Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or property
damage. Read the Installation, Operation and Service
Manual thoroughly before installing or servicing
this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
All rights reserved. No part of this work covered by the copyrights herein may be reproduced
or copied in any form or by any means - graphic, electronic, or mechanical, including
photocopying, recording, taping or information storage and retrieval systems - without the
written permission of Roberts-Gordon LLC.
Figure 20: LED Diagnostic Codes........................................... 34
Page 6
Page 7
SECTION 1: HEATER SAFETY
Your Safety is Important to Us!
This symbol is used throughout
the manual to notify you of
possible fire, electrical or burn
hazards. Please pay special
attention when reading and
following the warnings in these
sections.
Installation, service and annual
inspection of heater must be done by a contractor
qualified in the installation and service of gas-fired
heating equipment.
Read this manual carefully before installation,
operation or service of this equipment.
Not all heaters are approved for residential
installation. Check the heater’s silver rating plate for
residential approval status. Heaters that do not have
residential approval must not be installed in
residential spaces. These instructions, the layout
drawing, local codes and ordinances and applicable
standards that apply to gas piping, electrical wiring,
venting, etc. must be thoroughly understood before
proceeding with the installation.
Protective gear is to be worn during installation,
operation and service. Thin sheet metal parts,
including the various venting components, have
sharp edges. To prevent injury, the use of work
gloves is recommended.
Before installation, check that the local distribution
conditions, nature of gas and pressure and
adjustment of the appliance are compatible.
SECTION 1: HEATER SAFETY
1.1 Manpower Requirements
To prevent personal injury and damage to the
heater, two persons will be required for installation.
1.2 Safety Labels and Their Placement
Product safety signs or labels should be replaced by
product user when they are no longer legible.
Please contact Roberts Gordon LLC or your
ROBERTS GORDON
obtain replacement signs or labels.
®
independent distributor to
See Page 2,
Figure 1 through Page 4, Figure 3.
1
Page 8
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
• To install the heater, as well as the gas and
electrical supplies, in accordance with applicable
specifications and codes. Roberts-Gordon
recommends the installer contact a Local
Building Inspector or Fire Marshal for guidance.
• To use the information given in a layout drawing
and in the manual together with the cited codes
and regulations to perform the installation.
• To install the heater in accordance with the
clearances to combustibles.
• To furnish all needed materials not furnished as
standard equipment.
• To plan location of supports, vents and air
intakes.
• To provide access for servicing.
• To provide the owner with a copy of this
Installation, Operation and Service Manual.
• To never use heater as support for a ladder or
other access equipment and never hang or
suspend anything from heater.
• To ensure there is adequate air circulation
around the heater and to supply air for
combustion, ventilation and distribution in
accordance with local codes.
SECTION 1: HEATER SAFETY
of combustible materials, corrosive chemicals or
halogenated hydrocarbons* anywhere in the
premises.
* Halogenated Hydrocarbons are a family of chemical
compounds characterized by the presence of halogen elements (fluorine, chlorine, bromine, etc.). These compounds are
frequently used in refrigerants, cleaning agents, solvents, etc. If
these compounds enter the air supply of the burner, the life
span of the heater components will be greatly reduced. An outside air supply must be provided to the burners whenever the
presence of these compounds is suspected. Warranty will be
invalid if the heater is exposed to halogenated hydrocarbons.
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with
the latest revision of the applicable standards and
national codes. This refers also to the electric, gas
and venting installation. Note: Additional standards
for installations in public garages, aircraft hangars,
etc. may be applicable.
2.1 Wall Tag
A laminated wall tag is included with the heater as a
permanent reminder of the safety instructions and
the importance of the required clearances to
combustibles. Affix the tag by peeling off the backing
of the adhesive strips on the rear surface and
position the tag on a wall near the heater.
A copy of the wall tag (P/N 91040031) is illustrated
on the back cover.
Know your model number. Model number is found
on the heater and throughout the Installation,
Operation and Service Manual.
2.2 Corrosive Chemicals
Caution: Do not use heater in an area containing
corrosive chemicals. Avoid the use of corrosive
chemicals to ensure a longer life of the burner, heat
exchanger and other parts.
Roberts-Gordon cannot be responsible for ensuring
that all appropriate safety measures are undertaken
prior to installation; this is entirely the responsibility
of the installer. It is essential that the contractor, the
sub-contractor, or the owner identifies the presence
5
Page 12
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
WARNING
Fire Hazard
Some objects can catch fire or explode
when placed close to heater.
Keep all flammable objects, liquids and
vapors the required clearances to
combustibles away from heater.
Failure to follow these instructions can
result in death, injury or property damage.
WARNING
Carbon Monoxide Hazard
Heaters may be installed
vented or unvented.
Vented heaters must be
vented outdoors.
Unvented heaters must be
installed in buildings with
ventilation rates as per
section 6.4.
Failure to follow these
instructions can result in
death or injury.
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Basic Information
UHA[X][S] heaters have automatic ignition burners
for ON/OFF operation only.
3.2 Manufactured Units
Gas-fired, power-vented unit heater with tubular heat
exchanger. Units shall have a minimum of 82%
thermal efficiency. The standard unit shall consist of
a non-separated combustion design with an
aluminized heat exchanger. Design and heat
exchanger alternatives shall be offered as follows:
• Separated Combustion: A separated combustion
unit shall consist of an enclosed sealed burner
box to which combustion air is vented through a
piece of internal flexible air duct. This duct
terminates at an exterior cabinet flange to which
a vent ran to the outside of the heated space
should be attached.
• Stainless Steel Heat Exchanger: A stainless
steel heat exchanger unit shall consist of heat
exchanger tubes, heat exchanger tube supports,
heat exchanger tube plates and a vent box
produced of 409 stainless steel.
3.5 Clearances to Combustibles
Clearances must be as indicated on Page 7, Figure
4. If clearances to combustibles are not indicated,
then installation clearances apply.
3.6 Ventilation
3.3 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed in a level position with
horizontal discharge.
• May be mounted on a shelf of non-combustible
material using shelf mounting brackets.(
Page 11, Figure 6and Page 12, Figure 7 for
details.)
• May be suspended from above (See Page 11, Figure 5) or from wall brackets of sufficient
strength to support the heater as listed in the
Dimension Data Table
Drop rods must be a minimum of 3/8" diameter
mild steel. Four suspension points (3/8" nuts)
are located on top of the heater.
• Must be installed in a manner which allows
access to all serviceable components.
See Page 7, Figure 4 for details.
3.4 Minimum Required Installation Clearances
Clearances around the heater and vent must be as
indicated
through Page 20, Figure 14 to ensure access for
servicing, and correct operation.
6
on Page 7, Figure 4; Page 17, Figure 9
on Page 49, Section 15.1.
See
It is important to ensure that there is adequate air
space around the heater to supply air for
combustion, ventilation and distribution in
accordance with local and national code
14, Section 6.
on Page
Page 13
SECTION 3: CRITICAL CONSIDERATIONS
WARNING
Electrical Shock Hazard
Disconnect electrical and gas supply before
servicing.
This appliance must be connected to a
properly grounded electrical source.
Failure to follow these instructions can
result in death or electrical shock.
* Recommended mounting height varies with heater input.
Heaters may be mounted at a higher level if destratification
fans are installed.
Clearance to Vent: 2" (5 cm)
**18" (45.7 cm) minimum is
necessary for servicing.
The heater must always be installed at least 6' (2 m) above the floor.
The vent pipe must have clearance from combustibles by 2" (5 cm).
If installed at low levels where individuals can come in contact with hot heat exchanger components,
adequate guarding must be provided.
3.7 Gas Supply
3.8 Electrical Supply
WARNING
Fire Hazard
Connect gas supply according to Figure 15.
Do not use gas supply pipe and electrical
connections to support heater’s weight.
Gas can leak if not installed properly.
Failure to follow these instructions can
result in death, injury or property damage.
It is important that the gas supply pipe is sized
correctly to provide the inlet pressure as stated on
the heater data plate. The gas supply pipe and
electrical connections must not support any of the
heater's weight.
Figure 4: Installation Clearances and Clearances to Combustibles
See Page 22, Section 8
A permanent 120 V / 1 Ø / 60 Hz electrical supply is
required for the main electrical power. The heater
also requires suitable controls in accordance with
See Page 23, Section 9.
3.9 Vent
Choose heater orientation to allow for the proper
location of the vent. Each heater must be fitted with
a correctly sized sealed vent system.
If vented horizontally, no other appliance may be
connected to the vent.
See Page 14, Section 6.
7
Page 14
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES
4.1 Gas Codes
The type of gas appearing on the name plate
must be the type of gas used. Installation must
comply with national and local codes and
requirements of the local gas company.
United States: Refer to NFPA 54/ ANSI Z223.1
- latest revision, National Fuel Gas Code.
Canada: Refer to CSA B149.1 Natual Gas and
Propane Installation Code.
4.2 Aircraft Hangars
Installation in aircraft hangars must be in
accordance with the following codes:
United States: Refer to Standard for Aircraft
Hangars, NFPA 409 - latest revision.
Canada: Refer to Standard CSA B149.1 Natural
Gas and Propane Installation Code.
• In aircraft storage and servicing areas,
heaters shall be installed at least 10' (3 m)
above the upper surface of wings or of engine
enclosures of the highest aircraft which may be
housed in the hangar. The measurement shall
be made from the wing or engine enclosure
(whichever is higher from the floor) to the
bottom of the heater.
• In shops, offices and other sections of aircraft
hangars communicating with aircraft storage or
servicing areas, heaters shall be installed not
less than 8' (2.4 m) above the floor.
• Suspended or elevated heaters shall be so
located in all spaces of aircraft hangars that
they shall not be subject to injury by aircraft,
cranes, movable scaffolding or other objects.
Provisions shall be made to assure accessibility
to suspended heaters for recurrent
maintenance purposes.
4.3 Parking Structures and Repair Garages
Installation in garages must be in accordance
with the following codes:
United States: Standard for Parking Structures
NFPA 88A - latest revision or the Code for
Motor Fuel Dispensing Facilities and Repair
Garages, NFPA 30A - latest revision. Canada:
Refer to CSA B149.1 Natural Gas and Propane
Installation Code.
• In accordance with the Standard for Parking
Structures NFPA 88A, heaters must be located
a minimum of 18" (50 cm) below the floorceiling assembly or 18" (50 cm) above the
floor.
• In accordance with the Code for Motor Fuel
Dispensing Facilities and Repair Garages,
NFPA 30A - latest revision, heaters must not be
installed less than 8' (2.4 m) above the floor.
4.4 Electrical
The heater must be electrically grounded in
accordance with the following codes:
United States: Refer to National Electrical
®
Code
, NFPA 70 - latest revision. Wiring must
conform to the most current National Electrical
®
Code
, local ordinances and any special
diagrams furnished.
Canada: Refer to Canadian Electrical Code,
CSA C22.1 Part 1 - latest revision.
4.5 Venting
The venting must be installed in accordance
with the requirements within this manual and
the following codes:
United States: Refer to NFPA 54/ANSI Z223.1 latest revision, National Fuel Gas Code.
8
Canada: Refer to CSA B149.1 Natural Gas and
Propane Installation Code.
Page 15
4.6 High Altitude
These heaters are CSA-approved (without
modifications) for installations up to 2000' (610
m) in US and Canada. CSA approved heaters
installed above 2000' (610 m) must be derated. For installations above 2000' (610 m) in
US, consult factory for information on burner
de-rating. For installations from 2000' (610 m)
to 4500' (1370m) in Canada, high altitude
conversion kits are available. Heaters installed
over 4500' (1370 m) in Canada are not CSAapproved and must be approved by the local or
provincial authority.
SECTION 4: NATIONAL STANDARDSAND APPLICABLE CODES
9
Page 16
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
WARNING
Crush Hazard
Use 3/8" threaded rod
minimum.
Failure to follow these
instructions can result in
death, injury or property
damage.
SECTION 5: MAJOR COMPONENTS
5.1 General
Heaters are designed for installation above 6'
(1.8 m). These heaters must be installed within the
heated space. Duct delivery systems are not
permitted with axial fan units. When handling or
supporting the heater from below, ensure that the
weight is taken at the support points.
The gas or electrical supply lines must not be used
to support the heater.
Do not locate the gas or electrical supply lines
directly over the path of the flue products from the
heater.
The heater must be installed in accordance with
clearances to combustibles as indicated on the wall
tag and this manual.
5.2 Shelf Mounting and Suspension
Four suspension points (3/8" nuts) are located on
the top of the heater. Drop rods must be 3/8"
diameter mild steel.
When handling or supporting the heater from below,
ensure that the weight is taken at the support points.
For typical suspension, See Page 11, Figure 5.
For typical shelf mounting on existing shelf, See
Page 11, Figure 6
5.3 Wall Mounting
For typical suspension, See Page 12, Figure 7. Wall
mounted heaters blowing parallel to the wall can
only be installed with the service door away from the
wall.
The wall mounting brackets must be attached to a
suitable wall using all mounting holes. Screw sizes
less than 3/8" may not be used. In order for the wall
mounting brackets to adequately carry the weight of
the heater, it must be installed according to best
building practices.
10
Page 17
Figure 5: Suspension Methods
Cone Point
Set Pin
Window
Clamp
Unistrut
3/8"
Threaded
Rod
Nut
Washer
Riv
Nut
Support Points
Ensure all suspension
hardware is torqued to
a minimum of 20 ft lbs.
For models UHA[X][S] 60 and UHA[X][S] 75, horizontal louvers are re-used.
Remove horizontal
louvers.
SECTION 5: MAJOR COMPONENTS
Install vertical
louvers brackets
(top and bottom)
with supplied
screws.
Push in
louver and compress
spring to remove
(opposite end first)
Install vertical
louvers and springs
into brackets
with springs at top.
13
Page 20
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
SECTION 6: VENTING
WARNING
Carbon Monoxide Hazard
Heaters may be installed
vented or unvented.
Vented heaters must be
vented outdoors.
Unvented heaters must be
installed in buildings with
ventilation rates as per
section 6.4.
Failure to follow these
instructions can result in
death or injury.
6.1 Changing Vent and Air Intake Orientation
The heater is sold with rear horizontal vent and air
intake connections as standard (only separated
combustion models have air intake connection). If
vertical vent and air intake connections are required,
follow the instructions on Page 46, Section 14.6.
sheet metal screws.
For single wall venting, pressure sensitive aluminum
tape or silicone sealant must be used to seal all
joints.
Aluminum tape shall have a minimum temperature
rating of 400° F (204° C) and meet SMACNA AFTS100-73 standards. High temperature silicone
sealant must have a minimum temperature rating of
480° F (250° C).
6.2.1 United States Requirements
Vent must terminate at least 3' (.9 m) above any
forced air inlet located within 10' (3.1 m).
Vent must terminate at least 4' (1.2 m) below,
4' (1.2 m) horizontally from, or 1' (.3 m) above any
door, operable window, or gravity air inlet into any
building.
NFPA 54/ANSI Z223.1 - latest revision, National
Fuel Gas Code specifies a 4' (1.2 m) horizontal vent
terminal clearance from gas and electric meters,
regulators and relief equipment.
6.2 Venting
This heater must be vented in accordance with the
rules contained in this manual and with the following
national codes and any state, provincial or local
codes which may apply: United States: Refer to
NFPA54/ANSI Z223.1 - latest revision, National Fuel
Gas Code; Canada: Refer to CSA B149.1 Natural
Gas and Propane Installation Code.
Any portion of vent pipe passing through a
combustible wall must have a listed thimble to
conform with the above codes.
The heater may be installed unvented in
certain circumstances according to building
ventilation codes. Refer to the above codes
Page 15, Section 6.4 for further information.
Unvented operation also requires compliance with
the clearances to combustibles given
Figure 4.
The bottom of the vent or air intake terminal shall not
be located less than 1' (.3 m) above grade level.
The vent shall not terminate less than 7' (2.1 m)
above grade where located adjacent to public
walkways.
Vent terminal must be installed at a height sufficient
to prevent blockage by snow and building materials
protected from degradation by flue gasses.
Vent terminal must be beyond any combustible
overhang.
Secure all joints with corrosion resistant #8 x 3/8"
on Page 7,
and
6.2.2 Canadian Requirements
The vent shall not terminate within 6' (1.8 m) of a
mechanical air supply inlet to any building.
The vent shall not terminate within 3' (.9 m) of a
window or door that can be opened in any building,
any non-mechanical air supply inlet to any building,
or of the combustion air inlet of any other appliance.
6.3 Vent Installation
Maintain clearences to combustibles at all times
for safety. Clearences are the required distances
that combustible objects must be away from the
heater to prevent serious fire hazard.
Figure 4. For vented units, the vent must terminate
outside of the building.
Vents must be fully sealed and correctly sized for
the model. If the vent passes through a wall or
ceiling of combustible material, it must be enclosed
by a listed thimble and be separated from the
thimble by at least a 2" (5 cm) air gap.
For separated combustion models, vents and air
intakes must be a fully sealed system and correctly
sized for the model. Vent should be assembled as
detailed
Figure 14. The joints between the vent terminal and
the roof or wall must be properly sealed. If the vent
passes through a wall or ceiling of combustible
material, it must be enclosed by a listed thimble and
be separated from the thimble by at least a 2" (5 cm)
air gap.
on Page 17, Figure 9 through Page 20,
See Page 7,
14
Page 21
SECTION 6: VENTING
Vents and air intakes must be adequately
supported so that the heater does not bear the
weight of the pipes.
For vent termination See Page 17, Figure 9 through
Page 20, Figure 14.
6.3.1 Standard Vented Heaters
(Models UHA[X] 30 - 125)
The vent must be fitted with a low resistance
terminal.
Figure 10. Standard vented heaters do not allow
outdoor air intake for combustion air.
6.3.2 Separated Combustion Heaters
(Models UHA[X]S 30 - 125)
The heaters are designed to be installed as
separated combustion heaters. The vent and air
intake are run as separate pipes to the wall or roof
terminals.
vent and air intake are run as separate pipes to a
concentric vent box and a concentric vent/air intake
pipe penetrates the wall or roof.
Figure 13and Page 20, Figure 14.
For seperated combustion installation, the vent and
air intake must be fitted with an individual and
correctly sized sealed system and the vent and air
intake must terminate at approved wall and roof
terminals.
Seperated combustion units may not be common
vented.
6.4 Unvented Operation
See Page 17, Figure 9 through Page 17,
See Page 19, Figure 12. As an option, the
See Page 19,
See Page 14, Section 6
WARNING
Carbon Monoxide Hazard
Heaters may be installed
vented or unvented.
Vented heaters must be
vented outdoors.
Unvented heaters must be
installed in buildings with
ventilation rates as per
section 6.4.
Failure to follow these
instructions can result in
death or injury.
The heater must be vented when installed in
residential buildings.
For unvented operation in commercial installations,
sufficient ventilation must be provided in the amount
of 4 cfm per 1000 Btu/h firing rate (United States); 3
cfm per 1000 Btu/h firing rate (Canada).
WARNING: Combustion by-products contain a
chemical known to the State of California to cause
cancer and birth defects or other reproductive harm.
6.5 Horizontal Venting
Horizontally vented heaters must be individually
vented.
Vent pipe must be sloped ¼" (.6 cm) for every 1' (.3
m). For vent lengths greater than 5' (1.5 m),
condensation will form. Insulation is recommended
and condensation drains may be desired.
In noncombustible walls only, vent terminal
(P/N 02537801-1P) may be used.
For 4'' (10 cm) vents in either combustible or
noncombustible walls, use vent terminal (P/N
90502100) or equivalent insulated vent terminal.
Follow the manufacturer's instructions for proper
installation.
Instead of an insulated vent terminal, a listed thimble
(with 2" (5 cm) air gap) may be used with a 4" (10
cm) vent cap (P/N 90502102).
In the State of Massachusetts, the following
regulations apply to horizontally-vented heaters
certified for installation in structures used in whole or
in part for residential purposes (UHA 30-75 only)
and where the side wall exhaust vent termination is
less than seven (7) feet above finished grade in the
area of the venting, including but not limited to decks
and porches:
Installation of Carbon Monoxide Detectors: At the
time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or
gasfitter shall observe that a hard wired carbon
monoxide detector with an alarm and battery backup is installed on the floor level where the gas
equipment is to be installed. In addition, the
installing plumber or gasfitter shall observe that a
battery operated or hard wired carbon monoxide
detector with an alarm is installed on each additional
level of the dwelling, building or structure served by
the side wall horizontal vented gas fueled
equipment. It shall be the responsibility of the
property owner to secure the services of qualified
licensed professionals for the installation of hard
wired carbon monoxide detectors
• In the event that the side wall horizontally
vented gas fueled equipment is installed in a
crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery backup may be installed on the next adjacent floor
level.
15
Page 22
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
• In the event that the requirements of this
subdivision can not be met at the time of
completion of installation, the owner shall have a
period of thirty (30) days to comply with the
above requirements; provided, however, that
during said thirty (30) day period, a battery
operated carbon monoxide detector with an
alarm shall be installed.
Approved Carbon Monoxide Detectors: Each carbon
monoxide detector as required in accordance with
the above provisions shall comply with NFPA 720
and be ANSI/UL 2034 listed and IAS certified.
Signage: A metal or plastic identification plate shall
be permanently mounted to the exterior of the
building at a minimum height of eight (8) feet above
grade directly in line with the exhaust vent terminal
for the horizontally vented gas fueled heating
appliance or equipment. The sign shall read, in print
size no less than one-half (1/2) inch in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS”.
6.7 Length Requirements
If using vent lengths greater than 5' (1.5 m),
condensation will form in the vent pipe. Insulation
and additional sealing measures (high temperature
silicone at all seams) are required.
The entire vent should be insulated with foil faced
fiberglass insulation (1/2" thick, 1-1/2# density
minimum).
6.7.1 Maximum Vent Lengths
Model UHA[X][S]
30 - 60
25 ft (7.6 m)40 ft (12.2 m)1
20 ft (6.1 m)35 ft (10.7 m)2
15 ft (4.6 m)30 ft (9.1 m)3
10 ft (3.0 m)25 ft (7.6 m)4
5 ft (1.5 m)20 ft (6.1 m)5
Model UHA[X][S]
75 - 125
Number of Elbows
6.8 Vent Material
Vent material may be single wall 26 ga. (minimum)
galvanized steel or equal thickness stainless steel.
Completely seal all joints, refer to
Page 14, Section
6.3.
Inspection: The state or local gas inspector of the
side wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon
inspection, the inspector observes carbon monoxide
detectors and signage installed in accordance with
the provisions of 248 CMR 5.08(2)(a)1 through 4.
6.6 Vertical Venting
Vertically vented heaters can be common vented
(up to four heaters).
For vent lengths greater than 5' (1.5 m),
condensation will form. Insulation is recommended
and condensation drains may be desired. Venting
through the top of the heater cabinet is not
recommended if vent lengths are longer than 10'
(3 m). In this case, vent from the rear of the heater
cabinet then run the vent vertically and use a
condensate drain at the bottom of the vertical vent.
Vent pipe must be sloped 1/4'' (.6 cm) for every 1' (.3
m).
For 4'' (10 cm), an approved vent cap
(P/N 90502102) must be used.
For 6'' (15 cm) common vent, an approved vent cap
(P/N 90502103) must be used.
For common vertical venting of more than two
heaters,
See Page 18, Figure 11.
A vent shall not extend less than 2' (.6m) above the
highest point where it passes through a flat roof of a
building.
If penetrating a combustible wall or roof, a listed
thimble with 2" (5 cm) clearance must be used.
Where local codes permit, a single section of type
B-1 vent material may be used at the roof or wall
penetration instead of a thimble. Ensure vent
manufacturer's clearance from vent material is
maintained. Seal annular space of the type B-1 vent
as well as all joints in the remaining vent.
6.9 Replacing an Existing Heater in a Venting
System
When replacing an existing heater in a venting
system, the venting system may not be properly
sized to vent the new heater. The following steps
must be followed with each appliance connected to
the venting system placed in operation, while any
other appliances connected to the venting system
are not in operation.
1. Seal any unused openings in the venting
system.
2. Inspect the venting system for proper size and
horizontal pitch, as required by the NFPA 54/
ANSI Z223.1 - latest revision, National Fuel
Gas Code (US) or Standard CSA B149.1
Natural Gas and Propane Installation Code
(Canada) and these instructions. Determine
that there is no blockage or restriction, leakage,
corrosion and other deficiencies which could
cause an unsafe condition.
3. Close all building doors and windows and all
doors between the space in which the
appliance(s) connected to the venting system
16
Page 23
SECTION 6: VENTING
ModelVent DiameterPart Number
UHA[X] 30 - 1254" (10 cm)90502102
are located and other spaces of the building.
Turn on clothes dryers and any exhaust fans,
such as range hoods and bathroom exhausts
so that they shall operate at maximum speed.
Do not operate a summer exhaust fan. Close
must be in accordance with the appropriate
local codes and the NFPA 54/ANSI Z223.1 latest revision, National Fuel Gas Code (US) or
Standard CSA B149.1 Natural Gas and
Propane Installation Code (Canada).
fireplace dampers.
4. Follow the lighting instructions. Place the
Figure 9: Vent and Roof Detail
appliance being inspected in operation. Adjust
thermostat so that the appliance will operate
continuously.
5. For any appliance having a draft hood, test for
draft hood appliance spillage at the draft hood
relief opening after 5 minutes of main burner
operation. Use the flame of a match or candle.
6. After it has been determined that each
appliance connected to the venting system
properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace
dampers and any other gas-burning appliances
to their previous conditions of use.
7. If improper venting is observed during any of
the above tests, the venting system must be
corrected by a contractor qualified in the
installation and service of gas-fired equipment
or your local gas supplier. If the venting must
be resized, use appropriate tables in (US)
Appendix G of NFPA 54/ANSI Z223.1 - latest
revision, National Fuel Gas Code (US) or
Standard CSA B149.1 Natural Gas and
Propane Installation Code (Canada) to
determine minimum size. All vent corrections
Figure 10: Standard Vented Heater - Vertical and Horizontal Vent Termination
Flashing
(By Others)
Listed
Thimble
(2" [5 cm]
Clearance)
4" (10 cm)
Diameter Vent
Vertical
Option
Vent Terminal
Horizontal
Option
Vent
NOTE: Vent supports not
shown.
Listed
Thimble
(2" [5 cm] Clearance)
Flashing
(By Others)
Vent
Terminal
12" (31 cm)
Minimum
17
Page 24
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Figure 11: Standard Vented Heater - Common Vertical Vent Termination
When installed as a separated combustion heater
(UHA[X]S), the air for combustion is drawn in from
outside the building. It is important to ensure that
there is adequate space around heater to provide air
for the axial air distribution fan.
7.2 Unvented Installation
It is important to ensure that there is adequate fresh
air supply at all times for both combustion and
heating requirements in accordance with local and
national codes.
WARNING: Combustion by-products contain a
chemical known to the State of California to cause
cancer and birth defects or other reproductive harm.
7.3 Building Ventilation
Where ventilation is required, air must be taken from
an outside point where it is not likely to be
contaminated or obstructed.
SECTION 7: AIR SUPPLY
7.4 Outside Combustion Air Supply
If outside combustion air supply is required,
separated combustion model (UHA[X]S) heaters
must be used.
Caution: If the building has a slight negative
pressure or corrosive contaminants such as
halogenated hydrocarbons are present in the air, an
outside combustion air supply to the heater is
required. Seal all combustion air pipe joints.
The flexible air duct may have to be insulated to
prevent condensation on the outer surface. The
outside air terminal must not be more than 1' (31
cm) above the vent terminal.
7.4.1 Length Requirements
Follow the constraints listed on Page 16, Section
6.7.
21
Page 28
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Do not bend flexible
gas connector
sharply.
• Hold gas nipple
securely with pipe
wrench when attaching
the flexible gas
connector.
• Do not twist flexible
gas connector.
• Ensure all
joints are
gas tight.
SECTION 8: GAS PIPING
• Gas supply pipe work is run in medium or heavy
WARNING
gauge tubing in compliance with local and
national codes.
• Meter and service must be large enough to
handle all the burners being installed plus any
other connected load. The gas pipe which feeds
the system must be large enough to supply the
required gas with a maximum pressure drop of
Fire Hazard
Connect gas supply according to Figure 15.
1/2" wc When gas piping is not included in the
layout drawing, contact the local gas supplier.
• An isolating valve and union connection should
be used and fitted into the supply adjacent to the
Do not use gas supply pipe and electrical
connections to support heater’s weight.
Gas can leak if not installed properly.
heater.
• A minimum 1/8" NPT plugged tapping
accessible for test connection must be installed
immediately upstream of the gas supply
Failure to follow these instructions can
result in death, injury or property damage.
connection to the heater.
• For suspended heaters, an approved metal
flexible connection between the isolating valve
A gas meter is connected to the service pipe by the
gas supply company. An existing meter should be
checked, preferably by the company, to ensure that
the meter is adequate for the rate of gas supply
required.
Installation pipes must be fitted in accordance with
local and national codes. Pipes of smaller size than
the heater inlet gas connection should not be used.
and the heater may be used. To reduce
pressure loss, use one pipe size larger than
the heater gas connection.
IMPORTANT - The complete installation must be
purged and tested for gas soundness in accordance
with local and national codes.
Caution: Do not high pressure (in excess of 1/2 psi
[14" wc]) test the gas piping with the burner
connected. Close manual shut-off valve during any
8.1 Connections
Connect the heater to the gas supply ensuring that
the final connections are as follows:
pressure testing equal to or less than 1/2 psi (14"
wc).
Check the pipe and tubing ends for leaks before
placing heating equipment into service. When
checking for gas leaks, use a soap and water
solution; never use an open flame.
Figure 15: Gas Connection
22
Gas Shut-off Valve
Union
Connection
Option A:
Stainless Steel
Flexible Gas
Connector
Option B:
Medium or Heavy
Gauge Pipe
Gas Connector
Drip Leg
Cap
Page 29
SECTION 9: WIRING
WARNING
Electrical Shock Hazard
Disconnect electrical and gas supply before
servicing.
This appliance must be connected to a
properly grounded electrical source.
Failure to follow these instructions can
result in death or electrical shock.
All heater models require constant 120 V/1Ø/ 60 Hz
power supply. Check heater rating plate for electrical
rating for proper circuit sizing. For servicing, a
disconnect switch of proper electrical rating should
be installed in the vicinity of the heater.
All heaters are equipped with thermostat
connections suitable to power a 24 V thermostat.
Heater must be wired and electrically grounded in
accordance with local codes. In the absence of local
SECTION 9: WIRING
codes in accordance with: United States: refer to
National Electrical Code
®
NFPA 70 - latest revision;
Canada: refer to Canadian Electrical Code CSA
C22.1 Part I - latest revision.
9.1 Positioning Thermostats
A room thermostat should be mounted on a
vibration-free wall or column at a height of
approximately 5' (1.5 m) from the floor to measure
the ambient temperature. It should be clear of both
cold drafts and the direct path of warm air from the
heater.
Avoid mounting thermostat on outside walls or in
areas directly exposed to radiant heat or sunlight.
Install wall tag in a visible location near thermostat
See Page 5, Section 2.1 for wall tag details.
9.1.1 Fan Control
The heater’s axial fan can be used during the offseason for air circulation. A low-voltage
programmable thermostat with a fan switch (P/N
90425400) must be
See Page 23, Section 9.2.
used. For thermostat connection details. For the use
of multiple heaters on one thermostat,
See Page 24,
Section 9.3 through Page 25, Section 9.4
9.2 Low Voltage Thermostat with One Heater
Gas
Supply
Electrical
Supply
Gas
Supply
Terminal
Strip
R
G
W
C
Terminal
Strip
R
G
W
C
24 Volt
Thermostat
Heating
Only
R
W
24 Volt
Thermostat
with Fan
Control
R
G
W
C
Electrical
Supply
23
Page 30
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
ModelRelay TypeRelay Part Number Max. Number of Heaters
UHA[X][S] 30 - 45SPST904176004
9.3 Low Voltage Thermostat with Multiple Heaters 30 - 45
24
Page 31
9.4 Low Voltage Thermostat with Multiple Heaters 60 - 125
ModelRelay TypeRelay Part Number Max. Number of Heaters
UHA[X][S] 60 - 125DPST904363004
SECTION 9: WIRING
25
Page 32
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Blue
Black
Black
Orange
Yellow
Brown
Black
White
White
L2
L1
Black
Black
Green
White
White
Green
Green
Blue
Black
Black
Black
White
Green
Blue
Green
24 VAC
HOT
GROUND
Flame
Black
Black
Black
6
3
4
5
2
1
45
31
SENSE
ELECTRODE
LIMIT
SWITCH
PRESSURE
SWITCH
AXIAL FAN
GAS VALVE
IGNITION
MODULE
TRANSFORMER
AXIAL FAN (UHA 300,
350, 400) ONLY)
LIMIT
SWITCH
(UHA
300,350,
400 ONLY)
MANUAL RESET LIMIT SWITCH
(UHA 30 - 125 ONLY)
THERMOSTAT INPUT:
FIELD SUPPLIED
R = 24 VAC TO THERMOSTAT (RED)
G = MANUAL FAN INPUT FROM THERMOSTAT (GREEN)
W = HEAT DEMAND INPUT FROM THERMOSTAT (WHITE)
C = COMMON SIDE OF TRANSFORMER
FLUE
BLOWER
R
G
W
C
ACC
L1
CMB
Blower
Yellow
Orange
Orange
Orange
IMPORTANT:
For field wiring into service junction box, or if any of the original wire supplied with the heater
must be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C
(221° F) and 600 volts. For supply connections, use No. 14 AWG or larger wires.
9.5 Internal Wiring Diagram
26
Page 33
9.6 Ladder Wiring Diagram
IMPORTANT:
For field wiring into service junction box, or if any of the original wire supplied with the heater
must be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C
(221° F) and 600 volts. For supply connections, use No. 14 AWG or larger wires.
SECTION 9: WIRING
120 VAC
FLAME
SENSOR
ELECTRODE
Flame
Spark
AXIAL FAN
AXIAL FAN
FLUE BLOWER
GAS
2
1
3
6
4
5
IGNITION
MODULE
UHA (300, 350, 400 Only)
TRANSFORMER
VALVE
PRESSURE SWITCH
Limit Switch
THERMOSTAT
CONNECTION
Limit Switch (UHA 300,
350, 400 Only)
Manual Reset Limit Switch
(UHA 30 - 125 Only)
27
Page 34
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
BX Connector
Junction Box
Flexible Conduit
Burner
Connect wires together
with suitable approved
wire connectors.
Green to Ground
White to L2
Black to L1
L1
L2
Ground
Black
White
Green
9.7 Electrical Connection to the Heater
IMPORTANT: Junction box is not provided with heater.
Conduit can also be attached directly to heater with wire junction made within the heater cabinet.
28
Page 35
SECTION 10: OPERATIONAND MAINTENANCE
WARNING
Explosion Hazard
Installation, service and annual inspection
must be done by a contractor qualified in
the installation and service of gas-fired
heating equipment or your gas supplier.
Turn off gas and electrical supplies before
performing service or maintenance.
Failure to follow these instructions can
result in death, injury or property damage.
SECTION 10: OPERATION AND MAINTENANCE
Read this manual carefully before installation,
operation, or service of this equipment. All
components are accessed via the door secured by
four sheet metal screws. Opening the door exposes
live electrical connections and hot components.
10.1 Pre-Start-Up Checks
All pre-start-up checks must be carried out before
lighting the heater.
Ensure that the heater and all controls are suitable
for the gas, pressure and electrical supply to which
they are to be connected.
10.1.1 Louvers
WARNING
10.1.2 Electrical Checks
All pre-start-up checks must be carried out before
start-up the heater.
1. Check that all site wiring is connected in
accordance with the appropriate wiring diagram
on Page 26, Section 9.5.
10.1.3 Gas Supply
All aspects of the gas installation including the gas
meter must be inspected, tested for gas tightness
and purged in accordance with local and national
codes.
Ensure that the air is fully purged from the heater
inlet pipe up to the main gas valve inlet test nipple.
10.1.4 Mechanical Checks
1. Check that the fan is free to run and delivery
louvers are turned to give required air
deflection.
2. Check that the flue (and air intake for separated
combustion units) is installed in accordance
with these instructions and local regulations.
10.2 Begin Start-Up
10.2.1 Before Operating the Heater
To ensure that all the controls are in safe working
order, operate the heater for the first time with the
isolating gas valve turned off and power supply
turned on.
1. Turn off the isolating gas valve.
2. Turn up the thermostat above room
temperature. The automatic ignition
sequence will now begin as described
on Page 30, Figure 16.
There will be no ignition of the burner and lockout
will occur, which proves the controls are operating
correctly.
Cut Hazard
Turn off gas and electrical supply before
maintenance.
Fan can start automatically at any time.
Failure to follow these instructions can
result in severe injury or product damage.
Where fitted, the air delivery louvers need to be set
during start-up to give the required air distribution
(optional vertical louvers).
29
Page 36
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
If at any stage the flame fails, the control will retry
for ignition. The control has four trials for ignition
before a one hour lockout.
Pressure Regulator
Gas Outlet
Outlet Pressure
DescriptionPart Number
Gas Valve 30 - 45 NG90034500
Gas Valve 30 - 45 LP90034600
Figure 16: Automatic Burner Control Sequence
Burner Sequence for Ignition Control
START
Thermostat 24 V
RUN
SHUT DOWN
Flue Blower
Pressure
Switch
Ignition Spark
Start Gas Valve
Flame Signal
Axial Fan
NO
P
C
NC
*Purge time begins at pressure switch change over.
30 Seconds Purge*
ts = 10 Seconds
30 Seconds Delay90 Seconds Delay
Required Incoming Signals
Signals Output By Control
Figure 17: Gas Valve for Models UHA[X][S] 30 - 45
30 Seconds Post Purge
30
Page 37
Figure 18: Gas Valve for Models UHA[X][S] 60 - 125
½PSIIN
C
ON
OFF
Regulator
Outlet
Pressure
Gas Inlet
Inlet Pressure
TOP VIEW
END VIEW
DescriptionPart Number
Gas Valve 60 - 125 NG90032505
Gas Valve 60 - 125 LP90032506
SECTION 10: OPERATIONAND MAINTENANCE
10.2.2 Start-Up the Gas Valve (All Gases)
10.2.2.1 Check Burner Gas Pressure
1. Remove the plug in the outlet (burner) pressure
test point and connect a pressure tap and a
manometer.
2. With the burner firing, measure the pressure on
the manometer. To adjust the burner pressure,
remove the regulator cover from the valve and
turn the regulator adjustment screw to set the
required burner pressure as stated in the
Technical Data Tables for the correct gas and
model
on Page 50, Section 15.3.
IMPORTANT: If the correct burner pressure cannot
be reached, then check the inlet pressure to the
valve with the burner firing. See Technical Data
Ta bl e s
on Page 50, Section 15.3 for inlet pressure
requirement.
Do not continue to adjust the regulator if the
pressure is not changing.
If the inlet pressure is too low to allow correct burner
pressure setting, then the gas inlet pressure must be
corrected before completing the start-up.
Check Gas Rate
1. After burner pressure adjustment, allow the
heater to operate for at least 15 minutes and
then re-check settings. Adjust pressure setting
if necessary.
2. Check gas flow rate at gas meter.
3. Turn off heater and electrical supply.
4. Remove the manometer and refit all covers to
the valve and tighten the screw of the outlet
pressure tap.
10.2.3 Pressure Switch
The pressure switch is factory pre-set for each
model and is not adjustable.
10.2.4 Turning Off the Heater
Set the thermostat to the "OFF" position or lowest
setting and the main burner will stop.
The fan will continue to run for 90 seconds.
Do not use a disconnect switch for control of
heater. Disconnect switch will turn off the fan.
31
Page 38
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Heat exchanger could be damaged. Warranty will
not cover damage to the heat exchanger if
operated improperly. Only use the disconnect
switch for turning off heater for service or during
off-season.
10.2.5 External Controls
External controls may include time switch, interlock
switch, room thermostat and frost thermostat.
Operate each control to ensure that they function
correctly. Set the switches (if fitted) and
thermostat(s) to the users’ requirements.
10.3 Complete Start-Up
Ensure that all covers are fitted correctly and all test
points are properly sealed.
10.3.1 Instruction to the User
Explain the controls of the heater to the user
including how to turn it on and off, using the controls
fitted on site.
Give this manual to the user.
Ensure that the user is shown and understands the
importance of maintaining clearances to
combustibles
on Page 7, Figure 4 and the user
instructions on Page 6, Section 3and Page 33, Section 11 and all warnings defined in this manual.
32
Page 39
SECTION 11: USER INSTRUCTIONS
WARNING
Explosion Hazard
Installation, service and annual inspection
must be done by a contractor qualified in
the installation and service of gas-fired
heating equipment or your gas supplier.
Turn off gas and electrical supplies before
performing service or maintenance.
Failure to follow these instructions can
result in death, injury or property damage.
Reset Button
To reset manual reset limit switch, press reset
button. NOTE: To reset, the switch must be cool.
DescriptionPart Number
Manual Reset Limit Switch90412106
SECTION 11: USER INSTRUCTIONS
11.1 User Instructions
The UHA[X][S] Series heaters are fully automatic
and operate from the external controls fitted on site.
The only user control at the heater is the Manual
Reset Limit Switch - See Page 33, Section 11.3.1
11.2 Heater Operation
When the heater has been switched on by the
thermostat installed on site, the main burner will
automatically turn on.
The burner control box will control the safe ignition
of the flame.
All heaters require a constant gas and electricity
supply which must not be interrupted during the
normal operation of this heater.
11.3 Common User Controls
11.3.1 Manual Reset Limit Switch
WARNING
Explosion Hazard
Do not make more than one attempt to
restart the heater if manual reset limit switch
locks out.
The vent or heat exchanger may be blocked.
The fault must be traced and repaired.
Failure to follow these instructions can
result in death, injury or property damage.
On residentially approved models, the limit
thermostat is located inside the access door of the
heater.
protects against excessive heat build-up inside the
burner compartment.
Figure 19: Manual Reset Limit Switch
See Page 44, Section 14.3. This control
11.4 Lighting Instructions
11.4.1 To Turn On Heater
1. Ensure that the electrical and gas supplies to
the heater are on. Check that the on site
controls are "ON".
IMPORTANT: The thermostat setting must be above
the ambient temperature for the heater to operate.
33
Page 40
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
2. The automatic firing sequence will begin as
described
on Page 30, Figure 16. The heater
will now operate automatically under the control
of the on site controls.
11.4.2 To Turn the Heater Off
Set the thermostat to the "OFF" position.
The burner will turn off immediately.
The fan will continue to run for 90 seconds.
To restart, turn the thermostat above room
temperature.
11.5 Simple Troubleshooting
Some possible reasons for the heater not operating
are:
1. Gas supply not "ON".
2. Electricity supply not "ON".
3. The time and/or temperature controls are not
"ON".
4. A limit switch may have operated. This may be
caused by an interruption of the electrical
supply, failure of the distribution fan or vent or
heat exchanger blockage.
If a temperature limit switch persistently trips, there
is a fault which must be investigated by a contractor
qualified in the installation and service of gas-fired
heating equipment.
11.5.1 Simple Troubleshooting (Burner Faults)
If the burner fails to ignite for any reason, it will retry
for ignition (four trials total). After four unsuccessful
ignition trials, the control will put the heater into
lockout for one hour.
Lockout should not occur during normal operation of
the heater and indicates there is a fault condition
which must be corrected. There is an LED light on
the ignition control that flashes codes to assist in
fault correction.
See Page 34, Figure 20 for LED
indication codes.
Figure 20: LED Diagnostic Codes
LED INDICATION FAU LT MODE
Slow FlashNormal Operation - No call for heat.
Fast Flas hNormal Operation - Call for heat.
2 FlashesIgnition Lockout - No flame detected.
3 FlashesAirflow Fault - Pressure switch open or closed.
4 FlashesTemperature Limit or
Manual Reset Limit Switch Open
5 FlashesFlame Sense Error - Gas valve not energized.
Steady OnInternal Control Failure
34
Page 41
SECTION 12: SERVICING
WARNING
Explosion Hazard
Installation, service and annual inspection
must be done by a contractor qualified in
the installation and service of gas-fired
heating equipment or your gas supplier.
Turn off gas and electrical supplies before
performing service or maintenance.
Failure to follow these instructions can
result in death, injury or property damage.
SECTION 12: SERVICING
12.1 Servicing Instructions
After start-up, the heater will require maintenance to
be carried out annually. If the heater is used in a
dirty or dusty area, more frequent maintenance may
be required.
IMPORTANT: After any maintenance or repair work,
always test fire the heater in accordance with the
start-up instructions
Page 32, Section 10.3.1 to ensure all safety systems
are in working order before leaving the heater to
operate. Minor faults may be traced by using the
troubleshooting charts
through Page 41, Section 13.5.
IMPORTANT: Check all gas pipes and pipe joints to
ensure there are no cracks or gas leaks. Any cracks
in the pipes or pipe joints must be repaired.
IMPORTANT: Inspect all suspended components
and hardware. Ensure that they are in good
condition, properly tightened, and corrosion free
12.2 Burner Maintenance
1. Open the door and remove the burner
compartment cover. See Page 43, Section
14.2.
2. Clean any deposits from the main burner which
may have formed in the injectors or venturi of
the burner. See Page 43, Section 14.2.
on Page 29, Section 10 through
on Page 38, Section 13
3. Remove the ignition electrode and flame probe.
Check condition of ignition electrode and flame
probe. Clean off any deposits which may have
been formed, check condition of ceramic
insulators. Replace as required.
12.3 Fan/Motor Assembly Maintenance
WARNING
Cut Hazard
Turn off gas and electrical supply before
maintenance.
Fan can start automatically at any time.
Failure to follow these instructions can
result in severe injury or product damage.
The main fan bearings are permanently sealed and
do not need lubrication. Before cleaning, turn off gas
and electrical supply. Remove the fan and use a
small brush or duster to clean the fan blades from
each side. Replace fan when done.
12.4 Heat Exchanger Maintenance
The heat exchanger will remain clean unless a
problem has developed with combustion. Inspect the
heat exchanger. Look for signs of overheating at the
front tubes which may indicate burner over firing or
persistently low air flows.
12.5 Gas Valve Maintenance
No regular maintenance is required on this device.
To change gas control valves,
14.1 .
Do not repair or disassemble gas valve.
Replace faulty gas valves with replacement parts
sold and supplied by Roberts-Gordon.
12.6 Flue Blower
The flue blower should not require maintenance.
However, if the air pressure switch is causing burner
lockout, then remove the flue blower from the vent
box by unscrewing the three screws at the mounting
plate. Remove the four screws attaching the
mounting plate to the fan inlet (
Section 14.6). Ensure that the fan is free to run and
that the fan wheel is clean.
See Page 42, Section
See Page 46,
35
Page 42
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
12.7 Venting and Air Intake Pipe
Inspect all venting and air intake pipe. Ensure that
all seams are sealed and suspension points secure.
Repair suspension points if any part of the venting
or combustion air pipe is sagging. Check to make
sure any insulation is not missing or in poor
condition. Replace as required. Check all venting
and air intake components to ensure they are in
good condition, gas tight and corrosion-free.
12.8 Maintenance Checklist
Installation Code and Annual Inspections: All
WARNING
installations and service of ROBERTS GORDON
equipment must be performed by a contractor
qualified in the installation and service equipment
sold and supplied by Roberts-Gordon and conform
to all requirements set forth in the ROBERTS
GORDON
governmental authorities pertaining to the
Explosion Hazard
Installation, service and annual inspection
must be done by a contractor qualified in
the installation and service of gas-fired
heating equipment or your gas supplier.
installation, service and operation of the equipment.
To help facilitate optimum performance and safety,
Roberts-Gordon recommends that a qualified
contractor annually inspect your ROBERTS
GORDON
necessary, using only replacement parts sold and
Turn off gas and electrical supplies before
performing service or maintenance.
supplied by Roberts-Gordon.
®
manuals and all applicable
®
equipment and perform service where
®
Failure to follow these instructions can
result in death, injury or property damage.
The Vicinity of the HeaterDo not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.
See Page 6, Section 3.
Vehicles and Other
Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged in between the heat exchanger or in the louvers.
Immediately remove objects in violation of the clearances to combustibles.
See Page 6, Section 3.
Vent Pipe/TerminalsVenting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
If the vent terminal has a screen built in, remove any dirt, dust or deposits
from the screen.
36
See Page 21, Section 7.
Page 43
SECTION 12: SERVICING
Combustion Air Intake
Pipe
Intake pipe and inlet must be intact. Look for obstructions, cracks on the pipe,
gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Clean and reinstall as required.
Heat ExchangerMake sure there are no cracks.
Make sure there is no sagging, bending or distortion.
Clean or replace as required.
See Page 22, Section 8.
Gas Line and Shut-off
Check for gas leaks. See Page 22, Section 8.
Valves
Burner Observation
Window
Flue Blower Scroll, Wheel
Make sure it is clean and free of cracks or holes.
Clean and replace as required.
Compressed air or a vacuum cleaner may be used to clean dust and dirt.
and Motor
Inshot Burners and
Orifices
Clear obstructions (even spider webs will cause problems).
Carefully remove any dust and debris from the burner.
Direct-Spark IgniterReplace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.
The electrode gap should be 1/8" (3.2 mm).
ThermostatThere should be no exposed wire or damage to the device or wiring.
See Page 29, Section 10.
Suspension PointsMake sure the heater is hanging securely.
Look for signs of wear on the suspension materials or ceiling.
See Page 11, Figure 5.
Silicone TubingEnsure tight, secure fit on all pressure fittings at pressure switch,
burner partition, and blower outlet.
Gas ValveVerify that cap covering pressure regulator adjustment screw is secure and
has not been tampered with.
Verify all wiring connections.
Condensate Drain
Flush drain and clear any obstructions.
(when installed)
Wall TagIf wall tag is present, make sure it is legible and accurate. Please contact
Roberts Gordon LLC or ROBERTS GORDON® independent distributor if you
need a wall tag.
See Page 5, Section 2.1.
37
Page 44
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
SECTION 13: TROUBLESHOOTING
13.1 General
START
Are gas & electrical
supplies on?
Ye s
Is ignition control showing a
"4 flashes" LED code
?
No
Ye s
Turn on supplies.
UHA 30 - 75: Press in reset
button on manual reset limit
switch. UHA 100 - 125: Wait
10 - 15 minutes for limit
switch to cool. Does fan
stop running?
No
WARNING
Explosion Hazard
Installation, service and annual inspection
must be done by a contractor qualified in
the installation and service of gas-fired
heating equipment or your gas supplier.
Turn off gas and electrical supplies before
performing service or maintenance.
Failure to follow these instructions can
result in death, injury or property damage.
Ye s
Fan and limit switch are
operating normally.
No
No
Is ignition control showing a
"2 flashes" LED code?
No
Does the flue
blower run?
Ye s
Yes
With external controls (i.e.
thermostat) on, does the
burner continue through the
heating cycle?
Ye s
Heater Operating
TROUBLESHOOT ENDS.
Replace temperature
limit switch.
Burner has locked out due
Ye s
No
No
No
to ignition failure. Use
Troubleshooting for
Automatic Ignition Burner
Systems section to test
burner.
Use Troubleshooting for
Flue Blower section to test
fan.
Has burner “Locked Out”?
Ye s
Use Troubleshooting for
Automatic Ignition Burner
Systems section to test burner.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
No
The limit switch has
tripped. See Manual Reset
Limit Switch Figure.
Ensure proper air flow
clearance for axial fan.
Open louvers slightly.
Replace axial fan if it does
not operate.
Ye s
No
Replace limit switch.
38
Page 45
13.2 Troubleshooting For Automatic Ignition Burner Systems
For optimum heater performance, use only replacement parts sold and supplied by Roberts-Gordon.
Conduct start-up procedure as shown on Page 29, Section 10.
SECTION 13: TROUBLESHOOTING
39
Page 46
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.
Repair or replace as
required.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Replace ignition control.
Use General
Troubleshooting section to
trace the fault.
Heater Operating
TROUBLESHOOT ENDS.
No
Repair or replace as
required.
Is inlet burner gas pressure
correct? Is live and neutral
polarity correct? Is
flame probe circuit correct?
Is there a current flowing in
the flame probe circuit with
no flame present?
Ye s
No
Does “lockout” occur when
there is a flame present?
Ye s
Is the connecting lead
damaged? Is the flame probe
damaged or touching earthed
components?
No
Is the flame present and
at least 1 μA DC flame
current?
Connect a DC ammeter in
series with the flame probe.
Ye s
No
Ye s
Ye s
No
START
To measure flame current, connect a 0 - 50 μA DC meter in series with the flame probe. If the meter
reads negative values, then reverse the test leads.
13.3 Troubleshooting for Flame Supervision System
40
Page 47
13.4 Troubleshooting for Gas Valves
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
Blower Operating
TROUBLESHOOT ENDS.
No
Blower motor faulty.
Replace with correct type.
Check blower motor leads
for loose connections.
Correct power
supply problem.
Ye s
START
Does blower turn on and
off while burner is firing
continuously?
No
Ye s
Does flue blower run
automatically when there
is a call for heat?
No
Ye s
For optimum heater performance, use only replacement parts sold and supplied by Roberts-Gordon.
Conduct start-up procedure as shown on Page 29, Section 10.
START
SECTION 13: TROUBLESHOOTING
Is gas pressure at inlet of the
valve correct for gas type?
Note pressure found.
Does gas pressure at outlet
of the valve rise when
valve turns on?
Does gas pressure at
outlet of valve return to zero or
lower when valve turns off?
Valve Operating
TROUBLESHOOT ENDS.
13.5 Troubleshooting for Flue Blower
Ye s
Ye s
Yes
Ye s
No
No
No
No
Fault elsewhere.
Correct pressure problem.
Valve or ignition control
faulty. Replace with
one of correct type.
Valve faulty.
Replace with one of
correct type.
If problems persist, contact
Roberts-Gordon LLC at
www.rg-inc.com
41
Page 48
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
½PSIIN
C
ON
OFF
Flexible Air Duct
DescriptionPart Number
Gas Valve, NG (Models UHA[X][S] 30 - 45)90034500
Gas Valve, LP (Models UHA[X][S] 30 - 45)90034600
Gas Valve, NG (Models UHA[X][S] 60 - 125)90032505
Gas Valve, LP (Models UHA[X][S] 60 - 125)90032506
NOTE: Seperated combustion
model shown.
SECTION 14: REPLACEMENT PARTS
WARNING
Explosion Hazard
Installation, service and annual inspection
must be done by a contractor qualified in
the installation and service of gas-fired
heating equipment or your gas supplier.
Turn off gas and electrical supplies before
performing service or maintenance.
Failure to follow these instructions can
result in death, injury or property damage.
See warnings and notes on Page 35, Section 12
before removing or replacing parts.
14.1 Gas Valve
Remove the gas supply pipe at the heater inlet.
Follow steps in Section 14.2 and Section 14.2.1 to
remove gas valve/manifold.
Replace in reverse order. Verify that the gas flow
direction of the valve is correct. Use a minimum
amount of gas seal on the thread joint. Check that
all the joints are leak free. Reset gas valve.
See
Page 31, Section 10.2.2.
IT IS IMPORTANT THAT ONLY THE CORRECT
GAS VALVE IS USED WHEN REPLACING THESE
CONTROLS.
Burner Components
All serviceable burner parts are accessed by the
door on the side of the heater. Remove the
sheetmetal screws.
42
Page 49
14.2 Burner Compartment
Remove flexible
air duct from spigot
Viewing port
for flame probe
Flame Probe
Burner
Compartment
Cover
Ignition Electrode
Remove screws and
pull off burner cover
NOTE: Separated combustion
model shown.
The burner compartment is a sealed
compartment. Following any work,
re-seal the compartment with the
gas pipe rubber seal fully in place
and all screws fitted and tight.
To replace the electrode or flame probe, remove the electrical lead and screw.
Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the front view of
the burner compartment.
14.3 Ignition Electrode and Flame Probe
44
Page 51
SECTION 14: REPLACEMENT PARTS
Push in
Louver and compress
spring to remove
(opposite end first)
InstallVerticalLouver Brackets(top and bottom)with suppliedscrews.
InstallVerticalLouvers and Springinto BracketswithSprings atTop
HorizontalLouvers
Vertical Louvers
Push in
Louver and compress
spring to remove
(opposite end first)
Install Vertical
Louver Brackets
(top and bottom)
with supplied
screws.
Install Vertical
Louvers and Springs
into Brackets
with Springs at Top
Horizontal
Louvers
Vertical
Louvers
For models UHA[X][S] 60 and UHA[X][S] 75, horizontal louvers are re-used.
Description
UHA[X][S]
30 - 45
UHA[X][S]
60 - 75
UHA[X][S]
100 - 125
Horizontal Louvers P/N11111900
Spring P/N91901200
Quantity357
The heat exchanger consists of a four-pass design with 1.5" outer diameter [aluminized steel][409 stainless
steel] tube. The tube plates are made of [aluminized steel][409 stainless steel]. The tube supports are
made of [galvannealed steel] [409 stainless steel].
14.5 Louver and Louver Springs
45
Page 52
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Mounting Plate
to Vent Box
fixing screws
Flexible Air
Duct
Intake &
Exhaust
Covers
Air Intake Adapter
Gasket
To remove the blower,
remove screws securing the
fan and mounting plate to
the vent box.
To remove the blower from
the mounting plate, remove
screws.
Refit in reverse order.
To change the vent and air
intake orientation from back
to top, remove the blower
and mounting plate as
above.
Remove intake (if
applicable) and exhaust
covers from top of the
heater.
Rotate the blower, mounting
plate and gasket clockwise
until the flue adapter lines
up with the top hole. Secure
screws.
If applicable, remove the
flexible air duct from the air
intake adapter on the back.
If applicable, remove the air
intake adapter from the back
of the heater and install in
the appropriate hole on top.
Reconnect the flexible air
duct.
Install intake and exhaust
covers over the back holes.
NOTE: Seperated combustion model shown.
14.6 Flue Blower Vertical Installation
Intake &
Exha
Covers
Mounting Plate
to Vent Box
fixing screws
Air Intake
Adaptor
Mounting Plate
to Flue Blower
screws
Gaskets
Vent Box
ust
MODELUHA[X][S] 30 -75UHA[X][S] 100 - 125
Flue Blower P/N9071040490710405
IT IS IMPORTANT THAT ONLY THE CORRECT FLUE BLOWER SPECIFIED FOR EACH MODEL TYPE
IS USED WHEN REPLACING THESE ITEMS.
Carry out a start-up after working on or changing an flue blower. See Page 33, Section 11.
46
Page 53
SECTION 14: REPLACEMENT PARTS
14.7 Pressure Switch
Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of pressure
switch for model. The pressure switches are color coded for each pressure setting. Carry out a start-up
after working on or changing a pressure switch.
The control mounts to the heat exchanger plate. Pull out ignition cable and wiring from board, noting their
positions. Release the four mounting standoffs. Refit in reverse. Ensure correct location of ignition cable
and all other wiring.
14.9 Axial Fan/Guard/Motor Assembly
The axial fan unit for the heater is supplied completely assembled and balanced.
Axial Fan Guard91901103919011039190110291901102 9190110291901102
Axial Fan Motor90600104 90600104 90600105 90600105 90600106 90600106
Axial Fan Blade90709004 90709003 90709002 90709001 90709001 90709001
47
Page 54
UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATIONAND SERVICE MANUAL
Remove the screws
and washers.
Remove the mounting hardware.
14.9.1 Fan Removal and Replacement
DescriptionPart Number Quantity
Axial Fan UHA[X][S] 30120119101
Axial Fan UHA[X][S] 45120119111
Axial Fan UHA[X][S] 60120119201
Axial Fan UHA[X][S] 75120119211
Axial Fan UHA[X][S] 100 and UHA[X][S]
125
120119221
14.9.2 To Replace the Fan Assembly
To replace the fan assembly, reverse the procedure
shown above.
• Check that the fan blades are free to rotate
before turning on the power to the fan.
• Strictly comply with the color code of the fan
wires to ensure correct operation.
See Page 26,
Section 9.5 wiring diagram.
•Use only replacement parts sold and supplied
by Roberts-Gordon.
Natural Gas (G20) Data - Inlet Pressure 5.0 in wc Min., 14 in wc Max.
Burner Pressurein wc3.73.63.73.52.63.3
LPG / Propane (G31) Data - Inlet Pressure 12.0 in wc Min., 14 in wc Max.
Burner Pressurein wc9.49.69.610.09.110. 0
50
Page 57
SECTION 16: ROBERTS GORDON® COMBAT® UHA-SERIES WARRANTY
SECTION 16: ROBERTS GORDON® COMBAT® UHA-SERIES WARRANTY
ROBERTS GORDON® WILL PAY FOR:
Within 24 months from date of purchase by buyer or 27
months from the date of shipment by Roberts-Gordon
(whichever comes first), replacement parts will be
provided free of charge for any part of the product which
fails due to a manufacturing or material defect.
Roberts-Gordon will require the part in question to be
returned to the factory. Roberts-Gordon will, at its sole
discretion, repair or replace after determining the nature
of the defect and disposition of part in question.
ROBERTS GORDON® Replacement Parts are warranted
for a period of 18 months from date of shipment from
Roberts-Gordon or the remaining ROBERTS GORDON
COMBAT® UHA-Series warranty.
ROBERTS GORDON
Service trips, service calls and labor charges.
Shipment of replacement parts.
Claims where the total price of the goods have not
been paid.
Damage due to:
• Improper installation, operation or maintenance.
• Misuse, abuse, neglect, or modification of the
ROBERTS GORDON
way.
• Use of the ROBERTS GORDON® COMBAT® UHASeries for other than its intended purpose.
• Incorrect gas or electrical supply, accident, fire, floods,
acts of God, war, terrorism, or other casualty.
• Improper service, use of replacement parts or
accessories not specified by Roberts-Gordon.
• Failure to install or maintain the ROBERTS
®
GORDON
COMBAT® UHA-Series as directed in the
Installation, Operation and Service manual.
• Relocation of the ROBERTS GORDON® COMBAT
UHA-Series after initial installation
• The use of the ROBERTS GORDON® COMBAT® UHASeries in a corrosive atmosphere containing
contaminants.
• The use of the ROBERTS GORDON® COMBAT® UHASeries in the vicinity of a combustible or explosive
material.
• Any defect in the ROBERTS GORDON® COMBAT
UHA-Series arising from a drawing, design, or
specification supplied by or on behalf of the
consumer.
• Damage incurred during shipment. Claim must be
filed with carrier.
®
WILL NOT PAY FOR:
®
COMBAT® UHA-Series in any
The ownership of the ROBERTS GORDON® COMBAT
UHA-Series is moved or transferred. This warranty is
nontransferable.
Roberts-Gordon is not permitted to inspect the damaged
controller and/or component parts.
READ YOUR INSTALLATION, OPERATION AND
SERVICE MANUAL
If you have questions about your controller, contact your
installing professional. Should you need Replacement
Parts or have additional questions, call or write:
Roberts-Gordon
®
1250 William Street
P. O . B o x 4 4
Buffalo, New York 14240-0044
716.852.4400
On the web at: www.rg-inc.com
Roberts-Gordon' liability, and your exclusive remedy,
under this warranty or any implied warranty
(including the implied warranties of merchantability
and fitness for a particular purpose) is limited to
providing replacement parts during the term of this
warranty.
how long an implied warranty lasts, so this limitation may
not apply to you. There are no rights, warranties or
conditions, expressed or implied, statutory or otherwise,
other than those contained in this warranty.
Roberts-Gordon shall in no event be responsible for
incidental or consequential damages or incur liability
for damages in excess of the amount paid by you for
the ROBERTS GORDON
Some jurisdictions do not allow the exclusion or limitation
of incidental or consequential damages, so this limitation
or exclusion may not apply to you. This warranty gives
you specific legal rights, and you may also have other
rights which vary from jurisdiction to jurisdiction.
®
Roberts-Gordon shall not be responsible for failure to
perform under the terms of this warranty if caused by
circumstances out of its control, including but not limited
to war, fire, flood, strike, government or court orders, acts
of God, terrorism, unavailability of supplies, parts or
power. No person is authorized to assume for RobertsGordon any other warranty, obligation or liability.
LIMITATIONS ON AUTHORITY OF
®
REPRESENTATIVES:
No representative of Roberts-Gordon, other than an
Executive Officer, has authority to change or extend these
provisions. Changes or extensions shall be binding only if
confirmed in writing by Roberts-Gordon's duly authorized
Executive Officer.
Some jurisdictions do not allow limitations on
®
COMBAT® UHA-Series .
®
WARRANTY IS VOID IF:
The ROBERTS GORDON® COMBAT® UHA-Series is not
installed by a contractor qualified in the installation and
service of gas-fired heating equipment.
You cannot prove original purchase date and required
annual maintenance history.
The data plate and/or serial number are removed,
defaced, modified or altered in any way.
51
Page 58
Page 59
Warm Air Heating
OWNER WARRANTY REGISTRATION CARD
®
Roberts Gordon LLC • 1250 William Street, P.O. Box 44 • Buffalo, NY 14240-0044 • Phone: 716-852-4400 • Fax: 716-852-0854
Model#:_______________________ Serial #:___________________________ Fuel:____________ Installation Date:__________
Type of Installation (check one):
o Automotive o Manufacturing o Warehouse o Recreational o Aircraft
o Public Building o Office o Retail o Agricultural o Other______________
Toll Free: 800-828-7450 • www.rg-inc.com
Mail or Fax to:
Installation Code and Annual Inspections: All installations and service of ROBERTS GORDON® equipment must be performed by a
contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and conform to all
requirements set forth in the ROBERTS GORDON
installation, service and operation of the equipment.
To help facilitate optimum performance and safety, Roberts-Gordonrecommends that a qualified contractor annually inspect your
ROBERTS GORDON
Roberts-Gordon.
These products are not approved forresidential use, except for models UHA[X][S] 30 - UHA[X][S] 75.
Attach this information to the wall near the ROBERTS GORDON® heater
Read the Installation, Operation and Service Manual thoroughly before installation, operation or service.
OPERATING INSTRUCTIONS
1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting (above ambient temperature).
The automatic starting sequence begins.
1. Turn the thermostat/time switch to 'OFF' or lowest setting. The burner
will turn 'OFF' immediately, but fans will continue to cool heat exchanger
until the fan thermostat switches off.
1. Set the thermostat to off or the lowest setting.
2. Turn off electric power to the heater.
3. Turn off the manual gas valve in the heater supply line.
4. Call your installer/contractor qualified in the installation and service
of gas-fired heating equipment.
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER
Fire Hazard
Some objects can catch fire or explode when placed
close to heater.
Keep all flammable objects, liquids and vapors the
required clearances to combustibles away from heater.
Failure to follow these instructions can result in death,
injury or property damage.
TO TURN OFF THE HEATER
Roberts-Gordon, LLC
1250 William Street
P.O. Box 44
Buffalo, NY 14240-0044 USA
®
LeftRight
Bottom
Top
Clearances to Combustibles
Wall
Terminal
Roof Terminal
Max. Mounting Height*
Rear*
Installation Clearances
Installation Code and Annual Inspections:
All installations and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and
conform to all requirements set forth in the ROBERTS GORDON
®
manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help
facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON
®
equipment and perform service where necessary,
using only replacement parts sold and supplied by Roberts-Gordon.
For installations at elevations above 2000' (610 m), the appliance shall be derated 4% for each 1000' (305 m) of elevation above sea level.
Further Information:Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives. Please
contact us for any further information you may require, including the Installation, Operation and Service Manual.
Heaters can be mounted higher if destratification fans are installed. See Installation, Operation
and Service Manual for specific mounting height recommendations.
NOTE: Venting directly from top of heater not applicable on Models 150-400.
Models
Top
Bottom
Right
Left
Vent
30 - 125
1" (2.5 cm)
0" (0 cm)
1" (2.5 cm)
18" (46 cm)*
2" (5 cm)
150 - 400
6" (15 cm)
3" (8 cm)
31" (79 cm)*
6" (15 cm)
2" (5 cm)
* Clearance needed for servicing.
Top
Bottom
Right
Left
Models 30 - 125Models 150 - 400
(Optional separated
combustion concentric
venting shown.)
Top*
1
1
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.