Roberts Gorden HF 40 v1, HF 40 v2, HF 30 v5, HF 30 v6, HF 40 v3 Installation, Commissioning, Service & User Instructions

...
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
6. Immediately call your local gas supplier after leaving the building. Follow the gas suppliers instructions.
Do not store or use petrol or other flammable vapours and liquids in the vicinity of this or any other appli­ance.
Failure to follow these instructions can result in death, injury or property damage.
WARNING
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, operation and service manuals thoroughly before installing or servicing this equipment
Installation must be done by a contractor qualified in the installation and service of gas/oil fired heating equipment (whichever is applicable).
Installer
Please take time to read and understand these
instructions prior to any installation. Installer must
give a copyof this manual to the user/owner.
Owner/User
Keep this manual in a safe place close to the heater
to provide your serviceman with information should it
become necessary.
Roberts-Gordon Europe Ltd.
Oxford Street Bilston, West Midlands WV14 7EG UK Telephone: +44 (0)1902 494425 Fax: +44 (0)1902 403200 email: uksales@rg-inc.com
www.combat.co.uk www.rg-inc.com
Combat
®
Warm Air Cabinet
& High-Flow Heaters
OIL FIRED: POP, POPH and
POP /H versions
Models 015 to 0100
GAS FIRED: PGP, PGPH and
PGP /H/M versions
Models 015 to PGP 0100
Installation, Commissioning,
Service & User Instructions
WARNING
Fire Hazard
X523F 02/03
© Copyright 2002 Roberts-Gordon
Page 1
CABINET HEATER
T
he gas fired versions of these appliances have been tested and certified
as complying with the essential requirements of the Gas Appliance Directive, the Electromagnetic Compatibility Directive, The Low Voltage directive and the Machinery Directive for use on natural gas and L.P.G. Propane when installed, commissioned and maintained in accordance with these instructions
The gas fired heaters are category II
2H 3P
for natural gas or propane gas and are type B23 for
a natural draught flue.
These instructions refer to gas appliances designed to operate in the following countries: United kingdom (GB), Ireland (IE), Italy (IT) and Spain (ES)
The oil fired versions may also operate in these countries in accordance with local rules and laws.
The oil fired versions are constructed to the same Basic design criteria to burn fuel oil as specified below but there is no similar testing available for these products at the time of writing these instructions.
However the safe operation of the heaters depends on the proper installation, commissioning and maintenance of the appliances in accordance with these instructions .
The fuel specified for oil fired burners is:
Class D fuel oil to BS 2869 Which is similar to Gas oil with a maximum viscosity at 20° C of 1.5° E
These appliances must be installed in accordance with the rules in force, and used only in a sufficiently ventilated space, as specified in these instructions and local regulations.
Before installation, check that the local distribution conditions of the fuel, the quality of the fuel and the appliance adjustment are compatible.
These instructions cover the installation setting and operation of all variations of the COMBAT® range of cabinet heaters. The burner manufacturers instructions are also provided to give detailed instructions on the operation of the burner. The settings for use of the burner with the air heater are shown in these instructions or the relevant supplement which is issued with the appliance to cover specific features available for various options.
It is important that all of the relevant information is used when installing, setting or operating this equipment
© 2003
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping, or information storage and retrieval systems ­without written permission of Roberts-Gordon.
Page 2
CABINET HEATER
Contents
The parts of this manual are numbered by section, clause and sub clause. Hence: 1.2.3 refers to Section 1, clause 2, sub clause 3. Figure numbers also follow this notation hence: Fig 2.3 is Section 2, fig.3.
SECTION PAGE
1. General Specification 3
2. Technical Data 7
3. Installation Requirements 29
4. Installation of the Air Heater 33
5. Commissioning of the Air Heater 39
6. Wiring Diagrams 46
7. Servicing Instructions 56
8. Removal and Replacement of Parts 58
9. Fault Finding Charts 60
10. User Instructions 67
11. Conversion information 72
12. Parts List 73
13. Commissioning Data Sheet 74
THIS MANUAL RELATES TO THE AIR HEATERS WHICH ARE MANUFACTURED FOR USE WITH:-
OIL FIRED HEATERS: GAS FIRED HEATERS
Class D fuel oil to BS 2869 Natural gas G20 Which is similar to L.P.G Propane (G31) Gas oil with a maximum viscosity at 20° C of 1.5° E
THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER OR NEAR THE HEATER
Note: Every effort is made to ensure that the information within this manual is accurate.
However, Robert-Gordon reserves the right to alter specifications without prior notice.
Roberts-Gordon shall not be liable to rectify any defects or damage caused by any modifications made or attempted to be made to the heating units by the customer, his servants, agents or employees.
Page 3
CABINET HEATER
Section 1. General Specification
1.1 General Information - Standard Models
COMBAT® cabinet warm air heaters are self contained units fitted with a packaged burner and are supplied ready for installation on site to be used with external controls. The burner controls which form part of the packaged burner are designed for safe operation between
-20°C to 60°C. However the heater should not be operated in ambient temperatures above 32°C .At Ambient temperatures above 29°C some models may require the maximum heat input to be reduced, seek advice from Roberts-Gordon UK Ltd. under these circumstances
The standard PGP or POP heater is the free standing model.
Models are available with various options are:
PGPH & POPH models for use in the horizontal (suspended) mode PGPE & POPE weatherproof models for external siting HF range of 'High Flow' gas fired and oil fired heaters with higher air flows PGP/H and HF/H gas fired ranges for Ecoflam high /low burners PGP/M and HF/M gas fired ranges for Ecoflam fully modulating burners POP/H and HF/H oil fired ranges are also available with Ecoflam High /Low burners
COMBAT® cabinet heaters are available with heat outputs ranging from 47.3kW to 290kW.
All heaters are fitted with fully automatic 'packaged' forced draught oil fired or gas fired burners manufactured for Roberts-Gordon UK Ltd.
The heater cabinets are manufactured in Zintec coated mild steel which is finished with a stove cured powder coat paint.
The combustion chambers are of high grade stainless steel construction. The heat exchangers are mild steel tubular all welded construction.
Centrifugal fan(s) located in the base of the heater cabinet provide heated recirculation air, which is distributed from the top of the heater through the fully adjustable louvred outlet heads.
The fan(s) are either direct drive or belt driven dependent upon model:
Models 015 - 050 inclusive - Direct Drive (except High Flow) Models 060 - 0100 inclusive - Belt Drive
The required electrical supply is: 230 volt 50Hz single phase on models 015 to 030 and 400 volt 50Hz three phase and neutral on models 040 to 0100 (Models PGP and POP 040 and 050 are also available as single phase belt drive to special order). All High Flow models require a 400V, 50Hz, three phase and Neutral electrical supply.
ON/OFF control, temperature control, time control, and frost protection are available as a remote control which needs to be site wired to afford proper operation of the heater. Alternatively, any remote energy controls may be used which must be installed in accordance with Section 4.3.
Each heater must be fitted with its own natural draught flue in accordance with local regulations and the instructions in this booklet. Fig. 1.1 shows the basic parts of the heater.
Page 4
CABINET HEATER
Fig 1.1 Standard PGP/POP Cabinet Heater - General Arrangement
Air Diffuser Heads
Fan/Limit Thermostat
Flue
Flue Spigot (female)
Heat Exchanger
Rear Pressure Relief
Stainless Steel Combustion Chamber
Double Skin Panels
Burner Tube (for mounting the 'packaged' burner)
Electrical Connections
Lower Front Panel
Main Fan Assembly (Direct Drive on Models 15 - 50, Belt Dive on Models 60 -100)
Page 5
CABINET HEATER
1.2 Basic Information - High Flow (HF) Models
1.2.1 Introduction
The COMBAT® HF range of cabinet heaters are designed specifically to meet the needs of designers who require a high fan performance with the heat input that would be expected for the standard COMBAT® cabinet range of heaters. The result of this is to produce a lower average temperature rise over the heat exchanger dependant upon the final air flow of the installation.
High Flow Heaters are fitted with burners to the same specification as the PGP or POP 30 to 50 models for either gas or oil firing.
COMBAT® High Flow cabinet heaters are available in 10 sizes dependent upon air flow required, with a choice of 3 heat outputs; 81kW, 115kW and 145kW.
1.2.2 Electrical Supply
The HF range of heaters all require a 400v three phase and neutral 50Hz supply to the main terminals within the heater.
1.2.3 Controls
The HF range of heaters are designed to be operated with external controls and are provided with electrical terminals to accommodate these.
They may be controlled in the same manner as the PGP or POP models using Roberts-Gordon controls or other suitable controls.
1.2.4 Fan Operation
All of the HF range of heaters are provided with a fan operation relay as well as the combination fan thermostat to ensure that the fan will run correctly even though the temperature rise may be low.
The HF 40v3 and HF 50v2 to 50 v4 models are fitted with 5.5kW or 7.5kW motors that are controlled via an automatic
star/delta starter built into the heater to replace the direct on line starter used for the remainder of the range.
Page 6
CABINET HEATER
1.3 Heater Operation (On/Off)
Once the heater has initially been switched on using the remote controls, the operation of the heater becomes automatic under the control of the remote time/temperature controls (as fitted on site) and the safety devices.
When the external controls call for heat, the control box of the fully automatic burner checks that all systems are in a safe and ready position, and then initiates a start sequence. It then constantly monitors safe operation of the burner (see Section 2.2 & 2.3 for details).
When the heat exchanger has been sufficiently heated, the built in fan thermostat turns on the main fan(s) and warm air is distributed from the top of the heater.
Note: On horizontally mounted heaters, High Flow heaters, heaters fitted with high/low or modulating burners and some fully ducted heaters, the fan will come on during the burner firing cycle and not wait for the temperature rise. This is to ensure that there is always a proper operation of the heater under all possible conditions.
At the close down of the external controls, the burner shuts off and the main fan(s) continue to run until the fan thermostat detects a drop in leaving air temperature, sufficient to turn it off. The heater is then at rest until the beginning of the next cycle.
If for any reason the main fan should fail or the air flow through the heater is reduced, then the built in limit thermostat will cause the burner to go to safety shut down lockout. This condition will remain until the fault is corrected and the manual red reset button is operated at the limit thermostat.
1.2.1 Heater Operation (High/Low)
For burners which are capable of High/Low operation, a two stage thermostat will be required to be installed on site to alow the burner to operate On/Off and High/Low dependant upon conditions (see 4.3.1.1 for details)
1.2.2 Heater Operation (Fully Modulating)
For gas burners only which are capable of Fully Modulating operation the burner comes complete with a temperature control system. The sensor of this system needs to be installed on site (see 4.3.1.2) to allow the burner to vary the heat input to maintain a constant control temperature.
WARNING
The main electrical isolator should only be used in an emergency and for servicing.
It should never be used for closing down the burner, as this switches off the main fan prematurely
and may damage the heat exchanger, invalidating the warranty and causing a potential fire hazard.
Page 7
CABINET HEATER
Section 2. Technical Data
Table 2.1 General Data All Standard Models PGP and POP and All
Versions for High/Low or Modulating Burners
Dimensions for Horizontal heaters are as above, with heaters lain on their left hand side as standard.
* For vertical models add 54mm (2 ins) to the right hand side of the heater cabinet for the fan/limit thermostat.
* For horizontal models add 54mm (2 ins) to the top of the heater cabinet for the fan/limit thermostat.
Note: A permanent uninterrupted electrical supply is required for all models
A Width
B Depth - Cab.Only
C Height - Cab.Only
D Depth Overall Oil
D Depth Overall Gas
E Height Incl. Heads
F L/R Hand Air
Inlet Spigot Depth
G L/R Hand Air
Inlet Spigot Height
H Rear Air
Inlet Spigot Depth
J Rear Air
Inlet Spigot Height
Weight
Number and size
of air discharge heads
Flue Diameter
MAIN FAN
Motor Type
Motor Size
Motor Pulley
Fan Pulley
Main Fan Start
Current
Main Fan Run Current
Total Elec. Load
Airflow (Free Blowing)
AC Electrical Supply
Model
mm (ins)
mm (ins)
mm (ins)
mm (ins)
mm (ins)
mm (ins)
mm (ins)
mm (ins)
mm (ins)
mm (ins)
kgs (lbs)
mm
mm (ins)
kW (hp)
PCD
PCD
amps
amps
kW
M³/hr
ft/hr
Volts
Hertz
Phase
020
724 (28½)
857 (33¾)
1740 (68½)
1220 (48)
1306 (51½)
1988 (78¼)
781 (30¾)
457 (18)
648 (25½)
361 (14)
200 (441)
2 x 229
178 (7)
Dir. Drive
0.75 (1)
n/a
n/a245.3
2.1 3398
(2000)
230
50
1
030
724 (28½)
857 (33¾)
1740 (68½)
1220 (48)
1306 (51½)
2058 (81)
781 (30¾)
457 (18)
648 (25½)
361 (14)
200 (441)
2 x 356
178 (7)
Dir. Drive
0.75 (1)
n/a
n/a286.3
2.1 5097
(3000)
230
50
1
040
857 (33¾)
857 (33¾)
1930 (76)
1254 (49½)
1348 (53)
2235 (88)
781 (30¾)
559 (22)
781 (30¾)
446 (17¾)
245 (540)
2 x 356
178 (7)
Dir. Drive
2.2 (3)
n/a
n/a216.2
5.4 6796
(4000)
400
50
3N
050
857 (33¾)
1016 (40)
1930 (76)
1413 (55¾)
1507 (59½)
2235 (88)
940 (37)
559 (22)
781 (30¾)
446 (17¾)
270 (595)
2 x 356
178 (7)
Dir. Drive
2.2 (3)
n/a
n/a216.2
5.4 8495
(5000)
400
50
3N
060
1016 (40)
1676 (66)
1930 (76)
2251 (88¾)
2388 (94)
2235 (88)
1600 (63)
559 (22)
N/A
N/A
440 (970)
6 x 356
229 (9)
Belt Drive
1.5 (2) 2A x 80mm
2Ax180mm
10.2
3.5
4.4 11044
(6500)
400
50
3N
070
1016 (40)
1676 (66)
1930 (76)
2251 (88¾)
2388 (94)
2235 (88)
1600 (63)
559 (22)
N/A
N/A
440 (970)
6 x 356
229 (9)
Belt Drive
2.2 (3) 2A x 95mm
2Ax180mm
30
5.1
5.5 12443
(7500)
400
50
3N
080
1016 (40)
1676 (66)
1930 (76)
2251 (88¾)
2388 (94)
2235 (88)
1600 (63)
559 (22)
N/A
N/A
440 (970)
6 x 356
229 (9)
Belt Drive
2.2 (3) 2A x 95mm
2Ax180mm
30
5.1
5.5 12443
(7500)
400
50
3N
0100
1016 (40)
1994 (78½)
1930 (76)
2569 (101¼)
2706 (106½)
2235 (88)
1918 (75½)
559 (22)
N/A
N/A
530 (1168)
6 x 356
229 (9)
Belt Drive
4 (5.4)
2A x106mm
2A x 180mm
35
9.6
6.6 17330
(10200)
400
50
3N
015
724 (28½)
857 (33¾)
1740 (68½)
1220 (48)
1306 (51½)
1988 (78¼)
781 (30¾)
457 (18)
648 (25½)
361 (14)
200 (441)
2 x 229
178 (7)
Dir. Drive
0.75 (1)
n/a
n/a245.3
2.1 3398
(2000)
230
50
1
Page 8
CABINET HEATER
Dimensions of outlet spigots - Standard Cabinet Heaters
Dimensions - All Models PGP and POP
Cabinet Sizes 015 - 050 Cabinet Sizes 060 - 0100
Note: Horizontal heater dimensions are as vertical units, but with heaters lain on their left hand side as standard.
015/020/030 040 050 060/070/080 0100
MODEL
K Spigot Width
L Spigot Depth
mm
(ins)
mm
(ins)
015
648
(25½)
476
(18½)
020
648
(25½)
476
(18½)
030
648
(25½)
476
(18½)
040
781
(30¾)
476
(18½)
050
781
(30¾)
610 (24)
060/070/080
940 (37)
1238
(48¾)
0100
940 (37)
1524
(60)
Air Outlet Spigot Dimensions - Standard Cabinet Heaters
Page 9
CABINET HEATER
Table 2.2 General Data - High Flow Cabinet Heaters
For High Flow PGP and POP range heaters * Start current shown for direct on line starting.
Mod el Numb er HF 30 v4 HF 30 v5 HF 30 v6 HF 40 v1 HF 40 v2 HF 40 v3 HF 50 v1 HF 50 v2 HF 50 v3 HF 50 v4
Product Code HE (O) (G)34 HE(O) (G)35 HE(O) (G) 36 HE(O) (G) 41 HE(O) (G) 42 HE(O) (G) 43 HE (O) (G) 51 HE (O) (G) 52 HE (O) (G) 53 HE (O) (G) 54
Air Volume m³ /sec Static Pressure Pa See Graph HF 11 See Graph HF 12 See Graph HF 13 See Graph HF 4 See Graph HF5 See Graph HF 6 See Graph HF 7 See Graph HF 8 See Graph HF 9 See Graph HF 10 Motor Running Current Max Motor start current Amps 27 40 40 20.0 32.0 35.0 D.O.L. * 20.0 35.0 D.O.L. * 37.5 37.5 Max Moto r runnin
g
current Amps (FLC)5 8.4 8.4 5.4 9.4 11.5 8.7 11.5 16.5 18 Max Electrical load (on FLC) kW 4 6.6 6.6 4 6.6 8.3 6.6 8.3 11.9 11.9 Motor Size kW 2.2 4.0 4.0 2.2 4.0 5.5 4.0 5.5 7.5 7.5 Part Number A 064 A 072 A 072 A 064 A 072 A 063 A 072 A 063 A 062 A 062 Motor Pull ey 85 x 28 x 2A 106 x 28 x 2A 112 x 28 x 2A 95 x 28 x 2A 118 x 28 x 2A 140 x 38 x 2B 95 x 28 x 2A 112 x 38 x 2B 132 x 38 x 2B 140 x 38 x 2B Part Number A 132 A 108 A 411?? A 121 A 418 A 415 A 121 A 403 A 420 A 415 Fan Pul l ey 180 x 25 x 2A 180 x 25 x 2A 180 x 25 x 2A 180 x 25 x 2A 180 x 25 x 2A 200 x 25 x 2B 180 x 25 x 2A 180 x 25 x 2B 200 x 25 x 2B 200 x 25 x 2B Part Number A 168 A 120 A 120 A 120 A 120 A 413 A 120 A 405 A 413 A 413 Overload size Set at 6.4 Set at 6.4 set at 8.7 set at 8.7
4.0 - 7.5 Amp 6.0 - 10 Am p 6.0 - 10 Amp 4.0 - 7.5 Amp 6.0 - 10 Amp Star.Delta 7.5 A. FLC 6.0 - 10 Amp Star.De lta 7.5 A. FLC Star.Delta 10 A. FLC Star.Delta 10 A. FLC Part Number D 020 D 024 D 024 D 020 D 024 D 020 A D 024 D 020 A D 024 D 024 Vee Belt Size A49 A49 A49 A49 A49 B54 A49 B50 B52 B52 Part No A 136 A 136 A 136 A 136 A 136 A 408 A 136 A 409 A 410 A 410 Wiring Diagram RDW 1556/D RDW 1556/D RDW 1556/D RDW 1556/D RDW 1556/B RDW 1582/B RDW 1556/B RDW 1582/B RDW 1582/B RDW 1582/B Cabinet type 50 50 50 60 60 60 100 100 100 100
DIM ENSI ONS
'A' Width mm 857 857 857 1016 1016 1016 1016 1016 1016 1016 'B' Depth Cabinet Only mm 1016 1016 1016 1676 1676 1676 1994 1994 1994 1994 'C' Height Cabinet Only mm 1930 1930 1930 1930 1930 1930 1930 1930 1930 1930 'D' Depth overall (Oil Fired) mm 1326 1326 1326 1996 1966 1966 2314 2314 2314 2314 'D' Depth overall (Gas f ired) mm 1416 1416 1416 2066 2066 2066 2384 2384 2384 2384 'W' Outlet duct dimension Width mm 781 781 781 940 940 940 940 940 940 940 'L' Outlet duct dimension Depth mm 610 610 610 1030 1030 1030 1350 1350 1350 1350 'F' inlet duct dimension Depth mm 940 940 940 1600 1600 1600 1918 1918 1918 1918 'G' Inlet duct dimension Height mm 559 559 559 559 559 559 559 559 559 559
for High Flow PGP and POP range heaters * Start current show n for direct on line starting.
The burne r settings are as shown in the r elevant data table in the m ain instructions book . these models are fitted with star delta starters as standard
Heat inputs shown are m aximum for each version at minimum air flow on graph. Revision correct m otor shaft size for 50 v2 October 10 96
Dimensions - High Flow Cabinet Heaters - All Models
A
B
C
D
W
L
F
G
178
229 (HF30)
435 (HF40)
412 (HF50)
Page 10
CABINET HEATER
Table 2.3 Oil Fired Burner Data (Ecoflam Burner)
Burner Reference "G"
DATA TABLES - IMPORTANT NOTE
When reading the Data Tables 2.3 to 2.9 on the following pages,
ensure that the correct table for the burner and gas valve installed is being used.
The Data Tables are listed under a burner reference letter which can be found
on the heater data plate.
Refer also to the Burner Manufacturer's Instructions
and the specific instructions supplement where applicable.
The burner settings shown in the instructions should be used for burner settings.
Note: High Flow Heaters are fitted with burners to the same specification as the POP 30, 40 and 50 models for oil firing.
Mode l POP 015 POP 020 POP 030 POP 040 POP 050 POP 060 POP 070 POP 080 POP 0100
Heat Input (gross)
Kw 51 73.6 109.7 146.2 183.2 221.2 256.2 300.6 355.8
Btu/hr 174012 251073 374277 498786 625000 754870 874060 1025647 1213874
Nominal He at output
Kw 44 58.6 87.9 117.2 146.5 175.8 205.2 234.5 293.1
Btu/hr 150000 200000 300000 400000 500000 600000 700000 800000 1000000
Ecoflam Burner type
Minor 8 Minor 8 Minor 12 Minor 20 Minor 20 Minor 30 Minor 30 Minor 30 Major 30
Nozzle Size
Us gall/hr 1.00 1.50 2.25 3.00 3.00 4.00 5.00 5.50 7.00
Angle & Type
60S 60S 60S 60S 60S 60A 60A 60A 60A
Make
Danfoss Danfoss Danfoss Danfoss Danfoss Delevan Delevan Delevan Delevan
Head setting
mm 8 0 14
8
(Fully back)8(Fully back)8(Fully back)
8
(Fully back)
8
(Fully bac k )
(Fully
Forward)
Air setting
Number 4.2 8.5 5.5 2.5 4 3.7 4.5 6.2 1.8
Burner fuel
Bar 12 10.3 10.3 10 13.8 12.4 10.7 10 11
pressure
PSI 175 150 150 145 200 180 155 145 160
Fuel
L/hr 4.82 6.96 10.37 13.83 17.32 20.92 24.23 28.43 33.65
consumption
imp gall.hr 1.06 1.53 2.28 3 3.81 4.6 5.33 6.25 7.4
Max. oil pressure
Bar 0.21 0.21 0.21 0.21 0.21 0.21 0 .2 1 0.21 0.21
to pum p inle t
PSI3333333 33
Page 11
CABINET HEATER
Table 2.4 Ecoflam ON/OFF Natural Gas (G20) Dungs Valve, Burner
Reference C
Data for all versions "H" horizontal, "HF" high flow Gas rates corrected to standard conditions 1013.25 mbar 15°C
HEAD SETTING - See Adjustment Of The Firing Head in Ecoflam Instructions
INLET PRESSURE 20 mbar (Minimum 17 mbar, M ax imum 25 mbar)
MODEL PGP 015 PGP 020 PGP 030 PGP 040 PGP 050 PGP 060 PGP 070 PGP 080 PGP 0100
Gross heat input (kW)
56.1 73. 7 103 144.7 182.1 220 253.6 297 363
Net heat Input (kW)
51 67 93.6 131.5 165. 5 200 230.5 270 330
Ap pr o x heat output (kW)
46.9 60. 3 81.9 114.7 144.8 176 202.8 237.6 290.1
Start Gas Orifice (mm dia.) 5.0 6.0 7.0 7.0 7.0 7.0 Max Gas Rate (Sm
3
/hr)
5.4 7. 1 9.9 13. 9 17.5 21. 2 24.4 28. 6 34.9
Main Burner Gas Pressure (mbar)
4.7 2. 5 4.9 5.2 8.5 5. 6 7.5 9.5 11
Start Gas Pressure (mbar)
N/A N/ A N/A 1.8 2. 8 0.9 1.1 1.7 3.4
BURNER TYPE
A ZUR BLU BLU BLU BLU BLU BLU BLU BLU
60 12 0 120 170 250R 250 250 250S 350 Burner Head sssssssss Burner Injector Head Setting (mm)
0 1011151424242421
1st Flame Air Setting
3.5 3.9 8 2.8 5.1 3.3 5.3 2 2
2nd Flame Air Setting Ga s Valve S etting Valve Type MBDLE MBDL E MBDLE MBDLE MBDLE MBDL E MBDLE MBDLE MBDLE Main Gas 405 405 405 407 410 410 4 10 410 412
Valve Type SSSSSS Start Gas 0 832 051 0 832 051 0 832 051 0 83 2 05 1 0 832 051 0 832 051 AIR PRES SURE SWITCH SETTING (mbar) 3.8 4.5 5.9 2.9 5.5 3.6 4.5 6.8 5.1 Max flue static pressure norm. flue static pressure ( mbar) -0.05 -0 .05 -0.09 - 0 .30 -0.05 - 0.25 -0.17 0.10 0.45 Gas Connection 3/4" 3/4" 3/4" 3/4" 1 1/4" 1 1/4" 1 1/4" 1 1/4" 1 1/4" S.= S.I T H.= HONEYWELL
Page 12
CABINET HEATER
Table 2.5 Ecoflam ON/OFF LPG (G31) with Dungs Valve, Burner Reference C
Data for all versions "H" horizontal, "HF" high flow Gas rates corrected to standard conditions 1013.25 mbar 15°C
HEAD SETTING - See Adjustment Of The Firing Head in Ecoflam Instructions
INLET PRESSURE 37 mbar (MINIMUM 25 mbar , MAXIMUM 45 mbar)
MODEL PGP 015 PGP 020 PGP 030 PGP 040 PGP 050 PGP 060 PGP 070 PGP 080 PGP 0100
Gross heat Input (kW)
56.1 73.7 103 144.7 182.1 220 253.6 297 363
Net heat Input (kW)
51 67 93.6 131.5 165.5 200 230.5 270 330
Approx heat output (kW) 46.9 60.3 81.9 114.7 144.8 176.0 202.8 237.6 290.1 Main Gas Orifice (mm dia.) 8.5 10.0 10.0 14.5 14.5 14.5 14.5 14.5 Start Gas Orifice (mm dia.) 5.0 6.0 7 .0 7.0 7.0 7.0 Max Gas Rate (m
3
/hr) 2.10 2.70 3.80 5.40 6.80 8.20 9.40 11.00 13.50 (kg/hr) 3.9 5.1 7.1 10.1 12.7 15.4 17.6 20.6 25.3 Lt/hr 7.7 10.0 13.9 19.8 25.0 30.3 34.6 40.5 49.7
M ain Burner Gas P ressure (mbar) 3.9 3.1 5.6 4.6 7.0 5.2 6.8 9.5 7.6 Start Gas Pressure (mbar) 1.6 2.5 0.8 1.0 1. 5 3.1
BURNER TYPE
AZUR BLU BLU BLU BLU BLU BLU BLU BLU
60 AH 120 AH 120 AH 170 AH 250R AH 250 AH 250 AH 250S AH 350 AH Burner Head s s s s s s s s s Burner Injector LPG Head Setting (mm) 10.0 13.0 15.0 14 24.0 24.0 24.0 20.0 1st Flame Air Setting number 3.8 3.5 6.0 3.5 4.5 3.5 4.7 1.7 3.0 2nd Fl ame Ai r Setting Gas Valve Setting Valve Type MBDLE MBDLE MBDLE MB DLE MBDLE MBDLE MBDLE MBDLE MBDLE Main Gas 405 405 405 407 410 410 410 410 412
Valve Type S S S S S S Start Gas 0 832 051 0 832 051 0 832 051 0 832 051 0 832 051 0 832 051 AIR PRESSURE SWITCH SETTING (mbar) 3.8 4.5 5.9 2.9 5.5 3.6 4.5 6.8 5.1 Max flue static pressure norm. flue static pressure (mbar) -0.05 -0.05 -0.09 -0.30 -0.05 -0.25 -0.17 0.10 0.45 Gas Connection 3/4" 3/4" 3/4" 3/4" 1 1/4" 1 1/4" 1 1/4" 1 1/4" 1 1/4" S.= S I T H.= HONEYWELL
Page 13
CABINET HEATER
Table 2.6 Ecoflam HIGH/LOW or MODULATING Burner with Dungs
Valve, Burner Reference "H" Natural Gas G20
Data for all versions "H" horizontal, "HF" high flow Gas rates corrected to standard conditions 1013.25 mbar 15°C
When setting the minimum firing rate a check must be made following the setting of the burner combustion . The check is made by running the heater on low fire for a minimum of 15 minutes at the full transport air rate and at typical ambient conditions. During the test check that the flue gas temperature does not fall below 150°C .Should the flue gas temperature fall below 150°C then the low fire gas setting must be increased to a value that will achieve 150°C flue gas temperature, otherwise condensation may form in the heat exchanger and flue causing rapid corrosion and short operational life.
ECOFLAM HIGH/LOW GAS BURNER WITH DUNGS GAS VALVES FOR NATURAL GAS G20
INLET PRESSURE 20 mbar (minimum 17mbar maximum 25mbar)
MODEL PGP 015 PGP 020 PGP 030 PGP 040 PGP 050 PGP 060 PGP 070 PGP 080 PGP 0100
Maximum Gross heat Input (kW) 55.0 74.0 104.0 145.9 183.0 221.0 256.0 300.0 367.0 Maximum Net heat Input (kW) 49.6 66.7 93.7 131.5 164.9 199.1 230.7 270.3 330.7 Minimum Gross heat Input (kW) 33.85 44.40 63.82 87.13 109.88 133.19 153.16 179.80 219.76 Minimum net heat Input (kW) 30.50 40.00 57.50 78.50 99.00 120.00 138.00 162.00 198.00 Approx heat output (N et) (kW) 43.5 58.5 82.2 115.3 144.6 174.6 202.0 237.0 289.9 Start Gas Orifice (mm dia.) 7.0 7.0 7.0 7.0 7.0 7.0 Max Gas Rate
(Sm
3
/hr )
5.2 7.1 9.9 13.9 17.4 21.1 24.4 28.6 35.0
Min Gas Rate
(Sm
3
/hr )
3.1 4.2 6.0 8.5 10.6 13.0 15.0 17.5 21.6 Main Burner Gas Pressure (mbar) 4.7 2.5 4.1 5.2 8.5 5.9 7.5 9.5 9.6 Min . B urner G a s P r e s sure (mba r) 2 .1 2.0 2.2 2.1 3.4 2.1 2.8 3.8 4.5 Start Gas Pressure (mbar) 1.1 1.8 0.6 0.7 0.9 1.0 BURNER TYPE AZUR BLU BLU BLU BLU BLU BLU BLU BLU
60 120 120 170 250R 250 250 250 350 Burner Head sssssssss Burner Injector Head Setting (mm) 0.0 8.0 10 .0 15.0 14 T.O . T.O. T.O. T.O. Low Flame Air Orange C a m ** 20° 13° 22° 18° 18° 18° 22° 25° 25°
High Flame Air Red Cam ** 33° 40° 80° 30° 32° 30° 35° 55° 60° Ga s Valve Setting 0-1,5 0-1 0-1 ,4 0-1,4 0-1 ,4 0-1 ,4 0-1 ,4 0-1,4 0-1 ,4 Valve Type M BVEF MBVEF MBVEF M BVEF MBVEF MBVEF M BVEF MBVEF MBVEF Main Gas 407 407 407 407 412 412 412 412 412
Valv e Type S.I.T. S.I.T. S.I.T. S.I.T. S.I.T. S.I.T. Start Gas 832051 832051 832051 832051 832051 832051 AIR PRESSURE SWITCH SETTING (mbar) 1.5 1.5 1.5 1.0 1.5 1.5 1.5 2.0 2.5 Max flue static pressure norm. flue static pressure (mbar) -0.05 -0.05 -0.09 -0.30 -0.05 -0.25 -0.17 0.10 0.45 Gas Connection 3/4" 3/4" 3/4" 3/4" 1 1/4" 1 1/4" 1 1/4" 1 1/4" 1 1/4" S.= STANDARD ** Note the air s e ttin g is a g uide only , th e fin a l s e ttin g is s u b je c t to th e combu s tio n testing.
HEAD SETTING - See Adjustment Of The Firing Head in Ecoflam Instructions
Page 14
CABINET HEATER
Table 2.7 Ecoflam HIGH/LOW or MODULATING Burner with Dungs Valve
Burner Reference "H" L.P.G. G31
Data for all versions "H" horizontal, "HF" high flow Gas rates corrected to standard conditions 1013.25 mbar 15°C
INLET PRESSURE 37 mbar (minimum 25m bar, maxim um 45mb ar)
MODEL PGP 015PGP 020PGP 030PGP 040PGP 050PGP 060PGP 070PGP 080PGP 0100
Maximum Gross heat Input (kW) 55.0 74.0 104.0 145.9 183.0 221.0 256.0 300.0 367.0 Maximum Net heat Input (kW) 49.6 66.7 93.7 131.5 164.9 199.1 230.7 2 70.3 330.7 Minimum Gross hea t Input (kW) 33.85 44.40 63.82 87.13 109.88 133.19 153.16 1 79.80 219.76 Minimum net heat Input (kW) 30.50 40.00 57.50 78.50 99.00 1 20.00 138.00 162.00 198.00 Approx heat output (Net) (kW ) 43.5 58.5 82.2 115.3 144.6 174.6 202.0 2 37.0 289.9 Main Gas Orifice (mm d ia.) 8.5 10.0 10.0 14.5 14.5 14.5 14.5 14.5 N/A Start Gas Orifice (mm d ia.) 7.0 7.0 7.0 7.0 7.0 7.0 Max Gas Rate (Sm3/hr) 2.11 2.73 3.70 5.50 6.89 8.32 9.30 11.00 12.40 Min Gas Rate (Sm3/hr) 1.30 1.65 2.31 3.28 4.19 4.99 5.73 6.68 7.98 Main Burner Gas Pressure (m bar) 4.3 5.4 5.2 3.9 7.5 6.0 7.5 10.1 5.7 Min. Burner Gas Pressure (mbar) 1.7 2.2 1.2 1.5 1.9 1.9 2.0 2.7 1.5 Start Gas Pressure (mbar) 1.1 1.7 0.6 0.7 0.7 1.5 BURNER TYPE AZUR BLU BLU BLU BLU BLU BLU BLU BLU
60 120 120 170 250R 250 250 250 350 Burner Head ssssssss s Burner Injector LPG Head Setting (mm) 0.0 8.0 10.0 15.0 14 T.O. T.O. T.O. T.O . Low Flame Air Orange Ca m ** 20° 13° 22° 18° 18° 18° 22° 25° 25° High Flame Air Red Cam ** 33° 40° 80° 30° 32° 30° 35° 55° 60° Gas Valve Setting 0-1,4 0,3-0,9 0-1,1 0-1,1 0-1,1 0-1,4 0-1,4 0-1,5 0-0,85 Valve Type MBVEF MBVEF MBVEF MBVEF MBVEF MBVEF MBVEF MBVEF MBVEF Main Gas 407 407 407 407 412 412 412 412 412
Valve Type S.I.T . S.I.T . S .I.T . S.I.T . S .I.T . S .I.T . Start Gas 832051 832051 832051 832051 832051 832051 AIR PRESSURE SWITCH SETTING (mbar) 1.5 1.5 1.5 1.0 1.5 1.5 1.5 2.0 2.5 Max flue static pressure norm. flue static pressure (mbar) -0.05 -0.05 -0.09 -0.30 -0.05 -0.25 -0.17 0.10 0.45 Gas Connection 3/4" 3/4" 3/4" 3/4" 1 1/4" 1 1/4" 1 1/4" 1 1/4" 1 1/4" S.= STANDARD ** Note the air setting is a guide only, the final setting is subject to the combustion testing.
HEAD SETTING - See Adjustment Of The Firing Head in Ecoflam Instructions
When setting the minimum firing rate a check must be made following the setting of the burner combustion . The check is made by running the heater on low fire for a minimum of 15 minutes at the full transport air rate and at typical ambient conditions. During the test check that the flue gas temperature does not fall below 150°C .Should the flue gas temperature fall below 150°C then the low fire gas setting must be increased to a value that will achieve 150°C flue gas temperature, otherwise condensation may form in the heat exchanger and flue causing rapid corrosion and short operational life.
Page 15
CABINET HEATER
Fig. 2.1 Oil Fired Control Box Sequence
2.2 Control Box - Oil Fired Heaters
High /Low oil burners although following the general sequence as described below also have extra functional stages related to air damper positions. Refer to burner manufacturers instructions for further detail.
(See also the Burner Manufacturer's Instructions)
2.2.1
The oil fired burner fitted to the heater is controlled by a fully automatic control box and photoelectric flame monitor unit. This control ensures the safe start, ignition and stop sequence and also monitors the safe presence of a flame.
If the flame should fail, or fail to be monitored, then the control will go to the safety shut down lockout condition. The button on the front of the control box will light to indicate this. This button will then need to be pressed in manually to reset the control box to recommence the burner firing cycle.
This is a thermal control which, following a lockout condition, cannot be reset until the thermal element has cooled. This takes approximately one minute.
2.2.2 Operating Sequence
The operating sequence of the oil fired control boxes are as shown in Figure 2.1.
WARNING:
The control should not be reset from lockout more than three times without identifying and correcting the
cause. Residual fuel oil in a combustion chamber is an explosion risk.
Page 16
CABINET HEATER
2.2.3 Sequence of Events
The operating sequence is as follows:
With the external controls on and calling for heat, the burner fan and electric ignition will switch on.
After a combustion air purge of approximately 12 seconds, the oil solenoid valve will open and the burner will fire.
After another 5 seconds the electric ignition is turned off and the burner will go to its normal run position.
The photo cell monitors the safe presence of the flame continuously.
When the temperature control is satisfied, the control box will turn off all its outputs simultaneously, and returns to the rest position for the beginning of the next sequence.
2.2.4 Fault Conditions
If at any stage during normal running the photo electric cell fails to detect the flame, the control will switch off and make an instant restart attempt. If the flame signal is still missing lockout will occur.
If the flame is not detected by the photo cell during a normal start, there will be no restart attempt and lockout will occur in approximately 17 seconds after the start.
If a flame is detected during the first 12 seconds (purge) the solenoid valve will not open and the control will lockout. For control sequence see Fig. 2.1.
2.3 Control Box - Gas Fired Heaters
(See also the Burner Manufacturer's Instructions)
High /Low and Modulating burners although following the general sequence as described below also have extra functional stages related to air damper positions. Refer to burner manufacturers instructions for further detail.
Ecoflam gas burner have only one pressure switch which is configured to cover both available combustion air and reaction to increases in combustion chamber pressure.
2.3.1 Description of Gas Fired Heater Control Box
The gas fired burner fitted to all COMBAT® cabinet heaters is controlled by a full sequence plug-in control box. This control ensures the safe start and stop sequence and also monitors the safe presence of a flame and burner air pressure.
The Models 15 to 30 are wired for direct ignition of the main flame. All other models are wired for ignition of a start gas flame as first stage and then the main gas flame as the second stage.
2.3.2 Sequence of Events
The operating sequence is as follows:
With the external controls on and calling for heat, and the air pressure switch at rest, (contacts n.c. closed), the burner fan will switch on after a short wait for the control to "self check."
Note: If the air pressure switch contacts (n.c.) are open there will be no start.
Page 17
CABINET HEATER
Fig 2.2 Gas Fired Heater Control Box Sequence
2.3.3 Air Pressure Switch Contacts
The combustion air fan now turns on and the air pressure switch contacts (n.o.) have to close within the next 5 seconds to indicate the availability of sufficient combustion air or lockout will occur.
2.3.4 Purge
The sequence continues with a purge time with the burner fan only running.
2.3.5 Electric Ignition ON
The electric ignition switches ON at the end of this purge time.
2.3.6 Start Gas Valve (Main gas for models 015 to 030)
The start gas valve opens and once a flame has been established this remains on until close down. The flame probe is now continuously monitoring for the safe presence of flame.
2.3.7 Electric Ignition OFF
Five seconds later the electric ignition turns off, leaving the start gas flame to be proved as stable.
Page 18
CABINET HEATER
2.4 Honeywell Combination Fan/Limit Thermostat
This is a dual function control and safety device:
1. Fan Thermostat. This automatically turns the fan ON and OFF during the heater operation controlled by the leaving air temperature. It is fitted with a white manual override button which must be in its pulled out position for automatic operation. In its pushed in position the fan(s) will run continuously.
2. Limit Thermostat. This protects the heater from overheating caused by a reduction of air flow over the heat exchanger. It is a manual reset device and once operated prevents the heater restarting until reset.
To reset wait until the heater has cooled sufficiently then press in and release the red reset button. After operation of the limit thermostat, efforts should be made to locate the problem causing its operation.
Note: IT IS ESSENTIAL THAT THE LINK SHOWN IN FIG. 2.3 IS REMOVED IN THE EVENT OF A REPLACEMENT COMBINATION FAN/LIMIT THERMOSTAT BEING FITTED
Following replacement or adjustment, the limit thermostat setting must be re-sealed using a suitable paint spot seal.
For settings see Commissioning Section 5.1.2.1.
Fig. 2.3 Combination Fan/Limit Thermostat
2.3.8 Main Gas Valve (For models above 030)
Ten seconds from when the start gas is energised the main gas valves energise and the main flame expands from the start gas. The control is now in its normal run position.
When the external controls are satisfied the control box turns off all outputs simultaneously and returns to rest position for the beginning of the next sequence.
2.3.9 Fault Conditions
If at any stage the flame fails , the air pressure switch detects a loss of air pressure or a rise in combustion chamber pressure ,then the control will go to lockout. The red light on the control box will glow and the control will need to be manually reset before any further start attempt can be made.
For control sequence see Fig. 2.2.
Page 19
CABINET HEATER
Fig. 2.4 Motor Starter (Models 040 - 0100) and Thermal Overload
(Models 060- 0100 only)
2.5 Motor Starter and Thermal Overload
On belt driven fan models the motor is controlled by a direct on line contactor starter fitted with thermal overload protection. If the thermal overload should operate the main fan will not run. To reset, press in the reset button on the overload unit (see Fig. 2.4). Note: For models fitted with a 5.5kW motor or larger, then the direct on line starter will be replaced by an automatic start delta starter - see Fig. 6.14).
The overload should be set to indicate approximately 0.2 amps above the normal running current of the heater (see Table 2.1 Technical Data).
Single phase direct drive fans are controlled directly by the fan thermostat and three phase direct drive fans are controlled by a direct on line contactor starter, but using the motors built in thermal overload protection to operate the contactor coil. On direct drive fan models the thermal overload is built into the motor and is an automatic reset device, connected as shown in the Wiring Diagrams, Section 6.
2.6 Burners
For details of the Packaged Burners see the Manufacturers Instructions and the Data Tables in Section 2.1. When reading the Data Tables ensure that the correct table for the burner and gas valve installed is being used. The Data Tables are listed under a burner reference letter which can be found on the heater data plate.
2.7 Gas Valves Used with All Burners
2.7.1 Dungs Combination Gas Valves
The Combination Valve features as shown in Fig. 2.6.
All model 015 to 030 gas fired burners operate as direct main flame ignition and have no separate start gas train. All other models operate with a first stage start gas flame supplied from a start gas train containing a start gas pressure regulator and two safety shut off valves, for all gas types.
The main gas is released at the second stage and the combination main gas valve block contains a main burner pressure regulator and two safety shut off valves, for all gas types.
Page 20
CABINET HEATER
For Ecoflam High/Low or Modulating burners then the Dungs gas valve has extra features as it is an air/gas ratio control valve.Please refer to the manufacturers instructions regarding the setting of these controls.
The design of the gas train circuits is shown in Fig 2.5.
Orifice Plate
Most models require the fitting of a restrictor (orifice) plate between the main gas valve outlet and the burner to prevent the burner from being over fired and provide suitable operating conditions for the gas valves.
Orifice Plate Position Ecoflam Burner
For all models this will be fitted into the special union between the main valve and the burner at the point where the gas supply enters the heater.
2.7.1.1 Start Gas Valves
For models PGP015 to PGP030 there is no start gas valve fitted.
For all other models the start gas train is fitted with a pressure regulator and two start gas safety shut off valves.
The start gas regulator is used to adjust the burner firing rate during the start gas phase of these models.
2.7.1.2 Main Gas Valves
Figure 2.6 shows the position of the burner pressure regulation adjustment. This must be used to set the burner pressure as in the Data Tables as described in Section 5.
Note: For Ecoflam High/Low or Modulating burners then the Dungs gas valve has extra features as it is an air/gas ratio control valve.Please refer to the manufacturers instructions regarding the setting of these controls.
2.7.1.3 Throughput Adjuster
Fig 2.6 shows that these types of valve have a throughput adjuster fitted to the second main gas valve.
This will be factory set at fully open on new appliances and will need no further adjustment.
When replacing a gas valve ensure that this device is set in the fully open position by releasing the locking screw and turning the V MAX fully counter clockwise towards the " + " sign and then re-tightening the locking screw.
2.7.1.4 Rate of Opening
Fig. 2.6 also shows a slow opening adjustment. This device is a hydraulic damper which slows down the rate of opening of the second main gas valve to give a smooth main gas ignition.
This is preset at the factory at the slowest setting and will need no further adjustment.
If a new valve is fitted than remove the plastic screw-on cap and with a small screw driver turn the V start screw fully clockwise towards the " - " sign. Refit the plastic cover.
Page 21
CABINET HEATER
Fig 2.5 Gas Train Circuit for All Models with Dungs Gas Valves
Models 015 to 030 - all types of valve
Models 040 to 0100 - all types of valve
TO BURNER
TO BURNER
GAS INLET
GAS INLET
Automatic gas valve & regulator
Automatic gas valve
Note orifice plate fitted into union between valve and burner where required
1 = START GAS 2 = MAIN GAS
TP1 = Inlet Pressure TP2 = Pressure between main gas valves TP3 = Valve outlet pressure Burner pressure TP on burner
Automatic gas valve & regulator
Automatic gas valve
Note orifice fitted into union between valve and burner for models 40/50, and burner flange for models 60 and over.
Automatic gas valves
Regulator
Union
Burner flange
TP1
TP2
TP3
1
1
2
TP1
TP2
TP3
11
2
2
1 . Pressure regulator under swivel cover
2. Slow opening adjustment
3. Throughput adjuster (always fully open)
4. Inlet flange with inlet pressure test point
5. Outlet flange with outlet pressure test point
6. Test point between main valves Test between here and outlet test point for pressure drop across second valve.
Fig 2.6 Dungs Main Gas Valve Details for All Models
4
5
2
5
6
1
3
Loading...
+ 53 hidden pages