Robertshaw 300-229 User Manual

Features and Benefits
Contemporary Design
Compliments any décor.
Large Digital Display
Makes viewing and setting the temperature easy and accurate.
Auto Changeover
Automatically switches into heat or cool mode. Prevents having to manually change system from heat to cool.
3-Hour Temporary Program Override
Allows for manual temperature adjustment.
2 or 4 Events Per Day
Customizable for any environment.
Occupancy Terminal
A set of dry contacts allows control of fresh air dampers, security lighting, etc., for occupied and unoccupied periods.
LED Indicators
Two customizable LEDs for selectable fault indicators.
EEPROM Memory
Electronic memory storage with no batteries to replace.
Automatic Compressor Short Cycle Protection
A system safeguard. Reduces wear and tear of HVAC equipment.
Progressive Recovery
Allows gradual recovery from setback periods for increased energy savings.
Lockable Keypad and Front Cover
Two levels of security against unwanted tampering.
Remote Sensor Capable
Connects to optional remote indoor or outdoor sensors for optimal comfort.
7 Day Programmable 2 Heat / 2 Cool
Elegantly Sophisticated
The Robertshaw 300-229 takes comfort to the next level with state-of-the-art control for commercial applications.
Controlling your indoor environment is easy with standard features such as Auto Changeover, independent switching circuitry, Programmable Fan and selectable 2 or 4 events per day. Coupled to EEPROM permanent memory storage and a tamper-free control setting, this model provides worry-free operation.
Conventional control in an unconventional package. When you select a Robertshaw thermostat, you’ve made the choice of an industry partner that’s been making quality products for over 100 years.
Technical service available: 1-800-445-8299 M-F 7:30 a.m. - 5:30 p.m. CST
300-229
DELUXE PROGRAMMABLE THERMOSTAT
W
A
R
R
A
N
T
Y
T
W
O
Y
E
A
R
2
G
GAS
E
ELECTRIC
®
Terminal Designations
Specifications
Electrical rating: 24 Volt AC (20-30 VAC)
0.05 amp - 0.75 amp per output 3 Amp total maximum load (all terminals combined)
Temperature control range: Heating: 40° - 88°F (6° - 30°C) Cooling: 60° - 108°F (16° - 40°C) Accuracy: +/-1°F at 68°F (0.5°C at 20°C) Auto Changeover deadband: 2°F (1°C) Temporary temperature override: 3 hours maximum Remote sensor capable: Up to 6 remote sensors System configuration: Multi-stage gas, oil or electric heating/cooling
systems (up to 2 stages of heat, 2 stages of cool).
Other Multi Stage Gas / Electric Heat / Cool Thermostats
9515: Digital, Non-Programmable 9615: Programmable, 7 Day 9710: Deluxe Programmable, 7 Day 300-203: Digital, Non-Programmable
Architectural / Engineering Specification
The thermostat shall be a Robertshaw Model 300-229 or equivalent. The thermostat shall have seven-day programmability with up to 4 time/temperature changes per day. The thermostat will allow temporary temperature override for a maximum of 3 hours or the next setpoint time, whichever occurs first. The thermostat shall allow the user to program the system fan separately for continuous or automatic operation for each of the 4 time setpoints per day to meet local application and code requirements.
It shall be capable of operating with standard 24 VAC 2 stages of heat and 2 stages of cooling for gas, oil or electric heating and/or electric heating /cooling systems. The thermostat shall have an electrical rating of 0.75 amp maximum load per terminal, 3 amp total maximum load for all terminals combined. The thermostat shall have relay outputs with standard 24 VAC control circuits and be equipped with back-up circuitry to prevent loss of programming in memory during power outages.
The thermostat shall have automatic changeover capability to allow the thermostat to determine whether the heating or cooling program should be used to control room temperature.
The thermostat shall be equipped with trouble LED’s for selectable programmed operation. The thermostat will have an auxiliary relay coil which energizes during the occupied periods and de-energizes during unoccupied periods.
The keypad and case shall have an integral lock to prevent tampering and/or the altering of the program. The switching voltage shall be independent of the heating and cooling system transformer. The thermostat will provide remote sensor capability for up to six temperature sensors (including main thermostat sensor). The thermostat shall be equipped with a 5-minute delay on break for compressor short cycle protection during cooling operation to prevent compressor damage.
300-229
Shipping Information
Indiv. Ctn. Dim.: 4.75” x 6” x 1.75” Master Ctn. Qty.: 20 Master Ctn. Dim.: 10" x 6.25” x 17.5" Master Ctn. Cu. Ft.: .64 Master Ctn. Wt.: 15 lbs. Max. Pallet Qty.: 1120 Max. Pallet Wt.: 860 lbs.
Item 10-528 & 10-529 Remote Sensor
Indiv. Ctn. Dim.: 4.75” x 6” x 1.75” Master Ctn. Qty.: 40 Master Ctn. Dim.: 10" x 12.5” x 17.5" Master Ctn. Cu. Ft.: 1.28 Master Ctn. Wt.: 14 lbs.
W2
Heating
Relay
(2nd Stage)
W1
Heating
Relay
Y2
Cooling
Relay
(2nd Stage)
Y1 G
Fan
Relay
Cooling
Relay
R 24V
24V(C)
OB
24 VAC
Equipment
Transformer
Independent
Switching
Voltage
Cool Active
Reversing
Valve
24 VAC
Equipment
Common
Heat Active
Reversing
Valve
Distributed by:
DELUXE PROGRAMMABLE THERMOSTAT
LED1
Selectable
Function
Indication
RS2
LED2
RS1
RS+V
Outdoor/Indoor
Sensor
NO COM NC
Occupancy Relay Coil, De-energize during night event
Optional Remote Sensors:
INDOOR OUTDOOR 10-528 10-529
White-Rodgers Company* 1F97 Honeywell, Inc.* T7300D2007
* Verify specific application requirements before substitution.
THE ROBERTSHAW 300-229 REPLACES:
Climate Controls Americas
515 South Promenade Avenue Corona California 92879-1736 USA Telephone +1 800 304 6563 Facsimile +1 800 426 0804 Outside the USA +1 909 734 2600
www.icca.invensys.com ©2003 Climate Controls Americas 6/03 - #150-1556B
®
Loading...