Roberts Gorden AG15ST, AG20ST, AG30ST, AG35ST, AG25ST Installation, Operation & Service Manual

...
Page 1
WARNING
FOR YOUR SAFETY If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
5. Extinguish any open flame.
6. Leave the building.
7. Immediately call your local gas supplier after leaving the building. Follow the gas supplier’s instructions.
8. If you cannot reach your gas supplier, call the Fire Department.
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clear­ances to combustibles away from heater.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
Roberts-Gordon Europe Limited
Unit A, Kings Hill Business Park Darlaston Road, Wednesbury West Midlands, WS10 7SH UK Telephone: +44(0)121 506 7700 Fax: +44(0)121 506 7701 Service Telephone: +44(0)121 506 7709 Service Fax: +44(0)121 506 7702
E-mail: uksales@rg-inc.com E-mail: export@rg-inc.com
www.brooder-heater.com
WARNING
Installation must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the installation, operation and service manual thoroughly before installing or servicing this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
© 2011 Roberts-Gordon Europe Ltd
Blackheat
®
AG
Vacuum Assisted
Linear and Double Linear
Gas Fired Heating
Systems
Installation, Operation &
Service Manual
For Agricultural Use
IP55 Protected Burner Box
AG15ST AG20ST AG25ST AG30ST AG35ST AG40ST AG45ST AG50ST
AG30DL AG40DL AG50DL AG60DL AG70DL
170103UK Rev B 04/11
Page 2
Page 3
TABLE OF CONTENTS
SECTION 1: Heater Safety ............................................2
1.1 Manpower Requirements ....................................2
1.2 IP55 Protection....................................................2
1.3 Safety Labels and Their Placement ....................2
SECTION 2: Installer Responsibility............................4
2.1 Low Level User Instructions................................4
2.2 Corrosive Chemicals...........................................4
2.3 National Standards and Applicable Codes .........4
SECTION 3: Clearance To Combustibles ....................5
3.1 Required Clearances to Combustibles ...............5
3.2 Clearance Data - Linear and Double Linear .......6
SECTION 4: Major Component Descriptions..............8
SECTION 5: General Suspension Details ...................9
SECTION 6: Linear & Double Linear Heater
Installation .............................................. 11
6.1 Linear Standard Parts List ................................ 11
6.2 Double Linear Standard Parts List....................14
6.3 Burner Tube Installation ...................................17
6.4 Coupling and Tube Assembly...........................17
6.5 Tube Clamp Package Installation .....................19
6.6 Reflector Installation .........................................20
SECTION 7: Burner & Fan Installation ......................22
7.1 Burner Installation.............................................22
7.2 IP55 Fan Assembly ..........................................23
7.3 Linear Fan Installation ......................................23
7.4 Double Linear Fan Installation ..........................24
SECTION 8: Optional Heater Accessories ................26
8.1 Reflector Side Extension Installation ................27
8.2 Decorative Grille Installation .............................28
8.3 Protective Grille Installation...............................29
8.4 Sports Hall Guard Installation...........................30
8.5 Undershield Installation ....................................31
8.6 Wall Mounting...................................................32
SECTION 9: Venting and Fresh Air Supply ...............33
9.1 Type C12 , C32 & C62 Appliance .....................33
9.2 Type B22 Appliance ..........................................33
9.3 Flue Installation ................................................33
9.4 Ventilation Requirements ..................................33
9.5 Fresh Air Supply ...............................................33
9.6 Outside Combustion Air Supply........................34
9.7 Common Duct...................................................35
SECTION 10: Gas Piping ............................................36
SECTION 11: Wiring ....................................................38
11.1 Typical External Wiring Diagram (Linear) ........38
11.2 Typical External Wiring Diagram
(Double Linear Option 1) ................................. 39
11.3 Typical External Wiring Diagram
(Double Linear Option 2) .................................39
11.4 Internal Wiring Diagram ..................................40
SECTION 12: Operation..............................................41
12.1 Heater Lockout Indication (Optional) .............. 41
12.2 Testing ............................................................ 42
12.3 Commissioning (Multiburner)..........................42
12.4 System Checks ............................................... 42
12.5 User Instructions.............................................42
SECTION 13: Servicing Instructions .........................43
13.1 Annual Procedure ...........................................43
13.2 Sealing Gaskets ............................................. 43
13.3 Component Removal......................................43
13.4 Maintenance Checklist.................................... 44
SECTION 14: Troubleshooting ................................... 46
14.1 Troubleshooting Flow Chart
(Linear and Double Linear)............................. 47
14.2 Manifold Gas Pressure Setting .......................49
SECTION 15: Replacement Parts............................... 50
15.1 Replacement Packages ..................................52
SECTION 16: Specifications.......................................53
16.1 Material Specifications....................................53
16.2 Heater Specifications......................................53
16.3 Venting Specifications.....................................53
16.4 Suspension Specifications..............................53
16.5 Controls Specifications ................................... 53
16.6 Linear Heater..................................................54
16.7 Double Linear Heater...................................... 54
16.8 Burner Specifications......................................55
© 2011
Roberts-Gordon Europe Limited
Printed in U.K.
Page 4
Page 5
TABLE OF FIGURES
Figure 1: Bottom and Back Panel Label Placement ........3
Figure 2: Control Side Label Placement..........................3
Figure 3: Linear & Double Linear, Horizontal Mounts......6
Figure 4: Linear & Double Linear, One Side Reflector ....6
Figure 5: Linear & Double Linear, Two Side Reflectors ...6 Figure 6: Linear & Double Linear, 2 Foot Deco Grille &
Protective Grille ................................................7
Figure 7: Undershield ** ..................................................7
Figure 8: Linear & Double Linear, Venting.......................7
Figure 9: Critical Hanger Placement .............................10
Figure 10: Linear General Assembly Overview............. 12
Figure 11: Linear Layout Overview................................13
Figure 12: Double Linear General Assembly Overview.15
Figure 13: Double Linear Layout Overview ...................16
Figure 14: Linear (Horizontal)........................................32
Figure 15: Linear (Rear View) .......................................32
Figure 16: Individual Flue Connection Detail.................34
Figure 17: Flue Connection Dimensions .......................34
Figure 18: Air Supply with Flue Configurations..............35
Figure 19: Gas Connection with Stainless Steel Flex
Connector.....................................................37
Figure 20: Sequence of Operation Chart ......................41
Figure 21: Burner Cup Position.....................................44
Figure 22: Linear Specifications....................................55
Page 6
Page 7
1
Product Approval
ROBERTS GORDON® appliances have been tested and CE certified as complying with the essential requirements of the Gas Appliance Directive, the Low Voltage Directive, the Electromagnetic Compatibility Directive and the Machinery Directive for use on natural gas and LPG when installed, commissioned and maintained in accordance with these instructions.
These instructions refer to appliances designed to operate in the European Union. Appliances designed for other countries (Non-European Union) are available on request. This appliance must be installed in accordance with the local and national codes in force and used
only in a sufficiently ventilated space, as specified in these instructions. Before installation, check that the local gas distribution systems, nature of gas and pressure, and
adjustment of the appliance are compatible.
Page 8
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
2
SECTION 1: HEATER SAFETY
Your Safety is Important to Us!
This symbol is used throughout the manual to notify you of possible fire, electrical or burn hazards. Please pay special attention when reading and following the warnings in these sections.
Installation, service and annual inspection of heater must be done by a registered installer/contractor qualified in the installation and service of gas-fired heating equipment.
Read this manual carefully before installation, operation or service of this equipment.
This heater is designed for heating nonresidential indoor spaces. Do not install in residential spaces. These instructions, the layout drawing, local codes and ordinances, and applicable standards that apply to gas piping, electrical wiring, venting, etc. must be thoroughly understood before proceeding with the installation.
Protective gear is to be worn during installation, operation and service. Thin sheet metal parts, such as the reflector portion of the heater and the various venting components, have sharp edges. To prevent injury, the use of work gloves is recommended. The use of gloves will also prevent the transfer of body oils from the hands to the surface of the reflector.
Before installation, check that the local distribution conditions, nature of gas and pressure, and adjustment of the appliance are compatible.
The heater must be applied and operated under the gen­eral concepts of resonable use.
This appliance is not intended for use by persons (includ­ing children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concern­ing use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do no play with the appliance.
For additional copies of the Installation, Operation and Service Manual, please contact Roberts-Gordon Europe Limited.
1. 1 M a n p ow er Re quirements
To p revent personal injury and damage to the heater, two persons will be required for installation.
1.2 IP55 Protection
The burner is certified to protection class of IP55. This means that the internal components of the burner are protected against extreme dusty atmosphere and water jets from all sides. Outside air supply and flue are mandatory for this heater. The standard exhaust fans mentioned in this manual do NOT have IP55 protection and must be outside the wet environment. If the fan is to be installed in the wet environment, a special IP54 protected fan must be used. Consult Roberts-Gordon LLC for alternative exhaust fans. Optional stainless steel burner box provides long life in the most corrosive applications. Always ensure that the environment to be heated is not of an explosive or flammable nature. For
more information, please consult your ROBERTS GORDON
®
representative.
In order to have trouble free performance of your BLACKHEAT
®
AG heater and maintain the IP55 protection, follow all instructions in this manual, especially the replacement of sealing gaskets.
1.3 Safety Labels and Their Placement
Product safety signs or labels should be replaced by the product user when they are no longer are legible. Please contact Roberts-Gordon LLC or your ROBERTS GORDON
®
independent distributor to obtain replacement signs or labels. See Page 3, Figure 1 through Page 3, Figure 2.
Page 9
SECTION 1: HEATER SAFETY
3
Figure 1: Bottom and Back Panel Label Placement
Figure 2: Control Side Label Placement
Logo Label
Fan/Burner Label
Bottom Panel
Rating Plate Label
Back Panel
Model No.
Serial No.
Appliance Type
Gas Pressure at Manifold
Normal Input Rating (Net Calorific Value)
Min. Input Rating (Net Calorific Value)
Country of Destination
Year of Production
Category
Orifice Size
Electrical Rating
V
Hz
W
Gas Type
Infrared Radiant Tube Heater
This applicance must be installed in accordance with the
rules in force, and used only in a sufficiently ventilated space.
Consult instructions before installation and use of this applicance.
0063
Model No.
Serial No.
Appliance Type
Gas Pressure at Manifold
Normal Input Rating (Net Calorific Value)
Min. Input Rating (Net Calorific Value)
Country of Destination
Year of Production
Category
Orifice Size
Electrical Rating
V
Hz
W
Gas Type
Infrared Radiant Tube Heater
This applicance must be installed in accordance with the
rules in force, and used only in a sufficiently ventilated space.
Consult instructions before installation and use of this applicance.
0063
Description Part Number
Logo Label 91033200 Rating Plate Label 91031300 Fan/Burner Label 91033300
Top Panel
Gas Connection Label
Description Part Number
Logo Label 91033200 Wiring Diagram Label 91031404 Gas Connection Label 91018122
Page 10
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
4
SECTION 2: INSTALLER RESPONSIBILITY
• To install the heater, as well as the gas and electrical supplies, in accordance with applicable specifications and codes. Roberts-Gordon LLC recommends the installer contact a local Building Inspector or Fire Marshal for guidance.
• To use the information given in a layout drawing and in the manual together with the cited codes and regulations to perform the installation.
• To install the heater in accordance with the clear­ances to combustibles.
• To furnish all needed materials not furnished as standard equipment.
• To plan location of supports.
• To provide access to burners for servicing on all sides, for burner removal.
• To provide the owner with a copy of this Installation, Operation and Service Manual.
• To never use heater as support for ladder or other access equipment and never hang or suspend any­thing from heater.
• To ensure there is adequate air circulation around the heater and to supply air for combustion, ventilation and distribution in accordance with local codes.
To ensure the heater is placed in an approved application.
2.1 Low Level User Instructions
In all situations, clearances to combustibles must be maintained. Signs should be posted in storage areas to specify the maximum stacking height of items placed below heater to maintain required clearances to combustibles. Minimum clearances must be maintained from vehicles parked below the heater. Caution should be used when running the system near combustible materials such as wood, paper, rubber, etc. Consideration should be given to partitions, storage racks, hoists, building construction, etc.
A laminated wall tag is available for the heater as a permanent reminder of the safety instructions and the importance of the required clearances to combustibles. Please contact Roberts-Gordon LLC or your ROBERTS GORDON
®
independent distributor to obtain the wall tag. Affix the tag by peeling off the backing of the adhesive strips on the rear surface and position the tag on a wall near the heater (e.g. thermostat).
A copy of the wall tag (P/N 91037912) is illustrated on the back cover. This copy of the wall tag can be affixed on the wall near the heater. Know your model number and installed configuration. Model number and installed configuration are found on the burner and in the Installation, Operation and Service Manual. Write the largest clearance dimensions with permanent ink according to your model number and configuration in the open spaces on the tag.
2.2 Corrosive Chemicals
Roberts-Gordon LLC cannot be responsible for ensuring that all appropriate safety measures are undertaken prior to installation; this is entirely the responsibility of the installer. It is essential that the contractor, the sub­contractor, or the owner identifies the presence of combustible materials, corrosive chemicals or halogenated hydrocarbons* anywhere in the premises.
* Halogenated Hydrocarbons are a family of chemical com­pounds characterized by the presence of halogen elements (fluorine, chlorine, bromine, etc.). These compounds are frequently used in refrigerants, cleaning agents, solvents, etc. If these compounds enter the air supply of the burner, the lifes­pan of the heater components will be greatly reduced. An out­side air supply must be provided to the burners whenever the presence of these compounds is suspected. Warranty will be invalid if the heater is exposed to halogenated hydrocarbons.
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with the latest revision of the applicable standards and national codes. This refers also to the electric, gas and venting installation. Note: Additional standards for installations in Public Garages, Aircraft Hangars, etc. may be applicable.
The heater must not be operated in environmental temperatures below 0° C.
CAUTION
Product Damage Hazard
Do not use heater in area containing corrosive chemicals.
Refer to appropriate Material Safety Data Sheets (MSDS).
Failure to follow these instructions can result in product damage.
Page 11
SECTION 3: CLEARANCE TO COMBUSTIBLES
5
SECTION 3: CLEARANCE TO COMBUSTIBLES
3.1 Required Clearances to Combustibles
Clearances are the required distances that combustible objects must be away from the heater to prevent fire hazards. Caution should be used when running the system near combustibles. Combustibles are materials that may catch on fire and include common items such as
wood, paper, rubber, fabric, etc. Maintain clearances to combustibles at all times for safety.
Clearances for all heater models are located on Page 6, Figure 3 through Page 7, Figure 8 in this manual. Check
the clearances on each burner for the model heater being installed to make sure the product is suitable for your application and the clearances are maintained. Read and follow the safety guidelines below:
• Keep petrol or other combustible materials including flammable objects, liquids, dust or vapours away from this heater or any other appliance.
• The stated clearances to combustibles represents a surface temperature of 32°C (90°) above room tem- perature. Building materials with a low heat tolerance (such as plastics, vinyl siding, canvas, tri-ply, etc) may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that adja­cent materials are protected from degradation.
• Maintain clearances from heat sensitive material, equipment and workstations.
• Maintain clearances from vehicles parked below the heater.
• Maintain clearances from swinging and overhead doors, overhead cranes, vehicle lifts, partitions, storage racks, hoists, building construction, etc.
• In locations used for the storage of combustible mate­rials, signs must be posted to specify the maximum permissible stacking height to maintain required clearances from the heater to the combustibles. Signs must be posted adjacent to the heater thermostat. In the absence of a thermostat, signs must be posted in a conspicuous location.
• Consult local Building Inspector, Fire Insurance Carrier or other authorities for approval of proposed installation when there is a possibility of exposure to combustible airborne materials or vapours.
• Hang heater in accordance to the minimum suspension requirements on Page 9, Section 5.
WARNING
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clearances to combustibles away from heater.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
Page 12
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
6
3.2 Clearance Data - Linear and Double Linear
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, tees, elbows and crosses.
2. Clearances B, C and D can be reduced by 50% after 7500 mm of tubing downstream from the burner.
3. All measurements are in millimeters.
FIGURE 3: LINEAR & DOUBLE LINEAR, HORIZONTAL MOUNTS
Model
AG15ST
AG30DL
AG20ST
AG40DL
AG25ST
AG50DL
AG30ST
AG60DL
AG35ST
AG70DL
AG40ST
AG45ST
AG50ST
A 150 150 150 150 150 150 200 200
B 1024 1116 1116 1173 1346 1403 1472 1530
C 1570 1650 1650 1780 1930 1970 2010 2080
D 1024 1116 1116 1173 1346 1403 1472 1530
FIGURE 4: LINEAR & DOUBLE LINEAR, ONE SIDE REFLECTOR
Model
AG15ST
AG30DL
AG20ST
AG40DL
AG25ST
AG50DL
AG30ST
AG60DL
AG35ST
AG70DL
AG40ST
AG45ST
AG50ST
A 150 150 150 150 150 150 200 200
B 265 265 265 265 265 265 265 265
C 1580 1760 1760 1930 2090 2130 2160 2240
D 1380 1587 1587 1725 1909 1967 2024 2139
A
C
D
B
FIGURE 5: LINEAR & DOUBLE LINEAR, TWO SIDE REFLECTORS
Model
AG15ST
AG30DL
AG20ST
AG40DL
AG25ST
AG50DL
AG30ST
AG60DL
AG35ST
AG70DL
AG40ST
AG45ST
AG50ST
A 150 150 150 150 150 150 200 200
B 678 736 736 793 943 989 1024 1173
C 1660 1810 1810 1960 2110 2160 2210 2320
D 678 736 736 793 943 989 1024 1173
A
C
D
B
Page 13
SECTION 3: CLEARANCE TO COMBUSTIBLES
7
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, tees, elbows and crosses.
2. Clearances B, C and D can be reduced by 50% after 7500 mm of tubing downstream from the burner.
3. All measurements are in millimeters.
** When installed in the first 3 m.
FIGURE 6: LINEAR & DOUBLE LINEAR, 2 FOOT DECO GRILLE & PROTECTIVE GRILLE
Model
AG15ST
AG30DL
AG20ST
AG40DL
AG25ST
AG50DL
AG30ST
AG60DL
AG35ST
AG70DL
AG40ST
AG45ST
AG50ST
A 150 150 150 150 150 150 200 200
B 1024 1116 1116 1173 1346 1403 1472 1530
C 1570 1650 1650 1780 1930 1970 2010 2080
D 1024 1116 1116 1173 1346 1403 1472 1530
A
C
D
B
FIGURE 7: UNDERSHIELD **
Model
AG15ST
AG30DL
AG20ST
AG40DL
AG25ST
AG50DL
AG30ST
AG60DL
AG35ST
AG70DL
AG40ST
AG45ST
AG50ST
A 150 150 150 150 150 150 - -
B 1139 1173 1461 1461 1576 1610 - -
C 840 965 11 20 112 0 1220 1270 - -
D 1139 1173 1461 1461 1576 1610 - -
A
C
D
B
FIGURE 8: LINEAR & DOUBLE LINEAR, VENTING
Model
AG15ST
AG30DL
AG20ST
AG40DL
AG25ST
AG50DL
AG30ST
AG60DL
AG35ST
AG70DL
AG40ST
AG45ST
AG50ST
E 1000 1000 1000 1000 100 0 1000 1000 1000
F 500 500 500 500 500 500 500 500
Radiant tubes
Fan
Unvented
Vented
E
F
Page 14
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
8
SECTION 4: MAJOR COMPONENT DESCRIPTIONS
Burner (shown with Tube Gasket)
Must be installed with the flame observation window facing down.
Reflector (Aluminium or Stainless Steel)
Alternate overlap as shown on overview. Minimum overlap is 160 mm.
Coupling Assembly with Lock
Reflector End Cap
Punch out center section to accommodate tube.
Fan Assembly (Includes Flange)
Fan assembly is attached to the last section of tubing (fan tube).
Tube and Reflector Hanger
Suspend system from these hangers.
Flex Gas Line
Tube
Heat treated aluminised tube supplied in 3000 mm lengths.
Burner Tube
Supplied in 3000 mm lengths. Burner tube is always the first tube after the burner.
Reflector Support Strap, Wire Form & #8 x 3/4 Screw
Fan Tube with Internal Swirler
Supplied in 3000 mm lengths. Fan tube is always the last tube on the heater where the fan is attached. The swirler is welded inside of the tube end.
Fan Flange Assembly and Screws
Height Adjuster
Bow Shackle
Tee Assembly
Damper Flange Assembly
For use on Multiburner Systems.
Tube and Reflector Hanger with Clamp Package
Position this hanger no more than 100 mm away from the burner assembly.
Spring Hook
S-hook
Page 15
SECTION 5: GENERAL SUSPENSION DETAILS
9
SECTION 5: GENERAL SUSPENSION DETAILS
To ensure your safety, and comply with the terms of the warranty, all units must be installed in accordance with
these instructions.
The gas or the electrical supply lines must not be used to support the heater.
Do not locate the gas or electric supply lines directly over the path of the flue products from the heater.
The heater must be installed in a location that it is readily accessible for servicing.
The heaters must be installed in accordance with clearances to combustibles as indicated on the rating plate and in this manual.
The minimum and maximum gas inlet pressures must be maintained as indicated on the rating plate. Typical installation configurations are shown in Figure 9.
NOTE: Some models may receive S-hooks (P/N
91907302) or spring hooks (P/N91903300), rather than bow shackles.
WARNING
Severe Injury Hazard
Secure burner to burner tube with bolts and lockwashers.
Hang heater with materials with a minimum working load of 75 lbs (33 kg).
Failure to follow these instructions can result in death, injury or property damage.
WARNING
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
Failure to follow these instructions can result in injury.
Page 16
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
10
Figure 9: Critical Hanger Placement
Description Part Number
Burner Tube 03051100 S-hook 91907302 Spring Hook 91903300 Bow Shackle E0007576 Tube/Reflector Hanger 03090101
Page 17
SECTION 6: LINEAR & DOUBLE LINEAR HEATER INSTALLATION
11
SECTION 6: LINEAR & DOUBLE LINEAR HEATER INSTALLATION
The figures in this section provide a general overview of component placement in a BLACKHEAT
®
AG Linear and Double Linear system. The location of some components such as supports and couplings is crucial for proper installation. Assemble the heater components as shown on Page 12, Figure 10.
For optional reflector configurations for linear heaters see Page 6, Figure 3 through Page 7, Figure 8. Install appropriate suspension hardware, beam clamps, chain or rod at predetermined locations. Adjustments of chain length will provide uniform pitch.
If any step is unclear, please contact Roberts-Gordon LLC at +44 (0) 121 506 7700.
6.1 Linear Standard Parts List
* PVC coating must be removed prior to installation.
** Some models may receive S-hooks (P/N 91907302) or spring hooks (P/N91903300), rather than bow shackles.
Part No. Description
AG15ST
AG20ST
AG25ST
AG30ST
AG35ST
AG40ST
AG45ST
AG50ST
035XXXXX Burner Assembly (Input and Fuel Varies) 1 1 111111
07260051 Fan Package 1 IP55 1 1 1 1 1 - - -
07260053 Fan Package 3 IP55 - ----111
03051100Burner Tube, 100 mm x 3048 mm 11111111
91409408Tube, 100 mm x 3048 mm -1122233
S5127WFan Tube, 100 mm x 3048 mm, with 3048 mm Swirler -1111111
S5134WFan Tube, 100 mm x 3048 mm, with 2134 mm Swirler 1-------
01329600Standard Coupling Assembly 12233344
01329700Coupling Lock 12233344
02750303Reflector, Aluminium, 2439 mm 34466677
027503SSReflector, Stainless Steel, 2439 mm (Optional)* 34466677
02750800Reflector End Cap, Aluminium 22222222
027508SHReflector End Cap, Stainless (Optional)* 22222222
03090101Tube and Reflector Hanger, Wide Pattern 34455566
01318901Tube Clamp Package (including Nut, Washer & Bolt) 11111111
91908004Wire Form 23355566
94320812 Screw #8 x 3/4, (Goes with 03050001) 4 6 6 10 10 10 12 12
03050001Reflector Support Strap, Wide Pattern 23355566
E0007576Bow Shackle** 34455566
91107720 U-Clip Package (20 Pieces) 1 1 111111
Page 18
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
12
Figure 10: Linear General Assembly Overview
Vent Cap or
Bird Screen
Outside Wall
Fan Tube
Reflector
Reflector End Cap
Reflector Support
Burner
Coupling
U-Clips
Burner Tube
Tube and Reflector Hanger
Tube Clamp
Package
Fan Assembly*
(For Single Heater)
Damper Assembly
(Required for Multiburner)
*NOTE: Locate fan away from wet environment
or use the IP54 protected fan.
Fresh Air
Supply
Internal Swirler
Weld Spot
Page 19
SECTION 6: LINEAR & DOUBLE LINEAR HEATER INSTALLATION
13
Figure 11: Linear Layout Overview
Model AG15ST AG20ST AG25ST AG30ST AG35ST AG40ST AG45ST AG50ST
Reflector Overlap (approx.)
700 mm 250 mm 250 mm 530 mm 530 mm 530 mm 330 mm 330 mm
a = reflector width (not shown) - 365 mm b = end cap to burner/fan - 50 mm c = end cap to hanger - 50 mm d = distance first hanger - 2290 mm
e = distance typical between hangers - 3050 mm
f = burner height - 241 mm
g = burner length - 445 mm
Burner
Reflector
Tube
Tube/Reflector Hanger
Coupling Assembly
Fan Assembly
LEGEND
Damper Assembly
AG20ST AG25ST
c
b
de
b
e
AG30ST AG35ST AG40ST
c
b
de
b
e e
AG45ST AG50ST
c
b
de
b
e e e
g
c
b
de
b
AG15ST
f
g
f
g
f
g
f
Page 20
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
14
6.2 Double Linear Standard Parts List
* PVC coating must be removed prior to installation.
** Some models may receive S-hooks (P/N 91907302) or spring hooks (P/N91903300), rather than bow shackles.
Part No.
Description
AG30DL
AG40DL
AG50DL
AG60DL
AG70DL
035XXXXX Burner Assembly (Input and Fuel Varies) 2 2 2 2 2
07260053 Fan Package 3 IP55 1 1 1 1 1
03051100 Burner Tube, 100 mm x 3048 mm 2 2 2 2 2
91409408 Tube, 100 mm x 3048 mm - 2 2 4 4
S5127W Fan Tube, 100 mm x 3048 mm, with 3048 mm Swirler - 2 2 2 2
S5134W Fan Tube, 100 mm x 3048 mm, with 2134 mm Swirler 2 - - - -
E0009170 Tee, 100 mm x 100 mm x 100 mm 1 1 1 1 1
01329600 Standard Coupling Assembly 6 8 8 10 10
01329700 Coupling Lock 6 8 8 10 10
02750303 Reflector, Aluminium, 2439 mm 6 8 8 12 12
027503SS Reflector, Stainless Steel, 2439 mm (Optional)* 6 8 8 12 12
02750800 Reflector End Cap, Aluminium 4 4 4 4 4
027508SH Reflector End Cap, Stainless (Optional)* 4 4 4 4 4
03090101 Tube and Reflector Hanger, Wide Pattern 6 8 8 10 10
01318901 Tube Clamp Package (including Nut, Washer & Bolt) 2 2 2 2 2
91908004 Wire Form 4 6 6 10 10
03050001 Reflector Support Strap, Wide Pattern 4 6 6 10 10
E0007576 Bow Shackle** 6 8 8 10 10
91107720 U-Clip Package (20 Pieces) 2 2 2 2 2
E0007582 Height Adjuster 6 8 8 10 10
94320812 Screw #8 x 3/4, (Goes with 03050001) 8 12 12 20 20
Page 21
SECTION 6: LINEAR & DOUBLE LINEAR HEATER INSTALLATION
15
Figure 12: Double Linear General Assembly Overview
Vent Cap or
Bird Screen
Fresh Air
Supply
1200 mm approx.
Fan Tube
Burner
Fresh Air
Supply
Tube Clamp Package
Reflector
Reflector End Cap
Reflector Support
Coupling
Fan Assembly*
Burner Tube
Tube and Reflector Hanger
Tube Clamp
Package
U-Clips
Optional Tube Length
*NOTE: Locate fan away from wet environment
or use the IP54 protected fan.
Internal Swirler
Weld Spot
Outside Wall
Page 22
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
16
Figure 13: Double Linear Layout Overview
Model AG30DL AG40DL AG50DL AG60DL AG70DL
Reflector Overlap (approx.)
700 mm 250 mm 250 mm 530 mm 530 mm
Tee Assembly
Burner
Reflector
Tube
Tube/Reflector Hanger
Coupling Assembly
Fan Assembly
LEGEND
AG60DL AG70DL
c
b
de
b
e e
Repeated
Opposite
Side
AG40DL AG50DL
c
b
de
b
e
Repeated
Opposite
Side
AG30DL
g
c
b
de
b
f
Repeated
Opposite
Side
a = reflector width (not shown) - 365 mm b = end cap to burner/fan - 50 mm c = end cap to hanger - 50 mm d = distance first hanger - 2290 mm
e = distance typical between hangers - 3050 mm
f = burner height - 241 mm
g = burner length - 445 mm
g
f
g
f
Page 23
SECTION 6: LINEAR & DOUBLE LINEAR HEATER INSTALLATION
17
Step 6.3 Burner Tube Installation
Step 6.4 Coupling and Tube Assembly
Description Part Number
Burner Tube 03051100 Bow Shackle E0007576 Tube/Reflector Hanger 03090101
Tube
Tube
Orient coupling so that
the impact block is in the
2:00 or 10:00 oclock
positions
Closed
Open
Ta b
76 mm to 101 mm
Slide Bar
Coupling
Wide End
Coupling
Tube
Slide Bar
A
Close coupling
with tab
B
Start slide bar/coupling lock
onto coupling
C
Insert tubes into coupling
D
Tighten coupling to join tubes
Description Part Number
Coupling 01329600 Slide Bar/Coupling Lock 01329700 Tube 91409408
Page 24
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
18
Step 6.4.1 Coupling and Tube Assembly (Continued)
Step 6.4.2 Coupling and Tube Assembly (Continued)
Incorrect Slide Bar
position
Correct Slide Bar
dimensions
± 50 mm
Drive slide bar until tight. End of slide bar should be within tolerance listed below.
• Repeat Step 6.4 A - D until all tubes are assembled. See Page 18, Section 6.4.2 shown below.
Tighten slide bar as shown below.
3050 mm Typ
± 250 mm
2290 mm
± 250 mm
Total Overall Tube Length
Weld spot
at end of
heat exchanger
Model Overall Tube Length (mm)
Number
of Tubes
AG15ST 6000 2 AG20ST 9000 3 AG25ST 9000 3 AG30ST 12,000 4 AG35ST 12,000 4 AG40ST 12,000 4 AG45ST 15,000 5 AG50ST 15,000 5 AG55ST 18,000 6
Page 25
SECTION 6: LINEAR & DOUBLE LINEAR HEATER INSTALLATION
19
Step 6.5 Tube Clamp Package Installation
Description Part Number Tube Clamp Package01318901
Tube Clamp 01396801
Bolt 97113940 Flat Washer 95211600
Nut 92113900
Page 26
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
20
Step 6.6 Reflector Installation
WARNING
Fire Hazard
Support reflector with reflector hanger and support strap.
Reflector must not touch tube.
Failure to follow these instructions can result in death, injury or property damage.
Description Part Number
Tube/Reflector Hanger 03090101 Burner Tube 03051100 Reflector 02750303
Page 27
SECTION 6: LINEAR & DOUBLE LINEAR HEATER INSTALLATION
21
Step 6.6.1 Reflector, U-clip and Reflector Support Installation
The pictorial drawings of the heater construction in Section 6 are schematic only and provide a general guideline of where hangers, reflector supports and u-clips are to be installed.
To ensure proper expansion and contraction movement of the reflectors, a combination of u-clips and reflector
supports are used. The positioning of reflector supports and u-clips depend on the individual installation. Use either pop rivets or sheet metal screws instead of u-clips when installing end caps and joint pieces in areas where impact and high wind may be a factor. The following rules must be observed:
Description Part Number Reflector Support Package 03050011
Wire Form 91908004 Reflector Support Strap 03050000 Screw #8 x 3/4 94320812 U-clip Package 91107720 Reflector End Cap 027508XX
Page 28
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
22
SECTION 7: BURNER & FAN INSTALLATION Step 7.1 Burner Installation
Description Part Number
Bolt 94273914 Lock Washer 96411600 Gasket 02568200 Burner 035XXXXX
NOTE: Tube Clamp Package not shown for clarity.
For details, see Page 19, Step 6.5.
Page 29
SECTION 7: BURNER & FAN INSTALLATION
23
Step 7.2 IP55 Fan Assembly
Step 7.3 Linear Fan Installation
Fan Assembly
Vent Adapter
Nut
(Torque:
2 Nm
18 in lb)
Note: Apply Silicone (Recommended)
Install vent adapter with clamp in the up position.
Wire Gland
(tighten securely)
Washer
Description Part Number
Fan Assembly 072600XX Vent Adapter C1323B Nut M6 C0061B Washer M6 C0039B
Fan Tube
Fan Assembly
Tighten securely until tube cannot be removed.
Weld Spot
Page 30
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
24
Step 7.4 Double Linear Fan Installation
Step 7.4.1 Double Linear Fan Installation (Continued)
Te e
Fan Assembly
Tighten securely until tube cannot be removed.
Page 31
SECTION 8: OPTIONAL HEATER ACCESSORIES
25
SECTION 8: OPTIONAL HEATER ACCESSORIES
WARNING
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
Failure to follow these instructions can result in injury.
Page 32
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
26
8.1 Reflector Side Extension Installation Step 8.1.1 Bracket Installation
Step 8.1.2 Side Reflector Installation
Description Part Number Reflector Side Extension Package S7377K
Reflector Side Extension 01368000 Retainer Clips 02751200 Reflector Side Extension 01329910
Page 33
SECTION 8: OPTIONAL HEATER ACCESSORIES
27
8.2 Decorative Grille Installation Step 8.2.1 Grille Installation
Step 8.2.2 Frame Shield Installation
Step 8.2.3 Reflector Side Extension Installation for Decorative Grilles
Description Part Number
Aluminium Grille 91407000
Description Part Number
Deco Grille Shield 01365900
Distance "A" Extension
Minimum Maximum Part No. Width
40 mm 150 mm 01370408 200 mm 150 mm 260 mm 01370412 300 mm 260 mm 370 mm 01370416 400 mm
Description Part Number
Reflector Side Extension 01370412
Page 34
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
28
8.3 Protective Grille Installation Step 8.3.1 Silicone Cap Installation
Step 8.3.2 Grille End Cap Installation
Step 8.3.3 Grille Installation
Silicone Cap
Grille Finger
Description Part Number
Grille Section 08050001 Grille End Cap 08050002 Silicone Cap 91915951-6P
Bend up 90°.
Pull outward.
Grille
Grille End Cap
AB
CD
Grille
Grille End Cap
Reflector
Final Grille Section
1010 mm
Page 35
SECTION 8: OPTIONAL HEATER ACCESSORIES
29
8.4 Sports Hall Guard Installation Step 8.4.1 Grille Installation
Step 8.4.2 Fastener Installation
Step 8.4.3 Mesh Guard Connection
Description Part Number
Mesh Guard 2438 mm E0009855 Mesh Guard 1524 mm C2329B Strap Stainless Steel S5218W
Description Part Number
Nut Spire C1088B Screw #8 x 3/8 C1089B
Page 36
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
30
8.5 Undershield Installation Step 8.5.1 Hanger Installation
Step 8.5.2 Undershield Installation
Step 8.5.3 Adjust Undershield Height
Reflector
Tube
Assembly Hanging Bracket
Stud
Hex Nut
Description Part Number Undershield Reflector Package 1010 mm S7399K
Assembly Hanging Bracket C0318B Stud M6 x 90 C0693B Nut M6 C0090B
Undershield Reflector
Hex Nut
Shield Support Bracket
Description Part Number Undershield Reflector Package 1010 mm S7399K
Undershield Reflector 1010 mm C0521B Nut M6 C0090B Shield Support Bracket 02751700
1010 mm
Page 37
SECTION 8: OPTIONAL HEATER ACCESSORIES
31
8.6 Wall Mounting
Install wall mounting brackets at the height shown in the layout drawing provided by the estimator. Space wall mounting brackets and hangers as indicated by dimensions d, e and f in the relevant Layout Overview drawing for your heater. For Linear heaters see Page 13,
Figure 11, for Double Linear heaters see Page 16, Figure
13.
8.6.1 Hardware Installation
The wall mounting brackets must be attached to a suitable wall through all mounting holes. Screw sizes less than M8 (5/16") may not be used. In order for the wall
mounting brackets to adequately carry the weight of the heater, it must be installed with best building practice.
Figure 14: Linear (Horizontal)
Figure 15: Linear (Rear View)
Model Quantity of Wall Mounting Brackets
AG15ST 3 AG20ST 4 AG25ST 4 AG30ST 5 AG35ST 5 AG40ST 5 AG45ST 6 AG50ST 6
Page 38
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
32
SECTION 9: VENTING AND FRESH AIR SUPPLY
9.1 Type C
12
, C32 & C62 Appliance
Room Sealed
The heaters are designed to be installed as room sealed appliances. The flue and air intake are run as separate pipes to the special concentric wall or roof terminal. The wire mesh inside the fresh air adapter on the heater must be removed prior to installation. See Page 34, Figure 18.
9.2 Type B22 Appliance
The flue must be fitted with a low resistance terminal. See Page 34, Figure 18.
9.3 Flue Installation
The fan outlet may discharge vertically or horizontally. Connection should be made using 100 mm minimum diameter Aluminium or Stainless Steel flue material to National Standard and must be adapted to insert into the 100 mm flue adapter. Both fresh air supply and flue duct shall not exceed 10,000 mm. AG15 and AG20 flue must be insulated if longer than 5,000 mm. AG25 flue must be insulated if longer than 8,000 mm. For each 90° bend, subtract 1,000 mm from the maximum flue length. The
flue must be self supporting. Suitable terminals must be fitted for horizontal and vertical flue.
In order to locate fans that are not IP54 protected away from the wet environment, a 100 mm diameter extension tube between the heat exchanger end and fan must be installed. This length must be subtracted from the maximum flue length.
Fans
Horizontal Vert ical
83 BWLG 190 x 75 (hole) 150 mm dia. 90 BWTL 190 x 75 (hole) 150 mm dia.
9.4 Ventilation Requirements
Detailed recommendations for air supply are given in the relevant National Standards. There must be an adequate supply of air for both combustion and general ventilation. Air vents should have negligible resistance. Do not locate air vents where they can be easily blocked or flooded, or adjacent to any flues or extraction systems carrying flammable vapour.
9.5 Fresh Air Supply
The burner is equipped with a fresh air adapter which has a silicone gasket incorporated. This adapter accepts tubes with 100 mm outside diameter.
WARNING
Carbon Monoxide Hazard
Multiburner systems are not approved for unvented use and must be vented outdoors.
Unitary heaters installed unvented must be interlocked with sufficient building exhaust.
Heaters must be installed according to the installation manual.
Failure to follow these instructions can result in death or injury.
WARNING
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
Failure to follow these instructions can result in injury.
Fresh Air Adapter
Fresh Air
Supply Duct
100 mm OD
Page 39
SECTION 9: VENTING AND FRESH AIR SUPPLY
33
Figure 16: Individual Flue Connection Detail
Figure 17: Flue Connection Dimensions
9.6 Outside Combustion Air Supply
Clean air must be ducted into the burner box through the 100 mm diameter spigot on the back of the burner box.
See Page 32, Section 9.3 for recommendations on duct length. Air duct should be as straight as possible. Consult the manufacturer if more than 1 x 90° bend is necessary. The fresh air duct must be self supporting.
9.6.1 Air Supply Requirements
When fresh air duct is used, follow one of these rules:
• The flue must penetrate the roof while fresh air can penetrate any wall. (See Figure 18, A)
• The flue and fresh air supply must penetrate the roof at a minimum of 1,000 mm apart. (See Figure 18, B)
• The flue must penetrate 1,000 mm higher than the fresh air inlet on the same wall. (See Figure 18, C)
Fan Tube
Flue Pipe
Flue Adapter
Fan Assembly
Screw
(Torque:2 Nm
18 in lb)
Lockwasher
Nut
90710051 90710052 90710053
ABC
76 mm 95 mm 31 mm
82 mm 101 mm 38 mm 82 mm 101 mm 38 mm
Fan Part Number
Page 40
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
34
Figure 18: Air Supply with Flue Configurations
9.7 Common Duct
When using a common air inlet duct, always ensure that the area of the common air inlet duct represents the area of all air ducts.
C
52
C
32
C12 C32 C
62
B
22
C
12
Page 41
SECTION 10: GAS PIPING
35
SECTION 10: GAS PIPING
It is important that the gas supply pipe and electrical connections do not support any of the heater’s weight.
Installation pipes should be fitted in accordance with National Standards. Pipe work from the meter to the heater(s) must be of adequate size. Pipes of smaller size than the heater inlet gas connection should not be used.
Install the gas hose as shown on Page 36, Figure 19. The gas hose accommodates expansion of the heating system and allows for easy installation and service of the burner. Before connecting the burners to the supply system, verify that all high pressure testing of the gas piping has been completed.
There is an expansion of the tube with each firing cycle. This will cause the burner to move with respect to the gas hose. This can cause a gas leak resulting in an unsafe condition if the gas connection is not made in strict accordance with Figure 19.
Meter and service must be large enough to handle all the burners being installed plus any other connected load. The gas hose which feeds the system must be large enough to supply the required gas with a maximum pressure drop of 13 mm wc. When gas piping is not included in the layout drawing, the local gas supplier will usually help in planning the gas piping.
IMPORTANT - the complete installation must be tested for gas soundness and be purged in accordance with local and national codes.
• Check the pipe and tubing ends for leaks before placing heating equipment into service. When checking for gas leaks, use a soap and water solution; never use an open flame.
WARNING
Fire Hazard
Tighten gas line fittings to connect gas supply according to Figure 19.
Flex gas line can crack when twisted.
Gas line moves during normal operation.
Use only 1000 mm long connector of 1/2" or 3/4" nominal ID.
Failure to follow these instructions can result in death, injury or property damage.
WARNING
Explosion Hazard
Leak test all components of gas piping before operation.
Gas can leak if piping is not installed properly.
Do not high pressure test gas piping with heater connected.
Failure to follow these instructions can result in death, injury or property damage.
Page 42
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
36
Figure 19: Gas Connection with Stainless Steel Flex Connector
Shut-Off Valve (included with gas hose) must be parallel to burner gas inlet. The 80 mm
displacement shown is for the cold condition. This displacement may reduce when the system is fired.
CORRECT POSITIONS
Horizontal
45°
End View
Vertical
(as shown left)
Alternate positions okay
Flexible Gas Hose
910 mm length
80 mm) max. displacement
Side View
Heater Movement
30 mm
CAUTION
Product Damage Hazard
Hold gas nipple securely with pipe wrench when attaching gas hose.
Failure to follow these instructions can result in product damage.
INCORRECT POSITIONS (WRONG INSTALLATION)
Heater Movement
Heater Movement
Heater Movement Heater Movement
Page 43
SECTION 11: WIRING
37
SECTION 11: WIRING
Connect to the electrical supply using the power wire coming out of the wire gland via a locally mounted IP55 protected double pole fused switch having a minimum disconnection of 3 mm on each pole. This switch should be fused to 3 amps. There are no control connections in the standard burner. Control is affected by interruption of the main power inlet. See Page 37, Section 11.1 through Page 38, Section 11.3 for the external wiring details for the single-burner and double linear heaters.
If the IP55 protected fan MB 56 2BM is used with a single burner (linear), it must be wired as shown on Page 38, Section 11.2.
The fan must be protected with a 3 A fuse.
If the heater lockout indication is required, a BLACKHEAT
®
AG volt free package (P/N 03360008) must be installed in every burner. Drill a 20.5 mm hole to fit the wire gland. See Page 39, Section 11.4 for wire connections. Remove the taps from the power wire.
All wiring must comply with current wiring regulations and any local regulations which may apply. Always switch off the supply to the burner before removing the burner side panel.
11.1 Typical External Wiring Diagram (Linear)
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be properly grounded.
Failure to follow these instructions can result in death or electrical shock.
Description Part Number
BLACKHEAT
®
AG Lockout Indicator Package
03360008
Cable Gland U169 Power Wire 91300010 Blue Wire 91300011 Brown Wire 91300012
Burner 1
Fan 1
Earth
Burner 2
Fan 2
Burner 3
Fan 3
Controller or
Thermostat
230 V
1 Ø
50 Hz
L
N
Earth
N
L
Blue
Green
Black
Blue
Brown
Green/Yellow
4 Wire Cable
{
Blue
Green
Black
Blue
Brown
Green/Yellow
4 Wire Cable
{
Blue
Green
Black
Blue
Brown
Green/Yellow
4 Wire Cable
{
Page 44
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
38
11.2 Typical External Wiring Diagram (Double Linear Option 1)
11.3 Typical External Wiring Diagram (Double Linear Option 2)
230 V
1 Ø
50 Hz
Burner 1
Burner 2
L
N
Earth
Earth
N
L
Fan
3 A
Fuse
Controller or
Thermostat
Controller or
Thermostat
Burner 1 Burner 2
L
N
Earth
Fan
Earth
N
L
230 V
1 Ø
50 Hz
Page 45
SECTION 11: WIRING
39
11.4 Internal Wiring Diagram
Page 46
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
40
SECTION 12: OPERATION
Figure 20: Sequence of Operation Chart
NOTE: If the heater operates for more than 24 hours continuously, the ignition module will automatically recycle the burner to ensure that all safety functions are still in working condition.
12.1 Heater Lockout Indication (Optional)
In case of flame loss during operation of the heater, the burner control unit goes to lockout mode after three ignition trials. At this stage a signal or closed relay will enable the ROBERTS GORDON
®
controller, BMS system, etc. to indicate precisely which heater has failed. This can be done by two options.
12.1.1 Heater Lockout Indicator by Connector
A 230 V signal is provided which enables the ROBERTS GORDON
®
controller, BMS system, etc. to indicate the
heater that has failed. An additional wire has to be installed from the heater lockout indicator connector to the monitoring computer. See Page 39, Section 11.4.
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Burn Hazard
Allow heater to cool before service.
Tubing may still be hot after operation.
Explosion Hazard
Turn off gas supply to heater before service.
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be connected to a properly grounded electrical source.
P
P
Fan Neon
Burner Neon
Neon
Ignition
Gas Valve
Flame Sensing
Pressure Switch
Fan
Thermostat
KEY TO
SYMBOLS
T0 T1 T2 T3 T4 T5 T6 T7
10 sec
Tp
40 sec max.
Interruption of main
Tp
10 sec
Ts
10 sec
flame sensing
11 sec typical
T8
Lockout Alarm Signal (optional)
Burner Lockout
signal received after
3 ignition trial
failures
Description Part Number
Connector male - Lockout Indicator 91324000 Connector female - Lockout Indicator 91324001 Wire Blue 12" 91300011 Wire Brown 12" 91300012
Page 47
SECTION 12: OPERATION
41
12.1.2 Heater Lockout Indicator by Volt Free Connector
A volt free contact relay is closed which enables the ROBERTS GORDON
®
controller, BMS system, etc. to indicate the heater that has failed. An additional wire has to be installed from the heater volt free connector to the monitoring computer. See Page 39, Section 11.4.
12.2 Testing
Establish that a satisfactory purged gas supply and an electrical supply is available to the heater. Ensure that all time clocks and thermostats are set to call for heat.
With the gas supply cut off and the electrical supply isolated by switching off at the local switch, open the control chamber secured by the screws. Loosen the sealing screw from the pressure test point and remove the cover cap from the governor.
Turn on the gas supply and connect appliance electrical plug. Ensure that the timer or thermostat, if fitted, are set to call for full gas rate. Switch on at the local switch. The sequence as described should take place. If not, refer to detailed fault finding sequence. When flame is established, check the gas pressure reading and adjust if necessary. Refer to burner data label.
Check the gas pressure at the outlet of the gas valve. See Page 54, Section 16.8.1 for pressure settings or refer to the data plate.
Switch off the electrical supply (shutting down the heater), remove pressure gauge, tighten pressure test point screw, ensuring a tight gas seal. Replace governor cover cap. Replace control chamber door.
12.3 Commissioning (Multiburner)
1. Establish that a satisfactory purged gas supply and an electrical supply is available to the heater.
2. ENSURE that all the dampers are in the fully open position.
3. With the gas supply off at each of the burners and the electrical supply isolated, open the control chamber secured by six screws.
4. Ensure that all time clocks and thermostats are set to call for heat.
5. Switch on the electrical supply at the main isolator. This will start the exhaust fan.
6. Balancing Cold Suction Check each burner vacuum by connecting an
inclined pressure gauge to the tee on the pressure switch inlet side in the burner. Adjust the damper so that the suction is 1.9 mbar. Repeat for each burner.
7. Start at the end burner (furthest from the exhaust fan) with the inclined pressure gauge connected as described above. Turn on the gas and electrical sup­ply, reset the pressure switch by removing suction from the inlet side of the pressure switch waiting several seconds and reconnecting. The start up sequence described on Page 40, Section 12 should take place. If not, refer to detailed fault finding sequence. When flame is established, check the gas pressure reading and adjust if necessary. See data label. Check the gas pressure at the outlet of the gas valve. See Page 54, Section 16.8.1 for pressure set- tings or refer to the data plate. Switch off the electrical supply (shutting down the heater), remove pressure gauge, refit pressure test­point screw, ensuring a tight gas seal. Replace gov- ernor cover cap. Repeat this procedure for each burner in the sys­tem. Close the control chamber and secure with six screws.
8. Balancing Hot Suction Reconnect all the burners on the system and allow them to reach full operating temperature (approxi­mately 20 minutes). Return to each burner and recheck the hot suctions at the tee on the inlet to the pressure switch. Re-adjust the damper so that the hot suction of 1.7 mbar is achieved and lock the damper in position.
12.4 System Checks
Switch on again at the local switch to help ensure smooth ignition. Carry out the following system checks:
When running, turn off the gas supply at the appliance. The heater will immediately shut down followed by one attempt at restoration followed by lockout.
Linear and Double Linear only:
When running, disconnect the fan plug from the burner. The unit should shut down within three seconds, proving operation of the pressure switch.
12.5 User Instructions
After satisfactory testing, ensure that the client is fully aware of the operation of the system. Bring this manual to the attention of the user or purchaser; instruct them in the safe operation of the heater(s).
Description Part Number
Connector male - Volt Free 91324000 Connector female - Volt Free 91324001 Wire Blue 7" 91300004 Wire Brown 7" 91300005 Wire Yellow 12" 91300003 Screw #8 x 3/8 Hex Wshr PHH Type 23 94961406 Base relay P2RF05E C1050B Relay G2R1-SN IMO 220 V 10 A C1049B
Page 48
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
42
SECTION 13: SERVICING INSTRUCTIONS
IMPORTANT: Never use the heater as a support for ladders or other access equipment. Always test for gas soundness with a suitable detection fluid after completing any servicing or exchange of gas carrying component. On completion of any service/fault finding tasks which require the breaking and remaking of electrical connections, the checks:- A: Earth Continuity, B: Polarity and C: Resistance to Earth must then be repeated.
13.1 Annual Procedure
Carry out the following procedure annually. The preferred time would be immediately before the winter heating period. If very dirty conditions arise, it may be necessary to carry out this procedure more often. If the unit takes in air through an air duct or filter assembly, more frequent service may be necessary.
13.1.1 Burner and Fan Removal
Isolate the heater from the gas and electrical supplies. Remove the fan plug from the burner. Unscrew the securing screws on the burner flange. The burner can now be removed. Take care not to disturb the gasket on the flanged burner tube. Unscrew the securing screw on the fan flange spigot. The fan can now be removed.
13.1.2 Burner and Fan Removal Maintenance
Remove the fan and burner independently to floor level and clean both items internally using a soft brush and compressed air, if available. Take care not to damage the internal parts of the burner. Check fan impeller for cleanliness and free rotation.
The electrodes are an integral part of the burner. To check spark gap, remove the securing screws on the electrode and withdraw it ensuring the gasket is not damaged. Spark gap on electrode should be approximately 3 mm.
13.1.3 Tube and Reflector Maintenance
With burner and fan removed, clean the outer surfaces of the tubes using a brush and wipe the inner surface of the reflector with a soft damp cloth - use a household
detergent if necessary. Never use abrasive cleaners on the reflectors. Reassemble the burner and fan in reverse order. Carry out the Testing Procedure. See Page 41, Section 12.2.
13.2 Sealing Gaskets
During annual service, all gaskets, as indicated on Page 49, Section 15, must be inspected for cuts, misalignment
or dryness. All round rubber gaskets, sealing the screw holes, must be replaced in three year intervals or earlier as needed. All other gaskets must be replaced every five years or earlier as needed.
Old gaskets must be removed completely before installing the new gasket. When replacing gaskets on screws, ensure that the screws are not over tightened. Deformation of the gasket is an indication of suffcient torque. The control and combustion chamber doors have internal seals, replacements must be attached to the same location.
13.3 Component Removal
First, isolate the heater from the gas and electricity supply.
Entry to the burner assembly is gained by removing the six door screws and removing the control chamber door. Entry to the combustion chamber is gained by removing the combustion chamber door.
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Burn Hazard
Allow heater to cool before service.
Tubing may still be hot after operation.
Explosion Hazard
Turn off gas supply to heater before service.
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be connected to a properly grounded electrical source.
Page 49
SECTION 13: SERVICING INSTRUCTIONS
43
13.3.1 Electrode Figure 21: Burner Cup Position
13.3.2 Burner Head/Injector Jet
When the cover is removed completely, the burner assembly is exposed. Unscrew the burner cup. Remove brass injector jet (orifice). Replace in reverse sequence.
13.3.3 Solenoid Valve/Governor
Remove burner head. Unscrew two screws securing the solenoid/governor body. Withdraw the electrical connector and remove the flexible gas line connector. The solenoid/governor and fittings can now be withdrawn from the compartment. To ensure IP55 protection, replace the gasket on the gas valve inlet flange (P/N 03200100).
The solenoid(s) can be removed from the body by unscrewing central screw. Replace in reverse sequence.
13.3.4 Automatic Flame Control Unit
Remove black ignition lead. Withdraw the 10 point edge connector. Unscrew two screws from the cover. Replace if faulty. Refit in reverse sequence.
13.3.5 Pressure Switch
Disconnect the two silicone tubes. Remove electrical plug. Remove one screw which secures the pressure switch to the burner. Remove pressure switch.
Replace pressure switch, if faulty, and refit in reverse sequence ensuring that the rubber tubes are reconnected to the switch correctly.
13.3.6 Neons
Remove the two push on connectors and unscrew the nut. Replace in reverse sequence.
13.4 Maintenance Checklist Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON
®
equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON
®
manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment.
To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor conduct, at a minimum, annual inspections of your ROBERTS GORDON
®
equipment and perform service where necessary, using only replacement parts sold and supplied by Roberts-Gordon LLC.
Burner Cup (center horizontally)
Electrode Assembly
16 mm
Air Plate
Jet
The Vicinity of the Heater
Do not store or use flammable objects, liquids or vapours near the heater. Immediately remove these items if they are present.
See Page 5, Section 3.
Vehicles and Other Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged underneath the reflector, in between the tubes or in the decorative or protective grilles (included with select models).
Immediately remove objects in violation of the clearances to combustibles.
See Page 5, Section 3.
Reflector
Support reflector with reflector hanger and support strap.
Reflector must not touch tube.
Make sure there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make sure reflectors are correctly overlapped.
Clean outside surface with a damp cloth.
Page 50
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
44
Vent Pipe
Venting must be intact. Using a flashlight, look for obstructions, cracks on the pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
See Page 32, Section 9.
Outside Air Inlet
Inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust. Clean and reinstall as required.
Tube s
Make sure there are no cracks.
Make sure tubes are connected and suspended securely.
See Page 9, Section 5
Make sure there is no sagging, bending or distortion.
Gas Line
Check for gas leaks. See Page 35, Section 10.
Burner Observation Window
Make sure it is clean and free of cracks or holes.
Clean and replace as required.
Blower Scroll, Wheel and Motor
Compressed air or a vacuum cleaner may be used to clean dust and dirt.
Burner Cup and Orifice
Clear of obstructions (even spider webs will cause problems). Carefully remove any dust and debris from the burner.
Electrode
Replace if there are cracked ceramics, excessive carbon residue, or erosion of the electrode.
The electrode gap should be 3 mm.
Thermostat
There should be no exposed wire or damage to the thermostat.
See Page 37, Section 11.
Suspension Points
Make sure the heater is hanging securely.
Look for signs of wear on the chain or ceiling.
See Page 9, Section 5.
Sports Hall Guard, Decorative and Protective Grilles (optional)
The grille must be securely attached. If the grille is loose or off, contact a contractor qualified in the installation and service of gas-fired heating equipment for repair.
Check that side reflector extensions are installed correctly and secured in place if necessary. (Decorative grille only.)
See Page 27, Section 8.2.3 and Page 28, Section 8.3
Make sure shield is installed correctly and secured in place if necessary. (Decorative grille only.) See Page 27, Section 8.2.2.
Wall Tag
If a wall tag is present, make sure it is legible and accurate. Please contact Roberts-Gordon LLC or your ROBERTS GORDON® independent distributor if you need a wall tag. See Page 4, Section 2.1.
Page 51
SECTION 14: TROUBLESHOOTING
45
SECTION 14: TROUBLESHOOTING
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be properly grounded.
Failure to follow these instructions can result in death or electrical shock.
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clearances to combustibles away from heater.
Some objects will catch fire or explode when placed close to heater.
Cut/Pinch Hazard
Wear protective gear during installation, operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, injury or property damage.
Burn Hazard
Allow heater to cool before service.
Tubing may still be hot after operation.
Explosion Hazard
Turn off gas supply to heater before service.
Page 52
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
46
14.1 Troubleshooting Flow Chart (Linear and Double Linear)
No
No
No
Ye s
No Ye sYe sNo
No
No
No
No
Ye s
NoNoYe s
Ye s
Ye s
Ye s
NoYe s
Ye s
Ye s
Ye s
No
Replace ignition
module.
Is there power out
from pin 10 on
ignition module?
Replace Fan.
Turn up thermostat.
Does the fan turn on?
Place a jumper across
the thermostat terminals.
Does the fan turn on?
Check thermostat wiring
and replace thermostat if
necessary.
Is there power (230V)
at the burner?
Check relay wiring
(if applicable) and wiring
to the burner.
Remove electrical plug
from the pressure switch; place
jumper between black & white
leads. Does the fan turn on?
Replace pressure switch.
Remove obstruction.
Unplug burner.
Does the fan
turn freely?
Is the fan obstructed?
Fan bearings may have
failed. Replace fan.
Remove obstruction.
Repair, replace or
tighten hoses
as necessary.
Is the flue pipe or
the inlet of the
burner obstructed?
Are the hoses to the pressure
switch secure and leak free?
Replace pressure switch.
Is the igniter gap
set at 3 mm?
Carefully reset gap
to 3 mm.
Replace automatic
control unit.
Unplug burner and check
electrode and ignition wire.
Are they damaged?
Replace electrode and
ignition wire as needed.
Is there spark at the
igniter?
Remove electrical plug
from the pressure switch;
place jumper between
black & white leads.
Does the fan turn on?
Page 53
SECTION 14: TROUBLESHOOTING
47
Troubleshooting Flow Chart (Linear and Double Linear)
Page 54
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
48
14.2 Manifold Gas Pressure Setting
0
1
2
3
4
5
6
1
2
3
4
5
6
0
1
2
3
4
5
6
1
2
3
4
5
6
Manometer
4
RELAY
3
(14)
(12)
2
(A1)
1(-)
(A2)
5(+)
Combustion Chamber
Control Chamber
Governor (orifice) pressure while burner is running. See
Page 54, Section 16.8.1.
Gas supply pressure
while burner is running. See Page 52, Section 16.2.3.
Page 55
SECTION 15: REPLACEMENT PARTS
49
SECTION 15: REPLACEMENT PARTS
Carbon Monoxide Hazard
WARNING
Use only genuine ROBERTS GORDON
®
replacement parts per this installation, operation and
service manual.
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Explosion Hazard
DANGER
Electrical Shock Hazard
Fire Hazard
Page 56
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
50
.
*See Page 51, Section 15.1.
A
B
C
D
E
F
G
H
J
I
K
L, T
(2)
M
N
P
R
SV
V
(2)
W
(2)
Q
(6)
V
(2)
W
(3)
Q
(7)
R
(4)
R
(2)
R
(3)
Item Description Part Number Item Description Part Number
A Automatic Control Unit 90438702 P Gasket 1/2" OD x 1/4" ID 92700008 B Flex Line Adapter 91220700 Q Gasket 1/2" OD x 3/16" ID 92700001
C
Pressure Switch for HE50
HE35
HE15, 20, 30, 45
HE25
HE40
90439801 90439802 90439803 90439804 90439805
R Gasket 3/8" OD x 3/16" ID 92700002
D Amber Neon Lamp 91320604 S Valve Gasket 03200100
E* Gas Valve 90033101 T Window Gasket 92700003
FGovernor Screw N/A U Fresh Air Adaptor Gasket 92700005 G Outlet Pressure Tap N/A V Gasket 1/2" x 17 3/8" 92700006 H Cable Gland U169 W Gasket 1/2" x 8.5" 92700007
I Star Washer 96212100 N/S Ignition Wire 90427704
J
Jet Orifice (See Page 54, Section 16.8)
N/A N/S Burner Tube Gasket 92700004
K Burner Cup Assembly 03020100 N/S Wire Harness- Main Power 03320404
L Mica Window Assembly 03360004 N/S Wire Harness- Pressure Switch 03320405
M Electrode Assembly 90427403 N/S Purple Wire 07250007
N Fresh Air Adapter 90501002 N/S Electrode Gasket 02558501
Page 57
SECTION 15: REPLACEMENT PARTS
51
15.1 Replacement Packages
15.1.1 Screw and Gasket Replacement Package (P/N 03360005)
15.1.2 Viewer Window Replacement Package (P/N 03360004)
15.1.3 Door Gasket Replacement Package (P/N 03360002)
15.1.4 Gas Valve Replacement Package (P/N 03360003)
Description Quantity Part Number
Screw M4 x 8mm 2 93304506 Screw 10-24 x 5/8 4 94118110 Screw #8 x 3/8 4 94118107 Screw M8 x 20 mm 2 93304507 Burner Tube Gasket 1 92700004 Fresh Air Intake Gasket 1 92700005 Rubber Gasket 10 92700002 Gas Valve Gasket 1 03200100
Description Quantity Part Number
Viewer Ring 1 01390203 Mica Window Square 1 02553200 Window Gasket 2 92700003 Screw M6 x 16 mm 2 93304505 Rubber Gasket 2 92700008
Description Quantity Part Number
Screw 10-24 x 5/8 2 94118110 Silicone Gasket 4 92700006 Silicone Gasket 6 92700007 Rubber Gasket 13 92700001
Description Quantity Part Number
Gas Valve SIT 840 1 90033101 Screw M4 x 8 mm 2 93304506 Gas Valve Gasket 1 03200100
Page 58
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
52
SECTION 16: SPECIFICATIONS
16.1 Material Specifications
16.1.1 Combustion and Tubes
100 mm dia. 16 gauge heat treated aluminised mild steel.
16.1.2 Reflectors
NS3 H14 aluminium or 1.4016 2R stainless steel (option).
16.2 Heater Specifications
16.2.1 Sequence Controller
Fully automatic, single try, direct spark, 100% shut off ignition flame rectification module.
16.2.2 Electrical
Rating: 230V, 50 Hz, single phase, 1 amp
Connection: minimum IP55 junction box
16.2.3 Gas Supply
Connection: Rc1/2 (1/2" BSP int)
Natural G20: Minimum - Inlet 15 mbar (6 in wg)
Maximum - Inlet 50 mbar (20 in wg)
Natural G25: Minimum - Inlet 17.5 mbar (7 in wg)
Maximum - Inlet 50 mbar (20 in wg)
LP Gas (Propane or Butane):
Minimum - Inlet 32.5 mbar (13 in wg)
Maximum - Inlet 50 mbar (20 in wg)
16.3 Venting Specifications
16.3.1 IP54 Protected Fans
AG15, 20, 25, 30, 35........ Model: Torin DSA 508-128
(P/N 90710051)
AG40, 45, 50 .................. Model: Torin DSF 146-052
(P/N 90710053)
AG30DL - 70DL .............. Model: Torin DSF 146-052
(P/N 90710053)
Consult the manufacturer for availability of alternate fans.
16.3.2 Flue
The flue must be 100 mm, or greater in diameter, and must conform to National Codes. The flue must be self supporting. Inlet must be 100 mm diameter.
Multiburner - Flue will be 150 mm diameter. Flue material must conform to National Codes. The flue must be self supporting.
16.4 Suspension Specifications
Hang heater with materials with a minimum working load of 33 kg (75 lbs).
16.5 Controls Specifications
Time switches, thermostats, etc. can be wired into the electrical supply. External controls supplied as an optional extra.
Page 59
SECTION 16: SPECIFICATIONS
53
*Please contact Roberts-Gordon or your ROBERTS GORDON
®
independent distributor to obtain minimum and recommended installation heights. For poultry and other agricultural applications, it is important to install your heater in accordance with the appropriate clearances to combustibles. Also, it is recommended that the design and layout of all your agricultural buildings and barns are performed by a qualified professional in the design, installation and service of equipment sold and supplied by Roberts-Gordon.
16.6 Linear Heater*
AG15ST
AG20ST
AG25ST
AG30ST
AG35ST
AG40ST
AG45ST
AG50ST
Input - Gross (kW) 15 20 25 30 35 40 45 50/51
Input - Net (kW) 13.5 18 22.5 27 31.5 36 40.5 45/46
Tube Length (mm) 6096 9144 9144 12192 12192 12192 15240 15240
Overall Heater Length (mm) 6887 9935 9935 12983 12983 13028 16076 16076
Weight (kg) 41 55 55 68 68 68 81 81
16.7 Double Linear Heater*
AG30DL
AG40DL
AG50DL
AG60DL
AG70DL
Input - Gross (kW) 30 40 50 60 70
Input - Net (kW) 27.536455463
Tube Length (mm) 12802 18898 18898 24994 24994
Overall Heater Length (mm) 13914 20010 20010 26106 26106
Weight (kg) 82 110 110 136 136
Page 60
BLACKHEAT® AG INSTALLATION OPERATION AND SERVICE MANUAL
54
16.8 Burner Specifications Figure 22: Linear Specifications
**Based on Gross Caloric Value.
16.8 .1 Burner Specifications
AG15 AG20 AG25 AG30 AG35 AG40 AG45 AG50
Burner Airplate ID Number 515 505 513 502 500 501 500 506
Jet Numbers - Natural G20 & 25 #31 #28 5/32 #17 #12 #8 #3 #1
Jet Numbers - Propane/Butane #47 #43 #39 #33 #31 3.2 mm #29 #28
Gas Consumption**Natural G20 (m
3
/h) 1.43 1.91 2.38 2.86 3.34 3.81 4.29 4.76
Natural G25 (m
3
/h) 1.66 2.22 2.77 3.32 3.88 4.43 4.99 5.54
Propane (m
3
/h)
[kgh]
0.56 [1.08]
0.75 [1.44]
0.94 [1.80]
1.13 [2.16]
1.32 [2.52]
1.51 [2.88]
1.69 [3.25]
1.88 [3.61]
Butane (m
3
/h) 0.43 0.57 0.72 0.86 1.00 1.14 1.29 1.43
Governor Pressure Butane (mbar) 20.4 20.4 19.7 19.7 19.7 19.7 20 20.9
Butane (in wg) 8.1 8.2 7.9 7.9 7.9 7.9 8.0 8.4
Propane (mbar) 28.4 27.1 26.9 26.6 26.9 26.9 27.4 26.9
Propane (in wg) 11.4 10.9 10.8 10.7 10.8 10.8 11.0 10.8
Governor Pressure Natural G20 (mbar) 10.0 9.5 9.5 9.5 9.2 9.5 8.7 8.7
Natural G20 (in wg) 4.0 3.8 3.8 3.8 3.7 3.8 3.5 3.5
Natural G25 (mbar) 15.4 14.9 15.2 14.9 14.2 14.9 13.7 13.2
Natural G25 (in wg) 6.2 6.0 6.1 6.0 5.7 6.0 5.5 5.3
Swirler*
Side View
Reflector
End View
Tube Length
Fan
Burner Tube
100 mm
Damper
348 mm
499 mm
241 mm
Page 61
Page 62
Infrared Heating
Maintain clearance
to the side and
clearance below
the heater from vehicles
and combustible materials.
www.rg-inc.com Printed in U.S.A. P/N 91037912 Rev. H
Attach this information to a wall near the ROBERTS GORDON
®
heater.
Read the Installation, Operation, and Service Manual thoroughly before installation, operation, or service.
Know your model number and installed configuration. Model number and installed configuration are found on the burner and in the Installation, Operation and Service Manual. Write the largest clearance dimensions with permanent ink according to your model number and configuration in the open spaces below.
OPERATING INSTRUCTIONS
1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting.
1. Set the thermostat to off or the lowest setting.
1. Set the thermostat to off or the lowest setting.
2. Turn off electric power to the heater.
3. Turn off the manual gas valve in the heater supply line.
4. Call your registered installer/contractor qualified in the installation and service of gas-fired heating equipment.
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clearances to combustibles away from heater.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
TO TURN OFF THE HEATER
Service Telephone: +44 (0)121 506 7709 Service Fax: +44 (0)121 506 7702 E-mail: uksales@rg-inc.com E-mail: export@rg-inc.com
Roberts-Gordon LLC
1250 William Street P.O. Box 44 Buffalo, NY 14240-0044 USA Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
WARNING
Roberts-Gordon Europe Limited
Unit A, Kings Hill Business Park Darlaston Road, Wednesbury West Midlands WS10 7SH UK Telephone: +44 (0)121 506 7700 Fax: +44 (0)121 506 7701
®
Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON
®
manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help
facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor conduct, at a minimum, annual inspections of your ROBERTS GORDON
®
equipment and
perform service where necessary, using only replacement parts sold and supplied by Roberts-Gordon.
Further Information: Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives.
Please contact us for any further information you may require, including the Installation, Operation and Service Manual.
This product is not for residential use.
© 2009 Roberts-Gordon LLC All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means – graphic, electronic, or mechanical, including photocopying, recording, taping, or information storage and retrieval s
ystems – without written permission of Roberts-Gordon LLC.
Loading...