCH electronic board SCH2 W10 electronic board SCH3 MOD10 electronic board J1 J10 - jumper open N.O. CONTACT clean exit normally open MA Unit terminal block L phase
N neutral Components NOT SUPPLIED PMW Hot side water pump PMY Cold side water pump KPW Hot side pump control relay KPY Cold side pump control relay PTR SELV safety transformer IP bipolar pump switch
Variable flow pumps WILO STRATOS PARA can also be used (see Section 8 ACCESSO­RIES → 81). In this case, for the electrical wiring of the pumps, please refer to Figure
6.14 Wiring diagram for connection of Wilo variable rate pumps → 59 and the relevant paragraph.
Page 70
70
The primary circulation pump/s must be controlled by the S61 board, or directly (via “N.O. contact” contacts or 0-10V signal) or indirectly (“OR” use of said contacts by BMS type external systems). Otherwise, the primary circulation pump/s must be running permanently.
6.5 TYPE C CONSENT SWITCH
Before making the electrical connections, make sure that work is not carried out on live elements.
General indications
Check that the power supply voltage is 230 V 1N - 50 Hz power.• Make the electrical connections as given in the following wiring diagrams.• Make the electrical connection in such a way that the ground wire is longer than • the live wires. In this way it will be the last wire to be pulled away if the mains cable should accidentally be pulled, and will thus guarantee the ground connection.
Electrical safety is ensured only when the appliance is correctly connected to an efficient grounding system, realized according to current safety regulations. Do not use gas pipes as grounding.
How to connect the consent switch
You will need: the appliance is not powered electrically (external master power switch
set to OFF)
Connect the permissive (on-off switch or ambient thermostat or timer, etc.) to ter-1. minals R and W on the appliance’s electronic board as shown in Figure 6.23 Electri­cal wiring diagram → 70 (detail “CS”).
For the appliance to operate correctly, it is ALWAYS necessary to provide a consent switch. Do not use the general mains external circuit breaker («GS») to switch the appliance on or off.
Figure 6.23 – Electrical wiring diagram
electrical connections of ON/OFF command switch
LEGEND
SCH Electronic board R Common W Terminal consensus warming Components NOT SUPPLIED CS ON/OFF command switch
How to connect the system water circulation pumps For how to connect the system pumps, see the section with this title in Paragraph
6.4 TYPE B (DDC) → 60.
Page 71
Installation, user and maintenance manual – GAHP-GS/WS
71
Variable flow pumps WILO STRATOS PARA can also be used (see Section 8 ACCESSO­RIES → 81). In this case, for the electrical wiring of the pumps, please refer to Figure
6.14 Wiring diagram for connection of Wilo variable rate pumps → 59 and the relevant paragraph.
6.6 HOW TO RESET THE FLAME CONTROLLER FROM REMOTE
The flame controller reset can be controlled remotely by installing a button (not sup­plied) to the flame controller inside the unit’s electrical panel. Connect the button as instructed below.
You will need: the appliance disconnected from the electricity supply
The cable required to connect the reset button must be 3x0.75mm1.
2
. Cut a suitable length of cable.2. Connect the cable to the blind terminals A (see Figure 6.24 Button connection for 3. flame controller reset → 72).
The blind terminals are hidden on the rightinside the cable tray. To extract them, remove the cover of the tray, slide the cables out of the provided slots, and carefully close the tray again.
The cable may not be longer than 20 metres.
Incorrect wiring of the reset button may damage the component irreparably. Check the cabling carefully before powering the unit.
Page 72
72
Figure 6.24 – Button connection for flame controller reset
LEGEND
1 White
2 Grey
3 Orange
4 Green
5 Yellow/Black
6 Black
7 Yellow/Green (Ground)
8 Brown
9 Blue
10 Yellow
11 Violette
12 Pink
PLS Reset button
A Blind terminals
Page 73
Installation, user and maintenance manual – GAHP-GS/WS
73
7 INITIAL ACTIVATION AND MAINTENANCE
In this section you will find the following information:
Indications required by the authorized Robur Technical Assistance Centre (TAC) in • order to carry out the entire procedure of first start-up of the appliance. Indications regarding maintenance operations of the appliance.•
At the end of the section you will find instructions for changing the type of gas. Before proceeding with the operations described in this section, the installer is invited to read Paragraph 3.1 GENERAL INFORMATION → 8. Please refer to Paragraph 4.1 START UP (AND SHUT DOWN) → 17 for switching the appliance on and off.
If the appliance is connected to a CCP for the appliance start-up and switch-off control phases, reference must be made to the two CCP files dedicated to it.
If the appliance is connected to a DDC (and the DDC is in controller mode), for the phases of activation and deactivation of the appliance it is necessary to refer to the two manuals dedicated to the DDC itself.
7.1 PROCEDURE FOR FIRST START UP
The entire procedure for the initial activation of the appliance must only carried out by an authorised Robur Technical Assistance Centre (TAC). The product's guarantee may be void if the procedure is not carried out by a Robur TAC. Before leaving the factory, the appliance has been thoroughly tested. The entire procedure for initial activation of the appliance consists in carrying out the fol­lowing (main) operating stages:
preliminary verification of plant compliance;1. check/setup of the combustion parameters;2. regulating the plant operating parameters.3.
Preliminary checks of the installation compliance
The authorized technician must:
Check that the whole installation has been realized in accordance with its design, • following the manufacturer's instructions and respecting current legislation. The design must have been drawn up by a professional specifier. Check that all the connections (hydraulic, gas and electrical) of the appliance have • been made correctly. Check that the installation is actually compliant as per the Declaration of Conform-• ity provided by the installer to the owner.
The Declaration of Conformity CERTIFIES that the installation is compliant with current regulations. This Declaration is a mandatory document and as such it must be provided by the installer to the owner.
Check that the water pressure and flow in the hydraulic circuit and the dynamic • gas mains pressure are correct, as indicated by the manufacturer. Check that the electrical power supply is 230V 50Hz• Check that the air/fumes pipes are properly connected to the exterior.• Check that the fumes condensate discharge is properly installed.• Check that the safety clearances given in Figure 5.2 Clearances • → 28 have been observed.
If all the conditions listed above are in place, the authorized technician can proceed with the commissioning and start up of the appliance.
Page 74
74
If any non-compliance is found during the preliminary checks, the authorized technician may choose not to proceed with the "first start up". In this case, the authorized technician must:
Report the user/installer of any installation anomaly.• Report the user/installer of any situation that is potentially hazardous for the appli-• ance and for people. Report of any missing documentation relevant to the installation.• According to the reports made, advise any corrective action to be taken at the in-• staller's care in order to proceed with the "first start up".
It is the responsibility of the user/installation technician to carry out any corrective meas­ures on the plant indicated by the authorized technician. After such corrective measures have been completed, the authorized technician will assess the plant again. At this point, if safety and compliance conditions are judged satisfactory, the authorized technician must carry out the "first start up".
Plant conditions that are hazardous for people or for the appliance. If any of the follow­ing hazardous situations arises, the authorized technician must not carry out the "first start up":
appliance installed outdoors inadequately protected against the weather;• appliance installed close to combustible substances or surfaces or in any case in • conditions of bad accessibility or not allowing safe maintenance operations; control of switching on and off of the appliance not via the CCP/DDC or consent • switch but via the master power switch; damages or failures of the appliance due to transportation or installation;• smell of gas due to probable leaks from the plant itself and in any case all situations • that are due to non-compliant plants, considered potentially hazardous.
Plant anomalies. If any of the following situations exists, the authorized technician may carry out the "first start up" at his choice, but the appliance must be left off until the anomalies are removed:
installations (not potentially hazardous) not carried out according to sound work-• manship practices, installations (not potentially hazardous) not complying with current national and local regulations; installations (not potentially hazardous) not carried out according to good • workmanship practices, not complying with the instructions provided by the manufacturer; installations that can cause operational troubles on the appliance.•
Procedure for checking/setting-up the combustion parameters
During the initial activation procedure, the combustion parameters must be checked and set ONLY by a Robur TAC. In this stage, NEITHER the user NOR the installation technician is authorised to perform such operations, and in so doing may invalidate the guarantee of the appliance.
The appliance is supplied with all of its units already regulated for the type of gas for which the appliance itself is set up.
Page 75
Installation, user and maintenance manual – GAHP-GS/WS
75
The type of gas for which the appliance is set up can be identified from the adhesive label located on the unit’s internal gas pipe (detail M, Figure 7.2 Gas changeover → 80).
The nozzles required to change the gas type to G30 and G31 are supplied together with the appliance.
During the first start-up procedure it is in any case necessary to:
check the dynamic gas mains pressure• check and adjust the appliance’s combustion parameters•
You will need: the appliance connected to the gas and electricity supply: switched off and with the gas cock closed; front panel removed.
Check the dynamic gas mains pressure
Connect the manometer to the gas intake (see detail D, Figure 7.1 Gas 1. valve → 75). Open the gas valve and check that the grid static pressure complies to the value 2. reported in Table 5.2 Network gas pressure → 31 (with a tolerance of ±15%).
If the static mains pressure is greater than 50 mbar DO NOT switch on the appliance!
Give the consent signal for operation.3. After some seconds of operation, check that the grid dynamic pressure complies 4. with the value reported in Table 5.2 Network gas pressure → 31 (with a tolerance of ±15%).
Figure 7.1 – Gas valve
Gas valve Honeywell VK 4115V
LEGEND
A Plug B Key Torx TX40 C screw adjustment CO2 D gas pressure intake
Page 76
76
If the pressure measured by the pressure gage is not complying with the value re­ported in Table 5.2 Network gas pressure → 31 (with a tolerance of ±15%), it is NOT possible to switch the appliance on!
Proceed with the regulation/verification of the combustion parameters as stated 5.
in the next paragraph. Checking and adjusting the combustion parameters After having checked the dynamic mains pressure (see section), you may check and ad­just the combustion parameters as follows.
Fit a combustion products probe in one of the points provided for this purpose on 1.
the external fumes equipment or at point L in Figure 7.2 Gas changeover → 80
Give the unit functioning consent and wait for at least 5 minutes for normal com-2.
bustion conditions.
With the appliance running, access menu 2 parameter 4 of the unit's controller: the 3.
display will flash "P_H0", press to confirm forcing maximum thermal power.
Check that the value of CO4.
2
read on the flue gas analyser coincides with the value given in Table 7.3 Gas nozzles and content of CO2 → 79 at the "Content of CO2 with/MAX modulation" line with +0.2 -0.4 tolerance. Example (G20 gas): the nominal content of CO2 is equal to 9.1%, values in the range between 8.7-9.3% are therefore acceptable. Access menu 2 parameter 3 of the unit's controller inside the electric panel: the 5. display will flash "P_L0", press to confirm forcing minimum thermal power. Now check that the difference between the value read in point 4 and that now 6. displayed on the flue gas analyser, corresponds to the data given in the Table 7.3 Gas nozzles and content of CO2 → 79 at the "Delta CO2 between MAX and MIN potentiality" line with tolerance of +0.3-0.0. Example (G20 gas): if at point 4 a content of CO2 equal to 9.2% was detected, at point 6 there must be a value of (9.2%-0.4) with tolerance of +0.3 -0.0 on the delta value, i.e. a value in the range of 8.8-8.5%. If this is not the case, remove cap A from the gas valve (see Figure 7.1 Gas valve 7. → 75) and use a Torx TX40 wrench to act on screw C in Figure 7.1 Gas valve → 75. Turn clockwise to increase the percentage of CO2 and anti-clockwise to decrease the percentage of CO2.
1/8 turn of the regulator screw reduces (counterclockwise) or increases (clockwise) the CO2 content by approximately 0.1%. DO NOT turn the screw more than one full turn in either direction.
With the appliance running, access menu 2 parameter 4 of the unit's controller: the 8. display will flash "P_H0", press to confirm forcing maximum thermal power. Check that, also following a regulation intervention on screw C, the value of CO9.
2
corresponds to the value read in Table 7.3 Gas nozzles and content of CO2 → 79 at the "Content of CO2 with/Max modulation" line with tolerance of +0.2 -0.4.
If you cannot calibrate the CO2 percentage after the second attempt, DO NOT acti­vate the appliance; contact Robur technical service at +39 035/888111.
Page 77
Installation, user and maintenance manual – GAHP-GS/WS
77
If the check/setup of the combustion parameters has been successful, please enter 10. menu 2, parameter 5, of the electronic board inside the electric box of the appli­ance: on the display, the message "unF0", will blink; press to remove the operational override previously selected and then return to the normal operational configura­tion with modulation of the thermal power.
After 30 minutes of operation the appliance automatically cancels the preced­ing forced power mode. To anticipate this timing, select and execute action "5" in menu 2.
Switch the appliance off.11. Close the gas valve.12. Reinstall the cap A in Figure 7.1 Gas valve 13. → 75. Reinstall the front panel.14.
7.2 MAINTENANCE
Correct maintenance prevents problems, guarantees maximum operating efficiency of the appliance and allows running costs to be contained.
The maintenance operations described in this paragraph must be performed exclusively by the serviceman in charge of the plant or by an authorized CAT Robur.
Any operation that regards internal components of units of the appliance must be car­ried out by an authorized Robur Technical Assistance Centre (TAC), according to the in­structions supplied by the manufacturer.
The "efficiency check" and every other "check and maintenance operation" (see Table
7.1 → 78 and 7.2 → 78), must be performed with a frequency in agreement to cur- rent law or, if more restrictive, in respect of what requested by the planner (builder of the system) or by the manufacturer of the unit.
The liability of CHECKING THE EFFICIENCY AS A FUNCTION OF THE SYSTEM, OF THE FUEL IN USE AND OF THE THERMAL POWER, to be carried out with the purpose of containing the energy consumption, is in charge to the responsable of the system.
Before any maintenance operation, switch off the appliance by means of the permissive contacts (or by means of DDC/CCP) and wait for the completion of the shut-down cycle. When the appliance is off, switch off power supply and gas supply (according to anti­icing settings), opening the electrical breaker and closing the gas isolation valve.
GUIDELINES FOR THE PREVENTIVE MAINTENACE OPERATIONS
In Table 7.1 → 78 are reported the guidelines for the preventive maintenance operations.
If the unit is subject to particularly heavy duty (for example in process plants or in other conditions of continuous operation), these maintenance operations must be more frequent.
Page 78
78
Table 7.1
GUIDELINES FOR THE PREVENTIVE MAINTENACE OPERATIONS Check of the unit GAHP-A GAHP-GS/WS AY ACF GAHP-AR
Visually check of the general condition of the unit and of its air heat exchanger.
(1)
√ √ √ √ Check the correct operation of the device used for monitoring the water flow √ √ √ √ √ Check the % value of CO
2
√ √ √ check gas pressure to the burners √ √ Check that the condensate discharge is clean (clear the condensate discharge hole of any blockages)
[If necessary, frequency of the maintenace operation must be increased]
√ √ √
Replace the belts after 6 years or 12,000 hours of operation √ √ √ √ Check/restore the pressure of the primary hydronic circuit √ Check/restore the air pressure inside of the expansion vessel of the primary hydronic circuit √
Check every CCI or DDC
(2)
DDC o CCI
Check that the plant is able to achive the setpoint temperature √ Download the hystorical events √
1 It is suggested the cleaning of the air heat exchanger once every 4 years [the optimal frequency of this operation is in any case a consequence of the installation site]. 2 Check that the plant is able to achive the setpoint temperature.
ORDINARY SCHEDULED MAINTENANCE Perform the following operations at least once every 2 years.
If the unit is subject to particularly heavy duty (for example in process plants or in other conditions of continuous operation), these maintenance operations must be more frequent.
Table 7.2
SCHEDULED MAINTENANCE OPERATIONS TO BE PERFORMED AT LEAST ONE EVERY TWO YEARS Check of the unit GAHP-A GAHP-GS/WS AY ACF GAHP-AR
Clean the combustion chamber √ √ √ √ √ Clean the burner √ √ √ √ √ Clean the electrodes of ignition and flame sensing √ √ √ √ √
Check that the condensate discharge is clean (clear the condensate discharge hole of any blockages) √ √ √ Replace the silicone gasket √
In Section 5 HYDRAULIC INSTALLATION → 26 are reported suggestions related to the
hydraulic plant.
7.3 CHANGE OF GAS TYPE
This operation must be carried out exclusively by an authorised Robur Technical Assist­ance Centre (TAC).
If the appliance is to be used with a type of gas other than that indicated on the the adhe­sive label located on the unit's electric panel, switch off the appliance, shut off its power and gas supplies and proceed as follows (see Figure 7.2 Gas changeover → 80):
You will need: the appliance switched off and disconnected from the gas/electricity supplies
Disconnect the gas pipe from the gas valve.1. Undo the 4 bolts E shown in Figure 7.2 Gas changeover 2. → 80 and remove the gas valve/blower assembly from the burner. Protect the burner from bolts and nuts falling into it.3. Using a CH 4 hex key, undo the 4 bolts G indicated in Figure 7.2 Gas changeo-4. ver → 80 and remove the nozzle D from the gas valve.
Page 79
Installation, user and maintenance manual – GAHP-GS/WS
79
Replace the nozzle and o-ring B (see Figure 7.2 Gas changeover 5. → 80) with those of the diameter suited to the new type of gas (see Table 7.3 Gas nozzles and con­tent of CO2 → 79). The nozzle code is stamped on the nozzle itself. Check that the o-ring C is fitted (see Figure 7.2 Gas changeover 6. → 80). Reassemble the gas valve to the blower with the 4 bolts G taking care that the red 7. silicon hose between the venturi tube and the gas valve (see detail F of Figure 7.2 Gas changeover → 80) is correctly installed. Replace the white gasket between the blower and the burner.8. Reinstall the blower/gas valve assembly to the burner with the 4 bolts E, taking 9. care not to damage the white gasket. Reconnect the gas pipe to the gas valve.10. Replace the sticker indicating the type of gas for which the appliance was set up 11. with one that indicates the new type of gas used. Check the tightness of the installation as follows:12. Connect a manometer to the gas intake D (Figure 7.1 Gas valve • → 75). Open the gas valve.• Close the gas cock and check that the mains pressure has not dropped.• If there is no gas leak, supply gas and electricity to the appliance and restart it.13. complete the change of gas type by checking that all gas connections are sealed, 14. including those not directly affected by this operation (using soapy water or an­other suitable method). Now check and adjust the combustion parameters as indicated in the respective 15. paragraph.
Table 7.3 – Gas nozzles and content of CO2
Gas type G20 G25 G25.1 G27 G2.350 G30 G31
Nozzle code 180 181 181 187 184 182 183 Nozzle diameter 4,7 5,2 5,2 5,4 5,9 3,4 3,6 Content CO2 with MAX modulation 9,1% 9,2% 10,1% 9,0% 9,0% 10,4% 9,8% Delta CO2 between Max and Min potential 0,4 0,6 0,8 0,5 0,5 0,5 0,4
Page 80
80
Figure 7.2 – Gas changeover
Gas changeover
LEGEND
A Gas valve B O-ring C O-ring D Gas nozzle E Mounting holes F Red silicon hose G Mounting holes H Manual reset fumes thermostat L Fumes outlet
Page 81
Installation, user and maintenance manual – GAHP-GS/WS
81
8 ACCESSORIES
This section contains a list of the accessories that are available for the installation and use of the appliance. To order these accessories, contact Robur S.p.A. on +39 035.888111.
Table 8.1 – Accessories
ACCESSORIES Name Description Code Notes
CIRCULATION PUMPS
Wilo-Stratos Para 25-11. O-PMP004
Variable rate pump for cold and hot water.
Pompa Wilo-Stratos Para 30-12 O-PMP008 Max variable flow pump.
FILTERS Sludge filter 1" 1/4 O-FLT014
Sludge filter 1" 1/2 O-FLT015 Air separator filter 1" 1/4 O-FLT010 Air separator filter 1" 1/2 O-FLT016
BOILERS AND HYDRAULIC SEPARATORS Sanitary water boiler with oversize coil, 300 l O-SRB004
Sanitary water boiler with oversize coil, 500 l O-SRB005 Sanitary water boiler with oversize coil, 500 l O-SRB006 With integral solar coil. Sanitary water boiler with oversize coil, 750 l O-SRB007 With integral solar coil. Thermal tank, three fittings, 300 l O-SRB000 Thermal tank, three fittings, 500 l O-SRB001 Thermal tank, three fittings, 800 l O-SRB002 Thermal tank, three fittings, 1000 l O-SRB003
VALVES Flow regulator valve O-VLV001
3-way valve DN20 Kvs 6.3 O-VLV004 3-way valve DN25 Kvs 10 O-VLV005 3-way valve DN32 Kvs 16 O-VLV006 3-way zone ball valve 1"1/4 O-VLV002 3-way zone ball valve 1"1/2 O-VLV003
ANTIVIBRATION n.4 anti-vibration mounts O-NTV003 REGULATOR COMPONENTS Radio module (Siemens) O-DSP007
Repeater (Siemens) O-DSP009 Sender (Siemens) O-DSP008 Room unit basic (Siemens) O-DSP004 Room unit cooling (Siemens) O-DSP005 Room unit cooling (Siemens) (radio) O-DSP006 Servocontrol 230V AC for zone valves, on/off 90 sec O-BBN000 Modulating servocontrol for 3-way valves 230V AC 150 sec O-BBN001 Probe + sender (Siemens) O-DSP010 Contact probe (Siemens) O-SND006 External probe (Siemens) O-SND003 Immersion probe, length 2 m O-SND004 Solar sensor (Siemens) O-SND005 Commissioning tool O-DSP002 Communications switchboard O-DSP003
Robur “NETBUS” CAN BUS CABLE
Cable for data communication networks: for network connection between CCI and appliance.
O-CVO008
Transformer 50VA trasformer O-TRS005
Page 82
82
9 OPERATING CODES/TROUBLESHOOTING
9.1 OVERVIEW AND OPERATING CODES/TROUBLESHOOTING
Table 9.1 – TABLE OF OPERATING CODES generated by the S61 electronic board (firmware version 3.024)
CODES DESCRIPTION TRIP CONDITIONS RESET METHOD
E 200
FAULT ON RESET CIRCUIT OF FLAME CONTROL UNIT
Fault on reset circuit of flame control unit. Contact authorised Technical Assistance.
u 201
GENERATOR LIMIT TEMPERATURE THERMOSTAT
High temperature detected by limit thermostat on body of generator
Acknowledge the thermostat manually: reset will be automatic as soon as fault condition is over.
E 201
GENERATOR LIMIT TEMPERATURE THERMOSTAT
u_01 code active for 1 hour, or u_01 code generated 3 times in 2 hours of operation.
Contact authorised Technical Assistance.
u 202 FUMES THERMOSTAT
High temperature detected by exhaust fumes thermostat.
Acknowledge the thermostat manually: reset will be automatic as soon as fault condition is over.
E 202 FUMES THERMOSTAT
u_02 code active for 1 hour, or u_02 code generated 3 times in 2 hours of operation.
Contact authorised Technical Assistance.
u 203
COLD WATER ANTIFREEZE THERMOSTAT
Low temperature detected by cold outlet water sensor.
Reset occurs automatically when the condition that generated the code ceases, with hysteresis of 2 °C.
E 205 HIGH AMBIENT TEMPERATURE
HIGH temperature detected by ambient temperature sensor.
Reset occurs automatically when the condition that generated the code ceases.
u 206 LOW AMBIENT TEMPERATURE
LOW temperature detected by ambient temperature sensor.
Reset occurs automatically when the cause ceases or when the unit is switched off.
u 207
HIGH CONDENSER INLET TEMPERATURE
Temperature measured by condenser inlet sensor, fumes sensor or generator fin sensor HIGH.
Reset occurs automatically when the condition that generated the code ceases.
E 207
HIGH CONDENSER INLET TEMPERATURE
u_07 code active for 1 hour, or u_07 code generated 12 times in 2 hours of operation.
Carry out appropriate checks. Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
E 208 FLAME CONTROL UNIT ERROR
E_12 on unit and condenser inlet temperature increasing by over 10 °C within 1 hour.
Carry out appropriate checks. Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
u 210 INSUFFICIENT COLD WATER FLOW
Insufficient water flow (the circulator is on and the flowmeter is open).
Reset occurs automatically when correct water flow is restored.
E 210 INSUFFICIENT COLD WATER FLOW
u_10 code generated 5 times since appliance powered, or code u_10 is active for 1 hours.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
u 211
INSUFFICIENT ROTATION OF OIL PRESSURE PUMP
Insufficient rotation of oil pressure pump. Reset occurs automatically 20 minutes after the Code is generated.
E 211
INSUFFICIENT ROTATION OF OIL PRESSURE PUMP
u_11 code generated twice in 2 hours of operation.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
u 212 FLAME CONTROL UNIT ARREST Failure to ignite burner.
Reset occurs automatically when the solenoid valve opens again (new ignition attempt), or if the code persists for 5 minutes.
E 212 FLAME CONTROL UNIT ARREST Flame arrest signal.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 0). If the code persists, contact authorised TAC.
E 216
COLD OUTLET WATER TEMPERATURE SENSOR DEFECTIVE
Fault (interruption or short circuit) on outlet water temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
E 217
COLD INLET WATER TEMPERATURE SENSOR DEFECTIVE
Fault (interruption or short circuit) on condenser outlet temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
E 220
CONDENSER INLET TEMPERATURE SENSOR DEFECTIVE
Fault (interruption or short circuit) on condenser inlet temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
E 222 WATER FLOWMETER FAULT Water flowmeter fault.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
E 223 AIR/GAS MIXTURE SENSOR FAULT Air gas mixture sensor fault.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
E 224
FUMES TEMPERATURE SENSOR FAU LT
Fumes temperature sensor fault
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
E 225
CONDENSATE DISCHARGE CLOGGED
Condensate discharge clogged
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
E 226
GENERATOR FIN TEMPERATURE SENSOR
Generator fin temperature sensor
Reset may be performed from the controller (or from the S61 board via menu 2, parameter 21). If the code persists, contact authorised Technical Assistance.
E 228
GAS SOLENOID VALVE EXCITED DURING FLAME CONTROLLER ARREST
The flame controller is arrested (E_12) but the gas solenoid valve is excited. In this case the flame controller is de-excited (E_12 resets).
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
u 229
GAS SOLENOID VALVE WITHOUT ELECTRICAL POWER
Gas solenoid valve is off for 5 seconds (with central flame control unit on).
Reset occurs automatically if the gas solenoid valve switches on again within 10 minutes (with central flame control unit on).
E 229
GAS SOLENOID VALVE WITHOUT ELECTRICAL POWER
Code u_29 is active for more than 10 minutes (with flame controller unit on).
Carry out appropriate checks. Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
Page 83
Installation, user and maintenance manual – GAHP-GS/WS
83
CODES DESCRIPTION TRIP CONDITIONS RESET METHOD
u 236 BLOWER FAULT Blower fault
Reset occurs automatically 20 minutes after the operating code is generated.
E 236 BLOWER FAULT
u_36 code generated three times in 1 hour of operation.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
u 246
HOT INLET WATER TEMPERATURE TOO HIGH
Hot inlet water temperature higher than upper operating limit of the appliance (if the appliance is in operation).
Resets automatically if, with the circulator on, the cause resolves or (with circulator off) 20 minutes after generation of code.
u 247 LOW HOT WATER TEMPERATURE
Hot water temperature lower than lower operating limit of the appliance (if the appliance is in operation).
Reset occurs automatically when cause resolves or 430 seconds after the code is generated.
E 247 LOW HOT WATER TEMPERATURE
u_47 code generated 3 times in 1 hour of operation of the circulator.
Reset occurs automatically when the condition that generated the code ceases. If the code persists, contact authorised Technical Assistance.
u 248
HOT WATER DIFFERENTIAL TEMPERATURE TOO HIGH
High hot water differential temperature.
Reset occurs automatically 20 minutes after the operating code is generated.
E 248
HOT WATER DIFFERENTIAL TEMPERATURE TOO HIGH
u_48 code generated twice in 2 hours of operation.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1).
E 249 SATELLITE BOARD NOT PRESENT Satellite board not present.
Reset occurs automatically when the condition that generated the code ceases.
u 251
ANTIFREEZE FUNCTION ACTIVATED
- COLD SIDE Activation takes place only if the plant water circulator is off and the antifreeze function is enabled (see menu 1, parameter 77).
Inlet or outlet water temperature of the cold module falls below 4°C (the code generated signals that the antifreeze function has been activated). In this case the antifreeze function activates the plant water circulator.
Reset (deactivation of antifreeze function) occurs automatically when, with only the circulator on, the inlet and outlet water temperatures return to over 5°C (in this case the circulator switches off), or if the function itself is disabled.
u 275
INSUFFICIENT HOT SIDE WATER FLOW
On the hot side, the circulator is on and the flowmeter is open for 5 seconds (insufficient water flow).
The warning automatically resets when the circulator switches off or the flow meter closes for 5 seconds.
E 275
INSUFFICIENT HOT SIDE WATER FLOW
At the fifth u_75 from machine power supply, or after two hours of u_75 presence, the error is generated.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1).
E 276
HOT WATER DELIVERY TEMPERATURE PROBE FAULT.
Fault (interruption or short circuit) on outlet hot water temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1).
E 277
HOT WATER RETURN TEMPERATURE PROBE FAULT.
Fault (interruption or short circuit) on inlet water temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1).
u 278
OUTLET HOT WATER TEMPERATURE TOO HIGH
Outlet hot water temperature too high
Reset is automatic and occurs when the condition that generated it ceases to apply.
u 279
DEFROST FUNCTION ACTIVATED ­HOT SIDE Activation takes place only if the hot module is off and the antifreeze function is enabled (see menu 1, parameter 163).
Antifreeze function activated (with function enabled: see menu 1, item163; and only with machine off). In this case the antifreeze function activates the plant water circulator. If this temperature falls further to below 3 °C, the function also activates the flame controller.
Resets automatically (defrost function disabled) if, with only the circulator operating, the hot water inlet/outlet temperature rises above 5°C (at which point the circulator switches off); or, if also the flame controller is on, when the temperature reaches 18 °C (in this case the flame controller and then the circulator switch off).
u 280 INCOMPLETE PARAMETERS Incomplete parameters.
The code remains until operating parameters are entered and completed. Contact authorised Technical Assistance. If the board is replaced, Code E 80 may appear; this means that the unit’s characterisation parameters have not been set.
E 80/280 INVALID PARAMETERS
Invalid parameters or damage to parameter memory.
Reset occurs automatically when correct parameters are entered. If the code persists, contact authorised Technical Assistance: if the parameters are incorrect, it is necessary to enter and complete the unit operating and characterisation parameters; if the memory is damaged, the controller must be replaced.
u 281 INVALID BANK 1 PARAMETERS Invalid Bank 1 data - Bank 2 data OK. Reset occurs automatically 5 seconds after the code is generated.
E 281 INVALID BANK 1 PARAMETERS
The program attempts to resolve the problem by writing the second page over the first; if after 5 attempts this fails, the error is generated.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
u 282 PARAMETRI BANCO 2NON VALIDI Invalid Bank 2 data - Bank 1 data OK. Reset occurs automatically 5 seconds after the code is generated.
E 282 INVALID BANK 2 PARAMETERS
The program attempts to resolve the problem by writing the first page over the second; if after 5 attempts this fails, the error is generated.
Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists, contact authorised TAC.
E 284
FAULTY TRANSFORMER CONNECTION OR 24 V AC FUSES
Damage to one of the 2 24-0-24 V AC transformer fuses, or one of 24-0-24 V AC wires to the board not supplying current.
Check fuses and 24-0-24 V AC electrical power connections on the controller. Reset may be performed from the CCI/DDC (or from the S61 board via menu 2, parameter 1). If the code persists or occurs again, contact authorised TAC.
E 285
INCORRECT MODULE TYPES (from menu 6)
The set module type (from menu 6) does not correspond to the one managed by the controller.
Reset occurs automatically when correct parameters are entered. If
the code persists, contact authorised Technical Assistance. E 286 MEMORY TEST UNSUCCESSFUL Processor error. Contact authorised Technical Assistance. E 287 MEMORY TEST UNSUCCESSFUL Processor error. Contact authorised Technical Assistance. E 288 MEMORY TEST UNSUCCESSFUL Processor error. Contact authorised Technical Assistance. E 289 MEMORY TEST UNSUCCESSFUL Processor error. Contact authorised Technical Assistance.
E 290
AMBIENT TEMPERATURE SENSOR DEFECTIVE
Interruption or short circuit of ambient temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 1). If the code persists, contact authorised
TAC.
E 291 CONTROLLER DEFECTIVE
One of the following is absent: serial number of board, hardware version code or encryption key written during board test.
Contact authorised Technical Assistance.
TABLE OF OPERATING CODES generated by the S61 electronic board (firmware version 3.024)
Page 84
Page 85
Installation, user and maintenance manual – GAHP-GS/WS
95
DECLARATION OF CONFORMITY
Figure 1
coscienza ecologica caring for the environment
Robur S.p.A. tecnologie avanzate per la climatizzazione advanced heating and cooling technologies www.robur.it [email protected] via Parigi 4/6 24040 Verdellino/Zingonia (BG) Italy T +39 035 888111 F +39 035 884165 capitale sociale € 2.028.000,00 i.v. iscritta al Registro Imprese di Bergamo n. 154968 codice fiscale/partita iva 00373210160 V.A.T. code IT 00373210160 società soggetta all’attività di direzione e coordinamento di Fin Robur S.a.p.A. di Benito Guerra & C.
EC – DECLARATION OF CONFORMITY
Manufacturer : Robur S.p.A. Address : Via Parigi 4/6 City, Country : Verdellino/Zingonia 24040 (Bg), Italy
This is to declare that the ROBUR Gas Absortion Heat Pump (GAHP) are in conformity with the following EC­Directives:
2006/42/EC
Machinery Directive with subsequent amendments and integrations.
2004/108/EC Electromagnetic Compatibility with subsequent amendments and integrations.
Tested and examined according to the following norms: EN55014-1, EN55014-2, EN61000-3-2, EN61000-3-3, EN62233.
2006/95/EC Low Voltage Directive with subsequent amendments and integrations. Tested and examined according to the following norms: EN50165, EN60335-2-102, EN60335-1.
2009/142/EC Gas Appliance Directive with subsequent amendments and integrations. Tested and examined according to the following norms: EN 12309-1. EN 12309-2, EN 483. As proved whit EC certification number 0964, issued by KIWA Italia S.p.A Via G. Carducci,5 Milan-Italy
97/23/EC Pressure Equipment Directive with subsequent amendments and integrations. As proved with EC Certification number 1370 of all the components under pressure of the III° category, issued by BUREAU VERITAS Italia S.p.A. Viale Monza, 261 Milan-Italy
Jvan Benzoni R&D Director
Robur S.p.A.
Page 86
96
Figure 2
coscienza ecologica caring for the environment
Robur Spa tecnologie avanzate per la climatizzazione advanced heating and cooling technologies www.robur.it [email protected] via Parigi 4/6 24040 Verdellino/Zingonia (Bg) Italy T +39 035 888111 F +39 035 884165
D-FGL073 rev.F 11 MCM SDC 030 del 14/12/2011
Dichiarazione di Conformita’ n°: Declaration of Conformity n°: Déclaration de conformité n°: Konformitätserklärung N°: Declaración de Conformidad n°: Verklaring van conformiteit n°:
Zingonia, li/den 14/12/2011
IT
Con la presente si dichiara che i circuiti a pressione:
1. del Refrigeratore d’acqua a gas ad Assorbimento prodotto da ROBUR S.p.A., serie GA: ACF60-00
(standard e versioni speciali);
2. delle Pompe di Calore a gas ad Assorbimento prodotte da ROBUR S.p.A., serie GAHP: GS, WS, A, AR (standard e versioni speciali); serie GAS HP: G, W, A (standard e versioni speciali);
rispondono ai requisiti richiesti dalla Direttiva sulle attrezzature a pressione 97/23/CE (PED) come comprovato dal Certificato CE di Valutazione di Conformità nell'Insieme:
MODULO H, Garanzia Qualità Totale, numero CE-1370-PED-H-ROB001-10-ITA
Rilasciato da:
BUREAU VERITAS ITALIA S.p.A.
Viale Monza 261
20126 Milano – Italy
Si precisa che tali circuiti sono dotati di una valvola di sicurezza (pressione di taratura 35 bar) conforme ai requisiti della stessa Direttiva 97/23/CE (PED).
Page 87
Installation, user and maintenance manual – GAHP-GS/WS
97
Figure 3
coscienza ecologica caring for the environment
Robur Spa tecnologie avanzate per la climatizzazione advanced heating and cooling technologies www.robur.it [email protected] via Parigi 4/6 24040 Verdellino/Zingonia (Bg) Italy T +39 035 888111 F +39 035 884165
D-FGL073 rev.F 11 MCM SDC 030 del 14/12/2011
UK
We hereby declare that:
1. pressurized circuit of the Gas Absorption Chiller manufactured by ROBUR S.p.A., series GA: ACF60-00
(standard and special versions);
2. pressurized circuit of the Gas Absorption Heat Pump manufactured by ROBUR S.p.A., series GAHP: GS, WS, A, AR (standard and special versions); series GAS HP: G, W, A (standard and special versions);
comply with Pressure Equipment Directive 97/23/EC (PED) requirements, as proofed with EC Certification of all the components under pressure:
MODULE H for “Total Quality Assurance”, number CE-1370-PED-H-ROB001-10-ITA
Issued by:
BUREAU VERITAS ITALIA S.p.A.
Viale Monza 261
20126 Milan- Italy
In particular, these circuits are equipped with one safety valve (pressure gauge set at 35 bar) conforming to the requirements of 97/23/EC (PED) Directive.
FR
Nous déclarons par la présente que les circuits hermétiques pressurisés:
1. des unités à Absorption à gaz fabriquées par la Société ROBUR S.p.A., série GA: ACF60-00 (standard et versions spéciales);
2. des Pompes à Chaleur à Absorption à gaz fabriquées par la société ROBUR S.p.A., série GAHP: GS, WS, A, AR (standard et versions spéciales); série GAS HP: G, W, A (standard et versions spéciales);
répondent à la Directive sur les appareils sous pression 97/23/EC (PED) comme d’après le Certificat CE d’Evaluation de l’Ensemble sous Pression:
MODULE H, “GARANTIE QUALITE TOTALE”, numéro CE-1370-PED-H-ROB001-10-ITA
Délivré par:
BUREAU VERITAS ITALIA S.p.A.
Viale Monza 261
20126 Milano – Italy
Nous précisons que ces circuits sont équipés d'une soupape de sécurité (pression de réglage 35 bar) conformément à la Directive 97/23/EC (PED)
.
DE
Hiermit erklären wir, daß die hermetischen Kreisläufe:
1. der gasbefeuerte Absorptionskältemaschine , produziert durch ROBUR S.p.A., Typ GA: ACF60-00 (Standard und in den verschiedenen Ausführungen);
2. der Gasabsorptionswärmepumpe, produziert durch ROBUR S.p.A., Typ GAHP: GS, WS, A, AR (Standard und in den verschiedenen Ausführungen); Typ GAS HP: G, W, A (Standard und in den verschiedenen Ausführungen);
den Anforderungen der Druckbehälterverordnung 97/23/EC (PED) entsprechen und hiermit die EC Zertifizierung erfüllen im Ganzen:
x MODUL H, umfassende Qualitätssicherung CE-1370-PED-H-ROB001-10-ITA Ausgestellt von:
BUREAU VERITAS ITALIA S.p.A.
Viale Monza 261
20126 Milano – Italy
Hiermit möchten wir klarstellen , daß diese Behälter mit einem Sicherheitsventil (Eichungsdruck 35 bar) nach 97/23/EC (PED) Verordnung ausgerüstet sind.
Page 88
98
Figure 4
coscienza ecologica caring for the environment
Robur Spa tecnologie avanzate per la climatizzazione advanced heating and cooling technologies www.robur.it [email protected] via Parigi 4/6 24040 Verdellino/Zingonia (Bg) Italy T +39 035 888111 F +39 035 884165
D-FGL073 rev.F 11 MCM SDC 030 del 14/12/2011
ES
Por la presente certificamos que los circuitos herméticos presurizado:
1) de las Máquinas de Absorción con gas fabricadas por la Empresa ROBUR S.p.A., serie GA: ACF60-00 (Standard y versiones especiales);
2) de las bombas de calor por ciclo de absorción con gas fabricadas por la Empresa ROBUR S.p.A., serie GAHP: GS, WS, A, AR (Standard y versiones especiales); serie GAS HP: G, W, A (Standard y versiones especiales);
se adaptan a la Directiva 97/23/EC (PED) sobre aparatos a presión, y han sido probados conforme al procedimiento EC en conjunto:
MODULO H, control de aseguramiento de calidad total, número CE-1370-PED-H-ROB001-10-ITA
Efectuados por:
BUREAU VERITAS ITALIA S.p.A.
Viale Monza 261
20126 Milano – Italy
Se precisa que estos circuitos están equipados de una válvula de seguridad (presiòn de calibraciòn 35 bar) conforme a lo establecido en la Directiva 97/23/EC (PED).
NL
Hierbij verklaren wij dat de drukcircuiten:
1) van de GasAbsorptie Koelers geproduceerd door ROBUR S.p.A., serie GA: ACF60-00 (standaard e speciale versies);
2) van de Gasabsorptiewarmtepomp geproduceerd door ROBUR S.p.A., serie GAHP: GS, WS, A, AR (standaard en speciale versies); serie GAS HP: G, W, A (standaard en speciale versies);
voldoen aan de voorwaarden van de Pressure Equipment Directive 97/23/EC (PED), zoals gecertificeerd door EC Certificaat voor alle componenten onder druk:
Module H, Totale Qualiteits Garantie, nummer CE-1370-PED-H-ROB001-10-ITA
Gepubliceerd door:
BUREAU VERITAS ITALIA S.p.A.
Viale Monza 261
20126 Milaan-Italie
In het bijzonder is dit circuit uitgerust met een veiligheidsventiel (drukmeter op 35 bar) volgens de eisen van de 97/23/EC (PED) richtlijn.
ROBUR S.p.A.
Ing. Davide Schiavon
Quality and Safety Manager
Page 89
Installation, user and maintenance manual – GAHP-GS/WS
99
Page 90
Robur Spa tecnologie avanzate per la climatizzazione Via Parigi 4/6 24040 Verdellino/Zingonia (Bg) Italy T +39 035 888111 F +39 035 884165 www.robur.it [email protected]
Robur Mission
Revision: M Code: D-LBR509 12 MCM SDC 016 19/10/2012
Robur is dedicated to dynamic progression in research, development and promotion of safe, environmentally-friendly, energy-efficiency products, through the commitment and caring of its employees and partners.