Robertshaw RS311N Installation And Operation Manual

1 2 3 4 250028-001
Installation and Operation
Instructions for
RS311N
1-Heat / 1-Cool
Setback
Thermostat
for Gas, Electric, & Heat Pump Systems
www.robertshawclimate.com
TABLE OF CONTENTS
Introduction……………………………………… … ………
2
Standard Features………………………………………...
2
Button Operations…………………………………………
3
Thermostat Locations……………………………………..
3
Removing The Thermostat From The Backplate………
4
Description Of The Dip Switch Functions………………
5
Features And Settings……………………………………
6-7
Cover Lock…………………………………………………
7
Replacing The Thermostat On The Backplate…………
7
Button Press Combinations………………………………
8
Keypad Lockout………………………..………………….
9
Temporary Override………………………………………
9
Setback Input Terminals – Special Functions..………..
9
Changing Fahrenheit (°F) To Celsius (°C)……………..
10
Power Failures…………………………………………….
10
Remote Sensors (Optional)………………………………
10
Setup Menu………………………………………………..
10
Wiring Diagrams…………………………………………..
11-16
Specifications………………………………………………
17
Sensor Faults……………………………………………...
17
Description Of Icons………………………………………
18-19
Display………………………………………………………
19
Warranty…………………………………………………....
19-20
INTRODUCTION
The RS300N family of Non-Programmable Setback Thermostats represents the most advanced solid-state, microcomputer temperature control on the market today. The thermostat incorporates state-of-the-art technology packaged in an extremely low profile designer series case. They are a direct replacement for 300 series and DSL series non-programmable units. The Ultra-Touch push-buttons are combined with an easy-to-read, blue backlit full function liquid crystal display to provide the ultimate in user friendly operation of the heating and air conditioning, including gas, electric, oil and heat pump systems.
STANDARD FEATURES
No batteries required – always remembers
setpoints
Integrated electronic heat anticipation and cooling
droop with
built-in short cycle equipment protection
Intelligent Fuzzy Logic staging for
ef
ficient operation of
equipment, including auxiliary heat
Tamper proof electronic keyboard lockout
with
pr
ogrammable
override ranges and time
Automatic, Manual and Recirculation Fan
operation
Adjustable Fan Purge after Heating or Cooling Call
Automatic Heat/Cool Changeover, Cooling Only, or Heating
Only Mode Control
Adjustable Deadband between Heat and Cool Setpoint in
Auto Changeover
Dual Heating and Cooling Setpoints for Day (Occupied) and
Night (Unoccupied) operation
Adjustable Min/Max Setpoints for Heating and Cooling
Keypad Lockout with restricted +/-3°F(1°C) or +/-5°F(2°C)
setpoint adjustment and 0min to 24Hr override timer with
a
utomatic retur
n
Selectable Fahrenheit or Celsius
temperature
display
Adjustable Backlight Brightness
Integrated Installer Setup Menu
Occupancy Sensor Inputs (use RS-OSC or RS-OSW)
BUTTON OPERATION
THERMOSTAT LOCATION
To ensure proper operation, the thermostat
should be mounted on an inside wall in a frequently occupied area of the space. In addition, its position must be at least 18” (46 cm) from any outside wall,
and
approximately 5’, (1.5 m) above the floor in a
location with freely circulating air of an average
temperature.
Be sure to avoid the following locations:
Behind doors or in cor ners where freely
cir
culating air
is
unavailable
Where direct sunlight or radiant heat
from
appliances might
affect control
operation
On an outside wall
Adjacent to, or in line with, conditioned air
discharge grilles,
stairwells or outside
doors
Where its operation may be affected by steam
or water pipes or warm air stacks in an adjacent partition, or by any unheated / uncooled area behind the thermostat
Where its operation may be affected by
lighting dimmers
next
to it
Where its operation will be affected by the
supply air of an
adjacent
unit
Near sources of electrical interference such as
ar
cing
relay
contact
REMOVING THE THERMOSTAT FROM THE BACKPLATE
1. Insert a flat blade screwdriver or coin 1/8” into the slot located in the bottom center of the thermostat case and twist 1/4 turn. When you feel or hear a click, grasp the case from the bottom two corners and separate from the backplate as shown in the diagram at the left. Some models require more force than others when separating due to the number of terminals used.
2. Swing the thermostat out from the bottom.
3. Lift the thermostat up and off the backplate.
4. Place the rectangular opening in the backplate over the equipment control wires protruding from the wall and, using the backplate as a template, mark the location of the two mounting holes
NOTE: There are several versions of the RS300N thermostat. The wiring instructions for the equipment are identical.
5. Use the supplied anchors and screws for mounting on drywall or plaster; drill two 3/16” (5mm) diameter holes at the marked locations; use a hammer to tap the nylon anchors in flush to the wall surface and fasten backplate using the supplied screws. (Do not over tighten!)
6. Connect the wires from your system to the thermostat terminals as shown in the wiring diagrams. Carefully dress the wires so that any excess is pushed back into the wall cavity or junction box. Ensure that the wires are flush to the plastic backplate. The access hole should be sealed or stuffed to prevent drafts from affecting the thermostat.
NOTE: This product must be supplied from a UL/CSA LISTED Class 2 power supply. Operation from other supplies may result in a potential fire risk.
5 6 7 8
DESCRIPTION OF THE DIP SWITCH FUNCTIONS
DIP Switch 1 : GE/HP Operation
Place DIP Switch 1 to OFF position
for Gas/Electric fur
nace operation. Place DIP Switch 1 to ON position for Heat
Pump operation.
DIP Switch 2 : CLK Terminal Operation
Place DIP Switch 2 to OFF position to allow a short across the CLK terminals via contact closure or Robertshaw® Occupancy Sensor to engage Night (Unoccupied) operation until released. Place DIP Switch 2 to ON position to allow a short to change the thermostat to OFF mode until released.
DIP Switch 3 : 2 Minute or 4 Minute Minimum Off Times
When DIP Switch 3 is in the ON position, the minimum OFF time is 2
minutes. When in the OFF position it is set to 4 minutes.
The system will allow equipment recovery for 2 or 4 minutes before turning on again. This is also
known as short cycle pr
otection.
DIP Switch 4 : Unlocked/Locked Keypad
When DIP Switch 4 is in the ON position, all
buttons
are disabled with the exception of the UP, DOWN and MODE button. Users will be restricted to either a +/-3°F(1°C) or +/-5°F(2°C) range from the
Day (Occupied)
setpoints as defined by DIP Switch 7. Users
will still be able to
alternate
between HEAT and COOL.
DIP Switch 5 : Plenum Fan Switch
/Add-On
Heat Pump
DIP Switch 5 is used to determine when
the fan needs to be
tur
ned on. Place DIP Switch 5 to OFF and DIP Switch 1 to OFF to have the fan turn on immediately when there is a
call for
heat.
(Required with electric heat.) Place DIP Switch 5 to ON and DIP Switch 1 to OFF to
have the
plenum switch operate the
fan.
Place DIP Switch 5 to OFF and DIP Switch 1 to ON
for
normal heat pump operation. Place DIP Switch 5 to ON and DIP Switch 1 to ON for Add-On (Dual-Fuel)
Heat Pump
operation.
DIP Switch 6
: OFF
Keep OFF
DIP Switch 7 : Temporary Override Adjustment Range
Place DIP Switch 7 to OFF to limit
temporary adjustments to +/-3°F(1°C). Place DIP Switch 7 to ON limit
temporary adjustments
to
+/-5°F(2°C) .
DIP Switch 8 : Remote Sensor Operation
Place DIP Switch 8 to OFF to only use the r
emote indoor sensor
(10-528 or RS300-528) for temperature
contr
ol.
Place DIP Switch 8 to ON to average
the thermostat’
s inter
nal
sensor with the remote indoor sensor(s).
NOTE:
If no remote sensor is used, the thermostat will default to
the thermostat sensor regardless of the DIP Switch setting.
FEATURES AND SETTINGS
Random
Restart
After a power failure, the thermostat will delay the heating/ cooling equipment start-up by 8-40 seconds. When multiple Robertshaw® RS300N thermostats are used, this minimizes the ‘in rush’ current (electric power usage) as it reduces the number of HVAC units that will be turned on simultaneously.
Override Timer Configuration
The length of a temporary override can be adjusted from 0 minutes to 24 hours, in 10 minute increments. (0 minutes is a complete lockout). The default override time is 8 hours. To display/set the Override time, either use the integrated setup menu or press the MODE and DAY/NIGHT buttons simultaneously, then press the UP or DOWN button.
Recirculation Fan Configuration
Using the Setup Menu, Recirculation Fan can be set for up to 30 minutes of fan operation per hour. Default is 0min.
Fan Purge Configuration
Using the Setup Menu, Fan Purge time can be set for up to 60 seconds of fan run after a heating or cooling call in order to release remaining conditioned air into the space. Default is 0sec.
Temperature Calibration (De-calibration)
The thermostat is pre-calibrated at the factory, but in some installations, lack of airflow at the sensor or proximity to other warming or cooling source may cause the temperature to be off by a few degrees. To adjust the room temperature reading (with or without a remote indoor sensor connected), press and hold the Fan button for 12 seconds. The display will then show the room temp with 0.06F degree resolution. Press the UP or DOWN button to make the adjustment. Press the RESUME button to store the new value. To restore the thermostat to factory calibration, while in calibration mode, press the MODE button to reset and then the RESUME button to store.
FEATURES AND SETTINGS, continued
COVER LOCK
You also may lock the cover down to prevent unauthorized access to the thermostat by adding the clear plastic lock (included in the installation bag). To install, remove the thermostat from the backplate and place the clear plastic lock in the backplate as shown below. Replace the thermostat and close the cover. The cover now is locked. To open, simply use a screwdriver to carefully push the lock back, allowing the cover to open. To remove the lock, open the cover, remove the thermostat from the backplate, and then remove the lock.
REPLACING THE THERMOSTAT ON THE BACKPLATE
1. Position the thermostat on the hinged tabs located at the top of the backplate.
2. Gently swing the thermostat down and press on the bottom center edge until it snaps in place.
BUTTON PRESS COMBINATIONS
Single Press
MODE
Changes from COOL to HEAT to AUTO to OFF.
FAN
Sets the fan ON (continuous), or AUTO (operates with the equipment), or CIRC (recirculation). .
RESUME
When the keypad is locked, cancels temporary setpoint overrides and resumes previous operating mode.
DAY/NIGHT
Alternates between Day (Occupied) and Night (UnOccupied) setpoints.
UP
Increments the blinking numerical or icon segments of the display.
DOWN
Decrements the blinking numerical or icon segments of the display.
Multi-Press
UP & DOWN
Toggles between °F and °C.
FAN &
DAY/NIGHT
Changes backlight setting. On, dim or off. (After 15 seconds of inactivity)
MODE &
DAY/NIGHT
Changes the Override Timer. Press both, then press UP or DOWN to change the override time from 0 minutes to 24hrs in 10 minute increments
PRESS & HOLD (12 seconds unless stated otherwise)
UP & Down
MODE
(HOLD for 2 seconds) Enters the Setup Menu
Resets the thermostat to factory defaults. Press and hold the MODE button to show the number of resets. Press the MODE button a second time to reset the defaults.
FAN
Enters thermostat sensor de-calibration mode. Allows a temperature offset of up to +/-6°F. To remove the de­calibration, press and hold the MODE button.
MODE &
RESUME
Allows for adjustment of High and Low balance points when displaying outdoor temperature (hold for 5 seconds). NOTE: There must be an outdoor sensor attached for this feature to be available.
Loading...
+ 3 hidden pages