1
CONTROL TIPS
A ROBERTSHAW®INFORMATIONAL GUIDE
HOW HUMIDIFICATION/DEHUMIDIFICATION FEATURES OPERATE
THIS ISSUE
Congratulations, you are the proud owner of a Robertshaw®9801i, 9815i, 9820i, 9851i, 9865i, or 9870i
series thermostat. This Control Tips guide will provide you with the necessary information to set up
your thermostat for maximum humidity and dehumidification operation.
MODES
Manual with Heating
When the thermostat has a call for heat, the W terminal is energized (24VAC). If the relative humidity
(RH) drops 2% below RH setpoint, the H terminal is energized. When the temperature setpoint is
reached, both terminals are de-energized and the fan will shut off after the purge cycle or remain on
if the thermostat was set to Fan On.
Manual Independent
When the thermostat has a call (in heat mode) for humidity, and no call for heat, the H (24VAC) and G
terminals are energized.
When a call for heat is made, the H and G terminals will remain on while the W terminal is energized.
The fan remains on at the speed chosen for the furnace control for G only.
The second stage W2 energizes after a user-selected time (5 to 40 minutes) when the room
temperature is 0.5°F above the setpoint, or a 2°F differential has been met.
Auto with Heating or Auto Independent
These features can be selected from the Humidity Menu, but only when an outdoor sensor (9025i) is
connected. Humidity set point adjustment is an automatic adjustment made by the thermostat. The
indoor Relative Humidity (RH) is adjusted based on the outdoor temperature compared to the indoor
temperature. After the humidity set point has been automatically determined, there is a manual
adjustment that can be selected (±1% RH to ±15% RH) at 1% increments.
NOTE: When connecting the outdoor sensor, use a shielded, twisted pair of 18 guage 2-wire.
The wire length should not exceed 300 feet.