Roberts Gorden BZC 100, BZC 300 Operation Manual

Page 1
© Copyright 2000 Roberts-Gordon
10031600NA Original Issue 08/00
Operation Manual
Roberts-Gordon
1250 William Street P.O. Box 44 Buffalo, New York 14240-0044 Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
http://www.rg-inc.com
Roberts-Gordon Canada Inc.
241 South Service Road West Grimsby, Ontario L3M 1Y7 Canada Telephone: 905.945.5403 Fax: 905.945.0511
Roberts-Gordon
Oxford Street Bilston, West Midlands WV14 7EG UK Telephone: +44 (0) 1902 494425 Fax: +44 (0) 1902 403200
WARNING
Installation must be done by a electrician qualified in the installation and service of control systems for heating equipment.
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the installation and operation manuals thoroughly before installing or servicing this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place to provide your
serviceman with information should it become
necessary.
ROBERTS GORDON
®
CONTROLLER
BZC 100 & BZC 300
Page 2
Page 3
TABLE OF CONTENTS
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 What is a ROBERTS GORDON
®
BZC Controller . . . . . . . . . . . . . . . . . . . . .1
1.2 General Requirements . . . . . . . . . . . . . . . .1
1.3 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
2. Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.1 Material Specification . . . . . . . . . . . . . . . . .2
2.2 Electrical Specification . . . . . . . . . . . . . . . .2
2.3 Preset Default Factory Settings . . . . . . . .2
2.4 Keypad Layout . . . . . . . . . . . . . . . . . . . . .2
3. Viewing Screen Displays . . . . . . . . . . . . . . . . . . .4
3.1 Information Screens . . . . . . . . . . . . . . . . .4
3.2 Temperatures Sensed by Zone . . . . . . . . .4
3.3 Hours Run . . . . . . . . . . . . . . . . . . . . . . . . .4
4. Programming Options . . . . . . . . . . . . . . . . . . . . .5
4.1 Correcting Wrong Entries . . . . . . . . . . . . . .5
4.2 Temperature Setting . . . . . . . . . . . . . . . . .5
4.3 Switching Times . . . . . . . . . . . . . . . . . . . .5
4.4 Manual Override Temperature . . . . . . . . . .6
4.5 Manual Override Time . . . . . . . . . . . . . . . .7
4.6 Holiday Periods . . . . . . . . . . . . . . . . . . . . .7
4.7 Change the Current Time and Date . . . . . .7
4.8 Seasonal Time Adjustment . . . . . . . . . . . .8
4.9 How to Clear Memory . . . . . . . . . . . . . . . .8
4.10 Changing the Security Code . . . . . . . . . . .8
4.11 Changing the Override Limits . . . . . . . . . . .9
5. The ROBERTS GORDON®BZC
Controller Warranty . . . . . . . . . . . . . . . . . . . . . . . .11
TABLE OF FIGURES
Figure 1 Keypad Layout . . . . . . . . . . . . . . . . . . . . .2
Figure 2 ROBERTS GORDON®BZC Controller Quick
Programming Guide . . . . . . . . . . . . . . . . .3
Printed in the U.S.A.
© 2000
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon.
Page 4
Page 5
SECTION 1: INTRODUCTION
1.1 WHAT IS A ROBERTS GORDON®BZC
CONTROLLER?
The ROBERTS GORDON®BZC 100 and BZC 300 are micro processor based controllers designed for the most efficient control of CORAYVAC
®
,
BLACKHEAT
®
and CARIBE®heaters.
The ROBERTS GORDON®BZC 300 controller is capable of giving control outputs from 5 relays, 3 of which afford heating zone control capabilities. The controller also features 6 inputs which are used for signal condition monitoring.
The ROBERTS GORDON
®
BZC 100 controller is capable of giving control outputs from 3 relays, 1 of which affords heating zone control capabilities. The controller also features 2 inputs which are used for signal condition monitoring.
1.2 GENERAL REQUIREMENTS
The ROBERTS GORDON
®
BZC series of con­trollers are supplied pre-configured for their appli­cation and only for use with ROBERTS GORDON
®
infrared heating equipment. Failure to comply with the installation instructions and configuration will invalidate the limited warranty set out on
Page 11,
Section 5
.
Mount the ROBERTS GORDON
®
BZC Controller Quick Programming Guide next to the controller for easy reference of programming steps.
See
Page 3, Section 2, Figure 2.
1.3 SAFETY
Your Safety is Important to Us! This sym­bol is used throughout the manual to noti­fy you of possible fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these sections.
For optimum heater performance and safe heating conditions, inspect and maintain heater(s) before every heating season and as necessary. Also, know and maintain heater clearances to com­bustibles, see heater Installation, Operation and Service manual for further details. If you require additional manuals, contact your ROBERTS GORDON
®
independent distributor or Roberts­Gordon at (716) 852-4400 or (800) 828-7450 in the U.S., (905) 945-5403 in Canada or at www.rg­inc.com.
1
SECTION 1: INTRODUCTION
Installation, Service and Annual Inspection of controller must be done by an electrician qualified in the installation of control systems for heating equipment.
Installation, Service and Annual Inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment.
Read this manual carefully before installation, operation, or service of this equipment.
Failure to follow these instructions can result in death, injury or property damage.
WARNING
Page 6
2
SECTION 2: SPECIFICATIONS
2.1 MATERIAL SPECIFICATION
Enclosure Material: ABS (UL 94-5VA Rated) Weight: 1.6 Kg Dimensions: 199 x 62 x 290mm Protection: Rating IP20
2.2 ELECTRICAL SPECIFICATION
Supply: 120 AC 1ph ± 10% 50/60Hz 20A Relay Outputs: Single pole 4.4A 230V AC.
(resistive)
Battery Back-up: Lithium cell maintains data
memory and time clock for 10 years minimum at 25°C
2.3 PRESET DEFAULT FACTORY SETTINGS
Temperature Settings:
Day Temperature........................20°C
Night Temperature......................04°C
Override Up Temperature ..........02°C
Override Down Temperature ......04°C
Time Settings:
Switching Times ........................NONE
Override Limit ............................8 hours
Maximum Pre-heat Hours ..........3 hours
Date Format ..............................dd/mm/yy
Optional Settings:
HILO Switching Differential ........0°C
Security Codes:
Operators ..................................0000
2.4 KEYPAD LAYOUT
1. LCD Readout
2. Increase Temperature Set Point
3. Decrease Temperature Set Point
4. Enter Information
5. Delete
6. Scroll Forward
7. Return to Run Mode
8. Enter Program Mode
9. Time Override a Zone
ROBERTS GORDON®BZC 100 AND BZC 300 OPERATION MANUAL
FIGURE 1 - Keypad Layout (BZC 300 and BZC 100 have the same keypad layout)
1
6
5
4
2
3
7
8
9
Page 7
SECTION 2: SPECIFICATIONS
3
BZC Controller Quick Programming Guide
Read each section carefully before following the programming instructions.
®
Roberts-Gordon
1250 William Street, PO Box 44, Buffalo, NY, 14240-0044, USA. Tel: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
©
Roberts-Gordon Canada Inc.
241South Service Road West, Grimsby, Ontario, L3M 1Y7, Canada. Tel: 905.945.5403 Fax: 905.945.0511 Toll Free: 800.663.9025
Printed in the U.S.A www.rg-inc.com
Roberts-Gordon
Oxford Street, Bilston, West Midlands WV14 7EG UK Tel: +(44) 1902 494425 Fax: +(44) 1902 403200
P/N 10001600
1. DAY and NIGHT Temperature Settings
1.1 From the Normal (Run) Mode.
1.2 Press PROG. Enter the Operators Code 0000
- Press ENTER.
1.3 Choose 1 for Data.
1.4 Enter the Zone Number you wish to alter.
1.5 Enter the required DAY temperature (in degrees C or F as prompted). Enter new temperature using the numeric key­pad - Press ENTER.
1.6 Enter the required NIGHT temperature (in degrees C or F as prompted). Enter new temperature using the numeric key pad - Press ENTER.
1.7 The screen will now display switching times. If you wish to alter switching times, go to 2.6.
1.8 To accept the settings entered and exit the programming mode, press RUN to return to the menu.
1.9 Press RUN again to return to the Normal (Run) Mode.
2. Switching Times
2.1 From the Normal (Run) Mode.
2.2 Press PROG. Enter the Operators Code 0000
- Press ENTER.
2.3 Choose 1 for Data.
2.4 Enter the zone number you wish to alter.
2.5 Accept DAY and NIGHT temperatures by pressing ENTER (refer to 1.5 if you wish to alter the temperatures).
Note: Each zone must be programmed individually for up to four
ON/OFF periods per day.Each period is defined by START
and END times.
24 hour clock must be used throughout.
To set 1 time period only.
2.6 Enter the Start Time for period 1. e.g.08:00 - Press ENTER.
2.7 Enter the End Time for period 1. e.g. 17:00 - Press ENTER.
2.8 Unused periods must display start: 00.00 end: 00.00.
2.9 Periods 1 to 4 programmed for Monday can be copied to Tuesday by pressing the PROG key when Tuesday period 1 is displayed.This can be repeated for each subsequent day.
2.10 To accept the settings entered and to return to the Data Menu at any point, press RUN.
2.11 Press RUN again to return to the Normal (Run) Mode.
3. Override Time
3.1 From the Normal (Run) Mode.
3.2 Press the OVERRIDE key to enter the Override program. Enter a security code if required.
3.3 Enter the zone you wish to put into an Override.
3.4 Select 1 ON or 2 OFF.
Note: 1) ON - heating in the zone will operate to the required
DAY temperature.
2) OFF- heating in the zone will be in the NIGHT set back condition.
3.5 Enter the number of hours you wish to override. e.g. :01 The preset maximum number of hours is displayed in brack­ets.
3.6 Press ENTER.
3.7 When selection is complete, scrolling to the next screen (using the scroll key) in run mode will activate the override.
3.8 To end override before the set time is reached, repeat steps
3.1 to 3.5 and set the override Period to :00.
4.Override Temperature
4.1 From the Normal (Run) Mode.
4.2 Pressing the UP and DOWN ARROW KEYS allows you to increase or decrease the set point for any given zone within pre-set limits.
5. Current Time and Date
5.1 From the Normal (Run) Mode.
5.2 Press PROG. Enter the Operators Code 0000
- Press ENTER.
5.3 Choose 2 for Time.
5.4 Select the required date format. Press ENTER to accept this setting.
5.5 The current time will be displayed. Enter a new time, using 24 hour clock notation.
5.6 Press ENTER.
5.7 The current Date will be displayed. Enter a new date using the format selected.
5.8 Press ENTER. The Control will be returned to the Data Menu.
5.9 Press RUN to return to the Normal (Run) Mode.
6.Daylight Savings Time Adjustment
6.1 From the Normal (Run) Mode.
6.2 When adjustment is required depress the “1” key for a period of 5 seconds. Adjustment will be made automatically.
7. Holiday Periods
7.1 From the Normal (Run) Mode.
7.2 Press PROG. Enter the Operators Code 0000
- Press ENTER.
7.3 Choose 4 for Holidays. The control can be programmed for 5 holiday periods.
7.4 Enter a start date. Enter a date using the date format
selected (e.g. dd/mm/yy or mm/dd/yy) - Press ENTER.
7.5 Enter the length in number of days. e.g.05. - Press ENTER.
7.6 Repeat this for each holiday period to be set.
7.7 The Control will be returned to the Data Menu.
7.8 Press RUN to return to the Normal (Run) Mode.
Note: During the holiday period all the zones will operate at
NIGHT set back temperature.
8. Further Information
Further Programming and set up instructions can be found in the Operation and installation manuals listed below:
8.1 North America 120V
ROBERTS GORDON®BZC Controllers:
Part Number Manual 10011601NA 100 Installation and Service manual 10031600NA 300/100 Operation manual 10031601NA 300 Installation and Service manual 10071600NA 700 Operation manual 10071601NA 700 Installation and Service manual
8.2 Europe 230V
ROBERTS GORDON
®
BZC Controllers:
Part Number Manual 10011600UK 100 Operation manual 10011601UK 100 Installation and Service manual 10031600UK 300 Operation manual 10031601UK 300 Installation and Service manual 10071600UK 700 Operation manual 10071601UK 700 Installation and Service manual
FIGURE 2 - ROBERTS GORDON
®
BZC Controller Quick Programming Guide
Page 8
SECTION 3: VIEWING SCREEN DISPLAYS
In Normal (Run) Mode, the following options are available without the entry of a security code:
3.1 INFORMATION SCREENS
Pressing the SCROLL key will enable you to scroll through the zones one by one. The following screens will be displayed:
STATUS
ZONE INFORMATION
In Normal (Run) Mode, the following options are available with the entry of a security code:
3.2 TEMPERATURES SENSED BY ZONE FOR 24 HOUR PERIOD
Press PROG and enter the code 0376. Press ENTER.
The screen will now show:
By selecting 4, the status and recorded tempera­ture for zone 1 can be viewed for a 24 hour period in 15 minute intervals.
The screen will now show:
Use the ENTER key to view the incremental infor­mation recorded.
Press RUN to return to menu and press RUN again to return to Normal (Run) Mode.
3.3 HOURS RUN
Press PROG and enter the code 0376. Press ENTER.
The screen will now show:
By selecting 1, the running hours for the previous weeks for zone 1 can be viewed.
Press ENTER to return to selection screen. To view another zone, repeat the steps above.
Press RUN to return to menu and press RUN again to return to Normal (Run) Mode.
1) R1 2) R2 3) R3
4) S1 5) S2 6) S3
1) R1 2) R2 3) R3
4) S1 5) S2 6) S3
4
ROBERTS GORDON®BZC 100 AND BZC 300 OPERATION MANUAL
Day Date
MON 24-05-10
14.52.00 D D D
Time Status
Required Actual
Zone Title Zone Temp Zone Temp
ZONE1 (16) :15
HEAT ON
Heating
ON/OFF
Week #
WEEK 04 HOURS RUN 25.08
# running hours
Time Temperature
00.00 14 HEAT OFF NIGHT
Heating Status Time Status
Page 9
SECTION 4: PROGRAMMING OPTIONS
SECTION 4: PROGRAMMING OPTIONS
The following instructions cover the programming options for normal daily use. Please consult the ROBERTS GORDON
®
BZC 300 or BZC 100 Controller Installation Manual for initial set up information.
Zone choices, when displayed, only apply to the ROBERTS GORDON
®
BZC 300 Controller. Because the ROBERTS GORDON® BZC 100 Controller is a single zone controller, no selec­tion is necessary.
4.1 CORRECTING WRONG ENTRIES
4.1.1 If a wrong entry is made during the programming
sequence, continue following the instructions until the prompt returns to the menu.
4.1.2 The entry can be corrected by repeating the pro-
gramming sequence from the beginning.
4.1.3 Skip each correct screen by pressing ENTER.
4.1.4 When the incorrect entry is reached, type in the
correct entry and press ENTER. Continue press­ing ENTER to skip any following correct screens until the instructions direct you to return to the menu screen.
4.2 TEMPERATURE SETTING
There are two temperature settings for each zone. One setting is for the DAY temperature. This will be the set point temperature when the switching time is ON. One setting is for the NIGHT tempera­ture. This will be the set point temperature when the switching time is OFF.
Default Temperature Settings: Day Temperature 20°C Night Temperature 04°C
4.2.1 Press PROG and enter the code 0000.
Press ENTER. Enter 1 for DATA. Enter the zone number you wish to alter.
Each zone can have individual time and tempera­ture settings, therefore this procedure must be repeated for each zone to be altered.
4.2.2 The screen will now show:
Press two digits for the required temperature and then press ENTER.
4.2.3 The screen will now show:
Press two digits for the required temperature and then press ENTER.
4.2.4 The screen will now display switching times. If you
wish to alter switching times, go to
Page 5,
Section 4.3.2
.
4.2.5 To accept the settings and return to the DATA
menu, press RUN.
4.2.6 To alter the set points for further zones, repeat the
steps on
Page 5, Sections 4.2.1 to 4.2.3
.
4.2.7 If any mistakes were made during the program-
ming sequence, see
Page 5, Section 4.1
for cor-
rective action. When all the zones are correctly programmed,
return to Normal (Run) Mode by pressing RUN.
4.3 SWITCHING TIMES
4.3.1 Press PROG and enter the code 0000.
Press ENTER. Enter 1 for DATA. Enter the zone number you wish to alter.
Press ENTER to accept DAY and NIGHT temper­atures. To alter the temperatures, see
Page 5,
Section 4.2
.
4.3.2 The screen will now show:
Enter required switching times for Monday period
1. There are four switching periods per day for each individual zone.
4.3.3 The following example allows for one switching
period per day. Monday to Friday START 08:00 END 17:00
Saturday START 08:00 END 12:00 Sunday NO SWITCHING PERIOD
4.3.4 The screen will now show:
Enter start time 0800.
DAY PERIOD 1 MON S:00.00 E:00.00
ENTER THE REQUIRED
NIGHT TEMP. : 04
ENTER THE REQUIRED
DAY TEMP. : 20
5
DAY PERIOD 1 MON S:00.00 E:00.00
Page 10
6
Use 24 hour clock notation for the start of DAY TEMPERATURE (mistakes may be rectified by pressing DEL) and then press ENTER.
NOTE: When entering a start time, it is not necessary to
allow a warm-up period prior to the start of the required day temperature. This is automatically calculated by the ROBERTS GORDON
®
BZC 300 or BZC 100 Controller giving the required temper­ature at the time set.
4.3.5 The screen will now show:
Enter end time 1700. The screen will now show:
Press ENTER.
4.3.6 The screen will now show:
Press ENTER, to skip without altering the setting. The reason for leaving the start and end times
blank is because in this example we are only using one switching period per day.
Repeat as above for periods 3 and 4 for Monday.
4.3.7 The screen will now show:
Pressing the PROG key at this point will copy all of Monday’s switching times to Tuesday.
4.3.8 The screen will now show:
Pressing the PROG key at this point will copy the times from Tuesday to Wednesday. Repeat this for Thursday and Friday.
4.3.9 The screen will now show:
For Saturday, the switching period is different from the weekday settings. The new settings must be entered.
Enter start time 0800, Press ENTER. The screen will now show:
Enter end time 1200. The screen will now show:
Press ENTER. Leave the start and end times blank for periods 2,
3 and 4 because in this example we are only using one switching period on Saturday.
As no switching times are required for Sunday, press RUN to save the settings and return to the menu.
The process described above must now be repeated for each heating zone to be altered.
4.3.10 If any mistakes were made during the program-
ming sequence, see
Page 5, Section 4.1
for cor-
rective action.
4.3.11 Press RUN to return to Normal (Run) Mode. NOTE: If remote time enable is to be used, leave all
switching periods set to 00.00.
4.4 MANUAL OVERRIDE TEMPERATURE
4.4.1 To manually override temperature, first use the
SCROLL key to display the zone you wish to alter. Example for zone 1 is shown below:
The set point temperature appears in the brackets.
4.4.2 Pressing the UP(3) and DOWN(7) arrow keys will
increase or decrease the set point (in increments of 1
O
) for the displayed zone within pre-set limits.
NOTE: Changing the set point for the daytime tempera-
ZONE1 (20) :17
HEAT ON
DAY PERIOD 1 SAT
S:08.00 E:12.00
DAY PERIOD 1 SAT
S:08.00 E:00.00
DAY PERIOD 1 SAT
S:00.00 E:00.00
DAY PERIOD 1 WED S:00.00 E:00.00
DAY PERIOD 1 TUE
S:00.00 E:00.00
DAY PERIOD 2 MON S:00.00 E:00.00
DAY PERIOD 1 MON S:08.00 E:17.00
DAY PERIOD 1 MON S:08.00 E:00.00
ROBERTS GORDON®BZC 100 AND BZC 300 OPERATION MANUAL
Page 11
ture manually will only apply to the current switch­ing period.
4.5 MANUAL OVERRIDE TIME
4.5.1 From the Normal (Run) Mode, press the OVER-
RIDE key to enter the override program. Enter a security code if prompted.
Override will allow the heating system to be switched to day or night mode manually.
4.5.2 The screen will now show:
Select the zone required to be overridden.
4.5.3 The screen will now show:
Press 1 to select on (day settings) or 2 to select off (night settings).
4.5.4 The screen will now show:
Enter the number of hours you wish to override the zone for example :01.
The number in brackets is the maximum number in hours of the override period. This figure is preset and can only be altered by an authorized user.
4.5.5 The DEL key may be used to correct mistakes,
press ENTER when correct. The override time remaining will intermittenly appear on the screen.
4.5.6 When selection is complete, scrolling to the next
screen in run mode will activate the override com­mand.
4.5.7 To end override before the set time is reached, re-
enter override mode and set the override period to :00.
4.6 HOLIDAY PERIODS
4.6.1 From the Normal (Run) Mode:
Press PROG and enter the code 0000. Press ENTER. Enter 4 for HOLS.
Five periods can be preset by entering the start
date and then the number of days the holiday lasts.
4.6.2 The screen will now show:
Enter the date in the format selected under the time function (dd-mm-yy or mm-dd-yy).
Enter length (number of days duration of holiday).
4.6.3 The DEL key may be used to correct mistakes.
Press ENTER when correct.
4.6.4 If any mistakes were made during the program-
ming sequence, see
Page 5, Section 4.1
for cor-
rective action.
4.6.5 Press RUN to return to Normal (Run) Mode. NOTE: If ENTER is pressed at any display, then the cur-
rent setting will be retained.
NOTE: To cancel a holiday period in progress, repeat
4.6.1 to 4.6.3 changing the period in progress to 00 length.
4.7 CHANGE THE CURRENT TIME AND DATE
4.7.1 Press PROG and enter the code 0000.
Press ENTER. Enter 2 for TIME.
4.7.2 The screen will now show:
Press ENTER to leave the date format at the default day/month/year.
4.7.3 The screen will now show:
Enter a new time in (Hours: Minutes) in 24 hour clock notation.
Mistakes may be rectified by pressing DEL. Press ENTER when new time is correct.
TIME IS : 14.15 NEW TIME : .
DATE? D-M-Y (00)
M-D-Y (01) :00
HOLIDAY PERIOD 1 S: 00-00-00 L: 00
ENTER OVERRIDE
(08 HRS MAX) :00
OVERRIDE TO
1) ON OR 2) OFF
ENTER THE ZONE
NUMBER (1 - 3)
7
SECTION 4: PROGRAMMING OPTIONS
Page 12
4.7.4 The screen will now show:
Dates must be entered in the format selected. See
Page 8, Section 4.8.2
. Press ENTER.
4.7.5 The screen will now show:
Enter the appropriate number for the current day. Press ENTER when correct and the display will return to the Set-Up Menu.
4.7.6 Press RUN to return to Normal (Run) Mode.
If any mistakes were made during the program­ming sequence, see
Page 5, Section 4.1
for cor-
rective action.
4.8 SEASONAL TIME ADJUSTMENT
4.8.1 Pressing the number one button and holding it
down for 5 seconds during the months of March or April and October will give automatic seasonal cor­rection.
4.9 HOW TO CLEAR MEMORY
This facility will clear the logs of the hours run and monitor data.
4.9.1 Press PROG and enter the code 1805.
Press ENTER. Enter 4 for C.LOG
4.9.2 The screen will now show:
Press 1 for CLEAR MONITOR. Press the DEL key and a prompt for the passcode
will appear. Pressing any other key will abort the process.
4.9.3 The screen will now show:
Enter the code 0376 and press ENTER.
4.9.4 Press RUN to return to Normal (Run) Mode.
4.10 CHANGING THE SECURITY CODE
4.10.1 Press PROG and enter the code 0000.
Press ENTER. Enter 3 for CODE.
4.10.2 This is the section used to set the security code.
The screen will now show:
Pressing '1' will allow you to change the Manager Code
(Page 8, Section 4.10.3)
for programming the unit. Pressing '2' will allow you to change Override Code
(Page 8, Section 4.10.5)
.
4.10.3 Manager Code
The screen will now show:
Enter 4 digits for the new code (only asterisks will be shown when entering code).
4.10.4 Press RUN to return to Normal (Run) Mode.
4.10.5 Override Code
The screen will now show:
Selecting '00' here will allow you to override the time without needing a code. Selecting '01' will not allow you to override the time without knowing the security code.
4.10.6 Enter a new four digit code.
4.10.7 Press RUN to return to Normal (Run) Mode. NOTE: In the event that the code is forgotten, contact your
ROBERTS GORDON
®
independent distributor or Roberts-Gordon at (716) 852-4400 or (800) 828­7450 in the U.S., (905) 945-5403 in Canada or at www.rg-inc.com.
O/R CODE NO (00)
Y (01) SP(02) :00
CODE IS :0000 NEW CODE :
1) MANAGER CODE
2) OVERRIDE CODE
ENTER CODE TO CONTINUE : 0376
1) CLEAR MONITOR
2) VIEW CONFIG
ENTER DAY 01 = MON 07 = SUN :01
DATE IS :03-15-10 NEW ONE : - -
8
ROBERTS GORDON®BZC 100 AND BZC 300 OPERATION MANUAL
Page 13
SECTION 4: PROGRAMMING OPTIONS
9
4.11 CHANGING THE OVERRIDE LIMITS
4.11.1 Press PROG and enter the code 1805.
Press ENTER. Enter 1 for DATA.
4.11.2 These are the settings for limit of the override for
both time and temperature. The screen will now show:
Press ENTER to skip the calibration screens. There will be one displayed for each zone. The calibration of the sensors will be conducted by installer.
4.11.3 The screen will now show:
The default maximum override of 8 hours is dis­played. To alter the number, enter the new number and press ENTER.
4.11.4 The screen will now show:
The default upper offset limit of 2
O
C is displayed. To alter the number, enter the new number and press ENTER.
4.11.5 The screen will now show:
The default upper offset limit of 18
O
F or 5OC is dis­played. To alter the number, enter the new number and press ENTER.
4.11.6 If any mistakes were made during the program-
ming sequence, see
Page 5, Section 4.1
for cor-
rective action.
4.11.7 At the prompt for a zone to alter, press RUN to
return to the menu.
4.11.8 Press RUN again to return to Normal (Run) Mode
from the menu.
ENTER LOWER TEMP
OFFSET LIMIT : 05
ENTER UPPER TEMP
OFFSET LIMIT : 02
ENTER MAXIMUM OVERRIDE :08
CALIBRATION NO.1 SETTING :00
Page 14
Page 15
11
SECTION 5: THE ROBERTS GORDON®BZC
CONTROLLER WARRANTY
ROBERTS-GORDON WILL PAY FOR:
For 36 months from the date of purchase by the original consumer or 42 months from date of shipment by Roberts­Gordon, whichever occurs first: we will provide, free of charge, replacement parts for any part of the ROBERTS GORDON®BZC Controller that fails because of a manufac­turing or material defect.
ROBERTS GORDON®replacement parts are warrantied for the period of the original ROBERTS GORDON®BZC Controller Warranty.
ROBERTS-GORDON WILL NOT PAY FOR:
Service trips, service calls and labor charges.
Shipment of replacement parts.
Damage due to:
Failure to install, operate or maintain the ROBERTS GORDON®BZC Controller as directed in the Installation and Operation Manuals. You must follow requirements printed in these manuals.
Misuse, abuse, neglect or modification of the ROBERTS GORDON®BZC Controller in any way.
Improper service, use of replacement parts or acces­sories that are not specified by Roberts-Gordon.
Improper installation, or any relocation of the ROBERTS GORDON®BZC Controller after initial instal­lation.
Incorrect supply, accident, fire, flood, acts of God or other casualty.
Use of the ROBERTS GORDON®BZC Controller for other than its intended purpose.
Use of the ROBERTS GORDON®BZC Controller in a corrosive atmosphere or any atmosphere containing contaminants.
Shipping. Claim must be filed with carrier.
WARRANTY IS VOID IF:
The ROBERTS GORDON®BZC Controller is not installed by a electrician qualified in the installation of control sys­tems for heating equipment.
You cannot prove original purchase date and required annual maintenance history.
The data plate and/or serial number are removed, defaced, modified or altered in any way.
The ROBERTS GORDON®BZC Controller is transferred. This warranty is nontransferable.
Roberts-Gordon is not permitted to inspect the damaged ROBERTS GORDON®BZC Controller and/or component parts.
READ YOUR INSTALLATION MANUAL
If you have questions about your ROBERTS GORDON
®
BZC Controller, contact your installing professional. Should you need replacement parts or have additional questions, call or write Roberts-Gordon:
U.S.A.
1250 William Street P.O. Box 44 Buffalo, New York 14240-0044 Telephone: 716.852.4400 Fax: 716.852.0854
Canada
241 South Service Road, West Grimsby, Ontario L3M 1Y7 Telephone: 905.945.5403 Fax: 905.945.0511
On the web at:
www.rg-inc.com
Roberts-Gordon's liability, and your exclusive remedy, under this warranty or any implied warranty (including the implied warranties of merchantability and fitness for a particular purpose) is limited to providing replace­ment parts during the term of this warranty. Some juris-
dictions do not allow limitations on how long an implied war­ranty lasts, so this limitation may not apply to you. There are no rights, warranties or conditions, expressed or implied, statutory or otherwise, other than those contained in this warranty.
Roberts-Gordon shall in no event be responsible for incidental or consequential damages or incur liability for damages in excess of the amount paid by you for the ROBERTS GORDON®BZC Controller. Some jurisdic-
tions do not allow the exclusion or limitation of incidental or consequential damages, so this limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from jurisdiction to jurisdiction.
Roberts-Gordon shall not be responsible for failure to per­form under the terms of this warranty if caused by circum­stances out of its control, including but not limited to fire, flood, strike, government or court orders, unavailability of supplies, parts or power. No person is authorized to assume for Roberts-Gordon any other warranty, obligation or liabili­ty.
LIMITATIONS ON AUTHORITY OF REPRESENTATIVES:
No representative of Roberts-Gordon, other than an Executive Officer, has authority to change or extend these provisions. Changes or extensions shall be binding only if confirmed in writing by Roberts-Gordon's duly authorized Executive Officer.
S
ECTION 5: THE ROBERTS GORDON
®
BZC CONTROLLER WARRANTY
Page 16
Loading...