Robertshaw 9555 User Manual

Page 1
Application
The Robertshaw 9555 is a multi-stage auto changeover thermostat designed to control 24 VAC gas or electric two-stage heating and two­stage cooling systems. The 9555 requires the use of a common wire.
Features
• Multi-stage control
• Auto changeover [deadband adjustable from 2°F to 8°F (1.0°C - 4.5°C)]
• Adjustable 1STand 2NDstage temperature differential
• Compressor short cycle protection
• Adjustable fan delay on cooling
• LED indication of system status
• Zone system compatible as a master thermostat
• Battery-free EEPROM memory retention
• Optional temperature limiting settings
• Fahrenheit/Celsius display option
• Gas/electric operation
• Adjustable from 45°F to 90°F (7°C - 32°C)
• Quick wire terminal block
1
9555
ELECTRIC
E
GAS
G
®
NeW
2 Heat / 2 Cool with Auto Changeover
User's Manual
Quick Start Installation
W
A
R
R
A
N
T
Y
2
T
W
O
Y
E
A
R
DELUXE NON-PROGRAMMABLE THERMOSTAT
110-975D
110-975D En.qxd 5/13/03 2:43 PM Page 1 (Black plate)
Page 2
IMPORTANT SAFETY INFORMATION WARNING:
•Always turn off power at the main power source by unscrewing fuse or switching circuit breaker to the off position before installing, removing, cleaning, or servicing thermostat.
• Read all the information in this manual before installing or program­ming this thermostat.
• This is a 24 VAC low-voltage thermostat. Do not install on voltages higher than 30 VAC.
• All wiring must conform to local and national building and electrical codes and ordinances.
• Do not short (jumper) across terminals on the gas valve or at the system control to test installation. This will damage the thermostat and void the warranty.
Step 1: Replacing Existing Thermostat
1. Turn off power to heating and cooling system.
2. Remove cover from old thermostat to expose wires (Figure 1).
3. Disconnect wires one at a time from existing terminals. Use enclosed labels to mark existing wires. Refer to cross references in Table 1 if existing wiring does not directly match the labels.
Old Terminal New Label Description
C, X or B C 24 VAC, Transformer Common Side
R, V-VR or VR-R R 24 VAC, Return
W1 or W W1 1st Stage Heating Control
Y, Y1 or M Y1 1st Stage Cooling Control
O or R O Reversing Valve (Cooling Mode)
BBReversing Valve (Heating Mode)
F or G G Fan Control Relay
Y2 Y2 2nd Stage Cooling Control
W2 or W-U W2 2nd Stage Heating Control
NOTE: THIS THERMOSTAT REQUIRES A 24V COMMON WIRE FOR PROPER OPERATION.
2
Figure 1
Table 1
!
110-975D En.qxd 5/13/03 2:43 PM Page 2 (Black plate)
Page 3
• If you have any questions about cross referencing the old terminal to the new label, reference your equipment installation manual, a licensed contractor, or call Robertshaw Technical Support at (800) 445-8299.
4. Remove existing thermostat base from wall.
Recycling Thermostat
If this thermostat is replacing a thermostat that contains mercury in a sealed tube, do not place your old thermostat in the garbage. Contact your local waste management authority for instructions regarding proper disposal of the thermostat. If you have any ques­tions, call Robertshaw technical support at 1-800-445-8299.
Step 2: Installing Model 9555 Thermostat
NOTE: FOR NEW INSTALLATIONS, MOUNT THERMOSTAT ON
INSIDE WALL, FIVE FEET ABOVE THE FLOOR. DO NOT INSTALL BEHIND A DOOR, IN A CORNER, NEAR AIR VENTS, IN DIRECT SUNLIGHT, OR NEAR ANY HEAT OR STEAM GENERATING FIXTURES. INSTALLATION AT THESE LOCATIONS WILL AFFECT THERMOSTAT OPERATION.
1. Turn power off to the heating and cooling systems.
2. Place AUTO-HEAT-OFF-COOL in OFF position (Figure 2).
3. Place -ON-AUTO switch into AUTO position (Figure 2).
3
Figure 2
SETTING OR CHANGING THE SETPOINT TEMPERATURE:
1.Press or button. Display will show SET and the current temperature setpoint.
2. Press or button to adjust temperature setpoint.
3. After completing the change, the display will return to the curr
ent
room temperature after a few seconds.
CHANGING THE TEMPERATURE DIFFERENTIAL, DEAD BAND, AND RESIDUAL COOL:
The temperature differentials are factory set at 1˚F and 2˚F for 1STand 2NDstages respectively. The dead band for Auto­changeover is set at 3˚F. To change settings:
1.Press the and buttons at the same time and hold for 1 second. Display will indicate: DIFFERENTIAL 1ST.
2. Press either the or button to adjust the 1st stage differ- ential between 0.5˚F – 3˚F (0.5˚C - 1.5˚C).
3. Either wait five seconds or press the button. The display
will indicate: DIFFERENTIAL 2ND.
4.Press either the or button to adjust 2nd stage differen- tial between 1˚F – 6˚F (1˚C - 3˚C).
5. Either wait five seconds or press the button. The display
will indicate: DEADBAND.
6.Press either the or button to adjust the dead band between 3˚F – 6˚F (1.5˚C - 3˚C).
7.Either wait five seconds or press the button.The fan icon and ON will be displayed.
8. Press either the or button to adjust the Residual Cool fan delay between 0, 30, 60, or 90 seconds.
9.The display will return to the current room temperature after a few seconds.
Item
9555
120-1523
Maple Chase Company www.maplechase.com Tech Service: 1-800-445-8299 M-F 7:30 a.m. - 5:30 p.m. CST
MADEINMEXICO
110-975D En.qxd 5/13/03 2:43 PM Page 3 (Black plate)
TM
Page 4
4. Remove the cover using a coin or screwdriver (Figure 3). Set aside.
5. Place thermostat against the wall at desired location. Make sure wires will feed through opening (Figure 4) on base of thermostat.
6. Mark placement of mounting holes (Figure 4). Set base aside.
7. If mounting on drywall, tap plastic anchors into wall.
NOTE: ENCLOSED PLASTIC ANCHORS DO NOT REQUIRE A
DRILLED HOLE FOR DRYWALL.
8. Drill the marked holes using a 3/16" drill bit if mounting on a sur­face other than drywall.
9. Align base with plastic anchors and feed wires through opening.
10. Secure base to wall with supplied screws.
NOTE: THE THERMOSTAT WILL MOUNT HORIZONTALLY
ON A SINGLE GANG JUNCTION BOX.
11. Strip end of wires 5/16” if needed.
4
Figure 3
WIRING OPENING
W1 Y1 B O G W2 Y2
NON HP
Figure 4
110-975D En.qxd 5/13/03 2:43 PM Page 4 (Black plate)
Mounting Holes
Page 5
12. Terminal screws are already loose and ready for wire insertion. Insert wires into terminal strip (Figure 5) matching the label to the corresponding terminal (see Wiring Diagrams below). Tighten screws.
13. Make sure wire connections are secure.
14. Push access wire back through opening.
5
O
Y1
W1
B
G W2
Y2
W1
Wiring Diagrams for 9555
Typical 1 heat / 1 cool system
Typical 1 stage heat / 2 stage cool system
Typical 2 stage heat / 1 stage cool system
Typical 2 stage heat / 2 stage cool system
9555 WIRING SAMPLE #1
9555 WIRING SAMPLE #2
9555 WIRING SAMPLE #3
9555 WIRING SAMPLE #4
B O W2 Y2C R W1 Y1 G
B O W2 Y2C R W1 Y1 G
B O W2 Y2C R W1 Y1 G
B O W2 Y2C R W1 Y1 G
Figure 5
110-975D En.qxd 5/13/03 2:43 PM Page 5 (Black plate)
Page 6
15. Set the GAS/ELEC switch to either GAS for a gas/oil heating sys-
tem or ELEC for an electric heating system.
16. A temperature limiting jumper has been included in this thermo-
stat. Cutting this jumper (J3) limits the heating setpoint to no
greater than 72°F and the cooling setpoint to no lower than 78°F
(Figure 7).
6
W1 Y1 B O G W2 Y2
NON HP
Figure 6
TERMINAL LEGEND - 9555
TERM EQUIPMENT TO CONNECT REQ? TERMINAL FUNCTION
C 24VAC common connection Yes For input of 24VAC common
side of transformer
R 24VAC hot connection Yes For input of 24VAC hot side
of transformer
Y2 Second stage cooling connection No Energizes on a call for
second stage cooling (aux.)
Y1 First stage compressor connection Yes* Energizes on a call for first
stage of cooling
W1 First stage heat connection Yes* Energizes on a call for first
stage of heating
W2 Second stage heat connection No Energizes on a call for
second stage heating (aux.)
G Indoor fan connection Yes Energizes with W1, W2, Y1
and Y2 terminals or with FAN option switched to the ON position
O Accessory** No Energizes when in the in
COOL mode
B Accessory** No Energizes when in the
HEAT or EM modes
* This thermostat can be used as a heat only or cool only thermostat therefore it is not always
necessary to use both W1 and Y1.
** The O and B terminals are accessory terminals that typically are used for zoning applications.
110-975D En.qxd 5/13/03 2:43 PM Page 6 (Black plate)
GAS/ELECTRIC
Switch
Page 7
7
17. Replace thermostat cover by snapping into place.
18. Turn on power to system. Test thermostat as described in the fol-
lowing section.
Step 3: Testing the Thermostat
WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS
OF GAS VALVE OR SYSTEM CONTROL TO TEST OPERATION. THIS WILL DAMAGE THE THERMO­STAT AND VOID YOUR WARRANTY.
CAUTION: DO NOT SWITCH SYSTEM TO COOL IF THE TEMPERATURE IS
BELOW 50°F (10°C). THIS CAN DAMAGE THE AIR CONDITION­ING SYSTEM AND CAUSE PERSONAL INJURY.
1. Place the AUTO-HEAT-OFF-COOL switch into
the COOL position.
2. Press the button until the temperature setting
is at least 3 degrees below the room temperature.
The air conditioning system should turn on within
a few seconds.
NOTE: ONCE THE THERMOSTAT TURNS OFF WHEN IN THE COOL MODE, A
BUILT IN 5-MINUTE DELAY PREVENTS THE SYSTEM FROM TURN­ING ON AGAIN. THIS PROTECTS THE COMPRESSOR. NO ADDI­TIONAL TIME DELAY RELAY IS REQUIRED. TO OVERRIDE THE 5­MINUTE DELAY FOR INSTALLATION, PRESS THE RESET BUTTON.
Cut the J3 jumper to enable temperature limiting
W1 Y1 B O G W2 Y2
Figure 7
!
110-975D En.qxd 5/13/03 2:43 PM Page 7 (Black plate)
Page 8
3. Put the AUTO-HEAT-OFF-COOL switch into
the OFF position. The air conditioning system
should turn off.
4. Put the AUTO-HEAT-OFF-COOL switch into
the HEAT position.
5. Press the button until the temperature
setting is at least 3 degrees above room
temperature. The heating system should
turn on. The fan may not turn on immediately,
depending on the fan delay built into the furnace.
6. Put the AUTO-HEAT-OFF-COOL switch into
the OFF position. The heating system should
turn off. The fan may continue to run for a
short period of time.
7. Put the -ON-AUTO switch into the ON
position. The blower fan should turn on.
8. Put the -ON-AUTO switch into the AUTO
position. The blower fan should turn off.
8
110-975D En.qxd 5/13/03 2:43 PM Page 8 (Black plate)
Page 9
9
Step 4: Customizing the Thermostat
Settings
System
Cool: The thermostat controls the cooling. Off: The heating and cooling systems are off. Heat: The thermostat controls the heat. AUTO: The thermostat automatically selects heat or cool depending
on the temperature.
Fan
Auto: Equipment controls the fan. On: The fan operates continuously.
Temperature
The default setpoint temperature for heating is 70°F (21°C), for cooling is 78°F (25°C) and for auto is 72°F (22°C). After putting the system switch in heat, cool, or auto, press either the or
button to adjust the temperature setting up or down.
The display will return to the current room temperature five seconds after the last input and the new setpoint will be saved.
Temperature Differential and Deadband
The temperature differential is factory set at 1°F (0.5°C) for the 1STstage differential and 2°F (1.0°C) for the 2NDstage. This means that whenever the room temperature changes by one degree Fahrenheit from the temperature setting, the system will turn on. If the system turns on too often, increase the temperature differential.
The 2NDstage will turn on when the room temperature changes from the desired temperature by the sum of the 1STand 2NDstage differential set­tings. The 2NDstage will also turn on if the temperature has not increased (or decreased in the event of cooling) for a period of twenty minutes.
Although programmed at the same time as the temperature differentials, the deadband is used only during the AUTO mode. In the AUTO mode, the thermostat will automatically cycle either the heating or cooling system to maintain optimal comfort. The deadband is the minimum allowable tem­perature which must occur to switch to the opposite mode. For example, if the deadband is set at 3°F and the setpoint is set at 70°F, the thermostat will switch to cooling mode when the temperature reaches 73°F.
NOTE: IF THE TEMPERATURE LIMITING JUMPER J3 IS CUT
(FIGURE 7), THE DEADBAND IS NOT ADJUSTABLE AND IS AUTOMATICALLY SET TO 6°F (3°C).
Figure 8
110-975D En.qxd 5/13/03 2:43 PM Page 9 (Black plate)
Page 10
10
Changing Fahrenheit (F) to Celsius (C),
Temperature Differential, Deadband, and Residual Cool
The temperature differential is factory set at 1°F (0.5°C) for the 1STstage differential and 2°F (1.0°C) for the 2NDstage. The deadband for auto changeover is set at 3°F (1.5°C). To change settings:
1. The thermostat is preset to display the temperature in degrees Fahrenheit (U.S. models) or degrees Celsius (Canadian models). The temperature display can be changed. Press and hold both the
and
buttons for three seconds. The display will read F or C. Release the
buttons. Press either the or button to change the display.
2. After three seconds, the display will switch to the differential settings. The display will read DIFFERENTIAL 1
ST
.
3. The temperature differential is factory set at 1°F (0.5°C) for the first stage. Press either the or button to adjust the 1STstage differential between 0.5°F - 3°F.
4. Either wait three seconds or press the button. The display will indicate: DIFFERENTIAL 2ND.
5. The 2nd stage differential is factory set at 2°F (1.5°C). Press either the or button to adjust the 2nd stage temperature differential between 1°F - 6°F (1°C - 3°C).
6. Press the or button to adjust the 2nd stage timed differential between 5 to 40 minutes. Either wait 5 seconds or press the button.
7. Either wait three seconds or press the button. The display will indicate: AUTOCHANGE DEADBAND.
8. Press either the or button to adjust the deadband between 2°F - 8°F (1.0°C - 4.5°C).
9. Either wait three seconds or press the button. The fan icon and ON will be displayed.
10. Press either the or button to adjust the residual cool fan delay
between 0, 30, 60, or 90 seconds.
11. The display will return to the original room temperature display after a few seconds.
LED Indicators
The Robertshaw 9555 uses three LED indicators (in addition to icons on the LCD display) to indicate functionality of the thermostat. When illumi­nated, the right orange LED indicates that the thermostat is calling for heat. The left green LED indicates a call for cool. When the middle amber LED is illuminated, the thermostat is calling for second stage heating or cooling. If this LED is illuminated too frequently during periods of moderate temperature, check the differential settings (see Temperature Differential and Deadband section).
110-975D En.qxd 5/13/03 2:43 PM Page 10 (Black plate)
Page 11
Backlit Display
This thermostat is equipped with a backlight to make nighttime tempera­ture adjustments quick and easy. Press the button to activate the backlight. The backlight will turn off after about 15 seconds of inactivity.
Reset
To reset the thermostat to factory preprogrammed conditions, press the RESET button located beneath the lower left corner of the display.
Step 5: Troubleshooting
Symptom Remedy
11
If problems with thermostat cannot be resolved, call:
Technical Support: (800) 445-8299
Monday-Friday 7:30 AM - 5:30 PM CST
RESET Switch
W1Y1 B O G W2 Y2
NON HP
Thermostat does not turn on system.
Check wiring (see Installation section).
Increase temperature differential (see Changing the Temperature Differential section).
Thermostat turns system on and off too frequently.
System fan does not operate properly.
Move fan option switch to either gas or electric, to match system (see Installation section).
Check F/C (Fahrenheit/Celsius) setting. See Changing Fahrenheit (F) to Celsius (C).
Thermostat does not display proper room temperature.
Call technical support.
Er on display
110-975D En.qxd 5/13/03 2:43 PM Page 11 (Black plate)
Page 12
Two Year Limited Warranty
Climate Controls Americas warrants to the original contractor
installer, or to the original consumer user, each new Robertshaw thermo­stat to be free from defects in materials and workmanship under normal use and service for a period of two (2) years from date of purchase. This warranty and our liability does not apply to batteries or merchandise that has been damaged by misuse, neglect, mishandling, alterations, improper installation, or use in a way other than in accordance with Climate
Controls Americas recommendations and instructions.
Climate Controls Americas agrees to repair or replace at its option
any thermostat under warranty provided it is returned within the warranty period, postage prepaid, with proof of the date of purchase. Cost of thermostat removal or reinstallation is not the responsibility of Climate
Controls Americas.
Repair or replacement as provided under this warranty is the exclusive remedy of the consumer. Climate Controls Americas shall not be liable for any incidental or consequential damages for breach of any express or implied warranty on this product, or under any other theory of liability. Except to the extent prohibited by applicable law, any implied warranty of merchantability or fitness for a particular purpose on this product is limited to the duration of this warranty.
Some states do not allow the exclusion or limitation of incidental or consequential damages, or allow limitations on how long an implied warranty lasts, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
For warranty returns, send thermostat, shipping prepaid to: