This Installation, use and maintenance manual has been drawn up and printed by Robur S.p.A.; whole or partial reproduction of this
Installation, use and maintenance manual is prohibited.
The original is led at Robur S.p.A.
Any use of this Installation, use and maintenance manual other than for personal consultation must be previously authorised by Robur S.p.A.
The rights of those who have legitimately led the registered trademarks contained within this publication are not aected.
With the aim of continuously improving the quality of its products, Robur S.p.A. reserves the right to modify the data and contents of this
Installation, use and maintenance manual without prior notice.
Page 3
INDEX OF CONTENTS
I Introduction .............................................................................
terms, both used to designate single gas-red heat/chiller appliance (GAHP A/AR/GS/WS, or GA ACF/HR/TK absorption chiller
or AY00-120 condensing boiler), part of the preassembled unit
together with other modules/appliances.
TAC = Technical Assistance Centre authorised by Robur.
▶
end user, for appropriate and safe use of the preassembled
group;
▶
qualied installer, for correct installation of the preasslembled group;
▶
planner, for specic information on the preassembled group.
I.2 CONTROL DEVICE
In order to be able to work, the RT__ Link unit needs a control
device (DDC, CCP/CCI), which must be connected by the installer.
CCI Controller (Comfort Controller Interface) = optional Robur
control device which lets you manage up to three modulating
heat only GAHP units (A, WS, GS).
CCP Controller (Comfort Control Panel) = Robur control device which lets you manage in modulation mode up to three
GAHP units and all system components (probes, diverter/mixing
valves, circulating pumps), including any integration boiler.
DDC Control (Direct Digital Controller) = optional Robur device
to control one or more Robur appliances (GAHP heat pumps, GA
chillers and AY boilers) in ON/OFF mode.
RB100/RB200 Devices (Robur Box) = optional interface devices
complementary to DDC, which may be used to broaden its functions (heating/cooling/DHW production service demands, and
control of system components such as third party generators,
adjustment valves, circulators, probes).
Heat generator = equipment (e.g. boiler, heat pump, etc..) producing heating and/or DHW.
Preassembled Group / RT__ Link = equivalent terms, both
used to designate the generic heat/chiller hydronic group consisting of GAHP/GA/AY modules (see denition).
RTAR/RTCF/RTY/RTA/RTAY/RTYR/.. .Link to = initials to designate a specic heat/chiller preassembled group, consisting of a
specic combination of GAHP/GA/AY (see denition).
First start-up = preassembled group commissioning operation
that can only and exclusively be performed by a TAC.
III WARNINGS
III.1 GENERAL AND SAFETY WARNINGS
GAHP/GA/AY modules
As far as the individual GAHP/GA/AY appliances/modules
belonging to the preassembled group are concerned,
read the warnings in the respective Manuals (attached),
with particular regard to the following aspects:
Poisoning Moving parts Burn hazard Pressure vessels Water-ammonia solution Limescale and corrosion Chloride concentration Aggressive substances in air Switching the appliances o
4
Qualication of the installer/conductor/maintainer
Installation must exclusively be performed by a qualied
rm and by qualied personnel, with specic knowledge
on heating, cooling, electrical systems and gas appliances, in compliance with the laws in force in the Country of
installation.
Declaration of conformity
Upon completing installation, the installing rm shall
issue to the owner/client the appliance's workmanlike
conformity declaration, according to national/local regulations in force and the manufacturer's instructions/
provisions.
Page 5
III
Warnings
Misuse
The preassembled group must only be used for the purposes for which it has been designed. Any other use is
deemed hazardous. Incorrect use may aect operation,
duration and safety of the appliance. Adhere to the manufacturer's instructions.
Hazardous situations
Do not start the preassembled group in hazardous con-
ditions such as: gas odor, hydraulic/electric/gas system
problems, parts of the unit immersed in the water or
damaged, malfunction, deactivation or exclusion of control and safety devices.
In case of danger, request intervention by qualied per-
sonnel.
In case of danger, switch o the electrical power and gas
supplies only if this can be done in total safety.
Do not entrust children, persons with physical, sensory
or mental disabilities or persons with poor knowledge
and experience with use of the preassembled appliance.
Gas component tightness
Before performing any operation on gas ducting compo-
nents, close the gas valve.
Upon completing any procedure, perform the tightness
test according to regulations in force.
Gas smell
Distance from combustible or ammable materials
Do not deposit ammable materials (paper, diluents,
paints, etc.) near the preassembled group.
Acid ue gas condensate
If condensing units are present in the preassembled
group:
Discharge the acid condensate of combustion ue gas,
as indicated in Paragraph 3.10
with current exhaust regulations.
Shutting down the preassembled group
Interrupting the power supply during the operation of
the preassembled group may cause permanent damage
to the internal components.
Except for a hazard, do not interrupt the power supply to
turn o the preassembled group, but always and exclusively use the provided control device (DDC or CCP/CCI).
In the event of failure
Operations on internal components and repairs may
exclusively be carried out by a TAC, using only original
parts.
In the event of a failure of the preassembled group, or of
one or more of the individual appliances that make it up
and/or break parts of it, refrain from any repair or restoration attempt and contact the TAC immediately.
p. 30
, in compliance
If you smell gas:
Do not operate electrical devices near the preassembled
group (eg telephones, multimeters or other appliances
that can cause sparks).
Shut o the gas supply by turning the valve o. Disconnect electrical power supply by means of the
external isolation switch in the power supply electrical
panel.
Ask for qualied personnel from a phone away from the
preassembled group.
Electrocution hazard
Within the preassembled group (and the appliances that
compose it) there are live parts.
Disconnect the electrical power supply before any oper-
ation on appliance components.
For electrical connections exclusively use compliant
components and according to the specications provided by the manufacturer.
Make sure the preassembled group and the individual
GAHP/GA/AY modules of the same can not be reactivated inadvertently.
Connection and disconnection
For the RT__ Link electrical connection and disconnection operations follow the procedure described in Paragraph 7.1
p.40
.
Routine maintenance
Proper maintenance ensures the eciency and good operation of the preassembled group over time.
Maintenance must be performed according to the man-
ufacturer's instructions (see Chapter 7
compliance with current regulations.
Appliance maintenance and repairs may only be entrust-
ed to rms legally authorised to work on gas appliances
and systems.
Enter into a maintenance contract with an authorised
specialised rm for routine maintenance and for servicing in case of need.
Use only original parts.
Maintenance of GAHP/GA/AY modules
For the maintenance of the individual GAHP/GA/AY
modules belonging to the preassembled group, consult
their respective Manuals (attached).
Decommissioning and disposal
If the preassembled group or some of the individual
GAHP/GA/AY appliances/modules are to be dismantled,
please contact the manufacturer for disposal.
Keep the Manual
p. 40
) and in
Earthing
Electrical safety depends on an eective earthing system, properly connected to the preassembled group
and executed in accordance with current regulations.
Installation, use and maintenance manual – RT__ Link
This "Installation, Use, and Maintenance Manual", including all attached documents, must always accompany the
preassembled group and must be delivered to the new
owner or installer for sale or transfer.
5
Page 6
Warnings
III
III.2 CONFORMITY
EU Directives and standards
The GAHP/GA/AY modules/appliances that are part of RT__ Link,
namely the GAHP series heat pumps, GA ACF series chillers, and
AY00-120 condensing boilers comply with the essential requirements of the following standards and directives, each as
applicable:
▶
Eciency Directive 92/42/EEC and subsequent modications and additions.
▶
2016/426/EU "Gas Appliances Regulation" as amended and
added.
▶
2014/30/EC "Electromagnetic Compatibility Directive" as
amended and added.
▶
2014/35/EC "Low Voltage Directive" as amended and added.
▶
2006/42/EC "Machine Directive" as amended and added.
▶
2014/68/EU "Pressure Equipment Directive" as amended
and added.
▶
EN 12309 appliances for gas-red heating and/or cooling
absorption.
▶
EN 677 Specic requirements for condensing boilers with
nominal heat input up to 70 kW.
▶
EN 378 Refrigerating systems and heat pumps.
Other applicable provisions and standards
The design, installation, operation and maintenance of the systems shall be carried out in compliance with current applicable
regulations, depending on the Country and location, and in accordance with the manufacturer's instructions. In particular, regulations regarding the following shall be complied with:
▶
Gas systems and equipment.
▶
Electrical systems and equipment.
▶
Heating and air conditioning systems, heat pumps and chillers.
▶
Environmental protection and combustion products
exhaust.
▶
Fire safety and prevention.
▶
Any other applicable law, standard and regulation.
III.3 EXCLUSIONS OF LIABILITY AND
WARRANTY
Any contractual or extra-contractual liability of the manufacturer for any damage caused by incorrect installation and/or improper use and/or failure to comply with
regulations and with the manufacturer's directions/instructions shall be disclaimed.
In particular, the guarantee of the individual GAHP/GA/
AY modules/units belonging to the preassembled group
may be invalidated under the following conditions:
Incorrect installation. Misuse. Failure to comply with the manufacturer's indications on
installation, use and maintenance.
Alteration or modication of the product or any part
thereof.
Extreme operational conditions or however outside of
the operational ranges set forth by the manufacturer.
Damages caused by external agents such as salts, chlo-
rine, sulphur or other chemical substances contained in
the installation water or present in the air of the installation site.
Abnormal actions transmitted to the appliance by the
For the characteristics of the individual modules (GAHP/GA/AY
units) that make up the RT__ Link, and of the control devices
(DDC, CCP/CCI, ...), refer to the respective Manuals (attached).
Features and technical data
The aerothermal modules of RT__ Links may be in conguration:
▶
with standard fans (STD);
▶
with silenced fans (SIL or S1).
1.1 FEATURES
Preassembled groups
The RT__ Links are gas powered (natural gas or LPG) heating/
cooling sets, to supply hot and/or chilled water. Each group consists of a certain number of individual gas powered modules/
heating/cooling appliances (GAHP/GA/AY units). The set of appliances and components is preassembled at the factory, forming a complete hydronic group already predisposed to be simply
connected to the system.
Application
Each preassembled group according to its conguration (RTAR,
RTCF, RTY, RTAY, RTYR, RTA, ... Links) is able to simultaneously or
alternatively deliver heating, cooling, DHW production and heat
recovery, according to the needs of each single installation, with
a signicantly extensive range of heating and cooling output.
The various hydronic models (RTAR, RTCF, ... Links) are suitable
for all heating and cooling systems operating with hot and/or
chilled water, with common heat exchangers (e.g. radiators,
fan coils, radiant panels, fan heaters, air handling units, DHW
production boilers, pool heat exchangers...), including process
plants (industrial heat exchangers).
Manufacturing features
Each preassembled group, in addition to the GAHP/GA/AY heating/cooling modules/units gas powered, is composed of:
▶
delivery/return stainless steel hydraulic manifolds, insulated
with rigid cups lined with aluminum sheet;
▶
galvanized steel gas outlet manifold;
▶
exible connecting couplings of individual units to hydraulic
and gas manifolds;
▶
condensate discarge manifold (only if A/GS/WS/AY condensing appliances are included);
▶
electrical panel with protection devices (2 electrical panels
with more than 5-6 modules);
▶
bearing structure with galvanized steel sections.
Table1.1 Fittings diameter
Installation data
Gas tting diameter1 1/2” F
Water ttings diameter (inlet/outlet)2” M
Condensation discharge tting diameter1” F
Composition (GAHP/GA/AY modules)
The gas heating/cooling modules that make up a RT__ Link can
be:
from 2 to 8 in the case of GAHP/GA and AY
Groups with aerothermal units must be installed exclusively outside, while others may be installed either indoors or outdoors.
Congurations
▶
without circulators or with circulators (standard or oversize
circulators);
▶
2, 4 or 6 pipes, ie 1, 2 or 3 pairs of delivery/return hydraulic
collectors/connections for hot and/or cold water, connected
as needed.
1.2 CIRCULATING PUMPS
Preassembled groups without water circulation pumps
If the RT__ Link is without circulators, It must be installed on the
hydraulic/primary circuit at least one circulation pump, suitably
selected and rated (by the designer/installer).
Preassembled groups with water circulation pumps
In the RT__ Links already provided with circulators, each individual GAHP/GA/AY module that is part of the group has (at least) a
single independent circulator.
The circulators are installed externally to the GAHP/
GA units, which have a special protection cover (Figure
1.14
p.19
), while for AY00-120 units the circulators are
installed internally to the unit itself.
The available head at the hydraulic connections of the preassembled group should be considered net of internal pressure
drops, in the units and in the hydraulic manifolds.
Table 1.2
nominal ow in the largest conguration.
Table1.2 Minimum residual head
Wilo Yonos 25/0,5-72,0
Wilo Yonos 25/0,5-103,5
Wilo Stratos Para 25/1-112,0
Wilo Stratos Para 25/1-125,0
See the Design Manual for more detailed ow, head and pressure drop data.
p. 7
provides the minimum residual head at the
residual head [m w.c.]
1.3 CODING
Each group is encoded with a series of letters and digits that distinguish its composition and conguration. In order:
1. (3 or 4 letters) = group type (eg RTAR, RTCF, RTAY, RTA, RTY,
...), based on composing modules (GAHP A/AR/WS/GS, GA
ACF/HR/TK/LB, AY00-120;
2. (2 or 3 digits) = cold power, given by the sum of the cold
powers of the individual modules;
3. (2 or 3 digits) = heat power, given by the sum of the heat
powers of the individual modules;
4. (_, /4 or /6) = number of pipes, ie delivery/return manifold
pairs (1, 2 or 3);
5. (2 letters) = modules type;
6. (_, S, S1) = standard or silenced fans (only for aerothermal
units);
7. (MET/NAT, G25, GPL/LPG) = combustible gas (natural gas or
LPG);
8. (2 or 3 letters) = nationality;
Installation, use and maintenance manual – RT__ Link
7
Page 8
Features and technical data
1
9. (2 letters) circulators (with or without) and type (standard or
oversize);
10. (1 letter) predispositions, if any.
Figure1.1
The 1.1
coding in detail, providing the key for reading any possible composition and conguration, starting from an example.
p. 8
table/gure exemplies the meaning of the en-
8
Page 9
1
1.4 DIMENSIONS AND WEIGHTS
Features and technical data
The dimensions are given for the maximum footprint
conguration.
The weights are given for the maximum weight conguration.
Hydraulic/gas connections
Figure1.2 Water, gas and condensate discharge ttings position, for 2
pipes groups - Right side view (dimensions in mm)
Figure1.3 Position of water, gas and condensate connections for
4-pipe groups - Right side view (dimensions in mm)
A Condensate discharge connection [1" F] (only for groups with more than
one condensing unit)
B Gas connection [1 1/2" F]
C Cold/hot water outlet [2" M]
D Cold/hot water inlet [2" M]
* The height of low-noise model is 1650 mm
A Condensate discharge connection [1" F] (only for groups with more
than one condensing unit)
B Gas connection [1 1/2" F]
C Cold/hot water outlet [2" M]
D Cold/hot water inlet [2" M]
E Hot return [2" M]
F Hot delivery [2" M]
* The height of low-noise model is 1650 mm
Installation, use and maintenance manual – RT__ Link
9
Page 10
Features and technical data
Figure1.4 Position of water, gas and condensate connections for 6-pipe groups - Top view (dimensions in mm)
A Condensate discharge connection [1" F] (only for groups with more than one condensing unit). Sloping manifold, strictly connect on right side
B Gas connection [1 1/2" F]
C Cold/hot water outlet [2" M]
D Cold/hot water inlet [2" M]
E ACF HR recovery hot return (only left connection) [2" M]
F ACF HR recovery hot delivery (only left connection) [2" M]
G Hot return (only right connection) [2" M]
H Hot delivery (only right connection) [2" M]
1
Figure1.5 Position of water, gas and condensate connections for RTGS/WS groups - Right side view (dimensions in mm)
A Condensation drain connection [1 " F]
B Gas connection [1 1/2" F]
C Hot return [2" M]
D Cold return [2" M]
E Hot delivery [2" M]
F Cold delivery [2" M]
10
Page 11
1
Figure1.6 Preassembled ACF/A/AR group (with 2, 3, 4 and 5 units) - Dimensions and weights of preassembled units - front view (dimensions in mm)
Features and technical data
A 960 kg
B 1440 kg
C 1920 kg
D 2410 kg
Installation, use and maintenance manual – RT__ Link
11
Page 12
Features and technical data
Figure1.7 Preassembled AY group (with 2, 3, 4 and 5 units) - Dimensions and weights of preassembled groups - front view (dimensions in mm)
1
A 2 AY 330 kg
B 3 AY 450 kg
C 4 AY 580 kg
D 5 AY 700 kg
Note: The weight refers to links congured with oversize circulators
12
Page 13
1
Figure1.8 Preassembled ACF/A/AR + AY group (with 1+1, 1+2, 1+3, 1+4 units) - Dimensions and weights of preassembled groups - front and top
view (dimensions in mm)
Features and technical data
A 1+2 790 kg (*)
B 1+3 970 kg 1+4 1070 kg (*)
(*) The weight refers to a 2 pipe link (silent ventilation, "S"), congured with oversize circulators
The GAHP/GA + 1 AY00-120 congurations are replaced
by the Gitié units.
Installation, use and maintenance manual – RT__ Link
13
Page 14
Features and technical data
Figure1.9 Preassembled ACF/A/AR + AY group (with 1+5, 2+1 and 2+2 units) - Dimensions and weights of preassembled groups - front and top
view (dimensions in mm)
1
14
A 1+5 1210 kg (**)
B 2+1 1150 kg (*) 2+2 1270 kg (*)
(*) The weight refers to a 2 pipe link (silent ventilation, "S"), congured with oversize circulators
(**) The weight refers to a 4 pipe link (silent ventilation, "S"), congured on both circuits with oversize circulators
Page 15
1
Figure1.10 Preassembled ACF/A/AR + AY group (with 2+3, 2+4 and 2+5 units) - Dimensions and weights of preassembled groups - front and top
view (dimensions in mm)
Features and technical data
A 2+3 1460 kg (*) 2+4 1560 kg (**)
B 2+5 1700 kg (**)
(*) The weight refers to a 2 pipe link (silent ventilation, "S"), congured with oversize circulators
(**) The weight refers to a 4 pipe link (silent ventilation, "S"), congured on both circuits with oversize circulators
Installation, use and maintenance manual – RT__ Link
15
Page 16
Features and technical data
B
Figure1.11 Preassembled ACF/A/AR + AY group (with 3+1, 3+2 and 3+3 units) - Dimensions and weights of preassembled groups - front and top
view (dimensions in mm)
1
16
137
4936
A 3+1 1630 kg (*) 3+2 1750 kg (*)
B 3+3 1880 kg (**)
(*) The weight refers to a 2 pipe link (silent ventilation, "S"), congured with oversize circulators
(**) The weight refers to a 4 pipe link (silent ventilation, "S"), congured on both circuits with oversize circulators
155415291554
137
Page 17
1
Figure1.12 Preassembled ACF/A/AR + AY group (with 3+4 and 3+5 units) - Dimensions and weights of preassembled groups - front and top view
(dimensions in mm)
Features and technical data
A
A 3+4 2060 kg (*)
B 3+5 2190 kg (*)
(*) The weight refers to a 4 pipe link (silent ventilation, "S"), congured on both circuits with oversize circulators
Installation, use and maintenance manual – RT__ Link
B
17
Page 18
Features and technical data
Figure1.13 Preassembled ACF/A/AR + AY group (with 4+1, 4+2, 4+3 and 4+4 units) - Dimensions and weights of preassembled groups - front and
top view (dimensions in mm)
1
A
18
B
A 4+1 2120 kg (*) 4+2 2240 kg (**)
B 4+3 2380 kg (**) 4+4 2480 kg (**)
(*) The weight refers to a 2 pipe link (silent ventilation, "S"), congured with oversize circulators
(**) The weight refers to a 4 pipe link (silent ventilation, "S"), congured on both circuits with oversize circulators
Page 19
1
H
1.5 ROMA VALVE
Preassembled groups equipped with water circulation pumps
are also equipped with a check valve, mounted downstream of
each water circulation pump, equipped with air vent valves, as
Figure1.14 Roma valve GAHP/GA units
Features and technical data
detailed in the following Figure 1.14
units and in the following Figure 1.15
units.
p. 19
for the GAHP/GA
p.19
for the AY00-120
A Protection cover
B Protection cover
C Valve insulation
D Roma valve
E Air-vent valve
F Air-vent valve
G Circulator
H Connection to return
manifold
Figure1.15 Roma valve AY00-120 units
G
E
F
D Roma valve
E Air vent
E Air vent
G Circulator
H Connection to return
manifold
D
Installation, use and maintenance manual – RT__ Link
19
Page 20
Features and technical data
1
1.6 INDEPENDENT CIRCULATORS SELECTOR
SWITCH SETTINGS
In the RT__ Links already provided with circulators, each circulator is provided with a selector switch to determine the driving
mode of the circulator itself.
For Wilo Stratos Para circulators (available as optional), the selector switch is set as shown in Figure 1.16
the type of unit to which the circulator is connected.
Figure1.16 Wilo Stratos Para circulator selector switch setting
p.20
, depending on
For Wilo Yonos Para circulators (standard on RT__ Links already
provided with circulators) the selector switch must be set as
shown in Figure 1.17
IG Group electrical panel (QEG) switch disconnector
TR transformer 230/24 Vac
M1 transformer primary fuse
M2 condensate heating resistance protection fuse
M9 transformer secondary fuse
A blind panel (for detail of internal terminal blocks see specic gure)
I1 "ID00" unit magnetothermic breaker
Internal wiring diagrams
For the wiring diagrams of the internal cabling of the preassembled group, see the examples of some representative RT__ Link
models, in the Appendix 9.1
p.43
.
Power supply
The power supply of preassembled groups is 400 V three-phase
or 230 V single-phase.
Degree of protection
Preassembled groups have degree of protection IP X5D.
1.8 ELECTRONIC BOARDS
Electronic boards
Each module/unit GAHP/GA/AY belonging to the group has one
or more electronic boards (S61/Mod10/W1/AR11/AY10/S70) inside it. The boards are pre-wired, interconnected and connected
to the Electrical Panel of the preassembled group via a CANBUS signal cable. For the characteristics of the boards, see the
I2 "ID01" unit magnetothermic breaker
I3 "ID02" unit magnetothermic breaker
I4 "ID03" unit magnetothermic breaker
I5 "ID04" unit magnetothermic breaker
I6 "ID05" unit magnetothermic breaker
Note: the components within the QEG may have an order and/or position other
than the one shown in the gure
manuals of the individual GAHP/GA/AY units.
1.9 OPERATION MODE
ON/OFF or modulating operation
Depending on the types, the GAHP/GA/AY modules present on a
RT__ Link can work in one of the two following ways:
▶
Mode (1) ON/OFF, i.e. On (at full power) or O, with circulating pump at constant or variable ow.
▶
Mode (2) MODULATING, i.e. at variable load from 50% to
100% of heating capacity, with circulating pump at variable
ow.
The GAHP A, GAHP GS/WS modules can operate both in mode
(1) and mode (2).
GAHP-AR, GA ACF/HR/TK, and AY00-120 modules can only operate in mode (1).
For each mode, (1) or (2), specic control systems and devices
are provided (Paragraph 1.10
p.22
).
Installation, use and maintenance manual – RT__ Link
21
Page 22
Transport and positioning
1.10 CONTROLS
Control device
The preassembled group can only work when connected to a
control device, chosen from:
▶
(1) DDC controller (for ON/OFF operation);
▶
(2) CCP/CCI controller (for modulating operation, only for
A/WS/GS).
For connection of the selected device to the RT__ Link Electrical
Panel (Figure 4.4
1.10.1 Control system (1) with DDC (GAHP unit ON/
The DDC controller is able to control appliances, a single GAHP
unit, or even several Robur GAHP/GA/AY units in cascade, only
in ON/OFF mode (non modulating). For more details refer to the
DDC, RB100, RB200 Manuals and the Design Manual.
DDC Controller
The main functions are:
▶
setup and control of one (or more) Robur units of the ab-
sorption line (GAHP, GA, AY);
▶
Data display and parameters setting.
OFF)
p.34
), see Paragraph 4.4
p.33
.
2
▶
Hourly programming.
▶
Climatic curve control.
▶
Diagnostics.
▶
Errors reset.
▶
Possibility to interface with a BMS.
DDC functionality may be extended with auxiliary Robur devices
RB100 and RB200 (e.g. service requests, DHW production, Third
Party generator control, probe control, system valves or circulating pumps, ...).
1.10.2 Control system (2) with CCP/CCI (modulating
GAHP unit)
The CCP/CCI control is able to control up to 3 GAHP units in modulating mode (therefore A/WS/GS only, excluding AR/ACF/AY),
plus any integration ON/OFF boiler. For additional details and
diagrams refer to the CCP/CCI Manual and the Design Manual.
CCP/CCI Control
See CCP/CCI device Manual.
1.11 TECHNICAL CHARACTERISTICS
Refer to the technical data of the individual GAHP/GA/AY modules making up the group.
2 TRANSPORT AND POSITIONING
2.1 WARNINGS
Damage from transport or installation
The manufacturer shall not be liable for any damage
during transport and installation of the preassembled
group.
On-site inspection
Upon arrival at the site, ensure there is no transport dam-
age on packing, preassembled group, metal panels or
nned coils of the appliances that make up it.
After removing the packing materials, ensure the preas-
sembled group is intact and complete.
Packing
Only remove the packing after placing the preassembled
group on site.
Do not leave parts of the packing within the reach of
children (plastic, polystyrene, nails...) since they are potentially dangerous.
2.2 HANDLING
Handling and lifting
▶
Always handle the preassembled group in its packing, as de-
livered by the factory.
▶
To lift the assembled group use straps or slings inserted in
the holes of the base (Figure 2.1
▶
Use lifting beams to avoid damaging the outer panels and
the nned coils (Figure 2.1
▶
Comply with safety regulations at the installation site.
Figure2.1 Instruction for lifting
p.22
p.22
)
).
22
Weight
The crane and lifting equipment must be suitable for the
load.
Do not stand under suspended loads.
For weight, refer to Figures from 1.6
1.13
p.18
.
p. 11
to
A Front view
B Side view
In the event of handling with forklift or pallet truck,
comply with the handling instructions shown on the
packing.
Page 23
2
Transport and positioning
2.3 GROUP POSITIONING
Do not install the aerothermal RT__ Links inside a
room
The aerothermal RT__ Links include devices equipped
with nned coils and fan, approved for outdoor
installation.
Do not install the aerothermal RT__ Links inside a room,
not even if it has openings.
In no event start the aerothermal RT__ Link inside a
room.
Ventilation of aerothermal RT__ Links
The aerothermal RT__ Links require a large space, ventilated and free from obstacles, to enable smooth ow of
air to the nned coil and free air extraction from the fan
outlet, with no air recirculation.
Incorrect ventilation may aect eciency and cause
damage to the preassembled group.
The manufacturer shall not be liable for any incorrect
choices of the place and setting of installation.
Defrosting water drainage of RT__ aerothermal Links
In winter, in the aerothermal RT__ Links with GAHP A/AR units,
frost may form on the nned coils and the aerothermal appliances perform defrosting cycles.
▶
To prevent overowing and damage provide for a drainage
system.
In the event of indoor installation, the installation premises must
comply with the applicable local standards.
Do not install in a room that has no aeration openings.
Please refer to the manuals of the individual units suitable for
indoor installation, supplied with the links, for further important
prescriptions on the technical room.
2.4 MINIMUM CLEARANCE DISTANCES
Distances from combustible or ammable materials
▶
Keep the group away from combustible or ammable materials or components, in compliance with applicable regulations.
Clearances around the preassembled group
The minimum clearance distances shown in Figure 2.2
(bar any stricter regulations) are required for safety, operation
and maintenance.
Figure2.2 Minimum clearances (dimensions in mm)
p.23
Where to install the preassembled group for external
versions
In general, for all RT__ Links:
▶
They can be installed at ground level, on a terrace or on a
roof , if compatible with their dimensions and weight.
▶
They must be out of the dripping line from gutters or similar.
They do not require protection from atmospheric agents.
▶
No obstruction or overhanging structure (protruding roofs,
eaves, balconies, ledges, trees) shall obstruct the exhaust
fumes.
▶
The group ue gas exhaust must not be immediately close
to openings or air intakes of buildings, and must comply
with environmental regulations.
In particular, for aerothermal RT__ Links:
▶
They must be installed outside buildings, in an area of natural air circulation.
▶
No obstruction or overhanging structure (e.g. protruding
roofs, canopies, balconies, ledges, trees) must interfere with
the air owing out from the top of the appliances tted with
fans.
▶
Do not install near the exhaust of ues, chimneys or hot polluted air. In order to work correctly, aerothermal appliances
require clean air.
Acoustic issues
▶
Pre-emptively assess the group's sound eect in connection
to the site, taking into account that building corners, enclosed courtyards, restricted spaces may amplify the acoustic impact due to the reverberation phenomenon.
Machine room requirements for hydrothermal or
geothermal RT__ Links
Hydrothermal and geothermal RT__ Links (made up by GAHP
GS/WS modules) and the AY00-120 boilers links as well may be
installed either indoors or outdoors.
2.5 MOUNTING BASE
Mounting base constructive features
▶
Place the preassembled group on a levelled at surface
made of reproof material and able to withstand its weight.
(1) - installation at ground level
▶
Failing a horizontal supporting base, make a at and leveled
concrete base, at least 150 mm larger than the group dimensions on each side.
(2) - installation on terrace or roof
▶
The structure of the building must support the total weight
of the group and the mounting base.
▶
If necessary, provide a maintenance walkway around the
preassembled group.
Anti vibration connections and mountings
Although the group vibrations are minimal, resonance phenomena might occur in roof or terrace installations.
▶
Use anti-vibration mountings.
▶
Also provide anti-vibration joints between the preassembled group and water and gas pipes.
Installation, use and maintenance manual – RT__ Link
23
Page 24
Heating engineer
3 HEATING ENGINEER
3
3.1 WARNINGS
General warnings
Read the warnings in Chapter III.1
portant information on regulations and on safety.
Compliance with installation standards
Installation must comply with applicable regulations in
force, based on the installation Country and site, in matters of safety, design, implementation and maintenance
of:
heating systems; cooling systems; gas systems; electrical systems; ue gas exhaust; ue gas condensate discharge.
Installation must also comply with the manufacturer's
provisions.
GAHP/GA/AY modules
As far as the individual GAHP/GA/AY modules belonging
to the preassembled group are concerned, read the rel-
evant warnings and dangers in their respective Manuals
(attached).
p. 4
, providing im-
the gures 3.1
p.25
and 3.3
p.26
.
Hydraulic diagrams RT__ Links without circulating
pumps
These applications must be evaluated with particular care. The
common circulation pump is not provided with the link. Some
examples are shown in the gures 3.2
p.25
and 3.4
p.27
.
Minimum water content and buer tank
A high thermal inertia of the system favors the ecient operation of the appliances that are part of the group. Very short ON/
OFF cycles must be avoided.
▶
If necessary, provide for an inertial volume, to be suitably
sized (see Design Manual).
3.3 HYDRAULIC CONNECTIONS
Plumbing ttings
▶
O (= out) 2" M - WATER OUTLET (hot/chilled) (m = delivery to
the system);
▶
I (= in) 2 " M - WATER INPUT (r = return from the system).
on the right, at the bottom.
They can be moved to the left side by moving the blind caps
(unscrew and retighten).
(Figures 1.2
Hydraulic pipes, materials and features
▶
Use pipes for heating/cooling installations, protected from
weathering, insulated for thermal losses, with vapour barrier
to prevent condensation.
p.9
, 1.3
p.9
, 1.4
p.10
, 1.5
p.10
).
3.2 HYDRAULIC SYSTEM
Design and implementation
▶
The system must be designed and realized in a congruent
way with the features and functionality of the RT__ Link.
▶
For the appropriate system design, the following must be
considered: the characteristics of individual heating/cooling
appliances (GAHP/GA/AY modules/units) that make up the
group; the conguration of the manifolds and hydraulic connections; the endowment (or not) of circulators.
▶
For detailed information, please refer to the Design Manual
and/or contact the Robur consultancy service.
Primary and secondary circuit
▶
In many cases it is advisable to divide the hydraulic system
into two parts, primary and secondary circuit, uncoupled by
a hydraulic separator, or possibly by a tank that also acts as
inertial tank/buer.
Water ow
The preassembled group can be:
▶
already equipped with circulators for each unit/module (preferred conguration in many applications);
or
▶
without circulators, and then at least one common circulation pump at the primary circuit (a choice to be carefully
evaluated) will need to be installed.
Pipe cleaning
Before connecting the preassembled group, accurately
wash the water and gas piping and any other system
component, removing any residue.
Minimum components of primary plumbing circuit
▶
Always provide, near the hydraulic connections of the preassembled group:
on water piping, both output and input (m/r)
2 antivibration joints on water ttings 2 pressure gauges 2 isolation ball valves
on the input water piping (r)
1 SEPARATOR FILTER; 1 FLOW ADJUSTMENT VALVE, if the circulating pump is
constant ow (only for links without circulators);
1 WATER CIRCULATION PUMP, towards the appliance (on-
ly for links without circulators);
on the output water piping (m)
1 safety valve (3 bar) 1 expansion tank of the individual unit
24
Hydraulic diagrams RT__ Links with circulating pumps
Preferable in many applications. Some examples are shown in
Page 25
3
Principle schemes
Figure3.1 Example of hydraulic system diagram for connection of n. 1 RTCR version with circulating pumps
Heating engineer
1 anti-vibration connections
2 water lter (mesh min. 0.7 mm and max 1 mm)
3 shut-o valve
4 expansion tank of the primary circuit
5 3 bar safety valve
For the maximum available pressure head see Table 1.2
p.7
.
6 hydraulic separator (with air vent valve and drain valve)
7 expansion tank of the secondary circuit
8 circulating pump of the secondary circuit
9 DDC control panel
Figure3.2 Example of hydraulic system diagram for connection of n. 1 RTCR version without circulating pumps
1 anti-vibration connections
2 pressure gauge
3 ow regulator valve
4 water lter (mesh min. 0.7 mm and max 1 mm)
5 shut-o valve
6 expansion tank of the primary circuit
7 3 bar safety valve
8 primary circuit circulating pump
9 hydraulic separator (with air vent valve and drain valve)
10 expansion tank of the secondary circuit
11 circulating pump of the secondary circuit
12 DDC control panel
Installation, use and maintenance manual – RT__ Link
25
Page 26
Heating engineer
Figure3.3 Example of hydraulic system diagram for connection of n. 2 RTCR, version with circulating pumps
3
1 anti-vibration connections
2 water lter (mesh min. 0.7 mm and max 1 mm)
3 shut-o valve
4 expansion tank of the primary circuit
5 3 bar safety valve
For the maximum available pressure head see Table 1.2
p.7
6 hydraulic separator (with air vent valve and drain valve)
7 expansion tank of the secondary circuit
8 circulating pump of the secondary circuit
9 DDC control panel
.
26
Page 27
3
Figure3.4 Example of hydraulic system diagram for connection of n. 2 RTCR version without circulating pumps
Heating engineer
1 anti-vibration connections
2 pressure gauge
3 ow regulator valve
4 water lter (mesh min. 0.7 mm and max 1 mm)
5 shut-o valve
6 expansion tank of the primary circuit
3.4 ANTIFREEZE FUNCTION
Active antifreeze self-protection
The appliances (GAHP/GA/AY modules/units) that make up a
preassembled group are equipped with an antifreeze active
self-protection system to prevent freezing. The antifreeze function automatically starts the primary circulation pumps, and if
necessary also the burners (heat pumps and boilers only), when
the outside temperature approaches zero. Antifreeze function is
enabled by default for hot units and deactivated for cold units.
Electrical and gas continuity
The active antifreeze self-protection is only eective if
the power and gas supplies are assured. Otherwise, antifreeze liquid might be required.
3.5 ANTIFREEZE LIQUID
7 3 bar safety valve
8 primary circuit circulating pump
9 hydraulic separator (with air vent valve and drain valve)
10 expansion tank of the secondary circuit
11 circulating pump of the secondary circuit
12 DDC control panel
Always check product suitability and its expiry date with
the glycol supplier. Periodically check the product's preservation state.
Do not use car-grade antifreeze liquid (without inhibi-
tors), nor zinc-coated piping and ttings (incompatible
with glycol).
Glycol modies the physical properties of water (densi-
ty, viscosity, specic heat...). Size the piping, circulation
pump and thermal generators accordingly.
With automatic system water lling, a periodic check of
the glycol content is required.
With high glycol percentage (> 20…30%)
If the glycol percentage is ≥30% (for ethylene glycol) or
≥20% (for propylene glycol) the TAC must be alerted before rst start-up.
When producing DHW by DHW buer tank, use propylene glycol only.
Precautions with glycol
The manufacturer disclaims any liability for any damage
caused by improper glycol use.
Installation, use and maintenance manual – RT__ Link
Type of antifreeze glycol
Inhibited type glycol is recommended to prevent oxidation
phenomena.
27
Page 28
Heating engineer
3
Glycol eects
The Table 3.1
Table3.1 Technical data for lling the hydraulic circuit
The installer, the operator and the user must assure system water
quality of the plant water (Table 3.2
the manufacturer's instructions may compromise the operation,
integrity and durability of the appliances (GAHP/GA/AY modules/units) that make up the group, invalidating the warranty.
System water characteristics
Free chlorine or water hardness may damage the preassembled
group.
Adhere to the chemical-physical parameters in Table 3.2
and the regulations on water treatment for residential and industrial heating systems.
Table3.2 Chemical and physical parameters of water
CHEMICAL AND PHYSICAL PARAMETERS OF WATER IN HEATING/COOLING SYSTEMS
1 with aluminium or light alloys radiators, pH must also be lower than 8 (in compliance
with applicable rules)
2 value referred to the maximum water temperature of 80 °C
3 in compliance with applicable rules
Water topping up
The chemical-physical properties of the system's water may alter
over time, resulting in poor operation or excessive topping up.
▶
Ensure there are no leaks in the installation.
▶
Periodically check the chemical-physical parameters of the
water, particularly in case of automatic topping up.
Chemical conditioning and washing
Water treatment/conditioning or system washing carried out carelessly may result in risks for the preassembled group, the system, the environment and health.
Contact specialised rms or professionals for water treat-
ment or system washing.
p.28
). Failure to observe
°f< 15
°d< 8,4
p.28
glycol depending on its %.
Percentage of increase in pressure dropsLoss of eciency of unit
Check compatibility of treatment or washing products
with operating conditions.
Do not use aggressive substances for stainless steel. Do not leave washing residues.
3.7 SYSTEM FILLING
How to ll up the system
After completing all water, electrical and gas connections:
1. Pressurise (at least 1.5 bar) and vent the hydraulic circuit.
2. In links with circulators vent the circulators through the
vent valves in the body of the respective check valves
(see procedure below).
3. Let water ow (with appliances o).
4. Check and clean the lter(s) on the inlet pipe.
5. Repeat items 1, 2 and 3 until stabilization.
How to vent the GAHP/GA unit circulators (for links
with independent circulators)
1. Turn o the system by means of specially provided control
devices (DDC or CCP/CCI) and wait for the circulators to stop.
2. Remove the pump group protection cover (Figure
1.14
p.19
, details A and B).
3. Open the insulation (Figure 1.14
p.19
, detail C).
4. Close the sectioning valve on the delivery of the preassem-
bled group and open the rst vent valve (Figure 1.14
detail E).
5. Close the rst vent valve and open the sectioning valve on
the delivery of the preassembled group.
6. Close the sectioning valve on the return of the preassembled
group and open the second vent valve (Figure 1.14
detail F).
7. Close the second vent valve and open the sectioning valve
on the return of the preassembled group.
8. Reactivate the system and let water ow (with switched o
appliances).
9. If the air vent has been properly completed, close the insula-
tion and reassemble the protective covers. If not, repeat the
procedure from step 4.
How to vent the AY unit circulators (for links with in-
dependent circulators)
1. Turn o the system by means of specially provided control
devices (DDC or CCP/CCI) and wait for the circulators to stop.
2. Disassemble the front panel of the unit.
3. Close the sectioning valve on the delivery of the preassem-
bled group and open the rst vent valve (Figure 1.15
detail E).
p.19
p.19
p.19
,
,
,
28
Page 29
3
Heating engineer
4. Close the rst vent valve and open the sectioning valve on
the delivery of the preassembled group.
5. Close the sectioning valve on the return of the preassembled
group and open the second vent valve (Figure 1.15
p.19
detail F).
6. Close the second vent valve and open the sectioning valve
on the return of the preassembled group.
7. Reactivate the system and let water ow (with switched o
appliances).
8. If the air vent has been properly completed, reassemble the
front panel of the unit. If not, repeat the procedure from step
4.
The correct lling and air venting of the hydraulic system
are fundamental to ensure reliability over time of the
mechanical components, in particular the circulation
pumps.
3.8 FUEL GAS SUPPLY
Gas connection
▶
1"1/2 F
on the right, at the bottom.
It can be moved to the left side by moving the blind cap (unscrew
and retighten).
▶
Install an anti-vibration connection between the preassembled group and the gas supply piping.
,
Mandatory shut-o valve
▶
Provide a gas shut-o valve (manual) on the gas supply line,
next to the preassembled group, to isolate it when required.
▶
Perform connection in compliance with applicable regulations.
Gas pipes sizing
The gas pipes must not cause excessive pressure drops and,
consequently, insucient gas pressure for the appliances of the
group.
Supply gas pressure
This appliance is equipped for a maximum gas supply
pressure of 50 mbar.
The preassembled group appliances gas supply pressure, both
static and dynamic, must comply with Table 3.3
erance ± 15%.
Non compliant gas pressure may damage the appliances
and be hazardous.
p.29
, with tol-
Table3.3 Gas network pressure
Product
category
II
2H3B/P
II
2H3P
II
2ELL3B/P
II
2Esi3P
II
2HS3B/P
II
2E3P
II
2L3B/P
II
2EK3B/P
II
2E3B/P
II
2ELwLs3B/P
II
2ELwLs3P
I
2E(S)
I
3P
I
2H
I
3B/P
I
3B
Countries of destination
AL, BG, CY, CZ, DK, EE, FI, GR, HR, IT, LT,
MK, NO, RO, SE, SI, SK, TR
(1) GAHP-AR not approved for G25.1, G25.3 gases.
(2) GA ACF not approved for G25.1, G27, G2.350, G25.3 gases.
Vertical pipes and condensate
▶
Vertical gas pipes must be tted with siphon and discharge
of the condensate that may form inside the pipe.
▶
If necessary, insulate the piping.
LPG pressure reducers
With LPG the following must be installed:
▶
a rst stage pressure reducer, close to the liquid gas tank;
Installation, use and maintenance manual – RT__ Link
▶
a second stage pressure reducer, close to the group.
3.9 COMBUSTION PRODUCTS EXHAUST
Compliance with standards
The apliances that make up a preassembled group
(GAHP/AY modules/units) are approved for connection
to a discharge duct of combustion products.
29
Page 30
Heating engineer
3
Flue gas exhaust connection
The diameters (mm) of the connections, the residual head (Pa),
the ow rate (kg/h), the temperature (°C) and other smoke discharge properties of the individual GAHP/AY units belonging to
the group are indicated in their respective Manuals (attached).
For more informations, see also the Design Manual.
Flue gas exhaust kit
GAHP/AY units that are part of the group are equipped as standard with smoke exhaust kits, already assembled or to be assembled by the installer, which generally includes:
▶
1 pipe complete with terminal and socket for fuel gas analysis;
▶
1 support collar;
▶
1 possible 90° curve;
▶
1 rain cover.
How to install the ue gas kit
See the relevant instructions in the respective Manuals
of each GAHP/GA/AY appliance.
Possible ue
If necessary, the preassembled group can be connected to one
or more ue(s).
▶
To size the ue(s) refer to the data and information in the
GAHP/GA/AY individual manuals and the Design Manual.
▶
GAHP/GA/AY modules with dierent types of smoke exhaust
can not be connected to the same ue, but must be connected to separate ue.
▶
If several appliances are connected to a single ue, a clapet
valve is required on each drain, except the AR modules that
are natural draw.
▶
The ues must be designed, sized, veried and realized by a
qualied rm, with materials and components in accordance
with regulations in force in the country of installation.
▶
Always provide the necessary sockets for smoke analysis in
an accessible position.
3.10 FLUE GAS CONDENSATE DISCHARGE
If the preassembled group include GAHP A, GAHP GS/WS and
AY00-120 condensing appliances, condensation water is produced from combustion fumes, which must be evacuated in
compliance with current regulations.
Condensate acidity and exhaust regulations
The ue gas condensate contains aggressive acid substances. Refer to applicable regulations in force for condensate exhaust and disposal.
If required, install an acidity neutraliser of adequate ca-
pacity.
Do not use gutters to discharge the condensate
opposite side as the condensate manifold is sloping to-
wards the right side.
Flue gas condensate evacuation
To make the condensate evacuation duct:
▶
Size the ducts for maximum condensation ow rate (kg/h),
equal to the sum of the ow rates of the individual GAHP/AY
appliances/modules (see Manuals of the individual GAHP/AY
units attached);
▶
Use plastic materials resistant to acidity with pH 3 to 5;
▶
Provide for min. 1% slope, i.e. 1 cm for each m of pipe length
(otherwise a booster pump is required);
▶
Prevent freezing;
▶
Dilute, if possible, with domestic waste water (bathrooms,
washing machines, dish washers...), basic and neutralising.
Charging the siphon
In case of indoor installation, to prevent an initial discharge of
combustion products from the condensate drain, charge the siphon itself as described in the relative paragraph of the manuals
supplied with the single units.
If the appliance is operated with the siphon empty, there
is a risk of leaks of combusted gas.
3.11 DEFROSTING WATER DRAINAGE
Aerothermal units defrosting
In winter, in the aerothermal RT__ Links with GAHP A/AR
units, frost may form on the nned coils and the aero-
thermal appliances perform defrosting cycles.
Collection basin and drainage system
▶
Provide for a collection basin or containment rim and a discharge system of the defrosting water, to avoid overowing,
icing and damage.
3.12 SAFETY VALVE DRAIN
In the event of indoor installation, arrange for external piping of
the safety valve drainage, proceeding as described in the relative paragraph of the manuals supplied with the individual units.
The safety valve drain must be mandatorily ducted out-
side. Failure to comply with this provision jeopardizes
rst start-up.
Do not install any shut o device on the exhaust duct
between the safety valve and the outside exhaust.
30
Do not discharge the fume condensate in gutters, due to
the risk of materials corrosion and ice formation.
Flue gas condensate connection
The tting for ue gas condensate discharge is located on the
right side of the preassembled group (condensate discharge
manifold below Figures 1.2
1.5
p.10
).
The condensate drain cap can not be moved on the
p. 9
, 1.3
p. 9
, 1.4
p. 10
,
Page 31
4
4 ELECTRICAL INSTALLER
Electrical installer
4.1 WARNINGS
General warnings
Read the warnings in Chapter III.1
portant information on regulations and on safety.
Compliance with installation standards
Installation must comply with applicable regulations in
force, based on the installation Country and site, in matters of safety, design, implementation and maintenance
of electrical systems.
Installation must also comply with the manufacturer's
provisions.
Live components
After placing the preassembled group in the nal posi-
tion, and prior to making electrical connections, ensure
not to work on live components.
Earthing
The preassembled group must be connected to an eec-
tive earthing system, installed in compliance with regulations in force.
It is forbidden to use gas pipes as earthing.
Do not use the power supply switch to turn the preassembled group on/o
Never use the external switch to turn the preassembled
group on and o, as it may cause damage to the appliances and the system.
p. 4
, providing im-
To turn the preassembled group on and o, exclusively
use the suitably provided control device (DDC or CCP/
CCI).
Control of water circulation pump
In the case of RT__ Links without circulators:
The common hydraulic/primary circuit water pump must
be controlled by the Electrical Panel of the preassembled
group (terminals KK, PP, 12).
Circulator start/stop is not allowed without the request
of the preassembled group.
GAHP/GA/AY modules
As far as the individual GAHP/GA/AY modules belonging
to the preassembled group are concerned, read the relevant warnings and dangers in their respective Manuals
(attached).
4.2 ELECTRICAL SYSTEMS
Electrical connections must provide:
▶
(a) power supply line (three-phase or single-phase)
▶
(b) control system.
How to make connections
All electrical connections must be made in the preassembled group Electric Panel (QEG) (Figures 1.18
and 4.1
p.31
):
1. Ensure the group Electrical Panel is not live.
2. Open the Electric Panel with the appropriate key and re-
move the lower blind panel to access the terminal blocks.
3. Insert the wires through the suitable holes.
4. Make the connections.
5. Made the connections, reposition the blind panel and
reclose the Electrical Panel.
p.21
Figure4.1 Blind panel: detail of internal terminal blocks on DIN rail
A blind panel of QEG
AE power supply input terminals
K1-K2 24 V coil terminals for circulator request (hot/cold circuit side)
R-H condensate heating resistor terminals
Installation, use and maintenance manual – RT__ Link
1-2 24 V coil terminals for circulating pump request (HR recovery circuit side)
T1-T2 DHW tank thermostat terminals (HR recovery circuit side)
M 2-pole 24 Vac connector for service uses
CAN 3-pole connector for CAN bus network connection
31
Page 32
Electrical installer
4
4.3 ELECTRICAL POWER SUPPLY
Electrical protection
A 4-pole (three-phase) disconnector GS Figure 4.2
or bipolar (single-phase) IR+Id Figure 4.3
be provided by the installer in the external power supply
electrical panel, with fuses suitable for phases, minimum
contact opening 3 mm. No fuse on the neutral is allowed.
Indirect contact protection by means of dierential
switch and overload must be guaranteed by means of a
suciently dimensioned automatic switch or fuse.
Do not modify the RT__ Link Electric Panel or add components inside it (relays, ...).
Power supply line (three-phase or single-phase)
Provide a protected line (by the installer), which may be:
▶
three phase 400 V 3N - 50 Hz (Figure 4.2
or as an alternative,
▶
single phase 230 V 1N - 50 Hz (Figure 4.3
Figure4.2 Three phase power supply electrical connection 400 V 3N - 50 Hz
p.32
p.33
),
).
p. 33
p.32
must
How to connect the power supply
To connect the multipole power cable (Figures 4.2
4.3
p.33
):
1. Access the terminal blocks in the Electrical Panel of the
group (Paragraph 4.2
2. Locate the "AE" terminal block; with the "R-S-T-N" terminals.
3. Connect the conductors (ve/three-phase or three/sin-
gle-phase), providing the longest for the grounding (last to
break in case of accidental traction), to R-S-T-N three-phase
400 V 3N - 50 Hz terminals, Figure 4.2
terminals (phase L connected to all R,S,T terminals) for single
phase 230 V 1N - 50 Hz, Figure 4.3
4. Made the connections, reposition the blind panel and re-
close the Electrical Panel.
A cabling error, as well as aecting the operation, could
also damage the electrical components of the preassem-
bled group. In particular, in case of three-phase power
supply, be sure not to connect one of the phases to ter-
Figure4.3 Single phase power supply electrical connection 230 V 1N - 50 Hz
Electrical installer
AE power supply input terminals
IR bipolar disconnector with suitable fuse and minimum contact opening of 3 mm
LN phase/neutral
4.4 SETUP AND CONTROL
Electronic boards S61/Mod10/W10/AR11/AY10/S70
The RT__ Link electronics consists of the S61/Mod10/W10/AR11/
AY10/S70 electronic boards of the individual GAHP/GA/AY modules that are interconnected (pre-wired) by the CAN-BUS cable.
For information on S61/Mod10/W10/AR11/AY10/S70 electronic boards, see the manuals for the single GAHP/GA/AY unit
(attached).
Control systems, options (1) or (2)
Two separate control systems are provided for RT__ Links, (1)
and (2), each with specic features, components and diagrams:
▶
System (1), with the DDC control (with CAN-BUS
connections);
▶
System (2), with the CCP/CCI control (with CAN-BUS con-
nections).
For electrical connections and hookup Figure 4.4
CAN-BUS communication network
See GAHP/GA/AY units or DDC/RB100/RB200 control devices
manuals.
CAN-BUS signal cable
The DDC or CCP/CCI controllers are connected to the RT__ Link
through the CAN-BUS signal cable, shielded, compliant to Table
4.1
p.33
(admissible types and maximum distances).
For lengths ≤200 m and max 4 nodes (e.g. 1 DDC + 3 GAHP), a
simple 3x0.75 mm shielded cable may even be used.
Table4.1 CAN bus cables type
CABLE NAMESIGNALS / COLORMAX LENGTHNote
Robur
ROBUR NETBUSH= BLACKL= WHITEGND= BROWN450 m
Honeywell SDS 1620
BELDEN 3086A
TURCK type 530
DeviceNet Mid Cable
TURCK type 5711H= BLUEL= WHITEGND= BLACK450 m
Honeywell SDS 2022
TURCK type 531H= BLACKL= WHITEGND= BROWN200 m
H= BLACKL= WHITEGND= BROWN450 m
p.34
.
Ordering Code OCVO008
In all cases the fourth conductor should not be
used
How to connect the CAN-BUS cable to the RT__ Link
To connect the CAN-BUS cable to the preassembled group Electrical Panel, hence to the pre-wired S61/AY10 boards of the appliances it consists of (Figure 4.4
p.34
):
Installation, use and maintenance manual – RT__ Link
1. Access the terminal blocks in the Electrical Panel of the
group (Paragraph 4.2
p.31
).
2. Locate the "CAN" terminal block with the "GND-L-H"
terminals.
3. Connect the CAN-BUS cable to the GND (shielding/earthing)
33
Page 34
Electrical installer
4
+ L and H terminals (two signal wires).
4. Block the cable with the earthing terminal located behind
the DIN bar, ensuring a good electrical contact is made with
the shielding braid and the bare conductor (if any); see detail
in Figure 4.4
5. Position the J1 jumpers of the board of the last appliance on
the left of the RT__ Link closed if the node is terminal (case of
Figure4.4 Connection with CAN-BUS cable between 1 CCI/DDC and the electrical panel of the preassembled group
p.34
.
one RT__ Link only) or open if the node is intermediate (case
of several RT__ Links in the same system) Figure 4.6
6. Connect the CCI or the DDC (and possibly the RB100 or the
RB200) via the CAN-BUS cable according to the instructions
in the relevant device manuals.
7. Made the connections, reposition the blind panel and re-
close the Electrical Panel.
p.36
.
CAN 3-pole connector for CAN-BUS network connection
DDC CCI/DDC (rear view)
34
Page 35
4
1 RT__ Link + DDC/CCI conguration
Figure4.5 CAN-BUS connection for systems with one unit
Electrical installer
A terminal node connection to CCI/DDC
B CAN-BUS cable (not supplied - see table)
C terminal node on last unit (prewired)
QEG group electrical panel
E CCI/DDC
3 last unit of appliance (with "ID00")
Installation, use and maintenance manual – RT__ Link
35
Page 36
Electrical installer
2 RT__ Links + DDC/CCI conguration
Figure4.6 Example of CAN network with 7 nodes (1 CCI/DDC + 2 appliances connected on a single hydraulic circuit).
4
36
A terminal node connection to CCI/DDC
B CAN-BUS cable (not supplied - see table)
C terminal node on last unit (prewired)
QEG1 rst appliance group electrical panel
QEG2 second appliance group electrical panel
E CCI/DDC
F CAN-BUS cable (not supplied - see table)
3 last unit of appliance (with "ID00")
Page 37
4
Electrical installer
4.5 WATER CIRCULATION PUMPS
In RT__ Links with circulating pumps, the individual independent circulating pumps (1 or 2 for each GAHP/GA/AY module) are
already mounted and pre-wired on the preassembled group.
In RT__ Links without circulating pumps, electrical connections
must be made (both for power supply and control) of the common water circulation pump of the primary water circuit, as
shown in the diagrams Figures 4.7
p.37
, 4.8
p.38
.
Common circulation pump of a RT__ Link SC
Figure4.7 Electrical connection of single- or three-phase circulator directly controlled by the group (congurations "without circulators")
PM primary system water circulator (not supplied)
QP circulator electrical panel (external)
QEG preassembled group electrical panel
N/L neutral/phase single-phase circulation pump power supply
RST three-phase circulator power supply phases
IP circulating pump disconnector (not supplied)
Installation, use and maintenance manual – RT__ Link
F appropriate fuse for protecting the circulating pump used
KQ appropriate motor protection switch for the circulating pump used
KP NO relay for controlling the circulating pump (not supplied)
K1-K2 24 Vac coil terminals for the common circulating pump request of the hot/
cold link circuit
37
Page 38
Electrical installer
Figure4.8 Heat recovery exchanger: electrical connection of single- or three-phase circulator directly controlled by the group (congurations "with-
out circulators")
4
38
PM primary system water circulator (not supplied)
QP circulator electrical panel (external)
QEG preassembled group electrical panel
N/L neutral/phase single-phase circulation pump power supply
RST three-phase circulator power supply phases
IP circulating pump disconnector (not supplied)
How to connect the common circulation pump
To connect the common circulation pump (single-phase
or three-phase) of a RT__ Link without any circulating
pumps tted on (Figure 4.7
1. Access the terminal blocks in the Electrical Panel of the
group (Paragraph 4.2
2. Connect the two enable conductors to the appropriate
terminals K1-K2 or 1-2.
3. Made the connections, reposition the blind panel and
reclose the Electrical Panel.
p.31
p.37
).
or 4.8
p.38
)
F appropriate fuse for protecting the circulating pump used
KQ appropriate motor protection switch for the circulating pump used
KP NO relay for controlling the circulating pump (not supplied)
1-2 24 Vac coil terminals for the common circulating pump request of the heat
recovery circuit of link with HR
Page 39
6
5 FIRST START-UP
Normal operation
First start-up entails checking/setting up the combustion parameters and may exclusively be carried out by a
Robur TAC. NEITHER the user NOR the installation technician is authorised to perform such operations, under
penalty of voiding the warranty.
5.1 PRELIMINARY CHECKS
Preliminary checks for First start-up
Upon completing installation, before contacting the TAC the installer must check:
▶
Water, electrical and gas systems suitable for the required
capacities and equipped with all safety and control devices
required by the regulations in force.
▶
Absence of leaks in the water and gas systems.
▶
Type of gas for which the preassembled group is designed
(natural gas or LPG).
▶
Supply gas pressure corresponding to the required values,
with a tolerance of max ± 15%.
▶
Correct operation of the ue exhaust duct.
▶
Power supply mains corresponding to group nameplate data.
▶
Appliance correctly installed, according to the manufacturer's instructions.
▶
System installed in a workmanlike manner, according to national and local regulations.
Abnormal or hazardous installation situations
If abnormal or hazardous planting situations are found, the TAC
will not run the First start-up and the preassembled group shall
not be commissioned.
These situations may be:
▶
outdoor aerothermal RT__ Link installed within a room;
▶
failed compliance with minimum clearances;
▶
insucient distance from combustible or ammable materials;
▶
conditions that do not warrant access and maintenance operations in safety;
▶
starting/stopping the group with the main switch, rather
than with the provided control device (DDC or CCP/CCI);
▶
defects or faults in the preassembled group caused during
transport or installation;
▶
gas smell;
▶
non-compliant mains gas pressure;
▶
non-compliant ue gas exhaust;
▶
all situations that may involve operation abnormalities or are
potentially hazardous.
Non-compliant system and corrective actions
Should the TAC nd any non conformities, the user/installer is
bound to perform any corrective procedures required by the
TAC.
After performing the remedial actions (the installer's responsibility), if the TAC deems that safety and conformity conditions
are in place, rst start-up may be eected.
6 NORMAL OPERATION
This section is for the end user.
6.1 WARNINGS
General warnings
Prior to using the preassembled group carefully read the
warnings in Chapter III.1
formation on regulations and on safety.
First start-up by TAC
First start-up may exclusively be carried out by a Robur
TAC (Chapter 5
p.39
Never power the appliance o while it is running
NEVER power the appliance o while it is running (except in the event of danger, Chapter III.1
the appliances or system might be damaged.
6.2 SWITCH ON AND OFF
Routine switching on/o
The appliance may exclusively be switched on/o by
means of the suitably provided control device (DDC or
CCP/CCI).
p. 4
, providing important in-
).
p. 4
), since
Do not switch on/o with the power supply switch
Do not turn the preassembled group on/o with the
power switch. It may be harmful and dangerous for
group appliances and system components. If you need
to connect/disconnect the power supply, see Paragraph
7.1
p.40
.
Inspections before switching on
Before turning on the preassembled group check:
gas valve open; preassembled group electrical power (main switch (GS)
ON);
DDC or CCI power supply (through transformer); water circuit ready.
How to switch on/o
To turn on/o the RT__ Link see the Manual of the connected
control device (DDC or CCP/CCI).
Once switched on with the control device (DDC or CCP/CCI),
under normal operating conditions, the group appliances start/
stop automatically according to the heating and/or cooling requirements, providing hot/chilled water at the programmed
temperature.
It is not said that group appliances will activate imme-
diately, but will only start when there are actual heat or
cool demands.
Installation, use and maintenance manual – RT__ Link
39
Page 40
Maintenance
7
6.3 MESSAGES ON THE DISPLAY
4 digit display on GAHP/GA/AY modules
The S61/AY10 electronic boards on the GAHP/GA/AY modules,
which are part of the group, are equipped with a 4-digit display,
visible through the front panel of the respective appliances.
Signals in normal operation
On the display of each appliance of the group:
▶
When supplying voltage to the group all the LED light up
for 3 sec, then the name of the S61/AY10 electronic board
appears. After about 15 sec. the group appliances are ready
to operate.
▶
During normal operation, water temperature values alternate on the display: output, input and the dierence between the two.
Signals in the event of fault
In case of anomaly to one (or more) appliance(s), the relative display(s) ashes indicating an operating code (rst letter on the
display: "E" = error, or "U" = warning). Simultaneously, the relative display of the connected command ashes (DDC or CCI).
▶
If it is only a temporary warning, the appliance may continue
working.
▶
If it is a permanent error or warning the appliance stops.
6.4 ELECTRONIC ADJUSTMENT ON THE
APPLIANCE MENUS AND PARAMETERS
Electronic boards on the appliances
For the instructions on the S61/AY10 electronic boards on the
individual GAHP/GA/AY making up the group, refer to the respective GAHP/GA/AY Manuals (attached).
DDC or CCP/CCI control devices
For information on DDC or CCP/CCI control devices, see the respective manuals.
device (DDC or CCP/CCI). For instructions, see the control device
Manual.
Modify the settings of circulators
See Appendix 9.2
p.49
.
6.6 HOW TO RESTART THE LOCKEDDOWN
APPLIANCES
Fault signals on the displays
If one (or more) appliance(s) is/are blocked, an operating code
ashes on its/their respective display(s) (rst green digit on the
left, letter "U" = warning or "E" = error) , and the display of the
connected control device (DDC or CCP/CCI) ashes too
▶
To restart the appliance(s) you need to know and perform
the procedure for the problem reported and identied by
the code.
▶
Only act if you are familiar with the issue and with the procedure (technical expertise and professional qualications
might be required).
▶
If you do not know the code, the problem, or the procedure,
or you do not have sucient skills, and in any case of doubt,
contact the TAC.
Locked-down appliance
An external intervention (reset or repair) is required for a fault at
the appliance(s) or a problem with the system.
▶
A reset may be enough for a temporary and provisional fault.
▶
For a fault or breakdown, alert the maintenance technician
or TAC.
Reset
To perform a reset procedure (eg code 412 for the ame controller lockout), there are two possibilities:
(1) Act on the connected control device (DDC or CCP/CCI). For
instructions, see the device Manual.
(2) Operate on the electronic board of the appliance (S61/AY10),
as described in the relevant manual.
6.5 MODIFYING SETTINGS
Modify the settings through the DDC or CCP/CCI
To change the RT__ Link settings, use the connected control
Maintenance operations described herein may exclusively be performed by the TAC or skilled maintenance
technician.
Any operation on the internal components of the GAHP/
GA/AY modules that make up the RT__ Link may exclusively be performed by the TAC.
6.7 CIRCULATORS LOCKOUT
See Appendix 9.2
Before performing any operation: turn o the preassembled unit by means of the control device (DDC or CCP/
CCI) and wait for the end of the shutdown cycle of all the
units; stop the gas supply by acting on its tap; disconnect
the power supply as described in the Paragraph
Environmental or operational heavy conditions
In environmental or operational conditions particularly
heavy (for example: heavy-duty use of the appliance,
salty environment, etc.), maintenance and cleaning operations must be more frequent.
p.49
.
p.41
.
40
Page 41
7
Maintenance
Preassembled group electrical connection and
disconnection operations
investigate and resolve the problem before going to the
next step.
2. (4'.) Insert the remaining single-phase automatic break-
A) Electrical connection
The electrical connection must take place by doing the following sequence of operations:
1. Insert any switches/disconnectors located upstream of the
three-phase supply line of the preassembled group
2. Insert the 4-pole switch in the preassembled group electrical
panel
3. Insert the single-phase (magnetothermic) breakers of each
unit, located in the preassembled group electrical panel
In the case of commissioning (rst start-up), replace step
3 with the following steps:
1. (3 '.) Insert ONLY ONE of the single-phase automatic
(magnetothermic) breakers of the units located in the
preassembled group electrical panel, and verify that
the corresponding unit is actually powered; otherwise,
ers of the units.
B) Electrical disconnection
The electrical disconnection must take place by doing the following sequence of operations:
1. Open the single-phase automatic (magnetothermic) break-
ers of each unit, located in the preassembled group electrical panel
2. Open the 4-pole switch in the preassembled group electrical
panel
3. If required, open any switches/disconnectors located up-
stream of the three-phase supply line of the preassembled
group
For the maintenance of the individual GAHP/GA/AY
modules belonging to the preassembled group, consult
their respective Manuals (attached).
7.2 PREEMPTIVE MAINTENANCE
Recommended maintenance
▶
For pre-emptive maintenance, comply with the
recommendations in Table 7.1
Table7.1
GAHP AGAHP GS/WSAY00-120GA ACFGAHP-AR
Guidelines for the preventive maintenance operations
visually check of the general condition of the unit and of its nned coil√ (1)--√ (1)√ (1)
check the correct operation of the device used for monitoring the water
ow
check the % value of CO
check gas pressure to the burners---√√
Check of the unit
Check for every
DDC or CCI
(1) It is suggested to clean the nned coil once every 4 years (optimal frequency of the cleaning operation is in any case strongly aected by the installation site). Avoid excessively aggressive
cleaning of the nned coil (e.g. high-pressure washer).
check that the condensate discharge is clean (If necessary, frequency of
the maintenace operation must be increased)
replace the belts after 6 years or 12,000 hours of operation√√-√√
check/restore the pressure of the primary hydronic circuit--√-check/restore the air pressure inside of the expansion vessel of the
primary hydronic circuit
check that the plant is able to achieve the setpoint temperature√√√√√
download the event history√√√√√
2
√√√√√
√√√--
√√√--
--√--
p.41
.
7.3 SCHEDULED ROUTINE MAINTENANCE
Maintenance every 2 years
▶
For scheduled routine maintenance, perform the operations
Table7.2
Ordinary scheduled maintenance
clean the combustion chamber√ (1)√ (1)√√√ (1)
clean the burner√ (1)√ (1)√√√ (1)
Check of the unit
(1) Only in case the analysis of combustion products is non-compliant.
clean the ignition and ame sensor electrodes√√√√√
check that the condensate discharge is clean√√√-replace the silicone gasket between the front plate and the exchanger--√--
Installation, use and maintenance manual – RT__ Link
in Table 7.2
p.41
, at least once every 2 years.
GAHP AGAHP GS/WSAY00-120GA ACFGAHP-AR
41
Page 42
Diagnostics
8
7.4 PERIODS OF INACTIVITY
Avoid emptying the installation
Emptying the system can cause damage to the hydraulic pipes,
for oxidation or corrosion.
Deactivate the group in winter
If you intend to stop the preassembled group during the winter,
ensure at least one of the following two conditions:
1. antifreeze function active (Paragraph 3.4
2. sucient antifreeze glycol (Paragraph 3.5
Prolonged periods of inactivity
▶
If you plan to leave the preassembled group idle for a long
time, disconnect it from the electrical and gas supply mains.
These operations must be performed by qualied personnel.
How to disable the group for long periods
1. Turn o the group using the connected (DDC or CCP/
CCI) control device (Paragraph 6.2
2. Only when all the appliances of the grup are completely
powered o, disconnect the power supply as described
p.39
p.27
p.27
).
);
).
in Paragraph 7.1
3. Close the gas valve.
How to reactivate the group after long periods of inactivity
Prior to reactivating the group, the manager/maintainer
of the system must rst:
Check whether any maintenance operations are re-
quired (contact the TAC; see Paragraphs 7.2
7.3
p.41
).
Check content and quality of the water in the system, and
if necessary top it up (Paragraphs 3.7
and 3.5
p.27
Ensure the ue gas exhaust duct is not obstructed, and
that the condensate drain is clean.
After completing the above checks:
1. Open the gas valve and ensure there are no leaks; should
gas smell be noticed, close the gas valve again, do not
switch any electrical devices on and request intervention
by qualied personnel.
2. Connect the electrical power supply as described in Par-
agraph 7.1
3. Turn on the preassembled group using the provided
control device (DDC or CCP/CCI, Paragraph 4.4
).
p.40
p.40
.
.
p.41
and
p. 28
, 3.6
p. 28
p.33
).
8 DIAGNOSTICS
8.1 APPLIANCES/CONTROLLERS
Refer to the operating codes tables in the Manuals of the individual units or in the DDC/CCI/CCP controls Manuals (attachments)
for diagnostic.
8.2 CIRCULATING PUMPS
See Appendix 9.2
p.49
.
42
Page 43
9
9 APPENDICES
9.1 WIRING DIAGRAMS AND INTERNAL WIRINGS
Figure9.1 Diagram 1
TR
I1
U1
M9
Appendices
2A
U2
I1
S0 (fase0)
I2
N0
I2
1A
M1
N0
T0 (fase0)
230Vac
M2
24Vac
U0
U3
CAN
M
N0-M2
F0-M2
4A
N0
R0
N0
I6
AT
F0-TA
F0-M2
N
R
UNIT 6
N
S
S0
N0
I5
UNIT 5
CHR
N
PE
T
UNIT 4
N
R
N
S
UNIT 2UNIT 3
NT
UNIT 1
N0
T0
S0
R0
R H
K2
U3
K1
12
CF
11
CF
10
CF
9
CF
8
CF
7
CF
6
U2
4 5
2 3
CF CF CF CF CF
1
CF
N
NT
T
S
S
R
R
AE
T0
N0
R0
N0
S0
I4
I3
I2
N0
T0
I1
AE power supply input terminals
AT antifreeze thermostat
CAN 3-pole connector for CAN-BUS network connection
CHR condensation heating resistance
I1 "ID00" unit magnetothermic breaker
I2 "ID01" unit magnetothermic breaker
I3 "ID02" unit magnetothermic breaker
I4 "ID03" unit magnetothermic breaker
I5 "ID04" unit magnetothermic breaker
Installation, use and maintenance manual – RT__ Link
I6 "ID05" unit magnetothermic breaker
IG Group electrical panel (QEG) switch disconnector
M 2-pole 24 Vac connector for service uses
M1 transformer primary fuse
M2 condensate heating resistance protection fuse
M9 transformer secondary fuse
PE earth conductor
TR transformer 230/24 Vac
43
Page 44
Appendices
IEP
Figure9.2 Diagram 2
9
I1
S0 (fase0)
I2
N0
I1
I2
230Vac
1A
M1
N0
T0 (fase0)
TR
M2
24Vac
N0-M2
F0-M2
4A
SCH
ID: 04
N.O.
0
YR
W
CONTACT
H
2A
U1
U0
M9
U2
U3
B
L
GND
CAN
M
SCH
SCH
SCH
SCH
ID: 03
N.O.
ID: 02
N.O.
ID: 01
N.O.
ID: 00
N.O.
0
YR
W
CONTACT
0
YR
W
CONTACT
0
YR
W
CONTACT
0
YR
W
CONTACT
H
L
GND
F0-TA
AT
F0-M2
H
L
B
N0
S0
I5
N0
T0
I4
N0
R0
I3
N0
S0
I2
N0
T0
I1
PE
N
S
UNIT 5
N
T
UNIT 4
N
R
N
S
UNIT 2UNIT 3
NT
UNIT 1
N0
T0
S0
R0
IG
R H R H
H
R
N
T
T N
S
S
R
R
AE
A
GND
H
L
GND
H
L
GND
44
See the Figure 9.1
p.43
legend.
IEP Interior of the electrical panel
A CLOSED jumpers (from factory): keep CLOSED only if ID00 is a TERMINAL
node on the CAN network
B Open Jumpers (from factory): not to touch
Note on the position of jumpers A:
If ID00 is an intermediate node:
• the electric installer must OPEN ID00 unit jumpers
• the TAC must reset from the board, to progression, the enumeration of the
board ID of all units;
• on appliances with 2 units, only ID00 + ID01 units will be present (with
jumpers predened as in the example)
• on appliances with 3 units, only ID00 + ID01 + ID02 units will be present
(with jumpers predened as in the example)
• on appliances with 4 units, only ID00 + ID01 + ID02 + ID03 units will be
present (with jumpers predened as in the example)
Page 45
9
IEP
~~~~~~~~~~
Figure9.3 Diagram 3
I1
I2
I1
I2
N0
T0 (fase0)
R0 (fase0)
N0
1A
M1
Appendices
N
2A
TR
U1
24Vac
230Vac
U0
M9
U2
U3
B
CAN
T
KPs
T
KPt
B
M2
4A
N0
S0
N0
N0-M2
F0-M2
T0
M
F0-TA
AT
F0-M2
R H
T2
N5
No
Com
N
S
I5
I4
Nc
No
Com
N
T
Nc
T1
H
L
L N
230V
PUMP
SCH
ID: 04
N.O.
CONTACT
H
L
L N
230V
PUMP
SCH
ID: 03
N.O.
CONTACT
H
L
L N
230V
PUMP
SCH
ID: 02
N.O.
CONTACT
N3N4
N0
R0
N0
S0
I2I3
N1N2
N0
T0
I1
PE
No
N
S
Com
R
Nc
No
Com
N
Nc
No
Com
NT
Nc
I
I1
N0
N
T
T0
S0
R0
IG
T N
S
S
R
R
AE
A
H
L
GNDGNDGNDGND
L N
230V
PUMP
SCH
ID: 01
N.O.
CONTACT
H
L
GND
L N
230V
PUMP
SCH
ID: 00
N.O.
CONTACT
TER
L
R N
KPKPKPKP
A2
A1
4 N L
3
N
MA
2
1
TER
KP
A2
A1
4 N L
3
MA
N
2
1
TER
A2
A1
4 N L
3
MA
N
2
1
TER
A2
A1
4 N L
3
MA
N
2
1
TER
A2
A1
4 N L
3
MA
N
2
1
INT. I5
05
PM
05
PMR
N
L
S N
INT. I4
04
PM
04
PMR
N
L
S N
INT. I3
03
PM
03
PMR
N
L
T N
INT. I2
02
PM
02
PMR
N
L
T N
INT. I1
01
PM
01
PMR
See the Figure 9.2
p.44
legend.
KPt Thermostat with setpoint calibration of DHW tank (not supplied)
KPs Thermostat calibrated at 35 °C with capillary tube in the lower part of the
DHW tank (not supplied) [to be provided in the event the water ow rate
on the recovery circuit exceeds the nominal value of 1000 l/h]
MA unit terminal block
Installation, use and maintenance manual – RT__ Link
PM Water pump < 700 W
PMR Recovery exchanger pump
TER Power supply terminal block 230 Vac
NOTE if there are no ACF 60-00 HR units in the preassembled group, the T1-T2
terminals must be jumpered.
45
Page 46
Appendices
INT. I5
INT. I4
INT. I3
INT. I1
INT. I2
IEP
Figure9.4 Diagram 4
I1
I2
I1
I2
1A
M1
N0
N0
T0 (fase0)
R0 (fase0)
9
N
2A
TR
U1
24Vac
230Vac
U0
M9
U2
U3
CAN
H
L
GND
B
H
L
L NL N
230V
PUMP
SCH
ID: 04
N.O.
CONTACT
M
H
L
GNDGND
230V
PUMP
SCH
ID: 03
N.O.
CONTACT
M2
4A
N0-M2
F0-M2
F0-TA
KPs
T
KPt
T
AT
F0-M2
TER
L
KP
A2
A1
MA
TER
KP
A2
A1
MA
S N
4 N L
3
N
2
1
N
L
T N
4 N L
3
N
2
1
IG
U4
T2
T1
2
1
10
CP
9
CP
8
CP
7
CP
6
CP
5
CP
4
CP
3
CP
2
1
CP CP
R H
K2
K1
10
CF
9
CF
8
CF
7
CF
6
4 5
2 3
CF CF CF CF CF
1
CF
N
NT
T
S
S
R
R
B
A
AE
H
L
GND
H
L
GND
H
L
GND
SCH
SCH
SCH
ID: 02
N.O.
ID: 01
N.O.
ID: 00
N.O.
CONTACT
CONTACT
CONTACT
0
YR
W
0
YR
W
0
YR
W
N0
S0
N0
T0
N0
R0
N0
S0
N0
T0
N
S
UNIT 5
I5
N
T
I4
UNIT 4
N
R
I3
N
S
I2
UNIT 2UNIT 3
NT
I1
UNIT 1
N0
T0
S0
R0
PE
TER
TER
TER
N
L
R N
4 N L
3
N
2
1
N
L
S N
4 N L
3
N
2
1
N
L
T N
4 N L
3
N
2
1
46
See the Figure 9.3
p.45
legend.
Page 47
9
IEP
~
~
~
~
~
~
~
~
Figure9.5 Diagram 5
Appendices
See the Figure 9.3
p.45
I1
T0 (fase0)
legend.
CONTACT
NO
2A
TR
I1
I2
I2
U1
24Vac
230Vac
U0
1A
M1
N0
N0
N0-M2
F0-M2
4A
M2
R0 (fase0)
N0
S0
N0
S0
N0
T0
N0
R0
N0
S0
N0
T0
M9
U2
U3
F0-TA
AT
F0-M2
N
R
I6
N
S
I5
No
N
T
I4
N3N4
I2I3
N1N2
I1
PE
Nc
No
N
R
Nc
No
N
S
Nc
No
NT
Nc
I1
N0
T0
S0
R0
CAN
H
L
GND
M
T
KPs
T
KPt
BB
H
R
T2
T1
Com
Com
B
Com
Com
I
N
T
T N
S
S
R
R
IG
AE
A
H
L
SCH
SCH
SCH
SCH
SCH
ID: 03
ID: 02
ID: 01
ID: 00
NO
PUMP
PUMP
PUMP
PUMP
ID: 05
CONTACT
SCH
ID: 04
A1
L N
230V
N.O.
CONTACT
A1
L N
230V
N.O.
CONTACT
A1
L N
230V
N.O.
CONTACT
A1
L N
230V
N.O.
CONTACT
GND
H
L
GND
H
L
H
L
H
L
GNDGNDGND
H
L
GND
N
L
R N
INT. I6
TER
TER
TER
KP
A2
MA
TER
KPKPKP
A2
MA
TER
A2
MA
TER
A2
MA
~
06
PM
N
L
S N
INT. I5
~
05
PM
N
L
T N
INT. I4
04
PM
4 N L
3
N
2
1
4 N L
3
N
2
1
4 N L
3
N
2
1
4 N L
3
N
2
1
04
PMR
N
L
R N
INT. I3
03
PM
03
PMR
N
S N
L
INT. I2
02
PM
02
PMR
N
L
T N
INT. I1
01
PM
01
PMR
Installation, use and maintenance manual – RT__ Link
47
Page 48
Appendices
IEP2IEP1
Figure9.6 Diagram 6
9
B
SCH
ID: XX
N.O.
CONTACT
0
Y
W
R
H
L
GND
H
L
GND
CAN
M
B
NT
S
R
NT
S
R
H
L
GND
SCH
ID: XX
N.O.
CONTACT
0
Y
W
R
AE
B
SCH
ID: XX
N.O.
CONTACT
0
Y
W
R
H
L
GND
H
L
GND
CAN
M
A
SCH
ID: XX
N.O.
CONTACT
0
Y
W
R
H
L
GND
NT
S
R
AE
48
See the Figure 9.2
p.44
legend.
IEP Interior of the electrical panel
RSTN phases/neutral
Page 49
9
Appendices
9.2 CIRCULATING PUMPS
To access the circulating pumps, remove the plastic cover (for GAHP/GA, Figure 1.14
120 units (Figure 1.15
p.19
).
Table9.1 Wilo Yonos pump block signalings
CodeFaultCauseRemedial action
E04Insucient mains voltageSupply voltage too low on the mains sideCheck that power supply voltage is correct.
E05Excessive mains voltageSupply voltage too high on the mains sideCheck that power supply voltage is correct.
E09 (1)Turbine operation
E10LockingThe rotor is lockedAsk for TAC intervention.
E21 (2)OverloadThe motor runs with dicultyAsk for TAC intervention.
E23Short circuitMotor current too highAsk for TAC intervention.
E25Contact/windingDefective motor windingAsk for TAC intervention.
E30
E31
E36Electronic system errorDefective electronic systemAsk for TAC intervention.
1 Only for pumps with P1 ≥ 200 W.
2 In addition to the LED indicator, the fault LED turns red with xed light. See also message E21.
Over temperature of the
module
Power module overtemperature
The pump is driven backwards (pump ow from the delivery side to the suction side)
Module inside vane too hot
Ambient temperature too high
Table9.2 Wilo Yonos pump warning messages
CodeFaultCauseRemedies
E07Turbine operationWith the pump o the impeller remains in operationCheck the ow rate. If necessary, t the check valves.
E11Dry operationAir in the pumpCheck the amount/pressure of the water.
E21 (1)OverloadThe motor runs with dicultyAsk for TAC intervention.
p.19
), or remove the front panel of the AY00-
Check the ow rate. If necessary, t the check valves.
Improve ventilation of the environment, check the conditions of use. If necessary, ask for TAC intervention.
Improve ventilation of the environment, check the conditions of use. If necessary, ask for TAC intervention.
1 See also blocking signal E21.
Installation, use and maintenance manual – RT__ Link
49
Page 50
Page 51
Page 52
Robur mission
20/03/2019
Robur is dedicated to dynamic progression
in research, development and promotion
of safe, environmentally-friendly, energy-eciency products,
through the commitment and caring
of its employees and partners.
19MCMSDC009
Code: D-LBR563
Revision: F
Robur S.p.A.
advanced technologies
for climate conditioning
via Parigi 4/6
24040 Verdellino/Zingonia (BG) Italy
+39 035 888111 - F +39 035 884165
www.robur.it robur@robur.it
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.