Roberts Gorden TF-250, TF-200, TF-300, TF-350, TF-120 User Manual

...
Page 1
WARNING
FOR YOUR SAFETY If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
5. Extinguish any open flame.
6. Leave the building.
7. Immediately call your local gas supplier after leaving the building. Follow the gas supplier’s instructions.
8. If you cannot reach your gas supplier, call the Fire Department.
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clear­ances to combustibles away from heater.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
WARNING
Installation must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and Service Manual thoroughly before installing or servicing this equipment.

Vantage® TF

Twin Fire
Unitary Infrared Heater
Installation, Operation &
Service Manual
TF-120 TF-160 TF-200 TF-250
© 2012 Roberts-Gordon LLC
TF-300 TF-350 TF-380
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
Roberts-Gordon LLC
1250 William Street P. O. Bo x 4 4 Buffalo, New York 14240-0044 Telephone: +1.716.852.4400 Fax: +1.716.852.0854 Toll Free: 800.828.7450
www.rg-inc.com www.radiantheaters.com
P/N 190100NA Rev. H 05/12
Page 2
Page 3
© 2012
Roberts-Gordon LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon LLC.

TABLE OF CONTENTS

SECTION 1: Heater Safety...................................................... 1
1.1 Manpower Requirements ............................................. 1
1.2 Safety Labels and Their Placement ............................. 1
1.3 California Proposition 65 .............................................. 1
SECTION 2: Installer Responsibility ..................................... 4
2.1 Wall Tag .......................................................................4
2.2 Corrosive Chemicals.................................................... 4
2.3 National Standards and Applicable Codes ..................4
SECTION 3: Clearances to Combustibles............................. 5
3.1 Required Clearances to Combustibles.........................5
SECTION 4: National Standards and Applicable Codes ... 10
4.1 Gas Codes................................................................. 10
4.2 Aircraft Hangars ......................................................... 10
4.3 Public Garages .......................................................... 10
4.4 Electrical .................................................................... 10
4.5 Venting....................................................................... 10
4.6 High Altitude .............................................................. 10
SECTION 5: Major Components .......................................... 11
5.1 Standard Parts List .................................................... 12
SECTION 6: Suggested Layouts.......................................... 14
6.1 TF-380 - 4 Elbow Design (Common Vent) ................. 14
6.2 TF-350 - 4 Elbow Design (Common Vent) ................. 14
6.3 TF-300 - Double "U" Design (Common Vent) ............ 14
6.4 TF-160 - Single Elbow Design (Individual Vents)....... 15
6.5 TF-160 - Double "L" Design (Individual Vents)........... 15
6.6 TF-250 - Combination "L" and "U" Design
(Individual Vents) .......................................................15
SECTION 7: Heater Installation............................................ 16
7.1 Burner Tube Installation ............................................ 21
7.2 Burner Installation...................................................... 21
7.3 Tube Clamp Package Installation..............................22
7.4 Coupling and Tube Assembly....................................22
7.5 Turbulator Installation ................................................24
7.6 Reflector Installation ...................................................25
SECTION 8: Optional Heater Accessories..........................27
8.1 U-Tube Configu
8.2 Elbow Package Configuration ....................................31
8.3 Reflector Side Extension............................................33
8.4 Lower Clearance Shield Installation ..........................34
8.5 Two-Foot Decorative Grille Installation....................... 34
8.6 Protective Grille Installation........................................ 36
SECTION 9: Venting.............................................................. 37
9.1 Venting Requirements................................................37
9.2 Unvented Operation................................................... 37
9.3 Horizontal Venting......................................................37
9.4 Vertical Venting..........................................................38
9.5 Unvented Operation Tube Termination ......................38
9.6 Length Requirements ................................................38
9.7 Horizontal Ventilation 4" (10 cm) Pipe........................38
ration................................................. 27
9.8 Vertical Ventilation 4" (10 cm) Pipe............................ 39
9.9 Flexible Boot Installation (Single Vent) ...................... 39
9.10 Common Sidewall Venting....................................... 40
9.11 Vertical Ventilation 6" (15 cm) Pipe ......................... 40
9.12 Flexible Boot Installation (Common Vent)................ 41
9.13 Outside Combustion Air Supply............................... 42
SECTION 10: Gas Piping...................................................... 44
SECTION 11: Wiring.............................................................. 46
11.1 Line Voltage Thermostat Wiring ............................... 46
11.2 L o w Voltage Thermostat and Relay Wiring............... 47
11.3 Internal Wiring .......................................................... 48
11.4 Ladder Diagram....................................................... 48
11.5 Electrical Connection to the Burner.......................... 49
SECTION 12: Operation and Maintenance.......................... 50
12.1 Sequence of Operation............................................ 50
12.2 To Shut Off Heater ................................................... 50
12.3 To Start Heater ........................................................ 50
12.4 Pre-Season Maintenance and Annual Inspection.... 50
12.5 Maintenance Checklist............................................. 51
SECTION 13: Troubleshooting............................................. 53
13.1 Troubleshooting Flow Chart ..................................... 54
13.2 Manifold Gas Pressure Setting ................................ 56
SECTION 14: Replacement Parts ........................................ 57
SECTION 15: General Specifications .................................. 59
15.1 Material Specifications............................................. 59
15.2 Heater Specifications............................................... 59
15.3 Suspension Specifications....................................... 59
15.4 Controls Specifications ............................................ 59
SECTION 16: The ROBERTS GORDON
Warranty ......................................................... 61
®
VANTAGE® TF
Prin ted in U.S.A.
Page 4
Page 5
TABLE OF FIGURES
Figure 1: Top and Bottom Panel Label Placement ....................2
Figure 2: Side Panel Label Placement......................................3
Figure 3: Standard Reflector .....................................................6
Figure 4: One Side Reflector.....................................................6
Figure 5: Two Side Reflectors ................................................... 6
Figure 6: 45° Tilt Reflector ........................................................ 7
Figure 7: U-Tube, Standard Reflector........................................ 7
Figure 8: U-Tube, 45°................................................................ 7
Figure 9: U-Tube, Opposite 45° Reflector .................................8
Figure 10: 2-Foot Deco Grille and Protective Grille ................... 8
Figure 11: Lower Clearance Shield*.......................................... 8
Figure 12: Venting ..................................................................... 9
Figure 13: Major Component Descriptions.............................. 11
Figure 14: Critical Hanger Placement ..................................... 17
Figure 15: Linear Heater Assembly Overview ........................ 18
Figure 16: Linear Heater Layout Overview.............................. 19
Figure 17: Linear Heater Layout Overview (Continued) .......... 20
Figure 18: U-Tube Heater Assembly O
Figure 19: U-Tube Heater Layout Overview ............................29
Figure 20: U-Tube Heater Layout Overview (Continued) ........30
Figure 21: Reflector Joint Detail ..............................................32
Figure 22: Tube Termination ................................................... 38
Figure 23: Gas Connection with Flexible Gas Hose ...............45
verview ...................... 28
LIST OF TABLES
Table 1: Contents of Burner Carton........................................ 12
Table 2: Contents of Core and Extension Packages .............. 12
Table 3: Component Package Guide......................................13
Page 6
Page 7
SECTION 1: HEATER S AFETY

SECTION 1: HEATER SAFETY

Yo ur Safety is Important to Us! This symbol is used throughout the manual to notify you of possi­ble fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these sections.
Installation, Service and Annual Inspection of heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment.
Read this manual carefully before installation, operation or service of this equipment.
This heater is designed for heating nonresidential indoor spaces. Do not install in residential spaces. These instructions, the layout drawing, local codes and ordinances, and applicable standards that apply to gas piping, electrical wiring, venting, etc. must be thoroughly understood before proceeding with the installation.
Protective gear is to be worn during installation, operation and service. Thin sheet metal parts, including the aluminum reflector portion of the heater and the various
venting components, have sharp edges. To prevent injury, the use of work gloves is recommended. The use of gloves will also prevent the transfer of body oils from the hands to the surface of the reflector.
Before installation, check that the local distribution conditions, nature of gas and pressure, and adjustment of the appliance are compatible.
This heater must be applied and operated under the general concepts of reasonable use and installed using best building practices. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do no play with the appliance.
For additional copies of the Installation, Operation and Service Manual, please contact Roberts-Gordon LLC.
1. 1 M an p o we r R e
quirements
To p revent personal injury and damage to the heater, two persons will be required for installation.

1.2 Safety Labels and Their Placement

the product user when they are no longer legible. Please contact Roberts-Gordon LLC or your ROB- ERTS GORDON
®
independent distributor to obtain replacement signs or labels. See Page 2, Figure 1 through Page 3, Figure 2.

1.3 California Proposition 65

In accordance with California Proposition 65 require- ments, a warning label must be placed in a highly visible location on the outside of the equipment (i.e., near equipment’s serial plate). See label placement drawing on Page 2, Figure 1 for label location. Avoid placing label on areas with extreme heat, cold, corro­sive chemicals or other elements. To order additional labels, please contact Roberts-Gordon LLC or your
®
ROBERTS GORDON
independent distributor.
Product safety signs or labels should be replaced by
1
Page 8
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Logo Label
Rating Plate Label
Bottom Panel
Gas Connection Label
Lighting Instruction Plate Label
Top Panel
Printed in the U.S.A/Imprimé aux Etats-Unis P/N 91018124 Orig.
www.rg-inc.com
WARNING
Risque d’incendie Serrez et installez les raccords de canalisation de gaz pour relier la source de gaz selon l'exemple. Le ligne de gaz de câble peut se ssurer une fois tordue. Le ligne de gaz se déplace pendant l'exécution normale. Utilisez seulement un connecteur de ½" ou de ¾" en diamètre interne nominal et d’une longeur de 36" (91 cm). Le connecteur est fourni avec le chauffage pour les modèles américains (Pas avec les modèles canadiens). Le non-respect de ces consignes peut causer la mort, les blessures ou le dommage matériel.
© 2009 Roberts-Gordon LLC
INCORRECT POSITIONS / POSITION INEXACT
Horizontal/
Vue de côte
End View/Vue arrière
Vertical (as shown left)/ (montrée à gauche)
Alternate positions okay/
Positions alternatives sont bien
Fire Hazard Tighten and install gas hose ttings to connect gas supply according to example below. Gas hose can crack when twisted. Gas hose moves during normal operation. Use only 36" (91cm) long connector of 1/2" or 3/4" nominal ID. Connector supplied with heater for U.S. models (not with Canadian models). Failure to follow these instructions can result in death, injury or property damage.
CORRECT POSITIONS / POSITION EXACT
Heater Movement/
Mouvement d'appareil de
chauffage
Heater Movement/
Mouvement d'appareil de
chauffage
Heater Movement/
Mouvement d'appareil de
chauffage
Heater Movement/
Mouvement d'appareil de
chauffage
ATTENTION
Shut-Off Valve must be parallel to burner gas inlet. The 3" (8 cm) displacement shown is for the cold condition. This displacement may reduce when the system is fired.
Le Robinet d’arrêt doit être parallèle au tube d'admission de gaz du brûleur. Le déplacement de 3"(8 cm) montré est quand le système est froid. Ce déplacement peut diminuer quand le système est activé.
Shut-Off Valve(Included With Gas Hose)/
Robinet d’arrêt (Fournie avec le raccordement)
Heater Movement/Mouvement d'appareil de chauffage
Flexible Gas Hose 36" (91 cm) length/
Flexible de Raccordement de Gaz en Acier Inoxydable de longuer 36" (91 cm)
12"
(30 cm)
3" (8 cm) max. displacement/ déplacement maximum
Side View/Vue de côté
45°
45°
3/4" NPT Pipe/Tuyau
90° Pipe Elbow (Not Included)/
Coude á 90° (Non Inclus)
Printed in the U.S.A/Imprimé aux Etats-Unis P/N 91018124 Orig.
www.rg-inc.com
WARNING
Risque d’incendie Serrez et installez les raccords de canalisation de gaz pour relier la source de gaz selon l'exemple. Le ligne de gaz de câble peut se ssurer une fois tordue. Le ligne de gaz se déplace pendant l'exécution normale. Utilisez seulement un connecteur de ½" ou de ¾" en diamètre interne nominal et d’une longeur de 36" (91 cm). Le connecteur est fourni avec le chauffage pour les modèles américains (Pas avec les modèles canadiens). Le non-respect de ces consignes peut causer la mort, les blessures ou le dommage matériel.
© 2009 Roberts-Gordon LLC
INCORRECT POSITIONS / POSITION INEXACT
Horizontal/
Vue de côte
End View/Vue arrière
Vertical (as shown left)/ (montrée à gauche)
Alternate positions okay/
Positions alternatives sont bien
Fire Hazard Tighten and install gas hose ttings to connect gas supply according to example below. Gas hose can crack when twisted. Gas hose moves during normal operation. Use only 36" (91cm) long connector of 1/2" or 3/4" nominal ID. Connector supplied with heater for U.S. models (not with Canadian models). Failure to follow these instructions can result in death, injury or property damage.
CORRECT POSITIONS / POSITION EXACT
Heater Movement/
Mouvement d'appareil de
chauffage
Heater Movement/
Mouvement d'appareil de
chauffage
Heater Movement/
Mouvement d'appareil de
chauffage
Heater Movement/
Mouvement d'appareil de
chauffage
ATTENTION
Shut-Off Valve must be parallel to burner gas inlet. The 3" (8 cm) displacement shown is for the cold condition. This displacement may reduce when the system is fired.
Le Robinet d’arrêt doit être parallèle au tube d'admission de gaz du brûleur. Le déplacement de 3"(8 cm) montré est quand le système est froid. Ce déplacement peut diminuer quand le système est activé.
Shut-Off Valve(Included With Gas Hose)/
Robinet d’arrêt (Fournie avec le raccordement)
Heater Movement/Mouvement d'appareil de chauffage
Flexible Gas Hose 36" (91 cm) length/
Flexible de Raccordement de Gaz en Acier Inoxydable de longuer 36" (91 cm)
12"
(30 cm)
3" (8 cm) max. displacement/ déplacement maximum
Side View/Vue de côté
45°
45°
3/4" NPT Pipe/Tuyau
90° Pipe Elbow (Not Included)/
Coude á 90° (Non Inclus)
Proposition 65 Label
Description Part Number
Logo Label 91013202 Rating Plate Label 91010401 Gas Connection Label 91018124 Lighting Instruction Plate Label 91029602 Proposition 65 Label 91070016

FIGURE 1: Top and Bottom Panel Label Placement

2
Page 9

FIGURE 2: Side Panel Label Placement

Vent Length Label
Control Side Panel
Side Panel
Control Side Panel (Inside)
Wiring Label
Clearances to Combustibles Label
Description Part Number
Clearances to Combustibles Label 91013407 Wiring Label 91013302 Vent Length Label 91039500
SECTION 1: HEATER S AFETY
3
Page 10
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
CAUTION
Product Damage Hazard
Do not use heater in area containing corrosive chemicals.
Refer to appropriate Material Safety Data Sheets (MSDS).
Failure to follow these instructions can result in product damage.

SECTION 2: INSTALLER RESPONSIBILITY

The installer is responsible for the following:
• To install the heater, as well as the gas and elec­trical supplies, in accordance with applicable specifications and codes. Roberts-Gordon recom­mends the installer contact a local building inspector or Fire Marshal for guidance.
• To use the information given in a layout drawing and in the manual together with the cited codes and regulations to perform the installation.
• To install the heater in accordance with the clearances to combustibles.
• To furnish all needed materials not furnished as standard equipment.
• To plan location of supports.
• To provide access to burners for servicing on all sides for burner removal.
• To provide the owner with a copy of this installa­tion, operation and service manual.
• To never use heater as support for a ladder or
other access equipment and never hang or suspend anything from heater.
• To ensure there is adequate air circulation arou
the heater and to supply air for combustion, venti- lation and distribution in accordance with local codes.
• To safely and adequately install heater using
materials with a minimal working load of 75 lbs (33 kg).
• To ensure the heater is placed in a approved
application.

2.1 Wall Tag

A laminated wall tag is available for the heater as a permanent reminder of the safety instructions and the importance of the required clearances to combustibles. Please contact Roberts-Gordon or your ROBERTS GORDON
®
independent distributor to obtain the wall tag. Affix the tag by peeling off the backing of the adhesive strips on the rear surface and position the tag on a wall near the heater (e.g. thermostat or ROBERTS GORDON
®
Controller).
A copy of the wall tag (P/N 91037912) is illustrated on the back cover. For an immediate solution, you may affix this copy on the wall near the heater.
Know your model number and installed configuration. Model number and installed configuration are found on the burner and in the Installation, Operation and Service Manual. See Page 6, Figure 3 through Page
4
9, Figure 12. Write the proper clearance dimensions in permanent ink according to your model number and configuration in the open spaces on the tag.

2.2 Corrosive Chemicals

Roberts-Gordon cannot be responsible for ensuring that all appropriate safety measures are undertaken prior to installation; this is entirely the responsibility of the installer. It is essential that the contractor, the
nd
sub-contractor, or the owner identifies the presence of combustible materials, corrosive chemicals or halogenated hydrocarbons* anywhere in the premises.
* Halogenated Hydrocarbons are a family of chemi­cal compounds characterized by the presence of halogen elements (fluorine, chlorine, bromine, etc.). These compounds are frequently used in refriger­ants, cleaning agents, solvents, etc. If these com­pounds enter the air supply of the burner, the life span of the heater components will be greatly reduced. An outside air supply must be provided to the burners whenever the presence of these com­pounds is suspected. Warranty will be invalid if the heater is exposed to halogenated hydrocarbons.

2.3 National Standards and Applicable Codes

All appliances must be installed in accordance with the latest revision of the applicable standards and national codes. This refers also to the electric, gas and venting installation. Note: Additional standards for installations in P
ublic Garages, Aircraft Hangars,
etc. may be applicable.
Page 11

SECTION 3: CLEARANCES TO COMBUSTIBLES

WARNING
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clearances to combustibles away from heater.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.

3.1 Required Clearances to Combustibles

Clearances are the required distances that combustible objects must be away from the heater to prevent serious fire hazards. Combustibles are materials, that may catch on fire and include common items such as wood, paper, rubber, fabric, etc.
Maintain clearances to combustibles at all times for safety.
Clearances for all heater models are located on the burner of the heater and on Page 6, Figure 3 through Page 9, Figure 12 in this manual. Check the clearances on each burner for the model heater being installed to make sure the product is suitable for your application and the clearances are maintained. Read and follow the safety guidelines below:
• Keep gasoline or other combustible materials including flammable objects, liquids, dust or vapors away from this heater or any other appli- ance.
• The stated clearances to combustibles represent a surface temperature of 90° F (50° C) above room temperature. Building materials with a low heat tolerance (su vas, triply, etc.) may be subject to degradation at lower temperatures. It is the installer’s responsibil- ity to assure that adjacent materials are protected from degradation.
• Maintain clearances from heat sensitive equipment and workstations.
• Maintain clearances from vehicles parked below the heater.
• Maintain clearances from swinging and overhead doors, overhead cranes, vehicle lifts, partitions, storage racks, hoists, building construction, etc.
• In locations used for the storage of combustible materials, signs must be posted to specify the maximum permissible stacking height to maintain required clearances from the heater to the com­bustibles. Signs must be posted adjacent to the heater thermostat. In the absence of a thermo­stat, signs must be posted in a conspicuous location.
• Consult local Fire Marshal, Fire Insurance Carrier or other authorities for approval of proposed installation when there is a possibility of exposure to combustible airborne materials or vapors.
• Hang heater in accordance to the minimum sus­pension requirements
ch as plastics, vinyl siding, can-
on Page 17, Figure 14.
SECTION 3: CLEARANCES TO COMBUSTIBLES
• If the radiant tubes must pass through the building structure, be sure that adequate sleeving and fire stop is installed to prevent scorching and/or fire hazard.
5
Page 12
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
A
C
D
B
A
C
D
B
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the burner and burner tube connect.
FIGURE 3: STANDARD REFLECTOR
Model ABCDABCD
TF-120 6 35 63 35 16 89 161 89
TF-160 6 386638169716897
TF-200 6 40 71 40 16 10 2 181 102
TF-250 6 46 77 46 16 117 196 117
TF-300 6 50 80 50 16 127 204 127
TF-350 8 52 82 52 21 133 209 133
TF-380 8 52 82 52 21 133 209 133
FIGURE 4: ONE SIDE REFLECTOR
Model ABCDABCD
TF-120 6 9 63 47 16 23 161 120
TF-160 6 9 70 54 16 23 178 138
TF-200 6 9 77 59 16 23 196 150
TF-250 6 9 83 65 16 23 211 166
TF-300 6 9 86 69 16 23 219 176
TF-350 8 9 88 73 21 23 224 186
TF-380 8 9 88 73 21 23 224 186
(inches) (centimeters)
(inches) (centimeters)
FIGURE 5: TWO SIDE REFLECTORS
(inches) (centimeters)
Model ABCDABCD
TF-120 6 23 66 23 16 59 168 59
TF-160 6 25 72 25 16 64 183 64
TF-200 6 27 78 27 16 69 199 69
TF-250 6 328432168221482
TF-300 6 35 88 35 16 89 224 89
TF-350 8 40914021102232102
TF-380 8 40 91 40 21 10 2 232 102
6
Page 13
SECTION 3: CLEARANCES TO COMBUSTIBLES
A
C
D
B
B
C
D
A
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the burner and burner tube connect.
FIGURE 6: 45
° TILT REFLECTOR
Model ABCDABCD
TF-120 8 8 60 54 21 21 153 138
TF-160 8 8 66 60 21 21 168 153
TF-200 10 8 74 64 26 21 188 163
TF-250 10 8 78692621199176
TF-300 12 8 84 74 31 21 214 188
TF-350 12 8 85793121216201
TF-380 12 8 85 79 31 21 216 201
FIGURE 7: U-TUBE, STANDARD REFLECTOR
Model ABCDABCD
TF-120 6 35 63 30 16 89 161 77
TF-160 6 386937169717694
TF-200 6 40 76 39 16 102 194 100
TF-250 6 46794316117201110
TF-300 6 50 84 47 16 127 214 120
TF-350 8 54875121138221130
TF-380 8 54 87 51 21 138 221 130
(inches) (centimeters)
(inches) (centimeters)
FIGURE 8: U-TUBE, 45°
(inches) (centimeters)
Model ABCDABCD
TF-120 8 8 60 42 21 21 153 107
TF-160 8 8 66 46 21 21 168 117
TF-200 8 8 74 52 21 21 188 133
TF-250 8 8 78 61 21 21 199 155
TF-300 8 8 84 66 21 21 214 168
TF-350 8 8 85 70 21 21 216 178
TF-380 8 8 85 70 21 21 216 178
7
Page 14
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
A
C
D
B
A
C
D
B
A
C
D
B
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the burner and burner tube connect.
FIGURE 9: U-TUBE, OPPOSITE 45
° REFLECTOR
(inches) (centimeters)
Model ABCDABCD
TF-120 8 54 60 22 21 138 153 56
TF-160 8 6066222115316856
TF-200 10 64 74 22 26 163 188 56
TF-250 10 70 78 22 26 178 199 56
TF-300 12 74 84 22 31 188 214 56
TF-350 12 76 85 22 31 194 216 56
TF-380 12 76 85 22 31 194 216 56
FIGURE 10: 2-FOOT DECO GRILLE AND PROTECTIVE GRILLE
(inches) (centimeters)
Model ABCDABCD
TF-120 6 35 63 35 16 89 161 89
TF-160 6 38 66 38 16 97 168 97
TF-200 6 40 71 40 16 102 181 102
TF-250 6 46 77 46 16 117 196 117
TF-300 6 50 80 50 16 127 204 127
TF-350 8 52825221133209133
TF-380 8 52 82 52 21 133 209 133
FIGURE 11: LOWER CLEARANCE SHIELD*
(inches) (centimeters)
Model ABCDABCD
TF-120 6 39 33 39 16 100 84 100
TF-160 6 40 38 40 16 102 97 102
TF-200 6 50 44 50 16 127 11 2 127
TF-250 6 54485416138122138
TF-300 6 55 50 55 16 140 127 140
TF-350**
TF-380**
Unapproved Unapproved
Unapproved Unapproved
*When installed in the first 10’ (3 m) on each side of the burner. **Roberts-Gordon prohibits the installation of this heater for all unapproved applications.
8
Page 15
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
Radiant Tubes
Vent Pipes
Unvented
Vented
A
E
F
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the burner and burner tube connect.
FIGURE 12: VENTING
SECTION 3: CLEARANCES TO COMBUSTIBLES
(inches) (centimeters)
Model A E F A E F
TF-120 14 18 18 36 46 46
TF-160 20 24 18 51 61 46
TF-200 20 24 18 51 61 46
TF-250 20 24 18 51 61 46
TF-300 20 30 18 51 77 46
TF-350 20 30 18 51 77 46
TF-380 20 30 18 51 77 46
9
Page 16
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES

4.1 Gas Codes

The type of gas appearing on the nameplate must be the type of gas used. Installation must comply with national and local codes and requirements of the local gas company.
United States: Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest revision.
Canada: Refer to Natural Gas and Propane Installation Code CSA B149.1 - latest revision.

4.2 Aircraft Hangars

Installation in aircraft hangars must be in accordance with the following codes:
United States: Refer to Standard for Aircraft Hangars, NFPA 409 - latest revision.
Canada: Refer to Natural Gas and Propane Installation Code CSA B149.1 - latest revision.
In aircraft storage and servicing areas, heaters shall be installed at least 10' (3 m) above the upper surface of wings or of engine enclosures of the highest aircraft which may be housed in the hangar. The measurement shall be made from the wing or engine enclosure (whichever is higher from the floor) to the bottom of the heater.
• In shops, offices and other sections of aircraft hangars communicating with aircraft storage or servicing areas, heaters shall be installed not less than 8' (2.4 m) above the floor.
• Suspended or elevated heaters shall be so located in all spaces of aircraft hangars that they shall not be subject to injury by aircraft, cranes, movable scaffolding or other objects. Provisions shall be made to assure accessibility to suspended heaters for recurrent maintenance purposes.

4.3 Public Garages

Installation in garages must be in accordance with the following codes:
United States: Refer to Standard for Parking Structures NFPA 88A - latest revision or the Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision. Canada: Refer to Natural Gas and Propane Installation Code CSA B149.1 - latest revision.
• Heaters must not be installed less than 8' (2.4 m) above the floor. Minimum clearances to combustibles must be maintained from vehicles parked below the heater.
• When installed over hoists, minimum clearances to combustibles must be maintained from the upper most point of objects on the hoist.

4.4 Electrical

The heater must be electrically grounded in accordance with the following codes:
United States: Refer to National Electrical Code NFPA 70 - latest revision. Wiring must conform to the most current National Electrical Code
®
, local
ordinances and any special diagrams furnished.
Canada: Refer to Canadian Electrical Code, CSA C22.1 Part 1 - latest revision.

4.5 Venting

The venting must be installed in accordance with the requirements within this manual and the following codes:
United States: Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest revision.
Canada: Refer to Natural Gas and Propane Installation Code CSA B149.1 - latest revision.
®
,
10

4.6 High Altitude

These heaters are approved for installations up to 2000' (610 m)(US), 4500' (1370 m)(Canada) without modification. Consult factory if US installation is above 2000' (610 m) or Canadian installation is above 4500' (1370 m).
Page 17

SECTION 5: MAJOR COMPONENTS

Burner with Tube Gasket
Must be installed with the
flame observation
window facing down.
Reflector (Aluminum or Stainless Steel)
Alternate overlap as shown on overview and on Page 19, Figure 16. Minimum overlap is 6" (16 cm).
Tube and Reflector Hanger with Clamp Package
Position this hanger no more than 4" (10 cm) away from the burner.
Coupling Assembly with Lock
Reflector End Cap
Punch out center section to accommodate tube.
Tube and Reflector Hanger
Suspend system from these hangers.
Flex Gas Line with Shut Off Cock
Tube
Hot rolled or heat treated aluminized tube Supplied in 10' (3 m) lengths.
Burner Tube
Supplied in 10
'
(3 m) lengths. Burner tube is always the first tube after the burner.
Reflector Support Strap & Wire Form
Turbulator
Turbulator must be installed in the last standard section of tube. Turbulator is not required on the TF-250/ 300/350/380. For installation see Page 24, Step 7.5.
Flexible Boot
Flexible boot is used to connect the last tube to the vent.
Vent Sleeve
Vent sleeve installed inside flexible boot.

FIGURE 13: Major Component Descriptions

SECTION 5: MAJOR COMPONENTS
11
Page 18
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

5.1 Standard Parts List

Table 1: Contents of Burner Carton

Part No. Description TF-120 TF-160 TF-200 TF-250 TF-300 TF-350 TF-380

090XXXXX Burner Assembly (Rate and Fuel Varies) 1111111
02568200 Gasket (Burner to Burner Tube) 1 1 1 1 1 1 1
190100NA Installation, Operation and Service Manual 1 1 1 1 1 1 1
94273914 Hex Head Bolts 5/16-18 Rolok 8 8 8 8 8 8 8
96411600 Split Lock washer 8888888
*91412204 Flexible Stainless Steel Gas Hose - 3/4" NPT (US Models Only)1111111
03051503 Turbulator Adapter 2 2 2 - - - -
03051504
Turbulator 2.5' (76 cm) Aluminized Steel
884- -- -
91412800 Flexible Boot 2 2 2 2 2 2 2
91901300 Boot Clamp 4 4 4 4 4 4 4
09080000 Vent Sleeve 2 2 2 2 2 2 2
*Canadian Models: Rubber (Type 1) Gas Hoses available as an accessory. See Page 44, Section 10.
Table 2: Contents of Core and Extension Packages

Core Packages Extension Packages

Hot Rolled

with

Aluminum

Reflector

Part No. Description

91409300
91409408
03051101
03051601
Tube, Hot Rolled Steel, 10
'
Tube, HT Aluminized, 10' (3m)
Burner Tube, ALUMI-THERM
Burner Tube, HT ALUMI-THERM

(3m)

®
Steel, 10' (3m)
®
Steel, 10' (3m)
'
30
20

(6m)

(9m)

123--- - - -1234--------
- - - 123 12 3 - - - -12341234
-11-11-11------------
1- - 1--1- - ------------
01312700 Coupling Assembly 12 3 123 12 3 123412341234
02750303
Standard Reflector, 8
'
(3.5m)
34 6 346 - - - 23462346- - - -
'

(12m)

40
'
Aluminized

with

Aluminum

Reflector

20
'
30
'

(9m)

40

(12m)

(6m)

Aluminized with Stain-
less Steel
Reflector
'
20
'

(6m)

30

(9m)

Hot Rolled

with
Aluminum
Aluminized with
Aluminum
Reflector
Aluminized with
Stainless Steel
Reflector
Reflector
'
40
'
10
'
20
'
30
'
40
'
10
'
20
'
30
'
40
'
10
'
20
'
30
'

(12m)

(3m)

(6m)

(9m)

(12m

(3m)

(6m)

(9m)

(12m

(3m)

(6m)

(9m)

40

(12m

'
02750800End Cap 222222-- -------------
027503SS Stainless Steel Reflector, 8 (3.5m) -- - ---346--------2346
027508SS Stainless Steel End Cap -- --- -222------------
03090100 Tube and Reflector Hanger 3 4 5 3 4 5 3 4 5 1 2 3 4 1 2 3 4 1 2 3 4
91907302S-Hook 681068106810246824682468
03050010 Reflector Support Package
23 5 235 45 7 234623462346
(Strap, Wire Form, Screws)
91107720 U-Clip Package 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
90502700 Vent Adapter (Not required for TF Models) 111111111------------
01318901Tube Clamp Package 111111222------------

Part Number

CP20HRS
CP30HRS
CP40HRS
CP20ALUM
CP30ALUM
CP40ALUM
CP20ALUMSS
CP30ALUMSS
EXP10HRS
EXP20HRS
EXP30HRS
EXP40HRS
EXP10ALUM
EXP20ALUM
EXP30ALUM
CP40ALUMSS
EXP40ALUM
EXP10ALUMSS
EXP20ALUMSS
EXP30ALUMSS
12
EXP40ALUMSS
Page 19
SECTION 5: MAJOR COMPONENTS
Table 3: Component Package Guide

Tubing Length Each Side Core Packages (2 Required)

Model Minimum Hot Rolled with

Aluminum Reflector
TF-120 20' (6 m) CP20HRS CP20ALUM CP20ALUMSS
TF-160 20' (6 m) CP20HRS CP20ALUM CP20ALUMSS
TF-200 30' (9 m) CP30HRS CP30ALUM CP30ALUMSS
TF-250 40' (12 m) CP40HRS CP40ALUM CP40ALUMSS
TF-300 50' (15 m) CP30HRS + EXP20HRS CP30ALUM + EXP20ALUM CP30ALUMSS + EXP20ALUMSS
TF-350 50' (15 m) CP30HRS + EXP20HRS CP30ALUM + EXP20ALUM CP30ALUMSS + EXP20ALUMSS
TF-380 60' (18 m) CP30HRS + EXP30HRS CP30ALUM + EXP30ALUM CP30ALUMSS + EXP30ALUMSS
Aluminized with
Aluminum Reflector
Aluminized with
Stainless Steel Reflector
Additional tubing length may be added to heater. Tubing must be heat-treated, aluminized or porcelain coated. Any additional tubing lengths are considered as vent length for length determination. Maximum venting length for minimum heater length is 45' (13.7 m) total, or 22.5' (7 m) on each tube.
13
Page 20
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
10' Typ.
(3 m)
Burner
Tube
Common Vent
90° Elbow

SECTION 6: SUGGESTED LAYOUTS

The following are suggested layouts for the heater. These layouts are effective in maximizing the heat pattern and overall performance of the heater. All heaters can be common vented or individually vented (See Page 37, Section 9) depending on the building requirements. These are only suggested layouts. The heater can be designed in various configurations provided they are in the guidelines of this manual. When designing a U- Tube or Elbow configuration, the following rules must be adhered to:

• A minimum of 10' (3 m) of tubing on TF-120/160 and/or a minimum of 15' (4.5 m) of tubing on the TF-200/250/300/350/380 is required between the burner and the Elbow or U Tube.

• The design and installation must adhere to the rules and guidelines located in this manual (See Page 16, Section 7 and Page 37, Section 9).

• Review
venting options before selecting a layout.
6.1 TF-380 - 4 Elbow Design (Common Vent)
6.2 TF-350 - 4 Elbow Design (Common Vent)
6.3 TF-300 - Double "U" Design (Common Vent)
14
Page 21

6.4 TF-160 - Single Elbow Design (Individual Vents)

Burner
Tube
Individual Vent
90° Elbow
10' Typ.
(3 m)

6.5 TF-160 - Double "L" Design (Individual Vents)

SECTION 6: SUGGESTED L AYOUTS

6.6 TF-250 - Combination "L" and "U" Design (Individual Vents)

15
Page 22
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
WARNING
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
Failure to follow these instructions can result in injury.

SECTION 7: HEATER INSTALLATION

WARNING
Severe Injury Hazard
Secure burner to burner tube with bolts and lockwashers.
Hang heater with materials with a minimum working load of 75 lbs (33 kg).
Failure to follow these instructions can result in death, injury or property damage.
To ensure your safety, and comply with the terms of the warranty, all units must be installed in accordance with these instructions.
The gas or the electrical supply lines must not be used to support the heater. Do not locate the gas or electrical supply lines directly over the path of the flue products from the heater. The heater must be installed in a location that is readily accessible for servicing. The heaters must be installed in accordance with clearances to combustibles as indicated on the rating plate and in this instruction manual. The minimum and maximum gas inlet pressures must be maintained as indicated on the rating plate. Typical installation configurations are shown on Page 17, Figure 14. Expansion and contraction of the tube dictates that the minimum suspension lengths must be maintained. See table on Page 17, Figure 14.
16
Page 23

FIGURE 14: Critical Hanger Placement

Hanger
Side View
Must Be Within 4" (10 cm) Front View
S-hooks
Reflector
Hanger
45° Angle
* Allows for thermal expansion of system
Typical Suspension Details
Rod 3/8"
Beam Clamp
Concrete Beam
Wood Beam
Washers
Locknut
Screw Hook
3/8"
24" min.*
(61 cm)
X*
Anchor
S-hooks
Chain Size
3/16"
Minimum
Turnbuckle
Not Included
Description Part Number
S-Hook 91907302 Tube/Reflector Hanger 03090100
Tot a l St rai ght Length (both sides) or Length from U-Tube to U-Tube
in a Double "U" Layout
Typical Expansion
Each Side
Minimum “X” Length
0’ - 50’ ±1” (3 cm) 12” (31 cm) 51’ - 60’ ±2” (5 cm) 18” (46 cm) 61’ - 80’ ±3” (8 cm) 24” (61 cm)
81’ - 100’ ±4” (10 cm) 30" (76 cm)
101’ - 120’ ±5” (13 cm) 36" (91 cm) 121’ - 140’ ±6” (15 cm) 42" (107 cm) 141’ - 160’ ±7” (18 cm) 48" (122 cm)
If the installation requires a shorter suspension length than the minimum listed, the suspension length may be reduced by 6" (16 cm). In this case, tube clamps MUST be used at the two farthest hangers on each side of the burner. See Page 18, Figure 15.
SECTION 7: HEATER I NSTALLATION
17
Page 24
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Flat
Washer
Nut
(Torque 120 in/lb
13.56 Nm)
Tube Clamp
Bolt

FIGURE 15: Linear Heater Assembly Overview

For shorter than minimum
suspension lengths,
(purchased separately) must be
tube clamp packages
used at the two farthest hangers
on each side of the burner.
U-Clips
Reflector Support
Flexible Boot
Vent Sleeve
Tur bulator
(With Select Models)
18
Burner Tube
Tube and Reflector Hanger
Burner
Reflector
Tube Clamp Package
Burner Tube
Coupling
Reflector End Cap
Tube
Page 25

FIGURE 16: Linear Heater Layout Overview

Burner
Reflector
Tube
Tube/Reflector Hanger
Coupling Assembly
LEGEND
a = 14" (36 cm) reflector width (not shown)
b = 2" (5 cm) end cap to burner
c = 2" (5 cm) end cap to hanger
d = 7'6" (229 cm) distance first hanger
e = 10' (305 cm) distance between hangers
f = 9.5" (24 cm) burner height
g = 23.5" (60 cm) burner length
f
c
b
de
e
30' (9 m) Tube Length (Each Side)
g
f
c
b
de
e e
40' (12 m) Tube Length (Each Side)
g
f
g
c
b
de
20' (6 m) Tube Length (Each Side)
c
b
de
e e e
50' (15 m) Tube Length (Each Side)
f
g
Linear layouts showing one side. Use same measurements for the other side.
SECTION 7: HEATER I NSTALLATION
19
Page 26
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
c
b
de
e e e e
60' (18 m) Tube Length (Each Side)
f
g
b
c
de
e e e e e
70' (21 m) Tube Length (Each Side)
b
f
g
b
c
de
e e e e e
b
80' (24 m) Tube Length (Each Side)
f
g

FIGURE 17: Linear Heater Layout Overview (Continued)

20
Page 27

Step 7.1 Burner Tube Installation

7' 6" ± 1'
(229 cm ± 25 cm)
S-hook
Burner Tube
Hanger
29"± 2"
(73 cm ± 5 cm)
NOTE:
Tubing requires a downward slope of 1/2" (13 mm) per 20' (6 m) away from burner.
Weld seam must be to the bottom of the tube.
Offset mounting hole must be to the top.
Description Part Number
Burner Tube 03051XXX S-Hook 91907302 Tube/Reflector Hanger 03090100
Lock Washer
Gasket
Burner
Bolt
Description Part Number
Bolt 94273914 Lock Washer 96411600 Gasket 02568200 Burner 090XXXXX
SECTION 7: HEATER I NSTALLATION

Step 7.2 Burner Installation

21
Page 28
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Bolt
Flat Washer
Tube Clamp
Nut (Torque 120 in/lb
13.56 Nm)
Description Part Number Tub e C lamp Pack age01318901
Tube Clamp 01396801 Bolt 97113940 Flat Washer 95211600 Nut 92113900
Tube
Tube
Orient coupling so that
the impact block is in the
2:00 or 10:00 oclock
positions.
Closed
Open
Tab
3" (8 cm) to 4" (10 cm)
Slide Bar/Coupling Lock
Coupling
Wide End
Coupling
Tube
Slide Bar/Coupling Lock
A
Close coupling with tab.
B
Start Slide bar/Coupling Lock onto coupling.
C
Insert tubes into coupling.
D
Tighten coupling to join tubes.
Description Part Number
Coupling 01329600 Slide bar/Coupling Lock 01329700 Tube 91409XXX

Step 7.3 Tube Clamp Package Installation

Step 7.4 Coupling and Tube Assembly

22
Page 29

Step 7.4.1 Coupling and Tube Assembly (Continued)

Incorrect slide bar
position
Correct slide bar
dimensions
± 2" (5 cm)
Drive slide bar until tight. End of slide bar should be within tolerance listed below.
• Repeat Step 7.4 A - D until all tubes are assembled. See Page 23, Section 7.4.2.
Tighten slide bar as shown below
10' Typ. ± 1'
(254 cm Typ ± 25 cm)
7' 6" ± 1'
(229 cm ± 25 cm)
Model
Minimum Tube Length
Per Side
TF-120 20’ (6 m) TF-160 20’ (6 m) TF-200 30’ (9 m) TF-250 40’ (12 m) TF-300 50’ (15 m) TF-350 50’ (15 m) TF-380 60’ (18 m)
See recommended venting lengths on Page 37, Section 9, when using maximum tube lengths.
SECTION 7: HEATER I NSTALLATION

Step 7.4.2 Coupling and Tube Assembly (Continued)

23
Page 30
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
T
w
i
s
t
Pull String
Tab
Fold tab around outside of tube nearest to the vent to hold turbulator in place.
Turbulator Section
Turbulator Adapter
Description Part Number
Turbulator Adapter 03051503 Turbulator Section 03051504 Tube 91409XXX
Turbulator must be installed in the last standard section of tube.
Turbulator Installation
Model Tube Section
TF-120 2nd 10' Section Each Side TF-160 2nd 10' Section Each Side TF-200 3rd 10' Section Each Side TF-250 N/A TF-300 N/A TF-350 N/A TF-380 N/A
Model Each Side
TF-120 & TF-160
1 - 03051503 4 - 03051504
TF-200
1 - 03051503 2 - 03051504

Step 7.5 Turbulator Installation

24
Page 31

7.6 Reflector Installation

WARNING
Fire Hazard
Support reflector with reflector hanger and support strap.
Reflector must not touch tube.
Failure to follow these instructions can result in death, injury or property damage.
Burner
Hanger
Burner Tube
Reflector
Description Part Number
Tube/Reflector Hanger 03090100 Burner Tube 03051XXX Reflector 02750303
NOTE:All tube surfaces must be covered
by a reflector, except for a U-Tube.
SECTION 7: HEATER I NSTALLATION
25
Page 32
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
2. The overlap at the first and second reflector is a slip overlap.
Thereafter, every third reflector joint is a slip overlap. A slip overlap is achieved by either: a.) both reflectors lay inside a hanger.
(No reflector support needed.)
b.) using a reflector support with
loose screws at the reflector overlap.
3. The remaining reflector overlaps require a non-slip overlap connection. To affix the reflectors together in a non-slip overlap either: a.) use reflector support and tight screws. b.) if both reflectors lay inside a hanger, u-clips or
sheet metal screws may be used.
This section of three reflectors joined together must be affixed to the tube with at least one reflector support with tight screws.
Reflector End Cap
U-clips
1. The first reflector after the burner must be affixed in
the middle of the reflector with a reflector support and tight screws.
First Reflector
6"
(16 cm)
Overlap must be a
minimum of
6
" (16 cm).
Loose screws loosened 1/16" (.16 cm) to allow slippage.
2 A
Slip Overlap
Reflector
Support
2 B
Slip Overlap
Reflector
Tight
Screws
3 B
Non-Slip Overlap
U-clip
(2 Clips per Non-slip Overlap Inside a Hanger)
Reflector
3 A
Non-Slip Overlap
Wire Form
Reflector Support
Strap
Tight
Sheet Metal
Screw
Description Part Number Reflector Support Package 03050010
Wire Form 91908004 Reflector Support Strap 03050000
Screw #8 x 3/4 94320812 U-Clip Package 91107720 Reflector End Cap 027508XX

Step 7.6.1 Reflector, U-Clip and Reflector Support Installation

The pictorial drawings of the heater construction in Section 7 are schematic only and provide a general guideline of where hangers, reflector supports and U-clips are to be installed. To ensure proper expansion and contraction movement of the reflectors, a combination of U-clips and reflector supports are used. The positioning of
reflector supports and U-clips depends on the individual installation. Use either pop rivets or sheet metal screws instead of u-clips when installing end caps and joint pieces in areas where impact and high wind may be a factor. The following rules must be observed.
26
Page 33

SECTION 8: OPTIONAL HEATER ACCESSORIES

WARNING
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
Failure to follow these instructions can result in injury.

8.1 U-Tube Configuration

The heaters are approved for optional U-Tube configurations. This installation requires 1 or 2 U­Tube packages depending on configuration desired.
Shown below is an example of a typical 80' (24 m) U­Tube configuration. The U-Tube may be installed in either a standard horizontal position or in an opposite 45° position as shown below. When designing a U- Tube configuration, the following additional rules must be adhered to:
• A minimum of 10' (3 m) on TF-120/160 and a min­imum of 15' (4.5 m) on TF-200/250/300/ 350/380 is required between the burner and the U-Tube.
SECTION 8: OPTIONAL HEATER ACCESSORIES
• The correct turbulator (See Page 24, Step 7.5) must be installed in the last standard section of tube.
• The burner must never be operated in a tilted position.
• When installed in a full 45° position, the burner must be installed on the lower side.
• The heater mu tions. See Page 29, Figure 19.
st be properly supported at all loca-
27
Page 34
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Turbulator
12
12
1
2
U-tube, 45°
12
Vent sleeves and flexible boots not shown.
Reflector
Reflector End Cap
Tube
Reflector Support
Burner Tube
Burner
Tube Clamp Package
U-tube
18" (457 mm)
Center to Center
U-clips
U-tube Support Bracket Assembly
Reflector
End Caps
U-tube, Standard
U-tube, Opposite 45°
Nut Lock Washer Lock Washer Nut
U-bolt
Tight U-bolt
4" (10 cm) U-bolt,
secured to burner tube
with 1/4" (6 mm)
lockwashers and
1/4-20 Hex Nuts
Loose U-bolt
4" (10 cm) U-bolt,
secured to bracket with
1/4" (6 mm) lockwashers
and 1/4-20 hex nuts on
top and bottom to
allow for tube expansion
and contraction
Couplings
Couplings
Description Part Number U-Tube Package 03011000
180° U-Tube 01335901 Tube and Reflector Hanger 03090100 Coupling 01312700 Reflector End Cap (2) 02750800 U-Tube Support Bracket 03020501 4" (10 cm) U-Bolts (2) 90912500
Reflector Support Set 03050010
S-Hook 91907302 Hex Nut 92113000 Lock Washer 96411500

FIGURE 18: U-Tube Heater Assembly Overview

28
Page 35

FIGURE 19: U-Tube Heater Layout Overview

LEGEND
a = 14" (36 cm) reflector width (not shown)
b = 2" (5 cm) end cap to burner
c = 2" (5 cm) end cap to hanger
d = 7'6" (229 cm) distance first hanger
e = 10' (305 cm) distance between hangers
f = 5' (153 cm) distance between last full tube hanger and half tube hanger
g = 17.5" (44 cm) burner length
h = 9.5" (24 cm) burner height
*Requires the last reflector before the u-tube to be cut in half for use on both sides.
**Requires the last tube before the u-tube to be cut in half for use on both sides.
U-tube
Burner
Reflector
Tube 10' (3 m)
Tube/Reflector Hanger
Coupling Assembly
Tube 5' (1.5 m)**
c
b
de
f
50' (15 m) Tube Length* ** (Each Side)
h
g
c
b
de
40' (12 m) Tube Length (Each Side)
h
g
c
b
d
f
30' (9 m) Tube Length**(Each Side)
h
g
c
b
20' (6 m) Tube Length* (Each Side)
e
h
g
U-tube layouts showing one side. Use same measurements for the other side.
SECTION 8: OPTIONAL HEATER ACCESSORIES
29
Page 36
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
c
b
de
e
60' (18 m) Tube Length (Each Side)
h
g
c
b
de
e
f
70' (21 m) Tube Length** (Each Side)
h
g
e
c
b
de
e
80' (24 m) Tube Length** (Each Side)
h
g

FIGURE 20: U-Tube Heater Layout Overview (Continued)

30
Page 37

8.2 Elbow Package Configuration

Tube
90° Elbow
Coupling
Description Part Number Elbow Package 02718702
90° Elbow 01335801 Coupling 01312700 Reflector End Cap 02750800 Reflector Joint Piece 02750900
U-Clip Package 91107720
Minimum Distance Required Between Burner and Elbow
Model
Minimum
Distance
TF-120 10' TF-160 10' TF-200 15' TF-250 15' TF-300 15' TF-350 15' TF-380 15'
Tube
Coupling

Step 8.2.1 Elbow Installation

Step 8.2.2 Elbow Installation

SECTION 8: OPTIONAL HEATER ACCESSORIES

Step 8.2.3 Reflector Joint Installation

31
Page 38
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

Step 8.2.4 Reflector Joint Installation

Step 8.2.5 Reflector Joint Detail

FIGURE 21: Reflector Joint Detail

32
Page 39

8.3 Reflector Side Extension

Reflector Side
Extension Bracket
(2 per Reflector)
Use additional supports
in high air movement
applications.
Tube and Reflector Hanger
ReflectorTube
Reflector Support
Description Part Number Reflector Side Extension Package 02712700
Reflector Side Extension 01368000 Retainer Clips 02751200 Sheet Metal Screws 94118106
Order Separately
Reflector Side Extension 01329910
Retainer Clip (2 per Side)
Cut relief notches for supports and hangers.
Reflector Side Extension
#8 x 3/8 (3.9 x 9.5 mm) Sheet Metal Screw

Step 8.3.1 Bracket Installation

SECTION 8: OPTIONAL HEATER ACCESSORIES

Step 8.3.2 Side Reflector Installation

33
Page 40
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
12"
(30 cm)
Reflector
Lower Clearance Shield
17"
(43 cm)
Washers
Screws
Locknuts
Align Pilot Holes
Description Part Number Lower Clearance Shield Package 01397501
Shield Support Strap 01397500 Lower Clearance Shield 8' 02793000 Locknut #8 92311400 Flat Washer #8 95310800 Screw #8 x 3/8" 93511406
Description Part Number
Aluminium Grille 2’ x 4’ 91407000

8.4 Lower Clearance Shield Installation Step 8.4.1 Shield Support Strap Assembly

8.5 Two-Foot Decorative Grille Installation Step 8.5.1 Grille Installation

34
Page 41

Step 8.5.2 Frame Shield Installation

Description Part Number
Deco Grille Shield 01365900
Distance "A" Extension
Minimum Maximum Part No. Width
2" (4 cm) 6" (15 cm) 01370408 8" (20 cm)
6" (15 cm) 10" (26 cm) 01370412 12" (30 cm)
10" (26 cm) 14" (37 cm) 01370416 16" (40 cm)
Description Part Number
Reflector Side Extension 01370412
SECTION 8: OPTIONAL HEATER ACCESSORIES

Step 8.5.3 Reflector Side Extension Installation for Decorative Grilles

35
Page 42
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Silicone Cap
Grille Finger
Description Part Number
Grille Section 08050001 Grille End Cap 08050002 Silicone Cap 91915951-6P
Bend up 90°.
Pull outward.
Grille
Grille End Cap
A
B
C
D
Grille
Grille
End Cap
Reflector
Final Grille
Section
40"
(101 cm)

8.6 Protective Grille Installation Step 8.6.1 Silicone Cap Installation

Step 8.6.2 Grille End Cap Installation

Step 8.6.3 Grille Installation

36
Page 43
SECTION 9: VENTING
WARNING
Carbon Monoxide Hazard
Heaters installed unvented must be interlocked with sufficient building exhaust.
Heaters must be installed according to the installation manual.
Failure to follow these instructions can result in death or injury.
WARNING
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
Failure to follow these instructions can result in injury.

SECTION 9: VENTING

9.1 Venting Requirements

This heater must be vented in accordance with the rules contained in this manual and with the following national codes and any state, provincial or local codes which may apply:
United States: Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest revision.
Canada: Refer to Natural Gas and Propane Installation Code CSA B149.1 - latest revision.
Any portion of vent pipe passing through a combustible wall or roof must be dual insulated (Type B) vent pipe and have an approved thimble to conform with the above listed codes.
Vent pipe must be sloped downward away from the burner, 1/2" (1 cm) for every 20' (6 m).
Both sides of the TF-Series heater may be individually vented 4" (10 cm) or common vented 6" (15 cm).
The heater may also be installed unvented in certain
circumstances according to building ventilation codes. Refer to the above codes for further information. Unvented operation also requires compliance with the clearances to combustibles given on Page 9, Figure 12.
The bottom of the vent or air intake terminal shall not be located less than 1' (0.3 m) above grade level.
The vent shall not terminate less than 7' (2.1 m) above grade where located adjacent to public walkways.
Vent terminal must be installed at a height sufficient to prevent blockage by snow and building materials protected from degradation by flue gases.
Vent must be at least 6' (2 m) from the combustion air opening of this unit, or any other appliance. Secure all joints with #8 x 3/8 sheet metal screws. Seal all joints with high temperature silicone sealant. Vent terminal must be beyond any combustible overhang.

9.1.1 United States Requirements

Vent must terminate at least 3' (0.9 m) above any forced air inlet located w
Vent must terminate at least 4' (1.2 m) below, 4' (1.2 m) horizontally from, or 1' (0.3 m) above any door, operable window, or gravity air inlet into any building.

9.1.2 Canadian Requirements

The vent shall not terminate within 6' (1.8 m) of a mechanical air supply inlet to any building.
The vent shall not terminate within 3' (0.9 m) of a window or door that can be opened in any building, any non-mechanical air supply inlet to any building, or of the combustion air inlet of any other appliance.

9.2 Unvented Operation

Sufficient ventilation must be provided in the amount of 4 cfm per 1000 BTU/hr firing rate (United States); 3 cfm per 1000 BTU/hr firing rate (Canada).
Use of optional outside combustion air is not recommended with unvented heaters. If exhaust fans are used to supply ventilation air, an interlock switch must be used to prevent the heater from coming on when the fans are off. This may be done using a press

9.3 Horizontal Venting

In noncombustible walls only, vent terminal (P/N 02537801-1P) may be used.
For 4" (10 cm) vents in either combustible or noncombustible walls, use Tjernlund VH1-4 (P/N
90502100) or equivalent, insulated vent terminal. Follow the manufacturer's instructions for proper installation.
For 6" (15 cm) common vents in either combustible or noncombustible walls, use Tjernlund VH1-6 (P/N
90502101) or equivalent, insulated vent terminal. Follow the manufacturer's instructions for proper installation.
ithin 10' (3.1 m).
ure switch.
37
Page 44
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Burner
Tube
Flexible
Boot
Vent Terminal
Combustible or
Non-Combustible
Wall
Single Wall
Vent Pipe
Metalbestos Cap
4" (10 cm) Single Wall Pipe
Vent Terminal
18" (46 cm)
Min.
Non-Combustible
Wall
Approved Wall Thimble
Install with boot
extended
4" (10 cm) Single Wall Pipe
SIDE VIEW
Description Part Number
Flexible Boot 91412800 Boot Clamp 91901300 Vent Terminal (Comb. Wall) 90502100 Vent Terminal 02537801-1P Vent Sleeve 09080000

9.4 Vertical Venting

For 4" (10 cm), an approved vent cap (P/N 90502300) must be used. For 6" (15 cm) common vent, an approved vent cap (P/N 90502302) must be used. A vent shall not extend less than 2' (0.6m) above the highest point where it passes through a flat roof of a building.

9.5 Unvented Operation Tube Termination

Turndown type vent terminal with a screen must be installed at the exhaust end of the tube. Vent terminal design shall not incorporate backdraft flap.

FIGURE 22: Tube Termination

9.7 Horizontal Ventilation 4" (10 cm) Pipe

9.6 Length Requirements

The maximum vent length, where both tubes are vented together is 45’ (13.7 m) of 6" (15 cm) diameter
duct. The maximum vent length, where both tubes are vented individually is 45’ (13.7 m) of 4" (11 cm) diameter duct, or 22.5’ (7 m) on each tube.
The maximum outside air s
upply duct length allowed is 45’ (13.7 m) of either 4" (10 cm) or 5" (13 cm) diameter, however the maximum length depends on the venting arrangement used.
The total vent length, plus outside air duct length, plus any extensions to minimum heat exchanger lengths, cannot exceed 65' (19.8 m).
Vent length should be limited to less than 20' (6 m). If using vent lengths greater than 20' (6 m), condensation will form in the vent pipe. Insulation and additional sealing measures (high temperature silicone at all seams) are required. Optional heat exchanger lengths are considered as vent length for length determination.
Subtract 15' (4.6 m) of maximum allowed vent or duct length per vent elbow if more than two are used.
38
Page 45

9.8 Vertical Ventilation 4" (10 cm) Pipe

Burner
Tube
Flexible
Boot
Single Wall
Vent Pipe
(Type 'B' vent pipe
must be used for
pipe exiting building)
Flexible Boot
Boot Clamp
Secure all joints with (3) #8 x 3/8 Sheet Metal Screws
Roof
Vent Cap
4" (10cm)
SIDE VIEW
Description Part Number
Vent Cap 4" (10 cm) 90502300
Tube
Vent
Boot Clamp
Flexible Boot
Vent Sleeve
Bead
3"
(8 cm)
Expansion
Gap
Flexible Boot Installation
for Single Vent
Boot Clamp
Single Wall
Vent Pipe
Flexible
Boot
Tube
Bead
2" min.
(5 cm)
2"
(5 cm)
3"
(8 cm)
Description Part Number
Rolled Sleeve 09080000 Flexible Boot 4" (10 cm) 91412800 Boot Clamp 4" (10 cm) 91901300
SECTION 9: VENTING

9.9 Flexible Boot Installation (Single Vent)

39
Page 46
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Burner
Tube
Vent Terminal
TOP VIEW
6" (15 cm) Single Wall Pipe
Flexible Boot
*
6" (15 cm) Vent Pipe
Vent Tee
Boot
Clamp
* IMPORTANT
Compress boot on installation to allow at least 2" (5 cm) of movement on each side for thermal expansion of tube away from the tee.
Plan View
Description Part Number
Vent Tee 91916 100 Vent Terminal 6" (15 cm) 90502101
Vent Terminal
6" (15 cm) Single
Wall Pipe
Burner
Tube
Roof
Flexible Boot
6" (15 cm)
Vent Pipe
Vent Tee
Boot Clamp
Plan View
* IMPORTANT
Compress boot on installation to allow at least 2" (5 cm) of movement on each side for thermal expansion of tube away from the tee.
*
Description Part Number
Vent Cap 6" (15 cm) 90502302

9.10 Common Sidewall Venting

9.11 Vertical Ventilation 6" (15 cm) Pipe

40
Page 47

9.12 Flexible Boot Installation (Common Vent)

6" (15 cm)
18" (46 cm)
11" (28 cm)
6" (15 cm)
Tube
8" (20 cm) long Flexible
Boot Compressed
to 6" (15 cm) long
Vent Tee
3.5"
(9 cm)
3"
(8 cm)
3/4" (2 cm)
Rolled Sleeve Installation
for Common Vent
Expansion
Direction
3"
(8 cm)
Description Part Number
Rolled Sleeve 09080000 Flexible Boot 4" (10 cm) 91412800 Boot Clamp 4" (10 cm) 91901300 Vent Tee - 4" Dia. x 4" Dia. x 6" Dia. 91916100
SECTION 9: VENTING
41
Page 48
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Description Part Number
Vent Cap 5" (13 cm) 90502301

9.13 Outside Combustion Air Supply

IMPORTANT: If the building has a slight negative pressure or corrosive contaminants, such as halogenated hydrocarbons, are present in the air, an outside combustion air supply to the heater is required. Seal all combustion air pipe joints.
For TF-120 4" (10 cm) single wall pipe or for TF-160/200/250/300/350/380 5" (13 cm) single wall pipe, PVC pipe, aluminum flex duct, or equivalent may be used for outside air supply.

9.13.2 Vertical Outside Air Supply

Use of optional outside combustion air is not recommended with unvented heaters.
The air supply duct may have to be insulated to prevent condensation on the outer surface. The outside air terminal must not be more than 1' (31 cm) above the vent terminal.

9.13.1 Length Requirements

Follow the constraints listed on Page 38, Section 9.6.
Minimum of
2’ (0.61 m)
42
Page 49

9.13.3 Horizontal Outside Air Supply

Burner
Tube
Secure with (3)
#8 x 3/8 Sheet
Metal Screws
Single Wall
Vent Pipe
Approved
Vent Cap
Description Part Number
Vent Cap 5" (13 cm) 90502301
SECTION 9: VENTING
43
Page 50
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

SECTION 10: GAS PIPING Install the gas hose as shown on Page 45, Figure 23.

The gas hose accommodates expansion of the
WARNING
Fire Hazard
Tighten gas hose fittings to connect gas supply according to Figure 23.
Gas hose can crack when twisted.
Gas hose moves during normal operation.
Use only 36" (91 cm) long connector of 3/4" nominal ID.
Connector supplied with heater for U.S. models (not with Canadian models).
Failure to follow these instructions can result in death, injury or property damage.
WARNING
Explosion Hazard
Leak test all components of gas piping before operation.
heating system and allows for easy installation and service of the burner. A 90° pipe elbow (not supplied) must be installed into the gas valve to ensure proper orientation of the flex gas connector. Before connecting the burners to the supply system, verify that all high pressure testing of the gas piping has been completed.
There is an expansion of the tube with each firing cycle, this will cause the burner to move with respect to the gas line. This can cause a gas leak resulting in an unsafe condition if the gas connection is not made in strict accordance with Figure 23 on Page 45.
Meter and service must be large enough to handle all the burners being installed plus any other connected load. The gas line which feeds the system must be large enough to supply the required gas with a maximum press is not included in the layout drawing, the local gas supplier will usually help in planning the gas piping.
Gas lines must meet applicable codes: United States: The Flexible Stainless Steel Gas Hose (US models) supplied with the heater is certi­fied per the Standard for Connectors for Gas Appli­ances, ANSI Z21.24/CSA 6.10 - latest revision. Canada: The Rubber Type 1 Gas Hose (Canadian models) optional with the heater is certified as being in compliance with the Standard for Elastomeric Composite Hose and Hose Couplings for Conducting Propane and Natural Gas, CAN/CGA 8.1 - Latest revision.
• Check the pipe and tubing ends for leaks before placing heating equipment into ser­vice. When checking for gas leaks, use a soap and water solution; never use an open flame.
ure drop of 1/2" w.c. When gas piping
Gas can leak if piping is not installed properly.
Do not high pressure test gas piping with heater connected.
Failure to follow these instructions can result in death, injury or property damage.
44
Page 51

FIGURE 23: Gas Connection with Flexible Gas Hose

Shut-Off Valve (included with gas hose) must be parallel to burner gas inlet. The 3" (8 cm)
displacement shown is for the cold condition. This displacement may reduce when the system is fired.
CORRECT POSITIONS
Flexible Gas Hose 36" (91 cm) length
3" (8 cm) max. displacement
Side View
Heater Movement
12"
(30 cm)
3/4" NPT Pipe
Horizontal
End View
Vertical
(as shown left)
Alternate positions okay
45° 45°
90° Pipe Elbow (not supplied)
CAUTION
Product Damage Hazard
Hold gas nipple securely with pipe wrench when attaching gas hose.
Failure to follow these instructions can result in product damage.
Description Part Number
3/4" Flexible Stainless Steel Gas Hose (US Models) 91412204 3/4" Rubber Type 1 Gas Hose (Canadian Models) 91412207
INCORRECT POSITIONS (WRONG INSTALLATION)
Heater Movement
Heater Movement
Heater Movement Heater Movement
SECTION 10: GAS PIPING
45
Page 52
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be properly grounded.
Failure to follow these instructions can result in death or electrical shock.
L1
L2
Gnd.
NH
Gnd.
NH
Gnd.
Burners
Additional
Supply Circut
120 V - 60 Hz
Line Voltage Thermostat
Burner 1 Burner 2
Maximum 2 to 8 burners
per thermostat, depending on
thermostat chosen. (See thermostat
manufacturers specifications.)

SECTION 11: WIRING Heaters can be controlled using several methods.

Normally thermostats are used to control the heaters but they can also be controlled by an Energy Management System. Section 11.1 below illustrates the connection for heaters controlled by a line voltage thermostat.
To control multiple heaters on one low voltage thermostat, See Page 47, Section 11.2.
Heaters must be grounded in accordance with applicable codes: United States: refer to National Electrical Code
®
NFPA 70 - latest revision; Canada: refer to Canadian Electrical Code CSA C22.1 Part I ­latest revision.
If any of the original internal wiring must be replaced, it must be replaced with wiring materials having a temperature rating of at least 105° C and 600 V.

11.1 Line Voltage Thermostat Wiring

46
Page 53

11.2 Low Voltage Thermostat and Relay Wiring

SPDT Transformer Relay
Black
Black
FRONT VIEW BACK VIEW
1
COIL COIL
3
2
4
6
5
R C
W G Y
SECTION 11: WIRING
Low Voltage Thermostat
120 V - 60 Hz Supply Circuit
L1
L2
Gnd.
White
Red
N
H
Gnd.
Burner 1 Burner 2
N H
Additional
Burners
Gnd.
Maximum 6 burners per relay. (See thermostat manufacturers specifications.)
47
Page 54
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
TRANSFORMER
WHT
GRN
4
5
BLK
BLK
3
1
WHT
PRESSURE SWITCH
BLU
SWITCH
BLK
DOOR
SPARK 2
ELECTRODE
YEL
BRN
YEL
VALVE
GRN
SPARK 1
MODULE
BLK
ALARM
GND
VALVE
SENSE 1
ALARM
24VAC
VALVE
SENSE 2
GRN
BLK
BLOWER
BLU
BLU
BLK
ELECTRODE
GROUND
POWER
SENSE
SPARK
VALVE
L1 L2
BLOWER
PRESSURE SWITCHES
IGNITION MODULE
GAS VALVE
ELECTRODE
ELECTRODE
120V
24V
GAP GAP
LIGHT

11.3 Internal Wiring

11.4 Ladder Diagram

48
Page 55

11.5 Electrical Connection to the Burner

Conduit Hole
Wire Connector
Burner
Internal Wire Bundle
L1
L2
Gnd.
Connect wires together with suitable approved wire connections.
Green to Gnd. White to L2 Black to L1
Electrical Cord or Flexible Conduit
Green
White
Black
SECTION 11: WIRING
49
Page 56
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Burn Hazard
Allow heater to cool before service.
Tubing may still be hot after operation.
Explosion Hazard
Turn off gas supply to heater before service.
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be connected to a properly grounded electrical source.

SECTION 12: OPERATION AND MAINTENANCE

The heater is equipped with a dual direct spark ignition system.

12.1 Sequence of Operation

1. Turn the thermostat up, the blower motor will energize.

2. When the motor approaches nominal running RPM, the pressure switches will close and acti­vate the ignition module.

3. After a 45 second purge period, the ignition module then opens the gas valve and energizes both spark igniters. The light will be illuminated at any time the gas valve is energized.

4. When both flames are established, the sparking sequence ceases.

5. If both flames are not established during the ignition sequence, the ignition module closes the gas valve and purge begins. The module will try two additional times for ignition with purge between trials. If ignition is not established dur- ing either of these trials, the module will lock out.
6. After lock ou must be re-set by turning down the thermostat (disconnecting power) for five seconds, and rais­ing it again to the desired temperature.

7. When the thermostat is satisfied, all power to the heater is shut off.

12.2 To Shut Off Heater

Set thermostat to lowest setting.
50
t has occurred, the ignition module
Turn OFF electric power to heater. Turn OFF manual gas valve in the heater supply line.

12.3 To Start Heater

Turn gas valve and electric power OFF and wait five minutes for unburned gases to vent from heater. Turn ON main gas valve. Turn ON electric power.
Set thermostat to desired temperature. Burner should light automatically.

12.4 Pre-Season Maintenance and Annual Inspection

To e n s ure your safety and years of trouble-free operation of the heating system, ser inspections must be done by a contractor qualified in the installation and service of gas-fired heating equipment.
Turn off gas and electric supplies before performing service or maintenance. Allow heater to cool before servicing.
Before every heating season, a contractor qualified in the installation and service of gas-fired heating equipment must perform a thorough safety inspection of the heater.
For best performance, the gas, electrical, thermostat connections, tubing, venting, suspensions and overall heater condition should be thoroughly inspected.
NOTE: Gas flow and burner ignition are among the first things that should be inspected. Please see Page 51, Section 12.5 for suggested items to inspect.
vice and annual
Page 57
SECTION 12: OPERATION AND MAINTENANCE

12.5 Maintenance Checklist

Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon LLC and conform to all requirements set forth in the ROBERTS GORDON
®
manuals and all applicable
equipment.
To help facilitate optimum performance and safety,
®
Roberts-Gordon LLC recommends that a qualified contractor conduct, at a minimum, annual inspections of your ROBERTS GORDON
®
and perform service where necessary, using only replacement parts sold and supplied by Roberts­Gordon LLC.
equipment
governmental authorities pertaining to the installation, service and operation and labeling of the
The Vicinity of the Heater Do not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.
See Page 5, Section 3.
Vehicles and Other Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged underneath the reflector, in between the tubes or in the decorative or protective grilles (included with select models).
Immediately remove objects in violation of the clearances to combustibles.
See Page 5, Section 3.
Reflector Support reflector with reflector hanger and support strap.
Reflector must not touch tube.
Make sure there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make sure reflectors are correctly overlapped. See Page 26, Section 7.6.1.
Clean outside surface with a damp cloth.
Vent Pipe Venting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area mu
st be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
See Page 37, Section 9.
Outside Air Inlet Inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the
sealed areas or corrosion.
The area must be free of dirt and dust. Clean and reinstall as required.
Tubes Make sure there are no cracks.
Make sure tubes are connected and suspended securely.
See Page 16, Section 7.
Make sure there is no sagging, bending or distortion. Clean or replace as required.
51
Page 58
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Gas Line Check for gas leaks. See Page 44, Section 10.
Burner Observation Window
Blower Scroll, Wheel and
Make sure it is clean and free of cracks or holes.
Clean and replace as required.
Compressed air or a vacuum cleaner may be used to clean dust and dirt.
Motor
Burner Cup and Orifice Clear of obstructions (even spider webs will cause problems).
Carefully remove any dust and debris from the burner.
Electrodes Replace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrodes. The electrode gap should be 1/8" (3.2 mm).
Thermostat There should be no exposed wire or damage to the thermostat.
See Page 46, Section 11.
Suspension Points Make sure the heater is hanging securely. Look for signs of wear on the chain
or ceiling.
See Page 17, Figure 14.
Decorative and Protective Grille (optional)
The grille must be securely attached.
Check that the side reflector extensions are installed correctly and secured in place if necessary (Decorative grille only).
See Page 34, Section 8.5 and Page 36, Section 8.6
Make sure shield is installed correctly and secured in place if necessary. (Decorative grille only.) See Page 35, Section 8.5.2.
Lower Clearance Shield (optional)
The lower shield must be securely attached. Inspect shield support straps and lower clearance shield anchor points.
Make sure shield is installed correctly and secured in place if necessary.
See Page 34, Section 8.4.
Wall Tag If wall tag is present, make sure it is legible and accurate. Please contact
Roberts-Gordon LLC or your ROBERTS GORDON
®
independent distributor, if
you need a wall tag. See Page 4, Section 2.1.
Safety Labels Product safety signs or labels should be replaced by the product user when
they are no longer legible. Please contact Roberts-Gordon LLC or your ROB­ERTS GORDON
®
independent distributor to obtain replacement signs or
labels. See Page 2, Figure 1 through Page 3, Figure 2.
52
Page 59

SECTION 13: TROUBLESHOOTING

Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clearances to combustibles away from heater.
Some objects will catch fire or explode when placed close to heater.
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, injury or property damage.
Burn Hazard
Allow heater to cool before service.
Tubing may still be hot after operation.
Explosion Hazard
Turn off gas supply to heater before service.
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be properly grounded.
Failure to follow these instructions can result in death or electrical shock.
SECTION 13: TROUBLESHOOTING
53
Page 60
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Check wiring between
the power cord, blower
motor and transformer.
No
Replace ignition module.
Replace pressure switch.
Reconnect transformer
wires. Place a jumper wire
across each pressure switch.
Is there a spark?
Ye s
No
Replace transformer.
Remove the blue and yellow
wires from the transformer.
Is there 24 V at the
transformer secondary?
No
Ye s
Is the voltage
at the transformer black
and white leads 120 V?
Ye s
Repair, replace or tighten
hoses as necessary.
Are the air hoses to the
pressure switches secure
and leak free?
No
Ye s
Carefully reset the
spark gap to 1/8" (3 mm).
Replace igniters and
ignition wires as needed.
Remove
obstruction.
Is the vent pipe or the inlet
of the burner obstructed?
Ye s
No
Are the igniter gaps
set at 1/8" (3 mm)?
Ye s
No
Unplug burner and check
igniters and ignition wires.
Are they damaged?
No
Ye s
Is there spark
at the igniters?
No
Blower bearings may
have failed.
Replace blower.
Replace blower.
Check relay wiring
(if applicable) and wiring
to the burner.
Check thermostat wiring
and replace thermostat if
necessary.
Is the blower
obstructed?
No
Remove
obstruction.
Ye s
Unplug blower. Does
the blower turn freely?
No
Ye s
Is there power (120 V) at
the burner?
Ye s
No
Place a jumper across the
thermostat terminals.
Does the blower turn on?
No
Ye s
Turn up thermostat.
Does the blower turn on?
No
Ye s

13.1 Troubleshooting Flow Chart

54
Page 61
Contact
Roberts-Gordon LLC
at www.rg-inc.com.
Check for obstructions in
orifices and air plates
inside the burner.
Check the thermostat and
check the continuity of
the ground wire.
Does the burner turn off
when the call for heat
ends?
No
Ye s
Replace/correct wires.
Replace ignition module.
Are the wires
connecting the module
and electrodes OK?
Ye s
No
Does the burner
stay on?
No
Ye s
Turn valve ON.
Replace ignition module.
Replace/correct wires.
Replace gas valve.
Is the knob on the gas valve
in the ON position?
Ye s
No
Are the wires connecting
the ignition module OK?
Ye s
Check gas line stop cock.
Contact gas company.
Is there gas outlet
pressure available during
the ignition period?
No
Measure voltage on valve
terminals. Is there 24 V
during ignition time?
Ye s
No
Is the inlet gas pressure
during ignition correct?
(Natural 5.0" min.,
LP should be 12.0")
Ye s
No
Adjust the
valve pressure.
Is the gas outlet pressure
3.5" for Natural Gas
(10.5" for LP)?
Ye s
Purge Lines.
Were the gas lines
purged of air?
No
Ye s
Does the
burner light?
No
Ye s
Ye s
Ye s
No
No
®
TROUBLESHOOT ENDS.
If problems persist, contact
ROBERTS GORDON
Independent Distributor.
Ye s
SECTION 13: TROUBLESHOOTING
55
Page 62
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
0
1
2
3
4
5
6
1
2
3
4
5
6
0
1
2
3
4
5
6
1
2
3
4
5
6
Manometer
Natural Propane
3.5"
10.5"
Control Side View of Heater

13.2 Manifold Gas Pressure Setting

56
Page 63

SECTION 14: REPLACEMENT PARTS

Carbon Monoxide Hazard
WARNING
Use only genuine ROBERTS GORDON® replacement parts per this installation, operation and service manual.
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Explosion Hazard
DANGER
Electrical Shock Hazard
Fire Hazard
Gas Valve
Blower with Screen and Gasket
Burner Cup
Viewer Window
Electrode
Ignition Module
Pressure Switch
Electrode Gasket
Indicator Light
Transformer
Pressu
re
Switch
Air Collar
Blower with
Screen and Gasket
Door Switch
Burner Tube Gasket
SECTION 14: REPLACEMENT PARTS
57
Page 64
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Description
Gas Valve (Natural) Gas Valve Kit (LP) (consists of NG gas valve and spring conversion kit) Gasket:
(160/200/250/300/350/380) (120)
Screen
(160/200/250/300/350/380) (120)
Blower
(160/200/250/300/350/380)
(120) Burner Cup Assembly Mica Window Assembly Electrode Ignition Module Electrode Gasket Indicator Light Transformer Door Switch Air Collar
(160/200/250/300/350/380)
(120) Transition Tube Gasket Pressure Switch:
(120/380)
(160/200)
(250)
(350) 300
Part Number
90033700
90033700K
09060000 03050900
09050000 03050800
90710400-P 90708600-P
03020100
02553203
90427403 90434007 02558501
91316102
90436900K
90436800
08031500
91911700 02568200
90439802K 90439806K 90439808K 90439804K 90439807K
58
Page 65
SECTION 15: GENERAL SPECIFICATIONS
23.5"
(60 cm)
Side View
Reflector
Length "A"
Length "A"
End View
13.75"
(35 cm)
9.5"
(24 cm)
Length “A” Each Side Recommended
Heat Input Rate Minimum Minimum Mounting Height*
Model (Btu/h) X (1000) Linear U-Tube Space Spot
TF-120 120 20' (6 m) 11'6" (4 m) 12' (4 m) 9' (3 m)
TF-160 160 20' (6 m) 11'6" (4 m) 15' (5 m) 11' (3 m)
TF-200 200 30' (9 m) 16'6" (5 m) 15' (5 m) 12' (4 m)
TF-250 250 40' (12 m) 21’ 6" (7 m) 20' (6 m) 15' (5 m)
TF-300 300 50' (15 m) 26'6" (8 m) 20' (6 m) 20' (6 m)
TF-350 350 50' (15 m) 26'6" (8 m) 25' (8 m) 23' (7 m)
TF-380 380 60' (18 m) 31'6" (10 m) 25' (8 m) 23' (7 m)

SECTION 15: GENERAL SPECIFICATIONS

15.1 Material Specifications

15.1.1 Reflectors

.024 Aluminum (Optional .024 Stainless Steel Type 304)

15.2 Heater Specifications

15.2.1 Ignition

Fully automatic, three-try, direct spark, electronic ignition control, 100% safety shut-off.

General Specifications for heaters are as follows:

15.3 Suspension Specifications

Hang heater with materials with a minimum working load of 75 lbs (33 kg). See Page 17, Figure 14.

15.4 Controls Specifications

Time switches, thermostats, etc. can be wired into the electrical supply. External controls supplied as an optional extra.

*See Page 5, Section 3 for clearances to combustibles.

GAS PRESSURE AT MANIFOLD:
Natural Gas: 3.5" wc LP Gas: 10.5" wc
DIMENSIONS:
Vent Connection Size:
4" (10 cm) or 6" (15 cm)
Outside Air Connection Size:
4" (10 cm) or 6" (15 cm)
Refer to figure above for dimensional information.
PIPE CONNECTION:
3/4" NPT
GAS INLET PRESSURE: Natural Gas: 5.0" wc Minimum
16.0" wcMaximum
LP Gas: 12.0" wc Minimum
16.0" wcMaximum
ELECTRICAL RATING (ALL MODELS):
120V - 60 Hz., 1.0 Amp
59
Page 66
TF-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
60
Page 67

SECTION 16: THE ROBERTS GORDON® VANTAGE® TF WARRANTY

SECTION 16: THE ROBERTS GORDON
®
VANTAG E
TF WARRANTY
®
ROBERTS-GORDON LLC WILL PAY FOR:
Within 36 months from date of purchase by buyer or 42 months from date of shipment by Roberts-Gordon LLC (whichever occurs first), replacement parts will be provided free of charge for any part of the product which fails due to a manufacturing or material defect.
Roberts-Gordon LLC will require the part in question to be returned to the factory. Roberts-Gordon LLC will, at its sole discretion, repair or replace after determining the nature of the defect and disposition of part in question.
ROBERTS GORDON
®
Replacement Parts are warranted for a period of 12 months from date of shipment from Roberts-Gordon LLC or the remaining ROBERTS GORDON
®
VANTAGE® TF warranty.
ROBERTS-GORDON LLC WILL NOT PAY FOR:
Service trips, service calls and labor charges. Shipment of replacement parts. Claims where the total price of the goods have not
been paid. Damage due to:
• Improper installation, operation or maintenance.
• Misuse, abuse, neglect, or modification of the ROBERTS GORDON
• Use of the ROBERTS GORDON
®
VANTAGE® TF in any way.
®
VANTAGE® TF for
other than its intended purpose.
• Incorrect gas or electrical supply, accident, fire, floods, acts of God, war, terrorism, or other casualty.
• Improper service, use of replacement parts or acces­sories not specified by Roberts-Gordon.
• Failure to install or maintain the ROBERTS GORDON VANTAGE
®
TF as directed in the Installation, Opera-
tion and Service manual.
• Relocation of the ROBERTS GORDON
®
VANTAGE®
TF after initial installation.
• The use of the ROBERTS GORDON
®
VANTAGE® TF in
a corrosive atmosphere containing contaminants.
• The use of the ROBERTS GORDON
®
VANTAGE® TF in
the vicinity of a combustible or explosive material.
• Any defect in the ROBERTS GORDON
®
VANTAGE® TF arising from a drawing, design, or specification sup- plied by or on behalf of the consumer.
• Damage incurred during shipment. Claim must be filed with carrier.
WARRANTY IS VOID IF:
The ROBERTS GORDON® VANTAGE® TF is not installed by an contractor qualified in the installation and service of gas fired heating equipment.
Yo u cannot prove original purchase date and required annual maintenance history.
The data plate and/or serial number are removed, defaced, modified or altered in any way.
The ownership of the ROBERTS GORDON
®
VANTAGE® TF is moved or transferred. This warranty is nontransferable.
Roberts-Gordon LLC is not permitted to inspect the damaged equipment and/or component parts.
READ YOUR INSTALLATION, OPERATION AND SERVICE MANUAL
If you have questions about your equipment, contact your installing professional. Should you need Replacement Parts or have additional questions, call or write:
Roberts-Gordon LLC
1250 William Street P. O . B o x 4 4 Buffalo, New York 14240-0044 Telephone: +1.716.852.4400 Fax: +1.716.852.0854 Toll Free: 800.828.7450
www.rg-inc.com www.radiantheaters.com
Roberts-Gordon LLC's liability, and your exclusive remedy, under this warranty or any implied warranty (including the implied warranties of merchantability and fitness for a particular purpose) is limited to providing replacement parts during the term of this warranty.
Some jurisdictions do not allow limitations on
how long an implied warranty lasts, so this limitation may not apply to you. There are no rights, warranties or conditions, expressed or implied, statutory or otherwise, other than those contained in this warranty.
Roberts-Gordon LLC shall in no event be responsible for incidental or consequential damages or incur
®
liability for damages in excess of the amount paid by you for the ROBERTS GORDON
®
VANTAGE® TF. Some
jurisdictions do not allow the exclusion or limitation of incidental or consequential damages, so this limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from jurisdiction to jurisdiction.
Roberts-Gordon LLC shall not be responsible for failure to perform under the terms of this warranty if caused by circumstances out of its control, including but not limited to war, fire, flood, strike, government or court orders, acts of God, terrorism, unavailability of supplies, parts or power. No person is authorized to assume for Roberts-Gordon LLC any other warranty, obligation or liability.
LIMITATIONS ON AUTHORITY OF REPRESENTATIVES:
No representative of Roberts-Gordon LLC, other than an Executive Officer, has authority to change or extend these provisions. Changes or extensions shall be binding only if confirmed in writing by Roberts-Gordon LLC's duly authorized Executive Officer.
61
Page 68
Page 69
Page 70
Page 71
Page 72
Loading...